GENERAL NOTES:
1. ALARM MODE FOR DAY / NIGHT OPERATION SHALL REFER TO THAT PERIOD OF TIME
BETWEEN HOURS OF 6:00 PM AND 7:00 AM EVERY DAY, WHERE THE SECURITY
MANAGEMENT SYSTEM SHALL BE ACTIVATED. DOORS WITH 24 HOUR OPERATION SHALL BE
IN ALARM 24 HOURS PER DAY.
2. COORDINATE ALL SECURITY DEVICES WITH THE FINAL DOOR HARDWARE SCHEDULE
AND SPECIFICATION SECTION 088710.
DOOR WIRING LEGEND
(1)#18AWG, 2-CONDUCTOR, UNSHIELDED TWISTED PAIR CABLE WITHIN 3/4" CONCEALED CONDUIT
(1)#18AWG, 4-CONDUCTOR, UNSHIELDED TWISTED PAIR CABLE WITHIN 3/4" CONCEALED CONDUIT
(1)#18AWG, 6-CONDUCTOR, UNSHIELDED TWISTED PAIR CABLE WITHIN 3/4" CONCEALED CONDUIT
(1)#18AWG, 8-CONDUCTOR, SHIELDED TWISTED PAIR CABLE WITHIN 3/4" CONCEALED CONDUIT
(1)#22AWG, 2-CONDUCTOR, UNSHIELDED TWISTED PAIR CABLE WITHIN 3/4" CONCEALED CONDUIT
(1)#18AWG, 4-CONDUCTOR, SHIELDED TWISTED PAIR CABLE WITHIN 3/4" CONCEALED CONDUIT
FINISHED
FLOOR
OPERATIONAL DESCRIPTION:
TYPICAL SINGLE INTERIOR DOOR WITH ACCESS / ENTRY
CONTROL VIA CARD READER, 24 HOUR SECURED - HW-SH-3.
DOORS IN ALARM MODE. DOOR POSITION STATUS FOR EACH
DOOR IS MONITORED BY ELECTRONIC DOOR POSITION SWITCH
CONTACTS (DC). DOOR IS NORMALLY CLOSED AND LOCKED.
ELECTROMECHANICAL LOCK SHALL REMAIN IN SECURE MODE
DURING LOSS OF BUILDING POWER (FAIL SECURE). SIGNAL
FROM CARD CREDENTIAL MOMENTARILY SHUNTS SIGNAL FROM
DC & UNLOCKS ELECTROMECHANICAL LOCK. ACCESS IS THEN
ACHIEVED BY MANUAL OPERATION OF LEVER. FREE EGRESS IS
PERMITTED AT ALL TIMES BY MANUAL OPERATION OF LEVER
LOCK.
DOOR
DOOR FRAME
PROXIMITY
CARD READER
3/4" C 3/4" C
EL
CR
ACCESS/ENTRY SIDE
INTERIOR SIDE
JB
ACCESSIBLE CEILING - SEE RCP
JUNCTION BOX ABOVE ACCESSIBLE
CEILING ON INTERIOR SIDE
1-1/4" C
TO NEAREST
LVSR
CONCEALED
DOOR CONTACTS
(TYPICAL)
SIM. FOR EXTERIOR DOORS
DC
POWER TRANSFER DEVICE
TO FIRE ALARM
CONTROL MODULE
REQUEST TO
EXIT (REX)
24 VAC AUDIBLE ALARM AT
TR AND LVSR
ELECTROMAGNETIC MORTISE LOCK
OPERATIONAL DESCRIPTION:
SINGLE EXTERIOR, MONITORED
DOOR. DOOR IS NORMALLY
CLOSED AND MECHANICALLY
LOCKED. IN ALARM MODE, THE
DOOR POSITION STATUS (OPEN
OR CLOSED) IS MONITORED BY
DOOR CONTACTS. FREE EGRESS
IS PROVIDED AT ALL TIMES.
FINISHED
FLOOR
JB
ACCESSIBLE CEILING - SEE RCP
1-1/4" C
DC
EXTERIOR SIDE
INTERIOR SIDE
CONCEALED
DOOR CONTACT
(TYPICAL)
SIM. FOR EXTERIOR DOORS
DC
DOOR
DOOR FRAME
3/4" C
3/4" C
24 VAC LOCAL
AUDIBLE ALARM
DOUBLE DOORS AS IT OCCURS
- SEE PLAN
DOUBLE DOORS AS IT OCCURS
- SEE PLAN
JUNCTION BOX ABOVE ACCESSIBLE
CEILING ON INTERIOR SIDE
TO NEAREST
LVSR
CR
INTERIOR SIDE
EXTERIOR SIDE
FRAME
DOOR
FIN. FLR.
PROXIMITY
CARD READER
ACCESSIBLE CEILING - SEE RCP
JB
1-1/4" C TO FIRE ALARM CONTROL
MODULE
CONCEALED DOOR CONTACTS (TYPICAL)
OPERATIONAL DESCRIPTION:
DOUBLE DOOR, 24 HOUR SECURED - HW-SH-
1B. DOORS ARE NORMALLY CLOSED & LOCKED
IN ALARM MODE. DOOR POSITION STSTUS FOR
EACH DOOR IS MONITORED BY ELECTRONIC
DOOR POSITION CONTACTS (DC). IN THE EVENT
OF BUILDNG POWER LOSS, DOORS SHALL
REMAIN LOCKED (FAIL SECURE). ACCESS IS
ACHEIVED VIA AUTHORIZED CARD CREDENTIAL.
CARD MOMENTRAILY SHUNTS SIGNAL FROM
DC & MOMENTARILY UNLOCKS ELECTRIFIED
EXIT DEVICE SO A PERSON CAN MANUALLY
PULL THE DOOR OPEN USING THE EXIT DEVICE
PULL. CAMERA RECORDS FOR (DURATION TO
BE DETERMINED BY VA) SECONDS DURING
ACCESS AND EGRESS AUTHORIZED EVENTS.
CAMERA RECORD CONTINUOULSLY UPON
ALARM EVENT AT THIS DOOR LOCATION UNTIL
ALARM CONDITION HAS BEEN RESET. FREE
EGRESS IS PROVIDED AT ALL TIMES BY
MANUAL OPERATION OF EXIT DEVICE.
POWER
TRANSFER
DEVICE
POWER
TRANSFER
DEVICE
EXIT DEVICE WITH
INTEGRAL REX
120V BY DIV 26PS
DC DC
IC
ICRS
INTERCOM
SUBSTATION
REMOTE
RELEASE AT
INFORMATION
DESK
EL
TO NEAREST
LVSR
JUNCTION BOX ABOVE
ACCESSIBLE CEILING
ON INTERIOR SIDE
EL
LOCAL POWER SUPPLY
REQUEST TO
EXIT (REX)
CR
EX
INTERIOR SIDE
EXTERIOR SIDE
FRAME
DOOR
FIN. FLR.
PROXIMITY
CARD READER
JB
1-1/4" C TO FIRE ALARM CONTROL
MODULE
JUNCTION BOX ABOVE
ACCESSIBLE CEILING
ON INTERIOR SIDE
CONCEALED DOOR
CONTACTS (TYPICAL)
OPERATIONAL DESCRIPTION:
DOUBLE DOOR BQC01, AUTO OPERATION, 24 HOURS
SECURED, REMOTE RELEASE. DOORS ARE NORMALLY
CLOSED & LOCKED IN ALARM MODE. DOOR POSITION
STATUS FOR EACH DOOR IS MONITORED BY ELECTRONIC
DOOR POSITION SWITCH CONTACTS (DC). IN THE EVENT
OF BUILDING POWER LOSS, THE DOORS SHALL REMAIN
LOCKED (FAIL SECURE). ACCESS IS ACHIEVED VIA
AUTHORIZED CARD CREDENTIAL OR REMOTE RELEASE.
CARD OR REMOTE RELEASE MOMENTARILY SHUNTS
SIGNAL FROM DC, MOMENTARILY UNLOCKS THE
ELECTRIFIED EXIT DEVICE & SENDS SIGNAL TO LOW
ENERGY POWER ASSIST OPERATOR WHICH OPENS DOOR.
ALTERNATIVELY, A PERSON CAN MANUALLY PULL THE
DOOR OPEN USING THE EXIT DEVICE PULL. CAMERA
RECORDS FOR (DURATION TO BE DETERMINED BY VA)
SECONDS DURING ACCESS AND EGRESS OF AUTHORIZED
EVENTS. CAMERAS RECORD CONTINUOUSLY UPON AN
ALARM EVENT AT THIS DOOR LOCATION UNTIL ALARM
CONDITION HAS BEEN RESET. FREE EGRESS IS PROVIDED
AT ALL TIMES BY MANUAL OPERATION OF EXIT DEVICE OR
BY PRESSING WALL MOUNTED INTERIOR DOOR ACTIVATION
SWITCH (BY AUTO DOOR SUPPLIER).
POWER
TRANSFER
DEVICE
POWER
TRANSFER
DEVICE
EX
120V BY DIV 26PS
RS
REMOTE RELEASE
SWITCH AT
INFORMATION DESK
DC DC
IC
AUTO-DOOR OPERATOR (BY
AUTO-DOOR SUPPLIER)
AS
AUTO-ACTIVATION
SWITCH
AS
AUTO-ACTIVATION
SWITCH ON
INSIDE OF
BUILDING (BY
AUTO-DOOR
OPERATOR)
IC
TO NEAREST
LVSR
LOCAL POWER SUPPLY
REQUEST TO
EXIT (REX)
ROLL-UP DOOR OPERATOR
AND ASSOCIATED
EQUIPMENT (BY OTHERS)
FINISHED FLOOR OR
LOADING DOCK FLOOR
ROLL-UP DOOR
DOOR FRAME
MAGNETIC DOOR
CONTACT SWITCH AT
INTERIOR SIDE
SURFACE
MOUNT
4-CONDUCTOR
UNSHIELDED FOR DOOR
CONTACT SWITCH
4-CONDUCTOR, #22AWG
WITHIN 3/4" CONCEALED
CONDUIT
4-CONDUCTOR, #18AWG
WITHIN 3/4" CONDUIT TO
NEAREST LV SECURITY
ROOM
SURFACE MOUNTED
JUNCTION BOX LOCATED
AT SECURED SIDE.
JB
DATE
LOCATION
CHECKED DRAWN
PROJECT TITLE PROJECT NUMBER
DOCUMENT SET PACKAGE
DRAWING NUMBERAPPROVED: PROJECT DIRECTOR
DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:
REVISIONS: DATE
B
A
D
C
E
VA FORM 08-6231
O N
E
EI
G H
T
IN
C H
O
N E
FO
O
T O
N E
Q U
AR
TE
R
IN
C H
O
N E
FO
O
T O
N E
H A L
F
IN
C H
O
N E
FO
O
T
TH
R
EE
Q U
AR
TE
R S
IN
C
H
O N
E
FO
O T
TH
R
EE
IN
C H
ES
O N
E
FO
O T
O N
E
IN
C H
F
O R
TY
F
E E T
(1
0'
6"
6"
0'
0'
123456
F
B
A
D
C
E
F
O N
E
SI
X T
EE
N
TH
IN
C
H
O N
E
FO
O T
O N
E
AN
D O
N E
H
AL
F
IN
C H
ES
O N
E
FO
O T
6"
BUILDING NUMBER
NEW ORLEANS, LOUISIANA
5TY002
BUILDING 05 SECURITY DOOR DETAILS
JLE JJPJune 30, 2011
CONSTRUCTION DOCUMENTS 1
629-HS2-401SLVHCS REPLACEMENT MEDICAL
CENTER PROJECT
SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL
KORDA/NEMETH ENGINEERING / STRUCTURAL
BR+A CONSULTING ENGINEERS / MECH, ELECT, LOW VOLTAGE
ARCHITECTURAL ENGINEERING / PLUMBING
SCALES ASSOCIATES / FIRE PROTECTION
DESMAN ASSOCIATES / PARKING
CODE CONSULTANTS, INC. / CODE CONSULTANT
THE SEXTANT GROUP / AV & ACOUSTICAL
HAMMER DESIGN ASSOCIATES / FOOD SERVICE
PYBURN & ODOM / ABATEMENT
TATA & HOWARD / TANK CONSULTANT Department of
Veterans Affairs
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
EWP_04
1/2" = 1'-0"
SINGLE DOOR ELEVATION-TYP DOOR
WITH CR & DC
1/2" = 1'-0"
SINGLE DOOR ELEVATION-TYP DOOR
WITH DC
1/2" = 1'-0"
DOUBLE DOOR ELEVATION
1/2" = 1'-0"
DOUBLE DOOR ELEVATION.
1/2" = 1'-0"
OVERHEAD DOOR ELEVATION