Requirements for Identification and Replacement of A307 Bolts Memo_Signed.pdf

PDF 379 KB Posted

Attached to
Z2DA--657A5-23-110, Renovate 3B for Patient Privacy and Intensive Care Unit, (VA-25-00018450)
Solicitation number
36C25525R0015
Issued by

About this file

This Department of Veterans Affairs memorandum, dated December 13, 2024, provides urgent requirements regarding the identification and replacement of ASTM A307 bolts on steam and hot water piping systems at all VA medical centers. The memo identifies that A307 bolts, previously specified in VHA Master Specifications, lack the necessary material strength for elevated temperatures in steam and hot water piping systems and must be replaced with ASTM A193 bolts.

The memo outlines specific deadlines and requirements: VISN Capital Asset Managers must report impacted construction projects to the Office of Healthcare Engineering by January 3, 2025. All VAMCs must complete a survey of existing steam and hot water piping systems by June 18, 2025, with priority given to high and medium pressure systems operating over 50 PSI. Network Directors must immediately review and correct specifications for projects in design and modify any construction contracts that specify A307 bolts. Interim Safety Measures must be implemented where A307 bolts are identified until replacement can be completed.

View the file

Other files

File Type Posted
36C25525R0015 0006.docx DOCX document
S02 36C25525R0015 657A5-23-110 R3.docx DOCX document
Renovate 3B Hazardous Material Report.pdf PDF
36C25525R0015 0005.docx DOCX document
Sheet AI100 Color Schedule Key.pdf PDF
36C25525R0015 0004.docx DOCX document
36C25525R0015 0003.docx DOCX document
S04 Pre-Bid Site Visit Attendance.pdf PDF
36C25525R0015 0002.docx DOCX document
Marion VA_Renovate 3B_Bid Documents_Drawings_V1 of 4_09-20-2024 28 pages - Copy.pdf PDF
Marion VA_Renovate 3B_Bid Documents_Drawings_V4 of 4_09-20-2024 41 pages - Copy.pdf PDF
Marion VA_Renovate 3B_Bid Documents_Drawings_V2 of 4_09-20-2024 26 pages - Copy.pdf PDF
36C25525R0015 0001.docx DOCX document
S02 36C25525R0015 657A5-23-110.docx DOCX document
Marion VA_Renovate 3B_Bid Documents_Drawings_V3 of 4_09-20-2024 30 pages - Copy.pdf PDF
Marion VA_Renovate 3B_Bid Documents_Specifications_09-20-2024 1723 pages rev1 - Copy.pdf PDF
Marion VA_Renovate 3B_Bid Documents_Drawings_V3 of 4_09-20-2024 30 pages.pdf PDF
36C25525R0015.docx DOCX document
Marion VA_Renovate 3B_Bid Documents_Drawings_V1 of 4_09-20-2024 28 pages.pdf PDF
Marion VA_Renovate 3B_Bid Documents_Specifications_09-20-2024 1723 pages rev1.pdf PDF
Marion VA_Renovate 3B_Bid Documents_Drawings_V4 of 4_09-20-2024 41 pages.pdf PDF
Marion VA_Renovate 3B_Bid Documents_Drawings_V2 of 4_09-20-2024 26 pages.pdf PDF
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Department of Veterans Affairs

Memorandum

Date:

From: Acting Assistant Under Secretary for Health for Support (19)

Subj: URGENT: For Action: Requirements for Identification and Replacement of A307

Bolts on Steam and Hot Water Piping Systems (VIEWS 12473639)

To: Veterans Integrated Service Network (VISN) Directors (10N1-23)

1. PURPOSE: This memorandum provides notification and information on requirements for the identification and replacement of American Society for Testing and Materials (ASTM) A307 bolts (all grades) on steam and hot water piping systems for all Department of Veterans Affairs (VA) medical centers (VAMC).

2. BACKGROUND: Veterans Health Administration (VHA) Master Specifications for Hydronic Piping (Specification 23 21 13, Section 2.3) and Steam and Condensate Heating Piping (Specification 23 22 13, Section 2.3) indicate ASTM A307 bolts for use on steam and hot water pipe flanges. However, the ASTM A307 bolt (all grades) is considered a general-purpose bolt and does not possess the necessary material strength at elevated temperatures for use on steam and hot water piping systems.

These specifications are being updated to indicate ASTM A193 bolts as the appropriate fastener for steam and hot water piping systems. The current VHA Master Specifications can be accessed at:

https://www.cfm.va.gov/TIL/spec.asp.

All VAMCs must complete a survey of their existing steam and hot water piping systems and develop a replacement plan, prioritizing high and medium pressure steam and hot water piping systems operating over 50 pounds per square inch. If ASTM A307 bolts (all grades) are identified, an Interim Safety Measure must be developed to ensure the safety of staff and the facility until replacement is complete.

3. DECISION: Effective immediately, Network Directors must ensure all VAMCs in their VISN review their specifications for projects in design and correct any references to ASTM A307 bolts, and for projects in construction, assess if ASTM A307 bolts are specified for use on any steam or hot water piping system. If ASTM A307 bolts are indicated, the construction contract must be modified to remove the ASTM A307 bolts. VISN Capital Asset Managers (CAM) must provide a list of impacted construction projects via email to the Office of Healthcare Engineering (OHE) at VHAHealthcareEng@va.gov by Friday, January 3, 2025.

All VAMCs must develop a plan to survey existing steam and hot water piping systems by Wednesday, June 18, 2025, and notify their VISN CAM upon completion of the survey.

Page 2.

Subj: For Action: Requirements for Identification and Replacement of A307 Bolts on Steam and Hot Water Piping Systems (VIEWS 12473639)

4. For additional information or questions regarding this memorandum, please contact OHE at VHAHealthcareEng@va.gov.

Alfred A. Montoya Jr., MHA, FACHE

Text9: December 13, 2024