Marion VA_Renovate 3B_Bid Documents_Drawings_V4 of 4_09-20-2024 41 pages - Copy.pdf

PDF 10 MB Posted

Attached to
Z2DA--657A5-23-110, Renovate 3B for Patient Privacy and Intensive Care Unit, (VA-25-00018450)
Solicitation number
36C25525R0015
Issued by

About this file

This is a 41-page set of mechanical, electrical and plumbing (MEP) drawings for renovations to Building 801's 3rd floor patient ward and ICU at the Marion VA Medical Center. The drawings include detailed electrical plans showing power, lighting, and low voltage systems; mechanical plans showing HVAC ductwork, piping, and equipment; and plumbing plans showing medical gas, water, and waste systems. Key components include air handling unit AH-5 with relief fans, variable air volume boxes, exhaust fans, domestic hot water and medical gas piping systems, and electrical distribution panels.

The drawings contain specific equipment schedules, control sequences, and installation details for all MEP systems. Notable elements include negative pressure isolation rooms, medical gas outlets, nurse call systems, and emergency power connections. The drawings are part of bid documents for solicitation 36C25525R0015 issued by the VA Veterans Health Administration Network 15 for renovations to improve patient privacy and intensive care capabilities. The drawings provide the technical MEP requirements that contractors must follow during construction.

View the file

Other files

File Type Posted
36C25525R0015 0006.docx DOCX document
S02 36C25525R0015 657A5-23-110 R3.docx DOCX document
Renovate 3B Hazardous Material Report.pdf PDF
36C25525R0015 0005.docx DOCX document
Sheet AI100 Color Schedule Key.pdf PDF
36C25525R0015 0004.docx DOCX document
36C25525R0015 0003.docx DOCX document
S04 Pre-Bid Site Visit Attendance.pdf PDF
36C25525R0015 0002.docx DOCX document
Requirements for Identification and Replacement of A307 Bolts Memo_Signed.pdf PDF
Marion VA_Renovate 3B_Bid Documents_Drawings_V1 of 4_09-20-2024 28 pages - Copy.pdf PDF
Marion VA_Renovate 3B_Bid Documents_Drawings_V2 of 4_09-20-2024 26 pages - Copy.pdf PDF
36C25525R0015 0001.docx DOCX document
S02 36C25525R0015 657A5-23-110.docx DOCX document
Marion VA_Renovate 3B_Bid Documents_Drawings_V3 of 4_09-20-2024 30 pages - Copy.pdf PDF
Marion VA_Renovate 3B_Bid Documents_Specifications_09-20-2024 1723 pages rev1 - Copy.pdf PDF
Marion VA_Renovate 3B_Bid Documents_Drawings_V3 of 4_09-20-2024 30 pages.pdf PDF
36C25525R0015.docx DOCX document
Marion VA_Renovate 3B_Bid Documents_Drawings_V1 of 4_09-20-2024 28 pages.pdf PDF
Marion VA_Renovate 3B_Bid Documents_Specifications_09-20-2024 1723 pages rev1.pdf PDF
Marion VA_Renovate 3B_Bid Documents_Drawings_V4 of 4_09-20-2024 41 pages.pdf PDF
Marion VA_Renovate 3B_Bid Documents_Drawings_V2 of 4_09-20-2024 26 pages.pdf PDF
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ELECTRICAL ABBREVIATIONS

ABBREVIATION DESCRIPTION

REFER TO OTHER SCHEDULES AND NOTES FOR ADDITIONAL ABBREVIATIONS.

MOUNTING HEIGHT TO CENTERLINE (ABOVE FINISHED FLOOR)

AMPERE

AMPERE FRAME

ABOVE FINISHED FLOOR

ALUMINUM

AMPERE TRIP

CEILING

CIRCUIT BREAKER

CORRELATED COLOR TEMPERATURE

COPPER

DATA (WHEN APPLIED TO COMMUNICATIONS OUTLET)

DEMO (WHEN APPLIED TO EXISTING/DEMO ITEMS)

EXISTING

ELECTRICALLY OPERATED

ENERGY REDUCING MAINTENANCE SWITCH

FUSE

FULL LOAD AMPS

GROUND FAULT CIRCUIT INTERRUPTER

GROUND FAULT ALARM

GROUND FAULT PROTECTION

HORSEPOWER

KILOAMPERE INTERRUPTING CAPACITY

KILOVOLT AMPERE

KILOWATT

MAXIMUM

MINIMUM CIRCUIT AMPS

MAIN CIRCUIT BREAKER

MINIMUM

MAIN LUGS ONLY

MANUALLY OPERATED

NORMALLY CLOSED

NON-FUSED

NOT IN CONTRACT

NORMALLY OPEN

POLES

PARTIAL

RELOCATE

SHORT CIRCUIT CURRENT RATING

SURGE PROTECTIVE DEVICE

SHUNT TRIP

TYPICAL

UNLESS NOTED OTHERWISE

VOICE

WALL PHONE

WIRE

WEATHER RESISTANT

TRANSFORMER

ZONE SELECTIVE INTERLOCKING

A

AF

AFF

AL

AT

C

CB

CCT

CU

D

D

E

EO

ERMS

F

FLA

G, GFCI

GFA

GFP

HP

KAIC

KVA

KW

MAX

MCA

MCB

MIN

MLO

MO

NC

NF

NIC

NO

P

PART

R

SCCR

SPD

ST

TYP

UNO

V

W

W

WR

XFMR

ZSI

A. BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 75' SHALL UTILIZE #10 AWG CONDUCTORS.

RECEPTACLE BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 150' SHALL UTILIZE #8 AWG

CONDUCTORS.

B. FOR ALL CONDUIT AND OTHER ITEMS PENETRATING A FIRE RATED WALL, PROVIDE UL LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL CONSTRUCTION ASSEMBLY AND COMPLIANT WITH ASTM E814. INSTALL SYSTEM IN STRICT COMPLIANCE WITH THE FIRE STOPPING MANUFACTURER’S U.L. APPROVED DETAIL. WHERE EXISTING WALLS ARE BEING UPGRADED TO FIRE RATED WALLS OR THE FIRE RATING IS BEING MODIFIED, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM FOR ALL NEW AND EXISTING PENETRATIONS. REFER TO THE ARCHITECTURAL LIFE

SAFETY PLANS FOR LOCATIONS OF FIRE RATED WALLS.

C. NEW ROOF MOUNTED EQUIPMENT SHALL BE BONDED TO EXISTING BUILDING LIGHTNING PROTECTION SYSTEM IF ONE EXISTS. PROVIDE AIR TERMINALS ON TOP OF EQUIPMENT AND BOND TO EXISTING SYSTEM PER NFPA 780 AND UL 96A REQUIREMENTS. PROVIDE UL INSPECTION AND/OR LPI SYSTEM INSPECTION AS REQUIRED TO OBTAIN UL MASTER LABEL RECERTIFICATION, UL MASTER LABEL AND/OR LPI SYSTEM

CERTIFICATE.

D. ANY ITEMS DAMAGED BY THE CONTRACTOR SHALL BE REPLACED BY THE CONTRACTOR, AT NO ADDITIONAL

COST TO THE OWNER.

E. NEW WIRING DEVICES AND ASSOCIATED COVERPLATES SHALL MATCH EXISTING FINISH OF SIMILAR

INSTALLED DEVICES.

F. THE SELECTED EQUIPMENT AIC RATINGS ARE BASED ON THE IMPEDANCES FOR CONDUCTORS AND TRANSFORMERS USED IN THE CALCULATIONS. IF DIFFERENT EQUIPMENT OR DIFFERENT CONFIGURATIONS

ARE SELECTED FOR INSTALLATION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING

ADEQUATELY RATED EQUIPMENT THAT MEETS APPLICABLE SELECTIVE COORDINATION GOALS AND

PROVIDES SIMILAR INCIDENT ENERGY RISK OF ARC FLASH HAZARDS.

G. PROVIDE AN INSULATED CONTINUOUS COPPER CONDUCTOR, NOT SMALLER THAN #10, TO BOND ALL

NORMAL AND ESSENTIAL ELECTRICAL SYSTEM PANELBOARDS TOGETHER THAT SERVE THE SAME

INDIVIDUAL PATIENT VICINITY AS DEFINED IN NEC 517.14.

H. ALL CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, INCLUDING LIGHTING AND WALL RECEPTACLES, SHALL BE MECHANICALLY PROTECTED PER NEC 517.31(C)(3). NON-FLEXIBLE RACEWAY SHALL BE USED FOR CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, EXCEPT THAT THE FINAL CONNECTION TO VIBRATING EQUIPMENT OR LIGHT FIXTURES IF THE TOTAL LENGTH OF FLEXIBLE RACEWAY IS 6' OR LESS ACROSS THE

ENTIRE CIRCUIT LENGTH.

I. PROVIDE ADDITIONAL SUPPORTS AS REQUIRED TO INDEPENDENTLY SUPPORT ALL EXISTING TO REMAIN

CABLING.

J. SOME SPECIFIED PRODUCTS MAY HAVE SUBSTANTIAL LEAD TIMES. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PLACING ORDERS IN A MANNER TO ENSURE THEIR TIMELY ARRIVAL. THE CONTRACTOR SHALL BE RESPONSIBLE FOR EXPENSES, INCLUDING DESIGN FEES, RELATED TO ANY RESELECTIONS

REQUIRED DUE TO FAILURE TO ORDER PRODUCTS IN A TIMELY MANNER.

(GENERAL NOTES SHALL APPLY TO ALL SHEETS)

ELECTRICAL GENERAL NOTES:

LEGEND: (LOW VOLTAGE COORDINATION LEGEND)

CF: CONTRACTOR FURNISHED

CI: CONTRACTOR INSTALLED

OF: OWNER FURNISHED

OI: OWNER INSTALLED

REMARKS: (LOW VOLTAGE COORDINATION LEGEND)

1. PATCH PANELS SHALL BE CONTRACTOR FURNISHED AND CONTRACTOR INSTALLED PER SPECIFICATION. REFER TO TYPICAL COMMUNICATION TERMINATION

DETAIL.

2. AUDIO/VISUAL CABLING SCOPE VARIES BY DEVICE. REFER TO SYMBOL LEGEND FOR REQUIREMENTS.

3. FIRE ALARM IS AN EXTENSION OF AN EXISTING SIEMENS SYSTEM. NEW DEVICES SHALL FUNCTION AS AN EXTENSION OF THE EXISTING SYSTEM.

4. NURSE CALL IS AN EXTENSION OF AN EXISTING RAULAND SYSTEM. NEW DEVICES SHALL FUNCTION AS AN EXTENSION OF THE EXISTING SYSTEM.

5. SECURITY IS AN EXTENSION OF AN EXISTING SIEMENS SYSTEM. NEW DEVICES SHALL FUNCTION AS AN EXTENSION OF THE EXISTING SYSTEM.

6. PATIENT MONITORING IS AN EXTENSION OF AN EXISTING SYSTEM. NEW DEVICES SHALL FUNCTION AS AN EXTENSION OF THE EXISTING SYSTEM.

GENERAL NOTES: (LOW VOLTAGE COORDINATION LEGEND)

A. REFER TO SYMBOL LEGENDS AND SPECIFICATIONS FOR SPECIFIC REQUIREMENTS.

B. COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL EQUIPMENT SELECTION FOR ALL SYSTEMS.

C. COORDINATE ROUGH-IN REQUIREMENTS WITH OWNER FOR OWNER FURNISHED SYSTEMS.

D. CONDUITS SHALL ROUTE CONCEALED INSIDE WALL TO ABOVE NEAREST ACCESSIBLE CEILING SPACE, UNLESS OTHERWISE INDICATED.

E. WHERE CABLING IS CONTRACTOR FURNISHED AND CONTRACTOR INSTALLED, TERMINATE AND TEST ALL CABLING PER SPECIFICATION.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

A

B

C

D

2 4 5

Phase

DESIGNER OF RECORD

A/E:

STAMPCONSULTANTS

MEP: STRUCTURAL:

6"

6"

6"

6"

O N

E E

IG

H

T H

I N

C H

O

N E

F O

O T

1/

8"

'-0

O

N E

Q U

A R

T E

R I

N C

H

O N

E F

O O

T

1/ 4"

'-0

T H

R E

E E

IG

H

T H

S

IN

C H

O

N E

F O

O T

(3 /8

1' -0

O

N E

H A

LF

I

N C

H

O N

E F

O O

T

1/ 2"

'-0

T H

R E

E Q

U A

R T

E R

S

IN

C H

O

N E

F O

O T

3/

4"

'-0

O

N E

I N

C H

O

N E

F O

O T

1"

'-0

O N

E A

N D

O N

E H

A

LF

I N

C H

E S

O

N E

F O

O T

1/ 2"

'-0

T H

R E

E

IN

C H

E S

O

N E

F O

O T

3"

'-0

32 4 5 61

SPECIALIZED ENGINEERING SOLUTIONS

10360 ELLISON CIRCLE

OMAHA, NE 68134

(402) 991-5520

NATHAN BOWMAN (MECH & PUMB)

MAY ALEXANDER (ELEC)

BSE ENGINEERS

11320 WEST 79TH STREET

LENEXA, KS 66214

(913) 492-7400

KEVIN BOEHRINGER (STRUCT)

09/20/2024

A ut od es k D oc s:

//2

.0

V A

M ar io n

IL

R en ov at e

P at ie nt

P riv ac y

IC

U /6

-1

.M

E P

_R

.r vt

9/

/2

:4 0:

P

M

E-000

ELECTRICAL SYMBOLS AND ABBREVIATIONS

STONE / HFG ARCHITECTURE

600 EAST 7TH ST & 330 N. MEAD

SIOUX FALLS, SD 57103 & WICHITA, KS 67202

(605) 271-1144 & (316) 262-2500

BEAU FEY (ARCH) & WAYNE BONGARTZ (PM)

RENOVATE PATIENT WARD 3B

FOR PATIENT PRIVACY AND

INTENSIVE CARE

MARION IL

BLDG #001

WESLEY PINKS

09/20/2024 MEA NJG

SGA #231942

VA #657A5-23-110

FINAL BID DOCUMENTS

ELEC SHEET: 1 OF 16

ELECTRICAL FIXTURE

SYMBOLS

PLAN SYMBOL NAME

RECEPTACLE - DOUBLE DUPLEX

- CONV

RECEPTACLE - DUPLEX - CONV

RECEPTACLE - DUPLEX - CONV -

GFCI

RECEPTACLE - DUPLEX -

EMERGENCY (RED) - CONV

RECEPTACLE - DUPLEX -

EMERGENCY (RED) - CONV -

GFCI

RECEPTACLE - DUPLEX -

EMERGENCY (RED) - KNOWN

LOAD

RECEPTACLE - DUPLEX -

HORIZONTAL - CONV

RECEPTACLE - SIMPLEX

FIRE ALARM SYMBOLS

PLAN SYMBOL NAME

BELL - WALL

DETECTOR - SYSTEM SMOKE -

CEILING

HORN AND STROBE

COMBINATION - CEILING

MANUAL PULL STATION

LIGHTING DEVICE SYMBOLS

PLAN SYMBOL NAME

LIGHT SWITCH

OCCUPANCY SENSOR - CEILING

ELECTRICAL MISC SYMBOLS

PLAN SYMBOL NAME

BRANCH CIRCUIT CONCEALED IN

CEILING OR WALL

BRANCH CIRCUIT CONCEALED IN

FLOOR OR BELOW GRADE

CLEARANCE SPACE

CONDUIT BREAK

CONDUIT DOWN

CONDUIT STUB-OUT

CONDUIT UP

HOMERUN TO PANEL

G = GFCI CIRCUIT

(PART) = PARTIAL CIRCUIT

SWITCHED RECEPTACLE

LOW VOLTAGE COORDINATION LEGEND

SYSTEMS

ROUGH-INS &

PATHWAYS

CABLING &

TERMINATIONS

DEVICES &

EQUIPMENT REMARKS

ACCESS CONTROL CF / CI CF / CI CF / CI 5

AUDIO / VIDEO INTERCOM CF / CI CF / CI CF / CI -

AUDIO / VISUAL CF / CI REMARK 2 OF / OI -

FIRE ALARM CF / CI CF / CI CF / CI 3

LIGHTING CONTROLS CF / CI CF / CI CF / CI -

NURSE CALL CF / CI CF / CI CF / CI 4

PATIENT MONITORING/TELEMETRY CF / CI CF / CI OF / OI 6

PUBLIC ADDRESS CF / CI CF / CI CF / CI -

SECURITY SURVEILLANCE (CCTV) CF / CI CF / CI CF / CI 5

TELEVISION (CATV) CF / CI CF / CI OF / OI -

VOICE / DATA CF / CI CF / CI OF / OI 1

WIRELESS ACCESS POINTS CF / CI CF / CI OF / OI 1

ELECTRICAL EQUIPMENT

SYMBOLS

PLAN SYMBOL NAME

BUS DUCT

COMBINATION MAGNETIC

STARTER/DISCONNECT

(ENCLOSED MOTOR

CONTROLLER)

DISTRIBUTION PANEL

ENCLOSED DISCONNECT

SWITCH - FUSED

PANELBOARD - SURFACE

TRANSFORMER - DRY TYPE

NURSE CALL SYMBOLS

PLAN SYMBOL NAME

DEFAULT

MOUNTING

HEIGHT ROUGH-IN

NURSE DESK CONSOLE 18" 4" SQUARE, 2-1/8"

DEEP BACK BOX

WITH 1 GANG TRIM

RING

ROUGH-IN BED INTERFACE PLUG 18" COORDINATE

ROUGH-IN STAFF STATION 48" COORDINATE

STAFF ASSIST AND CODE BLUE

STATION

48" 4" SQUARE, 2-1/8"

DEEP BACK BOX

WITH 1 GANG TRIM

RING

DATA SYMBOLS

PLAN SYMBOL NAME

ANTENNA

ROUGH-IN TELEVISION OUTLET -

WALL

SECURITY SYMBOLS

PLAN SYMBOL NAME

ROUGH-IN INTRUSION

DETECTION SYSTEM - MOTION

SENSOR - WALL

ROUGH-IN SECURITY

SURVEILLANCE CAMERA -

CEILING

SECURITY SYMBOL LEGEND

PLAN SYMBOL NAME DESCRIPTION

ACCESS CONTROL DEVICE GENERAL:

PROVIDE ACCESS CONTROL COMPONENTS AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH ACCESS CONTROLLED DEVICE TYPE AT DOORS INDICATED. REFER TO FLOOR PLANS FOR DEVICE DESIGNATION. PROVIDE ROUGH-INS PER ACCESS CONTROL ROUGH-IN DETAIL. DOOR ACCESS COMPONENTS SHALL BE RATED FOR CONTINUOUS OPERATION IN THEIR INSTALLED PROJECT CONDITIONS AS REQUIRED IN SPECIFICATION SECTION 281300. COORDINATE REQUIRED CONDUITS TO DOOR FRAME AND WALL MOUNTED DEVICES WITH DOOR HARDWARE CONTRACTOR. PROVIDE SURFACE MOUNTED CONDUIT AND BACK BOX IN UNFINISHED AREAS. PROVIDE 20A 120V NORMAL, BRANCH CIRCUIT TO DOOR CONTROLLERS LOCATED ABOVE EACH ACCESS CONTROLLED DOOR. PROVIDE FINAL CONNECTION OF 120V BRANCH CIRCUIT TO ALL POWER SUPPLIES REQUIRED FOR EACH DOOR FUNCTION. REFER TO FLOOR PLANS FOR BRANCH CIRCUIT DESIGNATIONS. PROVIDE ACCESS CONTROL CABLING FROM DOOR CONTROLLER TO COMPONENTS REQUIRED BY THE DOOR HARDWARE SPECIFICATION INCLUDING BUT NOT LIMITED TO CARD READER, DOOR POSITION SWITCH, ELECTRIC STRIKE, ELECTRIFIED HINGE, DOOR RELEASE PUSH BUTTON, MAGNETIC LOCK, AND REQUEST TO EXIT. PROVIDE DOOR POSITION SWITCH AND REQUEST TO EXIT AT EACH ACCESS CONTROLLED DOOR, UNLESS PROVIDED BY DOOR HARDWARE CONTRACTOR. CONTRACTOR SHALL TERMINATE ACCESS CONTROL CABLING TO DEVICES.

COORDINATE ALL TERMINATION REQUIREMENTS AND EXACT LOCATION OF TERMINATIONS WITH OWNER'S ACCESS CONTROL MANAGER. CABLE SHALL BE ROUTED WITHIN CABLE TRAY WHERE ABOVE ACCESSIBLE CEILINGS AND WITHIN CONDUIT IN UNFINISHED AREAS. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE SYSTEM PER SPECIFICATION SECTION 281300 INCLUDING BUT NOT LIMITED TO INSTALLATION, CONFIGURATION, DEVICES, AND CABLING. WHERE DOOR IS ALSO SPECIFIED/SHOWN TO UTILIZE DOOR OPERATOR, PROVIDE INTERLOCK TO ALLOW AUTOMATIC DOOR OPENING FROM THE ACCESS CONTROL SYSTEM UPON SUCCESSFUL CARD READ. SUBMIT SHOP DRAWINGS FOR APPROVAL. PROVIDE FIRE ALARM SYSTEM CONNECTION FOR DOOR RELEASE UPON ALARM.

INTEGRATE ACCESS CONTROL SYSTEM WITH DOOR OPERATORS, FIRE ALARM, WANDER PREVENTION, INFANT PROTECTION, INTERCOM, AND DOOR HARDWARE. REFER TO ACCESS CONTROL AND ARCHITECTURAL DOOR HARDWARE SPECIFICATIONS FOR COORDINATION OF FEATURES, DEVICES, AND CONNECTIONS REQUIRED.

TYPE ‘DPS’, DOOR POSITION SWITCH DOOR:

PROVIDE DOOR POSITION SWITCH MONITORED FROM ACCESS CONTROL SYSTEM. NO CARD READER SHALL BE

PROVIDED AT DOOR.

TYPE ‘DR#’, DOOR RELEASE OF ACCESS CONTROLLED DOOR: PROVIDE RELEASE OF DOOR INDICATED FROM PUSH BUTTON OF SAME TYPE AS INDICATED ON FLOOR PLANS. REFER TO DOOR RELEASE PUSH BUTTON SYMBOL

LEGEND DESCRIPTION FOR LABELING REQUIREMENTS.

CREDENTIAL CARD READER GENERAL:

PROVIDE PROXIMITY CARD READER AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH CARD READER TYPE AT APPROXIMATE LOCATION INDICATED. PROVIDE ROUGH-IN PER ACCESS CONTROL ROUGH-IN DETAIL. CARD READERS SHALL BE RATED FOR CONTINUOUS OPERATION IN THEIR INSTALLED PROJECT CONDITIONS AS REQUIRED IN SPECIFICATION SECTION 281300. SUBMIT SHOP DRAWINGS FOR APPROVAL.

COORDINATE EXACT LOCATION OF CARD READER WITH ARCHITECT, ARCHITECTURAL INTERIOR ELEVATIONS, AND OTHER DOOR COMPONENTS INCLUDING BUT NOT LIMITED TO PUSH PLATE ACTUATORS, REQUEST TO EXIT PUSH BUTTONS, INTERCOM STATIONS, AND NURSE CALL CANCEL STATIONS. REFER TO ACCESS CONTROL SYMBOL

LEGEND DESCRIPTION FOR CABLING AND ADDITIONAL REQUIREMENTS.

DOOR OPERATOR PROVIDE 20A 120V NORMAL BRANCH CIRCUIT TO DOOR OPERATOR. REFER TO FLOOR PLANS FOR BRANCH CIRCUIT DESIGNATIONS. COORDINATE REQUIRED ROUGH-IN TO DOOR FRAME FOR PUSH PLATE OR HAND WAVE ACTUATOR CABLING WITH DOOR HARDWARE CONTRACTOR. INCLUDE INTERLOCKS WITH OTHER DOOR HARDWARE COMPONENTS REQUIRED BY THE DOOR HARDWARE SPECIFICATION INCLUDING BUT NOT LIMITED TO CARD READER, ELECTRIC STRIKE, ELECTRIFIED HINGE, MAGNETIC LOCK, REQUEST TO EXIT, MOTION SAFETY CONTROLS, KEY SWITCH, AND POWER SUPPLY. WHERE DOOR IS ALSO SPECIFIED/SHOWN TO UTILIZE ACCESS CONTROL, PROVIDE INTERLOCK TO ALLOW AUTOMATIC DOOR OPENING FROM THE ACCESS CONTROL SYSTEM UPON SUCCESSFUL CARD READ. PROVIDE FIRE ALARM SYSTEM CONNECTION FOR OPERATOR DISABLING UPON ALARM.

INTEGRATE DOOR OPERATOR WITH FIRE ALARM, ACCESS CONTROL, WANDER PREVENTION, INFANT PROTECTION, INTERCOM, AND DOOR HARDWARE. REFER TO PUSH PLATE OR HAND WAVE ACTUATOR SYMBOL LEGEND DESCRIPTION FOR ADDITIONAL REQUIREMENTS. COORDINATE INSTALLATION WITH DOOR HARDWARE

CONTRACTOR.

DOOR OPERATOR HAND WAVE

ACTUATOR

INSTALL HAND WAVE ACTUATORS FURNISHED WITH DOOR OPERATOR AT APPROXIMATE LOCATION INDICATED ON FLOORPLANS. PROVIDE 4" SQUARE BACK BOX MOUNTED AT 48" AFF WITH SINGLE GANG TRIM RING AND ONE (1) 3/4" CONDUIT TO ABOVE NEAREST ACCESSIBLE CEILING FOR CABLING TO DOOR OPERATOR. COORDINATE EXACT LOCATION OF HAND WAVE ACTUATOR WITH ARCHITECT, ARCHITECTURAL INTERIOR ELEVATIONS, AND OTHER DOOR COMPONENTS INCLUDING BUT NOT LIMITED TO CARD READERS, REQUEST TO EXIT PUSH BUTTONS, INTERCOM STATIONS, NURSE CALL CANCEL STATIONS, INTRUSION DETECTION KEYPADS, WANDER PREVENTION KEYPADS, AND INFANT PROTECTION KEYPADS. HAND WAVE ACTUATORS MAY REQUIRE LOCATIONS REMOTE FROM THE DOOR TO ALLOW FOR OPERATION WHILE SIMULTANEOUSLY TRANSPORTING A PATIENT BED. MULTIPLE HAND WAVE ACTUATORS WILL BE REQUIRED WHERE APPROACH TO SAME SIDE OF DOOR IS FROM MULTIPLE DIRECTIONS. INTERLOCK TO OPERATE ASSOCIATED DOOR OPERATOR. REFER TO DOOR OPERATOR SYMBOL LEGEND DESCRIPTION FOR ADDITIONAL REQUIREMENTS. COORDINATE INSTALLATION WITH DOOR HARDWARE

CONTRACTOR.

DURESS ALARM HOLD-UP

BUTTON

GENERAL:

PROVIDE DURESS ALARM BUTTON AT APPROXIMATE LOCATION INDICATED ON FLOOR PLANS. PROVIDE 4" SQUARE BACK BOX WITH SINGLE GANG TRIM RING AND ONE (1) 1" CONDUIT TO ABOVE NEAREST ACCESSIBLE CEILING FOR CABLING. INTEGRATE DURESS ALARM WITH SECURITY SURVEILLANCE AND ACCESS CONTROL SYSTEM MONITORING. CABLING SHALL BE ROUTED IN CONDUIT CONCEALED WITHIN WALLS AND SUPPORTED EXPOSED ABOVE ACCESSIBLE CEILINGS UTILIZING CABLE TRAY OR J-HOOKS EVERY 10' ON CENTER MINIMUM IN CORRIDOR.

PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE SYSTEM, INCLUDING BUT NOT LIMITED TO: 120V BRANCH CIRCUITS, DURESS ALARM SYSTEM, INSTALLATION, CONFIGURATION, DEVICES, ROUGH-INS, AND CABLING. SUBMIT SHOP DRAWINGS FOR APPROVAL. COORDINATE EXACT MOUNTING LOCATION OF DURESS ALARM PUSH BUTTON

WITH ENGINEER, ARCHITECT, AND ARCHITECTURAL INTERIOR ELEVATIONS.

TYPE 'WALL', WALL MOUNTED, DURESS ALARM PUSH BUTTON:

PROVIDE ROUGH-IN DESCRIBED ABOVE, MOUNTED AT 36" AFF AT APPROXIMATE LOCATION INDICATED. PROVIDE SHROUDED HEAD RED PUSH BUTTON WITH STAINLESS STEEL FACEPLATE. PROVIDE FACEPLATE WITH RED

ENGRAVED LETTERING READING "DURESS ALARM".

INTERCOM - VIDEO GENERAL:

PROVIDE VIDEO INTERCOM SYSTEM COMPONENTS AS DESCRIBED IN THESE GENERAL NOTES AND THE NOTES BELOW FOR EACH DEVICE TYPE AT LOCATIONS INDICATED. REFER TO FLOOR PLANS FOR DEVICE DESIGNATION.

PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE SYSTEM. PROVIDE ONE (1) CATEGORY 6A NETWORK DATA CABLE FROM EACH DEVICE TO POWER OVER ETHERNET (POE) DATA SWITCH WITHIN ASSOCIATED COMMUNICATIONS DISTRIBUTION ROOM. COORDINATE DATA SWITCH REQUIREMENTS WITH OWNER'S IT REPRESENTATIVE. PROVIDE NETWORK DATA CABLE, JACK, INSERT, AND FACEPLATE PER SPECIFICATION SECTION 271200. PROVIDE ALL ACCESSORIES FOR A COMPLETE INSTALLATION. CABLING SHALL BE ROUTED IN CONDUIT CONCEALED WITHIN WALLS AND SUPPORTED EXPOSED ABOVE ACCESSIBLE CEILINGS UTILIZING CABLE TRAY OR J-HOOKS EVERY 10' ON CENTER MINIMUM IN CORRIDOR. SUBMIT SHOP DRAWINGS FOR APPROVAL. INTEGRATE DOOR RELEASE WITH DOOR HARDWARE. REFER TO ACCESS CONTROL AND ARCHITECTURAL DOOR HARDWARE

SPECIFICATIONS FOR COORDINATION OF FEATURES, DEVICES, AND CONNECTIONS REQUIRED.

TYPE 'MD', VIDEO MASTER STATION - DESK MOUNT:

PROVIDE AIPHONE MODEL IX-MV7-HB HANDSET MASTER STATION WITH DESKTOP STAND (OR PRIOR APPROVED EQUIVALENT) DESK MOUNTED AT LOCATION INDICATED. PROVIDE 4" SQUARE BACK BOX MOUNTED AT 18" AFF WITH SINGLE GANG TRIM RING AND ONE (1) 1" CONDUIT TO ABOVE NEAREST ACCESSIBLE CEILING FOR CABLING.

TYPE 'WF', VIDEO WALL STATION – FLUSH MOUNT:

PROVIDE AIPHONE MODEL IX-DVF-FLUSH MOUNT VIDEO INTERCOM (OR PRIOR APPROVED EQUIVALENT) WALL MOUNTED AT LOCATION INDICATED. INSTALL MANUFACTURER FURNISHED CUSTOM BACK BOX MOUNTED AT 50" AFF AND ONE (1) 1" CONDUIT TO ABOVE NEAREST ACCESSIBLE CEILING FOR CABLING. ADJUST CAMERA ANGLE TO +13

DEGREES (HIGH) TO ACCOMMODATE MOUNTING HEIGHT.

KEYPAD GENERAL:

PROVIDE PROXIMITY CARD READER AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH CARD READER TYPE AT APPROXIMATE LOCATION INDICATED. PROVIDE ROUGH-IN PER ACCESS CONTROL ROUGH-IN DETAIL. WHERE SHOWN MOUNTED ON DOOR/WINDOW SYSTEM MULLION, PROVIDE MULLION MOUNT CARD READER SURFACE MOUNTED ON MULLION. CABLING SHALL BE ROUTED RECESSED WITHIN MULLION TO ACCESSIBLE CEILING SPACE. COORDINATE INSTALLATION WITH MULLION MANUFACTURER. CARD READERS SHALL BE RATED FOR CONTINUOUS OPERATION IN THEIR INSTALLED PROJECT CONDITIONS AS REQUIRED IN SPECIFICATION SECTION 281300. SUBMIT SHOP DRAWINGS FOR APPROVAL. COORDINATE EXACT LOCATION OF CARD READER WITH ARCHITECT, ARCHITECTURAL INTERIOR ELEVATIONS, AND OTHER DOOR COMPONENTS. REFER TO ACCESS

CONTROL SYMBOL LEGEND DESCRIPTION FOR CABLING AND ADDITIONAL REQUIREMENTS.

PROVIDE COMBINATION KEYPAD PROXIMITY CARD READER PER SPECIFICATION.

SECURITY SURVEILLANCE

CAMERA - CEILING

GENERAL:

PROVIDE POWER, ROUGH-INS, AND CABLING FOR OWNER PROVIDED POWER OVER ETHERNET (POE) SECURITY SURVEILLANCE CAMERA AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH CAMERA TYPE AT LOCATIONS INDICATED. REFER TO FLOOR PLANS FOR CAMERA DESIGNATION. SECURITY SURVEILLANCE COMPONENTS SHALL BE RATED FOR CONTINUOUS OPERATION IN THEIR INSTALLED PROJECT CONDITIONS AS REQUIRED IN SPECIFICATION SECTION 282300. PROVIDE ONE (1) CATEGORY 6A NETWORK DATA CABLE FROM ASSOCIATED COMMUNICATIONS DISTRIBUTION ROOM TO APPROXIMATE LOCATION INDICATED ON FLOOR PLANS, COILED ABOVE FINISHED CEILING. TERMINATE CABLE WITH RJ45 CONNECTOR. PROVIDE WITH 10' OF CABLE SLACK AT LOCATION INDICATED. INSTALL CAMERA CENTERED IN CEILING TILE. PROVIDE 4" SQUARE BACK BOX WITH SINGLE GANG TRIM RING AND ONE (1) 1" CONDUIT TO ABOVE NEAREST ACCESSIBLE CEILING FOR CABLING AT LOCATIONS INDICATED WITHIN GYP CEILINGS. PROVIDE SURFACE MOUNTED CONDUIT AND BACK BOX IN UNFINISHED AREAS. COORDINATE ROUGH-IN REQUIREMENTS, PENDANT MOUNTS, PROTECTIVE DOMES, AND OTHER REQUIRED ACCESSORIES FOR EXTERIOR CAMERA LOCATIONS WITH SELECTED MANUFACTURER. PROVIDE 20A 120V NORMAL BRANCH CIRCUIT TO CAMERA LOCATIONS AS REQUIRED BY SELECTED MANUFACTURER FOR PAN-TILT-ZOOM FUNCTIONS AND ACCESSORIES. COORDINATE CABLING, POWER, AND ROUGH-IN REQUIREMENTS WITH SELECTED MANUFACTURER FOR CAMERA LOCATIONS WITH NETWORK DATA CABLE LENGTHS EXCEEDING 100 METERS. CABLE SHALL BE ROUTED WITHIN CABLE TRAY WHERE ABOVE ACCESSIBLE CEILINGS AND WITHIN CONDUIT IN UNFINISHED AREAS. PROVIDE NETWORK DATA CABLES AND JACKS PER SPECIFICATION SECTION

271200. COORDINATE EXACT MOUNTING LOCATION WITH OWNER PRIOR TO INSTALLATION.

ONE LINE SYMBOL

PLAN SYMBOL NAME

AUTOMATIC TRANSFER SWITCH

CIRCUIT BREAKER

CONTINUATION

CURRENT TRANSFORMER

DISCONNECT SWITCH

ENCLOSED CIRCUIT BREAKER

GENERATOR

GENERATOR CONNECTION BOX

GROUND BAR

GROUNDING ELECTRODE

KEY INTERLOCK

MOTOR STARTER

PANEL BOARD

SURGE PROTECTIVE DEVICE

SWITCHBOARD

SWITCHBOARD/SWITCHGEAR

SWITCHBOARD/SWITCHGEAR -

DOUBLE TUB

TRANSFORMER

UTILITY METER

REVISION # DESCRIPTION DATE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

A

B

C

D

2 4 5

Phase

DESIGNER OF RECORD

A/E:

STAMPCONSULTANTS

MEP: STRUCTURAL:

6"

6"

6"

6"

O N

E E

IG

H

T H

I N

C H

O

N E

F O

O T

1/

8"

'-0

O

N E

Q U

A R

T E

R I

N C

H

O N

E F

O O

T

1/ 4"

'-0

T H

R E

E E

IG

H

T H

S

IN

C H

O

N E

F O

O T

(3 /8

1' -0

O

N E

H A

LF

I

N C

H

O N

E F

O O

T

1/ 2"

'-0

T H

R E

E Q

U A

R T

E R

S

IN

C H

O

N E

F O

O T

3/

4"

'-0

O

N E

I N

C H

O

N E

F O

O T

1"

'-0

O N

E A

N D

O N

E H

A

LF

I N

C H

E S

O

N E

F O

O T

1/ 2"

'-0

T H

R E

E

IN

C H

E S

O

N E

F O

O T

3"

'-0

32 4 5 61

SPECIALIZED ENGINEERING SOLUTIONS

10360 ELLISON CIRCLE

OMAHA, NE 68134

(402) 991-5520

NATHAN BOWMAN (MECH & PUMB)

MAY ALEXANDER (ELEC)

BSE ENGINEERS

11320 WEST 79TH STREET

LENEXA, KS 66214

(913) 492-7400

KEVIN BOEHRINGER (STRUCT)

09/20/2024

A ut od es k D oc s:

//2

.0

V A

M ar io n

IL

R en ov at e

P at ie nt

P riv ac y

IC

U /6

-1

.M

E P

_R

.r vt

9/

/2

:4 0:

P

M

E-001

ELECTRICAL SYMBOLS

STONE / HFG ARCHITECTURE

600 EAST 7TH ST & 330 N. MEAD

SIOUX FALLS, SD 57103 & WICHITA, KS 67202

(605) 271-1144 & (316) 262-2500

BEAU FEY (ARCH) & WAYNE BONGARTZ (PM)

RENOVATE PATIENT WARD 3B

FOR PATIENT PRIVACY AND

INTENSIVE CARE

MARION IL

BLDG #001

WESLEY PINKS

09/20/2024 MEA NJG

SGA #231942

VA #657A5-23-110

FINAL BID DOCUMENTS

ELEC SHEET: 2 OF 16

ELECTRICAL FIXTURE SYMBOL LEGEND

PLAN SYMBOL NAME DESCRIPTION

DUPLEX AND DATA (CONV) PROVIDE DUPLEX RECEPTACLE AND COMMUNICATIONS OUTLET AT APPROXIMATE LOCATION INDICATED. BACK BOXES FOR EACH DEVICE SHALL BE MOUNTED APPROXIMATELY 6" BETWEEN BOX CENTERS. REFER TO SYMBOL

LEGEND ENTRY FOR EACH DEVICE FOR ADDITIONAL REQUIREMENTS.

DUPLEX AND DATA (CONV) -

GFCI

PROVIDE DUPLEX RECEPTACLE AND COMMUNICATIONS OUTLET AT APPROXIMATE LOCATION INDICATED. BACK BOXES FOR EACH DEVICE SHALL BE MOUNTED APPROXIMATELY 6" BETWEEN BOX CENTERS. REFER TO SYMBOL

LEGEND ENTRY FOR EACH DEVICE FOR ADDITIONAL REQUIREMENTS.

[CONFIRM COMMUNICATIONS OUTLET SYMBOL LEGEND ENTRY IS POPULATED FOR REQUIREMENTS]

DUPLEX AND DATA (KNOWN

LOAD)

PROVIDE DUPLEX RECEPTACLE AND COMMUNICATIONS OUTLET AT APPROXIMATE LOCATION INDICATED. BACK BOXES FOR EACH DEVICE SHALL BE MOUNTED APPROXIMATELY 6" BETWEEN BOX CENTERS. REFER TO SYMBOL

LEGEND ENTRY FOR EACH DEVICE FOR ADDITIONAL REQUIREMENTS.

DUPLEX QUAD AND DATA (CONV) PROVIDE DUPLEX RECEPTACLE, QUAD RECEPTACLE, AND COMMUNICATIONS OUTLET AT APPROXIMATE LOCATION INDICATED. BACK BOXES FOR EACH DEVICE SHALL BE MOUNTED APPROXIMATELY 6" BETWEEN BOX CENTERS.

REFER TO SYMBOL LEGEND ENTRY FOR EACH DEVICE FOR ADDITIONAL REQUIREMENTS.

EM DUPLEX AND DATA (CONV) PROVIDE EMERGENCY (RED) DUPLEX RECEPTACLE AND COMMUNICATIONS OUTLET AT APPROXIMATE LOCATION INDICATED. BACK BOXES FOR EACH DEVICE SHALL BE MOUNTED APPROXIMATELY 6" BETWEEN BOX CENTERS.

REFER TO SYMBOL LEGEND ENTRY FOR EACH DEVICE FOR ADDITIONAL REQUIREMENTS.

EM DUPLEX AND DATA (CONV) -

GFCI

PROVIDE EMERGENCY (RED) DUPLEX RECEPTACLE AND COMMUNICATIONS OUTLET AT APPROXIMATE LOCATION INDICATED. BACK BOXES FOR EACH DEVICE SHALL BE MOUNTED APPROXIMATELY 6" BETWEEN BOX CENTERS.

REFER TO SYMBOL LEGEND ENTRY FOR EACH DEVICE FOR ADDITIONAL REQUIREMENTS.

EM DUPLEX AND DATA (KNOWN

LOAD)

PROVIDE EMERGENCY (RED) DUPLEX RECEPTACLE AND COMMUNICATIONS OUTLET AT APPROXIMATE LOCATION INDICATED. BACK BOXES FOR EACH DEVICE SHALL BE MOUNTED APPROXIMATELY 6" BETWEEN BOX CENTERS.

REFER TO SYMBOL LEGEND ENTRY FOR EACH DEVICE FOR ADDITIONAL REQUIREMENTS.

EM DUPLEX AND DATA (KNOWN

LOAD) - GFCI

PROVIDE EMERGENCY (RED) DUPLEX RECEPTACLE AND COMMUNICATIONS OUTLET AT APPROXIMATE LOCATION INDICATED. BACK BOXES FOR EACH DEVICE SHALL BE MOUNTED APPROXIMATELY 6" BETWEEN BOX CENTERS.

REFER TO SYMBOL LEGEND ENTRY FOR EACH DEVICE FOR ADDITIONAL REQUIREMENTS.

[CONFIRM COMMUNICATIONS OUTLET SYMBOL LEGEND ENTRY IS POPULATED FOR REQUIREMENTS]

EM QUAD AND DATA (CONV) PROVIDE EMERGENCY (RED) DUPLEX RECEPTACLE AND COMMUNICATIONS OUTLET AT APPROXIMATE LOCATION INDICATED. BACK BOXES FOR EACH DEVICE SHALL BE MOUNTED APPROXIMATELY 6" BETWEEN BOX CENTERS.

REFER TO SYMBOL LEGEND ENTRY FOR EACH DEVICE FOR ADDITIONAL REQUIREMENTS.

EM QUAD AND DATA (KNOWN

LOAD)

PROVIDE EMERGENCY (RED) DUPLEX RECEPTACLE AND COMMUNICATIONS OUTLET AT APPROXIMATE LOCATION INDICATED. BACK BOXES FOR EACH DEVICE SHALL BE MOUNTED APPROXIMATELY 6" BETWEEN BOX CENTERS.

REFER TO SYMBOL LEGEND ENTRY FOR EACH DEVICE FOR ADDITIONAL REQUIREMENTS.

FIRE ALARM SYMBOL LEGEND

PLAN SYMBOL NAME DESCRIPTION

SMOKE DAMPER OR FIRE/SMOKE

DAMPER

CIRCUIT FIRE AND FIRE/SMOKE DAMPERS PROVIDED BY MECHANICAL CONTRACTOR TO 20A 120V BRANCH CIRCUITS IN ASSOCIATED LIFE SAFETY BRANCH PANEL (INSTALL CIRCUIT BREAKER LOCK ON BRANCH BREAKERS).

EACH BRANCH CIRCUIT SHALL SERVE A MAXIMUM OF 20 DAMPERS. PROVIDE INDIVIDUAL CIRCUITS FOR EACH AIR HANDLING UNIT ZONE. REFER TO MECHANICAL PLANS FOR ASSOCIATED ZONES. CONTROL EACH DAMPER INDIVIDUALLY WITH ADDRESSABLE CONTROL MODULES FROM FIRE ALARM SYSTEM. LABEL EACH RELAY WITH THE NAME OF THE AIR HANDLING UNIT SERVING THE SMOKE ZONE AND WITH THE WORDS "SMOKE DAMPER CONTROL".

PROVIDE SYSTEM DUCT SMOKE DETECTOR IN ACCESSIBLE LOCATION WITHIN 5 FEET OF THE DAMPER TO CONTROL DAMPER. DUCT DETECTOR MAY BE OMITTED WHERE THE DAMPER IS INSTALLED IN A CORRIDOR WALL OR CEILING AND IS CONTROLLED BY AN AREA SMOKE DETECTION SYSTEM INSTALLED IN THE CORRIDOR. PROVIDE REMOTE STATUS INDICATOR AND TEST STATION FOR DETECTOR AND COORDINATE ASSOCIATED MOUNTING

LOCATION WITH OWNER. REFER TO LOW VOLTAGE FLOOR PLANS FOR DAMPER LOCATIONS.

LIGHTING DEVICE SYMBOL LEGEND

PLAN SYMBOL NAME DESCRIPTION

PUSH BUTTON DEVICE SHALL PROVIDE ON/OFF CONTROL OF ZONES INDICATED. SUBSCRIPT LETTER(S) CORRESPOND TO LIGHTING ZONE(S) IN AREA. PROVIDE DEVICE CAPABLE OF SWITCHING QUANTITY OF ZONES INDICATED. WHERE NO ZONES ARE INDICATED, PROVIDE CONTROL OF SINGLE ZONE. MUST BE CAPABLE OF 3 AND 4 WAY SWITCHING FROM

ADDITIONAL DEVICES.

TYPE ‘D’ – DEVICE SHALL PROVIDE ON/OFF AND MIN/MAX DIMMING CONTROL OF ZONES INDICATED. SUBSCRIPT LETTER(S) CORRESPOND TO LIGHTING ZONE(S) IN AREA, PROVIDE DEVICE CAPABLE OF SWITCHING QUANTITY OF ZONES INDICATED. MUST BE CAPABLE OF 3 AND 4 WAY SWITCHING FROM ADDITIONAL DEVICES.

TYPE ‘SC#’ – DEVICE SHALL PROVIDE SCENE CONTROL CAPABLE OF CONTROLLING ALL ZONES IN ROOM BY PRESET SCENES. NUMBER INDICATES QUANTITY OF SCENES TO BE SELECTED AT THIS LOCATION. SEE LIGHTING SCENE

SCHEDULE FOR DESCRIPTION OF DESIRED SCENES.

TYPE ‘GFX’ – DEVICE SHALL INCLUDE GRAPHICAL TOUCH SCREEN TO PROVIDE SCENE CONTROL AS WELL AS

ON/OFF AND MIN/MAX DIMMING CONTROL OF ALL ZONES IN ROOM.

ELECTRICAL MISC SYMBOL LEGEND

PLAN SYMBOL NAME DESCRIPTION

CABLE TRAY PROVIDE CABLE TRAY AT LOCATIONS INDICATED ON PLANS. REFER TO FLOOR PLANS FOR TYPE DESIGNATION.

COORDINATE MOUNTING WITH OTHER TRADES AND REQUIREMENTS IN SPECIFICATION.

TYPE 'WIDTH x DEPTH", WIRE BASKET CABLE TRAY:

PROVIDE CABLE TRAY IN DIMENSION INDICATED ON FLOOR PLANS.

TYPE 'WIDTH LADDER', LADDER CABLE TRAY:

PROVIDE CABLE TRAY IN DIMENSION INDICATED ON FLOOR PLANS.

LIGHTING CONTROL TAG REFER TO LIGHTING CONTROL SCHEDULE FOR ADDITIONAL INFORMATION.

COMMUNICATION SYMBOL LEGEND

PLAN SYMBOL NAME DESCRIPTION

PUBLIC ADDRESS SPEAKER -

CEILING

PROVIDE PUBLIC ADDRESS CEILING SPEAKER, FLUSH MOUNTED AT APPROXIMATE LOCATION INDICATED ON FLOOR PLANS, CENTERED WITHIN CEILING TILE. [PROVIDE SPEAKER WITH INTEGRAL VOLUME CONTROL.] PROVIDE ONE (1) 1" CONDUIT TO NEAREST ACCESSIBLE CEILING SPACE WHEN MOUNTED WITHIN AN INACCESSIBLE CEILING.

PROVIDE CABLING FROM ASSOCIATED [ELECTRICAL] [COMMUNICATIONS] ROOM PUBLIC ADDRESS AMPLIFIER.

PROVIDE PUBLIC ADDRESS CABLES, CONDUCTORS, BACK CAN, TILE BRIDGES, POWER AMPLIFIERS, AND SPEAKERS PER SPECIFICATION SECTION 275116. PROVIDE ALL ACCESSORIES FOR A COMPLETE INSTALLATION. REFER TO

SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

WALL MOUNTED CLOCK PROVIDE ROUGH-IN PER COMMUNICATIONS OUTLET DETAIL. PROVIDE WITH BLANK FACEPLATE. PROVIDE ONE (1) 1" CONDUIT FOR CLOCK SYSTEM WIRING. PROVIDE WITH PULL CORDS. CONDUITS SHALL ROUTE CONCEALED INSIDE WALL TO ABOVE NEAREST ACCESSIBLE CEILING SPACE FOR INSTALLATION OF CABLING. COORDINATE EXACT

MOUNTING HEIGHT AND LOCATION WITH ARCHITECT AND INTERIOR ELEVATIONS.

NURSE CALL SYMBOL LEGEND

PLAN SYMBOL NAME

DEFAULT

MOUNTING

HEIGHT ROUGH-IN DESCRIPTION

BEDSIDE STATION - PILLOW

SPEAKER

48" 3 GANG, 3-1/2"

DEEP BACK BOX

PROVIDE CONTROL OF THE FOLLOWING SYSTEMS WITHIN SAME ROOM:

- LIGHT CONTROL: PILLOW SPEAKER SHALL PROVIDE SEPARATE CONTROL OF READING AND AMBIENT LIGHT SOURCES OF MULTI-FUNCTION OVERBED FIXTURE. REFER TO LIGHTING FIXTURE SCHEDULES FOR FIXTURE

FUNCTIONS. PROVIDE LOW-VOLTAGE RELAY TO INTERFACE WITH LIGHTING CONTROL SYSTEM.

- TV CONTROL: PILLOW SPEAKER SHALL PROVIDE ON/OFF CONTROL OF PATIENT TELEVISION AND HAVE SPEAKER

FOR TELEVISION VOLUME.

DOME LIGHT - CEILING -- 4" SQUARE, 2-3/4"

DEEP BACK BOX

WITH 1 GANG

TRIM RING

PROVIDE ONE (1) 1" CONDUIT TO ABOVE NEAREST ACCESSIBLE CORRIDOR CEILING SPACE WHEN INSTALLED

WITHIN GYP CEILING.

PULL CORD 48" 4" SQUARE, 2-1/8"

DEEP BACK BOX

WITH 1 GANG

TRIM RING

PULL CORD INSTALLATION SHALL MEET THE FOLLOWING REQUIREMENTS:

- TOILETS: LOCATED TO THE SIDE OF TOILETS, WITHIN 12" OF THE FRONT OF THE TOILET BOWL.

PULL CORD - SHOWER/TUB 48" 4" SQUARE, 2-1/8"

DEEP BACK BOX

WITH 1 GANG

TRIM RING

PULL CORD INSTALLATION SHALL MEET THE FOLLOWING REQUIREMENTS:

- SHOWERS & TUBS: LOCATED WITHIN NORMAL VIEW OF THE USER AND WITHIN REACH OF STAFF WITHOUT THE

NEED TO STEP INTO THE SHOWER OR TUB.

ZONE LIGHT - WALL 80" 4" SQUARE, 2-3/4"

DEEP BACK BOX

WITH 1 GANG

TRIM RING

PROVIDE ONE (1) 1" CONDUIT TO ABOVE NEAREST ACCESSIBLE CORRIDOR CEILING SPACE

DATA SYMBOL LEGEND

PLAN SYMBOL NAME DESCRIPTION

COMMUNICATIONS OUTLET -

CEILING

PROVIDE ONE (1) CATEGORY 6A NETWORK DATA CABLE FROM ASSOCIATED COMMUNICATIONS DISTRIBUTION ROOM TO APPROXIMATE LOCATION INDICATED ON FLOOR PLANS. TERMINATE CABLE WITH RJ45 CONNECTOR IN FACEPLATE, CENTERED IN CEILING TILE. PROVIDE WITH 15' OF CABLE SLACK AT LOCATION INDICATED. PROVIDE ROUGH-IN PER COMMUNICATIONS OUTLET DETAIL AT LOCATIONS INDICATED WITHIN GYP CEILINGS. PROVIDE SURFACE MOUNTED CONDUIT AND BACK BOX IN UNFINISHED AREAS. CABLE SHALL BE ROUTED WITHIN CABLE

TRAY WHERE ABOVE ACCESSIBLE CEILINGS AND WITHIN CONDUIT IN UNFINISHED AREAS.

COMMUNICATIONS OUTLET -

WALL

GENERAL:

PROVIDE COMMUNICATIONS OUTLET AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH OUTLET TYPE. REFER TO PLANS FOR OUTLET DESIGNATION AND QUANTITIES OF NETWORK VOICE/DATA CABLES TO BE PROVIDED TO OUTLET FROM ASSOCIATED NEAREST COMMUNICATIONS DISTRIBUTION ROOM. PROVIDE ROUGH-IN PER COMMUNICATIONS OUTLET DETAIL. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE SYSTEM PER SPECIFICATION SECTION 271200 INCLUDING, BUT NOT LIMITED TO INSTALLATION, CONFIGURATION, DEVICES, JACKS, INSERTS, FACEPLATES, AND CABLING. SUBMIT SHOP DRAWINGS FOR APPROVAL. COORDINATE EXACT FINAL LOCATION WITH ARCHITECTURAL INTERIOR ELEVATIONS PRIOR TO INSTALLATION. PROVIDE CABLING AS LISTED BELOW. OUTLETS WITH NO CABLING DESIGNATION SHALL BE EMPTY WITH A BLANK WALL PLATE.

CABLING DESIGNATIONS ARE TYPICAL FOR ALL WALL, FLOOR, AND CEILING COMMUNICATIONS DEVICES. REFER TO

SPECIFICATIONS FOR CABLING REQUIREMENTS FOR EACH TYPE.

-A = ONE (1) ANALOG VOICE CABLE

-V = ONE (1) VOICE CABLE

-D = ONE (1) DATA CABLE

TYPE ‘H’, HORIZONTAL:

PROVIDE COMMUNICATIONS OUTLET DESCRIBED ABOVE, MOUNTED HORIZONTALLY TO ACCOMMODATE BUILDING

CONSTRAINTS.

TYPE ‘W’, WALL PHONE:

PROVIDE ONE (1) NETWORK VOICE CABLE, MOUNTED IN WALL PHONE MOUNTING BRACKET FACEPLATE, MOUNTED AT 48” AFF. COORDINATE MOUNTING LOCATION WITH OTHER TRADES AND FINAL EQUIPMENT SELECTION.

TELEVISION OUTLET AND WALL

BOX

GENERAL:

PROVIDE TELEVISION, DATA, AND AUDIO/VISUAL CONNECTIONS AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH TELEVISION TYPE. REFER TO PLANS FOR TELEVISION OUTLET/ WALL BOX DESIGNATION.

PROVIDE RG6 COAX CABLES FROM ASSOCIATED COMMUNICATIONS DISTRIBUTION ROOM CATV DISTRIBUTION POINT. PROVIDE NETWORK DATA CABLE FROM ASSOCIATED COMMUNICATIONS DISTRIBUTION ROOM. PROVIDE CATV CABLES, NETWORK DATA CABLES, INSERTS, AND FACEPLATES PER SPECIFICATION SECTIONS 274133 AND 271200. COORDINATE REQUIREMENTS WITH WALL BOX MANUFACTURER. PROVIDE ALL ACCESSORIES FOR A COMPLETE INSTALLATION, INCLUDING BUT NOT LIMITED TO: BRACKETS, BLANK COVER ASSEMBLIES, MOUNTING FRAMES, AND ADAPTERS. CONDUITS SHALL ROUTE CONCEALED INSIDE WALL TO NEAREST CORRIDOR CABLE TRAY FOR INSTALLATION OF CATV AND NETWORK DATA CABLING. WHERE NOTED ON PLANS, CONDUITS SHALL ROUTE CONCEALED INSIDE WALL TO LOCATION INDICATED BELOW FOR AUDIO/VISUAL CONNECTIONS. COORDINATE EXACT MOUNTING HEIGHT AND LOCATION WITH ARCHITECT AND INTERIOR ELEVATIONS. SUBMIT PRODUCT DATA FOR

APPROVAL.

NO TYPE, CATV AND DATA TELEVISION OUTLET:

PROVIDE ROUGH-IN PER COMMUNICATIONS OUTLET DETAIL. PROVIDE WITH FACEPLATE TO MATCH WIRING DEVICES. PROVIDE ONE (1) FEMALE TYPE F CONNECTOR AND ONE (1) RJ-45 DATA NETWORK JACK IN COMMON FACEPLATE. PROVIDE ONE (1) RG6 COAX CABLE, ONE (1) NETWORK DATA CABLE. PROVIDE (1) DUPLEX RECEPTACLE MOUNTED ADJACENT TO TELEVISION OUTLET. RECEPTACLE SHALL BE MOUNTED WITHIN 6" OF TELEVISION OUTLET.

TYPE 'AV1', CATV, DATA, AND AUDIO/VISUAL ROUGH-IN RECESSED WALL BOX:

PROVIDE WIREMOLD MODEL EFSB4 RECESSED WALL BOX AT APPROXIMATE LOCATION INDICATED. PROVIDE ONE (1) 1-1/2" CONDUIT WITH PULL CORD TO ABOVE FINISHED ACCESSIBLE CEILING WITHIN THE SAME SPACE FOR OWNER PROVIDED AUDIO/VISUAL CABLING. PROVIDE ONE (1) 1-1/4" CONDUIT FOR CATV AND NETWORK DATA CONNECTIONS.

PROVIDE ONE (1) FEMALE TYPE F CONNECTOR AND TWO (2) RJ-45 DATA NETWORK JACK IN COMMON FACEPLATE.

PROVIDE TWO (2) DUPLEX RECEPTACLES, MOUNTED WITHIN WALL BOX. PROVIDE ONE (1) 3/4" CONDUIT TO ELECTRICAL SOURCE FOR ONE (1) 20A 120V BRANCH CIRCUIT. REFER TO PLANS FOR BRANCH CIRCUIT. PROVIDE

ONE (1) RG6 COAX CABLE AND TWO (2) NETWORK DATA CABLES.

TYPE 'INFO', DATA, AND AUDIO/VISUAL ROUGH-IN RECESSED WALL BOX:

PROVIDE WIREMOLD MODEL EFSB4 RECESSED WALL BOX AT APPROXIMATE LOCATION INDICATED. PROVIDE ONE (1) 1-1/2" CONDUIT WITH PULL CORD TO ABOVE FINISHED ACCESSIBLE CEILING WITHIN THE SAME SPACE FOR OWNER PROVIDED AUDIO/VISUAL CABLING. PROVIDE ONE (1) 1-1/4" CONDUIT FOR CATV AND NETWORK DATA CONNECTIONS.

PROVIDE TWO (2) RJ-45 DATA NETWORK JACKS IN COMMON FACEPLATE. PROVIDE ONE (1) DUPLEX RECEPTACLE, MOUNTED WITHIN WALL BOX. PROVIDE ONE (1) 3/4" CONDUIT TO ELECTRICAL SOURCE FOR ONE (1) 20A 120V BRANCH CIRCUIT. REFER TO PLANS FOR BRANCH CIRCUIT. PROVIDE TWO (2) NETWORK DATA CABLES.

TV OUTLET - CEILING GENERAL:

PROVIDE TELEVISION, DATA, AND AUDIO/VISUAL CONNECTIONS AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH TELEVISION TYPE. REFER TO PLANS FOR TELEVISION OUTLET DESIGNATION. PROVIDE WITH FACEPLATE(S) TO MATCH WIRING DEVICES. PROVIDE RG6 COAX CABLES FROM ASSOCIATED COMMUNICATIONS DISTRIBUTION ROOM CATV DISTRIBUTION POINT. PROVIDE NETWORK DATA CABLE FROM ASSOCIATED COMMUNICATIONS DISTRIBUTION ROOM. PROVIDE CATV CABLES, NETWORK DATA CABLES, AUDIO/VISUAL CABLES, JACKS, INSERTS, AND FACEPLATES PER SPECIFICATION SECTIONS 274133 AND 271200.

PROVIDE DUPLEX RECEPTACLE MOUNTED ADJACENT TO TELEVISION OUTLET PER PLANS. RECEPTACLE SHALL BE MOUNTED WITHIN 6". COORDINATE EXACT MOUNTING LOCATION WITH FINAL TELEVISION/ PROJECTOR LOCATION.PROVIDE ALL ACCESSORIES FOR A COMPLETE INSTALLATION. SUBMIT PRODUCT DATA FOR APPROVAL.

NO TYPE, CATV AND DATA TELEVISION OUTLET:

PROVIDE ONE (1) 4" SQUARE, 2-1/8" DEEP, JUNCTION BOX WITH SINGLE GANG TRIM RING RECESSED IN CEILING AT APPROXIMATE LOCATION INDICATED. PROVIDE ONE (1) 1" CONDUIT TO ACCESSIBLE CEILING SPACE WHERE INSTALLED WITHIN INACCESSIBLE CEILING. PROVIDE ONE (1) FEMALE TYPE F CONNECTOR AND ONE (1) RJ-45 DATA NETWORK JACK IN COMMON FACEPLATE. PROVIDE ONE (1) RG6 COAX CABLE AND ONE (1) NETWORK DATA CABLE.

DATA SYMBOL LEGEND

PLAN SYMBOL NAME DESCRIPTION

WIRELESS ACCESS POINT -

CEILING

OWNER PROVIDED WIRELESS ACCESS POINT AT APPROXIMATE LOCATION INDICATED. PROVIDE ONE (1) CATEGORY 6A NETWORK DATA CABLE FROM ASSOCIATED COMMUNICATIONS DISTRIBUTION ROOM TO APPROXIMATE LOCATION INDICATED ON FLOOR PLANS, COILED ABOVE FINISHED CEILING. TERMINATE CABLE WITH RJ45 CONNECTOR WITHIN SURFACE MOUNT BOX. PROVIDE WITH 15' OF CABLE SLACK AT LOCATION INDICATED.

PROVIDE ROUGH-IN PER COMMUNICATIONS OUTLET DETAIL AT LOCATIONS INDICATED WITHIN GYP CEILINGS.

PROVIDE SURFACE MOUNTED CONDUIT AND BACK BOX IN UNFINISHED AREAS. CABLE SHALL BE ROUTED WITHIN CABLE TRAY WHERE ABOVE ACCESSIBLE CEILINGS AND WITHIN CONDUIT IN UNFINISHED AREAS. LOCATIONS

SHOWN ARE PRELIMINARY. CONFIRM FINAL LOCATION WITH OWNER PRIOR TO PULLING CABLE.

ELECTRICAL FIXTURE SYMBOL LEGEND

PLAN SYMBOL NAME DESCRIPTION

EM QUAD AND DATA (KNOWN

LOAD) - GFCI

PROVIDE EMERGENCY (RED) DUPLEX RECEPTACLE AND COMMUNICATIONS OUTLET AT APPROXIMATE LOCATION INDICATED. BACK BOXES FOR EACH DEVICE SHALL BE MOUNTED APPROXIMATELY 6" BETWEEN BOX CENTERS.

REFER TO SYMBOL LEGEND ENTRY FOR EACH DEVICE FOR ADDITIONAL REQUIREMENTS.

GROUND BAR PROVIDE LENGTH AS REQUIRED TO ACCOMMODATE TERMINATIONS, MINIMUM 20" IN LENGTH FOR ELECTRICAL GROUND BARS AND MINIMUM 10" IN LENGTH FOR TELECOMMUNICATIONS GROUND BARS. REFER TO

SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

HARDWIRED PLUMBING PROVIDE 20A 120V CONNECTION TO PLUMBING FIXTURE TRANSFORMER AND ASSOCIATED LOW VOLTAGE CONTROLS. REFER TO PLANS FOR BRANCH CIRCUIT. LOW VOLTAGE TRANSFORMER (FURNISHED BY MECHANICAL CONTRACTOR) SHALL BE MOUNTED INSIDE NEMA 1 ENCLOSURE, ABOVE FINISHED CEILING IN ACCESSIBLE LOCATION. PROVIDE NEMA 5-20 RECEPTACLE WITHIN ENCLOSURE OR SINGLE POLE TOGGLE SWITCH DISCONNECT MOUNTED ADJACENT TO ENCLOSURE TO ACCOMMODATE TRANSFORMER (COORDINATE WITH FURNISHED TRANSFORMER). PROVIDE LOW VOLTAGE WIRING FROM TRANSFORMER LOCATION TO AUTOMATIC PLUMBING FIXTURE COMPONENTS (FAUCET OR FLUSH VALVE SENSORS, SOLENOID VALVES, AND CONTROL BOXES) CONCEALED IN 1/2" CONDUIT WITHIN WALLS AND UTILIZING MANUFACTURER'S FINISHED METAL CLAD CABLE WHERE MOUNTED EXPOSED TO VIEW. DEVICE BOXES FOR CONNECTIONS TO EXTERNAL PLUMBING COMPONENTS SHALL BE LOCATED DIRECTLY ADJACENT TO THOSE COMPONENTS SO AS TO MINIMIZE THE LENGTH OF ANY EXPOSED CABLE. UTILIZE MANUFACTURER'S CONNECTION CABLE AND DEVICE/ESCUTCHEON PLATES WHERE APPLICABLE. COORDINATE SELECTION OF CABLE LENGTHS TO ACCOMMODATE CONSTRUCTION. OBTAIN APPROVAL FROM ARCHITECT FOR LOCATION OF DEVICES EXPOSED TO VIEW. MULTIPLE DEVICES MAY BE SERVED FROM A SINGLE TRANSFORMER WITH APPROPRIATE SIZING FROM THE MANUFACTURER. COORDINATE REQUIREMENTS AND CONDUIT STUB LOCATION BELOW SINK WITH MECHANICAL CONTRACTOR AND FINAL PLUMBING FIXTURE SELECTION. REFER TO PLUMBING PLANS FOR PLUMBING FIXTURE SCHEDULE.

JUNCTION BOX - CEILING GENERAL:

PROVIDE JUNCTION BOX AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH JUNCTION BOX TYPE. REFER TO PLANS FOR JUNCTION BOX DESIGNATION. PROVIDE ONE (1) 4" SQUARE, 2-1/8" DEEP JUNCTION BOX. WHERE SHOWN AS PART OF BRANCH CIRCUIT, PROVIDE CONDUCTORS WITHIN CONDUIT TO SOURCE

INDICATED ON FLOOR PLANS.

TYPE ‘SCALE’, DIGITAL SCALE FLOOR FRAME:

PROVIDE ONE (1) 1" CONDUIT FROM FLOOR-MOUNTED RECESSED FRAME TO READOUT PANEL BACK BOX FOR COMMUNICATIONS CABLING BY OWNER. COORDINATE EXACT MOUNTING LOCATION WITH FINAL EQUIPMENT

SELECTION.

TYPE 'LIFT', PATIENT LIFT MOTOR AND SYSTEM CONNECTION:

PROVIDE 20A 120V BRANCH CIRCUIT TO PATIENT LIFT TRANSFORMER DEVICE. LOCATE JUNCTION BOX ABOVE ACCESSIBLE CEILING. COORDINATE ROUGH-IN AND ELECTRICAL CONNECTION WITH FINAL TRANSFORMER LOCATION, LIFT VENDOR (GULDMANN), AND ARCHITECT. WHERE CEILING IS NOT ACCESSIBLE, PROVIDE 12" SQUARE ACCESS PANEL AT LOCATION OF JUNCTION BOX OF RATING AND FINISH SIMILAR TO CEILING.

JUNCTION BOX - WALL GENERAL:

PROVIDE JUNCTION BOX AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH JUNCTION BOX TYPE. REFER TO PLANS FOR JUNCTION BOX DESIGNATION. PROVIDE ONE (1) 4" SQUARE, 2-1/8" DEEP JUNCTION BOX WITH SINGLE GANG TRIM RING AND BLANK WALL PLATE WITH ONE (1) 1” CONDUIT TO ABOVE FINISHED CEILING WHERE NOT INDICATED OTHERWISE. WHERE SHOWN ADJACENT TO RECEPTACLES ON FLOOR PLANS, PROVIDE MAXIMUM 12” BETWEEN BACK BOXES. WHERE SHOWN AS PART OF BRANCH CIRCUIT, PROVIDE CONDUCTORS

WITHIN CONDUIT TO SOURCE INDICATED ON FLOOR PLANS.

TYPE 'EWC-1', ELECTRIC WATER COOLER:

PROVIDE DUPLEX RECEPTACLE AT APPROXIMATE LOCATION INDICATED. CONFIRM HEIGHT "AFF. COORDINATE EXACT MOUNTING LOCATION WITH ADA REQUIREMENTS, FINAL PLUMBING FIXTURE SELECTION, AND PLUMBING

CONTRACOR INSTALLATION LOCATION TO CONCEAL BEHIND EQUIPMENT PANEL.

TYPE 'GLASS', ELECTROCHROMIC PRIVACY GLASS:

PROVIDE JUNCTION BOX CONCEALED ABOVE ACCESSIBLE CEILING FOR FINAL TERMINATION OF QUANTITY OF ASSOCIATED SWITCHING POWER PACKS FOR ELECTROCHROMIC GLASS INSTALLATION IN ALCOVE. COORDINATE

FINAL LOCATION OF JUNCTION BOX WITH PRIVACY GLASS INSTALLER.

TYPE ‘NP’, MODULAR FURNITURE FEED POWER CONNECTION:

PROVIDE CONNECTION FOR NORMAL POWER TO MODULAR HEADWALL.

TYPE ‘CP’, MODULAR FURNITURE FEED POWER CONNECTION:

PROVIDE CONNECTION FOR CRITICAL POWER TO MODULAR HEADWALL.

TYPE ‘NC’, MODULAR FURNITURE FEED POWER CONNECTION:

PROVIDE CONNECTION FOR NURSE CALL FUNCTIONS TO MODULAR HEADWALL.

QUAD AND DATA (CONV) PROVIDE QUAD RECEPTACLE AND COMMUNICATIONS OUTLET AT APPROXIMATE LOCATION INDICATED. BACK BOXES FOR EACH DEVICE SHALL BE MOUNTED APPROXIMATELY 6" BETWEEN BOX CENTERS. REFER TO SYMBOL

LEGEND ENTRY FOR EACH DEVICE FOR ADDITIONAL REQUIREMENTS.

RECEPTACLE - DUPLEX -

CEILING MOUNTED

GENERAL:

PROVIDE DUPLEX RECEPTACLE AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH TYPE.

REFER TO FLOOR PLANS FOR DESIGNATION. PROVIDE ONE (1) 4" SQUARE, 2-1/8" DEEP JUNCTION BOX WITH SINGLE GANG TRIM RING WITH ONE (1) 3/4” CONDUIT TO ELECTRICAL SOURCE. WHERE SHOWN ADJACENT TO AUDIO/VISUAL CEILING COMPONENTS ON FLOOR PLANS, PROVIDE MAXIMUM 8" BETWEEN BACK BOXES. REFER TO FLOOR PLANS

FOR BRANCH CIRCUIT DESIGNATION.

NO TYPE, CEILING MOUNTED DUPLEX RECEPTACLE:

PROVIDE NEMA 5-20 RECEPTACLE, MOUNTED FLUSH WITH CEILING TILE OR GYP CEILING BOARD AT APPROXIMATE

LOCATION INDICATED.

TYPE 'BOX', CEILING BOX:

PROVIDE NIGEL B DESIGN MODEL NB-PLWB (OR PRIOR APPROVED EQUIVALENT), UL 2043 LISTED ENCLOSURE AT APPROXIMATE LOCATION INDICATED. ENCLOSURE SHALL BE MOUNTED ABOVE FINISHED CEILING IN ACCESSIBLE LOCATION. ENCLOSURE SHALL INCLUDE NEMA 5-20 RECEPTACLE, MOUNTED WITHIN ENCLOSURE. SERVE FROM 20A 120V BRANCH CIRCUIT INDICATED ON FLOORPLANS. INSTALL PER MANUFACTURER REQUIREMENTS. PROVIDE ALL

PARTS NECESSARY FOR A COMPLETE INSTALLATION. SUBMIT SHOP DRAWINGS FOR APPROVAL.

SURFACE RACEWAY - POWER GENERAL:

PROVIDE SURFACE RACEWAY AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH SURFACE RACEWAY TYPE. REFER TO PLANS FOR RACEWAY DESIGNATION. PROVIDE GFCI TYPE RECEPTACLES WHERE LOCATED WITHIN 6'-0" OF SINK EDGE. PROVIDE RACEWAY LENGTH PER PLANS. MOUNT 5" ABOVE BACKSPLASH WHERE INDICATED ABOVE COUNTERTOP. MOUNT AT 48" AFF AT ALL OTHER LOCATIONS, UNLESS OTHERWISE INDICATED. PROVIDE MINIMUM ONE (1) 20A 120V BRANCH CIRCUIT FOR EACH 10'-0" OF RACEWAY. REFER TO PLAN SHEETS FOR CIRCUIT DESIGNATIONS. COORDINATE REQUIREMENTS WITH RACEWAY MANUFACTURER. PROVIDE ALL ACCESSORIES FOR A COMPLETE INSTALLATION, INCLUDING BUT NOT LIMITED TO: END CAPS, COUPLINGS, AND SUPPORTS. CONCEAL ALL CONDUITS IN ADJACENT WALL. COORDINATE EXACT MOUNTING HEIGHT AND LOCATION

WITH ARCHITECTURAL ELEVATIONS.

TYPE 'SR1', 20A STEEL RACEWAY:

PROVIDE WIREMOLD SERIES 5400 (OR PRIOR APPROVED EQUIVALENT) PLUGMOLD TWO CHANNEL STEEL SURFACE RACEWAY. PROVIDE WITH STAINLESS STEEL FINISH. PROVIDE WITH DUPLEX RECEPTACLES AT LOCATIONS INDICATED ON PLANS. PROVIDE WITH QUANTITY OF DATA ROUGH-INS AT LOCATIONS INDICATED ON PLANS, AND ADJACENT TO NEAREST DUPLEX RECEPTACLE. PROVIDE 3', 5', AND 6' SECTIONS COUPLED TOGETHER TO MATCH

OVERALL LENGTHS INDICATED ON PLANS.

TYPE 'SR2', 20A STEEL RACEWAY:

PROVIDE WIREMOLD SERIES 2000 (OR PRIOR APPROVED EQUIVALENT) PLUGMOLD SINGLE CHANNEL STEEL SURFACE RACEWAY. PROVIDE WITH STAINLESS STEEL FINISH. PROVIDE WITH SIMPLEX RECEPTACLES LOCATED 12" ON CENTER. PROVIDE 3', 5', AND 6' SECTIONS COUPLED TOGETHER TO MATCH OVERALL LENGTHS INDICATED ON

PLANS.

TV

J

F

ID

S

S

S

S

S S

S

S

S

S

AT

AT

AT

AT

AT

AT

AT

ATAT

AT

AT

AT

AT

AT AT

AT

AT

AT

ATAT

AT ATAT

AT

AT

ATAT

D

D

D

D

D

D

D

D

D

D

D

DD

F F F

F

F

F

F

F

N C

F

NC

C

CC

NC

NC

NC

F

N C

N C

N C

NC

NC

NC

NC

NC

NC

A. THE INTENT OF THE DEMOLITION DRAWINGS IS TO DEFINE THE SCOPE OF ELECTRICAL DEMOLITION WORK. EXISTING ELECTRICAL SYSTEMS (DEVICES, FIXTURES, EQUIPMENT, WIRING, AND RACEWAYS INCLUDING DATA/COMMUNICATION SYSTEMS). EXISTING ELECTRICAL SYSTEMS SERVING ADJACENT AREAS SHALL REMAIN UNLESS OTHERWISE INDICATED. RE-SUPPORT EXISTING CONDUITS AND CABLES THAT MUST

REMAIN. REFER TO FLOORPLANS FOR INDICATION OF DEMOLITION TYPE FOR EACH AREA:

a. BLANKET DEMOLITION AREAS:

• EXISTING ELECTRICAL SYSTEMS WITHIN LIMITS OF DEMOLITION SHALL BE REMOVED UNLESS

OTHERWISE INDICATED.

b. SELECTIVE DEMOLITIONS AREAS:

• PROVIDE DEMOLITION FOR ITEMS AS SHOWN. EXISTING ELECTRICAL SYSTEMS WITHIN LIMITS OF

DEMOLITION SHALL REMAIN UNLESS OTHERWISE INDICATED.

B. ITEMS INDICATED WITH A SUBSCRIPT 'E' SHALL BE EXISTING TO REMAIN (E-EXISTING). ITEMS INDICATED WITH A

SUBSCRIPT 'D' OR SHOWN DASHED SHALL BE REMOVED (D-DEMOLITION). ITEMS INDICATED WITH A SUBSCRIPT

'R' SHALL BE REMOVED, STORED, AND REINSTALLED PER NEW WORK (R-RELOCATION).

C. THESE DRAWINGS DO NOT IDENTIFY EACH INDIVIDUAL ITEM TO BE REMOVED. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING ITEMS WHICH MUST BE REMOVED TO FACILITATE NEW CONSTRUCTION. SEE ARCHITECTURAL PLANS FOR EXACT LIMITS OF DEMOLITION AND CONSTRUCTION. THESE PLANS ARE BASED

ON PAST PROJECT DRAWINGS AND SITE OBSERVATIONS. THE DRAWINGS ARE PROVIDED TO THE

CONTRACTOR AS AN AID IN DETERMINING THE EXTENT OF WORK REQUIRED FOR DEMOLITION AND TO PROVIDE GENERAL INFORMATION ABOUT EXISTING SYSTEMS. THESE DRAWINGS MAY NOT BE ACCURATE IN ALL AREAS. THE CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH EXISTING CONDITIONS AND

IS ENCOURAGED TO REVIEW FACILITY DRAWINGS PRIOR TO THE BID DATE.

D. THE OWNER SHALL HAVE FIRST SALVAGE RIGHTS TO ALL ITEMS REMOVED. IF OWNER REFUSES SALVAGE, CONTRACTOR IS RESPONSIBLE FOR DISPOSAL.

E. WHERE EXISTING WALLS ARE TO BE REMOVED, ALL ASSOCIATED ELECTRICAL EQUIPMENT SHALL BE REMOVED. DISCONNECT POWER SO THAT DEVICES AND EQUIPMENT MAY BE REMOVED WITH WALLS. SEE ARCHITECTURAL DRAWINGS FOR WALLS TO BE REMOVED. ABANDON CONCEALED CONDUITS WHERE WALLS ARE NOT REMOVED. CONCEALED CONDUITS MAY BE REUSED WHERE AVAILABLE. WHERE EXISTING CIRCUITING/CABLING IS TO BE DEMOLISHED AND NOT REUSED, REMOVE CONDUCTORS AND ASSOCIATED ACCESSIBLE RACEWAYS/CONDUIT BACK TO THE SOURCE. WHERE EXISTING ELECTRICAL CONDUITS SERVING CIRCUITS TO BE DEMOLISHED ARE EMBEDDED IN CONCRETE FLOORS OR WALLS, CONDUITS MAY BE ABANDONED IN PLACE. EXISTING CONDUCTORS SHALL BE REMOVED BACK TO SOURCE AND CONDUITS SHALL BE CUT AT SURFACE OF CONCRETE AND FILLED. EXISTING BACK BOXES AND CONDUITS REMAINING FROM DEVICES BEING REMOVED MAY BE UTILIZED FOR NEW DEVICES WHERE LOCATIONS PERMIT. REMOVE AND PATCH WHERE BOXES ARE NOT REUSED. REMOVE CONCRETE EQUIPMENT PADS THAT REMAIN, TO BE FLUSH

WITH FLOOR/GRADE.

F. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL ELECTRICAL DEMOLITION ITEMS. DISCONNECT AND REMOVE ELECTRICAL DEVICES, EQUIPMENT AND ASSOCIATED WIRING AS REQUIRED TO ACCOMMODATE NEW WORK. IF THE CONTRACTOR IS UNCLEAR REGARDING A SPECIFIC ITEM TO REMAIN OR BE REMOVED, THE

CONTRACTOR SHALL SEEK CLARIFICATION FROM THE ARCHITECT.

G. SYSTEMS SERVING ADJACENT AREAS AND ITEMS THAT REMAIN SHALL BE MAINTAINED AT ALL TIMES. MODIFY SYSTEMS AS REQUIRED THROUGHOUT CONSTRUCTION TO MAINTAIN CONTINUITY OF SERVICE. DO NOT INTERRUPT SERVICE WITHOUT OWNER'S PRIOR WRITTEN APPROVAL. LIMIT DURATION OF INTERRUPTION ONLY TO THE TIME NECESSARY FOR DISCONNECTION AND IMMEDIATE RECONNECTION. INTERRUPTION TO SERVICE DEEMED BY OWNER AS ESSENTIAL MAY REQUIRE PREMIUM TIME AND SHALL BE INCLUDED WITH THE BID.

EXTREME CARE SHALL BE TAKEN BY THE CONTRACTOR TO IDENTIFY EXISTING SYSTEM COMPONENTS ASSOCIATED WITH THESE SERVICES. APPROPRIATE METHODS OF MARKING THESE SHALL OCCUR TO ELIMINATE THE POSSIBILITY OF ACCIDENTAL INTERRUPTION. FOR CONDUIT AND CABLING THAT CAN REMAIN, PROVIDE SUPPORT AS REQUIRED. RELOCATE EXISTING JUNCTION BOXES THAT BECOME INACCESSIBLE DUE

TO NEW WORK.

H. COORDINATE DEMOLITION WITH THE WORK OF OTHER TRADES. PROVIDE TEMPORARY POWER AND LIGHTING

AS REQUIRED TO ALLOW THE WORK OF OTHER TRADES TO PROCEED.

I. PROTECT EXISTING ELECTRICAL EQUIPMENT THAT REMAINS. IF DAMAGED OR DISTURBED IN THE COURSE OF THE WORK, REMOVE DAMAGED PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL CAPACITY, QUALITY, AND

FUNCTIONALITY.

J. PATCH AND REPAIR OPENINGS IN EXISTING WALLS AND FLOORS RESULTANT FROM SPECIFIED ELECTRICAL DEMOLITION. PATCH SHALL MATCH EXISTING CONSTRUCTION, FIRE RATING, AND FINISH. SEE ARCHITECTURAL SPECIFICATIONS FOR MEANS AND METHODS. ALL DEMOED PENETRATIONS THROUGH FIRE/SMOKE RATED ASSEMBLIES SHALL BE TEMPORARILY/PERMANENTLY SEALED WITH THE PROPER RATED ASSEMBLY BY THE

END OF THE SHIFT.

K. WHERE DEMOLITION OF EQUIPMENT INVOLVES REMOVAL OF EQUIPMENT LOCATED ON CONCRETE HOUSEKEEPING PADS, PADS SHALL ALSO BE REMOVED AND FLOOR/GRADE SHALL BE FINISHED TO MATCH

ADJACENT SURFACE.

L. ALL UNLABELED ELECTRICAL DEVICES [WITH CIRCUITRY OR DEVICES MODIFIED DURING CONSTRUCTION] [THAT EXIST IN ALL ROOMS WHERE THERE IS WORK WITHIN SCOPE] SHALL BE CIRCUIT TRACED AS NEEDED WITH A

LABEL PROVIDED.

(ELECTRICAL DEMOLITION NOTES APPLY TO ALL ELECTRICAL DEMOLITION PLANS AND

ALL ELECTRICAL DEMOLITION WORK)

ELECTRICAL DEMOLITION GENERAL NOTES:

1 2 3

54 7 8 9 10 11 12 13 15 16 17

6 14 18 19 20

R

K

J

H

G

E

D

B

A

D D

E

D W D D

D

D D

D D

D D

D

D

D

DD

D

D D

D

D

D

D

D

D

D

D

D

D

D

D

D D

D D

D

D

D

D

D D D

D D DD

D

D D

D

D

DD

D

D

D

E E D

D

D

D

E

E E-103

D6

D

D

D

D

D D D D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

E

R

R

R

R D

D

R

R

R

E R R R

R

R

R R

R

RR

R

R

R

R

R

RR

R

R

R

R

R

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

DD

E R R

R

R

R

E

E

D

D

D

D

D

E-103

C6

E E

D D

E E

E E

E

E-103

D1

E E

D

D

D

D

D

E

D

D

D

D

D

D

D

D

D

D

D D D D

D

D

D

D

D

D

D D

DD

D D

DD

D

D

D

D

D

D D

DDD

D

D

D D

D DR

R

R

D

D

D

D

D

DD

D

D

D

D

D

DD

D

T-3B-1-1 D

D 38/1-6 D

T-3B-1-EC-1

D

38/1-2 D

38/1-EC-2

D

C

F F

M M

FS-1FS-1

E

D D D D D

D D

D

D

D

D D

D D

D

D

D

D

DD

D DD

D

D

D

DDD

D

D

D

D

D

D

DD

D

D D D

D D

D D

D

D

D D

D

DD

D

D D D

D D

D D

D

D

D D

E

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

A

B

C

D

2 4 5

Phase

DESIGNER OF RECORD

A/E:

STAMPCONSULTANTS

MEP: STRUCTURAL:

6"

6"

6"

6"

O N

E E

IG

H

T H

I N

C H

O

N E

F O

O T

1/

8"

'-…

This is the start of the file's text. The full file is on GovTribe.