Renovate 3B Hazardous Material Report.pdf
PDF 3 MB Posted
- Attached to
- Z2DA--657A5-23-110, Renovate 3B for Patient Privacy and Intensive Care Unit, (VA-25-00018450)
- Solicitation number
- 36C25525R0015
About this file
This is a hazardous material testing report for the renovation project of Patient Ward 3B at the Marion VA Medical Center in Marion, Illinois, conducted by Castle Hill Associates in December 2023. The report is part of the 60% Design Development submission for VA Contract #36C25523R0096.
The testing identified two types of asbestos-containing materials: exterior stucco wall coating on all floors and pipe insulation in inaccessible wall chases behind plaster walls. Lead-based paint was found on metal door frames in Stairwells 1 and 2 and Rooms 332 and 325A. Universal waste consisting of 8 exit light fixture batteries was identified in stairwells and hallways. The report includes detailed laboratory analysis from Eurofins EPK Built Environment Testing showing no asbestos detected in 15 additional material samples tested. The inspector recommends that asbestos materials must be removed if disturbed during renovation, lead-painted components must be properly handled if disturbed, and universal wastes must be disposed of according to EPA requirements if removed. All testing was conducted by Brett Brumbaugh, a certified Illinois Asbestos Inspector and EPA Lead Paint Risk Assessor.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Hazardous Material Report Renovate Patient Ward 3B for Patient Privacy and Intensive Care Marion VA Medical Center VA Contract # 36C25523R0096 Marion, Ill.
H VA MARI 23100
60% Design Development – Submission February 02, 2024
ASBESTOS & HAZMAT TESTING REPORT FOR 30% SD SUBMISSION
MARION, IL VAMC - RENOVATE 3B FOR PATIENT PRIVACY AND ICU
VA PROJECT 589A5-17-130
DECEMBER 2023
Date: January 2, 2024
Items: Summary Results of Asbestos/HazMat Survey, Visual Inspection, Lab Results
Inspector: Brett Brumbaugh, Castle Hill Associates
BUILDING 1 – THIRD FLOOR 3B VALIANT WING – MEDICAL SURGICAL ROOMS
ASBESTOS MATERIALS IN WORK AREA
Asbestos Containing Materials Locations Quantity
Exterior stucco wall coating Exterior of building – all floors n/a
Pipe insulation on steam & water lines Inaccessible wall chases behind plaster walls n/a
LEAD-BASED PAINT & LEAD COMPONENTS
LEAD PAINTED/CONTAING COMPONENT LOCATIONS
Metal door frames (original frames, flush with plaster walls)
Stairwells 1 and 2; Rooms 332 and 325A
UNIVERSAL WASTES
UNIVERSAL WASTE MATERIAL Locations Quantity
Exit light fixture batteries Stairwells and hallways 8 fixtures
ASBESTOS & HAZMAT COST ESTIMATE
Estimator: Brett Brumbaugh
Notes: Based on 2024/25 construction and bidding
EXCLUDES:
• Overtime or shift work.
INCLUDES:
• Bonds, insurance, contractor overhead and profit
• Prevailing wage rates for Marion, IL
Cost Index: Marion, IL
ASBESTOS & HAZMAT TESTING REPORT
LOCATION:
MARION VA MEDICAL CENTER
2401 W. MAIN ST.
MARION, IL 62959
PROJECT:
RENOVATE 3B FOR PATIENT PRIVACY AND ICU
BUILDING 1 – 3rd FLOOR VALIANT
VA PROJECT #: 589A5-17-130
SAMPLING DATE:
DECEMBER 18, 2023
CONSULTANT:
CASTLE HILL ASSOCIATES, LLC
1197 FARNSWORTH RD., UNIT E
WATERVILLE, OH 43066
567-952-0212 www.CASTLEHILLASSOCIATES.com http://www.castlehillassociates.com/
TABLE OF CONTENTS
• ASBESTOS & LEAD PAINT SAMPLING SUMMARY
• ABESTOS BULK SAMPLING DESCRIPTIONS AND LAB RESULTS
• LEAD SAMPLING DESCRIPTIONS AND RESULTS
• ASBESTOS & LEAD COMPONENT PHOTOS
• ASBESTOS LABORATORY REPORT
• WORK AREA EXTENT DRAWING
• INSPECTOR & ASBESTOS LABORATORY CERTIFICATION
ASBESTOS & HAZMAT TESTING SUMMARY
On December 18, 2023, Brett Brumbaugh performed asbestos and lead-based paint testing along with an inventory of universal wastes in the on the 3rd Floor of Building 1 (3B Medical Surgical Area) at the Marion VA Medical Center in Marion, IL in preparation of the renovation for Patient Privacy and ICU.
As part of this inspection, the previous asbestos testing conducted by the VA in 2010 in was utilized to develop this report in addition to the samples collected during this inspection.
ASBESTOS INSPECTION FINDINGS
As a result of this inspection, testing, and laboratory analyses, it has been determined that asbestos is present in Building 58 in the renovation area as follows:
Asbestos Containing Materials Locations Quantity
Exterior stucco wall coating Exterior of building – all floors n/a
Pipe insulation on steam & water lines Inaccessible wall chases behind plaster walls n/a
LEAD-BASED PAINT & LEAD COMPONENT FINDINGS
There was lead-based paint and lead coated components identified in the renovation areas as follows:
LEAD PAINTED/CONTAING COMPONENT LOCATIONS
Metal door frames (original frames, flush with plaster walls)
Stairwells 1 and 2; Rooms 332 and 325A
UNIVERSAL WASTES FINDINGS
There were universal wastes identified in the renovation areas as follows:
UNIVERSAL WASTE MATERIAL Locations Quantity
Exit light fixture batteries Stairwells and hallways 8 fixtures
CONCLUSIONS/RECOMMENDATIONS
ASBESTOS: The asbestos containing materials identified in the renovation areas must be removed if they will be disturbed as part of the renovation activities. If no disturbance is planned, they can be left in-place indefinitely until removal is required prior to demolition. All removal must be conducted by an Illinois licensed Asbestos Contractor.
LEAD-BASED PAINT: The building components coated with lead-based paint or lead glazing in the renovation areas must be properly handled if they will be disturbed as part of the renovation activities. If no disturbance is planned, they can be left in-place indefinitely.
UNIVERSAL WASTES: The identified Universal Wastes are not required to be removed prior to renovation, however if they are removed then they must be handled, transported, and disposed/recycled in an EPA approved facility by persons with proper training in the handling of Universal Wastes.
Inspector, Brett L. Brumbaugh, REPA, CESCO State of Illinois Asbestos Inspector - License # 100-09972 EPA Lead Paint Risk Assessor - EPA License # LBP-R-I216003-2
ASBESTOS TESTING DATA
Site: Marion VA Medical Center - Marion, IL
Building: Building 1 – 3rd Floor 3B
Project: 589A5-17-130
Sampling Date: 12/18/2023
Inspector: Brett L. Brumbaugh
Certification: Illinois Asbestos Inspector
Analysis Dates: January 2, 2024
Laboratory: Eurofins - Naperville, IL
SAMPLE
ROOM MATERIAL ASBESTOS CONTENT
1 304 Floor leveling (gray) No Asbestos Detected
2 318 Floor leveling (gray) No Asbestos Detected
3 304 12" tan floor tile and mastic No Asbestos Detected
4 322 12" tan floor tile and mastic No Asbestos Detected
5 Hall at 316 Tan cove base and mastic No Asbestos Detected
6 Hall at 307 12" tan floor tile and mastic No Asbestos Detected
7 304 Sink caulking No Asbestos Detected
8 319 Sink caulking No Asbestos Detected
9 319 Ceramic wall tile grout No Asbestos Detected
10 304-1 Ceramic wall tile grout No Asbestos Detected
11 319 Ceramic wall tile adhesive No Asbestos Detected
12 304-1 Ceramic wall tile adhesive No Asbestos Detected
13 Chase @ 323 Gray duct seam sealant No Asbestos Detected
14 304 Drywall mud No Asbestos Detected
15 306 Drywall mud No Asbestos Detected
LEAD XRF TESTING DATA
PHOTOGRAPHS OF ASBESTOS MATERIALS
Photo A1 Exterior stucco wall coating
Photo A2
Photo A3
PHOTOGRAPHS OF LEAD-PAINT COMPONENTS
Photo L1 Lead-based paint on stairwell door frame
Photo L2 Lead-based paint on original flush mounted door frame
Photo L3 Lead-based paint on original flush mounted door frame
ASBESTOS LAB REPORT
Approved by:
Cluster Leader Dr. Kamash Pillai
Report for:
Mr. Brett Brumbaugh, REPA Castle Hill Associates PO Box 283 Waterville, OH 43566
Regarding:
Eurofins EPK Built Environment Testing, LLC Project: Marion, IL VAMC; Renovate 3B
EML ID: 3491707
All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. The results relate only to the samples as received and tested. The results include an inherent uncertainty of measurement associated with estimating percentages by polarized light microscopy. Measurement uncertainty data for sample results with >1% asbestos concentration can be provided when requested.
Eurofins EPK Built Environment Testing, LLC ("the Company"), a member of the Eurofins Built Environment Testing group of companies, shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results. In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor.
Dates of Analysis:
Asbestos PLM: 01-02-2024
Service SOPs: Asbestos PLM (EPA 40CFR App E to Sub E of Part 763 & EPA METHOD 600/R-93-116, SOP EM-AS-S-1267) NVLAP Lab Code 600194-0
EMLab ID: 3491707, Page 1 of 5Eurofins EPK Built Environment Testing, LLC
Eurofins EPK Built Environment Testing, LLC 1815 West Diehl Road, Suite 800, Naperville, IL 60563
(866) 871-1984 www.eurofinsus.com/Built Client: Castle Hill Associates C/O: Mr. Brett Brumbaugh, REPA Re: Marion, IL VAMC; Renovate 3B
Date of Sampling: 12-18-2023 Date of Receipt: 12-27-2023 Date of Report: 01-02-2024
ASBESTOS PLM REPORT
Total Samples Submitted: 15 Total Samples Analyzed: 15
Total Samples with Layer Asbestos Content > 1%: 0
Location: 1, Floor Leveling Lab ID-Version‡: 17035081-1
Sample Layers Asbestos Content Beige Leveling Compound ND
Sample Composite Homogeneity: Poor
Location: 2, Floor Leveling Lab ID-Version‡: 17035082-1
Sample Layers Asbestos Content Beige Leveling Compound ND
Sample Composite Homogeneity: Poor
Location: 3, 12" Tan FT & Mastic Lab ID-Version‡: 17035083-1
Sample Layers Asbestos Content Beige Floor Tile ND White Floor Tile ND
Tan Mastic ND Sample Composite Homogeneity: Moderate
Location: 4, 12" Tan FT & Mastic Lab ID-Version‡: 17035084-1
Sample Layers Asbestos Content Beige Floor Tile ND White Floor Tile ND
Tan Mastic ND Sample Composite Homogeneity: Moderate
EMLab ID: 3491707, Page 2 of 5Eurofins EPK Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
(866) 871-1984 www.eurofinsus.com/Built Client: Castle Hill Associates C/O: Mr. Brett Brumbaugh, REPA Re: Marion, IL VAMC; Renovate 3B
Date of Sampling: 12-18-2023 Date of Receipt: 12-27-2023 Date of Report: 01-02-2024
ASBESTOS PLM REPORT
Location: 5, Tan Cove Base Lab ID-Version‡: 17035085-1
Sample Layers Asbestos Content Tan Baseboard ND Beige Mastic ND
Beige Compound ND Tan Paper ND Composite Non-Asbestos Content: 8% Cellulose Sample Composite Homogeneity: Good
Location: 6, Tan Cove Base Lab ID-Version‡: 17035086-1
Sample Layers Asbestos Content Tan Baseboard ND Beige Mastic ND
Tan Paper ND Composite Non-Asbestos Content: 8% Cellulose Sample Composite Homogeneity: Good
Location: 7, Sink Caulk Lab ID-Version‡: 17035087-1
Sample Layers Asbestos Content White Caulk ND
Sample Composite Homogeneity: Good
Location: 8, Sink Caulk Lab ID-Version‡: 17035088-1
Sample Layers Asbestos Content White Caulk ND
Sample Composite Homogeneity: Good
EMLab ID: 3491707, Page 3 of 5Eurofins EPK Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/Built Client: Castle Hill Associates C/O: Mr. Brett Brumbaugh, REPA Re: Marion, IL VAMC; Renovate 3B
Date of Sampling: 12-18-2023 Date of Receipt: 12-27-2023 Date of Report: 01-02-2024
ASBESTOS PLM REPORT
Location: 9, Ceramic Tile Grout Lab ID-Version‡: 17035089-1
Sample Layers Asbestos Content White Grout ND
Sample Composite Homogeneity: Good
Location: 10, Ceramic Tile Grout Lab ID-Version‡: 17035090-1
Sample Layers Asbestos Content White Grout ND
Sample Composite Homogeneity: Good
Location: 11, Ceramic Tile Glue Lab ID-Version‡: 17035091-1
Sample Layers Asbestos Content Tan Glue ND Sample Composite Homogeneity: Good
Location: 12, Ceramic Tile Glue Lab ID-Version‡: 17035092-1
Sample Layers Asbestos Content Tan Glue ND Sample Composite Homogeneity: Good
EMLab ID: 3491707, Page 4 of 5Eurofins EPK Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/Built Client: Castle Hill Associates C/O: Mr. Brett Brumbaugh, REPA Re: Marion, IL VAMC; Renovate 3B
Date of Sampling: 12-18-2023 Date of Receipt: 12-27-2023 Date of Report: 01-02-2024
ASBESTOS PLM REPORT
Location: 13, Gray Duct Sealant Lab ID-Version‡: 17035093-1
Sample Layers Asbestos Content Gray Sealant ND
Sample Composite Homogeneity: Good
Location: 14, Drywall Mud Lab ID-Version‡: 17035094-1
Sample Layers Asbestos Content White Mud ND
Sample Composite Homogeneity: Good
Location: 15, Drywall Mud Lab ID-Version‡: 17035095-1
Sample Layers Asbestos Content White Mud ND
Sample Composite Homogeneity: Good
EMLab ID: 3491707, Page 5 of 5Eurofins EPK Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
WORK AREA EXTENT DRAWING
3RD FLOOR – BUILDING 1
3B VALIANT WING
INSPECTOR & LAB CERTIFICATIONS
INSPECTOR CERTIFICATIONS
LABORATORY CERTIFICATIONS