589A5-22-106_Replace_HVAC_Bldg_4_Drawings_05-15-24_3 of 3.pdf

PDF 24 MB Posted

Attached to
589A5-22-106, REPLACE BLDG4 HVAC
Solicitation number
36C25524R0114_1
Issued by

About this file

This document is a 3-part set of construction drawings related to a federal solicitation for replacing the HVAC system in Building 4 at the Colmery-O'Neil VA Medical Center in Topeka, Kansas.

The solicitation is a 100% Service-Disabled Veteran-Owned Small Business (SDVOSB) set-aside for construction services to install a new HVAC system and controls in Building 4. The construction services will be performed in phases over a 540-calendar day period of performance. The North American Industry Classification System (NAICS) code is 236220, Commercial and Institutional Building Construction, with a $45 million size standard. Contractors must be certified in the SBA VetCert program and registered in SAM.gov to be eligible for award. There will be a site visit on September 12, 2024, and questions are due by September 13, 2024. The solicitation period has been shortened to meet a 2024 contract award deadline.

View the file

Other files

Show all 24

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DN

UP

UP

A

B

E

C

D1

D

F

G

H

J

1 2 3 4 5 6 7 8

9 10 1211

B0-C1

B09B09A

B09B A0-S1

A11

A2E A01E

B06

B07E

B08F

B08

B07

A01B05 B04 B03 A02

B10

4-AHU-B1

4" CHWS

4" CHWR

KEY PLAN

SEE SHEET

4-MP-1B2

SEE SHEET

4-MP-1B2

TU-4 TU-4 TU-4 TU-4 TU-4

TU-4TU-4

2-1/2" HWS

2-1/2" HWR

2-1/2" HWS

2-1/2" HWR

4" CHWS

4" CHWR

2-1/2" HWS

2-1/2" HWR

4" CHWS

4" CHWR

4-CHP-1

4-CHP-2

1-1/2" CHWS

1-1/2" CHWR

UP

9 11

D

F

7 8 10

E

MECHANICAL ROOM B10

SCALE: 1/8" = 1'-0"

FOR CONTINUATION

SEE BASEMENT FLOOR PLAN THIS

SHEET

EX-4-FC-1

SEE C7 PLAN

THIS SHEET FOR

CONTINUATION

SEE MECHANICAL ROOM B10;

DETAIL C7 THIS SHEET

5"

5"

1-1/2" CHWS

& CHWR

5" CHWS

& CHWR

RETURN PIPING ELEVATION DETAIL

NO SCALE

2-1/2"HWR BRANCH PIPE2-1/2"HWR BRANCH PIPE

3" HWR MAIN

EX-CHWS

EX-CHWR

4-HWP-1

4-HWP-2

4-HE-1

4-AS-1

EXIST. LPS

EXIST. CR

1- 1/

2" C

R

4" MPS

2" CR

4-EXP-1

CHWS

CHWR

3" 3"

EX-CR

EX-CR

EX-MPS

EXIST. LPS

EXIST. CR

EXIST. MPS

EXIST. CR

SEE DETAIL D-7

THIS SHEET

2"CR

www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

05-15-2024

CONSTRUCTION DOCUMENTS

DESIGN REPLACE HVAC &

ASSOCIATED COMPONENTS

589A5-22-106

COLMERY-O'NEIL VAMC

2200 SW GAGE BLVD. - TOPEKA, KS 66622

FULLY SPRINKLERED

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

4-MP-1B1

MECHANICAL PIPING REVISED PLAN

BASEMENT FLOOR B WING

KEYED PLAN NOTES

1. 2-1/2" HEATING WATER SUPPLY AND RETURN TO FIRST FLOOR.

2. 4" CHILLED WATER SUPPLY AND RETURN TO SECOND FLOOR.

3. CONNECT 5" CHILLED WATER SUPPLY AND RETURN TO

EXISTING NEAR THIS POINT.

4. SET NEW PUMPS ON EXISTING CONCRETE BASES. MODIFY

BASES AS REQUIRED FOR NEW PUMPS.

5. NEW HEAT EXCHANGER TO BE MOUNTED ON WALL WITH

STEEL BRACKETS IN LOCATION OF DEMO'D HEAT

EXCHANGER AS REQUIRED. SEE DETAILS ON SHEET 4-MG-005.

6. NEW PUMPS TO BE MOUNTED ON TOP OF EXISTING CHILLER

CONCRETE PAD.

7. 4"MPS UP TO 1ST FLOOR.

8. 1-1/4"MPS TO AHU-B-1 PREHEAT COIL.

9. 2" CR UP TO 1ST FLOOR.

10. 3/4" CR FROM STEAM HUMIDIFIER AND 1"CR FROM HEATING

COIL.

11. 1"LPS TO STEAM HUMIDIFIER.

12. FROM CHILLER PLANT.

13. CONNECT NEW 1-1/4" CHWS&R TO EXISTING.

14. RECONNECT EXISTING.

15. 3"HWS/R AND 1-1/4"CHWS/R

16. PIPE 1-1/4" COPPER CONDENSATE DRAIN FROM AHU TO FLOOR

DRAIN AS REQUIRED. SEE DETAIL D3 ON DRAWING 4-MG-003.

17. CORE DRILL HOLES. SEE DETAILS F1 AND F7 ON SHEET

4-MG-004. COORDINATE LOCATION WITH DUCTWORK ON

FLOORS ABOVE.

18. EXISTING CHWS/R PIPING.

19. CONNECT NEW 2"CR TO EXISTING AS REQUIRED.

GENERAL NOTES:

1. ALL TERMINAL UNITS TO BE PIPED WITH SIZE SHOWN ON

PIPING SCHEDULE THIS SHEET AND TWO-WAY VALVES. SEE

DETAIL B8 ON DRAWING 4-MG-003.

2. PIPING SHOWN FOR CLARITY. CONTRACTOR TO MOUNT

PIPING STACKED AGAINST ONE SIDE OF CORRIDOR AS HIGH

AS POSSIBLE; TYPICAL. COORDINATE WITH DUCTWORK AND

ELECTRICAL/TECHNOLOGY.

A

B

E

C

D1

D

F

G

H

J

16 17 18 19 20 21 22 23 24 2512 13 14 15

C0-C1A0-C1

C17 C17A

C17B

C17F

C18

C19E

C15

C15B

C15A

C19

C23 C22

A14

A24 A24A

A24B

A13

A1 2F

A01A

A01

C21 C20

A0-E9 A0-E10

4" CHWS

4" CHWR

4" CHWS

4" CHWR

KEY PLAN

SEE SHEET

4-MP-1B1

SEE SHEET

4-MH-1B1

TU-4 TU-4 TU-4

TU-4

TU-4 TU-4

TU-4

TU-4

TU-4

TU-4

2" HWS

2" HWR

2-1/2" HWS

2-1/2" HWR

2-1/2" HWS

2-1/2" HWR

www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

05-15-2024

CONSTRUCTION DOCUMENTS

DESIGN REPLACE HVAC &

ASSOCIATED COMPONENTS

589A5-22-106

COLMERY-O'NEIL VAMC

2200 SW GAGE BLVD. - TOPEKA, KS 66622

FULLY SPRINKLERED

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

4-MP-1B2

MECHANICAL PIPING REVISED PLAN

BASEMENT FLOOR A & C WINGS

KEYED PLAN NOTES

1. 2" HWS/R TO FIRST FLOOR.

2. 4"CHWS/R TO SECOND FLOOR.

3. 1" CHWS/R UP TO FIRST FLOOR.

4. CORE DRILL HOLES. SEE DETAILS F1 AND F7 ON SHEET

4-MG-004. COORDINATE LOCATION WITH DUCTWORK ON

FLOORS ABOVE.

GENERAL NOTES:

1. ALL TERMINAL UNITS TO BE PIPED WITH SIZE SHOWN ON

PIPING SCHEDULE THIS SHEET. SEE DETAIL B8 ON DRAWING

4-MG-003.

2. PIPING SHOWN FOR CLARITY. CONTRACTOR TO MOUNT

PIPING STACKED AGAINST ONE SIDE OF CORRIDOR AS HIGH

A

B

E

C

D1

D

F

G

H

J

1 2 3 4 5 6 7 8 9 10 1211

A1-S1

A102

B134

A102EA103E

A103

A1-C4

B112

B104B105

B1 -C

B131

B108

B132

B132A

B130

B129

B129A

B128

B106

B107

B125F

B1-S3

B125

B125A

B126

B126A

B127

B127A

B133B123

B115E

B122

B113

B114

B115

B121E

B116B116AB117B118

B121

B121A

B120

B109

B119

B119A

B110

B1-C1

B1 -C

B1-C3

3/4" HWS

KEY PLAN

SEE SHEET

4-MP-114

SEE SHEET

4-MP-114

TU-7

TU-6

TU-6

TU-7 TU-4TU-4

TU-4

TU-4 TU-6 TU-5 TU-6 TU-6

TU-5TU-5

TU-5TU-5

TU-7TU-7

TU-7TU-7

TU-4

TU-5

TU-6

TU-7

TU-8

TU-8 TU-8

2" H

W S

2" H

W R

3/4" HWR

1-1/2" HWS

1-1/2" HWR

3/ 4"

H W

S

3/ 4"

H W

R

1-1/2" HWS

1-1/2" HWR

1" HWS

1" HWR

3/4" HWS

3/4" HWR

3/ 4"

H W

S

3/ 4"

H W

R

3/ 4"

H W

S

3/ 4"

H W

R

3/ 4"

H W

S

3/ 4"

H W

R

1" HWS

1" HWR

3/4"HWS/R

2" HWR

1-1/2" HWS

1-1/2" HWR

1-1/2" HWR

3/4" HWR

1" HWS

3/4" HWS

WALL

2"HWS

A HWS/R PIPING DETAIL

NO SCALE

www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

05-15-2024

CONSTRUCTION DOCUMENTS

DESIGN REPLACE HVAC &

ASSOCIATED COMPONENTS

589A5-22-106

COLMERY-O'NEIL VAMC

2200 SW GAGE BLVD. - TOPEKA, KS 66622

FULLY SPRINKLERED

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

4-MP-113

MECHANICAL PIPING REVISED PLAN

FIRST FLOOR B WING

KEYED PLAN NOTES

1. 2-1/2" HEATING WATER SUPPLY UP FROM BASEMENT AND 1-1/2"

HEATING WATER SUPPLY UP TO SECOND FLOOR.

2. 2-1/2" HEATING WATER RETURN DOWN TO BASEMENT AND

1-1/2" HEATING WATER RETURN DOWN FROM SECOND FLOOR.

3. 4" CHILLED WATER SUPPLY AND RETURN TO BASEMENT AND

SECOND FLOOR.

4. 4" MPS TO BASEMENT AND SECOND FLOOR. 2" CR TO

BASEMENT AND SECOND FLOOR.

5. CORE DRILL HOLES. SEE DETAILS F1 AND F7 ON SHEET

4-MG-004. COORDINATE LOCATION WITH DUCTWORK ON

FLOORS ABOVE.

6. SEE DETAIL 'A' THIS SHEET FOR PIPING DETAIL.

7. FLOOR SHUTOFF VALVES. PHASE 1 WORK TO STOP AT THESE

VALVES.

GENERAL NOTES:

1. ALL TERMINAL UNITS TO BE PIPED WITH SIZE SHOWN ON

PIPING SCHEDULE THIS SHEET. SEE DETAIL B8 ON DRAWING

4-MG-003.

2. PIPING SHOWN FOR CLARITY. CONTRACTOR TO MOUNT

PIPING STACKED AGAINST ONE SIDE OF CORRIDOR AS HIGH

A101

A138A

A136

A139

A136A

A137

A141

A143

A140

A144 A145

A138

A101A

C1-3

C163E C163

C164 C165

C166

C167

C168C169C169AC170

C148

C149

C150

C151

C153

C154 C155

C156

C157

C158

C1

F

C162

C161C160

C142A

C145

C1

B

C146

C1

A

C143

C143A C143B

C142

C144

C175A C174A

C172

C171

C170E

C152

C173

C174C175

C147

C1

C

C1-C1A1-C2

A1-C1

A1 -C

C1 -C

C1

A

C163A

A1-E9 C1-S2

A1

A1

A1-C4

A103 A102

B134

A103E

A102E A101

UP

DN

A

B

E

C

D1

D

F

G

H

J

10 16 17 18 19 20 21 22 23 24 251211 13 14 159

KEY PLAN

SEE SHEET

4-MP-113

SEE SHEET

4-MP-113

TU-9

TU-10

TU-6

TU-10

TU-4

TU-8

TU-6

TU-7

TU-6

TU-5

TU-5

TU-5

TU-7TU-7

TU-5

TU-6

TU-5

TU-4

TU-5

TU-4

TU-6 TU-7

TU-6TU-4TU-5

TU-4

TU-6

TU-7 TU-7 TU-7

TU-4

3/ 4"

H W

S

3/ 4"

H W

R

3/4" HWS

3/4" HWR1" HWS

1" HWR

3/ 4"

H W

S

3/ 4"

H W

R

1- 1/

2" H

W S

1- 1/

2" H

W R

3/4" HWS

3/4" HWR

3/4" HWS

3/4" HWR

1-1/2" HWS

1-1/2" HWR

1" H

W S

1" H

W R

3/ 4"

H W

S

3/ 4"

H W

R

3/ 4"

H W

S

3/ 4"

H W

R

1" H

W S

1" H

W R

3/ 4"

H W

S

3/ 4"

H W

R

3/4" HWS

3/4" HWR

3/4" HWS

3/4" HWR

3/4" HWS

3/4" HWR

EX-4-HV-3

TU-4

3/ 4"

H W

S 3/

4" H

W R

1" C

H W

S 1"

C H

W R

NO BULLHEAD TEES

A HWR CONNECTION

NO SCALE

HWR BRANCH

HWR BRANCH

HWR COMMON

www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

05-15-2024

CONSTRUCTION DOCUMENTS

DESIGN REPLACE HVAC &

ASSOCIATED COMPONENTS

589A5-22-106

COLMERY-O'NEIL VAMC

2200 SW GAGE BLVD. - TOPEKA, KS 66622

FULLY SPRINKLERED

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

4-MP-114

MECHANICAL PIPING REVISED PLAN

FIRST FLOOR A & C WINGS

KEYED PLAN NOTES

1. 2" HEATING WATER SUPPLY UP FROM BASEMENT AND 1-1/2"

HEATING WATER SUPPLY UP TO SECOND FLOOR.

2. 2" HEATING WATER RETURN DOWN TO BASEMENT AND 1-1/2"

HEATING WATER RETURN DOWN FROM SECOND FLOOR.

3. 4" CHILLED WATER SUPPLY AND RETURN TO BASEMENT AND

SECOND FLOOR.

4. 1" CHILLED WATER SUPPLY AND RETURN DOWN TO

BASEMENT. CORE DRILL FLOOR TIGHT TO WALL IN CORNER.

FIELD VERIFY BEST LOCATION.

5. CONNECT 1" CHILLED WATER SUPPLY AND RETURN TO

EXISTING 1" CHILLED WATER SUPPLY AND RETURN FOR

EXISTING AIR HANDLER.

6. SEE DETAIL 'A' THIS SHEET FOR HWR CONNECTION.

7. CORE DRILL HOLES. SEE DETAILS F1 AND F7 ON SHEET

4-MG-004. COORDINATE LOCATION WITH DUCTWORK ON

FLOORS ABOVE.

8. FLOOR SHUTOFF VALVE. PHASE 1 WORK TO STOP AT THESE

VALVES.

9. EXISTING 1"CHWS/R

GENERAL NOTES:

1. ALL TERMINAL UNITS TO BE PIPED WITH SIZE SHOWN ON

PIPING SCHEDULE THIS SHEET. SEE DETAIL B8 ON DRAWING

4-MG-003.

2. PIPING SHOWN FOR CLARITY. CONTRACTOR TO MOUNT

PIPING STACKED AGAINST ONE SIDE OF CORRIDOR AS HIGH

A

B

E

C

D1

D

F

G

H

J

1 2 3 4 5 6 7 8 9 10 1211

A2-S1 B231

A234 A234A

A202EA203E

B204B205B206

B232

B230

B225F

B2-C1

B225

B225A

B223

B222

B221E

B215E

B2-C3

B213

B214

B215

B216AB217B218

B226A

B226

B209B208

B207

A203

B232A

B233

B229A

B229

B227A

B227 B228

B2-S3

B218A

B219

B220A

B220

B221

B216 A202

B210B212

B2 -C

B2 -C

KEY PLAN

SEE SHEET

4-MP-126

SEE SHEET

4-MP-126

TU-7

TU-7 TU-5

TU-5TU-5TU-6

TU-5

TU-5

TU-7

TU-7TU-7

TU-7

TU-4 TU-6 TU-5 TU-5 TU-6

TU-5TU-5TU-4

TU-4

TU-4

TU-7

TU-8

TU-8 TU-8

TU-5

1- 1/

2" H

W S

1- 1/

2" H

W R3"

C H

W S

3" C

H W

R 3/ 4"

H W

S 3/

4" H

W R

1" H

W S

1" HWR

1-1/2" HWS

1-1/2" HWR

3/4" HWS

3/4" HWR

3/4" HWS

3/4" HWR

3/ 4"

H W

S

3/ 4"

H W

R

3/ 4"

H W

S

3/ 4"

H W

R

3/ 4"

H W

S

3/ 4"

H W

R

3/4" HWS

3/4" HWR

4"

C H

W S

4" C

H W

R

2- 1/

2" C

H W

S 2-

1/ 2"

C H

W R

4" MPS

2" C

R

3" MPS

2" CR

3" M

PS

1" HWR

3" MPS

2" CR

WALL

A PIPING DETAIL

NO SCALE

1- 1/

2" H

W S

1- 1/

2" H

W R

4" M

PS

2"

C R

4" C

H W

S 4"

C H

W R

2"CR

4"MPS

2-1/2"CHWS

2-1/2"CHWR

1-1/2"HWS

1-1/2"HWR

3"CHWS

3"CHWR

1"HWS

1"HWR

1" H

W S

1" H

W R www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

05-15-2024

CONSTRUCTION DOCUMENTS

DESIGN REPLACE HVAC &

ASSOCIATED COMPONENTS

589A5-22-106

COLMERY-O'NEIL VAMC

2200 SW GAGE BLVD. - TOPEKA, KS 66622

FULLY SPRINKLERED

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

4-MP-125

MECHANICAL PIPING REVISED PLAN

SECOND FLOOR B WING

KEYED PLAN NOTES

1. 1-1/2" HEATING WATER SUPPLY AND RETURN TO FIRST FLOOR.

2. 4" CHILLED WATER SUPPLY AND RETURN TO BASEMENT

FLOOR.

3. 3" CHILLED WATER SUPPLY AND RETURN TO RTU-12 ON ROOF.

SEE DRAWING 4-MP-1R7.

4. 2-1/2" CHILLED WATER SUPPLY AND RETURN TO RTU-22 ON

ROOF. SEE DRAWING 4-MP-1R7.

5. 4" MPS DOWN TO 1ST FLOOR AND 3" MPS AND 2"CR UP TO

RTU-12 ON ROOF. 2" LPS TO FIRST FLOOR AND 1" MPS UP TO

RTU-12 ON ROOF.

6. 2"MPS AND 1-1/2" CR UP TO RTU-22 ON ROOF.

7. CORE DRILL HOLES. SEE DETAILS 'F1' AND 'F7' ON SHEET

4-MG-004. COORDINATE LOCATION WITH DUCTWORK AS

REQUIRED.

8. FLOOR SHUTOFF VALVE. PHASE 1 WORK TO STOP AT THESE

VALVES.

9. SEE DETAIL 'A' THIS SHEET FOR PIPING DETAIL.

10. PHASE 4 WORK.

11. PHASE 4 TO STOP AT THESE VALVES.

GENERAL NOTES:

1. ALL TERMINAL UNITS TO BE PIPED WITH SIZE SHOWN ON

PIPING SCHEDULE THIS SHEET. SEE DETAIL B8 ON DRAWING

4-MG-003.

2. PIPING SHOWN FOR CLARITY. CONTRACTOR TO MOUNT

PIPING STACKED AGAINST ONE SIDE OF CORRIDOR AS HIGH

B

E

C

D1

D

F

G

H

J

9 10 16 17 18 19 20 21 22 23 24 251211 13 14 15

A201

A236

A271

A234F A238

A269 C268 C267

C265

C239A

C240

C239

C249

C250

C256 C255A

C254

C253A

C253

C263 C255

C262

C256E

C251E

C257

C258

C2-S2

C247

C243A

C243

C242

C246A

C246

C2

F

C247G

C244A

C264

C2-C1

C2 -C

C252

C241

C2-C3

C251AC251

C244

C247A

A270

C266

C261 C2

-C

C259

A2-9 A0-E10

2- 1/

2" C

H W

S 2-

1/ 2"

C H

W R

KEY PLAN

SEE SHEET

4-MP-125

SEE SHEET

4-MP-125

TU-5

TU-6

TU-5 TU-5 TU-6

TU-6 TU-4 TU-5

TU-5 TU-6 TU-7

TU-6TU-6TU-5

TU-4

TU-4

TU-5 TU-5

TU-6

TU-7TU-7

TU-7

TU-7

TU-7

TU-7TU-9

TU-4

TU-5

3/4" HWS

3/4" HWR

1- 1/

2" H

W S

1- 1/

2" H

W R

3/ 4"

H W

S

3/ 4"

H W

R

3/ 4"

H W

S

3/ 4"

H W

R

1" HWS

1" H

W R

3/4" HWS

3/4" HWR

3/4" HWS

3/4" HWR

3/4" HWS

3/4" HWR

3/4" HWS

3/4" HWR

3/ 4"

H W

S

3/ 4"

H W

R

1-1/2" HWS

1-1/2" HWR

3/ 4"

H W

S 3/

4" H

W R 1

2- 1/

2" C

H W

S 2-

1/ 2"

C H

W R

4" C

H W

S 4"

C H

W R

2" M

PS

1"

C R

2" M

PS

1" C

R

TU-4

2" CR

3" MPS

2" CR

3" MPS

WALL

A PIPING DETAIL

NO SCALE

1- 1/

2" H

W S

1- 1/

2" H

W R

4" C

H W

S 4"

C H

W R

2-1/2"CHWR

2-1/2"CHWS

1-1/2"HWS

1-1/2"HWR

2- 1/

2" H

W S

2- 1/

2" H

W R

1"HWS

1"HWR

10 2

12 3 www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

05-15-2024

CONSTRUCTION DOCUMENTS

DESIGN REPLACE HVAC &

ASSOCIATED COMPONENTS

589A5-22-106

COLMERY-O'NEIL VAMC

2200 SW GAGE BLVD. - TOPEKA, KS 66622

FULLY SPRINKLERED

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

4-MP-126

MECHANICAL PIPING REVISED PLAN

SECOND FLOOR A & C WINGS

KEYED PLAN NOTES

1. 1-1/2" HEATING WATER SUPPLY AND RETURN TO FIRST FLOOR.

2. 4" CHILLED WATER SUPPLY AND RETURN TO FIRST FLOOR.

3. 2-1/2" CHILLED WATER SUPPLY AND RETURN TO RTU-11 ON

ROOF. SEE DRAWING 4-MP-1R8.

4. 2-1/2" CHILLED WATER SUPPLY AND RETURN TO RTU-21 ON

ROOF. SEE DRAWING 4-MP-1R8.

5. 2" MPS AND 1" CR UP TO RTU-21 ON ROOF.

6. 2" MPS AND 1" CR UP TO RTU-11 ON ROOF.

7. CORE DRILL HOLES. SEE DETAILS F1 AND F7 ON SHEET

4-MG-004. COORDINATE LOCATION WITH DUCTWORK AS

REQUIRED.

8. FLOOR SHUTOFF VALVE. PHASE 1 WORK TO STOP AT THESE

VALVES.

9. SEE DETAIL 'A' THIS SHEET FOR PIPING.

10. WING SHUT OFF VALVE. PHASE 1 WORK TO STOP AT THESE

VALVES.

11. PHASE 3 WORK TO STOP AT THESE VALVES.

12. PHASE 3 WORK, UNLESS NOTED OTHERWISE.

GENERAL NOTES:

1. ALL TERMINAL UNITS TO BE PIPED WITH SIZE SHOWN ON

PIPING SCHEDULE THIS SHEET. SEE DETAIL B8 ON DRAWING

4-MG-003.

2. PIPING SHOWN FOR CLARITY. CONTRACTOR TO MOUNT

PIPING STACKED AGAINST ONE SIDE OF CORRIDOR AS HIGH

1 2 3 4 5 6 9 11

A

B

C

D

F

H

7 8 1210

E

G

I

KEY PLAN

SEE SHEET

4-MP-1R8

SEE SHEET

4-MP-1R8

RTU-12

RTU-22

KEYED PLAN NOTES

1. 2-1/2" CHILLED WATER SUPPLY AND RETURN TO FROM 2ND

FLOOR. SEE DETAIL 'B8' ON DRAWING 4-MG-003 FOR CHILLED

WATER COIL PIPING.

2. SEE PENTHOUSE DRWAINTS FOR WORK, SHEETS A-MD-1P15

AND 4-MD-1P16.

3. 3"MPS FROM SECOND FLOOR. 2-1/2"MPS TO STEAM PREHEAT

COIL AND 2"MPS TO HUMIDIFIER. 1-1/2"CR FROM PREHEAT

COIL AND HUMIDIFIER. SEE DETAILS 'D9', 'F1' AND 'F3' ON

DRAWING 4-MG-003.

4. 2"MPS AND 1"CR TO STEAM PREHEAT COIL. 1-1/2"MPS TO

HUMIDIFIER. 1"CR FROM STEAM PREHEAT COIL AND

HUMIDIFIER. SEE DETAIL 'D9' ON DRAWING 4-MG-003 FOR

STEAM COIL PIPING.

www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

05-15-2024

CONSTRUCTION DOCUMENTS

DESIGN REPLACE HVAC &

ASSOCIATED COMPONENTS

589A5-22-106

COLMERY-O'NEIL VAMC

2200 SW GAGE BLVD. - TOPEKA, KS 66622

FULLY SPRINKLERED

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

4-MP-1R7

MECHANICAL PIPING REVISED PLAN

ROOF B WING

13 16 18 20 22 24

B

C

D

F

H

12 14 17 19 21 23 25

E

G

I

KEY PLAN

SEE SHEET

4-MH-1R7

SEE SHEET

4-MP-1R7

RTU-11

RTU-21

KEYED PLAN NOTES

1. 2-1/2" CHILLED WATER SUPPLY AND RETURN TO FROM 2ND

FLOOR. SEE DETAIL B8 ON DRAWING 4-MG-6013 FOR CHILLED

WATER COIL PIPING DETAILS.

2. 2" LPS AND 1" CR FROM SECOND FLOOR. 2" LPS TO PREHEAT

COIL AND 1" LPS TO HUMIDIFIER. 1" CR FROM PREHEAT COIL

AND 3/4" CR FROM HUMIDIFIER. SEE DETAILS 'D9', 'F1' AND 'F3'

ON DRAWING 4-MG-003.

www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC.

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

05-15-2024

CONSTRUCTION DOCUMENTS

DESIGN REPLACE HVAC &

ASSOCIATED COMPONENTS

589A5-22-106

COLMERY-O'NEIL VAMC

2200 SW GAGE BLVD. - TOPEKA, KS 66622

FULLY SPRINKLERED

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

4-MP-1R8

MECHANICAL PIPING REVISED PLAN

ROOF A & C WINGS

ELECTRICAL SYMBOLS

EXISTING OUTLET OR DEVICE TO REMAIN. MAINTAIN EXISTING CIRCUITING.

DASH SYMBOL INDICATES PARTICULAR OUTLET OR DEVICE TO BE REMOVED AND CIRCUITRY MADE CONTINUOUS WHERE

REQUIRED.

ELECTRICAL CONNECTION.

20A-125V SINGLE RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERWISE).

SPECIAL PURPOSE RECEPTACLE. REFER TO NOTE ON PLAN.

20A-125V DOUBLE DUPLEX RECEPTACLE. NEMA 5-20R, (18" MH UNLESS NOTED OTHERWISE) TWO GANG ASSEMBLY.

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R WITH BOTTOM OUTLET CONTROLLED BY WALL SWITCH. (18" MH UNLESS

NOTED OTHERWISE).

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R, WITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH UNLESS NOTED

OTHERWISE).

20A-125V WEATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R (HORIZONTAL 18" MH UNLESS NOTED OTHERWISE) WITH

TAYMAC #MM420G EXTRA DUTY GRAY COVER, VERTICAL MOUNT.

20A-125V WEATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R WITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH UNLESS NOTED OTHERWISE), WITH TAYMAC #MM420G EXTRA DUTY GRAY COVER, VERTICAL MOUNT.

20A-125V POWERLOCK GROUNDING TYPE RECEPTACLE, HOSPITAL USE (66" MH UNLESS NOTED OTHERWISE).

20A-125V DUPLEX PEDESTAL TYPE FLOOR RECEPTACLE, NEMA 5-20R, IN HUBBELL BA-2527 FLOOR BOX WITH SA-2525

COVERPLATE AND SC-3091 HOUSING. PROVIDE CARPET FLANGE WHERE REQUIRED.

20-125V DUPLEX RECEPTACLE, NEMA 5-20R, WITH ISOLATED GROUND (18" MH UNLESS NOTED OTHERWISE).

20A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-20R (18" MH UNLESS NOTED OTHERWISE).

30A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-30R (18" MH UNLESS NOTED OTHERWISE).

50A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-50R (18" MH UNLESS NOTED OTHERWISE).

20A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-20R (18" MH UNLESS NOTED OTHERWISE).

30A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-30R (18" MH UNLESS NOTED OTHERWISE).

50A-250V-3PH-4W SINGLE RECEPTACLE, NEMA 15-50R (18" MH UNLESS NOTED OTHERWISE).

JUNCTION BOX. SQUARE DEVICE INDICATES A CONNECTION TO CRITICAL POWER.

MULTI-OUTLET RECEPTACLES ASSEMBLY, NEMA 5-15R (SINGLE OUTLETS ON 18" CENTERS) (46" MH UNLESS NOTED

OTHERWISE).

CLOCK HANGER OUTLET, SINGLE NEMA 5-15R RECESSED IN COVER PLATE (84" MH UNLESS NOTED OTHERWISE).

SINGLE POLE SWITCH (46" MH UNLESS NOTED OTHERWISE).

TWO POLE WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).

MULTI-WAY WALL SWITCH, # INDICATES NUMBER OF WAYS (46" MH UNLESS NOTED OTHERWISE).

SWITCH WITH NEON PILOT LIGHT. ONE-GANG ASSEMBLY (46" MH UNLESS NOTED OTHERWISE).

KEY OPERATED WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).

LIGHTING DIMMER SWITCH (46" MH UNLESS NOTED OTHERWISE) 1000 WATTS UNLESS OTHERWISE INDICATED.

SWITCH WITH RECEPTACLE (46" MH UNLESS NOTED OTHERWISE) STANDARD TWO-GANG ASSEMBLY OF SWITCH AND

RECEPTACLE.

FLUSH FRACTIONAL HORSEPOWER MOTOR STARTER WITH NEON PILOT LIGHT. ONE-GANG ASSEMBLY (46" MH UNLESS

NOTED OTHERWISE).

HP RATED WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).

DISCONNECT SWITCH.

MOTOR STARTER.

COMBINATION MOTOR STARTER AND DISCONNECT SWITCH.

ELECTRIC MOTOR.

ELECTRICAL PANEL OR SWITCHBOARD PER DRAWINGS.

PULL BOX.

LINE VOLTAGE THERMOSTAT.

UNIT HEATER.

FAN COIL.

ELECTRIC BASEBOARD HEATER.

AIR CONDITIONER.

CONDENSING UNIT.

UNIT VENTILATOR.

CORD REEL.

POWER POLE.

PHOTOELECTRIC SENSOR.

LIGHTING CONTACTOR.

CEILING MOUNTED OCCUPANCY SENSOR.

WALL MOUNTED OCCUPANCY SENSOR.

CEILING MOUNTED DAYLIGHT SENSOR.

OCCUPANCY SENSOR POWER PACK.

PUSHBUTTON (46" MH UNLESS NOTED OTHERWISE) EDWARDS 852 (120 VOLT).

BUZZER (90" MH UNLESS NOTED OTHERWISE) EDWARDS 340-A (120 VOLT).

4" DIAMETER (90" MH UNLESS NOTED OTHERWISE) EDWARDS "ADAPTABEL" (120 VOLT).

GF

WP

WP/GF

T

IG

20A

30A

50A

20A

50A

30A

J

P

K

DM

R

H

UH

FC

AC

CU

UV

PP

OS

M

OS

M

DS

OP

PC

T

B

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (46" MH UNLESS NOTED OTHERWISE).

C

M

CR

LC

P/B

ELAPSED TIME INDICATOR CLOCK (90" MH UNLESS NOTED OTHERWISE) WITH RESET SWITCH (46" MH UNLESS NOTED

OTHERWISE).

INTERCOM SYSTEM DESK MOUNTED MASTER CONTROL STATION. SUBSCRIPT "W" INDICATES WALL MOUNT (46" MH

UNLESS NOTED OTHERWISE).

INTERCOM STAFF STATION (46" MH UNLESS NOTED OTHERWISE).

INTERCOM HORN TYPE SPEAKER (84" MH UNLESS NOTED OTHERWISE).

INTERCOM SPEAKER FLUSH MOUNT IN CEILING.

I

M

H

S

DUCT HEATER.H

DH

H

EB

LOW-VOLTAGE MOMENTARY WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).L

ABBREVIATIONS

AAP - AREA ALARM PANEL - MEDICAL GAS

ACC - ACCESS

ADJ - ADJUSTABLE

AF - ARC FAULT CIRCUIT INTERRUPTER

AFCI - ARC FAULT CIRCUIT INTERRUPTER

AFF - ABOVE FINISHED FLOOR TO BOTTOM OF ITEM

AFG - ABOVE FINISHED GRADE TO BOTTOM OF ITEM

ALT - ALTERNATE

AP - ACCESS PANEL

APPROX - APPROXIMATE

ARCH - ARCHITECT OR ARCHITECTURAL

ASSY - ASSEMBLY

ATS - AUTOMATIC TRANSFER SWITCH

BLDG - BUILDING

BOE - BOTTOM OF EQUIPMENT

BOT - BOTTOM

BTWN - BETWEEN

CFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLED

CKT - CIRCUIT

CLG - CEILING

CMU - CONCRETE MASONRY UNIT

CONN - CONNECT OR CONNECTION

CONTR - CONTRACTOR

CORR - CORRIDOR

CTR - CENTER

D - DEPTH

DET - DETAIL

DIA - DIAMETER

DIM - DIMENSION

DIV - DIVISION

DN - DOWN

DWG - DRAWING

EA - EACH

EC - ELECTRICAL (DIVISION 26)

EJ - EXPANSION JOINT

ELEC - ELECTRICAL

ELEV - ELEVATION OR ELEVATOR

EM - EMERGENCY

EQ - EQUAL

EQS - EQUIPMENT SUPPLIER

EQUIP - EQUIPMENT

E/R - EXISTING TO BE RELOCATED

EX - EXISTING TO REMAIN

EXP - EXPANSION

EXT - EXTERIOR

FCE - FIRE CONTROL EQUIPMENT

FF - FINISHED FLOOR ELEVATION

FLR - FLOOR

FSC - FIRE SUPPRESSION (DIVISION 21)

FT - FEET

FTG - FOOTING

GC - GENERAL TRADE (DIV 01)

GF - GROUND FAULT CIRCUIT INTERRUPTER

GFCI - GROUND FAULT CIRCUIT INTERRUPTER OR GOVERNMENT

FURNISHED CONTRACTOR INSTALLED

GFFT - GROUND FAULT FEED THRU

HC - HVAC (DIVISION 23)

HP - HORSE POWER OR HIGH POINT

HVAC - HEATING, VENTILATING, AND AIR CONDITIONING

ID - INSIDE DIAMETER

IN - INCHES

KEC - KITCHEN EQUIPMENT CONTRACTOR

L - LENGTH

LBS - POUNDS

MAP - MASTER ALARM PANEL (MEDICAL GAS)

MAX - MAXIMUM

MEZZ - MEZZANINE

MFR - MANUFACTURER

MH - MANHOLE OR MOUNTING HEIGHT TO CENTER LINE OF ITEM

MIN - MINIMUM OR MINUTE

MISC - MISCELLANEOUS

MTD - MOUNTED

MTG - MOUNTING

NIC - NOT IN CONTRACT

NOM - NOMINAL

NTS - NOT TO SCALE

OD - OUTSIDE DIAMETER

OFCI - OWNER FURNISHED CONTRACTOR INSTALLED

OFOI - OWNER FURNISHED OWNER INSTALLED

PC - PLUMBING (DIVISION 22)

PLBG - PLUMBING

RAD - RADIUS

REC - RECESSED

REQD - REQUIRED

RI - ROUGH-IN

S - SURFACE MOUNTED

SC - SECURITY CONTRACTOR

SCH - SCHEDULE

SHT - SHEET

SMS - SECURITY MANAGEMENT SYSTEM

SPEC - SPECIFICATIONS

SQ - SQUARE

SS - STAINLESS STEEL

STD - STANDARD

STRUC - STRUCTURAL OR STRUCTURE

SUC - SITE UTILITY CONTRACTOR

TC - TECHNOLOGY (DIVISION 27)

TEMP - TEMPERATURE

TOE - TOP OF EQUIPMENT

TYP - TYPICAL

UNO - UNLESS NOTED OTHERWISE

VFD - VARIABLE FREQUENCY DRIVE

VOL - VOLUME

W/ - WITH

W/O - WITHOUT

WP - WEATHERPROOF

ZVC - ZONE VALVE CABINET

LUMINAIRE SYMBOLS

LIGHTING FIXTURE. CAPITAL LETTER DENOTES FIXTURE TYPE, LOWER CASE LETTER DENOTES

SWITCHING ARRANGEMENT.

LIGHTING FIXTURE ON NIGHT LIGHT OR EMERGENCY CIRCUIT.

EXIT LIGHTING FIXTURE, ARROWS AS INDICATED.

A a

WIREMOLD RACEWAY, AS NOTED ON PLANS.

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R WITH 2 INTEGRAL USB CHARGERS (18" MH UNLESS NOTED OTHERWISE).

NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT

TO MODIFICATIONS ON OTHER DRAWINGS.

ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT

NECESSARILY BE USED ON THIS PROJECT.

LIGHTING FIXTURE ON CRITICAL CIRCUIT.

SQUARE DEVICE INDICATES A CONNECTION TO CRITICAL POWER. SPECIFICATION IS SAME AS RESPECTIVE ROUND DEVICE.

J

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R, IN HUBBELL BA-2527 FLUSH FLOOR BOX WITH ROUND SA-3925 COVERPLATE.

PROVIDE CARPET FLANGE WHERE REQUIRED.

F

F

F

F

F

S F

KF

S

H

C

D

FS

V

R W

SD

FT

PS

AM

C/I

PIV

K S

H

S S/R

S/R

FACP

FIRE ALARM SYMBOLS

FIRE ALARM BELL & SIGNAL LIGHT (88" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.

FIRE ALARM SPEAKER & SIGNAL LIGHT (88" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.

FIRE ALARM CHIME & SIGNAL LIGHT (88" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.

FIRE ALARM HORN & SIGNAL LIGHT (88" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.

FIRE ALARM SIGNAL LIGHT (88" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.

CEILING MOUNTED FIRE ALARM SPEAKER.

FIRE ALARM CONTROL PANEL.

CEILING MOUNTED FIRE ALARM SPEAKER & SIGNAL LIGHT. # WHEN SHOWN INDICATES CANDELA RATING OF STROBE.

WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER

LOCATIONS.

FIRE ALARM MANUAL STATION (46" MH UNLESS NOTED OTHERWISE). SUBSCRIPT "K" INDICATES KEY OPERATED.

CEILING MOUNTED SMOKE DETECTOR.

CEILING MOUNTED HEAT DETECTOR.

DUCT MOUNTED SMOKE DETECTOR. SUBSCRIPT "S" INDICATES SUPPLY. SUBSCRIPT "R" INDICATES RETURN.

DUCT MOUNTED HEAT DETECTOR. SUBSCRIPT "S" INDICATES SUPPLY. SUBSCRIPT "R" INDICATES RETURN.

ELECTRIC RELEASE DOOR CLOSER.

ELECTRO-MAGNETIC DOOR HOLDER.

WATER FLOW SWITCH.

VALVE SUPERVISORY SWITCH.

CEILING MOUNTED REMOTE TEST STATION AND ALARM INDICATOR LIGHT FOR DUCT DETECTOR. SUBSCRIPT "W" INDICATES

WALL MOUNTED.

SMOKE DAMPER.

FIRE FIGHTER'S TELEPHONE (60" MH UNLESS NOTED OTHERWISE).

PRESSURE SWITCH.

ADDRESSABLE MODULE. SUBSCRIPT "I" INDICATES INPUT. SUBSCRIPT "C" INDICATES CONTROL.

POST INDICATOR VALVE.

KNOX BOX (46" MH UNLESS NOTED OTHERWISE). SUBSCRIPT "S" INDICATES SUPERVISED UNIT.

FIRE ALARM BELL (88" AFF UNLESS NOTED OTHERWISE). SUBSCRIPT "W" INDICATES EXTERIOR WEATHERPROOF UNIT.

BEAM DETECTOR. SUBSCRIPT "T" INDICATES TRANSMITTER FUNCTION. SUBSCRIPT "R" INDICATES RECEIVER FUNCTION.

AIR SAMPLING SMOKE DETECTOR SAMPLING PORT.

REMOTE ANNUNCIATOR PANEL.

NOTIFICATION APPLIANCE CIRCUIT EXTENDER PANEL.

AIR SAMPLING SMOKE DETECTOR BASE UNIT.

SURFACE MOUNTED FIRE ALARM SPEAKER (88" AFF). SUBSCRIPT "R" INDICATES RECESSED MOUNTING.

RAP

NAC

ASSD

F W

S 15 F

S R

A

B T/R

E2

B

E2

DETAIL: B = DETAIL DESIGNATION

E2 = SHEET WHERE DETAIL IS LOCATED

SECTION: 1 = SECTION DESIGNATION

E2 = SHEET WHERE SECTION IS LOCATED

PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN.

DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.

GENERAL FLOOR PLAN NOTES

WIRE & CONDUIT IN WALL OR ABOVE CEILING.

WIRE & CONDUIT IN OR BELOW SLAB OR GRADE.

EACH ARROWHEAD REPRESENTS ONE COMPLETE CIRCUIT; "X" DENOTES PANEL NAME;

NUMBER(S) DENOTES CIRCUIT(S).

LADDER TRAY, 12" x 4" DEEP UNLESS NOTED OTHERWISE.

CONDUIT FOR DATA CIRCUITRY.DAT

WIRE & CONDUIT FOR FIRE ALARM CIRCUITRY.FA

WIRE & CONDUIT FOR NURSE CALL CIRCUITRY.NC

EXISTING WIRE & CONDUIT TO REMAIN.EX

CONDUIT TO BE REMOVED.

WIRE & CONDUIT FOR NIGHT LIGHT CIRCUITRY.NL

CONDUIT FOR PHONE CIRCUITRY.PHO

WIRE & CONDUIT FOR SECURITY SYSTEM CIRCUITRY.SEC

WIRE RUN IN SURFACE WIREWAY.W

CABLE MANAGEMENT SYSTEM PATHWAY.CM

X - 1,2

WIRE & CONDUIT FOR EMERGENCY CIRCUITRY.EM

WIRE & CONDUIT FOR SOUND SYSTEM CIRCUITRY.S

WIRE & CONDUIT FOR INTERCOM SYSTEM CIRCUITRY.I

WIRE & CONDUIT FOR TELEVISION SYSTEM CIRCUITRY.TV

CABLE TRAY, 12" x 4" DEEP UNLESS NOTED OTHERWISE.

4"

4"

4"

T2 1 ELEVATION: 1 = ELEVATION DESIGNATION

T2 = SHEET WHERE ELEVATION IS LOCATED

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERWISE). WHEN SHOWN, RECEPTACLE TO HAVE

"CONTROLLED" MARKINGS.

CEILING MOUNTED FIRE ALARM SIGNAL LIGHT. # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.

F

LIGHTING CONTROL DETAIL NOTE. APPLIES TO THE LIGHTING CONTROL SEQUENCE OF OPERATIONS

SCHEDULE FOR ROOM CONTROL.

3 DEVICE QUANTITY - POWER NOTE. REFER TO DEVICE QUANTITIES - POWER SCHEDULE.

CEILING MOUNTED FIRE ALARM HORN & SIGNAL LIGHT. # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.

F

GENERAL NOTES

A. THESE NOTES APPLY EQUALLY TO THE FULL SET OF DOCUMENTS.

B. SITE VISIT(S) SHALL BE AS OUTLINED IN PROJECT SPECIFICATIONS.

C. INCLUDE ALL WORK NECESSARY TO ACCOMMODATE PHASING. REFER TO

ARCHITECTURAL DRAWINGS AND GENERAL REQUIREMENTS SECTION 01 00 00.

D. THE CONTRACTOR SHALL REFER TO ALL SPECIFICATION SECTIONS AND THE

DRAWINGS FOR DETAILS OF BUILDING CONSTRUCTION TO ENSURE SPACE AND

SATISFACTORY ARRANGEMENT FOR THEIR WORK. THE VARIOUS DRAWINGS

COMPRISING THE SET ARE INTERDEPENDENT AND MUST BE USED JOINTLY AT

ALL TIMES. THE CONTRACTOR SHALL REFER TO THE GENERAL REQUIREMENTS

OF THE CONTRACT. THE NOTES AND SYMBOLS INDICATED ON THE DRAWINGS

ARE FOR THE GUIDANCE OF ALL TRADES INVOLVED IN THE PROJECT AND MUST

BE FOLLOWED TO EXECUTE THE WORK AS INTENDED. IF DISCREPANCIES

OCCUR, CONTACT THE COR THROUGH THE CONTRACTING OFFICER FOR

CLARIFICATION BEFORE PROCEEDING.

E. ALL WORK MUST BE COORDINATED WITH THE CONTRACTING OFFICER AND

(FOR ALL OTHERS) TO MAINTAIN OPERATION OF THE EXISTING FACILITY.

F. ALL WORK SHALL BE PERFORMED IN COMPLETE COMPLIANCE WITH ALL

CURRENT GOVERNING CODES AND STANDARDS.

G. EXISTING CONDITIONS SHOWN HAVE BEEN BASED UPON AVAILABLE DRAWING

INFORMATION, AND MAY BE AT VARIANCE WITH ACTUAL WORK IN PLACE. THE

CONTRACTOR SHALL TAKE NECESSARY FIELD MEASUREMENTS AND FIELD

VERIFY ALL CONDITIONS AFFECTING THE EXECUTION OF THE WORK. ANY

DISCREPANCIES BETWEEN EXISTING CONDITIONS AND THE WORK SHOWN ON

THE CONTRACT DOCUMENTS WHICH MAY IMPACT THE PROGRESS OF THE

WORK SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER

IN WRITING FOR RESOLUTION BEFORE PROCEEDING WITH THE WORK.

H. ALL PENETRATIONS THROUGH FIRE-RATED ASSEMBLIES SHALL BE

PROTECTED AND/OR FIRE-STOPPED AS REQUIRED TO MAINTAIN FIRE-RATINGS

INDICATED. COORDINATE WITH ALL TRADES TO ENSURE FIRE-RATED

PENETRATION REQUIREMENTS AND DETAILS ARE MET.

I. ANNULAR SPACE OF ALL PIPE, CONDUIT, DUCT AND OTHER SIMILAR

PENETRATIONS OF FIRE RATED ASSEMBLIES SHALL BE FIRESTOPPED. IN

ADDITION, PENETRATIONS THROUGH 0-HOUR RATED WALLS AND FLOORS

SHALL BE FIRESTOPPED TO RETARD PASSAGE OF FIRE AND SMOKE.

J. ALL CONDUITS IN FINISHED ROOMS, CORRIDORS, ETC. SHALL BE CONCEALED

IN A WALL OR ABOVE CEILING.

K. ACCESS PANELS IN NON ACCESSIBLE CEILINGS SHALL BE PROVIDED FOR ALL

ELECTRICAL ITEMS REQUIRING ACCESS.

L. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION

OF LIGHTS, SPEAKERS, NURSE CALL DEVICES, ETC.

M. ALL CUTTING AND PATCHING REQUIRED FOR THIS PROJECT SHALL BE

INCLUDED IN THE CONTRACT. REFINISH ANY SURFACE DISTURBED UNDER THIS

WORK TO MATCH EXISTING.

N. ANY REMOVED EQUIPMENT SHALL BE TURNED OVER TO THE VA. ITEMS NOT

DESIRED BY THE VA SHALL BE REMOVED FROM THE PREMISES AND DISPOSED

OF PROPERLY BY THE CONTRACTOR.

O. THE CONTRACT DRAWINGS ARE NOT INTENDED TO SHOW EVERY VERTICAL OR

HORIZONTAL OFFSET WHICH MAY BE NECESSARY TO COMPLETE THE

SYSTEMS. COORDINATE WORK IN ADVANCE WITH ALL OTHER TRADES AND

REPORT IMMEDIATELY AND DIFFICULTIES WHICH CAN BE ANTICIPATED.

P. ALL ABANDONED EXTRANEOUS CONDUITS, WIRING, DEVICES, ETC. SHALL BE

REMOVED.

Q. REFER TO MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION

CONCERNING MECHANICAL EQUIPMENT THAT REQUIRED ELECTRICAL

CONNECTIONS.

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

P: 937-224-0861 www.heapy.com

PROJECT NO.

U.S. Department of Veterans Affairs

CONSULTANTS:

Revisions:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

REMOVE AND REPLACE AHU-4

589A-22-106 o n e e ig h th in c h o n e fo o t

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM

08-6231 1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Date:

ARCHITECT/ENGINEERS:

DESIGN-AIRE ENGINEERING, INC.

www.daengineering.comwww.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

COLMERY-O'NEIL VAMC

2200 SW GAGE BLVD. - TOPEKA, KS 66622

FULLY SPRINKLERED

1-EG-001

JASMSG

CONSTRUCTION DOCUMENTS

2022-05156

ABBREVIATIONS, LEGEND &

DRAWING INDEX

DRAWING INDEX - ELECTRICAL

SHEET NUMBER SHEET NAME

1-EG-001 ABBREVIATIONS, LEGEND & DRAWING INDEX

1-EG-002 SCHEDULES & DIAGRAM

1-EG-003 SCHEDULES & DIAGRAMS

1-EG-004 SCHEDULES & DIAGRAMS

4-ED-1B1 ELECTRICAL DEMOLITION PLAN BASEMENT FLOOR B WING

4-ED-1B2 ELECTRICAL DEMOLITION PLAN BASEMENT A & C WINGS

4-ED-1P7 ELECTRICAL DEMOLITION PLAN PENTHOUSE FLOOR

4-ED-113 ELECTRICAL DEMOLITION PLAN FIRST FLOOR B WING

4-ED-114 ELECTRICAL DEMOLITION PLAN FIRST FLOOR A & C WING

4-ED-125 ELECTRICAL DEMOLITION PLAN SECOND FLOOR B WING

4-ED-126 ELECTRICAL DEMOLITION PLAN SECOND FLOOR A & C WINGS

4-EL-1B1 LIGHTING REVISED PLAN BASEMENTFLOOR B WING

4-EL-1B2 LIGHTING REVISED PLAN BASEMENT FLOOR A & C WINGS

4-EL-113 LIGHTING REVISED PLAN FIRST FLOOR B WING

4-EL-114 LIGHTING REVISED PLAN FIRST FLOOR A & C WINGS

4-EL-125 LIGHTING REVISED PLAN SECOND FLOOR B WING

4-EL-126 LIGHTING REVISED PLAN SECOND FLOOR A & C WINGS

4-EP-1B1 POWER REVISED PLAN BASEMENT FLOOR B WING

4-EP-1R3 POWER REVISED PLAN ROOF B WING

4-EP-1R4 POWER REVISED PLAN ROOF A & C WINGS

05/15/2024 10681

Type A

RECESSED LED ARCHITECTURAL LAY-IN FIXTURE

HOUSING: DIE-FORMED COLD-ROLLED STEEL.

FINISH: NON-GLARE HIGH-REFLECTANCE WHITE POWER COAT

FINISH, PAINTED AFTER FABRICATION.

OPTICS: HIGH TRANSMISSION EXTURDED ACRYLIC LENSES.

LAMPS: LED LIGHT SOURCE, 60,000 HOUR RATED AT L80, 80 CRI.

4000K

CERTIFICATION: UL1598, UL2108, CSA LABEL. DESIGNLIGHTS CONSORTIUM

(DLC) QUALIFIED. IC RATING - STANDARD

VOLTAGE: UNIVERSAL 120-277V.

VARIATIONS: “A14” 1’ X 4’ 4500 LM, 33 W, NOMINAL

“A22” 2’ X 2’ 4300 LM, 35 W, NOMINAL

"A24" 2' X 4' 4900 LM, 37 W, NOMINAL

BASIS OF DESIGN: H.E.WILLIAMS "PT" SHALLOW PLENUM TROFFER

A

Type C1

LED LENSED STRIPLIGHT FIXTURE

SURFACE MOUNTED OR CHAIN HUNG

HOUSING: DIE-FORMED COLD-ROLLED STEEL.

FINISH: NON-GLARE HIGH-REFLECTANCE BAKED ENAMEL FINISH,

PAINTED AFTER FABRICATION.

OPTICS: ACRYLIC LENS.

LAMPS: LED LIGHT SOURCE, 50,000 HOUR RATED AT L80, 80 CRI.

4000K

CERTIFICATION: UL1598, UL2108, CSA LABEL. DESIGNLIGHTS CONSORTIUM

(DLC) QUALIFIED.

DIMMING: 0-10VDC 1% DIMMING.

VOLTAGE: UNIVERSAL 120-277V.

VARIATIONS: “C1a” 4’ 2500 LM, 25 W, NOMINAL “C1b” 4’ 5000 LM, 48 W, NOMINAL “C1c” 4’ 6100 LM, 55 W, NOMINAL

“C1x” 8’ 5000 LM, 48 W, NOMINAL “C1y” 8’ 10,100 LM, 96 W, NOMINAL “C1z” 8’ 12,200 LM, 111 W, NOMINAL

BASIS OF DESIGN: COLUMBIA LCL

C1

Type DR

RECESSED LED 6” DIAMETER OPEN DOWNLIGHT FIXTURE

HOUSING: 22 GA. NON-CORROSIVE STEEL PLATFORM. J-BOX WITH

SNAPON COVER. ACCESSABLE FROM ABOVE AND BELOW

CEILING.

REFLECTOR: ALUMINUM, ALZAK SEMI-DIFFUSE REFLECTOR. SELF-

TRIMED.

45DEG BEAM SPREAD.

LAMPS: LED LIGHT SOURCE, 50,000 HOUR RATED AT L70, 80 CRI.

4000K

CERTIFICATION: CSA LABEL. ENERGY STAR QUALIFIED. NON-IC RATING

DIMMING: 0-10VDC 10% DIMMING.

VOLTAGE: UNIVERSAL 120-277V.

VARIATIONS: “DR6” 6” 45DEG 2000 LM, 27 W, NOMINAL

BASIS OF DESIGN: PRESOLITE LITEFRAME LF6LEDG4)

DR

Type X

LED EXIT SIGN

HOUSING: DIE-CAST ALUMINUM BODY. BLACK TEXTURED FINISH.

MOUNTING: UNIVERSAL WALL, CEILING, END MOUNTING.

LAMPS: LED LIGHT SOURCE, RED STENCIL LETTERS. BREAK OUT

CHEVRONS.

CERTIFICATION: EMERGENCY FIXTURES-UL924

VOLTAGE: UNIVERSAL 120-277V.

VARIATIONS: “X1” SINGLE FACE EXIT.

“X2” DOUBLE FACE EXIT.

BASIS OF DESIGN: DUALLITE SE SERIES

X

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

P: 937-224-0861 www.heapy.com

PROJECT NO.

U.S. Department of Veterans Affairs

CONSULTANTS:

Revisions:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

REMOVE AND REPLACE AHU-4

589A-22-106 o n e e ig h th in c h o n e fo o t

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM

08-6231 1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Date:

ARCHITECT/ENGINEERS:

DESIGN-AIRE ENGINEERING, INC.

www.daengineering.comwww.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

COLMERY-O'NEIL VAMC

2200 SW GAGE BLVD. - TOPEKA, KS 66622

FULLY SPRINKLERED

1-EG-002

JASMSG

CONSTRUCTION DOCUMENTS

2022-05156

SCHEDULES & DIAGRAM

1X4 OR 2X2

NOTES:

1. SINGLE POINT POWER CONNECTION AT UNIT.

2. UNIT CONTAINS MULTIPLE FAN MOTORS. FEEDER SIZED FOR

SINGLE POINT CONNECTION TO UNIT.

3. REFER TO SINGLE LINE DIAGRAM FOR FEEDER SIZE.

MOTORS, STARTERS, DISCONNECTS & CONTROLS

MARK

MOTOR STARTER DISCONNECT MEANS CONTROL FEEDER

S E

E N

O T

E

NAMEPLATE

CHARACTERISTICS LOCATION

N E

M A

S

IZ

E

TYPE LOCATION

F U

R N

IS

H

E D

B Y

TYPE LOCATION

F U

R N

IS

H

E D

B Y

I N

T E

R L O

C K

W

IT

H M

O T

O R

N O

B

Y E

.C

M

N U

A L A

T S

T A

R T

E R

I N

T E

G R

A L

W

IT

H E

Q U

IP

M

E N

T

F U

R N

IS

H

E D

B Y

S E

E N

O T

E

N U

M B

E R

O F

C O

N D

U C

T O

R S

W

IR

E S

IZ

E

G R

O U

N D

S

IZ

E

C O

N D

U

IT

S

IZ

E

H O

R S

E P

O W

E R

H

P

L O

A D kV

A

V

-1 P

H

V

-1 P

H

V

-3 P

H

V

-1 P

H

V

-3 P

H

V

-1 P

H

V

-1 P

H

V

-3 P

H

R O

O M

N U

M B

E R

ROOM NAME M

A

N U

A L

M A

G N

E T

IC

B U

IL

T

-I N

M O

T O

R O

/L

-S

P E

E D

V F

D

S E

E N

O T

E

N E

A R

M O

T O

R

M O

T O

R C

O N

T C

E N

T E

R

E Q

U

IP

C O

N T

P A

N E

L

R O

O M

N U

M B

E R

S E

E N

O T

E

D

IS

C S

W

IT

C H

M A

N U

A L S

T A

R T

E R

R E

C E

P T

A C

L E

F E

E D

E R

S W

O R

B R

E A

K E

R

N E

M A

T Y

P E

D

IS

C S

IZ

E

F U

S E

S

IZ

E

N E

A R

M O

T O

R

M O

T O

R C

O N

T C

E N

T E

R

E Q

U

IP

C O

N T

P A

N E

L

P A

N E

L B

O A

R D

S E

E N

O T

E

4-CHP-1 4-CHP-1 10 11.6 ● B07 ● ● B07 DIV 23 ● ● DIV 23 DIV 23 3 6 10 1

4-CHP-2 4-CHP-2 10 11.6 ● B07 ● ● B07 DIV 23 ● ● DIV 23 DIV 23 3 6 10 1

4-HWP-1 4-HWP-1 3 0 ● B10 ● ● B10 DIV 23 ● ● DIV 23 DIV 23 3 12 12 1

4-HWP-2 4-HWP-2 3 0 ● B10 ● ● B10 DIV 23 ● ● DIV 23 DIV 23 3 12 12 .75

AHU-B-1 AHU-B-1 2- 5 12.03 ● B07 ● ● B07 DIV 23 ● ● DIV 23 DIV 23 3 8 8 .75

RTU-11 RTU-11 4 - 5 24.07 ● ROOF - AREA A ● ● DIV 23 ● ● DIV 23 DIV 23 1,2,3

RTU-12 RTU-12 6 - 7.5,

3 - 10

59.44 ● ROOF - AREA B ● ● DIV 23 ● ● DIV 23 DIV 23 1,2,3

RTU-21 RTU-21 4 - 5 24.07 ● ROOF - AREA A ● ● DIV 23 ● ● DIV 23 DIV 23 1,2,3

RTU-22 RTU-22 4 - 5 24.07 ● ROOF - AREA B ● ● DIV 23 ● ● DIV 23 DIV 23 1,2,3

05/15/2024 82 106

ENEN

100AF

100AT

3P

150AF

150AT

3P

225AF

225AT

3P

225AF

225AT

3P

225AF

225AT

3P

225AF

225AT

3P

600AF

600AT

3P

MAIN SWITCHBOARD "MSB" (EXISTING)

600A, 208Y/120V, 3PH-4W, 42 KAIC

AHU

4-HV-1

PANELS

LBA

L1A L2A

PANELS

LBC

L1C

L2C PANEL

SR

PANELS

LBB

L1B L2B

ATS

600A,3P

225KVA

480V PRI

208Y/120V SEC

TO

GENENATOR

IN BLDG #56

EDP-56

100A 3P

175A 3P

80A 3P

60A 3P

150A 3P

60A 3P

PANEL ES (EXISTING)

400A, 208Y/120V, 3PH-4W, 42 KAIC

PANELS

EBA

E1A E2A

ELEVATOR MED. AIR

PENTHOUSE

PANEL

SN

(TEL. RM)

PANELS

LBS

LS1

LS2

PANEL

ES-4

AHU

4-HV-2

DETAIL NOTES

1. REMOVE EXISTING FEED. MAINTAIN BREAKER FOR

FUTURE USE.

2. REMOVE EXISTING FEED AND BREAKER.

3. ABANDON ELECTRICAL SERVICE INTO BASEMENT

MECHANICAL ROOM B10. REMOVE DISCONNECT.

MAINTAIN SERVICE FEED.

4. REMOVE FEED FOR ELEVATOR TO REROUTE. REFER

TO NEW SINGLE LINE DIAGRAM.

PANEL

SR-1

600A 3P

600AF

600AT

3P

TO MANHOLE

MH9

SPACE

3P

SPACE

3P

SPACE

3P

SPACE

3P

SPACE

3P

200AF

200AT

3P

ELEVATOR

(40HP)

4-T1

225KVA

12.47KV PRI

208Y/120V SEC

4-T2

225KVA

12.47KV PRI

480Y/277V SEC

TO MANHOLE

MH24

250A 3P

DETAIL NOTES

1. REPLACE BREAKER AND FEEDER FROM AHU 4-HV2

WITH 45A/3P BREAKER AND FEEDER AS INDICATED.

2. INSTALL NEW BREAKER IN AVAILABLE SPACE.

3. REPLACE BREAKER AND FEED FROM H/C PUMPS

WITH 150A/3P BREAKER AND FEEDER INDICATED.

4. CONNECT EXISTING CONDUCTORS TO NEW

DISTRIBUTION PANEL.

5. CONNECT TO EXISTING ELEVATOR

CONTROLLER/DISCONNECT.

100AF

100AT

3P

150AF

150AT

3P

225AF

225AT

3P

225AF

225AT

3P

225AF

225AT

3P

225AF

225AT

3P

600AF

600AT

3P

MAIN SWITCHBOARD "MSB" (EXISTING)

600A, 208Y/120V, 3PH-4W, 42 KAIC

PANELS

LBA

L1A L2A

PANELS

LBC

L1C

L2C PANEL

SR

PANELS

LBB

L1B L2B

ATS

600A,3P

4-T1

225KVA

480V PRI

208Y/120V SEC

TO

GENENATOR

IN BLDG #56

EDP-56

100A 3P

175A 3P

80A 3P

60A 3P

150A 3P

60A 3P

PANEL ES (EXISTING)

400A, 208Y/120V, 3PH-4W, 42 KAIC

PANELS

EBA

E1A E2A

ELEVATOR MED. AIR

PENTHOUSE

PANEL

SN

(TEL. RM)

PANELS

LBS

LS1

LS2

PANEL

ES-4

PANEL

SR-1

600A 3P

600AF

600AT

3P

TO MANHOLE

MH9

SPACE

3P

SPACE

3P

SPACE

3P

SPACE

3P

200AF

200AT

3P

400AF

400AT

3P

150A 3P

80A 3P

80A 3P

60A 3P

PANEL LPDP (NEW)

400A, 208Y/120V, 3PH-4W, 22 KAIC

RTU-12

(NEW)

200A 3P

RTU-21

(NEW)

100A 3P

RTU-22

(NEW)

100A 3P

RTU-11

(NEW)

60A 3P

4#600MCM

#3 GND

4"C

3#2/0

#6 GND

2"C

3#4

#8 GND

1"C

3#6

#10 GND

1"C

3#4

#8 GND

1"C

VFDVFDVFDVFD

100A 3P

4#2

#8 GND

1.5"C

"LPA"

6782 AIC

6084 AIC

AHU

B-1

(NEW)

VFD

PUMP

4-CHP-1

(NEW)

VFD

SPARE

8000 AIC

4-T2

225KVA

12.47KV PRI

480Y/277V SEC

TO MANHOLE

MH24

250A 3P

4-MHDP

NEW

100A 3P

45KVA

480V PRI

208Y/120V SEC

ELEVATOR

(40HP)

SPARE

3#4

#8 GND

1.25"C

4#4/0

#2 GND

2.5"C

7742 AIC

6015 AIC

6579 AIC

6239 AIC

PUMP

4-CHP-2

(NEW)

VFD

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

P: 937-224-0861 www.heapy.com

PROJECT NO.

U.S. Department of Veterans Affairs

CONSULTANTS:

Revisions:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

REMOVE AND REPLACE AHU-4

589A-22-106 o n e e ig h th in c h o n e fo o t

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM

08-6231 1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Date:

ARCHITECT/ENGINEERS:

DESIGN-AIRE ENGINEERING, INC.

www.daengineering.comwww.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

COLMERY-O'NEIL VAMC

2200 SW GAGE BLVD. - TOPEKA, KS 66622

FULLY SPRINKLERED

1-EG-003

JASMSG

CONSTRUCTION DOCUMENTS

2022-05156

SCHEDULES & DIAGRAMS

SCALE: 12" = 1'-0"

EXISTING ELECTRICAL SINGLE LINE DEMOLITION

SCALE: 12" = 1'-0"

EXISTING ELECTRICAL SINGLE LINE - REVISED

28.99 kVA

TOTAL CONNECTED ESTIMATED DEMAND

Notes: $ - PROVIDE NEW CIRCUIT BREAKER SIZED AS INDICATED. MATCH EXISTING BREAKER CHARACTERISTICS.

Total Est. Demand: 80 A

Total Conn.: 80 A

Spare 12340 VA 100.00% 12340 VA Total Est. Demand: 28.99 kVA

Motor 7 VA 112.50% 8 VA Total Conn. Load: 28.99 kVA

Equipment 16644 VA 100.00% 16644 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 9.83 kVA 9.63 kVA 9.53 kVA

41 Space -- -- 0 VA 0 VA -- -- Space 42

39 Space -- -- 0 VA 0 VA -- -- Space 40

37 Space -- -- 0 VA 0 VA -- -- Space 38

35 Space -- -- 0 VA 2900... -- -- -- 36

33 Space -- -- 0 VA 2900... -- -- -- 34

31 EX LOAD 20 A 1 500 VA 2900... 3 45 A $ NEW AHU-B-1 32

29 Space -- -- 0 VA 100 VA 1 20 A EX LOAD 30

27 -- -- -- 800 VA 0 VA 1 20 A Spare 28

25 EX LOAD 20 A 2 800 VA 100 VA 1 20 A EX LOAD 26

23 -- -- -- 1000... 0 VA 1 20 A Spare 24

21 -- -- -- 1000... 500 VA 1 20 A EX LOAD 22

19 EX LOAD 20 A 3 1000... 100 VA 1 20 A EX LOAD 20

17 EX LOAD 20 A 1 1100... 1000... -- -- -- 18

15 Space -- -- 0 VA 1000... -- -- -- 16

13 Space -- -- 0 VA 1000... 3 20 A EX LOAD 14

11 -- -- -- 1325... 180 VA -- -- -- 12

9 -- -- -- 1325... 180 VA 2 30 A EX LOAD 10

7 $ 4-HWP-2 20 A 3 1325... 180 VA 1 20 A EX LOAD 8

5 -- -- -- 1325... 600 VA -- -- -- 6

3 -- -- -- 1325... 600 VA -- -- -- 4

1 $ 4-HWP-1 20 A 3 1325... 600 VA 3 20 A EX LOAD 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 120/208 Wye-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type: MLO

Location: Mounting: Surface A.I.C. Rating: 22K

Panel: SR

43.87 kVA

TOTAL CONNECTED ESTIMATED DEMAND

Notes: $ - PROVIDE NEW CIRCUIT BREAKER SIZED AS INDICATED. MATCH EXISTING BREAKER CHARACTERISTICS

Total Est. Demand: 122 A

Total Conn.: 122 A

Total Est. Demand: 43.87 kVA

Spare 20622 VA 100.00% 20622 VA Total Conn. Load: 43.87 kVA

Equipment 23244 VA 100.00% 23244 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 14.62 kVA 14.62 kVA 14.62 kVA

41 42

39 40

37 38

35 36

33 34

31 32

29 Space -- -- 0 VA 0 VA -- -- -- 30

27 Space -- -- 0 VA 0 VA -- -- -- 28

25 EX LOAD 20 A 1 0 VA 0 VA 3 30 A EX LOAD 26

23 -- -- -- 0 VA 0 VA 1 20 A EX LOAD 24

21 -- -- -- 0 VA 0 VA 1 20 A Spare 22

19 EX LOAD 40 A 3 0 VA 0 VA 1 20 A EX LOAD 20

17 -- -- -- 0 VA 0 VA -- -- -- 18

15 -- -- -- 0 VA 0 VA -- -- -- 16

13 EX LOAD 20 A 3 0 VA 0 VA 3 20 A EX LOAD 14

11 -- -- -- 3874... 3000... -- -- -- 12

9 -- -- -- 3874... 3000... -- -- -- 10

7 $ NEW 4-CHP-2 60 A 3 3874... 3000... 3 50 A EX LOAD 8

5 -- -- -- 3874... 3874... -- -- -- 6

3 -- -- -- 3874... 3874... -- -- -- 4

1 EX LOAD 70 A 3 3874... 3874... 3 60 A $ NEW 4-CHP-1 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 120/208 Wye-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type: MLO

Location: Mounting: Surface A.I.C. Rating: 22K

Panel: SR1

MOTOR MOTOR

BLDG 4 BASEMENT MECH RM B7

SWITCHBOARD MSB

BLDG 4 BASEMENT MECH RM B7

SWITCHBOARD MSB

1.44 kVA 1.44 kVA (4 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes:

Total Est. Demand: 4 A

Total Conn.: 4 A

Total Est. Demand: 1.44 kVA

Total Conn. Load: 1.44 kVA

Receptacle 1440 VA 100.00% 1440 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 0.72 kVA 0.36 kVA 0.36 kVA

23 Space -- -- 0 VA 0 VA -- -- Space 24

21 Space -- -- 0 VA 0 VA -- -- Space 22

19 Space -- -- 0 VA 0 VA -- -- Space 20

17 Space -- -- 0 VA 0 VA -- -- Space 18

15 Space -- -- 0 VA 0 VA -- -- Space 16

13 Space -- -- 0 VA 0 VA -- -- Space 14

11 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 12

9 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 10

7 UV LTG - RTU-22 20 A 1 180 VA 180 VA 1 20 A UV LTG - RTU-12 8

5 RTU-22 Rec 20 A 1 180 VA 180 VA 1 20 A RTU-12 Rec 6

3 UV LTG - RTU-11 20 A 1 180 VA 180 VA 1 20 A UV LTG - RTU-21 4

1 RTU-11 Rec 20 A 1 180 VA 180 VA 1 20 A RTU-21 Rec 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 120/208 Wye-3PH-4W Mains Rating: 100 A Supply From: LPDP Enclosure: Type 1 Mains Type: MLO

Location: Mounting: Surface A.I.C. Rating: 10KAIC

Panel: LPA

BLDG 4 PENTHOUSE

PANEL LPDP

(EXISTING) (EXISTING)(NEW)

45.00 kVA

TOTAL CONNECTED ESTIMATED DEMAND

Notes:

Total Est. Demand: 54 A

Total Conn.: 54 A

Total Est. Demand: 45 kVA

Total Conn. Load: 45 kVA

Spare 45000 VA 100.00% 45000 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 15.00 kVA 15.00 kVA 15.00 kVA

17 Space -- -- 0 VA 0 VA -- -- Space 18

15 Space -- -- 0 VA 0 VA -- -- Space 16

13 Space -- -- 0 VA 0 VA -- -- Space 14

11 Space -- -- 0 VA 0 VA -- -- Space 12

9 Space -- -- 0 VA 0 VA -- -- Space 10

7 Space -- -- 0 VA 0 VA -- -- Space 8

5 -- -- -- 1500... 0 VA -- -- -- 6

3 -- -- -- 1500... 0 VA -- -- -- 4

1 ELEV XFMR 70 A 3 1500... 0 VA 3 60 A Spare 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 480/277 Wye-3PH-4W Mains Rating: 250 A Supply From: Enclosure: Type 1 Mains Type: MCB

Location: Mounting: Surface A.I.C. Rating: 22KA

Panel: 4-MHDP

BLDG 4 - B10 MECHANICAL RM

XFMR 4-T2

(NEW)

05/15/2024 106

1 2 3 4 5 6 7 8 9 10 11

CRAWL SPACE

UP

B09A

B08

CRAWL SPACE

B08F B09 B0-C1

B07E

B07 B06 B05 B04 B03

B09B

OPEN TO BELOW

DN

CRAWL SPACE

A02

SPSPSP

AP

S

N

SR SR1

AHU 4-HV-2

SR-32,34,36 1

TYP.

TYP.

PUMP 4P-2

PUMP 4P-1

TYP.

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

P: 937-224-0861 www.heapy.com

PROJECT NO.

U.S. Department of Veterans Affairs

CONSULTANTS:

Revisions:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

REMOVE AND REPLACE AHU-4

589A-22-106 o n e e ig h th in c h o n e fo o t

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM

08-6231 1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Date:

ARCHITECT/ENGINEERS:

DESIGN-AIRE ENGINEERING, INC.

www.daengineering.comwww.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

COLMERY-O'NEIL VAMC

2200 SW GAGE BLVD. - TOPEKA, KS 66622

FULLY SPRINKLERED

4-ED-1B1

JASMSG

CONSTRUCTION DOCUMENTS

2022-05156

ELECTRICAL DEMOLITION PLAN

BASEMENT FLOOR B WING

ELECTRICAL DEMOLITION PLAN BASEMENT FLOOR B WING

KEYPLAN - B WING

NOTES

1 DISCONNECT AND REMOVE FEED FROM PANEL.

2 REMOVE STARTER AND DISCONNECT FOR AHU.

3 REMOVE ELECTRICAL POWER AND CONTROL CONNECTION TO AHU..

4 EXISTING RECESSED CORRIDOR LIGHTING SHALL BE REMOVED.

MAINTAIN EXISTING LIGHTING CIRCUIT FOR NEW LIGHTING LAYOUT.

REFER TO SHEET 4-EL-1B1.

6 ACT TILED CEILING SHALL BE REMOVED. REMOVE SIGNAL DEVICES

FROM CEILING FOR RELOCATION INTO NEW CEILING. SUPPORT FROM

STRUCTURE ABOVE AND MAINTAIN OPERATION TO DEVICE.

7 REMOVE DUCT SMOKE DETECTORS AND CONNECTIONS TO FIRE

ALARM SYSTEM. ADJUST FA PROGRAMMING ACCORDINGLY.

8 REMOVE FORMER CHILLER DISCONNECT SWITCH. REMOVE SERVICE

CONDUCTORS FROM TRANFORMER (GRADE…

This is the start of the file's text. The full file is on GovTribe.