Attachment 4 - Project 550-25-108 - Asbestos HazMat 65 Submission - Feb. 2025.pdf
PDF 3 MB Posted
- Solicitation number
- 36C25227R0001
About this file
This is an Asbestos & Hazmat Testing Report for a 65% construction document submission related to bathroom renovation work at VA Illiana Healthcare System in Danville, Illinois (VA Project 550-25-108). The report documents findings from testing conducted on February 7, 2025, by inspector Brett Brumbaugh of Castle Hill Associates.
The testing identified asbestos-containing materials (ACM) requiring removal in both Building 103 and Building 72. In Building 103, approximately 128 mud fittings on domestic water line insulation in restroom pipe chases and ceiling plenums tested positive for 10% chrysotile asbestos. In Building 72, 6 mud fittings in Room 6A storage and 30 linear feet of pipe insulation on steam lines tested positive for chrysotile asbestos, along with 3 window units containing 3% chrysotile asbestos in glazing and caulking. Lead-based paint components were also identified: 9,680 square feet of tan ceramic wall tile in Building 103 restrooms tested positive for lead (13.8-14.7 mg/cm²), and Building 72 contained lead-based paint on 3 window units and 4 doors/frames. The cost estimate for asbestos removal, testing, and lead paint handling totals $24,500.00, including OSHA testing, Virginia VPIH air monitoring, and contractor overhead with prevailing wage rates for Danville, Illinois. The inspector holds a current Illinois Asbestos Inspector License (#100-09972) and EPA Lead Paint Risk Assessor certification (#LBP-R-I216003-1). Laboratory analysis was performed by Eurofins Built Environment Testing Central, LLC (NVLAP Lab Code 600194-0), which is accredited for asbestos fiber analysis to ISO/IEC 17025:2017.
View the file
Other files
Show all 39
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ASBESTOS & HAZMAT TESTING REPORT FOR 65% SUBMISSION
VA ILLIANA HCS, DANVILLE, IL - RENOVATE BATHROOMS IN B103 PRRTP & B64/72
VA PROJECT 550-25-108
FEBRUARY 2025
Date: February 16, 2025
Items: Summary Results of Asbestos/HazMat Survey, Visual Inspection, Lab Results
Inspector: Brett Brumbaugh, Castle Hill Associates
BUILDING 103
Asbestos Containing Materials Locations Quantity
Pipe insulation mud fittings on domestic water lines
Restroom pipe chases and ceiling plenums in 106B, 106C, 107B, 107C, 136C, 159C, and 160C
~128 fittings
LEAD-BASED PAINT COMPONENTS
Lead Containing Components Locations Quantity
Tan ceramic wall tile Restrooms 106B, 106C, 107B, 107C, 136C, 159C, and 160C
9,680 sf
BUILDING 72
Pipe insulation mud fittings on domestic water lines
Room 6A storage/mech. 6 fittings
Pipe insulation on steam lines Loft above Rooms 6 and 6A 30 linear feet
Window glazing & caulking on metal window units Room 6 and 6A windows 3 window units (5’x6’)
LEAD-BASED PAINT COMPONENTS
Lead Based Paint Components Locations Quantity
Window frames on metal window units (interior and exterior paint)
Rooms 6 and 6A exterior windows 3 window units (5’x6’)
Wood doors and door frames Rooms 5, 6, 6A, and 7 4 doors & frames
ASBESTOS & HAZMAT COST ESTIMATE
Estimator: Brett Brumbaugh
Notes: Based on 2025/26 construction and bidding
EXCLUDES:
• Overtime or shift work.
INCLUDES:
• Bonds, insurance, contractor overhead and profit
• Prevailing wage rates for Danville, IL
Cost Index: Danville, IL
Description Material Quantity Unit Cost Amount
Section 02 82 11
Asbestos Removal Pipe insulation mud fittings 134 75.00 $10,050.00
Pipe insulation on steam lines 30 55.00 $1,650.00
Window glazing on metal window units 3 1000.00 $3,000.00
Asbestos OSHA Testing CPIH (day) 3 1400.00 $4,200.00
Asbestos VA VPIH Air Monitoring (day) 3 1400.00 $4,200.00
Lead Paint Handling OSHA Testing (day) 1 1400.00 $1,400.00
TOTAL COSTS $24,500.00
ASBESTOS & HAZMAT TESTING REPORT
65% SUBMISSION
LOCATION:
VA ILLIANA HCS - DANVILLE, IL
1900 E. MAIN ST.
DANVILLE, IL 61832
PROJECT:
RENOVATE BATHROOMS IN B103 PRRTP & B64/72
VA PROJECT #: 550-25-108
SAMPLING DATE:
FEBRUARY 7, 2022
CONSULTANT:
CASTLE HILL ASSOCIATES, LLC
1197 FARNSWORTH RD., UNIT E
WATERVILLE, OH 46566
567-952-0212 www.CASTLEHILLASSOCIATES.com http://www.castlehillassociates.com/
ASBESTOS & HAZMAT TESTING REPORT FOR 65% SD SUBMISSION
TABLE OF CONTENTS
• ASBESTOS & LEAD PAINT SAMPLING SUMMARY
• ABESTOS BULK SAMPLING DESCRIPTIONS AND LAB RESULTS
• LEAD SAMPLING DESCRIPTIONS AND RESULTS
• ASBESTOS LABORATORY REPORT
• INSPECTOR & ASBESTOS LABORATORY CERTIFICATIONS
ASBESTOS & LEAD TESTING SUMMARY
On February 7, 2025, Brett Brumbaugh performed asbestos and lead-based paint testing in Buildings 103 and 72 at the Danville VA Medical Center in Danville, IL in preparation of the renovations in 8 bathrooms in the buildings.
As part of this inspection, the previous asbestos testing conducted by Castle Hill Associates in 2018 were utilized to assist in developing this report. Castle Hill conducted this survey for the VA and sampled all suspect materials in the building. Asbestos was found during that survey in both buildings.
ASBESTOS INSPECTION FINDINGS
As a result of this inspection, testing, and laboratory analyses, it has been determined that asbestos is present in the renovation areas of B103 and B72 as follows:
water lines
Restroom pipe chases and ceiling plenums in 106B, 106C, 107B, 107C, 136C, 159C, and 160C
~128 fittings water lines
Room 6A storage/mech. 6 fittings
Pipe insulation on steam lines Loft above Rooms 6 and 6A 30 linear feet
Window glazing & caulking on metal window units
Room 6 and 6A windows 3 window units (5’x6’)
LEAD-BASED PAINT COMPONENT FINDINGS
As a result of this inspection and XRF testing, the following lead-based paint components are present in the 2 buildings:
Lead Containing Components Locations Quantity
Tan ceramic wall tile Restrooms 106B, 106C, 107B, 107C, 136C, 159C, and 160C
9,680 sf
Lead Based Paint Components Locations Quantity
Window frames on metal window units (interior and exterior paint)
Rooms 6 and 6A exterior windows 3 window units (5’x6’)
Wood doors and door frames Rooms 5, 6, 6A, and 7 4 doors & frames
CONCLUSIONS/RECOMMENDATIONS
ASBESTOS: The asbestos containing materials identified in the renovation areas in both buildings must be removed by an Illinois licensed Asbestos Contractor in compliance with VA and US EPA asbestos regulations.
LEAD PAINT: Lead-based paint (LBP), lead coating building materials, and Lead-containing paint (LCP) is not required to be removed prior to renovation or demolition. According to the OSHA Lead in Construction Standard (1926.62), anyone who might create a dust by disturbing paint with any concentration of lead are required to conduct an initial exposure assessment of their workers or rely on historical data from a previous project to determine whether the action level (30 ug/m3) for airborne Pb will be exceeded during the project. All other requirements of the OSHA Lead standard would also apply to the contractors who will disturb the paint during renovation or demolition.
Inspector, Brett L. Brumbaugh, REPA, CESCO
State of Illinois Asbestos Inspector - License # 100-09972 EPA Lead Paint Risk Assessor - EPA License # LBP-R-I216003-1
ASBESTOS BULK SAMPLE DESCRIPTIONS & RESULTS
Site: Danville VA Medical Center – Danville, IL
Buildings: Renovate Bathrooms in B103 PRRTP & B72
Project: VA Project 550-25-108
Sampled: February 7, 2025
Inspector: Brett L. Brumbaugh
Analysis: February 13, 2025
Laboratory: Eurofins Built Environment Testing Central, LLC - Naperville, IL
SAMPLE
BLDG. ROOM MATERIAL ASBESTOS CONTENT
1 103 159C restroom Ceramic wall tile grout No Asbestos Detected
2 103 136C restroom Ceramic wall tile grout No Asbestos Detected
3 103 106C restroom Ceramic wall tile grout No Asbestos Detected
4 103 159C restroom Ceramic wall tile adhesive No Asbestos Detected
5 103 136C restroom Ceramic wall tile adhesive No Asbestos Detected
6 103 106C restroom Ceramic wall tile adhesive No Asbestos Detected
7 103 159C restroom Ceramic floor tile grout No Asbestos Detected
8 103 136C restroom Ceramic floor tile grout No Asbestos Detected
9 103 106C restroom Ceramic floor tile grout No Asbestos Detected
10 103 159C restroom 2x4 lay-in ceiling tile No Asbestos Detected
11 103 136C restroom 2x2 lay-in ceiling tile No Asbestos Detected
12 103 106C restroom 2x2 lay-in ceiling tile No Asbestos Detected
13 103 159C restroom Mud fitting of FG insulated water line 10% Chrysotile Asbestos
14 103 136C restroom Mud fitting of FG insulated water line 10% Chrysotile Asbestos
15 103 106C restroom Mud fitting of FG insulated water line 10% Chrysotile Asbestos
16 103 159C restroom Caulking on sink counter No Asbestos Detected
17 103 136C restroom Caulking on sink counter No Asbestos Detected
18 103 106C restroom Caulking on sink counter No Asbestos Detected
19 103 159C restroom Brown cove base and mastic No Asbestos Detected
20 103 136C restroom Brown cove base and mastic No Asbestos Detected
21 103 106C restroom Brown cove base and mastic No Asbestos Detected
22 72 6A-72 storage room Window glazing (interior) 3% Chrysotile Asbestos
23 72 6-72 restroom Window glazing (interior) 3% Chrysotile Asbestos
24 72 6-72 restroom Window glazing (interior) 3% Chrysotile Asbestos
25 72 6A-72 storage room Exterior window frame caulking 3% Chrysotile Asbestos
26 72 6-72 restroom Exterior window frame caulking 3% Chrysotile Asbestos
27 72 6-72 restroom Exterior window frame caulking 3% Chrysotile Asbestos
ASBESTOS LABORATORY REPORT
Approved by:
Laboratory Manager Itzel Cuellar
Report for:
Mr. Brett Brumbaugh, REPA Castle Hill Associates PO Box 283 Waterville, OH 43566
Regarding:
Eurofins Built Environment Testing Central, LLC Project: Danville VAMC; B72 & 103 Renovate Restrooms
EML ID: 3941215
All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. The results relate only to the samples as received and tested. The results include an inherent uncertainty of measurement associated with estimating percentages by polarized light microscopy. Measurement uncertainty data for sample results with >1% asbestos concentration can be provided when requested.
Eurofins Built Environment Testing Central, LLC ("the Company"), a member of the Eurofins Built Environment Testing group of companies, shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results. In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor.
Dates of Analysis:
Asbestos PLM: 02-11-2025
Service SOPs: Asbestos PLM (EPA 40CFR App E to Sub E of Part 763 & EPA METHOD 600/R-93-116, SOP EM-AS-S-1267) NVLAP Lab Code 600194-0
EMLab ID: 3941215, Page 1 of 9Eurofins Built Environment Testing Central, LLC
Eurofins Built Environment Testing Central, LLC 1815 West Diehl Road, Suite 800, Naperville, IL 60563
(866) 871-1984 www.eurofinsus.com/BuiltClient: Castle Hill Associates C/O: Mr. Brett Brumbaugh, REPA Re: Danville VAMC; B72 & 103 Renovate Restrooms
Date of Sampling: 02-07-2025 Date of Receipt: 02-10-2025 Date of Report: 02-13-2025
ASBESTOS PLM REPORT
Total Samples Submitted: 27 Total Samples Analyzed: 27
Total Samples with Layer Asbestos Content > 1%: 9
Location: 1, Cer. Wall Tile Grout Lab ID-Version‡: 19566949-1
Sample Layers Asbestos Content White Grout ND
Sample Composite Homogeneity: Moderate
Location: 2, Cer Wall Tile Grout Lab ID-Version‡: 19566950-1
Sample Layers Asbestos Content White Grout ND
Sample Composite Homogeneity: Moderate
Location: 3, Cer. Wall Tile Grout Lab ID-Version‡: 19566951-1
Sample Layers Asbestos Content White Grout ND
Sample Composite Homogeneity: Moderate
Location: 4, Cer Wall Tile Glue Lab ID-Version‡: 19566952-1
Sample Layers Asbestos Content Beige Glue with White Compound (Trace) ND
Sample Composite Homogeneity: Moderate
EMLab ID: 3941215, Page 2 of 9Eurofins Built Environment Testing Central, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
(866) 871-1984 www.eurofinsus.com/BuiltClient: Castle Hill Associates C/O: Mr. Brett Brumbaugh, REPA Re: Danville VAMC; B72 & 103 Renovate Restrooms
Date of Sampling: 02-07-2025 Date of Receipt: 02-10-2025 Date of Report: 02-13-2025
ASBESTOS PLM REPORT
Location: 5, Cer Wall Tile Glue Lab ID-Version‡: 19566953-1
Sample Layers Asbestos Content Beige Glue with White Compound (Trace) ND
Sample Composite Homogeneity: Moderate
Location: 6, Cer Wall Tile Glue Lab ID-Version‡: 19566954-1
Sample Layers Asbestos Content Beige Glue with White Compound (Trace) ND
Sample Composite Homogeneity: Moderate
Location: 7, Cer. Floor Tile Grout Lab ID-Version‡: 19566955-1
Sample Layers Asbestos Content White Grout ND
Sample Composite Homogeneity: Moderate
Location: 8, Cer. Floor Tile Grout Lab ID-Version‡: 19566956-1
Sample Layers Asbestos Content White Grout ND
Sample Composite Homogeneity: Moderate
EMLab ID: 3941215, Page 3 of 9Eurofins Built Environment Testing Central, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/BuiltClient: Castle Hill Associates C/O: Mr. Brett Brumbaugh, REPA Re: Danville VAMC; B72 & 103 Renovate Restrooms
Date of Sampling: 02-07-2025 Date of Receipt: 02-10-2025 Date of Report: 02-13-2025
ASBESTOS PLM REPORT
Location: 9, Cer. Floor Tile Grout Lab ID-Version‡: 19566957-1
Sample Layers Asbestos Content White Grout ND
Sample Composite Homogeneity: Moderate
Location: 10, 2x2 Ceil Tile Lab ID-Version‡: 19566958-1
Sample Layers Asbestos Content Gray Ceiling Tile with White Surface ND
Composite Non-Asbestos Content: 40% Cellulose 40% Glass Fibers
Sample Composite Homogeneity: Moderate
Location: 11, 2x2 Ceil Tile Lab ID-Version‡: 19566959-1
Sample Layers Asbestos Content Gray Ceiling Tile with White Surface ND
Composite Non-Asbestos Content: 40% Cellulose 40% Glass Fibers
Sample Composite Homogeneity: Moderate
Location: 12, 2x2 Ceil Tile Lab ID-Version‡: 19566960-1
Sample Layers Asbestos Content Gray Ceiling Tile with White Surface ND
Composite Non-Asbestos Content: 40% Cellulose 40% Glass Fibers
Sample Composite Homogeneity: Moderate
EMLab ID: 3941215, Page 4 of 9Eurofins Built Environment Testing Central, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/BuiltClient: Castle Hill Associates C/O: Mr. Brett Brumbaugh, REPA Re: Danville VAMC; B72 & 103 Renovate Restrooms
Date of Sampling: 02-07-2025 Date of Receipt: 02-10-2025 Date of Report: 02-13-2025
ASBESTOS PLM REPORT
Location: 13, Mud Fittings on FGI TSI Lab ID-Version‡: 19566961-1
Sample Layers Asbestos Content Gray Insulation 10% Chrysotile
Sample Composite Homogeneity: Moderate
Location: 14, Mud Fittings on FGI TSI Lab ID-Version‡: 19566962-1
Sample Layers Asbestos Content Gray Insulation 10% Chrysotile
Sample Composite Homogeneity: Moderate
Location: 15, Mud Fittings on FGI TSI Lab ID-Version‡: 19566963-1
Sample Layers Asbestos Content Gray Insulation 10% Chrysotile
Sample Composite Homogeneity: Moderate
Location: 16, Sink Counter Caulk Lab ID-Version‡: 19566964-1
Sample Layers Asbestos Content White Caulk ND
Sample Composite Homogeneity: Good
EMLab ID: 3941215, Page 5 of 9Eurofins Built Environment Testing Central, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/BuiltClient: Castle Hill Associates C/O: Mr. Brett Brumbaugh, REPA Re: Danville VAMC; B72 & 103 Renovate Restrooms
Date of Sampling: 02-07-2025 Date of Receipt: 02-10-2025 Date of Report: 02-13-2025
ASBESTOS PLM REPORT
Location: 17, Sink Counter Caulk Lab ID-Version‡: 19566965-1
Sample Layers Asbestos Content White Caulk ND
Sample Composite Homogeneity: Good
Location: 18, Sink Counter Caulk Lab ID-Version‡: 19566966-1
Sample Layers Asbestos Content White Caulk ND
Sample Composite Homogeneity: Good
Location: 19, Cove Base Lab ID-Version‡: 19566967-1
Sample Layers Asbestos Content Black Cove Base ND Yellow Adhesive ND
Sample Composite Homogeneity: Moderate
Location: 20, Cove Base Lab ID-Version‡: 19566968-1
Sample Layers Asbestos Content Black Cove Base ND Yellow Adhesive ND
Sample Composite Homogeneity: Moderate
EMLab ID: 3941215, Page 6 of 9Eurofins Built Environment Testing Central, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/BuiltClient: Castle Hill Associates C/O: Mr. Brett Brumbaugh, REPA Re: Danville VAMC; B72 & 103 Renovate Restrooms
Date of Sampling: 02-07-2025 Date of Receipt: 02-10-2025 Date of Report: 02-13-2025
ASBESTOS PLM REPORT
Location: 21, Cove Base Lab ID-Version‡: 19566969-1
Sample Layers Asbestos Content Black Cove Base ND Yellow Adhesive ND
Sample Composite Homogeneity: Moderate
Location: 22, Window Glazing Lab ID-Version‡: 19566970-1
Sample Layers Asbestos Content Off-White Window Glazing 3% Chrysotile
Sample Composite Homogeneity: Moderate
Location: 23, Window Glazing Lab ID-Version‡: 19566971-1
Sample Layers Asbestos Content Off-White Window Glazing 3% Chrysotile
Sample Composite Homogeneity: Moderate
Location: 24, Window Glazing Lab ID-Version‡: 19566972-1
Sample Layers Asbestos Content Off-White Window Glazing 3% Chrysotile
Sample Composite Homogeneity: Moderate
EMLab ID: 3941215, Page 7 of 9Eurofins Built Environment Testing Central, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/BuiltClient: Castle Hill Associates C/O: Mr. Brett Brumbaugh, REPA Re: Danville VAMC; B72 & 103 Renovate Restrooms
Date of Sampling: 02-07-2025 Date of Receipt: 02-10-2025 Date of Report: 02-13-2025
ASBESTOS PLM REPORT
Location: 25, Window Caulk Lab ID-Version‡: 19566973-1
Sample Layers Asbestos Content Off-White Caulk 3% Chrysotile
Sample Composite Homogeneity: Moderate
Location: 26, Window Caulk Lab ID-Version‡: 19566974-1
Sample Layers Asbestos Content Off-White Caulk 3% Chrysotile
Sample Composite Homogeneity: Moderate
Location: 27, Window Caulk Lab ID-Version‡: 19566975-1
Sample Layers Asbestos Content Off-White Caulk 3% Chrysotile
Sample Composite Homogeneity: Moderate
EMLab ID: 3941215, Page 8 of 9Eurofins Built Environment Testing Central, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
All components not quantified as asbestos content and non-asbestos content are considered to be non-fibrous matrix components. Matrix components may include, but are not limited to, gypsum, paint, silicate minerals, vinyl, binder, calcium carbonate, tar, and foam.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/BuiltClient: Castle Hill Associates C/O: Mr. Brett Brumbaugh, REPA Re: Danville VAMC; B72 & 103 Renovate Restrooms
Date of Sampling: 02-07-2025 Date of Receipt: 02-10-2025 Date of Report: 02-13-2025
ASBESTOS PLM REPORT
PROJECT ANALYST AND SIGNATORY REPORT
Project Analyst
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
Analyst: Avery Raica
EMLab ID: 3941215, Page 9 of 9Eurofins Built Environment Testing Central, LLC
PHOTOGRAPHS OF ASBESTOS MATERIALS
Photo 1 Asbestos mud fittings on fiberglass insulated pipes above ceiling tile in
B72
Photo 2
Asbestos mud fittings in B72 6A storage room
Photo 3 Interior window glazing on metal windows in B72
Photo 4 Exterior window caulk on metal windows in B72
LEAD XRF TESTING DATA
LEAD PAINT XRF TESTING DATA AND RESULTS
Danville VA Medical Center – Danville, IL
Renovate Bathrooms in B103 PRRTP & B72
VA Project 550-25-108
Brett Brumbaugh
Viken Detection Model Pb200i - SN 2757
Reading # Bldg. # Room Building Area/Room Component Paint Color Substrate Pb Conc.
mg/cm2 Result
1 103 159C Restroom Wall Tan Ceramic tile 14.7 POSITIVE
2 103 159C Restroom Door Tan Metal 0.1 Negative
3 103 159C Restroom Door frame Tan Metal 0.2 Negative
4 103 159C Restroom Stall divider Tan Metal 0.2 Negative
5 103 159C Restroom Roof truss Red Metal 0.3 Negative
6 103 159C Restroom Floor Tan Ceramic tile 0.1 Negative
7 103 159C Restroom storage Door frame Tan Metal 0.1 Negative
8 103 159C Restroom storage Door Tan Metal 0.2 Negative
9 103 160C Restroom Wall Tan Ceramic tile 14.7 POSITIVE
10 103 160C Restroom Door Tan Metal 0.1 Negative
11 103 160C Restroom Door frame Tan Metal 0.2 Negative
12 103 160C Restroom Stall divider Tan Metal 0.2 Negative
13 103 160C Restroom Roof truss Red Metal 0.3 Negative
14 103 160C Restroom Floor Tan Ceramic tile 0.1 Negative
15 103 136C Restroom Wall Tan Ceramic tile 13.8 POSITIVE
16 103 136C Restroom Door Tan Metal 0.1 Negative
17 103 136C Restroom Door frame Tan Metal 0.2 Negative
18 103 136C Restroom Stall divider Tan Metal 0.2 Negative
19 103 136C Restroom Roof truss Red Metal 0.3 Negative
20 103 136C Restroom Floor Tan Ceramic tile 0.1 Negative
21 103 106C Restroom storage Door frame Tan Metal 0.1 Negative
22 103 106C Restroom storage Door Tan Metal 0.2 Negative
23 103 106C Restroom Wall Tan Ceramic tile 14.2 POSITIVE
24 103 106C Restroom Door Tan Metal 0.1 Negative
25 103 106C Restroom Door frame Tan Metal 0.2 Negative
26 103 106C Restroom Stall divider Tan Metal 0.2 Negative
27 103 106C Restroom Roof truss Red Metal 0.3 Negative
28 103 106C Restroom Floor Tan Ceramic tile 0.1 Negative
29 103 107C Restroom storage Door frame Tan Metal 0.1 Negative
30 103 107C Restroom storage Door Tan Metal 0.2 Negative
31 103 107C Restroom Wall Tan Ceramic tile 14.4 POSITIVE
32 103 107C Restroom Door Tan Metal 0.1 Negative
33 103 107C Restroom Door frame Tan Metal 0.2 Negative
34 103 107C Restroom Stall divider Tan Metal 0.2 Negative
35 103 107C Restroom Roof truss Red Metal 0.3 Negative
36 103 107C Restroom Floor Tan Ceramic tile 0.1 Negative
37 103 106B Restroom Wall Tan Ceramic tile 14.5 POSITIVE
38 103 106B Restroom Door Tan Metal 0.1 Negative
39 103 106B Restroom Door frame Tan Metal 0.2 Negative
40 103 106B Restroom Stall divider Tan Metal 0.2 Negative
41 103 106B Restroom Roof truss Red Metal 0.3 Negative
42 103 106B Restroom Floor Tan Ceramic tile 0.1 Negative
43 103 106B Restroom storage Door frame Tan Metal 0.1 Negative
44 103 107B Restroom storage Door Tan Metal 0.2 Negative
45 103 107B Restroom Wall Tan Ceramic tile 14.1 POSITIVE
46 103 107B Restroom Door Tan Metal 0.1 Negative
47 103 107B Restroom Door frame Tan Metal 0.2 Negative
48 103 107B Restroom Stall divider Tan Metal 0.2 Negative
49 103 107B Restroom Roof truss Red Metal 0.3 Negative
XRF Info:
Inspector:
February 7, 2025
Project Name:
Location:
Project Number:
Date:
LEAD PAINT XRF TESTING DATA AND RESULTS
Danville VA Medical Center – Danville, IL
Renovate Bathrooms in B103 PRRTP & B72
VA Project 550-25-108
Brett Brumbaugh
Viken Detection Model Pb200i - SN 2757
Reading # Bldg. # Room Building Area/Room Component Paint Color Substrate Pb Conc.
mg/cm2 Result
XRF Info:
Inspector:
February 7, 2025
Project Name:
Location:
Project Number:
Date:
50 103 107B Restroom Floor Tan Ceramic tile 0.1 Negative
51 103 107B Restroom storage Door frame Tan Metal 0.1 Negative
52 103 107B Restroom storage Door Tan Metal 0.2 Negative
53 103 107B Restroom Wall Tan Ceramic tile 14.7 POSITIVE
54 103 107B Restroom Door Tan Metal 0.1 Negative
55 72 6A-72 Storage Window frame Tan Metal 7.7 POSITIVE
56 72 6A-72 Storage Window frame (ext.) Tan Metal 8.3 POSITIVE
57 72 6A-72 Storage Block wall Tan Block 0.3 Negative
58 72 6A-72 Storage Concrete wall Tan Concrete 0.4 Negative
59 72 6A-72 Storage Door frame Tan Wood 6.8 POSITIVE
60 72 6A-72 Storage Door Tan Wood 5.7 POSITIVE
61 72 6-72 Restroom Window frame (ext.) Tan Metal 8.3 POSITIVE
62 72 6-72 Restroom Window sill Tan Concrete 0.4 Negative
63 72 6-72 Restroom Stall divider Tan Metal 0.1 Negative
64 72 5-72 Storage Block wall Tan Block 0.3 Negative
65 72 7-72 Locker room Block wall Tan Block 0.2 Negative
66 72 7-72 Locker room Door frame Tan Wood 7.2 POSITIVE
67 72 7-72 Locker room Floor Gray Concrete 0.1 Negative
NOTE: Any XRF reading equal to or greater than 1.0 mg/cm2 is considered to be lead-based paint (LBP) per EPA
NOTE: Any XRF reading greater than 0.0 mg/cm2 is considered to be lead-containing paint (LCP) per OSHA
INSPECTOR CERTIFICATIONS
LAB CERTIFICATIONS