A0003 - VA 695-24-107 Addendum 03 Combined Drawing SetPart-2.pdf

PDF 6 MB Posted

Attached to
Z1DA--Project 695-24-107 Replace Boilers 4 and 5 Clement J. Zablocki, VA Medical Center 5000 West National Avenue Milwaukee, WI 53295
Solicitation number
36C25227B0001
Issued by

About this file

This document is a comprehensive set of bid documents for the Replace Boilers 4 & 5 project at the U.S. Department of Veterans Affairs facility located at 5000 W. National Ave., Milwaukee, Wisconsin. The project is identified as Project Number 695-24-107, Building Number 112, with an issue date of April 20, 2026, and includes Revision 1 (Addendum 03) dated November 4, 2026, with an expiration date of January 31, 2028.

The bid documents include detailed architectural and mechanical drawings, process and instrumentation diagrams (P&IDs), and mechanical schedules covering the complete demolition of existing boiler infrastructure and installation of new equipment. The scope requires contractor demolition and removal of existing boiler units, associated piping, support structures, and exhaust stacks, with specific requirements to salvage framing members for later reinstallation. Installation work includes a new 600 HP steam boiler (Cleaver-Brooks CBLE-200-600-250ST, Unit 112-105-BLR-005) rated for 250 PSI with 30 PPM NOx emissions capability, capable of burning natural gas or No. 2 fuel oil. Supporting equipment includes an economizer (Cleaver-Brooks CRE-48G), three chemical feed pumps, two vortex flow meters for steam metering, safety relief valves, steam traps, and all necessary fuel oil, natural gas, feedwater, condensate, and compressed air piping systems. The contract includes coordination with existing Boiler 4, requiring connection of the new Boiler 5 to the existing steam header and integration with existing building systems. The facility is marked as "NOT SPRINKLERED" and drawings indicate phased work with coordination requirements across multiple trades including electrical and HVAC systems.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FIRST FLOOR LEVEL

71' - 0"

MID ROOF LEVEL

94' - 9"

/1 AD105

2 2

20' - 0" REF 20' - 0" REF 20' - 0" REF

C8 x1

1.5 (E

C8 x1 1.5

(E

C8x11.5 (E)

C8x11.5 (E)

C8 x1

1.5 (E

C8x11.5 (E) W10x21 (E)

C8 x1

1.5 (E

C8 x1

1.5 (E

C8 x1

1.5 (E

L3x3x1/4 (E) L3x3x1/4 (E)L3x3x1/4 (E) L3x3x1/4 (E) L3x3x1/4 (E) L3x3x1/4 (E)

L3x3x1/4 (E)L3x3x1/4 (E) L3x3x1/4 (E)L3x3x1/4 (E)L3x3x1/4 (E)L3x3x1/4 (E)

W10x25 (E) W10x21 (E)

L2 1/2x2 1/2x5/16 (E) L2 1/2x2 1/2x5/16 (E)C8 x1

1.5 (E

L2 1/2x2 1/2x5/16 (E) L2 1/2x2 1/2x5/16 (E)C8 x1

1.5 (E

C8x11.5 (E) C8x11.5 (E)

W 8x

(E

W 8x

(E

W 8x

(E

W 8x

(E

L2 1/

2x 2 1

/2x 5/1

6 ( E)

L2 1/2x2 1/2x5/16 (E)

L2 1/2x2 1/2x5/16 (E)

L2 1/

2x 2 1

/2x 5/1

6 ( E)

L2 1/2x2 1/2x5/16 (E)

L2 1/

2x 2 1

/2x 5/1

6 ( E)

L2 1/2x2 1/2x5/16 (E) L2

1/ 2x

2 1 /2x

5/1 6 (

E)

C8 x1

1.5 (E

C8 x1

1.5

C8 x1

1.5 (E

C8x11.5

(E

C8 x1

1.5 (E

C8x11.5 (E)C8x11.5 (E) C8x11.5 (E) C8x11.5 (E) C8x11.5 (E) C8x11.5 (E)C8x11.5 (E)

C8 x1

1.5 (E

C8 x1

1.5 (E

C8 x1

1.5 (E

C8 x1 1.5

(E

TOS TOP OF STAIR

ABBREVIATIONS:

23 MECHANIC STREET, SPRINGVILLE, NY 14141

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD "Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".CONSULTANT

321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"

6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t

6"

6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t

BID DOCUMENTS REPLACE BOILERS 4 & 5

5000 W. NATIONAL AVE

MILWAUKEE, WI 53295

695-24-107

2026-04-20

CERTIFICATION OF AUTHORIZATION NUMBER: 0023683

AD305

ARCHITECTURAL BID DEDUCT

DEMOLITION BUILDING SECTION 112

ANL ADL

NOT SPRINKLERED

2. CONTRACTOR TO SALVAGE ALL REMOVED FRAMING FOR LATER REINSTALLATION.

1. SEE A-001 FOR A-SERIES NOTES AND LEGENDS.

GENERAL NOTES

SCALE: 3/8" = 1'-0"1 ARCHITECTURAL BID DEDUCTION DEMOLITION BUILDING SECTION

KEYED NOTES

1 4X4X3/8" L UNBOLTED FROM SLAB

2 REMOVE EXISITING STEEL

Revision: Date:

REV 0 - BID DOCUMENTS 2026-04-20

REV 1 - ADDENDUM 03 2026-11-04

Exp.: 01/31/2028 11/5/2026

E

D

C

20' - 0" REF 20' - 0" REF 20' - 0" REF

0" R

EF

0"

R

EF

AE501

AE301

AE201

NEW PLATFORM (BY

BOILER MANUFACTURER)

8622 SF

EAST BOILER ROOM

AE502

D105A

Room name

XXX SF

ROOM NAME, NUMBER, AND AREA

GENERAL SYMBOLS:

REF REFERENCE

SF SQUARE FOOT

ABBREVIATIONS:

23 MECHANIC STREET, SPRINGVILLE, NY 14141

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD "Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".CONSULTANT

321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"

6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t

6"

6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t

BID DOCUMENTS REPLACE BOILERS 4 & 5

5000 W. NATIONAL AVE

MILWAUKEE, WI 53295

695-24-107

2026-04-20

CERTIFICATION OF AUTHORIZATION NUMBER: 0023683

AE101

ARCHITECTURAL PLAN - FIRST

FLOOR LEVEL 112

JRF KRL

NOT SPRINKLERED

1. SEE A-001 FOR A-SERIES NOTES AND LEGENDS.

GENERAL NOTES

SCALE: 3/8" = 1'-0"1 ARCHITECTURAL PLAN - FIRST FLOOR LEVEL

N

N

KEYPLAN

20' - 0"20' - 0"20' - 0"

0"

0"

0"

0"

4321E ED DCBAUPUP

AREA OF WORK

KEYED NOTES

1 REINSTALL SALVAGED PANEL & FRAMING MEMBERS

2 CONTRACTOR TO INSTALL NEW INSULATED ROLLING SERVICE DOOR AND SECURITY

GRATE

Revision: Date:

REV 0 - BID DOCUMENTS 2026-04-20

D

C

20' - 0" REF 20' - 0" REF 20' - 0" REF

0" R

EF

0"

R

EF

AE205

8622 SF

EAST BOILER ROOM

NEW PLATFORM (BY

BOILER MANUFACTURER)

AE502

D105A

Room name

XXX SF

ROOM NAME, NUMBER, AND AREA

GENERAL SYMBOLS:

REF REFERENCE

SF SQUARE FOOT

ABBREVIATIONS:

23 MECHANIC STREET, SPRINGVILLE, NY 14141

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD "Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".CONSULTANT

321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"

6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t

6"

6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t

BID DOCUMENTS REPLACE BOILERS 4 & 5

5000 W. NATIONAL AVE

MILWAUKEE, WI 53295

695-24-107

2026-04-20

CERTIFICATION OF AUTHORIZATION NUMBER: 0023683

AE105

ARCHITECTURAL BID DEDUCT

PLAN - FIRST FLOOR LEVEL 112

JRF KRL

NOT SPRINKLERED

1. SEE A-001 FOR A-SERIES NOTES AND LEGENDS.

GENERAL NOTES

SCALE: 3/8" = 1'-0"1 ARCHITECTURAL BID DEDUCTION PLAN - FIRST FLOOR LEVEL

N

N

KEYPLAN

20' - 0"20' - 0"20' - 0"

0"

0"

0"

0"

4321E ED DCBAUPUP

AREA OF WORK

KEYED NOTES

1 CONTRACTOR TO INSTALL NEW INSULATED ROLLING SERVICE DOOR AND SECURITY

GRATE

Revision: Date:

REV 0 - BID DOCUMENTS 2026-04-20

D

C

MIDDLE ROOF AREA

20' - 0" REF 20' - 0" REF 20' - 0" REF

0" R

EF

0"

R

EF

EXISTING ROOF OPENING EXISTING CAPPED

ROOF OPENING

BOILER STACK GUY WIRE

ANCHOR LOCATION, TYP

AE501

AE1212

AE501

REF REFERENCE

TYP TYPICAL

ABBREVIATIONS:

EXISTING BOILER 5 STACK

OPENING TO BE CAPPED

EXISTING ROOF OPENING

TO BE REACTIVATED FOR

NEW BOILER 5 STACK

/1 AE121

23 MECHANIC STREET, SPRINGVILLE, NY 14141

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD "Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".CONSULTANT

321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"

6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t

6"

6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t

BID DOCUMENTS REPLACE BOILERS 4 & 5

5000 W. NATIONAL AVE

MILWAUKEE, WI 53295

695-24-107

2026-04-20

CERTIFICATION OF AUTHORIZATION NUMBER: 0023683

AE121

ARCHITECTURAL PLAN - ROOF

LEVEL 112

JRF KRL

NOT SPRINKLERED

2. ALL REMOVALS TO BE COORDINATED WITH MECHANICAL AND ELECTRICAL DRAWINGS.

1. SEE A-001 FOR A-SERIES NOTES AND LEGENDS.

GENERAL NOTES

SCALE: 3/8" = 1'-0"1 ARCHITECTURAL PLAN - ROOF LEVEL

N

N

KEYPLAN

20' - 0"20' - 0"20' - 0"

0"

0"

0"

0"

4321E ED DCBAUPUP

AREA OF WORK

KEYED NOTES

1 INSTALL NEW ROOF STACK. REFER TO DETAIL 1/AE-501

2 CONTRACTOR TO PATCH AND REPAIR EXISTING ROOF MEMBRANE AND MECHANICAL

CURB FOLLOWING ALL EQUIPMENT REMOVALS

3 CONTRACTOR TO INSTALL GUY WIRE ANCHORS FOR NEW BOILER STACK. REFER TO

DETAIL 9/AE501

SCALE: NTS2 EXISTING ROOF CONDITIONS

Revision: Date:

REV 0 - BID DOCUMENTS 2026-04-20

REF REFERENCE

TYP TYPICAL

ABBREVIATIONS:

E

D

C

MIDDLE ROOF AREA

20' - 0" REF 20' - 0" REF 20' - 0" REF

0" R

EF

0"

R

EF

EXISTING ROOF OPENINGEXISTING ROOF OPENING

BOILER STACK GUY WIRE

ANCHOR LOCATION, TYP

AE501

AE1212

AE501

EXISTING BOILER 5 STACK

OPENING TO BE CAPPED

EXISTING ROOF OPENING

TO BE REACTIVATED FOR

NEW BOILER 5 STACK

/1 AE125

23 MECHANIC STREET, SPRINGVILLE, NY 14141

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD "Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".CONSULTANT

321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"

6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t

6"

6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t

BID DOCUMENTS REPLACE BOILERS 4 & 5

5000 W. NATIONAL AVE

MILWAUKEE, WI 53295

695-24-107

2026-04-20

CERTIFICATION OF AUTHORIZATION NUMBER: 0023683

AE125

ARCHITECTURAL BID DEDUCT

PLAN - ROOF LEVEL 112

JRF KRL

NOT SPRINKLERED

2. ALL REMOVALS TO BE COORDINATED WITH MECHANICAL AND ELECTRICAL DRAWINGS.

1. SEE A-001 FOR A-SERIES NOTES AND LEGENDS.

GENERAL NOTES

N

N

KEYPLAN

20' - 0"20' - 0"20' - 0"

0"

0"

0"

0"

4321E ED DCBAUPUP

AREA OF WORK

KEYED NOTES

1 INSTALL NEW ROOF STACK. REFER TO DETAIL 1/AE-501

2 CONTRACTOR TO PATCH AND REPAIR EXISTING ROOF MEMBRANE AND MECHANICAL

CURB FOLLOWING ALL EQUIPMENT REMOVALS

3 CONTRACTOR TO INSTALL GUY WIRE ANCHORS FOR NEW BOILER STACK. REFER TO

DETAIL 9/AE501

SCALE: 3/8" = 1'-0"1 ARCHITECTURAL BID DEDUCTION PLAN - ROOF LEVEL

SCALE: NTS2 EXISTING ROOF CONDITIONS

Revision: Date:

REV 0 - BID DOCUMENTS 2026-04-20

4 3 2 1

MID ROOF LEVEL

94' - 9"

UPPER ROOF LEVEL

109' - 0"

-/+ 11' - 0" V.I.F.

/1 AE101

2'

- 6

" GUY WIRE

ATTACHMENT BAND

3"

6"

V .I.F

-/+ 12' - 7 1/2" V.I.F.

20' - 0" REF20' - 0" REF20' - 0" REF

9"

V .I.F

APPROXIMATE GRADE

D105A

23 MECHANIC STREET, SPRINGVILLE, NY 14141

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD "Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".CONSULTANT

321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"

6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t

6"

6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t

BID DOCUMENTS REPLACE BOILERS 4 & 5

5000 W. NATIONAL AVE

MILWAUKEE, WI 53295

695-24-107

2026-04-20

CERTIFICATION OF AUTHORIZATION NUMBER: 0023683

AE201

ARCHITECTURAL EXTERIOR

ELEVATION - NORTH 112

ANL ADL

NOT SPRINKLERED

SCALE: 3/8" = 1'-0"1 ARCHITECTURAL EXTERIOR ELEVATION - NORTH

1. SEE A-001 FOR A-SERIES NOTES AND LEGENDS.

GENERAL NOTES

KEYED NOTES

1 REPLACE SALVALGED WALL PANEL. CONTRACTROR TO REPAIR OR REPLACE ANY

COMPONENTS DAMAGED DURING REMOVAL PROCESS

2 CONTRACTOR TO INSTALL NEW INSULATED ROLLING SERVICE DOOR AND SECURITY

GRATE

Revision: Date:

REV 0 - BID DOCUMENTS 2026-04-20

4 3 2 1

MID ROOF LEVEL

94' - 9"

UPPER ROOF LEVEL

109' - 0"

/1 AE105

GUY WIRE

ATTACHMENT BAND

0" 2'

- 6

6"

V .I.F

-/+ 12' - 7 1/2" V.I.F.

APPROXIMATE GRADE

D105A

23 MECHANIC STREET, SPRINGVILLE, NY 14141

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD "Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".CONSULTANT

321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"

6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t

6"

6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t

BID DOCUMENTS REPLACE BOILERS 4 & 5

5000 W. NATIONAL AVE

MILWAUKEE, WI 53295

695-24-107

2026-04-20

CERTIFICATION OF AUTHORIZATION NUMBER: 0023683

AE205

ARCHITECTURAL BID DEDUCT

EXTERIOR ELEVATION - NORTH 112

ANL ADL

NOT SPRINKLERED

SCALE: 3/8" = 1'-0"1 ARCHITECTURAL BID DEDUCTION EXTERIOR ELEVATION - NORTH

1. SEE A-001 FOR A-SERIES NOTES AND LEGENDS.

GENERAL NOTES

KEYED NOTES

1 CONTRACTOR TO INSTALL NEW INSULATED ROLLING SERVICE DOOR AND SECURITY

GRATE

Revision: Date:

REV 0 - BID DOCUMENTS 2026-04-20

AE301

/1 AE101

W10x21 (E)

20' - 0" REF 20' - 0" REF 20' - 0" REF

L3x3x1/4 (E)L3x3x1/4 (E)

C8 x1

1.5

C8x11.5

L2 1/

2x 2 1

/2x 5/1

6 ( E)

C8x11.5 (E) C8x11.5 (E)

L2 1/2x2 1/2x5/16 (E)

C8x11.5 (E)

C8 x1

1.5 (E

C8 x1

1.5 (E

C8x11.5 (E)

L2 1/

2x 2 1

/2x 5/1

6 ( E)

L3x3x1/4 (E)L3x3x1/4 (E)

C8 x1

1.5 (E

C8 x1

1.5 (E

L2 1/2x2 1/2x5/16 (E)

L2 1/2x2 1/2x5/16 (E)L2 1/2x2 1/2x5/16 (E)

W10x25 (E)

C8 x1

1.5 (E

L2 1/

2x 2 1

/2x 5/1

6 ( E)

L2 1/2x2 1/2x5/16 (E) L2 1/

2x 2 1

/2x 5/1

6 ( E)

L2 1/2x2 1/2x5/16 (E)C8 x1

1.5

C8x11.5 (E) C8x11.5 (E)

C8 x1

1.5 (E

C8 x1

1.5 (E

L3x3x1/4 (E)

L3x3x1/4 (E) L3x3x1/4 (E)

L3x3x1/4 (E)

C8x11.5 (E) C8x11.5 (E)C8x11.5 (E)

C8 x1

1.5 (E

C8 x1 1.5

(E

C8 x1

1.5 (E

C8 x1

1.5 (E

C8x11.5 (E)C8x11.5 (E)

W 8x

(E

W 8x

(E

W 8x

(E

W 8x

(E

L2 1/2x2 1/2x5/16 (E) L2 1/2x2 1/2x5/16 (E)

C8 x1

1.5 (E

W10x21 (E)

AE301

6"

FIRST FLOOR LEVEL

71' - 0"

E

AE501

AE501

AE501

/3 AE301

TOS TOP OF STAIR

ABBREVIATIONS:

AE502

2'-4"

3'- 6"

1'-2 1/8"

3'-8 1/8"

5"

BENT STEEL PLATE JAMB

TO STRUCTURAL

FRAMING

OVERHEAD DOOR

OVERHEAD DOOR

ASSEMBLY

/3 AE301

OVERHEAD COILING

DOOR & GRILL TO BE

INSTALLED AS PER THE

MANUFACTURER'S

SPECIFICATIONS

/1 AE305

23 MECHANIC STREET, SPRINGVILLE, NY 14141

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD "Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".CONSULTANT

321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"

6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t

6"

6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t

BID DOCUMENTS REPLACE BOILERS 4 & 5

5000 W. NATIONAL AVE

MILWAUKEE, WI 53295

695-24-107

2026-04-20

CERTIFICATION OF AUTHORIZATION NUMBER: 0023683

AE301

ARCHITECTURAL BUILDING

SECTION 112

ANL ADL

NOT SPRINKLERED

2. CONTRACTOR TO SALVAGE ALL REMOVED FRAMING FOR LATER REINSTALLATION.

1. SEE A-001 FOR A-SERIES NOTES AND LEGENDS.

GENERAL NOTES

SCALE: 3/8" = 1'-0"3 ARCHITECTURAL BUILDING SECTION

KEYED NOTES

1 4X4X3/8" L BOLTED TO SLAB

2 REINSTALL BOLTED CONNECTIONS AT ENDS OF 8" C-CHANNEL FRAMING

SCALE: 3/4" = 1'-0"1 WALL PANEL SECTION

SCALE: 3/4" = 1'-0"2 OVERHEAD DOOR SECTION

Revision: Date:

REV 0 - BID DOCUMENTS 2026-04-20

MID ROOF LEVEL

94' - 9"

/1 AE105

C8x11.5 (E)

20' - 0" REF 20' - 0" REF 20' - 0" REF

L2 1/2x2 1/2x5/16 (E)

L2 1/

2x 2 1

/2x 5/1

6 ( E)

L2 1/

2x 2 1

/2x 5/1

6 ( E)

L2 1/2x2 1/2x5/16 (E)

C8x11.5 (E)

C8x11.5 (E)

W10x21 (E)

C8 x1

1.5 (E

C8 x1

1.5 (E

L3x3x1/4 (E) L3x3x1/4 (E)L3x3x1/4 (E)L3x3x1/4 (E)

W 8x

(E

W 8x

(E

W 8x

(E

W 8x

(E

L3x3x1/4 (E) L3x3x1/4 (E)

L3x3x1/4 (E)L3x3x1/4 (E)

W10x25 (E) W10x21 (E)

L2 1/2x2 1/2x5/16 (E) L2 1/2x2 1/2x5/16 (E)C8 x1

1.5 (E

L2 1/2x2 1/2x5/16 (E) L2 1/2x2 1/2x5/16 (E)C8 x1

1.5 (E

C8x11.5 (E) C8x11.5 (E)

L2 1/

2x 2 1

/2x 5/1

6 ( E)

L2 1/2x2 1/2x5/16 (E)

L2 1/2x2 1/2x5/16 (E)

L2 1/

2x 2 1

/2x 5/1

6 ( E)

C8 x1

1.5 C8

x1 1.5

C8x11.5

C8 x1

1.5 (E

C8 x1

1.5 (E

C8 x1

1.5 (E

C8 x1

1.5 (E

C8 x1

1.5 (E

C8 x1 1.5

(E

C8x11.5 (E)

AE301

TOS TOP OF STAIR

ABBREVIATIONS:

23 MECHANIC STREET, SPRINGVILLE, NY 14141

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD "Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".CONSULTANT

321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"

6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t

6"

6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t

BID DOCUMENTS REPLACE BOILERS 4 & 5

5000 W. NATIONAL AVE

MILWAUKEE, WI 53295

695-24-107

2026-04-20

CERTIFICATION OF AUTHORIZATION NUMBER: 0023683

AE305

ARCHITECTURAL BID DEDUCT

BUILDING SECTION 112

ANL ADL

NOT SPRINKLERED

2. CONTRACTOR TO SALVAGE ALL REMOVED FRAMING FOR LATER REINSTALLATION.

1. SEE A-001 FOR A-SERIES NOTES AND LEGENDS.

GENERAL NOTES

SCALE: 3/8" = 1'-0"1 ARCHITECTURAL BID DEDUCTION BUILDING SECTION

Revision: Date:

REV 0 - BID DOCUMENTS 2026-04-20

NON-COMBUSTIBLE INSULATION

RAIN HOOD

LAP SEALANT

METAL COLLAR

CONT LAP SEALANT

PRESSURE-SENSITIVE

ELASTOFORM FLASHING

AND EPDM PRIMER 1-1/4" HOT DIPPED GALV

ROOF NAIL @ 4" OC MAX

5" CONC ROOF DECK (3-1/2" CON

OVER 1-1/2" METAL DECK-

REFER TO STRUCTURAL

DRAWINGS.)

FULLY ADHERED EPDM MEMBRANERIGID INSULATION

EPDM MEMBRANE

SEE ROOF TYPE DETAILS FOR

SPECIFIC DECK CONSTRUCTION

INFORMATION

6"

APPROX

OVERLAP

4" WIDE SPLICE TAPE 1/8" MIN

1/2" MAX

SPLICE TAPE

FIELD SPLICE

NOTE 3

2" MIN AT TAPE

OVERLAPS AS SHOWN

MIN 1"

TAPE OVERLA

P

2" M

IN

SPLICE TAPE

ATTACH PANELS TO EXISTING L3"x3"x1/4"(E)

CONTINUOUS ANGLE

FIELD OR FACTORY INSTALLED CONTINUOUS

BUTYL SEALANT IN VERTICAL PANEL JOINT

INSTALLER TO ENSURE THERE ARE NO GAPS

IN SEALANT

(2) 1/4" HWH FASTENERS PER CLIP

CONTINUOUS BUTYL SEALANT BOTH SIDES OF

TRIM W/ MARRIAGE BEAD TO VERTICAL PANEL

JOINT

12 GA. STAINLESS STEEL

HIDDEN FASTENER CLIP

(1 PER PANEL, PER SUPPORT)

SET CLIP IN BUTYL SEALANT

BASE TRIM W/ POP RIVETS @ 8" O.C.

BASE FLASHING

CONTINUOUS URETHANE SEALANT

*INSTALLERS RESPONSIBILITY TO ENSURE

SEALANT COMPATIBILITY TO BONDING

SURFACE

NOTE: THE NEW WALL PANEL MAY EXTEND PAST FACE OF FOUNDATION WALL

SALVAGED METAL PANEL TO BE

REINSTALLED

3"

1/4" - 14 X 1" PANCAKE DP3

THROUGH FASTENER

W/O WASHER @ 12" O.C.

1/4" PANCAKE THROUGH FASTENER WITH 1-1/8"

BONDED WASHER @ 12" O.C.

CONTINUOUS BUTYL SEALANT BOTH SIDES

OF EXTRUSION

COMPRESSIBLE FOAM CLOSURE

2"

TWO PIECE JAMB EXTRUSION CAPFIELD CUT PANELS WHERE

REQUIRED

EXPOSED SEALANT AND BACKER ROD

COMPRESSED MINERAL WOOL

WALL

FIELD CUT PANELS WHERE

REQUIRED

EXISTING C8x11.5 GIRT

SALVAGED METAL PANEL TO BE

REINSTALLED

1/8" DIA GALVANIZED STEEL CABLE 7X19

3/8" DIA EYEBOLT HIT-HY

200 V3 HILTI EPOXY2-1/2" EMBEDMENT LENGTH

PROVIDE EPDM FLASHING MEMBRANE

& SEALANT TO MAINTAIN THE

WATERTIGHT INTEGRITY OF THE ROOF

/1 AE121

/1 AE125

NEW E.P.D.M.

ROOF MEMBRANE

NEW TAPERED INSULATION

(2) NEW LAYERS OF 1-1/2" POLYISO. INSULATION

NEW FASCIA COVER ON FASTEN PER MANUF. RECOMENDATIONS

EXTRUDED BAR ANCHOR

NEW CONTINUOUS WOOD.BLOCKING

EXISTING 6"X18" CONCRETE CURB TO REMAIN

EXISTING E.P.D.M. MEMBRANE ON

PRECAST CONCRETE ROOF SLAB

CONSTRUCTION TO REMAIN

EXISTING CEMENT CANT (V.I.F.) TO REMAIN

EXISTING 12" WF PURLIN (V.I.F.) TO REMAIN

EXISTING 8" WF STEEL BEAM (V.I.F.)

TO REMAIN

EXISTING STEEL PLATE 4"X 1/4" TO REMAIN

1-1/2" METAL DECK, 22 GAUGE 50 KSI, REFER TO

STRUCTURAL DETAIL. BASIS OF DESIGN;

VULCRAFT 1.5-36/1.5BI-36/1.5PLB-36

EXISTING E.P.D.M. ROOF MEMBRANE

NEW 1/2" COVERBOARD

EXISTING 5/8" F.T. PLYWOOD TYPICAL

1/4" PER FOOT SLOPE

1'- 6 1

/16

V.

I.F

4'-0" V.I.F.

6" V.I.F.

5'-1 1/4" V.I.F.

1/4" CONCRETE ANCHORS EVERY 6",

MINIMUM 2" CONCRETE EDGE

DISTANCE, BASIS OF DESIGN TAPCON

8" 3"

OPTIONAL CONTINUOUS BUTYL

SEALANT IN EXTERIOR (FACER) JOINT

(2) 1/4" HWH FASTENERS PER CLIP

12 GA. STAINLESS STEEL HIDDEN

FASTENER CLIP (1 PER PANEL,

PER SUPPORT) SET CLIP IN BUTYL

SEALANT

EXISTING C8X11.5 GIRT

FIELD OR FACTORY INSTALLED

CONTINUOUS BUTYL SEALANT IN

VERTICAL PANEL JOINT INSTALLER

TO ENSURE THERE ARE NO GAPS

IN SEALANT

INTERIOR EXTERIOR

/1 AE301

SALVAGED METAL PANEL TO BE

REINSTALLED

INTERIOREXTERIOR

/1 AE301

EX

IS

TI

NG

NE

W

CUT EDGE OF EXISTING PANEL

SMOOTH

EXISTING C8 x 11.5 GIRT

1/4" - 14 X 1" PANCAKE DP3

THROUGH FASTENER

W/O WASHER @ 12" O.C.

CONTINUOUS BUTYL SEALANT BOTH

SIDES OF EXTRUSION

TWO PIECE JAMB EXTRUSION BASE 3"

1/4" PANCAKE THROUGH FASTENER

WITH 1-1/8" BONDED WASHER @ 12" O.C.

TWO PIECE JAMB EXTRUSION CAP

EXPOSED SEALANT AND

BACKER ROD FIELD CUT PANELS

WHERE REQUIRED

COMPRESSED MINERAL WOOL

WALLINTERIOREXTERIOR

/1 AE301

SALVAGED METAL PANEL TO BE REINSTALLED

INTERIOR

EXTERIOR

/1 AE101

APPROX. APPROXIMATE

CONC. CONCRETE

CONT. CONTINUIOUS

EPDM ETHYLENE PROYLENE DIENE MONMER

GA. GAUGE

GALV GALVANIZED

HWH HEX WASHER HEAD

MAX. MAXIMUM

MIN. MINIMUM

O.C. ON CENTER

V.I.F VERIFY IN FEILD

W/ WITH

W/O WITHOUT

ABBREVIATIONS:

/1 AE121

/1 AE125

MECHANICAL DUCT

STAINLESS STEEL COLLAR,

SEAL ALL JOINTS

EXTEND ROOFING MEMBRANE

UP AND OVER CURB

STAINLESS STEAL FLASHING

UP AND OVER CURB

STRUCTURAL STEEL BEAM,

SEE STRUCTURAL

/1 AE121

/2 AE125

23 MECHANIC STREET, SPRINGVILLE, NY 14141

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD "Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".CONSULTANT

321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"

6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t

6"

6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t

BID DOCUMENTS REPLACE BOILERS 4 & 5

5000 W. NATIONAL AVE

MILWAUKEE, WI 53295

695-24-107

2026-04-20

CERTIFICATION OF AUTHORIZATION NUMBER: 0023683

AE501

ARCHITECTURAL DETAILS

ANL ADL

NOT SPRINKLERED

SCALE: 12" = 1'-0"2 ROOF STACK DETAIL SCALE: 1 1/2" = 1'-0"3 MEMBRANE SPLICE DETAIL

SCALE: 1" = 1'-0"5 EXISTING ROOF PATCH DETAIL

SCALE: NTS

PANEL MID-POINT ATTACHMENT DETAIL4

SCALE: 3" = 1'-0"7 PANEL SILL DETAIL

SCALE: NTS

PANEL HEAD DETAIL6

SCALE: 3" = 1'-0"8 PANEL JAMB DETAIL

1. SEE A-001 FOR A-SERIES NOTES AND LEGENDS.

GENERAL NOTES

SCALE: 3" = 1'-0"9 GUY WIRE ANCHOR DETAIL

SCALE: 12" = 1'-0"1 MECHANICAL EQUIPMENT CURB

Revision: Date:

REV 0 - BID DOCUMENTS 2026-04-20

PE

NE

TR

AT

IO

N

PE

NE

TR

AT

IO

N

POURABLE SEALER

NO

N-

SH

RIN

KIN

G

GR

OU

T

SUBSTRATE

INSULATION

SUBSTRATE

INSULATION

METAL PENETRATION POCKET

9" QUICKSEAM FORMFLASH

EPDM MEMBRANE

WOOD NAILER (MATCH INSUL HEIGHT)

1-1/4" HOT DIPPED GALV ROOF

NAIL @ 4" OC MAX

PRIMER

CONTINUOUS BEAD OF WATER BLOCK

CONTINUOUS BEAD OF AP SEALANT

MEMBRANE ADHESIVE

(ADHERED SYSTEM ONLY)

CONTINUOUS BEAD

OF LAP SEALANT

1"

1/2" MIN

1" MIN

EPDM FLASHING

FLANGED VENT PENETRATION

FLASHING, CLEAN TO BRIGHT

METAL AND PRIME

GALV GALVANIZED

INSUL. INSULATION

MAX. MAXIMUM

MIN. MINIMUM

O.C. ON CENTER

TPO THERMOPLASTIC POLYOLEFIN

ABBREVIATIONS:

PANEL CAP TRIM

C8X11.5 EXISTING FRAMING

EXISTING METAL WALL PANEL

JAMB TRIM

3/4" EDGE DISTANCE, MIN

OVERHEAD DOOR FRAME/ASSEMBLY

TO BE INSTALLED AS PER THE

MANUFACTURER'S SPECIFICATIONS

OVERHEAD DOOR COILING

ASSEMBLY, MOTOR AND

ENCLOSURE

2"

2'-4"

3'- 6"

1'- 9 1

/2" 9 1

/2"

1'-2 1/8" 3'-8 1/8"

EXISTING METAL WALL PANEL

PANEL CAP TRIM

HEAD FLASHING

WITH DRIP

FLASHING

EXSITING C8x11.5 FRAMING

/2 AE301

OVERHEAD COILING DOOR & GRILL TO

BE INSTALLED AS PER THE

MANUFACTURER'S SPECIFICATIONS

23 MECHANIC STREET, SPRINGVILLE, NY 14141

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD "Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".CONSULTANT

321 4 5 6 7 8 9 10 on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t 6"

6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t

6"

6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t

BID DOCUMENTS REPLACE BOILERS 4 & 5

5000 W. NATIONAL AVE

MILWAUKEE, WI 53295

695-24-107

2026-04-20

CERTIFICATION OF AUTHORIZATION NUMBER: 0023683

AE502

ARCHITECTURAL DETAILS

ANL ADL

NOT SPRLINKLERED

SCALE: 6" = 1'-0"1 CONDUIT ROOF PENETRATION DETAIL

SCALE: 1" = 1'-0"2 TYP VENT PENETRATION DETAIL

1. SEE A-001 FOR A-SERIES NOTES AND LEGENDS.

GENERAL NOTES

SCALE: 3" = 1'-0"4 OVERHEAD DOOR JAMB DETAIL

SCALE: 1 1/2" = 1'-0"3 OVERHEAD DOOR DETAIL

Revision: Date:

REV 0 - BID DOCUMENTS 2026-04-20

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

23 MECHANIC STREET, SPRINGVILLE, NY 14141

PROCESS - NOTES AND LEGENDS BID DOCUMENTS

NOT SPRINKLERED

REPLACE BOILERS 4 & 5

5000 W. NATIONAL AVE.

MILWAUKEE, WI 53295

2026-04-20 D-001

695-24-107

BEH DAK

GENERAL LINETYPES ABBREVIATIONS

PIPE INSULATION

MOTOR

TEMPERATURE PROTECTION

DOUBLE WALL PIPE

INSTRUMENT SYMBOLSPROCESS VALVESEQUIPMENT SYMBOLS

INSTRUMENTATION IDENTIFICATION TABLE

CONTINUATION ARROWS

TRANSFER TO SAME SHEET(X-X)

PRIMARY LOCATION ACCESSIBLE TO

OPERATOR-DISCRETE INSTRUMENT

FIELD MOUNTED-DISCRETE INSTRUMENT

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

AUXILIARY LOCATION ACCESSIBLE TO

OPERATOR-DISCRETE INSTRUMENT

INACCESSIBLE, HIDDEN, OR BACK/INSIDE

PANEL-DISCRETE INSTRUMENT

XXX

XXX

XXX

XXX

FIELD MOUNTED-SHARED DISPLAY, SHARED

CONTROL

PRIMARY LOCATION ACCESSIBLE TO OPERATOR-SHARED

DISPLAY, SHARED CONTROL FOR PUMP SKID

(LOCATED IN FUEL OIL PUMP SKID HMI/PLC), * = PANEL LEGEND

INACCESSIBLE, HIDDEN, OR BACK/INSIDE

PANEL-SHARED DISPLAY, SHARED CONTROL

AUXILIARY LOCATION ACCESSIBLE TO

OPERATOR-SHARED DISPLAY, SHARED CONTROL

DRAWING

POS1 POS2

XXXX

XXXX

FLOW ARROW

FLOW DIRECTION

(SINGLE )

FLOW DIRECTION

(BOTH)

FLOW DIRECTION

AREA A

AREA BOUNDRY

PILOT LIGHT

PUMP

AREA B

LEVEL FLOAT

SUMP PUMP

CHECK VALVE

VALVES (GENERAL)

DUPLEX STRAINER

S

PRESSURE RELIEF VALVE

GLOBE VALVE

REDUCER (CONCENTRIC)

LINE WITH PLUG

BACK PRESSURE REGULATOR VALVE

STRAINER

HOSE CONNECTION

PRESSURE/VACUUM VENT

PRESSURE RUPTURE DISK

BALL VALVE

SOLENOID ACTUATED VALVE

DRAIN

MATERIAL

A

POINT OF CONNECTION BETWEEN NEW AND

EXISTING WORK

MATERIAL

B

PRIMARY LOCATION ACCESSIBLE TO OPERATOR-SHARED

DISPLAY, SHARED CONTROL FOR TANK MONITORING SYSTEM

(LOCATED IN TANK MONITORING SYSTEM HMI/PLC)

* = PANEL LEGEND

ELECTRIC TANK IMMERSION HEATER

DIAPHRAGM VALVE

SIGHT GLASS WITH ROTOR

FILTER

FLEX CONNECTION

PLUG VALVE

PRESSURE REDUCING VALVE WITH

INTEGRAL OUTLET PRESSURE RELIEF

UNION

POSITION ON ACTUATOR

RESTRICTION ORIFICE

CONVERSIONI/P

THREE WAY VALVE

C CONDENSATE POT

SIPHON

ANGLE GLOBE VALVE

WATER COLUMN

FLOAT TRAP

NEEDLE VALVE

XXX

XXX

XXX

XXX

XXX

XXX

POSITIVE DISPLACEMENT FLOW METER

MAGNETIC FLOW METER

VORTEX SHEDDING FLOW METER

GATE VALVE W/ GLOBE VALVE BYPASS

EQUIPMENT TYPE

BLR = BOILER

CF = CHEMICAL FEED

ECO = ECONOMIZER

2-100-BLR-001

NUMBERING DESIGNATIONS FOR EQUIPMENT

IDENTIFIER NUMBER

BUILDING NUMBER

ROOM NUMBER

STEAM TRAP- INVERTED BUCKET

SKID LIMITS

UV FLAME SCANNER

STRAINER WITH BLOW-OFF VALVE

STEAM TRAP- FLOAT & THERMOSTATIC

REDUCER (ECCENCTRIC)

A COMPRESSED AIR

AFF ABOVE FINISHED FLOOR

AFGSOV AUTOMATIC FUEL GAS SHUTOFF VALVES AND

SOLENOID VENT VALVE

AFGSVV AUTOMATIC FUEL GAS SHUTOFF SOLENOID VENT

VALVE

AFOSV AUTOMATIC FUEL OIL SHUTOFF VALVES

ALWCO AUXILIARY LOW WATER CUTOFF ON STEAM

BOILERS

APFGSOV AUTOMATIC PILOT FUEL GAS SHUTOFF VALVES

APFGSVV AUTOMATIC PILOT FUEL GAS SOLENOID VENT

VALVE

BAPS DTM BOILER AND ASSOCIATED PLANT SAFETY DEVICE

TESTING MANUAL

BBD BOTTOM BLOWDOWN

BD BLOWDOWN

CAPS COMBUSTION AIR PRESSURE SWITCH

CBD CONTINUOUS BLOWDOWN

CF CHEMICAL FEED

CIP CLEAN-IN-PLACE

CO CLEAN OUT

CT CONDENSATE TRANSFER

CW COLD WATER

DR DRAIN

ESPB EMERGENCY STOP/PANIC BUTTON

FDDWOPS FORCED DRAFT DAMPER WIDE OPEN POSITION

SWITCH

FOF FUEL OIL FILL

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FPI FURNACE PRESSURE INTERLOCK

FW FEEDWATER

G NATURAL GAS

HFGPAMG HIGH FUEL GAS PRESSURE ALARM ON MAIN GAS

LINE

HFGPCS HIGH FUEL GAS PRESSURE CUTOFF SWITCH

HFOPCS HIGH FUEL OIL PRESSURE CUTOFF SWITCH

HPR HIGH PRESSURE CONDENSATE RETURN

HPS HIGH PRESSURE STEAM

HSPLS HIGH STEAM PRESSURE LIMIT SWITCH

HW HOT WATER

HWAB HIGH WATER ALARM ON BOILER

HWACT HIGH WATER ALARM ON CONDENSATE TANK

HWADT HIGH WATER ALARM ON DEAERATOR TANK

LAMPS LOW ATOMIZING MEDIA PRESSURE SWITCH

LC LOCKED CLOSED

LFPS LOW FIRE PROVING SWITCH

LFGPCS LOW FUEL GAS PRESSURE CUTOFF SWITCH

LFOPCS LOW FUEL OIL PRESSURE CUTOFF SWITCH

LO LOCKED OPEN

LPS LOW PRESSURE STEAM

LPR LOW PRESSURE CONDENSATE RETURN

LPG LIQUEFIED PETROLEUM GAS

LPFGPCS LOW PILOT FUEL GAS PRESSURE CUTOFF

SWITCH

LRVOPS LIQUID RELIEF VALVE ON OIL PUMP SET

LWA LOW WATER ALARM

LWCO LOW WATER CUTOFF ON STEAM BOILER

MV MANUAL VALVE

NC NORMALLY CLOSED

NO NORMALLY OPEN

NRBSPLS NON-RECYCLE BOILER STEAM PRESSURE LIMIT

SWITCH

O/W OIL AND WATER SEPARATOR

OFL OVER FLOW LEVEL

OSDPI OUTLET STACK DAMPER POSITION INTERLOCK

SWITCH

PAPS PURGE AIRFLOW PROVING SWITCH

POC PROOF OF CLOSURE

PRS PRESSURE REDUCING STATION

PRV PRESSURE REDUCING VALVE

RBSPLS RECYCLE BOILER STEAM PRESSURE LIMIT

SWITCH

RO REVERSE OSMOSIS

SLAMPS SECONDARY LOW ATOMIZING MEDIA

PRESSURE SWITCH

SVB STEAM SAFETY VALVES ON BOILER

SVFPRV SAFETY VALVE FOLLOWING PRV

SW SOFTENED WATER

TP TEST POINT

V VENT

VTR VENT TO ROOF

PRESSURE REDUCING VALVE

FAN

MOTORIZED DAMPER

M

SHUTOFF VALVE

EQUIPMENT TYPE

0 = GENERAL

4 = BOILER 4

5 = BOILER 5

12-FO-V-11001

NUMBERING DESIGNATIONS FOR INSTRUMENTATION

IDENTIFIER NUMBER

BUILDING NUMBER

ASSOCIATED SYSTEM

TYPE

UNIQUE IDENTIFIER

SHEET NUMBER

M

MOTORIZED CONTROL VALVE

DRIP PAN ELBOW

XXX

XXX

XXX

XXX *

XXX

XXX *

LPG TANK

VACUUM BREAKER

BACKFLOW PREVENTER

(REDUCED PRESSURE ZONE)

ANALOG SIGNAL

PIPING PROCESS

NETWORK CONNECTION

PROCESS SYMBOLS

SILENCER

HEAT EXCHANGER

DRAWING

POS1 POS2

XXX

NON-RETURN STOP-CHECK

PRESSURE RELIEF VALVE (HANDLE)

GENERAL NOTES

1. ALL VALVES SPECIFIED AS LOCKABLE (LOCK OPEN) SHALL NOT HAVE THE ABILITY TO BE LOCKED CLOSED.

PIPE CAP

FIRST LETTERS SUCCEEDING LETTERS

COLUMN 1 COLUMN 2 COLUMN 3 COLUMN 4 COLUMN 5

LETTER MEASURED/INITIATING

VARIABLE

VARIABLE MODIFIER READOUT/PASSIVE

FUNCTION

OUTPUT/ACTIVE FUNCTION FUNCTION MODIFIER

A ALALYSIS ALARM

B BURNER, COMBUSTION USERS CHOICE USERS CHOICE USERS CHOICE

C USERS CHOICE CONTROL CLOSE

D USERS COICE DIFFERENCE, DIFFERENTIAL DEVIATION

E VOLTAGE SENSOR, PRIMARY

ELEMENT

F FLOW,FLOW RATE RATIO

G USERS CHOICE GLASS, GAUGE,VIEWING

DEVICE

H HAND HIGH

I CURRENT INDICATE

J POWER SCAN

K TIME, SCHEDULE TIME RATE OF CHANGE CONTROL STATION

L LEVEL LIGHT LOW

M USERS CHOICE MIDDLE, INTERMEDIATE

N USERS CHOICE USERS CHOICE USERS CHOICE USERS CHOICE

O USERS CHOICE - OIL LEAK

DETECTION

ORIFICE, RESTRICTION OPEN

P PRESSURE POINT (TEST CONNECTION)

Q QUANTITY INTEGRATE TOTALIZE INTEGRATE, TOTALIZE

R RADIATION RECORD RUN

S SPEED, FREQUENCY SAFETY SWITCH STOP

T TEMPERATURE TRANSMIT

U MULTIVARIABLE MUTIFUNCTION (21) MULTIFUNCTION

V VIBRATION, MECHANICAL

ANALYSIS

VALVE, DAMPER, LOUVER

W WEIGHT, FORCE WELL, PROBE

X UNCLASSIFIED X-AXIS ACCESSORY DEVICES,

UNCLASSIFIED

UNCLASSIFIED UNCLASSIFIED

Y EVENT, STATE, PRESENCE Y-AXIS AUXILIARY DEVICES

Z POSITION, DIMENSION Z-AXIS, SAFETY

INSTRUMENTED SYSTEM

DRIVER, ACTUATOR,

UNCLASSIFIED FINAL

CONTROL ELEMENT

VENTURI FLOW METER

REV 0 - BID DOCUMENTS 2026-04-20

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

CERTIFICATE OF AUTHORIZATION NUMBER: 0023683

REV 1 - ADDENDUM 03 2026-11-04

EXP 01/31/2027 11/4/2026

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

1" FOS

V-13001

S S

NC

NC

NC

PG

13025

BURNER

112-105-BLR-005

SIGHT GLASS WITH ROTOR

FE

13016

FIT

13016

NC

M

NC NC

3/4" FOR

TG

13013

PSL

13030

PIT

13029

SLAMPS

FUEL FLOW

CONTROL VALVE AFOSOV

PG

13020

AFOSOV

TP

TP

V-13006 FCV-13014

V-13018

V-13017V-13015 YSV-13019 YSV-13021

V-13025

AIR BLEED

PI

13003

PT

13003

PI

13003

PDI

13003

PDI

13003

PI

13008

PI

13008

CP-1

FG

13034

ZIC

13014

ZC

13014

ZI

13014

ZI

13014

ZCO

13019

ZSO

13019

ZSC

13019

ZCO

13019

CP-1

ZIO

13019

ZIC

13019

ZIO

13019

ZIC

13019

ZCO

13021

ZSO

13021

ZSC

13021

ZCO

13021

CP-1

ZIO

13021

ZIC

13021

ZIO

13021

ZIC

13021

PI

13029

PI

13029

PAL

13030

PAL

13030

CP-1

FI

13016

FQI

13016

CP-1

CP-1

CP-1

FQI

13016

FI

13016

F-13005

INCLUDED WITH BOILER #112-105-BLR-005

V-

PG

13004

V-

V-

V-

13009

PSL

V-

NC

V-13010

TP

LOCKABLE

(LOCK OPEN)

LFOPCS

CP-1

PG

13010

PAL

13009

13011

PSH

V-

NC

V-13012

TP

LOCKABLE

(LOCK OPEN)

HFOPCS

CP-1

PG

13012

PAH

13011

V-

V-

0 V-

PG

13007

PT

13008

V-

V-

CK

V-

CK

V-

TP

LOCKABLE

(LOCK OPEN)

PG

13040

V-

13040

CP-1

PAH

13011

PAL

13009

3/4" FOS

1-1/2" FOR

1/2" FOR

V-13035

FROM FUEL

PUMPS

RETURN TO TANK

1" CA

COMPRESSED AIR

PSV

13031

AIR CONTROLS BY

BURNER

MANUFACTURER

GENERAL NOTES

1. SEE D-001 FOR D-SERIES NOTES AND LEGENDS.

KEYED NOTES

1 CHANGE OF FUELS SHALL NOT REQUIRE ANY DISASSEMBLY AND REASSEMBLY OF

THE FUEL TRAIN OR FUEL NOZZLES

2 LOW-FIRE PROVING SWITCH REQUIRED ON FLOW CONTROL VALVE, REFER TO

BAPSDTM

3 PROOF OF CLOSURE SWITCH REQUIRED ON SOLENOID VALVES, REFER TO BAPSDTM

CONNECT EXISTING SHOP GENERAL COMPRESSED AIR TO BURNER FOR FUEL

ATOMIZATION DURING COLD START AND TIE EXISTING LOW ATOMIZATION MEDIA

PRESSURE SWITCH (LAMPS) FOR SAFETY BOILER SHUTDOWN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

23 MECHANIC STREET, SPRINGVILLE, NY 14141

PROCESS - P&ID - FUEL OIL -

BOILER #5

BID DOCUMENTS

NOT SPRINKLERED

REPLACE BOILERS 4 & 5

5000 W. NATIONAL AVE.

MILWAUKEE, WI 53295

2026-04-20 D-611

695-24-107

BEH DAK

REV 0 - BID DOCUMENTS 2026-04-20

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

CERTIFICATE OF AUTHORIZATION NUMBER: 0023683

REV 1 - ADDENDUM 03 2026-11-04

GENERAL LINETYPES

ANALOG SIGNAL

PIPING PROCESS

NETWORK CONNECTION

CONTINUATION ARROWS

FLOW ARROW

FLOW DIRECTION

(SINGLE )

DRAWING

POS1 POS2

XXX

AREA BOUNDRY

POINT OF CONNECTION BETWEEN NEW AND

EXISTING WORK

REDUCER (CONCENTRIC)

FLEX CONNECTION

PROCESS SYMBOLS

PROCESS VALVES

VALVES (GENERAL)

S

SOLENOID ACTUATED VALVE

PLUG VALVE

M MOTORIZED CONTROL VALVE

FILTER

PIPE CAP

XXX

XXX

POSITIVE DISPLACEMENT FLOW METER

CHECK VALVE

PRESSURE RELIEF VALVE

BALL VALVE

INSTRUMENT SYMBOLS

FIELD MOUNTED-DISCRETE INSTRUMENT

XXX

XXX

PRIMARY LOCATION ACCESSIBLE TO OPERATOR-SHARED

DISPLAY * = PANEL LEGEND

XXX

XXX *

PRIMARY LOCATION ACCESSIBLE TO OPERATOR-SHARED

DISPLAY * = PANEL LEGEND

XXX

XXX *

ABBREVIATIONS

AFOSV AUTOMATIC FUEL OIL SHUTOFF VALVES

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

HFOPCS HIGH FUEL OIL PRESSURE CUTOFF SWITCH

LC LOCKED CLOSED

LFOPCS LOW FUEL OIL PRESSURE CUTOFF SWITCH

LO LOCKED OPEN

NC NORMALLY CLOSED

NO NORMALLY OPEN

O/W OIL AND WATER SEPARATOR

SLAMPS SECONDARY LOW ATOMIZING MEDIA

PRESSURE SWITCH

TP TEST POINT

BAPSDTM BOILER AND ASSOCIATED PLANT SAFETY DEVICE

TESTING MANUAL

EXP 01/31/2027 11/4/2026

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

FIT

22102

NC

PIT

22105

S S

ZCO

22115

ZSC

22115

ZSO

22115

ZCO

22120

ZSC

22120

ZSO

22120

S

ZCC

22117

PG

22116

PG

22118

LOCKABLE

(LOCK OPEN)

FUEL FLOW

CONTROL VALVEDIRT

POCKET

TP

PSL

22013

LPFGPCS

S S

LOCKABLE

(LOCK OPEN)

IGNITER

112-105-BLR-005

DIRT POCKETS

FLEX

CONN

3/4 " G

3" G

TP

ROOF

NC

NC

NC

AFGSOV AFGSOV

AFGSVV

APFGSVV

APFGSOV APFGSOV

V-22101 V-22103

V-22104

V-22108 PCV-22110 V-22115 V-22122

V-22118

V-22120 V-22126

TP

M

1" V

2" V

1" V

3/4" G/LPG

TP

V-22021V-22019V-22014CKV-22009PCV-22008

V-22010

PCV-22005 CKV-22006

V-22017

V-22003

FI

22102

CP-1

FI

22102

PI

22105

PI

22105 ZCO

22115

ZIO

22115

ZIC

22115

ZIC

22115

ZIO

22115

ZSC

22117

ZSO

22117

ZCC

22117

ZIO

22117

ZIC

22117

ZIC

22117

ZIO

22117

ZCO

22120

ZIO

22120

ZIC

22120

ZIC

22120

ZIO

22120

PAH

22123

FCV-22125

ZIC

22125

ZC

22125

ZI

22125

ZI

22125

ZCO

22019

ZSC

22019

ZSO

22019

ZCO

22019

ZIO

22019

ZIC

22019

ZIC

22019

ZIO

22019

ZCO

22014

ZSC

22014

ZSO

22014

ZCC

22016

ZCO

22014

ZIO

22014

ZIC

22014

ZIC

22014

ZIO

22014

ZSC

22016

ZSO

22016

ZCC

22016

ZIO

22016

ZIC

22016

ZIC

22016

ZIO

22016PAL

22013

PAL

22013

PT

22011

PI

22011

PI

22011

FQI

22102

FQI

22102

CP-1

CP-1 CP-1

CP-1

CP-1

CP-1

CP-1

CP-1

CP-1

CP-1 CP-1

F-22109

V-

DIRT

POCKET

F-22004

F-22007

INCLUDED WITH BOILER #112-105-BLR-005

FACTORY LPG CONNECTION

6" G

1" LPG

FACTORY NATURAL

GAS CONNECTION

NC

3/4

V-

NC

1/2

V-

V-

PT

22111

PI

22111

PI

22111

CP-1

V-

V-

PG

22002

V-

V-

PG

22112

V-

22113

PSL

V-

PAL

22113

CP-1

NC

V-22114

TP

LOCKABLE

(LOCK OPEN)

LFGPCS

V-

V-

22123

PSH

V-

NC

V-22124

TP

LOCKABLE

(LOCK OPEN)

HFGPCS

PG

22127

V-

V-

PG

22012

V-

V-

V-

V-

S

V-

TP V-

V-

3/4" V

BURNER

112-105-BLR-005

NATURAL GAS

SUPPLY HEADER

LPG SUPPLY

HEADER

3/4" V

TPPG

22022

V-22022

PG

22015

LOCKABLE

(LOCK OPEN)

ZIC

22123

3" G

V-2200X

V-2200X

GENERAL NOTES

1. SEE D-001 FOR D-SERIES NOTES AND LEGENDS.

KEYED NOTES

1 MAXIMUM DISTANCE FROM AFGSOV TO BURNER IS 4'-0".

2 LOW-FIRE PROVING SWITCH REQUIRED ON FLOW CONTROL VALVE, REFER TO

BAPSDTM

3 PROOF OF CLOSURE SWITCH REQUIRED ON SOLENOID VALVES, REFER TO BAPSDTM

PCV-22110

PRESSURE REDUCING VALVE

SET POINT: 2 PSIG

PCV-22005

PRESSURE REDUCING VALVE

SET POINT: 2 PSIG

PCV-22008

PRESSURE REDUCING VALVE

SET POINT: 2 PSIG

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

23 MECHANIC STREET, SPRINGVILLE, NY 14141

PROCESS - P&ID - NATURAL GAS -

BOILER #5

BID DOCUMENTS

NOT SPRINKLERED

REPLACE BOILERS 4 & 5

5000 W. NATIONAL AVE.

MILWAUKEE, WI 53295

2026-04-20 D-621

695-24-107

BEH DAK

REV 0 - BID DOCUMENTS 2026-04-20

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

CERTIFICATE OF AUTHORIZATION NUMBER: 0023683

REV 1 - ADDENDUM 03 2026-11-04

GENERAL LINETYPES

ANALOG SIGNAL

PIPING PROCESS

NETWORK CONNECTION

CONTINUATION ARROWS

FLOW ARROW

FLOW DIRECTION

(SINGLE )

DRAWING

POS1 POS2

XXX

AREA BOUNDRY

POINT OF CONNECTION BETWEEN NEW AND

EXISTING WORK

PROCESS SYMBOLS

FILTER

XXX

XXX

VORTEX SHEDDING FLOW METER

UNION

PIPE CAP

FLEX CONNECTION

PROCESS VALVES

CHECK VALVE

VALVES (GENERAL)

S

SOLENOID ACTUATED VALVE

PLUG VALVE

PRESSURE REDUCING VALVE WITH

INTEGRAL OUTLET PRESSURE RELIEF

THREE WAY VALVE

M

MOTORIZED CONTROL VALVE

INSTRUMENT SYMBOLS

FIELD MOUNTED-DISCRETE INSTRUMENT

XXX

XXX

PRIMARY LOCATION ACCESSIBLE TO OPERATOR-SHARED

DISPLAY * = PANEL LEGEND

PRIMARY LOCATION ACCESSIBLE TO OPERATOR-SHARED

DISPLAY, * = PANEL LEGEND

XXX

XXX *

XXX

XXX *

ABBREVIATIONS

AFGSOV AUTOMATIC FUEL GAS SHUTOFF VALVES AND

SOLENOID VENT VALVE

AFGSVV AUTOMATIC FUEL GAS SHUTOFF SOLENOID VENT

VALVE

APFGSOV AUTOMATIC PILOT FUEL GAS SHUTOFF VALVES

APFGSVV AUTOMATIC PILOT FUEL GAS SOLENOID VENT VALVE

BAPSDTM BOILER AND ASSOCIATED PLANT SAFETY DEVICE

TESTING MANUAL

G NATURAL GAS

HFGPCS HIGH FUEL GAS PRESSURE CUTOFF SWITCH

LFGPCS LOW FUEL GAS PRESSURE CUTOFF SWITCH

LPG LIQUEFIED PETROLEUM GAS

TP TEST POINT

V VENT

EXP 01/31/2027 11/4/2026

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

TIT

38005

TE

38005

TIT

38009

TE

38009

STACK

ECONOMIZER

112-105-ECO-001

VENT TO SAFE PLACE

IN BOILER ROOM

SIGHT GLASS

WITH ROTOR

PG

38012

NC

TP

V-

V-

NC

V-

V-38012

V-

FG

38014

CP-1

CP-1 CP-1

CP-1

PI

38004

TI

38005

TDI

38005

TI

38009

PDI

38010

PI

38010

LRVE

SET POINT: 168 PSIG

FACTORY FEEDWATER INLET CONNECTION (TYP)

PIT

38010

V-

FACTORY FEEDWATER OUTLET CONNECTION (TYP)

NC

V-

PSV

38015

3" FW

BOILER #112-105-BLR-005

F-38003

1" CF NC

V-38031

NC

2 1/2" FW

LSLL

38108

LT

38107

PSHH

38116

PSH

38115

PIT

38114

PG

38112

BOILER #112-105-BLR-005

GAUGE GLASS

BALL VALVES

PROHIBITED (TYP)

LWCO SHUNT SWITCH

(LOCATE WITHIN 3'-0" OF LWCO

& GAUGE GLASS DRAIN VALVE)

PLUGGED CROSS (TYP)

NRBSPLS RBSPLS

LWCO

FLOAT-TYPE

LEVEL SENSOR

PIT

38004

V-

NC

V-

9V-38007 FCV-38020 V-38022

V-38023

CKV-38028

FE

38026

FIT

38026

M V-38025 V-38027 V-38030

M

ZIC

38020

NC

V-38112

NC

V-38114

NC

NC

LG

38106

V-

V-

CP-1

CP-1

CP-1CP-1

CP-1CP-1CP-1

ZI

38020

ZC

38020

FI

38026

FQI

38026

PAHH

38116

PAH

38115

PI

38114

LALL

38108

LI

38107

ALWCO SHUNT SWITCH

(LOCATE WITHIN 3'-0"

OF ALWCO DRAIN VALVE)

HS

38120

YI

38120

CP-1

HS

38108

YI

38108

CP-1

LWCO SHUNT

SWITCH

FACTORY FEEDWATER

INLET CONNECTION (TYP)

NC

V-

NC

V-

NC

V-

V-

V-

SIGHT GLASS

WITH ROTOR

FG

38122

3/4" BD

CKV-38124V-38123

V-

V-

V-

V-38001

BOILER

(END VIEW)

FEEDWATER

LSH

38118

LSL

38119

LSLL

38120

ALWCO

LWA

HWAB

PROBE COLUMN

LAH

38118

LAL

38119

LALL

38120

CP-1

CP-1

CP-1

LSHH

38117

LAHH

38117

CP-1

3/4" BD

PG

38034

TP

V-

TO DRAIN

SULFITE OXYGEN SCAVENGER (EXISTING)

CKV-36009

PG

36008

V-

M

SIC

36007

HS

36007

2-128-CF-203B

CKV-36006

LSL

36006

LBL

36006

CP-1

AMINE

55 GAL DRUM

CKV-36024

PG

36023

V-

M

SIC

36022

HS

36022

2-128-CF-201C

CKV-36025

LSL

36025

LBL

36025

CP-1

1" CF NC

V-38031

1" CF NC

V-38031

SCALE INHIBITOR (EXISTING)

CKV-36034

PG

36033

V-

M

SIC

36032

HS

36032

2-128-CF-202C

CKV-36035

LSL

36035

LBL

36035

CP-1

GENERAL NOTES

1. SEE D-001 FOR D-SERIES NOTES AND LEGENDS.

2.

ALL VALVE BODIES AND FITTINGS IN THE BOILER PLANT SHALL BE CAST OR FORGED

STEEL. CAST IRON, DUCTILE IRON, AND BRONZE ARE PROHIBITED, WITH THE

EXCEPTION OF DOMESTIC WATER SERVICES.

KEYED NOTES

1 ORIFICE SIZE TO BE PROVIDED BY ECONOMIZER MANUFACTURER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

23 MECHANIC STREET, SPRINGVILLE, NY 14141

PROCESS - P&ID - FEEDWATER

BOILER #5

BID DOCUMENTS

NOT SPRINKLERED

REPLACE BOILERS 4 & 5

5000 W. NATIONAL AVE.

MILWAUKEE, WI 53295

2026-04-20 D-631

695-24-107

BEH DAK

REV 0 - BID DOCUMENTS 2026-04-20

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

CERTIFICATE OF AUTHORIZATION NUMBER: 0023683

REV 1 - ADDENDUM 03 2026-11-04

GENERAL LINETYPES

CONTINUATION ARROWS

ANALOG SIGNAL

PIPING PROCESS

NETWORK CONNECTION

XXXX

XXXX

FLOW ARROW

FLOW DIRECTION

PROCESS VALVES

CHECK VALVE

VALVES (GENERAL)

PRESSURE RELIEF VALVE

BALL VALVE

M

MOTORIZED CONTROL VALVE

INSTRUMENT SYMBOLS

FIELD MOUNTED-DISCRETE INSTRUMENT

XXX

XXX

PRIMARY LOCATION ACCESSIBLE TO OPERATOR-SHARED

DISPLAY * = PANEL LEGEND

XXX

XXX *

ABBREVIATIONS

BD BLOWDOWN

FW FEEDWATER

LWCO LOW WATER CUTOFF ON STEAM BOILER

NRBSPLS NON-RECYCLE BOILER STEAM PRESSURE LIMIT

SWITCH

RBSPLS RECYCLE BOILER STEAM PRESSURE LIMIT SWITCH

TP TEST POINT

XXX

XXX

M

M

PROCESS SYMBOLS

MAGNETIC FLOW METER

MOTOR

PUMP

EXP 01/31/2027 11/4/2026

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

TO BOTTOM

BLOWDOWN

NC

V-

1 1 /2"

C

BD

1 1/2" CBD

CK

V-

V-

V-41012

3" BBD

TO STEAM

HEADER

V-

V-

NC

V-

FE

41011

FIT

41011

FI

41011

FQI

41011 CP-1

PIT

41009

PI

41009

PG

41008ZSO

41001

ZAO

41001 CP-1

ZSO

41002

ZAO

41002 CP-1

V-41001 V-41002

V-

V-41004

V-41005

V-

V-

NON-RETURN

STOP CHECK

ROOF

TO SURFACE

BLOWDOWN

2" CBD

V-41018

V-41019

8" HPS

BOILER #112-105-BLR-005

1/4" SAMPLE

OUTLET

3/4"

ANTI-SYPHON

VACUUM BREAKER

MOUNT CBD SAMPLE

COOLER 4' ± ABOVE

FINISHED FLOOR ON

WALL OR COLUMN

DR

TG

42118

V-42117

V-42118

V-

V-

V-

COLD WATER

1" CWS

112-105-FLO-001

GENERAL NOTES

1. SEE D-001 FOR D-SERIES NOTES AND LEGENDS.

2.

ALL VALVE BODIES AND FITTINGS IN THE BOILER PLANT SHALL BE CAST OR FORGED

STEEL. CAST IRON, DUCTILE IRON, AND BRONZE ARE PROHIBITED, WITH THE

EXCEPTION OF DOMESTIC WATER SERVICES.

3 ALL BOTTOM BLOWDOWN PIPING SHALL USE SHORT RADIUS 45 DEGREE ELBOWS OR

LONG RADIUS 90 DEGREE ELBOWS.

4 WYE-TYPE TEE FITTINGS SHALL BE USED FOR ALL BOTTOM BLOWDOWN PIPING. 90

DEGREE TEES ARE PROHIBITED.

5 BOTTOM BLOWDOWN VALVES SHALL HAVE CLEAR, UNOBSTRUCTED ACCESS AND NO

PART OF THE VALVE SHALL BE LOCATED UNDER ANY PART OF THE BOILERS.

KEYED NOTES

1 3/4" THREADED HALF-COUPLING FOR CALORIMETER CONNECTION. LOCATE TO

ALLOW SPACE FOR PROVIDED PLUG.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

23 MECHANIC STREET, SPRINGVILLE, NY 14141

PROCESS - P&ID - STEAM BOILER #5 BID DOCUMENTS

NOT SPRINKLERED

REPLACE BOILERS 4 & 5

5000 W. NATIONAL AVE.

MILWAUKEE, WI 53295

2026-04-20 D-641

695-24-107

BEH DAK

REV 0 - BID DOCUMENTS 2026-04-20

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

CERTIFICATE OF AUTHORIZATION NUMBER: 0023683

REV 1 - ADDENDUM 03 2026-11-04

112-105-BLR-005

FIRETUBE BOILER

RATING: 600 HP

FUEL: NATURAL GAS, NO 2 FUEL OIL

DESIGN PRESSURE: 250 PSI

NOx EMMISIONS LEVEL: 30 PPM

BLOWER MOTOR POWER: 25 HP

BASIS OF DESIGN: CLEAVER-BROOKS CBLE-4W

GENERAL LINETYPES

CONTINUATION ARROWS

XXXX

XXXX FLOW DIRECTION

ANALOG SIGNAL

PIPING PROCESS

NETWORK CONNECTION

FLOW DIRECTION

(SINGLE )

DRAWING

POS1 POS2

XXX

AREA BOUNDRY

POINT OF CONNECTION BETWEEN NEW AND

EXISTING WORK

PROCESS VALVES

CHECK VALVE

VALVES (GENERAL)

ANGLE GLOBE VALVE

NEEDLE VALVE

GATE VALVE W/ GLOBE VALVE BYPASS

NON-RETURN STOP-CHECK

PRESSURE RELIEF VALVE

INSTRUMENT SYMBOLS

FIELD MOUNTED-DISCRETE INSTRUMENT

XXX

XXX

PRIMARY LOCATION ACCESSIBLE TO OPERATOR-SHARED

DISPLAY * = PANEL LEGEND

XXX

XXX *

ABBREVIATIONS

BBD BOTTOM BLOWDOWN

CBD CONTINUOUS BLOWDOWN

HPS HIGH PRESSURE STEAM

EXP 01/31/2027 11/4/2026

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

8" HPS

10" HPS

3/4" DR3/4" DR

TRP-44031

HPS TO MAIN STEAM

HEADER

8" HPS

NC

V-

NC

V-

V-

NC

V-

V-44033

8" HPS

V-

V-

PIT

44001

V-

HPR1"

PI

44001

TRP-44032

D-641 9 C

112-105-BLR-005

CP-1

V-44034

V-44004

NC

V-44006

V-44007

FE

44005

FIT

44005

FI

44005

FIQ

44005

3"

NC

V-

V-

3" HPS8" HPS

4" H

PS

4" H

PS

112-105-FLO-002

GENERAL NOTES

1. SEE D-001 FOR D-SERIES NOTES AND LEGENDS.

2.

ALL VALVE BODIES AND FITTINGS IN THE BOILER PLANT SHALL BE CAST OR FORGED

STEEL. CAST IRON, DUCTILE IRON, AND BRONZE ARE PROHIBITED, WITH THE

EXCEPTION OF DOMESTIC WATER SERVICES.

3 ALL BOTTOM BLOWDOWN PIPING SHALL USE SHORT RADIUS 45 DEGREE ELBOWS OR

LONG RADIUS 90 DEGREE ELBOWS.

4 WYE-TYPE TEE FITTINGS SHALL BE USED FOR ALL BOTTOM BLOWDOWN PIPING. 90

DEGREE TEES ARE PROHIBITED.

5 BOTTOM BLOWDOWN VALVES SHALL HAVE CLEAR, UNOBSTRUCTED ACCESS AND NO

PART OF THE VALVE SHALL BE LOCATED UNDER ANY PART OF THE BOILERS.

KEYED NOTES

1 3/4" THREADED HALF-COUPLING FOR CALORIMETER CONNECTION. LOCATE TO

ALLOW SPACE FOR PROVIDED PLUG.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

23 MECHANIC STREET, SPRINGVILLE, NY 14141

PROCESS - P&ID - STEAM - BOP

BASE BID

BID DOCUMENTS

NOT SPRINKLERED

REPLACE BOILERS 4 & 5

5000 W. NATIONAL AVE.

MILWAUKEE, WI 53295

2026-04-20 D-642

695-24-107

BEH DAK

REV 0 - BID DOCUMENTS 2026-04-20