S06 - Infection Control 676-22-110 Upgrade Fire Alarm.pdf

PDF 95 KB Posted

Attached to
Z1DA--Upgrade Fire Alarm System Construction 676-22-110
Solicitation number
36C25226B0014-1
Issued by

About this file

This document is an Infection Control requirements table for a fire alarm upgrade project (676-22-110) that specifies infection control and risk assessment levels across multiple buildings and spaces within a large facility complex.

The table details 95+ locations across numerous buildings (numbered 1-455) with designations for building type, floor level, ICRA (Infection Control Risk Assessment) level, mobile ICRA cart approval status, and infection control comments. ICRA levels range from Level 2 (standard precautions) to Level 4 (highest risk), with most spaces classified as Level 2. All locations show "X" approval for mobile ICRA cart use. Locations designated as Level 3 or 4—including medical wards, surgical areas, sterile processing departments, gyms, laundries, kitchens, and certain specialty spaces—include a standardized infection control requirement: "Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements." The scope encompasses diverse facility types including hospitals, medical wards, administrative offices, mechanical rooms, garages, warehouses, recreation areas, and support facilities. This document appears to serve as a planning and compliance tool for managing infection control protocols during the fire alarm system upgrade across the entire campus.

View the file

Other files

File Type Posted
S06 - Att 1 Updates to Pages 3 and 11 of SOL 36C25226B0014.pdf PDF
S06 - Att 2 Addendum No1 676-22-110 Upgrade Fire Alarm System 20260929.pdf PDF
S06 - Att 3 RFI Response A0003 Oct 6 2026.pdf PDF
36C25226B0014 0003.docx DOCX document
S06 - 36C25226B0014 0002.pdf PDF
S06 - Low Risk Locations - Upgrade Fire Alarm.pdf PDF
S06 - Site Visit Sign-in Aug 25 27-2026.pdf PDF
S06 - High-Highest Risk Locations - Upgrade Fire Alarm.pdf PDF
S06 - RFI Response A0001 Sep 3 2026.pdf PDF
S06 - Medium Risk Locations - Upgrade Fire Alarm 02.pdf PDF
36C25226B0014 0001.docx DOCX document
S02 - PART 3 - FIRE ALARM DEMO PLANS 20260421.pdf PDF
S02 - PART 5 - FIRE ALARM DEMO ONE-LINE DIAGRAMS 20260421.pdf PDF
S02 - PART 8 - FIRE ALARM NEW ONE-LINE DIAGRAMS 20260421.pdf PDF
S02 - PART 4 - FIRE ALARM DEMO PLANS 20260421.pdf PDF
S02 - PART 1 - GENERAL DRAWINGS 20260421.pdf PDF
S02 - Wage Determination WI20260011 Building Mod 1 20260518.pdf PDF
S02 - Bid Specifications_20260421.pdf PDF
S02 - PART 6 - FIRE ALARM NEW PLANS 20260421.pdf PDF
S02 - PART 7 - FIRE ALARM NEW PLANS 20260421.pdf PDF
S02 - 36C25226B0014.docx DOCX document
S02 - PART 9 - ELECTRICAL DRAWINGS 20260421.pdf PDF
S02 - PART 2 - CIVIL DRAWINGS 20260421.pdf PDF
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Infection Control 676-22-110 Upgrade Fire Alarm

Building Building type Floor

ICRA

LEVEL

Mobile ICRA Cart

Approved Infection Control Comments

1 house basement 2 X 1 house 1st 2 X 3 Apartment basement 2 X 3 Apartment 1st 2 X

3 house 2nd 3 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

4 house basement 2 X 4 house 1st 2 X 5 house basement 2 X 5 house 1st 2 X 5 house 2nd 2 X 6 house basement 2 X 6 house 1st 2 X

10 Administration 1st 2 X 12 house basement 2 X 12 house 1st 2 X 12 house 2nd 2 X

15 Gym 1st 3 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

15 Gym 2nd 3 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

18 Apartment Basement 2 X 18 Apartment 1st 2 X 18 Apartment 2nd 2 X 23 Facility services Basement 2 X 23 Facility services 1st 2 X 23 Facility services 2nd 2 X 23 Mechanical room Attic 2 X 25 Mechanical room Basement 2 X 25 Transportation 1st 2 X

Information Technology

Basement 2 X

Information Technology

1st 2 X

36 Fire department 1st 2 X 40 Shops 1st 2 X 52 Wearhouse 1st 2 X

212 Garage 1st 2 X 215 Water Filtration 1st 2 X 223 Garage 1st 2 X 240 Garage 1st 2 X

240A Telephone Shed 1st 2 X

ICRA

LEVEL

Mobile ICRA Cart

Approved Infection Control Comments

Roads and grounds stroage 1st 2 X

270 Garage 1st 2 X

290 HVAC storage Garage 1st 2 X

295 Golf Shack 1st 2 X 296 Picnic Shelter 1st 2 X

400 Mechanical room Basement/Cra wlspace 2 X

400 Hospital 1st 3 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

400 Hospital 2nd 3 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

400 Hospital 3rd 3 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

400 Hospital 4th 3 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

400 Mechanical room Attic 3 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

400 4010B Room 4 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

400 4010D Room 4 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

401 Mechanical room Basement/Cra wlspace 2 X

401 Medical ward Building 1st 3 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

401 Medical ward Building 2nd 4 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

ICRA

LEVEL

Mobile ICRA Cart

Approved Infection Control Comments

401 Medical ward Building 3rd 4 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

401 Mechanical room Attic 2 X

402 Mechanical room Basement/Cra wlspace 2 X

402 Medical ward Building 1st 4 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

402 Medical ward Building 2nd 4 X Vent out doors or low risk adjacent space with particle counter. See specifications for complete details.

402 Medical ward Building 3rd 4 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

402 Mechanical room Attic 2 X

403 Mechanical room Basement/Cra wlspace 2 X

403 Medical ward Building 1st 2 X

403 Medical ward Building 2nd 4 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

403 Medical ward Building 3rd 4 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

403 Mechanical room Attic 2 X

404 Mechanical room Basement/Cra wlspace 2 X

404 Medical ward Building 1st 4 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

404 Medical ward Building 2nd 4 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

404 Medical ward Building 3rd 4 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

404 Mechanical room Attic 2 X

ICRA

LEVEL

Mobile ICRA Cart

Approved Infection Control Comments

405 Medical ward Building 1st 4 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

405 Medical ward Building 2nd 4 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

405 Medical ward Building 3rd 4 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

406 Mechanical room Basement/Cra wlspace 2 X

Administration/phar macy/med storage

1st 2 X

406 med supply 1655/1657/16

58/1659 3 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

406 pharmacy 1660/1672 4 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

406 Bowling alley 1615 3 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

406 Hallway 6C25 3 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

406 Hallway 6C23 3 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

406 Administration 2nd 2 X

406 Medical ward Building 3rd 4 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

406 Mechanical room Attic 2 X

407 Mechanical room Basement/Cra wlspace 2 X

407 Administration 1st 2 X 407 Administration 2nd 2 X 407 Administration 3rd 2 X

ICRA

LEVEL

Mobile ICRA Cart

Approved Infection Control Comments

407 Mechanical room Attic 2 X

408 Mechanical room Basement/Cra wlspace 2 X

408 Administration 1st 2 X

408 Storage 1841 3 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

408 Storage 1810 3 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

408 Hallway 8C11 3 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

408 Administration 2nd 2 X 408 Administration 3rd 2 X 408 Mechanical room Attic 2 X 409 Veterans Home Basement 2 X

409 Veterans Home 1st 4 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

410 Veterans Home Basement 2 X

410 Veterans Home 1st 4 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

411 Women's health 1st 4 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

412 Veterans Home 1st 4 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

415 Boiler plant Lower 2 X 415 Boiler plant 1st 2 X 415 Boiler plant Mezzanine 2 X 416 Mechanical room Basement 2 X

416 Laundry 1st 3 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

421 Pump house 1st 2 X

423 Greenhouse 1st 2 X

ICRA

LEVEL

Mobile ICRA Cart

Approved Infection Control Comments

424 Mechanical room Basement 2 X

424 Kitchen 1st 3 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

424 Kitchen Attic 2 X

425 Chapel 1st 3 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

427 pump house 1st 2 X 445 Generator 1st 2 X 446 Generator 1st 2 X 447 Generator 1st 2 X 448 Generator 1st 2 X 449 Generator 1st 2 X 450 Bulk oxygen 1st 2 X 451 Generator 1st 2 X

Sterile processing department 1st 4 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.

455 Recreation Mechanical 2 X

455 Recreation 1st 3 X

Vent out doors or low risk adjacent space with particle counter. See specifications for complete requirements.