This is Amendment A0007 to a sealed-bid solicitation for fire alarm system upgrade construction services at Tomah VA Medical Center in Tomah, Wisconsin (Solicitation 36C25226B0014). The amendment publishes responses to Requests for Information (RFIs) and extends the bid due date to December 9, 2026, at 10:00 AM local time, with virtual public bid opening scheduled for 11:30 AM the same day via Microsoft Teams.

The amendment addresses critical technical clarifications regarding fire alarm design and installation requirements, including guidelines for heat detectors, smoke detectors, audible/horn strobes, pull stations, duct smoke detectors at air-handling units, door holds, fire alarm control panels, and associated monitoring modules. Key RFI responses confirm that the VA will maintain the existing fire alarm system until the new system is operational (unless the contractor disrupts it), that Davis-Bacon wage classification ELEC0014-005 (Teledata system installer/technician) applies to on-site fire alarm installation and commissioning work, that elevator controllers' makes and models are not provided but fire recall and shunt-trip disconnects are already installed and operational, and that no additional site visits will be scheduled. Bidders must submit bids via email to Lynn.VanderVelde@va.gov and Ryan.McMillin@va.gov with subject line "36C25226B0014" and acknowledge that code compliance and design responsibility rest with the contractor, requiring comprehensive technical knowledge of NFPA fire alarm codes.

View the file

Other files

File Type Posted
S06 - 36C25226B0014 0007 .docx DOCX document
36C25226B0014 0006.docx DOCX document
S06 - Att 2 Addendum No2_20261104.pdf PDF
S06 - Att 1 RFI Response A0005 FINAL 20261104.pdf PDF
36C25226B0014 0005.docx DOCX document
36C25226B0014 0004.docx DOCX document
S06 - Att 1 Updates to Pages 3 and 11 of SOL 36C25226B0014.pdf PDF
S06 - Att 2 Addendum No1 676-22-110 Upgrade Fire Alarm System 20260929.pdf PDF
S06 - Att 3 RFI Response A0003 Oct 6 2026.pdf PDF
36C25226B0014 0003.docx DOCX document
S06 - 36C25226B0014 0002.pdf PDF
S06 - Low Risk Locations - Upgrade Fire Alarm.pdf PDF
S06 - Infection Control 676-22-110 Upgrade Fire Alarm.pdf PDF
S06 - Site Visit Sign-in Aug 25 27-2026.pdf PDF
S06 - High-Highest Risk Locations - Upgrade Fire Alarm.pdf PDF
S06 - RFI Response A0001 Sep 3 2026.pdf PDF
S06 - Medium Risk Locations - Upgrade Fire Alarm 02.pdf PDF
36C25226B0014 0001.docx DOCX document
S02 - PART 3 - FIRE ALARM DEMO PLANS 20260421.pdf PDF
S02 - PART 5 - FIRE ALARM DEMO ONE-LINE DIAGRAMS 20260421.pdf PDF
S02 - PART 8 - FIRE ALARM NEW ONE-LINE DIAGRAMS 20260421.pdf PDF
S02 - PART 4 - FIRE ALARM DEMO PLANS 20260421.pdf PDF
S02 - PART 1 - GENERAL DRAWINGS 20260421.pdf PDF
S02 - Wage Determination WI20260011 Building Mod 1 20260518.pdf PDF
S02 - Bid Specifications_20260421.pdf PDF
S02 - PART 6 - FIRE ALARM NEW PLANS 20260421.pdf PDF
S02 - PART 7 - FIRE ALARM NEW PLANS 20260421.pdf PDF
S02 - 36C25226B0014.docx DOCX document
S02 - PART 9 - ELECTRICAL DRAWINGS 20260421.pdf PDF
S02 - PART 2 - CIVIL DRAWINGS 20260421.pdf PDF
Show all 30

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SF 30 Continuation Page 36C25226B0014 676‐22‐110 Upgrade Fire Alarm System Tomah VA Medical Center, Tomah, WI

Amendment A0007

Amendment 0007 publishes a response to an RFIs and extends out due date.

Question/Comment

It seems the VA is hanging its hat on the design and code compliance being our responsibility. If that is true do we have everything we need today to determine that there is code issues? We have zero HVAC plans, we need that to determine what each building has for air handlers and the CFM associated to determine duct detectors. Do we know the occupancy loading for every room in every building? How do we know what rooms are required to have. We can’t determine if it is code compliant if we do not have the right information.

Critical technical point: duct smoke detectors are governed by air handler CFM ratings (typically >2,000 CFM under NFPA 90A/72). Without mechanical/HVAC drawings showing air handler locations and CFM capacities, it is physically impossible for any electrical bidder to price code-compliant duct detection.

Please confirm via solicitation amendment whether the VA will be updating the drawings/RFI responses and extending the bid date, or if bidders are to price this project strictly per the current plans and specifications as drawn, acknowledging that deferring these clarifications will result in significant post-award schedule and cost impacts.

FIRE ALARM DEVICES

GUIDELINES for Fire Alarm Design and RFI Response on 2026, Nov. 23

NFPA requirements for fire alarm for all buildings associated with the bidding process should be known by the bidders. Anyone unfamiliar with NFPA chapters referenced and/or required to provide a legitimate bid for this project, should then not bid this project.

The NFPA code and code requirements like it should already be known by any one person working on a bid price for the construction of this project.

HEAT DETECTORS

· Delete in all areas except mechanical spaces.

· In kitchen areas – change smoke detectors to heat detectors.

· Generator Rooms.

· Separate/Individual Storage buildings.

· Review plans and one-lines for exceptions.

SMOKE DETECTORS

· Delete all smoke detectors except in:

· Hallways/corridors, located every 30ft, reset after smoke doors.

· IT rooms.

· Electrical and Switchgear Rooms.

· Elevator Lobbies.

· Storage Rooms.

· Classrooms.

· Libraries.

· Attic Mech Rooms.

· In Tramway at Building entry/exit.

· In Buildings at exit to Tramway.

· Stairs (as shown on select plans and one-lines).

· Review plans and one-lines for exceptions.

GENERATOR ROOMS / BUILDINGS

· Rooms

· No smoke detector required in sprinkled building.

· Add heat detector in non-sprinkled building.

· Review plans and one-lines for exceptions.

· Generator houses (small buildings)

· No devices required.

· Review plans and one-lines for exceptions.

AUDIBLE / HORN STROBES –

· Hallways/corridors, located within 15 ft of doorway, end of hall, or (reset) after smoke doors, space/locate every 100 ft.

· Delete all horn/strobes, except in:

· Conference rooms

· Meeting rooms

· Break rooms

· Assembly areas

· Cafeteria

· Open office spaces

· Waiting rooms

· Generator Rooms.

· In Tramway at Building entry/exit.

· In Buildings at exit to Tramway.

· Weather-proof at exterior of buildings.

· Review plans and one-line diagrams.

STROBE ONLY

· Toilet rooms, 15cd.

· Lactation rooms.

· Review plans and one-line diagrams.

PULL STATIONS

· Locate within 5ft of exterior doorway.

· In Buildings at any exit to a Tramway.

· At exit of Basement Mech Rooms at stair bottom.

· At top of stairs exit from any Attic Mech Room.

· At the emergency exit hatch from any Attic Mech Room.

· Generator Rooms.

· Separate/Individual Storage buildings.

· Provide as shown on plans and one-line diagrams.

· Delete from interior stairwell doors and stairwell doors that lead to “no-where” or basement.

STAFF SLEEPING ROOMS

· No smoke detectors in rooms but add to halls.

· Add audible/horn strobe to each room.

ELEVATOR ROOMS

· Three (3) control modules (CM) and a smoke detector.

· Smoke detector required within 20 ft of elevator and marked with “ER”.

FLOW SWITCHES and TAMPER SWITCHES with MONITORING MODULES

· Directly replace at each location noted on the plans and one-lines.

· Directly replace at PIV ass shown on plans and one-lines.

DUCT SMOKE DETECTORS AT AIR-HANDLING UNITS (AHU)

· Directly replace components, devices, and replays at each location noted on the plans.

· At all AHU’s, except as noted, provide manufacturers standard 2.5 to 5 foot sampling tube, cut to length, add holes as required, support opposite end of tube.

· Exception: at AHU-1 in B400 Attic provide manufacturers standard 10 foot sampling tube, cut to length, add holes as required, support opposite side of tube.

· Sample tubes vary in length. The new sample tube must cover 2/3 of the duct or AHU it is installed at. Per NFPA 72 sampling tubes at or over 36” require support through the duct opposite side of the detector. This code and code requirements like it should already be known by any one person working on a bid estimate for this project.

· All air velocities standard ratings device, 300 – 4,000 ft/min.

· Provide/Replace; in-place at existing demolished/new AHU DUCT SMOKE DETECTOR.

DUCT SMOKE DETECTORS and MONITORING MODULES and REPLAYS located at SMOKE DAMPERS with KEY SWITCHES

· Directly replace components, devices, and relays at each location noted on the plans and one-lines.

DOOR HOLDS and MONITORING MODULES and necessary RELAYS

· Directly replace components, devices, and relays at each location noted on the plans and one-lines.

FIRE ALARM CONTROL PANELS

· Provide as shown on plans and one-line diagrams.

FIRE ALARM NAC, ANNUNCIATORS, AND ASSOCIATED REQUIRED

· Provide as shown on plans and one-line diagrams.

· Additional necessary per manufacturers requirements provided by contractor(s).

Question/Comment
Response (VA - COR)

Maintenance of the existing fire alarm system

Spec 01 00 00, paragraph I.1 makes the contractor responsible for maintaining existing fire protection and alarm equipment once a building is turned over. Please confirm the following:

(a) Who maintains the existing system before each building is turned over to the contractor, and between phases?

(b) If an existing device or component fails after turnover but before the new system is fully functional and accepted, through no fault of the contractor, who is responsible for the repair or replacement? Would that be handled by change order?

VA will maintain existing fire alarm system tell new system is operational unless contractor interacts or disrupts operation of existing system.

2. Davis-Bacon classification for fire alarm labor

Wage Determination WI20260011 Mod 1 has no fire alarm technician classification. For on-site fire alarm installation, programming, testing and commissioning, please confirm which classification applies: Electrician (ELEC0014-001) or Teledata system installer/technician (ELEC0014-005). If neither applies, please advise how the VA wants an unlisted classification handled.

USE - ELEC0014-005

We’re pricing the elevator tie-ins for the Tomah fire alarm upgrade. Is there an existing equipment list or a drawing we should use to confirm which elevators are affected, their controller makes and models, and whether fire recall and shunt-trip disconnects are already installed and working?

If that information isn’t available and the VA is allowing additional site visits, could you let us know how to request one?

We don’t have a list of elevator controllers makes and models, fire recall and shunt-trip disconnect are already installed and working. Operation is provided in specification 28 31 00, 3.2 Typical Operation.

No additional site visits will be scheduled for this solicitation.

VIRTUAL BID OPENING INFORMATION:

1) There will be no in-person public bid opening process. This will be conducted as a public virtual activity.

2) The virtual bid opening will be available to the public via Microsoft Teams at the following link and/or phone number:

Join: https://teams.microsoft.com/meet/2473414420095?p=HOJS7WNgrbgMwvO73f

a) (Meeting will be available to be accessed 10 min prior to bid opening)

b) Meeting ID: 247 341 442 009 5

c) Passcode: ks79ub9w

d) Dial-in by phone: 1-872-701-0185; Phone conference ID: 947 858 19#

3) IAW FAR 52.214-5 Submission of Bids and FAR 14.202-8 Electronic Bids; Bids shall be provided via email to the Contracting Officer at Lynn.VanderVelde@va.gov AND Ryan.McMillin@va.gov as follows:

with Subject: 36C25226B0014

BIDS DUE: Vendor bids are due via email as shown above at 10:00 AM local time on December 9th.

The virtual public bid opening will be held at 11:30 AM local time on December 9th at the link and/or the phone # provided above.

……..End of Amendment A0007……..