S06 - 36C25226B0014 0007 .docx
DOCX document 128 KB Posted
- Solicitation number
- 36C25226B0014-1
About this file
This is Amendment 0007 (SF 30 Continuation Page) to solicitation 36C25226B0014 for the Upgrade Fire Alarm System at Tomah VA Medical Center in Tomah, Wisconsin. The amendment extends the bid due date to December 9, 2026 at 10:00 AM CST and publishes responses to Requests for Information (RFIs). The Department of Veterans Affairs Great Lakes Acquisition Center is the issuing office, with Contracting Officer Ryan McMillin administering the contract. Bidders must submit bids via email to Lynn.VanderVelde@va.gov and Ryan.McMillin@va.gov, with virtual bid opening conducted via Microsoft Teams at 11:30 AM CST on December 9, 2026.
The amendment provides critical fire alarm design guidelines and RFI responses addressing bidder concerns regarding code compliance and design responsibility. Key responses clarify that contractors are responsible for NFPA code compliance; Davis-Bacon wage classification ELEC0014-005 applies to fire alarm installation, programming, testing, and commissioning; elevator fire recall and shunt-trip disconnects are already installed and working, with operation detailed in specification 28 31 00; and the VA will not provide additional site visits or updated mechanical/HVAC drawings. The guidelines specify fire alarm device placement requirements including heat detectors in mechanical and generator spaces, smoke detectors in hallways/corridors (every 30 feet), IT rooms, and electrical rooms, audible/horn strobes in hallways (within 15 feet of doorways, spaced every 100 feet) and select rooms, duct smoke detectors at air-handling units with sampling tubes covering two-thirds of the duct, and pull stations within 5 feet of exterior doorways and exits. The VA will maintain the existing fire alarm system until the new system is operational, unless contractor interaction disrupts operations.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SF 30 Continuation Page 36C25226B0014 676‐22‐110 Upgrade Fire Alarm System Tomah VA Medical Center, Tomah, WI
5. PROJECT NUMBER (if applicable)
CODE
7. ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER
3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE OF PAGES
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO.
1. CONTRACT ID CODE
FACILITY CODE
CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office.
is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER
16A. NAME AND TITLE OF CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 30
PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) (such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign) (Signature of Contracting Officer)
676-22-110 36C252 Department of Veterans Affairs 36C252 115 South 84th Street, Suite 101
Milwaukee WI 53214-1476
36C252 Department of Veterans Affairs 36C252 Great Lakes Acquisition Center - HC 115 South 84th Street, Suite 101 Milwaukee WI 53214-1476 To all Offerors/Bidders
36C25226B0014 08-13-2026
X
X
** HOUR & DATE for Receipt of Offers is EXTENDED to: 12-09-2026 10:00 CST
A0007: See SF30 Continuation Page
Ryan McMillin Contracting Officer
Amendment A0007
Amendment 0007 publishes a response to an RFIs and extends out due date.
Question/Comment
It seems the VA is hanging its hat on the design and code compliance being our responsibility. If that is true do we have everything we need today to determine that there is code issues? We have zero HVAC plans, we need that to determine what each building has for air handlers and the CFM associated to determine duct detectors. Do we know the occupancy loading for every room in every building? How do we know what rooms are required to have. We can’t determine if it is code compliant if we do not have the right information.
Critical technical point: duct smoke detectors are governed by air handler CFM ratings (typically >2,000 CFM under NFPA 90A/72). Without mechanical/HVAC drawings showing air handler locations and CFM capacities, it is physically impossible for any electrical bidder to price code-compliant duct detection.
Please confirm via solicitation amendment whether the VA will be updating the drawings/RFI responses and extending the bid date, or if bidders are to price this project strictly per the current plans and specifications as drawn, acknowledging that deferring these clarifications will result in significant post-award schedule and cost impacts.
Response
FIRE ALARM DEVICES GUIDELINES
for Fire Alarm Design and RFI Response on 2026, Nov. 23
NFPA requirements for fire alarm for all buildings associated with the bidding process should be known by the bidders. Anyone unfamiliar with NFPA chapters referenced and/or required to provide a legitimate bid for this project, should then not bid this project.
The NFPA code and code requirements like it should already be known by any one person working on a bid price for the construction of this project.
HEAT DETECTORS
· Delete in all areas except mechanical spaces.
· In kitchen areas – change smoke detectors to heat detectors.
· Generator Rooms.
· Separate/Individual Storage buildings.
· Review plans and one-lines for exceptions.
SMOKE DETECTORS
· Delete all smoke detectors except in:
· Hallways/corridors, located every 30ft, reset after smoke doors.
· IT rooms.
· Electrical and Switchgear Rooms.
· Elevator Lobbies.
· Storage Rooms.
· Classrooms.
· Libraries.
· Attic Mech Rooms.
· In Tramway at Building entry/exit.
· In Buildings at exit to Tramway.
· Stairs (as shown on select plans and one-lines).
· Review plans and one-lines for exceptions.
GENERATOR ROOMS / BUILDINGS
· Rooms
· No smoke detector required in sprinkled building.
· Add heat detector in non-sprinkled building.
· Review plans and one-lines for exceptions.
· Generator houses (small buildings)
· No devices required.
· Review plans and one-lines for exceptions.
AUDIBLE / HORN STROBES –
· Hallways/corridors, located within 15 ft of doorway, end of hall, or (reset) after smoke doors, space/locate every 100 ft.
· Delete all horn/strobes, except in:
· Conference rooms
· Meeting rooms
· Break rooms
· Assembly areas
· Cafeteria
· Open office spaces
· Waiting rooms
· Generator Rooms.
· In Tramway at Building entry/exit.
· In Buildings at exit to Tramway.
· Weather-proof at exterior of buildings.
· Review plans and one-line diagrams.
STROBE ONLY
· Toilet rooms, 15cd.
· Lactation rooms.
· Review plans and one-line diagrams.
PULL STATIONS
· Locate within 5ft of exterior doorway.
· In Buildings at any exit to a Tramway.
· At exit of Basement Mech Rooms at stair bottom.
· At top of stairs exit from any Attic Mech Room.
· At the emergency exit hatch from any Attic Mech Room.
· Generator Rooms.
· Separate/Individual Storage buildings.
· Provide as shown on plans and one-line diagrams.
· Delete from interior stairwell doors and stairwell doors that lead to “no-where” or basement.
STAFF SLEEPING ROOMS
· No smoke detectors in rooms but add to halls.
· Add audible/horn strobe to each room.
ELEVATOR ROOMS
· Three (3) control modules (CM) and a smoke detector.
· Smoke detector required within 20 ft of elevator and marked with “ER”.
FLOW SWITCHES and TAMPER SWITCHES with MONITORING MODULES
· Directly replace at each location noted on the plans and one-lines.
· Directly replace at PIV ass shown on plans and one-lines.
DUCT SMOKE DETECTORS AT AIR-HANDLING UNITS (AHU)
· Directly replace components, devices, and replays at each location noted on the plans.
· At all AHU’s, except as noted, provide manufacturers standard 2.5 to 5 foot sampling tube, cut to length, add holes as required, support opposite end of tube.
· Exception: at AHU-1 in B400 Attic provide manufacturers standard 10 foot sampling tube, cut to length, add holes as required, support opposite side of tube.
· Sample tubes vary in length. The new sample tube must cover 2/3 of the duct or AHU it is installed at. Per NFPA 72 sampling tubes at or over 36” require support through the duct opposite side of the detector. This code and code requirements like it should already be known by any one person working on a bid estimate for this project.
· All air velocities standard ratings device, 300 – 4,000 ft/min.
· Provide/Replace; in-place at existing demolished/new AHU DUCT SMOKE DETECTOR.
DUCT SMOKE DETECTORS and MONITORING MODULES and REPLAYS located at SMOKE DAMPERS with KEY SWITCHES
· Directly replace components, devices, and relays at each location noted on the plans and one-lines.
DOOR HOLDS and MONITORING MODULES and necessary RELAYS
· Directly replace components, devices, and relays at each location noted on the plans and one-lines.
FIRE ALARM CONTROL PANELS
· Provide as shown on plans and one-line diagrams.
FIRE ALARM NAC, ANNUNCIATORS, AND ASSOCIATED REQUIRED
· Provide as shown on plans and one-line diagrams.
· Additional necessary per manufacturers requirements provided by contractor(s).
| Question/Comment |
| Response |
Maintenance of the existing fire alarm system
Spec 01 00 00, paragraph I.1 makes the contractor responsible for maintaining existing fire protection and alarm equipment once a building is turned over. Please confirm the following:
(a) Who maintains the existing system before each building is turned over to the contractor, and between phases?
(b) If an existing device or component fails after turnover but before the new system is fully functional and accepted, through no fault of the contractor, who is responsible for the repair or replacement? Would that be handled by change order?
VA will maintain existing fire alarm system until new system is operational unless contractor interacts or disrupts operation of existing system.
2. Davis-Bacon classification for fire alarm labor
Wage Determination WI20260011 Mod 1 has no fire alarm technician classification. For on-site fire alarm installation, programming, testing and commissioning, please confirm which classification applies: Electrician (ELEC0014-001) or Teledata system installer/technician (ELEC0014-005). If neither applies, please advise how the VA wants an unlisted classification handled.
USE - ELEC0014-005
We’re pricing the elevator tie-ins for the Tomah fire alarm upgrade. Is there an existing equipment list or a drawing we should use to confirm which elevators are affected, their controller makes and models, and whether fire recall and shunt-trip disconnects are already installed and working?
If that information isn’t available and the VA is allowing additional site visits, could you let us know how to request one?
We don’t have a list of elevator controllers makes and models, fire recall and shunt-trip disconnect are already installed and working. Operation is provided in specification 28 31 00, 3.2 Typical Operation.
No additional site visits will be scheduled for this solicitation.
VIRTUAL BID OPENING INFORMATION:
1) There will be no in-person public bid opening process. This will be conducted as a public virtual activity.
2) The virtual bid opening will be available to the public via Microsoft Teams at the following link and/or phone number:
Join: https://teams.microsoft.com/meet/2473414420095?p=HOJS7WNgrbgMwvO73f
a) (Meeting will be available to be accessed 10 min prior to bid opening)
b) Meeting ID: 247 341 442 009 5
c) Passcode: ks79ub9w
d) Dial-in by phone: 1-872-701-0185; Phone conference ID: 947 858 19#
3) IAW FAR 52.214-5 Submission of Bids and FAR 14.202-8 Electronic Bids; Bids shall be provided via email to the Contracting Officer at Lynn.VanderVelde@va.gov AND Ryan.McMillin@va.gov as follows:
with Subject: 36C25226B0014
BIDS DUE: Vendor bids are due via email as shown above at 10:00 AM local time on December 9th.
The virtual public bid opening will be held at 11:30 AM local time on December 9th at the link and/or the phone # provided above.
……..End of Amendment A0007……..