Testing Block-One-10-07-2026.xlsx
XLSX spreadsheet 27 KB Posted
- Solicitation number
- 36C25027Q0009
About this file
This is a testing and inspection requirements document for fire alarm and suppression systems at the Richard L. Roudebush VA Medical Center. The file specifies detailed device locations, quantities, and testing requirements across multiple campus locations including the RLR Campus main facility, a New Building 5, a Vivarium facility, and a Cold Springs Road remote site. Testing requirements are organized by equipment category and reference NFPA 72-2025, NFPA 90A-2025, NFPA 25-2025, and NFPA 101-2025 standards with specific table references for compliance validation.
The RLR Campus main facility requires testing of 3,282 individual devices across 29 device categories, including smoke detectors (684 units), speakers/strobes (717 units), pull stations (226 units), duct detectors (284 units), strobes (253 units), releasing devices (192 units), heat detectors (34 units), and specialized equipment such as fire pump monitoring devices, damper controls, pre-action systems, elevators, and kitchen hood connections. New Building 5 contains 76 devices across 12 categories including control panels, strobes, speakers, smoke detectors, and duct detectors. The Vivarium facility requires testing of 13 devices, and the Cold Springs Road location requires testing of 64 devices including pull stations, smoke detectors, heat detectors, waterflow switches, supervisory devices, strobes, and communicators. All testing requirements are documented with effective dates of October 7, 2026, and align with specific NFPA standards applicable to fire alarm system maintenance and periodic inspection protocols.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25027Q0009 0003.docx | DOCX document | |
| Table 7.1.3 example only.xlsx | XLSX spreadsheet | |
| Testing Block 7.8-10-07-2026.xlsx | XLSX spreadsheet | |
| Site visit sign in 10.7.2026.pdf | ||
| 36C25027Q0009 0002.docx | DOCX document | |
| Testing Block-7.1-7.6-10-07-2026.xlsx | XLSX spreadsheet | |
| RFI Response-10-15-2026.docx | DOCX document | |
| ATTACHMENT II - Instructions for VAAR 852.219-75 UPDATED.docx | DOCX document | |
| RFI Form.docx | DOCX document | |
| 36C25027Q0009 0001.docx | DOCX document | |
| ATTACHMENT II - Instructions for VAAR 852.219-75.docx | DOCX document | |
| 36C25027Q0009.docx | DOCX document | |
| ATTACHMENT I - SCA.pdf |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| 7.0 - SPECIFIC WORK ITEMS SUMMARY & LOCATION PAGE | ||||||
| RLR Campus | ||||||
| 7.1 - Devices location and quantities | ||||||
| Building | Section | Devices Type | Testing Requirements | Location | # of | |
| EOC | NFPA | Table | Devices | |||
| One | 7.1.1 | Supervisory Devices | 02.03.05 EP 01 | 72-2025, Table 14.4.3.20(17)(10)(b-g) | 7.1.1 | 4 |
| One | 7.1.2 | Duct Detectors | 02.03.05 EP 03 | 72, 2025, Table 14.4.3.2 (17) | 7.1.2 | 142 |
| One | 7.1.3 | Heat Detectors | 02.03.05 EP 03 | 72, 2025, Table 14.4.3.2 (17) | 7.1.3 | 34 |
| One | 7.1.4 | Pull Stations | 02.03.05 EP 03 | 72, 2025, Table 14.4.3.2 (17) | 7.1.4 | 226 |
| One | 7.1.5 | Smoke Detectors | 02.03.05 EP 03 | 72, 2025, Table 14.4.3.2 (17) | 7.1.5 | 684 |
| One | 7.1.6 | Releasing Devices | 02.03.05 EP 04 | 72, 2025, Table 14.4.3.2 (22) | 7.1.6 | 192 |
| One | 7.1.7 | Speakers | 02.03.05 EP 04 | 72, 2025, Table 14.4.3.2 (22) | 7.1.7 | 150 |
| One | 7.1.8 | Speakers/ Strobes | 02.03.05 EP 04 | 72, 2025, Table 14.4.3.2 (22) | 7.1.8 | 717 |
| One | 7.1.9 | Strobes | 02.03.05 EP 04 | 72, 2025, Table 14.4.3.2 (22) | 7.1.9 | 253 |
| One | 7.1.10 | Communicators | 02.03.05 EP 05 | 72, 2025, Table 14.4.3.2 (4) | 7.1.10 | 1 |
| One | 7.1.11 | Monitoring Devices | 02.03.05 EP 05 | 72, 2025, Table 14.4.3.2 (4) | 7.1.11 | 7 |
| One | 7.1.12 | Duct Detectors | 02.03.05 EP 19 | 72,Table 14.4.3.2 (17)(7)€ | 7.1.12 | 142 |
| One | 7.1.13 | Fan Shutdown Operation | 02.03.05 EP 19 | 90A, 2025, 6.4.1 | 7.1.13 | 74 |
| One | 7.1.14 | Damper Controls | 02.03.05 EP 18 | 90A, 2025, 5.4.8,80-2025 19.5,105-2025, 7.6.2 | 7.1.14 | 4 |
| One | 7.1.15 | Protected Master Fire Alarm Panel | 02.01.34 EP 02 | 7.1.15 | 3 | |
| One | 7.1.16 | Batteries | 02.01.34 EP 10 | 101-2025 18/19.3.4 | 7.1.16 | 86 |
| One | 7.1.17 | Kitchen Hoods | 02.01.34 EP 10 | 101-2025 18/19.3.4 | 7.1.17 | 6 |
| One | 7.7.18 | Power Supplies | 02.01.34 EP 10 | 101-2025 18/19.3.4 | 7.7.18 | 47 |
| One | 7.1.19 | Programmable Relays | 02.01.34 EP 10 | 101-2025 18/19.3.4 | 7.1.19 | 1 |
| One | 7.1.20 | Remote Test Switch | 02.01.34 EP 10 | 101-2025 18/19.3.4 | 7.1.20 | 3 |
| One | 7.1.21 | Special Controls | 02.01.34 EP 10 | 101-2025 18/19.3.4 | 7.1.21 | 14 |
| One | 7.1.22 | Elevators | 02.01.05 EP 07 | 101-2025 18/19.3.4 | 7.1.22 | 29 |
| One | 7.1.23 | Pre-Action System | 02.01.34 EP 10 | 101-2025 18/19.3.4 | 7.1.23 | 1 |
| One | 7.1.24 | Tamper Switches | 02.03.05 EP 02 | 72-2025 Table 14.4.3.2 (17)(10)(a) & (17)(11) | 7.1.24 | 158 |
| One | 7.1.25 | Waterflow Switches | 02.03.05 EP 02 | 72-2025 Table 14.4.3.2 (17)(10)(a) & (17)(11) | 7.1.25 | 140 |
| One | 7.1.26 | Fire Pump Power | 02.03.05 EP 11 | 25-2025 8.3.3 | 7.1.26 | 1 |
| One | 7.1.2 | Fire Pump Running | 02.03.05 EP 11 | 25-2025 8.3.3 | 7.1.2 | 1 |
| One | 7.1.28 | Fire Pump Trouble | 02.03.05 EP 11 | 25-2025 8.3.3 | 7.1.28 | 1 |
| One | 7.1.29 | Riser Drain Test | 02.03.05 EP 11 | 25-2025 8.3.3 | 7.1.29 | 7 |
10/07/2026
Sheet2
| 7.0 - SPECIFIC WORK ITEMS SUMMARY & LOCATION PAGE | ||||||
| RLR Campus | ||||||
| 7.1 - 7.7 Device location and quantities | ||||||
| Building | Section | Devices Type | Testing Requirements | Location | # of | |
| EOC | NFPA | Table | Devices | |||
| 5 | 7.2.1 | Smoke Detectors | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.2.1 | 2 |
| 5 | 7.2.2 | Speaker/Strobe | 02.03.05 EP 04 | 72-2025, Table 14.4.3.2 (22) | 7.2.1 | 1 |
| 6 | 7.3.1 | Smoke Detectors | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.3.1 | 3 |
| 6 | 7.3.2 | Pull Stations | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.3.2 | 3 |
| 6 | 7.3.3 | Speaker/Strobe | 02.03.05 EP 04 | 72-2025, Table 14.4.3.2 (22) | 7.3.3 | 2 |
| 19 | 7.4.1 | Smoke Detectors | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.4.1 | 2 |
| 19 | 7.4.2 | Pull Stations | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.4.2 | 2 |
| 19 | 7.4.3 | Heat Detectors | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.4.3 | 3 |
| 19 | 7.4.4 | Speaker/Strobe | 02.03.05 EP 04 | 72-2025, Table 14.4.3.2 (22) | 7.4.4 | 4 |
| 19 | 7.4.5 | Strobe | 02.03.05 EP 04 | 72-2025, Table 14.4.3.2 (22) | 7.4.5 | 2 |
| 23 | 7.5.1 | Pull Stations | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.5.1 | 2 |
| 23 | 7.5.2 | Smoke Detectors | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.5.2 | 2 |
| New Bldg 5 | 7.6.1 | Control Panel | 02.03.05 EP 05 | 72, 2025, Table 14.4.3.2 (4) | 7.6.1 | 1 |
| New Bldg 5 | 7.6.2 | Tamper Switches | 02.03.05 EP 02 | 72-2025 Table 14.4.3.2 (17)(10)(a) & (17)(11) | 7.6.2 | 3 |
| New Bldg 5 | 7.6.3 | Waterflow Switches | 02.03.05 EP 02 | 72-2025 Table 14.4.3.2 (17)(10)(a) & (17)(11) | 7.6.3 | 1 |
| New Bldg 5 | 7.6.4 | Speaker/Strobes | 02.03.05 EP 04 | 72-2025, Table 14.4.3.2 (22) | 7.6.4 | 26 |
| New Bldg 5 | 7.6.5 | Ceiling Strobes | 02.03.05 EP 04 | 72-2025, Table 14.4.3.2 (22) | 7.6.5 | 1 |
| New Bldg 5 | 7.6.6 | Strobes | 02.03.05 EP 04 | 72-2025, Table 14.4.3.2 (22) | 7.6.6 | 7 |
| New Bldg 5 | 7.6.7 | Smoke Detectors | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.6.7 | 10 |
| New Bldg 5 | 7.6.8 | Pull Stations | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.6.8 | 10 |
| New Bldg 5 | 7.6.9 | Door Holders | 02.03.05 EP 04 | 72, 2025, Table 14.4.3.2 (22) | 7.6.9 | 2 |
| New Bldg 5 | 7.6.10 | Dual Monitoring Monitors | 02.03.05 EP 05 | 72, 2025, Table 14.4.3.2 (4) | 7.6.10 | 3 |
| New Bldg 5 | 7.6.11 | Duct Detectors | 02.03.05 EP 03 | 72, 2025, Table 14.4.3.2 (17) | 7.6.11 | 2 |
| New Bldg 5 | 7.6.12 | Monitoring Module with relay | 02.03.05 EP 05 | 72, 2025, Table 14.4.3.2 (4) | 7.6.12 | 1 |
| Vivarium | 7.7.1 | Supervisory Devices | 02.03.05 EP 05 | 72, 2025, Table 14.4.3.2 (4) | 7.7.1 | 1 |
| Vivarium | 7.7.2 | Smoke Detectors | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.7.2 | 5 |
| Vivarium | 7.7.3 | Pull Stations | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.7.3 | 2 |
| Vivarium | 7.7.4 | Strobes | 02.03.05 EP 04 | 72-2025, Table 14.4.3.2 (22) | 7.7.4 | 3 |
| Vivarium | 7.7.5 | Horn/Strobe | 02.03.05 EP 04 | 72-2025, Table 14.4.3.2 (22) | 7.7.5 | 2 |
Old 7.8
| 7.0 - SPECIFIC WORK ITEMS SUMMARY & LOCATION PAGE | ||||||
| Cold Springs Road Location | ||||||
| 7.8 - Device location and quantities | ||||||
| Building | Section | Devices Type | Testing Requirements | Location | # of | |
| EOC | NFPA | Table | Devices | |||
| 9 | 7.8.1 | Pull Stations | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.8.1 | 8 |
| 9 | 7.8.2 | Smoke Detectors | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.8.2 | 13 |
| 9 | 7.8.3 | Heat Detectors | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.8.3 | 2 |
| 9 | 7.8.4 | Waterflow Switches | 02.03.05 EP 02 | 72-2025 Table 14.4.3.2 (17)(10)(a) & (17)(11) | 7.8.4 | 4 |
| 9 | 7.8.5 | Supervisory Devices | 02.03.05 EP 01 | 72-2025, Table 14.4.3.20(17)(10)(b-g) | 7.8.5 | 4 |
| 9 | 7.8.6 | Strobes | 02.03.05 EP 04 | 72-2025, Table 14.4.3.2 (22) | 7.8.6 | 4 |
| 9 | 7.8.7 | Horn/Strobe | 02.03.05 EP 04 | 72-2025, Table 14.4.3.2 (22) | 7.8.7 | 15 |
| 9 | 7.8.8 | Communicators | 02.03.05 EP 05 | 72, 2025, Table 14.4.3.2 (4) | 7.8.8 | 1 |
New 7.8
| 7.0 - SPECIFIC WORK ITEMS SUMMARY & LOCATION PAGE | ||||||
| Cold Springs Road Location | ||||||
| 7.8 - Device location and quantities | ||||||
| Building | Section | Devices Type | Testing Requirements | Location | # of | |
| EOC | NFPA | Table | Devices | |||
| 9 | 7.8.1 | Pull Stations | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.7.1 | 8 |
| 9 | 7.7.2 | Smoke Detectors | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.7.2 | 13 |
| 9 | 7.7.3 | Heat Detectors | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.7.3 | 2 |
| 9 | 7.7.4 | Waterflow Switches | 02.03.05 EP 02 | 72-2025 Table 14.4.3.2 (17)(10)(a) & (17)(11) | 7.7.4 | 4 |
| 9 | 7.7.5 | Supervisory Devices | 02.03.05 EP 01 | 72-2025, Table 14.4.3.20(17)(10)(b-g) | 7.7.5 | 4 |
| 9 | 7.7.7 | Strobes | 02.03.05 EP 04 | 72-2025, Table 14.4.3.2 (22) | 7.7.6 | 4 |
| 9 | 7.7.7 | Horn/Strobe | 02.03.05 EP 04 | 72-2025, Table 14.4.3.2 (22) | 7.7.7 | 15 |
| 9 | 7.7.8 | Communicators | 02.03.05 EP 05 | 72, 2025, Table 14.4.3.2 (4) | 7.7.8 | 1 |