Copy of Testing Block-One-11-04-2026-FINAL.xlsx
XLSX spreadsheet 26 KB Posted
- Solicitation number
- 36C25027Q0009
About this file
This file is a Testing Block summary document detailing specific work items, device locations, and testing requirements for fire alarm and suppression system inspections across multiple buildings at the Richard L. Roudebush VA Medical Center. The document specifies quantities and NFPA standards for testing various fire safety devices including smoke detectors (684 in Building 1 alone), pull stations (226), heat detectors (34), duct detectors (142), releasing devices (192), speakers (150), speaker/strobes (717), strobes (253), communicators (1), monitoring devices (7), waterflow switches (140), tamper switches (158), and specialized equipment such as fire pump controls, elevator recall systems, and pre-action systems across the WTS Building 1 (Building 1), RLR Campus outlying buildings (Buildings 5, 6, 19, 21, 22, 23, and Vivarium), and Cold Springs Road location (Buildings 7, 9, 42, 43). Each device entry references specific NFPA 72-2025 and NFPA 25-2025 standards with corresponding testing requirements, including semi-annual supervisory device testing, monthly elevator recall function testing, and quarterly standpipe testing. Testing locations marked with asterisks indicate that contractor must search for device locations as addresses are unavailable. The contract requires all work to comply fully with NFPA 25 standards with no work exclusions permitted, and all listed work must be completed and included in the quoted price with rejection of any quotation containing exclusions. The revised quote submission deadline is November 16, 2026 at 10:00 AM ET to stacie.hill@va.gov, with a target contract start date of December 15, 2026 and performance completion target by December 31, 2026.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25027Q0009 0004.docx | DOCX document | |
| Price Schedule Revised.pdf | ||
| 36C25027Q0009 0003.docx | DOCX document | |
| Testing Block-7.1-7.6-10-07-2026.xlsx | XLSX spreadsheet | |
| RFI Response-10-15-2026.docx | DOCX document | |
| 36C25027Q0009 0002.docx | DOCX document | |
| Testing Block-One-10-07-2026.xlsx | XLSX spreadsheet | |
| Site visit sign in 10.7.2026.pdf | ||
| Testing Block 7.8-10-07-2026.xlsx | XLSX spreadsheet | |
| Table 7.1.3 example only.xlsx | XLSX spreadsheet | |
| ATTACHMENT II - Instructions for VAAR 852.219-75 UPDATED.docx | DOCX document | |
| 36C25027Q0009 0001.docx | DOCX document | |
| RFI Form.docx | DOCX document | |
| ATTACHMENT II - Instructions for VAAR 852.219-75.docx | DOCX document | |
| ATTACHMENT I - SCA.pdf | ||
| 36C25027Q0009.docx | DOCX document |
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WTS Bldg 1 7.1
| 7.0 - SPECIFIC WORK ITEMS SUMMARY & LOCATION PAGE | ||||||
| RLR Campus | ||||||
| 7.1 - Devices location and quantities | ||||||
| Building | Section | Devices Type | Testing Requirements | Location | # of | |
| EOC | NFPA | Table | Devices | |||
| One | 7.1.1 | Supervisory Devices | 02.03.05 EP 01 | 72-2025, Table 14.4.3.20(17)(10)(b-g) Semi-Annual | 7.1.1 | 4 |
| One | 7.1.2 | Duct Detectors | 02.03.05 EP 03 | 72, 2025, Table 14.4.3.2 (17) | 7.1.2 | 142 |
| One | 7.1.3 | Heat Detectors | 02.03.05 EP 03 | 72, 2025, Table 14.4.3.2 (17) | 7.1.3 | 34 |
| One | 7.1.4 | Pull Stations | 02.03.05 EP 03 | 72, 2025, Table 14.4.3.2 (17) | 7.1.4 | 226 |
| One | 7.1.5 | Smoke Detectors | 02.03.05 EP 03 | 72, 2025, Table 14.4.3.2 (17) | 7.1.5 | 684 |
| One | 7.1.6 | Releasing Devices | 02.03.05 EP 04 | 72, 2025, Table 14.4.3.2 (22) | 7.1.6 | 192 |
| One | 7.1.7 | Speakers | 02.03.05 EP 04 | 72, 2025, Table 14.4.3.2 (22) | 7.1.7 | 150 |
| One | 7.1.8 | Speakers/ Strobes | 02.03.05 EP 04 | 72, 2025, Table 14.4.3.2 (22) | 7.1.8 | 717 |
| One | 7.1.9 | Strobes | 02.03.05 EP 04 | 72, 2025, Table 14.4.3.2 (22) | 7.1.9 | 253 |
| One | 7.1.10 | Communicators | 02.03.05 EP 05 | 72, 2025, Table 14.4.3.2 (4) | 7.1.10 | 1 |
| One | 7.1.11 | Monitoring Devices | 02.03.05 EP 05 | 72, 2025, Table 14.4.3.2 (4) | 7.1.11 | 7 |
| One | 7.1.12 | Duct Detectors | 02.03.05 EP 19 | 72,Table 14.4.3.2 (17)(7)€ | 7.1.12 | 142 |
| One | 7.1.13 | Fan Shutdown Operation | 02.03.05 EP 19 | 90A, 2025, 6.4.1 | 7.1.13 | 74 |
| One | 7.1.14 | Damper Controls | 02.03.05 EP 18 | 90A, 2025, 5.4.8,80-2025 19.5,105-2025, 7.6.2 | 7.1.14 | 4 |
| One | 7.1.15 | Protected Master Fire Alarm Panel | 02.01.34 EP 02 | 72-2025, Table 14.4.3.20(17)(10)(b-g) Semi-Annual | 7.1.15 | 3 |
| One | 7.1.16 | Batteries | 02.01.34 EP 10 | 101-2025 18/19.3.4 | 7.1.16 | 86 |
| One | 7.1.17 | Kitchen Hoods | 02.01.34 EP 10 | 101-2025 18/19.3.4 | 7.1.17 | 6 |
| One | 7.7.18 | Power Supplies | 02.01.34 EP 10 | 101-2025 18/19.3.4 | 7.7.18 | 47 |
| One | 7.1.19 | Programmable Relays | 02.01.34 EP 10 | 101-2025 18/19.3.4 | 7.1.19 | 1 |
| One | 7.1.20 | Remote Test Switch | 02.01.34 EP 10 | 101-2025 18/19.3.4 | 7.1.20 | 3 |
| One | 7.1.21 | Special Controls | 02.01.34 EP 10 | 101-2025 18/19.3.4 | 7.1.21 | 14 |
| One | 7.1.22 | Elevators | 02.01.05 EP 07 | 101-2025 18/19.3.4 Recall function-monthly | 7.1.22 | 29 |
| One | 7.1.23 | Pre-Action System | 02.01.34 EP 10 | 101-2025 18/19.3.4 | 7.1.23 | 6 |
| One | 7.1.24 | Tamper Switches | 02.03.05 EP 02 | 72-2025 Table 14.4.3.2 (17)(10)(a) & (17)(11) Semi-Annual | 7.1.24 | 158 |
| One | 7.1.25 | Waterflow Switches | 02.03.05 EP 02 | 72-2025 Table 14.4.3.2 (17)(10)(a) & (17)(11) Semi-Annual | 7.1.25 | 140 |
| One | 7.1.26 | Fire Pump Power | 02.03.05 EP 11 | 25-2025 8.3.3 Alarms verifed during annual test, readiness checked monthly by VA | 7.1.26 | 1 |
| One | 7.1.27 | Fire Pump Running | 02.03.05 EP 11 | 25-2025 8.3.3 Alarms verifed during annual test, readiness checked monthly by VA | 7.1.27 | 1 |
| One | 7.1.28 | Fire Pump Trouble | 02.03.05 EP 11 | 25-2025 8.3.3 Alarms verifed during annual test, readiness checked monthly by VA | 7.1.28 | 1 |
| One* | 7.1.29 | Riser Drain Test | 02.03.05 EP 11 | 25-2025 8.3.3 Quarterly | 7.1.29 | 7 |
| One | 7.1.30 | 5 YR Standpipe Test | 02.03.05 EP12 | 25-2025 6.3.1 | 7.1.30 | 1 |
| Note: This Note applies to all entries with an asterisk adjacent to the Buidling designation. |
| Location and address not available. Contractor wil have to search for devices. |
111/02/2026
WYS Outlying Buildings 7.2-7.9
| 7.0 - SPECIFIC WORK ITEMS SUMMARY & LOCATION PAGE | ||||||
| RLR Campus | ||||||
| 7.2 - 7.9 Device location and quantities | ||||||
| Building | Section | Devices Type | Testing Requirements | Location | # of | |
| EOC | NFPA | Table | Devices | |||
| 5 | 7.2.1 | Smoke Detectors | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.2.1 | 2 |
| 5 | 7.2.2 | Speaker/Strobe | 02.03.05 EP 04 | 72-2025, Table 14.4.3.2 (22) | 7.2.1 | 1 |
| 6 | 7.3.1 | Smoke Detectors | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.3.1 | 3 |
| 6 | 7.3.2 | Pull Stations | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.3.2 | 3 |
| 6 | 7.3.3 | Speaker/Strobe | 02.03.05 EP 04 | 72-2025, Table 14.4.3.2 (22) | 7.3.3 | 2 |
| 19 | 7.4.1 | Smoke Detectors | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.4.1 | 2 |
| 19 | 7.4.2 | Pull Stations | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.4.2 | 2 |
| 19 | 7.4.3 | Heat Detectors | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.4.3 | 3 |
| 19 | 7.4.4 | Speaker/Strobe | 02.03.05 EP 04 | 72-2025, Table 14.4.3.2 (22) | 7.4.4 | 4 |
| 19 | 7.4.5 | Strobe | 02.03.05 EP 04 | 72-2025, Table 14.4.3.2 (22) | 7.4.5 | 2 |
| 23 | 7.5.1 | Pull Stations | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.5.1 | 2 |
| 23 | 7.5.2 | Smoke Detectors | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.5.2 | 2 |
| New Bldg 5 | 7.6.1 | Control Panel | 02.03.05 EP 05 | 72, 2025, Table 14.4.3.2 (4) | 7.6.1 | 1 |
| New Bldg 5 | 7.6.2 | Tamper Switches | 02.03.05 EP 02 | 72-2025 Table 14.4.3.2 (17)(10)(a) & (17)(11) | 7.6.2 | 3 |
| New Bldg 5 | 7.6.3 | Waterflow Switches | 02.03.05 EP 02 | 72-2025 Table 14.4.3.2 (17)(10)(a) & (17)(11) | 7.6.3 | 1 |
| New Bldg 5 | 7.6.4 | Speaker/Strobes | 02.03.05 EP 04 | 72-2025, Table 14.4.3.2 (22) | 7.6.4 | 26 |
| New Bldg 5 | 7.6.5 | Ceiling Strobes | 02.03.05 EP 04 | 72-2025, Table 14.4.3.2 (22) | 7.6.5 | 1 |
| New Bldg 5 | 7.6.6 | Strobes | 02.03.05 EP 04 | 72-2025, Table 14.4.3.2 (22) | 7.6.6 | 7 |
| New Bldg 5 | 7.6.7 | Smoke Detectors | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.6.7 | 10 |
| New Bldg 5 | 7.6.8 | Pull Stations | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.6.8 | 10 |
| New Bldg 5 | 7.6.9 | Door Holders | 02.03.05 EP 04 | 72, 2025, Table 14.4.3.2 (22) | 7.6.9 | 2 |
| New Bldg 5 | 7.6.10 | Dual Monitoring Monitors | 02.03.05 EP 05 | 72, 2025, Table 14.4.3.2 (4) | 7.6.10 | 3 |
| New Bldg 5 | 7.6.11 | Duct Detectors | 02.03.05 EP 03 | 72, 2025, Table 14.4.3.2 (17) | 7.6.11 | 2 |
| New Bldg 5 | 7.6.12 | Monitoring Module with relay | 02.03.05 EP 05 | 72, 2025, Table 14.4.3.2 (4) | 7.6.12 | 1 |
| Vivarium | 7.7.1 | Supervisory Devices | 02.03.05 EP 05 | 72, 2025, Table 14.4.3.2 (4) | 7.7.1 | 1 |
| Vivarium | 7.7.2 | Smoke Detectors | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.7.2 | 5 |
| Vivarium | 7.7.3 | Pull Stations | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.7.3 | 2 |
| Vivarium | 7.7.4 | Strobes | 02.03.05 EP 04 | 72-2025, Table 14.4.3.2 (22) | 7.7.4 | 3 |
| Vivarium | 7.7.5 | Horn/Strobe | 02.03.05 EP 04 | 72-2025, Table 14.4.3.2 (22) | 7.7.5 | 2 |
| Bldg 21* | 7.8.1 | Pull Stations | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.8.1 | 4 |
| Bldg 21* | 7.8.2 | Smoke Detectors | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.8.2 | 4 |
| Bldg 21* | 7.8.3 | Horn/Strobe | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.8.3 | 6 |
| Bldg 21* | 7.8.4 | Tamper Switches | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.8.4 | 1 |
| Bldg 21* | 7.8.5 | Waterflow Switches | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.8.5 | 1 |
| Bldg 22* | 7.9.1 | Pull Stations | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.9.1 | 6 |
| Bldg 22* | 7.9.2 | Smoke Detectors | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.9.2 | 1 |
| Bldg 22* | 7.9.3 | Horn/Strobe | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.9.3 | 9 |
| Bldg 22* | 7.9.4 | Tamper Switches | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.9.4 | 2 |
| Bldg 22* | 7.9.5 | Waterflow Switches | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.9.5 | 2 |
| Bldg 22* | 7.9.6 | Pressure Switches | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.9.6 | 1 |
| Note: This Note applies to all entries with an asterisk adjacent to the Buidling designation. | ||||||
| Location and address not available. Contractor wil have to search for devices. |
11/02/2026
7.10-7.12
| 7.0 - SPECIFIC WORK ITEMS SUMMARY & LOCATION PAGE | ||||||
| Cold Springs Road Location | ||||||
| 7.10 - 7.12 Device location and quantities | ||||||
| Building | Section | Devices Type | Testing Requirements | Location | # of | |
| EOC | NFPA | Table | Devices | |||
| 9 | 7.10.1 | Pull Stations | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.10.1 | 8 |
| 9 | 7.10.2 | Smoke Detectors | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.10.2 | 13 |
| 9 | 7.10.3 | Heat Detectors | 02.03.05 EP 03 | 72-2025, Table 14.4.3.2 (17) | 7.10.3 | 2 |
| 9 | 7.10.4 | Waterflow Switches | 02.03.05 EP 02 | 72-2025 Table 14.4.3.2 (17)(10)(a) & (17)(11) | 7.10.4 | 4 |
| 9 | 7.10.5 | Supervisory Devices | 02.03.05 EP 01 | 72-2025, Table 14.4.3.20(17)(10)(b-g) | 7.10.5 | 4 |
| 9 | 7.10.6 | Strobes | 02.03.05 EP 04 | 72-2025, Table 14.4.3.2 (22) | 7.10.6 | 4 |
| 9 | 7.10.7 | Horn/Strobe | 02.03.05 EP 04 | 72-2025, Table 14.4.3.2 (22) | 7.10.7 | 15 |
| 9 | 7.10.8 | Communicators | 02.03.05 EP 05 | 72, 2025, Table 14.4.3.2 (4) | 7.10.8 | 1 |
| 7* | 7.11.0 | Horn/Strobe | 02.03.05 EP 05 | 72-2025, Table 14.4.3.2 (17) | 7.11.0 | 6 |
| 7* | 7.11.2 | Pull Stations | 02.03.05 EP 05 | 72-2025, Table 14.4.3.2 (17) | 7.11.2 | 5 |
| 7* | 7.11.3 | Smoke Detectors | 02.03.05 EP 05 | 72-2025, Table 14.4.3.2 (17) | 7.11.3 | 16 |
| 43* | 7.11.4 | Pull Stations | 02.03.05 EP 05 | 72-2025, Table 14.4.3.2 (17) | 7.11.4 | 3 |
| 43* | 7.11.5 | Smoke Detectors | 02.03.05 EP 05 | 72-2025, Table 14.4.3.2 (17) | 7.11.5 | 7 |
| 43* | 7.11.6 | Horn/Strobe | 02.03.05 EP 05 | 72-2025, Table 14.4.3.2 (17) | 7.11.6 | 7 |
| 42* | 7.12.1 | Horn/Strobe | 02.03.05 EP 05 | 72-2025, Table 14.4.3.2 (17) | 7.12.1 | 46 |
| 42* | 7.12.2 | Smoke Detectors | 02.03.05 EP 05 | 72-2025, Table 14.4.3.2 (17) | 7.12.2 | 46 |
| 42* | 7.12.3 | Pull Stations | 02.03.05 EP 05 | 72-2025, Table 14.4.3.2 (17) | 7.12.3 | 16 |
| 42* | 7.12.4 | Waterflow Switches | 02.03.05 EP 05 | 72-2025, Table 14.4.3.2 (17) | 7.12.4 | 4 |
| 42* | 7.12.5 | Supervisory Devices | 02.03.05 EP 05 | 72-2025, Table 14.4.3.2 (17) | 7.12.5 | 12 |
| Note: This Note applies to all entries with an asterisk adjacent to the Buidling designation. | ||||||
| Location and address not available. Contractor wil have to search for devices. |
11-02/2026