Attachment II - MD105B - FIFTH FLOOR DEMOLITION PLAN - AREA B.pdf
PDF 410 KB Posted
- Attached to
- Z1DA--Project # 539-21-111 - Upgrade Terminal Units Additional information available on page # 2.
- Solicitation number
- 36C25021B0125
About this file
This document package includes a demolition plan drawing and details for a federal construction project along with the associated solicitation information. The demolition plan drawing provides specifications for removing and replacing various HVAC components on the fifth floor of a Veterans Affairs medical center. Key components to be removed and replaced include terminal units, ductwork, control valves, fans, pumps and piping. The work must be conducted after hours or on weekends to avoid disrupting airflow to parts of the fourth floor. The related solicitation is for project number 539-21-111 to upgrade the terminal units at the specified Veterans Affairs location, with responses due on October 1, 2021. The solicitation is designated for the Department of Veterans Affairs Veterans Health Administration VISN 10.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Med Svc
B501
Office
B503
Office
B504
Office
B518
Office
B517
Office
B516
2 9
AHU-12
12 12
3" C
H S
3" C
H R
3" C
H S
3" C
H R
9" ø
O A
9"ø OA
"ø
O A
Compound Picking
B527
Rolling Storage
B525
Office
B508
Office
B510
Office
B511 Office
B512
Office
B513
Storage
B505H
Office
B505
Conference Rm.
B507
Office
B509
Office
B514
222222
242424242424
101010
101010
22222
26 26
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Cincinnati V.A.
Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FULLY SPRINKLERED
C
U s e rs
\d m c c le a ry
\D o c u m e n ts
\S ta n
C V
A M
C
U p g ra d e
A T
U s
B
M E
P c a d
T Y
G
P .r v t
/1 /2
:0
:3
P
M
MD105B
FIFTH FLOOR DEMOLITION PLAN -
AREA B
08/31/2021 JAC DEM
CINCINNATI, OH
539-21-111CONSTRUCTION
DOCUMENTS
UPGRADE TERMINAL
UNITS
1/8" = 1'-0"
FIFTH FLOOR DEMOLITION PLAN - AREA B
D R A W I N G N O T E S :
1 REMOVE EXISTING VERTICAL FLOOR SET INDUCTION UNIT AND ASSOCIATED ACCESSORIES,
SUPPORTS, CONTROLS, ETC. REMOVE EXISTING OUTSIDE AIR DUCT, CHILLED WATER
SUPPLY & RETURN PIPING, AND CONDENSATE DRAIN PIPING THRU FLOOR SLAB - REFER TO
SHEET BELOW FOR CONTINUATION.
2 EXISTING DUCTWORK TO REMAIN.
3 REMOVE EXISTING DUCTWORK TO THIS POINT, CAP AND SEAL AIRTIGHT.
4 REMOVE EXISTING CHILLED WATER BOOSTER PUMP, FOR REPLACEMENT IN NEW WORK.
5 EXISTING OUTSIDE AIR DUCT, CHILLED WATER SUPPLY & RETURN PIPING, AND
CONDENSATE DRAIN PIPING UP THRU FLOOR SLAB TO REMAIN.
6 REMOVE EXISTING AIR DEVICE AND ASSOCIATED DUCTWORK, ACCESSORIES, ETC.
7 REMOVE EXISTING RETURN FAN VFD FOR REPLACEMENT IN NEW WORK.
8 EXISTING SUPPLY FAN VFD TO REMAIN.
9 EXISTING AIR HANDLING UNIT TO REMAIN.
10 EXISTING PIPING TO REMAIN.
11 EXISTING AIR VALVE TO REMAIN. REFER TO MH SERIES SHEET FOR SCOPE OF WORK
ASSOCIATED WITH THIS VALVE.
12 EXISTING FAN COIL UNIT TO REMAIN. REFER TO MH SERIES SHEET FOR SCOPE OF WORK
ASSOCIATED WITH THIS UNIT.
13 EXISTING ABOVE CEILING INDUCTION UNIT AND ASSOCIATED DUCTWORK, ACCESSORIES,
SUPPORTS, CONTROLS, ETC. TO REMAIN. REFER TO MH SERIES SHEET FOR SCOPE OF
WORK ASSOCIATED WITH THIS UNIT.
14 REMOVE EXISTING SINGLE DUCT VAV BOX AND ASSOCIATED DUCTWORK, ACCESSORIES,
SUPPORTS, CONTROLS, ETC.
15 REMOVE EXISTING AHU-12 RETURN FAN FOR REPLACEMENT IN NEW WORK.
16 REMOVE EXISTING AHU-12 STEAM PREHEAT COIL CONTROL VALVE, FOR REPLACEMENT IN
NEW WORK.
17 REMOVE EXISTING AHU-12 CHILLED WATER COIL CONTROL VALVE, FOR REPLACEMENT IN
NEW WORK.
18 REMOVE EXISTING DUCTWORK AND ASSOCIATED SUPPORTS, ACCESSORIES, ETC.
19 EXISTING INLINE HEATING HOT WATER PUMP TO REMAIN.
20 REMOVE EXISTING DUCT TO THIS POINT FOR RECONNECTION IN NEW WORK.
21 REMOVE EXISTING VERTICAL PIPING BACK TO NEAR FLOOR SLAB, FOR RECONNECTION IN
NEW WORK.
22 EXISTING SUPPLY DUCT HEADER TO REMAIN. REMOVE AND CAP EXISTING INLET DUCT
FROM AHU.
23 REMOVE EXISTING PIPING TO THIS POINT FOR RECONNECTION IN NEW WORK.
24 EXISTING DUCT - MOUNTED STEAM COIL AND ASSOCIATED DUCTWORK, PIPING,
ACCESSORIES, CONTROLS, ETC. TO REMAIN.
25 CAREFULLY REMOVE EXISTING AVERAGING TYPE DDC TEMPERATURE SENSOR, FOR
REINSTILLATION IN NEW WORK.
26 REMOVE EXISTING STEAM HUMIDIFIER AND AND ASSOCIATED PIPING, ACCESSORIES,
CONTROLS, ETC.
27 REMOVE EXISTING PIPING TO THIS POINT AND CAP.
28 REMOVE EXISTING PIPING AND ASSOCIATED SUPPORTS, ACCESSORIES, ETC.
29 REMOVE EXISTING STEAM PIPING THRU FLOOR SLAB, AND INFILL SLAB OPENING TO MATCH
EXISTING. REFER TO FLOOR PLAN BELOW FOR CONTINUATION.
30 REMOVE EXISTING SHEETMETAL TRANSITION AND PLENUM BOX AT OUTLET OF AHU.
31 BOXED OUT REGION REPRESENTS APPROXIMATE AREA ASSOCIATED WITH 5TH FLOOR
INPATIENT PHARMACY. ALL WORK PERFORMED WITHIN THIS AREA SHALL BE
ACCOMPLISHED USING A HEPA CART. COORDINATE ALL WORK AND SCHEDULING WITH COR.
NKEYPLAN
FIFTH FLOOR
Revisions: Date:
Addendum #1 10/01/2021
G E N E R A L N O T E S :
A DURING PERFORMANCE OF THIS WORK, ANY DISRUPTION OF AIRFLOW TO THE SOUTH
WING ON FOURTH FLOOR (INDICATED BY DASHED BOX) SHALL BE LIMITED TO AFTER-
HOURS (NIGHTS OR WEEKENDS). PROVIDE TEMPORARY COOLING/HEATING AS NOTED,
FOR ANY AIRFLOW DISRUPTION TO THE SOUTH WING REQUIRED DURING NORMAL
BUSINESS HOURS.
| Sheets |
| MD105B - FIFTH FLOOR DEMOLITION PLAN - AREA B |
| MH105B - FIFTH FLOOR HVAC PLAN - AREA B |
File details come from the government source that posted it. Updated .