13.53_M602 - MECHANICAL SCHEDULES.pdf

PDF 379 KB Posted

Attached to
Z1DA--Project # 539-21-111 - Upgrade Terminal Units Additional information available on page # 2.
Solicitation number
36C25021B0125
Issued by

About this file

This document contains mechanical schedules for an HVAC system upgrade project. It specifies various air handling equipment including air devices, return grilles, fire dampers, pumps, fans, terminal units, and a steam humidifier. Device schedules provide minimum and maximum airflow ranges, pressure drops, mounting details, motor specifications, and other technical requirements. The project is for upgrading terminal units at the Cincinnati VA Medical Center located in Cincinnati, Ohio under solicitation number 36C25021B0125 issued by the Department of Veterans Affairs Veterans Health Administration VISN 10.

View the file

Other files

File Type Posted
36C25021B0125 0005.docx DOCX document
Attachment II - Amendment No. 5.pdf PDF
Attachment I - Combine Specification Air Terminal Units.pdf PDF
13.54_M700 - MECHANICAL CONTROLS.pdf PDF
JA - DDCASC.pdf PDF
07.03_AC141 - FIRST FLOOR REFLECTED CEILING PLAN.pdf PDF
07.06_AC144 - FOURTH FLOOR REFLECTED CEILING PLAN.pdf PDF
07.08_AC146 - SIXTH FLOOR REFLECTED CEILING PLAN.pdf PDF
07.04_AC142 - SECOND FLOOR REFLECTED CEILING PLAN.pdf PDF
36C25021B0125 0004.docx DOCX document
07.05_AC143 - THIRD FLOOR REFLECTED CEILING PLAN.pdf PDF
Appendix B - Hazardous Material Report.pdf PDF
07.07_AC145 - FIFTH FLOOR REFLECTED CEILING PLAN.pdf PDF
QA.pdf PDF
Specs.pdf PDF
07.09_AC147 - SEVENTH FLOOR REFLECTED CEILING PLAN.pdf PDF
36C25021B0125 0003.docx DOCX document
36C25021B0125 0002.docx DOCX document
36C25021B0125 0001.docx DOCX document
Attachment II - MD105B - FIFTH FLOOR DEMOLITION PLAN - AREA B.pdf PDF
Attachment III - MH105B - FIFTH FLOOR HVAC PLAN - AREA B.pdf PDF
Attachment I - Q and A.pdf PDF
Attachment I - Drawings.pdf PDF
Attachment III - DBA WD.pdf PDF
IFB - 36C25021B0125.pdf PDF
Attachment II - Specifications.pdf PDF
36C25021B0125_1.docx DOCX document
Attachment IV - EMR Form.pdf PDF
Attachment VI - J_A x2.pdf PDF
Attachment V - RFI Form.pdf PDF
Show all 30

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AIR DEVICE SCHEDULE (SUPPLY)

MARK TYPE

AIR FLOW

MAX APD

MOUNTING

PANEL/FRAME SIZE NECK SIZE

NC DAMPER FINISH REMARKSMIN MAX

IN x IN [mm x mm] IN [mm]

CFM [L/s] CFM [L/s] IN WG [Pa]

SD-1 PLAQUE FACE 20 [ 9 ] 75 [ 35 ] 0.100 [ 25 ] CEILING 12 x12 [ 300 x 300 ] 6 ø [150 ø] 30 NONE WHITE 1

SD-2 PLAQUE FACE 75 [ 35 ] 100 [ 47 ] 0.100 [ 25 ] CEILING 24 x 24 [ 600 x 600 ] 6 ø [150 ø] 25 NONE WHITE 1

SD-3 PLAQUE FACE 100 [ 47 ] 200 [ 94 ] 0.100 [ 25 ] CEILING 24 x 24 [ 600 x 600 ] 8 ø [200 ø] 30 NONE WHITE 1

SD-4 PLAQUE FACE 200 [ 94 ] 375 [ 180 ] 0.100 [ 25 ] CEILING 24 x 24 [ 600 x 600 ] 10 ø [250 ø] 30 NONE WHITE 1

SD-5 PLAQUE FACE 375 [ 180 ] 600 [ 280 ] 0.100 [ 25 ] CEILING 24 x 24 [ 600 x 600 ] 12 ø [300 ø] 30 NONE WHITE 1

SD-6 LINEAR SLOT 290 [ 140 ] 365 [ 170 ] 0.100 [ 25 ] CEILING 48 x 4 [ 1200 x 100 ] 10 ø [250 ø] 30 NONE WHITE -----

SD-7

AUTO-CHANGEOVER

LINEAR SLOT

300 [ 140 ] 300 [ 140 ] 0.125 [ 31 ] CEILING 48 x 4 [ 1200 x 100 ] 12 OVAL [300 OVAL] 25 NONE WHITE 2

SD-8 LOUVERED FACE 700 [ 330 ] 700 [ 330 ] 0.050 [ 13 ] DUCT 14 x 12 [ 350 x 300 ] 14 x 12 [ 350 x 300 ] 25 NONE WHITE -----

NOTES:

1. ALL AIR DEVICES 4-WAY THROW UNLESS NOTED ON THE FLOOR PLAN.

2. PROVIDE BI-DIRECTIONAL AIRFLOW PATTERN DETERMINED BY HEATING OR COOLING MODE.

AIR DEVICE SCHEDULE (RETURN)

MARK TYPE

AIR FLOW

MAX APD

MOUNTING

PANEL/FRAME SIZE NECK SIZE

NC FILTER FINISH REMARKSMIN MAX

CFM [L/s] CFM [L/s] IN WG [Pa] IN x IN [mm x mm] IN x IN [mm x mm]

RG-1

EGG CRATE

RETURN GRILLE

0 [ ] 50 [ 24 ] 0.10 25.00 CEILING 12 x 12 [300 x 300 ] 6 x 6 [ 152 x 152 ] 25 NONE WHITE 1

RG-2

EGG CRATE

RETURN GRILLE

50 [ 24 ] 125 [ 59 ] 0.10 25.00 CEILING 12 x 24 [300 x 600 ] 6 x 6 [ 152 x 152 ] 25 NONE WHITE 1

RG-3

EGG CRATE

RETURN GRILLE

125 [ 59 ] 275 [ 130 ] 0.10 25.00 CEILING 12 x 24 [300 x 600 ] 8 x 8 [ 203 x 203 ] 25 NONE WHITE 1

RG-4

EGG CRATE

RETURN GRILLE

275 [ 130 ] 480 [ 230 ] 0.10 25.00 CEILING 12 x 24 [300 x 600 ] 10 x 10 [ 254 x 254 ] 25 NONE WHITE 1

RG-5

EGG CRATE

RETURN GRILLE

480 [ 230 ] 800 [ 380 ] 0.10 25.00 CEILING 24 x 24 [ 600 x 600 ] 12 x 12 [ 600 x 600 ] 25 NONE WHITE 1

RG-6

EGG CRATE

RETURN GRILLE

800 [ 380 ] 1050 [ 480 ] 0.10 25.00 CEILING 24 x 24 [ 600 x 600 ] 14 x 14 [ 600 x 600 ] 25 NONE WHITE 1

RFG-1

EGG CRATE

RETURN GRILLE

0 [ ] 50 [ 24 ] 0.10 25.00 CEILING 12 x 12 [300 x 300 ] 6 x 6 [ 152 x 152 ] 25 MERV 4 WHITE 1

RFG-2

EGG CRATE

RETURN GRILLE

50 [ 24 ] 120 [ 57 ] 0.10 25.00 CEILING 12 x 24 [300 x 600 ] 6 x 6 [ 152 x 152 ] 25 MERV 4 WHITE 1

RFG-3

EGG CRATE

RETURN GRILLE

125 [ 59 ] 275 [ 130 ] 0.10 25.00 CEILING 12 x 24 [300 x 600 ] 8 x 8 [ 203 x 203 ] 25 MERV 4 WHITE 1

RFG-4

EGG CRATE

RETURN GRILLE

275 [ 130 ] 500 [ 240 ] 0.10 25.00 CEILING 12 x 24 [300 x 600 ] 10 x 10 [ 254 x 254 ] 25 MERV 4 WHITE 1

RFG-5

EGG CRATE

RETURN GRILLE

500 [ 240 ] 1380 [ 650 ] 0.10 25.00 CEILING 24 x 24 [ 600 x 600 ] 24 x 24 [ 600 x 600 ] 25 MERV 4 WHITE 1

NOTES:

1. MAX APD SHALL INCLUDE AIR FILTER PRESSURE DROP FOR RETURN GRILLES WITH FILTERS.

FIRE DAMPER SCHEDULE

MARK LOCATION

FAN

SYSTEM

SYSTEM

AND/OR

SERVICE

DUCT SIZE

DUCT PRESSURE

CLASS REMARKS

IN [mm] IN WG [Pa]

FD-1 A144 1-AHU26 VAV26-A144 6 ø [152 ø] 3 [ 750 ] ----

FD-2 A144A 1-AHU26 VAV26-A144 6 ø [152 ø] 3 [ 750 ] ----

FD-3 A144 1-AHU26 VAV26-A144 8 ø [152 ø] 3 [ 750 ] ----

FD-4 B505E 1-AHU12 1-AHU-12 48" X 30" [1219 X 762 ] 3 [ 750 ] ----

PUMP SCHEDULE

MARK LOCATION

AREA AND/OR BLDG

SERVED

SYSTEM AND/OR

SERVICE

TYPE

CIRCULATING FLUID

MIN %

EFF

ELECTRICAL MOTOR

REMARKS

FLUID

FLOW HEAD TEMPERATURE

SP GR

NOMINAL

POWER PHASE VOLT

MAX

RPM

SPEED

CONTROL

GPM [L/s] FT [kPa] °F [°C] HP [kW]

1-P1C 5TH FLOOR PENTHOUSE 4TH FLOOR AREA B HEATING HOT WATER INLINE ECM BOOSTER CLEAR WATER 25 [ 2 ] 40 [ 640 ] 180 [ 82 ] 1 - 0.5 [ ] 1 208 - VARIABLE (ECM) ----

1-P2-1 2ND FLOOR A/C SHAFT (AHU-1 RISER) 2ND FLOOR AREA B CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 30 [ 2 ] 30 [ 480 ] 45 [ 7 ] 1 62.4 1 [ 1 ] 3 460 4600 VARIABLE (ECM) ----

1-P3-1 3RD FLOOR A/C SHAFT (AHU-1 RISER) 3RD FLOOR AREA B CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 45 [ 3 ] 30 [ 480 ] 45 [ 7 ] 1 62.4 1 [ 1 ] 3 460 4600 VARIABLE (ECM) ----

1-P4-1 4TH FLOOR A/C SHAFT (AHU-1 RISER) 4TH FLOOR AREA B CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 145 [ 9 ] 40 [ 640 ] 45 [ 7 ] 1 62.4 3 [ 2 ] 3 460 4600 VARIABLE (ECM) ----

1-P4-2 4TH FLOOR A/C SHAFT (AHU-2 RISER) 4TH FLOOR AREA A SOUTH CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 30 [ 2 ] 30 [ 480 ] 45 [ 7 ] 1 62.4 1 [ 1 ] 3 460 2950 VARIABLE (ECM) ----

1-P4-3 4TH FLOOR A/C SHAFT (AHU-3 RISER) 4TH FLOOR AREA A NORTH CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 35 [ 2 ] 30 [ 480 ] 45 [ 7 ] 1 62.4 1 [ 1 ] 3 460 2950 VARIABLE (ECM) ----

1-P5-1 5TH FLOOR A/C SHAFT (AHU-1 RISER) 5TH FLOOR AREA B CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 85 [ 5 ] 40 [ 640 ] 45 [ 7 ] 1 62.4 2 [ 2 ] 3 460 3300 VARIABLE (ECM) ----

1-P5-2 5TH FLOOR A/C SHAFT (AHU-2 RISER) 5TH FLOOR AREA A SOUTH CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 45 [ 3 ] 30 [ 480 ] 45 [ 7 ] 1 62.4 1 [ 1 ] 3 460 2950 VARIABLE (ECM) ----

1-P5-3 5TH FLOOR A/C SHAFT (AHU-3 RISER) 5TH FLOOR AREA A NORTH CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 65 [ 4 ] 30 [ 480 ] 45 [ 7 ] 1 62.4 1 [ 1 ] 3 460 2950 VARIABLE (ECM) ----

1-P6-1 6TH FLOOR A/C SHAFT (AHU-1 RISER) 6TH FLOOR AREA B CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 45 [ 3 ] 40 [ 640 ] 45 [ 7 ] 1 62.4 1 [ 1 ] 3 460 2950 VARIABLE (ECM) ----

1-P7-1 7TH FLOOR A/C SHAFT (AHU-1 RISER) 7TH FLOOR AREA B CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 35 [ 2 ] 40 [ 640 ] 45 [ 7 ] 1 62.4 1 [ 1 ] 3 460 2950 VARIABLE (ECM) ----

1-P7-2 7TH FLOOR A/C SHAFT (AHU-2 RISER) 7TH FLOOR AREA A SOUTH CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 55 [ 4 ] 30 [ 480 ] 45 [ 7 ] 1 62.4 1 [ 1 ] 3 460 2950 VARIABLE (ECM) ----

1-P7-3 7TH FLOOR A/C SHAFT (AHU-3 RISER) 7TH FLOOR AREA A NORTH CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 65 [ 4 ] 30 [ 480 ] 45 [ 7 ] 1 62.4 1 [ 1 ] 3 460 2950 VARIABLE (ECM) ----

1-P8-1 9TH FLOOR PENTHOUSE (AHU-1 RISER) 8TH FLOOR AREA B CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 25 [ 2 ] 40 [ 640 ] 45 [ 7 ] 1 62.4 1 [ 1 ] 3 460 2950 VARIABLE (ECM) ----

1-P8-3 8TH FLOOR A/C SHAFT (AHU-3 RISER) 8TH FLOOR AREA A NORTH CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 35 [ 2 ] 30 [ 480 ] 45 [ 7 ] 1 62.4 1 [ 1 ] 3 460 2950 VARIABLE (ECM) ----

1-P9-1 9TH FLOOR PENTHOUSE (AHU-1 RISER) 9TH FLOOR AREA B SOUTH CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 20 [ 1 ] 40 [ 640 ] 45 [ 7 ] 1 62.4 1 [ 1 ] 3 460 3600 VARIABLE (ECM) ----

1-P9-2 9TH FLOOR A/C SHAFT (AHU-2 RISER) 9TH FLOOR AREA A SOUTH CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 35 [ 2 ] 30 [ 480 ] 45 [ 7 ] 1 62.4 1 [ 1 ] 3 460 2950 VARIABLE (ECM) ----

FAN SCHEDULE

MARK LOCATION

AREA

AND/OR

BLDG

SERVED

SYSTEM

AND/OR

SERVICE

AIR FLOW TSP

FAN MOTOR ELECTRICAL

CONTROL

SEQUENCE

REMARKS

TYPE WHEEL CLASS

ARRANGEMENT,

ROTATION, AND

DISCHARGE

DIAMETER MIN %

EFF

DRIVE

FAN

MAX

RPM

NOMINAL POWER

PHASE VOLT RPM

SPEED

CONTROL

CFM [L/s] IN [Pa] IN [mm] BHP HP [kW]

12-RF1

5TH FLOOR

PENTHOUSE

4TH FLOOR

AREA B

1-AHU12 11700 [ 5500 ] 3 [ 750 ]

SINGLE WIDTH

SINGLE INLET

AIRFOIL I

ARR 10, CCW ROTATION,

UPBLAST

33 [ 839 ] 78% BELT 1210 7.5 10 [ 8 ] 3 208 960 VARIABLE EXISTING ---

SINGLE DUCT AIR TERMINAL UNIT SCHEDULE (EXHAUST)

MARK LOCATION

SYSTEM AIR

HANDLING

APPROX. DUCT

INLET SIZE

MAX APD MAX

ROOM NC

AIR FLOW

CONTROL

TYPE

CONTROL

SEQUENCE

REMARKSMAX MIN UNOCCUPIED

IN [mm] IN WG [Pa] CFM [L/s] CFM [L/s] CFM [L/s]

EV23-C236 C236 23 8 [ 200 ] 0.25 [ 63 ] 35 750 [ 350 ] 250 [ 120 ] 250 [ 120 ] VAV SEE DRAWINGS 1,2,3,4

EV23-C229 C229 23 12 [ 300 ] 0.25 [ 63 ] 35 1380 [ 650 ] 1380 [ 650 ] 1380 [ 650 ] CAV SEE DRAWINGS 1,2,3,4

EV23-C229G C229H 23 6 [ 150 ] 0.25 [ 63 ] 35 170 [ 80 ] 110 [ 52 ] 110 [ 52 ] VAV SEE DRAWINGS 1,2,3,4

EV23-C229J C229J 23 12 [ 300 ] 0.25 [ 63 ] 35 810 [ 380 ] 810 [ 380 ] 810 [ 380 ] CAV SEE DRAWINGS ALL

EV23-C229N C229N 23 5 [ 130 ] 0.25 [ 63 ] 35 260 [ 120 ] 180 [ 85 ] 180 [ 85 ] VAV SEE DRAWINGS 1,2,3,4

EV23-C230 C230 23 12 [ 300 ] 0.25 [ 63 ] 35 1380 [ 650 ] 1380 [ 650 ] 1380 [ 650 ] CAV SEE DRAWINGS 1,2,3,4

EV23-C231 C231 23 12 [ 300 ] 0.25 [ 63 ] 35 1840 [ 870 ] 480 [ 230 ] 480 [ 230 ] VAV SEE DRAWINGS 1,2,3,4

EV23-C*2*9 C*2*9 23 16 [ 400 ] 0.25 [ 63 ] 35 3330 [ 1600 ] 3330 [ 1600 ] 3330 [ 1600 ] CAV SEE DRAWINGS 1,2,3,4

EV23-A456E A456E 23 12 [ 300 ] 0.25 [ 63 ] 35 1325 [ 630 ] 1325 [ 630 ] 410 [ 190 ] VAV SEE DRAWINGS 1,2,3,4

NOTES:

1. MAX APD IS THE PRESSURE DIFFERENCE BETWEEN THE UNIT INLET, DISCHARGE, AND SOUND ATTENUATOR. IT IS ALSO THE MINIMUM PRESSURE REQUIRED AT THE UNIT INLET TO OBTAIN THE SCHEDULED MAX AIRFLOW.

2. PROVIDE HOSPITAL GRADE SOUND ATTENUATOR WHERE REQUIRED TO COMPLY WITH THE SCHEDULED MAX ROOM NC VALUE.

3. UNIT SOUND POWER LEVEL SHALL NOT EXCEED THE SCHEDULED MAX ROOM NC FROM BOTH AIRBORNE AND RADIATED NOISE, BASED ON A 10 DB ROOM ABSORPTION COEFFICIENT, WITH 3" INLET STATIC PRESSURE.

4. CONTROL TYPES: VVR = VARIABLE AIR VOLUME WITH REHEAT, CVR = CONSTANT AIR VOLUME WITH REHEAT, VAV = VARIABLE AIR VOLUME WITHOUT REHEAT, CAV = CONSTANT AIR VOLUME WITHOUT REHEAT.

5. PROVIDE WITH STAINLESS STEEL CONSTRUCTION.

AIR DEVICE SCHEDULE (EXHAUST)

MARK TYPE

AIR FLOW

MAX APD

MOUNTING

PANEL/FRAME SIZE NECK SIZE

NC FILTER FINISH REMARKSMIN MAX

CFM [L/s] CFM [L/s] IN WG [Pa] IN x IN [mm x mm] IN x IN [mm x mm]

EG-1 EGG CRATE 260 [ 120 ] 260 [ 120 ] 0.10 25.00 CEILING 12 x 24 [300 x 600 ] 8 x 8 [ 203 x 203 ] 25 NONE WHITE -

STEAM HUMIDIFIER SCHEDULE

MARK LOCATION

SYSTEM

AND/OR

SEVICE

HUMIDIFIER

TYPE

AIR FLOW # OF

MANIFOLDS

EAT LAT

SOURCE

STEAM

TRAP CAPACITY

REMARKSDb

%RH

Db

%RH

PRESS ENT VALVE PRESS ENT HEATER FLOW

CFM [L/s] °F [°C] °F [°C] PSIG [kPa] PSIG [kPa] LBS/HR [kg/HR] LBS/HR [kg/HR]

1-SH12 FIFTH FLOOR PENTHOUSE AHU-12 STEAM 12,765 [ 6000 ] 1 54.5 [ 13 ] - 55 [ 13 ] - BUILDING STEAM 30 [ 210 ] 15 [ 100 ] 67 [ 30 ] 14 [ 6 ] ----

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Cincinnati V.A Medical Center

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FULLY SPRINKLERED

C U s e rs

\j o h n f\

D o c u m e n ts \F

F E

C in c in n a ti

U p g ra d e A

T U s B

M

E P jo h n

.g ru b e rA

Q

P J .r v t

/1 /2

:5

:2

P M

M602

MECHANICAL SCHEDULES

08/31/2021 KF JG

CINCINNATI, OH

539-21-111CONSTRUCTION

DOCUMENTS

UPGRADE TERMINAL

UNITS

05/20/2021 Revisions: Date:

AMENDMENT 2 10/20/2021

08/31/2021

Sheets
M602 - MECHANICAL SCHEDULES