This document contains mechanical schedules for an HVAC system upgrade project. It specifies various air handling equipment including air devices, return grilles, fire dampers, pumps, fans, terminal units, and a steam humidifier. Device schedules provide minimum and maximum airflow ranges, pressure drops, mounting details, motor specifications, and other technical requirements. The project is for upgrading terminal units at the Cincinnati VA Medical Center located in Cincinnati, Ohio under solicitation number 36C25021B0125 issued by the Department of Veterans Affairs Veterans Health Administration VISN 10.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AIR DEVICE SCHEDULE (SUPPLY)
MARK TYPE
AIR FLOW
MAX APD
MOUNTING
PANEL/FRAME SIZE NECK SIZE
NC DAMPER FINISH REMARKSMIN MAX
IN x IN [mm x mm] IN [mm]
CFM [L/s] CFM [L/s] IN WG [Pa]
SD-1 PLAQUE FACE 20 [ 9 ] 75 [ 35 ] 0.100 [ 25 ] CEILING 12 x12 [ 300 x 300 ] 6 ø [150 ø] 30 NONE WHITE 1
SD-2 PLAQUE FACE 75 [ 35 ] 100 [ 47 ] 0.100 [ 25 ] CEILING 24 x 24 [ 600 x 600 ] 6 ø [150 ø] 25 NONE WHITE 1
SD-3 PLAQUE FACE 100 [ 47 ] 200 [ 94 ] 0.100 [ 25 ] CEILING 24 x 24 [ 600 x 600 ] 8 ø [200 ø] 30 NONE WHITE 1
SD-4 PLAQUE FACE 200 [ 94 ] 375 [ 180 ] 0.100 [ 25 ] CEILING 24 x 24 [ 600 x 600 ] 10 ø [250 ø] 30 NONE WHITE 1
SD-5 PLAQUE FACE 375 [ 180 ] 600 [ 280 ] 0.100 [ 25 ] CEILING 24 x 24 [ 600 x 600 ] 12 ø [300 ø] 30 NONE WHITE 1
SD-6 LINEAR SLOT 290 [ 140 ] 365 [ 170 ] 0.100 [ 25 ] CEILING 48 x 4 [ 1200 x 100 ] 10 ø [250 ø] 30 NONE WHITE -----
SD-7
AUTO-CHANGEOVER
LINEAR SLOT
300 [ 140 ] 300 [ 140 ] 0.125 [ 31 ] CEILING 48 x 4 [ 1200 x 100 ] 12 OVAL [300 OVAL] 25 NONE WHITE 2
SD-8 LOUVERED FACE 700 [ 330 ] 700 [ 330 ] 0.050 [ 13 ] DUCT 14 x 12 [ 350 x 300 ] 14 x 12 [ 350 x 300 ] 25 NONE WHITE -----
NOTES:
1. ALL AIR DEVICES 4-WAY THROW UNLESS NOTED ON THE FLOOR PLAN.
2. PROVIDE BI-DIRECTIONAL AIRFLOW PATTERN DETERMINED BY HEATING OR COOLING MODE.
AIR DEVICE SCHEDULE (RETURN)
MARK TYPE
AIR FLOW
MAX APD
MOUNTING
PANEL/FRAME SIZE NECK SIZE
NC FILTER FINISH REMARKSMIN MAX
CFM [L/s] CFM [L/s] IN WG [Pa] IN x IN [mm x mm] IN x IN [mm x mm]
RG-1
EGG CRATE
RETURN GRILLE
0 [ ] 50 [ 24 ] 0.10 25.00 CEILING 12 x 12 [300 x 300 ] 6 x 6 [ 152 x 152 ] 25 NONE WHITE 1
RG-2
EGG CRATE
RETURN GRILLE
50 [ 24 ] 125 [ 59 ] 0.10 25.00 CEILING 12 x 24 [300 x 600 ] 6 x 6 [ 152 x 152 ] 25 NONE WHITE 1
RG-3
EGG CRATE
RETURN GRILLE
125 [ 59 ] 275 [ 130 ] 0.10 25.00 CEILING 12 x 24 [300 x 600 ] 8 x 8 [ 203 x 203 ] 25 NONE WHITE 1
RG-4
EGG CRATE
RETURN GRILLE
275 [ 130 ] 480 [ 230 ] 0.10 25.00 CEILING 12 x 24 [300 x 600 ] 10 x 10 [ 254 x 254 ] 25 NONE WHITE 1
RG-5
EGG CRATE
RETURN GRILLE
480 [ 230 ] 800 [ 380 ] 0.10 25.00 CEILING 24 x 24 [ 600 x 600 ] 12 x 12 [ 600 x 600 ] 25 NONE WHITE 1
RG-6
EGG CRATE
RETURN GRILLE
800 [ 380 ] 1050 [ 480 ] 0.10 25.00 CEILING 24 x 24 [ 600 x 600 ] 14 x 14 [ 600 x 600 ] 25 NONE WHITE 1
RFG-1
EGG CRATE
RETURN GRILLE
0 [ ] 50 [ 24 ] 0.10 25.00 CEILING 12 x 12 [300 x 300 ] 6 x 6 [ 152 x 152 ] 25 MERV 4 WHITE 1
RFG-2
EGG CRATE
RETURN GRILLE
50 [ 24 ] 120 [ 57 ] 0.10 25.00 CEILING 12 x 24 [300 x 600 ] 6 x 6 [ 152 x 152 ] 25 MERV 4 WHITE 1
RFG-3
EGG CRATE
RETURN GRILLE
125 [ 59 ] 275 [ 130 ] 0.10 25.00 CEILING 12 x 24 [300 x 600 ] 8 x 8 [ 203 x 203 ] 25 MERV 4 WHITE 1
RFG-4
EGG CRATE
RETURN GRILLE
275 [ 130 ] 500 [ 240 ] 0.10 25.00 CEILING 12 x 24 [300 x 600 ] 10 x 10 [ 254 x 254 ] 25 MERV 4 WHITE 1
RFG-5
EGG CRATE
RETURN GRILLE
500 [ 240 ] 1380 [ 650 ] 0.10 25.00 CEILING 24 x 24 [ 600 x 600 ] 24 x 24 [ 600 x 600 ] 25 MERV 4 WHITE 1
NOTES:
1. MAX APD SHALL INCLUDE AIR FILTER PRESSURE DROP FOR RETURN GRILLES WITH FILTERS.
FIRE DAMPER SCHEDULE
MARK LOCATION
FAN
SYSTEM
SYSTEM
AND/OR
SERVICE
DUCT SIZE
DUCT PRESSURE
CLASS REMARKS
IN [mm] IN WG [Pa]
FD-1 A144 1-AHU26 VAV26-A144 6 ø [152 ø] 3 [ 750 ] ----
FD-2 A144A 1-AHU26 VAV26-A144 6 ø [152 ø] 3 [ 750 ] ----
FD-3 A144 1-AHU26 VAV26-A144 8 ø [152 ø] 3 [ 750 ] ----
FD-4 B505E 1-AHU12 1-AHU-12 48" X 30" [1219 X 762 ] 3 [ 750 ] ----
PUMP SCHEDULE
MARK LOCATION
AREA AND/OR BLDG
SERVED
SYSTEM AND/OR
SERVICE
TYPE
CIRCULATING FLUID
MIN %
EFF
ELECTRICAL MOTOR
REMARKS
FLUID
FLOW HEAD TEMPERATURE
SP GR
NOMINAL
POWER PHASE VOLT
MAX
RPM
SPEED
CONTROL
GPM [L/s] FT [kPa] °F [°C] HP [kW]
1-P1C 5TH FLOOR PENTHOUSE 4TH FLOOR AREA B HEATING HOT WATER INLINE ECM BOOSTER CLEAR WATER 25 [ 2 ] 40 [ 640 ] 180 [ 82 ] 1 - 0.5 [ ] 1 208 - VARIABLE (ECM) ----
1-P2-1 2ND FLOOR A/C SHAFT (AHU-1 RISER) 2ND FLOOR AREA B CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 30 [ 2 ] 30 [ 480 ] 45 [ 7 ] 1 62.4 1 [ 1 ] 3 460 4600 VARIABLE (ECM) ----
1-P3-1 3RD FLOOR A/C SHAFT (AHU-1 RISER) 3RD FLOOR AREA B CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 45 [ 3 ] 30 [ 480 ] 45 [ 7 ] 1 62.4 1 [ 1 ] 3 460 4600 VARIABLE (ECM) ----
1-P4-1 4TH FLOOR A/C SHAFT (AHU-1 RISER) 4TH FLOOR AREA B CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 145 [ 9 ] 40 [ 640 ] 45 [ 7 ] 1 62.4 3 [ 2 ] 3 460 4600 VARIABLE (ECM) ----
1-P4-2 4TH FLOOR A/C SHAFT (AHU-2 RISER) 4TH FLOOR AREA A SOUTH CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 30 [ 2 ] 30 [ 480 ] 45 [ 7 ] 1 62.4 1 [ 1 ] 3 460 2950 VARIABLE (ECM) ----
1-P4-3 4TH FLOOR A/C SHAFT (AHU-3 RISER) 4TH FLOOR AREA A NORTH CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 35 [ 2 ] 30 [ 480 ] 45 [ 7 ] 1 62.4 1 [ 1 ] 3 460 2950 VARIABLE (ECM) ----
1-P5-1 5TH FLOOR A/C SHAFT (AHU-1 RISER) 5TH FLOOR AREA B CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 85 [ 5 ] 40 [ 640 ] 45 [ 7 ] 1 62.4 2 [ 2 ] 3 460 3300 VARIABLE (ECM) ----
1-P5-2 5TH FLOOR A/C SHAFT (AHU-2 RISER) 5TH FLOOR AREA A SOUTH CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 45 [ 3 ] 30 [ 480 ] 45 [ 7 ] 1 62.4 1 [ 1 ] 3 460 2950 VARIABLE (ECM) ----
1-P5-3 5TH FLOOR A/C SHAFT (AHU-3 RISER) 5TH FLOOR AREA A NORTH CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 65 [ 4 ] 30 [ 480 ] 45 [ 7 ] 1 62.4 1 [ 1 ] 3 460 2950 VARIABLE (ECM) ----
1-P6-1 6TH FLOOR A/C SHAFT (AHU-1 RISER) 6TH FLOOR AREA B CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 45 [ 3 ] 40 [ 640 ] 45 [ 7 ] 1 62.4 1 [ 1 ] 3 460 2950 VARIABLE (ECM) ----
1-P7-1 7TH FLOOR A/C SHAFT (AHU-1 RISER) 7TH FLOOR AREA B CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 35 [ 2 ] 40 [ 640 ] 45 [ 7 ] 1 62.4 1 [ 1 ] 3 460 2950 VARIABLE (ECM) ----
1-P7-2 7TH FLOOR A/C SHAFT (AHU-2 RISER) 7TH FLOOR AREA A SOUTH CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 55 [ 4 ] 30 [ 480 ] 45 [ 7 ] 1 62.4 1 [ 1 ] 3 460 2950 VARIABLE (ECM) ----
1-P7-3 7TH FLOOR A/C SHAFT (AHU-3 RISER) 7TH FLOOR AREA A NORTH CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 65 [ 4 ] 30 [ 480 ] 45 [ 7 ] 1 62.4 1 [ 1 ] 3 460 2950 VARIABLE (ECM) ----
1-P8-1 9TH FLOOR PENTHOUSE (AHU-1 RISER) 8TH FLOOR AREA B CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 25 [ 2 ] 40 [ 640 ] 45 [ 7 ] 1 62.4 1 [ 1 ] 3 460 2950 VARIABLE (ECM) ----
1-P8-3 8TH FLOOR A/C SHAFT (AHU-3 RISER) 8TH FLOOR AREA A NORTH CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 35 [ 2 ] 30 [ 480 ] 45 [ 7 ] 1 62.4 1 [ 1 ] 3 460 2950 VARIABLE (ECM) ----
1-P9-1 9TH FLOOR PENTHOUSE (AHU-1 RISER) 9TH FLOOR AREA B SOUTH CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 20 [ 1 ] 40 [ 640 ] 45 [ 7 ] 1 62.4 1 [ 1 ] 3 460 3600 VARIABLE (ECM) ----
1-P9-2 9TH FLOOR A/C SHAFT (AHU-2 RISER) 9TH FLOOR AREA A SOUTH CHILLED WATER INLINE ECM BOOSTER CLEAR WATER 35 [ 2 ] 30 [ 480 ] 45 [ 7 ] 1 62.4 1 [ 1 ] 3 460 2950 VARIABLE (ECM) ----
FAN SCHEDULE
MARK LOCATION
AREA
AND/OR
BLDG
SERVED
SYSTEM
AND/OR
SERVICE
AIR FLOW TSP
FAN MOTOR ELECTRICAL
CONTROL
SEQUENCE
REMARKS
TYPE WHEEL CLASS
ARRANGEMENT,
ROTATION, AND
DISCHARGE
DIAMETER MIN %
EFF
DRIVE
FAN
MAX
RPM
NOMINAL POWER
PHASE VOLT RPM
SPEED
CONTROL
CFM [L/s] IN [Pa] IN [mm] BHP HP [kW]
12-RF1
5TH FLOOR
PENTHOUSE
4TH FLOOR
AREA B
1-AHU12 11700 [ 5500 ] 3 [ 750 ]
SINGLE WIDTH
SINGLE INLET
AIRFOIL I
ARR 10, CCW ROTATION,
UPBLAST
33 [ 839 ] 78% BELT 1210 7.5 10 [ 8 ] 3 208 960 VARIABLE EXISTING ---
SINGLE DUCT AIR TERMINAL UNIT SCHEDULE (EXHAUST)
MARK LOCATION
SYSTEM AIR
HANDLING
APPROX. DUCT
INLET SIZE
MAX APD MAX
ROOM NC
AIR FLOW
CONTROL
TYPE
CONTROL
SEQUENCE
REMARKSMAX MIN UNOCCUPIED
IN [mm] IN WG [Pa] CFM [L/s] CFM [L/s] CFM [L/s]
EV23-C236 C236 23 8 [ 200 ] 0.25 [ 63 ] 35 750 [ 350 ] 250 [ 120 ] 250 [ 120 ] VAV SEE DRAWINGS 1,2,3,4
EV23-C229 C229 23 12 [ 300 ] 0.25 [ 63 ] 35 1380 [ 650 ] 1380 [ 650 ] 1380 [ 650 ] CAV SEE DRAWINGS 1,2,3,4
EV23-C229G C229H 23 6 [ 150 ] 0.25 [ 63 ] 35 170 [ 80 ] 110 [ 52 ] 110 [ 52 ] VAV SEE DRAWINGS 1,2,3,4
EV23-C229J C229J 23 12 [ 300 ] 0.25 [ 63 ] 35 810 [ 380 ] 810 [ 380 ] 810 [ 380 ] CAV SEE DRAWINGS ALL
EV23-C229N C229N 23 5 [ 130 ] 0.25 [ 63 ] 35 260 [ 120 ] 180 [ 85 ] 180 [ 85 ] VAV SEE DRAWINGS 1,2,3,4
EV23-C230 C230 23 12 [ 300 ] 0.25 [ 63 ] 35 1380 [ 650 ] 1380 [ 650 ] 1380 [ 650 ] CAV SEE DRAWINGS 1,2,3,4
EV23-C231 C231 23 12 [ 300 ] 0.25 [ 63 ] 35 1840 [ 870 ] 480 [ 230 ] 480 [ 230 ] VAV SEE DRAWINGS 1,2,3,4
EV23-C*2*9 C*2*9 23 16 [ 400 ] 0.25 [ 63 ] 35 3330 [ 1600 ] 3330 [ 1600 ] 3330 [ 1600 ] CAV SEE DRAWINGS 1,2,3,4
EV23-A456E A456E 23 12 [ 300 ] 0.25 [ 63 ] 35 1325 [ 630 ] 1325 [ 630 ] 410 [ 190 ] VAV SEE DRAWINGS 1,2,3,4
NOTES:
1. MAX APD IS THE PRESSURE DIFFERENCE BETWEEN THE UNIT INLET, DISCHARGE, AND SOUND ATTENUATOR. IT IS ALSO THE MINIMUM PRESSURE REQUIRED AT THE UNIT INLET TO OBTAIN THE SCHEDULED MAX AIRFLOW.
2. PROVIDE HOSPITAL GRADE SOUND ATTENUATOR WHERE REQUIRED TO COMPLY WITH THE SCHEDULED MAX ROOM NC VALUE.
3. UNIT SOUND POWER LEVEL SHALL NOT EXCEED THE SCHEDULED MAX ROOM NC FROM BOTH AIRBORNE AND RADIATED NOISE, BASED ON A 10 DB ROOM ABSORPTION COEFFICIENT, WITH 3" INLET STATIC PRESSURE.
4. CONTROL TYPES: VVR = VARIABLE AIR VOLUME WITH REHEAT, CVR = CONSTANT AIR VOLUME WITH REHEAT, VAV = VARIABLE AIR VOLUME WITHOUT REHEAT, CAV = CONSTANT AIR VOLUME WITHOUT REHEAT.
5. PROVIDE WITH STAINLESS STEEL CONSTRUCTION.
AIR DEVICE SCHEDULE (EXHAUST)
MARK TYPE
AIR FLOW
MAX APD
MOUNTING
PANEL/FRAME SIZE NECK SIZE
NC FILTER FINISH REMARKSMIN MAX
CFM [L/s] CFM [L/s] IN WG [Pa] IN x IN [mm x mm] IN x IN [mm x mm]
EG-1 EGG CRATE 260 [ 120 ] 260 [ 120 ] 0.10 25.00 CEILING 12 x 24 [300 x 600 ] 8 x 8 [ 203 x 203 ] 25 NONE WHITE -
STEAM HUMIDIFIER SCHEDULE
MARK LOCATION
SYSTEM
AND/OR
SEVICE
HUMIDIFIER
TYPE
AIR FLOW # OF
MANIFOLDS
EAT LAT
SOURCE
STEAM
TRAP CAPACITY
REMARKSDb
%RH
Db
%RH
PRESS ENT VALVE PRESS ENT HEATER FLOW
CFM [L/s] °F [°C] °F [°C] PSIG [kPa] PSIG [kPa] LBS/HR [kg/HR] LBS/HR [kg/HR]
1-SH12 FIFTH FLOOR PENTHOUSE AHU-12 STEAM 12,765 [ 6000 ] 1 54.5 [ 13 ] - 55 [ 13 ] - BUILDING STEAM 30 [ 210 ] 15 [ 100 ] 67 [ 30 ] 14 [ 6 ] ----
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Cincinnati V.A Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FULLY SPRINKLERED
C U s e rs
\j o h n f\
D o c u m e n ts \F
F E
C in c in n a ti
U p g ra d e A
T U s B
M
E P jo h n
.g ru b e rA
Q
P J .r v t
/1 /2
:5
:2
P M
M602
MECHANICAL SCHEDULES
08/31/2021 KF JG
CINCINNATI, OH
539-21-111CONSTRUCTION
DOCUMENTS
UPGRADE TERMINAL
UNITS
05/20/2021 Revisions: Date:
AMENDMENT 2 10/20/2021
08/31/2021
| Sheets |
| M602 - MECHANICAL SCHEDULES |