36C25020B0028-007.pdf
PDF Posted
- Solicitation number
- 36C25020B0028
About this file
This pre-solicitation notice is for the renovation of approximately 17,000 square feet of ICU/TCU space at the Dayton VA Medical Center located at 4100 West Third Street, Dayton, OH 45428. The contractor shall provide all labor, supervision, materials and equipment to professionally renovate and modernize the space, which is currently over 25 years old, as well as upgrade antiquated IT systems. Work must be completed within 365 calendar days of notice to proceed. The solicitation will be posted on March 20, 2020 on FBO.gov with proposals due approximately 30 days later. This is a 100% set-aside for service-disabled veteran-owned small businesses, who must be registered and verified in various websites. The NAICS code is 236220 with a small business size standard of $39.5 million. The contractor must perform a minimum of 15% of construction work. Bid, payment and performance bonds will be required along with a one-time site visit. Questions may be emailed by March 20, 2020.
36C25020B0028 S02. Attachment 6 - Project Drawings - Division 23 (2 of 2).pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25020B0028 0006.docx | DOCX document | |
| 36C25020B0028 0005.docx | DOCX document | |
| Site Visit sign-in.pdf | ||
| 20200702 Addendum 1.pdf | ||
| 20200701 TCUICU 2nd Floor Room Names.pdf | ||
| 20200701 TCUICU 2nd Floor RCP.pdf | ||
| PreBid RFIs Answers.pdf | ||
| 36C25020B0028 0004.docx | DOCX document | |
| Bid Opening Instructions.pdf | ||
| 36C25020B0028-0003000.docx | DOCX document | |
| 36C25020B0028-0002000.docx | DOCX document | |
| 36C25020B0028-0001000.docx | DOCX document | |
| 36C25020B0028-0001001.pdf | ||
| 36C25020B0028-004.pdf | ||
| 36C25020B0028-009.pdf | ||
| 36C25020B0028-005.pdf | ||
| 36C25020B0028-008.pdf | ||
| 36C25020B0028-002.pdf | ||
| 36C25020B0028-006.pdf | ||
| 36C25020B0028-003.pdf | ||
| 36C25020B0028-001.docx | DOCX document |
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ROOFING
LAG SCREW
FIBERGLASS INSULATION
ROOF
INSULATION
ROOF DECK
2x6 WOOD NAILER
18 GAUGE GALVANIZED STEEL COUNTER-FLASHING.
WELDED 14 GAUGE EQUIPMENT SUPPORT CURB, MEETING ASTM A-446, 525, 526 AND 527
REQUIREMENTS, WITH WELDED CORNERS WITH SEAMS JOINED BY CONTINUOUS WELDS. CURB
SHALL BE INTERNALLY REINFORCED WITH BULKHEADS AND SPREADERS, 24" ON CENTER TO
MEET LOAD RATING OF EQUIPMENT. CURB TO EXTEND 6" BEYOND EQUIPMENT. REFER TO
FLOOR PLANS FOR HEIGHT.
SECURE CURB TO ROOF WITH EXPANSION BOLTS (CONCRETE ROOF) OR RUST RESISTANT BOLTS
(METAL DECK AND BAR JOIST ROOF), 12" O.C.
4"x4"x1/4"
STEEL PLATE
5 FT
6 8 10
9 1110 12
-1312 14 -16 -
1614 17 2219 23
2725 28 3230
20 241814 16128 1064 532 2 1/21 1/21 1 1/4THRU 3/4
7 7
7 98
SECTION "A-A"
"B" "B"
RISER CLAMP
RISER CLAMP
PIPE SLEEVE WHERE
ANCHOR POINTS ONLY
CLAMP REQUIRED AT
RISER CLAMP. BOTTOM
BOLT (TYPICAL)
INSULATION
FIRE-STOPPING
FLOOR SLAB
MATERIAL
BOLT
ELEVATION
PLAN
RISER
SPECIFIED
BOLT
WHERE SPECIFIED
PIPE SLEEVEPIPE
420ONE 1 x 18 GA. STRAP36
TWO 1/2 DIA. RODS
TWO 3/8 DIA. RODS
ONE 1 x 16 GA. STRAP
50 700
ONE 1 x 22 GA. STRAP
QUANTITY/SIZEMAX. DUCT
HANGER STRAPS OR RODS
MAX. LOAD
LBS.
MAX.
IN.
SPACING
DIA. - IN. IN.
50" DIA. &
UNDER
LOAD RATED
FASTENERS
BAND OF SAME
SIZE AS HANGER
STRAP
HANGER RODS
OVER 50" DIA.
BAND
NOTE:
TABULATED DATA FROM SMACNA
ALLOWS FOR DUCT REINFORCING AND
INSULATION, BUT NO EXTERNAL LOAD.
ACCESS
PANEL
NOTE 5
PERIMETER ANGLE, NOTE 3
(NOT FASTENED TO PARTITION)
TYPICAL DUCT
INSULATION
FIRE BARRIER
PARTITION OR CHASE
NOTE 6
SLEEVE, NOTE 2
DAMPER COLLAR
EXTENSION INTEGRAL
PART OF SLEEVE
DAMPER,
NOTE 1
DUCT
CONNECTION
NOTE 4
SLEEVE, NOTE 2
A VERTICAL DAMPER IS SHOWN. HORIZONTAL DAMPER INSTALLATION, IS SIMILAR. FOLLOW
DAMPER MANUFACTURER'S INSTRUCTIONS, INCLUDING FASTENER OPTIONS AND GAGES
FOR SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST BE INSTALLED IN THE
PARTITION OR FLOOR AND NOT OUTSIDE THE PENETRATION.
GALVANIZED SLEEVE: GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO
DAMPER FRAME AND TO PERIMETER ANGLES.
PERIMETER ANGLES: GALVANIZED STEEL, NOT LESS THAN 1-1/2"x1-1/2" , 14 GAGE, TO PROVIDE 1" MINIMUM OVERLAP OF OPENING ON ALL 4 SIDES.
BREAKAWAY DUCT CONNECTION: CONTRACTOR'S OPTION OF TYPES SHOWN IN SMACNA.
ACCESS PANELS: SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE LINK OR
LINKS.
PROVIDE 1/4" TO 1/2" CLEARANCE ON HEIGHT AND WIDTH. IN ORDER TO MAINTAIN U.L.
RATING FOR FIRE DAMPER, DO NOT FILL THIS OPEN SPACE WITH FIRESTOP MATERIAL.
ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS
AND MECHANICAL ROOM FLOORS, SHALL BE PROVIDED WITH 3" HIGH CONCRETE CURB
AROUND OPENING FOR DUCT.
NOTES:
1.
2.
3.
4.
5.
6.
7.
DUCT RISER
HOLE IN STRUCTURAL FLOOR
2 INCHES WG TO 4 INCHES WG (HIGH AND MEDIUM PRESSURE) DUCT RISER SUPPORT
FLOOR
ARRANGE RISER SO
REINFORCER TRANSVERSE JOINT
IS AT RISER SUPPORT POINT
0.5 INCH WG TO 2 INCHES WG (LOW PRESSURE) DUCT RISER SUPPORT
DUCT RISER
HOLE IN STRUCTURAL FLOOR
1-1/2"x1-1/2"x1/8" ANGLE.
INSTALL ON BOTH LONG DIMENSION
SIDES OF DUCT. FOR DUCTS OVER
60" USE 2"x2"x1/8" ANGLE.
SHEET METAL SCREWS 4" ON
CENTER
DUCT RISER - SEE FLOOR
PLANS FOR SIZES
EXTEND ANGLE 3"
BEYOND DUCT
FLOOR
SEAL HOLE WITH FIREPROOFING
MATERIAL AFTER DUCT INSTALLATION
DUCT RISER - SEE FLOOR
PLANS FOR SIZES
2"x2"x1/4" ANGLE. INSTALL
ON BOTH LONG DIMENSION
SIDES OF DUCT
SEAL HOLE WITH FIREPROOFING
MATERIAL AFTER DUCT INSTALLATION
NOTE:
ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS
AND MECHANICAL ROOM FLOORS SHALL BE PROVIDED WITH A 3" HIGH CONCRETE CURB
AROUND OPENING FOR DUCT.
1/8" CLEARANCE
ALL AROUND
"A"
"A"
INSULATION
INSULATION
GASKET
DUCT
INSULATION
SECTION "B-B" FACTORY
FABRICATED
LATCH
FLEXIBLE
WASHER
HANDLE INSIDE
GASKET
CASING
ACCESS DOOR
ACCESS PANEL
NOTES:
1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS TIGHTLY.
2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS.
3. SEE SMACNA 2005, FIGURE 9-15
SECTIONSIDE ELEVATION
STIFFEN BLADE
AS REQUIRED
DUCT
1/2" ROUND ROD PIN
INSULATION
STAND-OFF
HANDLE WITH
LOCKING
QUADRANT
INSIDE END BEARING
OUTSIDE END BEARING
DAMPER BLADE
INSULATION SEE
SPECIFICATION
DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR
FOR MULTI-BLADE DAMPERS & ROUND DAMPERS.
NOTES:
1.
2.
3/8" MIN DIA
INSERTS NEW
CONSTRUCTION ONLY.
3/8" MIN DIA
HANGER RODS
TURNBUCKLE
FOR PIPES UNDER 2" IN SIZE USE
1-1/2"x1-1/2"x1/4" ANGLE. ALL PIPES
2" & LARGER USE 3"x3"x1/4" ANGLE
3/8" MIN DIA
HANGER RODS
NUTS & WASHERS
CLIP
ANGLE
CONCRETE
FLOOR SLAB
3/8" MIN DIA EXPANSION BOLTS FOR
EXISTING CONSTRUCTION AND INSERTS
FOR NEW CONSTRUCTION
STEEL EXPANSION SHIELD FOR EXISTING CONSTRUCTION AND
INSERTS FOR NEW CONSTRICTION. THIS TYPE SHALL BE
USED ONLY IN SLABS OR BEAMS OF 4" MIN DEPTH
NOTE: SEE SPECIFICATIONS FOR
DETAILED HANGER REQUIREMENTS
M A
X
FT.
FT.
IN.
TUBING
PIPE
NOM. SIZE
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
MAXIMUM PIPE/TUBING SUPPORT SPACING
HANGER ROD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
PROVIDE HIGH
COMPRESSIVE STRENGTH
INSULATION (9 PSF MIN.
DENSITY) UNDER
INSULATION SHIELD
INSULATION SHIELD
AT HANGER
SADDLE
WELD
1/2" DIA. HANGER
RODS WITH 36"
MAX. SPACING ON
EACH CHANNEL
1-5/8" 12 GAUGE CHANNEL
OR 2"x2"x1/4" ANGLE
BAND
PROVIDE INSULATION SHIELD
& INSERT FOR ALL PIPING
(8" MIN.)
ADJUSTABLE CLEVIS HANGER
TYPE 43 - SEE SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER
TYPE 1 - SEE SPECIFICATIONS
SIDE VIEW TRAPEZE HANGER FOR UP TO
1000 LB. UNIFORM LOAD
THIS DETAIL IS NOT INTENDED FOR ROOFTOP AHU SUPPORT. REFER TO STRUCTURAL DRAWINGS
GENERAL NOTE:
1.
FOR REQUIREMENTS OF ROOFTOP AHU SUPPORT.
SUPPORT/ANCHOR FOR PIPE RISERS
ROUND DUCT HANGERS
SECTION THRU FIRE DAMPER INSTALLATION
DUCT RISER SUPPORTS
ACCESS PANEL AND DOOR DETAIL
VOLUME DAMPER DETAIL
SECURING HANGER RODS IN CONCRETE
PIPE HANGERS
EQUIPMENT/DUCT SUPPORT ROOF CURB
NOTES:
ROOF PENETRATION CURB
1. DUCTWORK.
2. SUPPORT RING. FASTEN TO DUCTWORK AND
CHANNEL.
3. CONCRETE OR METAL ROOF DECK.
4. PRE-FRABRICATED INSULATED ROOF CURB.
5. LAG BOLTS (TYP.)
6. 16 GAGE GALVANIZED STEEL PEDESTAL LAGGED TO
ROOF CURB.
7. ROOFING MATERIAL.
8. FLASHING.
9. COUNTER FLASHING.
10. CONTRACTOR INSTALLING DUCT OR CONDUIT SHALL
SEAL PENETRATION WEATHERTIGHT.
11. REMOVABLE 16 GAGE GALVANIZED STEEL CAP
SECURE TO PEDESTAL WITH SHEET METAL SCREWS.
SLOPE CAP TO DRAIN OFF ANY WATER.
12. INSULATE INSIDE OF CAP AND PEDESTAL WITH 1"
CLOSED CELL INSULATION.
13. CHANNEL SUPPORT FORM ADJACENT JOIST OR
CONCRETE SUPPORT STRUCTURE.
12 10
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt er s in ch t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o t th re e in c h e s o n e fo o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
FULLY SPRINKLERED
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
JPA Project No.
Dwg. ofHEAPY PROJECT No.: 2017-05154 FIRM LICENSE No.: 01528
/9
/2
:3
:2
A
M
Renovate TCU-ICU Space Bldg. 330
03/09/2020
DETAILS
M502
PCWW JS
17005.00
552-18-102
Dayton, Ohio
Revisions Date
1 For Bid 03.09.2020
UNIT HEATER & TERMINAL UNIT WATER
COILS - PIPING CONNECTIONS
HORIZONTAL PIPE ANCHOR DETAIL
12"MIN
6"MIN
12"MIN
6"MIN
12"MIN
6"MIN
ABOVE 2" DIA. PIPE 2" DIA. & SMALLER
VERTICAL
2 1/2" DIA.
ABOVE 2" DIA. PIPE 2" DIA. & SMALLER
HORIZONTAL
2 1/2" DIA.
TYPICAL MANUAL AIR VENT
TYPICAL CHILLED AND HOT WATER
PIPING DRAIN VALVE CONNECTIONS
ELEVATION
THREADED PIPING
ELEVATION
WELDED PIPING
TYPICAL WATER PIPING
REDUCER, IF REQUIRED
3/4" BALL VALVE
ADAPTER TO 3/4" HOSE
THREAD-PROVIDE HOSE CAP NUT
NOTES:
1. DRAIN ALL LOW POINTS AS INDICATED ABOVE.
2. WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS
AND/OR PLANS, LOCATE DRAIN AT BOTTOM OF SCALE POCKET.
AIR VENT
1/2" BALL VALVE
1/4" COPPER TUBING
1/2" x 4" NIPPLE
CIRCULATING WATER PIPING
ELEVATION
NOTES:
1. VENT ALL HIGH POINTS AS INDICATED ABOVE.
2. IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE TO NEAREST DRAIN.
MV
OR
AV
COIL
TEST PLUG (TYP.)
REDUCER, IF REQUIRED
WATER RETURN
MANUAL AIR VENT
UNION CONNECTIONS
(TYP.)
WATER SUPPLY
SHUTOFF BALL VALVE (TYP.)
DRAIN WITH HOSE
CONNECTION
MODULATING
CONTROL VALVE
(SEE NOTE 2)
COMBINATION BALANCING/
SHUT-OFF VALVE
STRAINER WITH
BLOW DOWN
2. REFER TO UNIT HEATER AND AIR TERMINAL UNIT SCHEDULES ON SHEETS M0.6 AND
M0.7 FOR VALVE TYPE (2-WAY OR 3-WAY)
1. THIS DETAIL APPLIES TO VAV/CV REHEAT UNITS AND UNIT HEATERS.
REHEAT
NOTES:
1. INSTALLATION OF SENSORS AND TRANSMITTERS SHALL CONFORM TO
RECOMMENDATIONS OF MANUFACTURERS OF TRANSMITTERS.
1/2" STEEL PIPE OR STEEL
TUBING TO SENSORS
DIFFERENTIAL PRESSURE
TRANSMITTER (FLOW, LEVEL)
BLOWDOWN
PT
ELEVATION
NOTES:
M
IN
M
M
M
IN
DRIP LEG (TYP.)
3/4" DRAIN (ALTERNATE
LOCATIONS) (TYPICAL)
(TYPICAL)
CAP (TYPICAL)
PIPE TO STEAM
TRAP (TYPICAL)
NOTE:
DRIP LEG PIPE SIZE SAME
AS STEAM MAIN UNLESS
OTHERWISE NOTED.
STEAM LINE DRIP POCKET
STEAM TRAP ASSEMBLY
PIPE SIZES SAME AS CONNECTION
ON TRAP - 3/4" MIN.
FROM DRIP LEG
OR EQUIPMENT
CONNECTION
DRIP
RETURN
3/8" TEST CONNECTION
FLOAT AND THERMOSTATIC
TRAP (SEE PLANS)
STRAINER
GATE VALVE
CHECK VALVE DIELECTRIC FITTING
(WHERE METAL
MATERIALS ARE
DISSIMILAR)
TO RETURN MAIN - SEE
DRAWINGS FOR PIPE SIZES
GLOBE VALVE
NC
BYPASS - INSTALL IN HORIZONTAL
PLANE LEVEL WITH TRAP OR IN
VERTICAL PLANE AND BELOW TRAP.
D R
IP
L
E G
D R
IP
L
E G
S C
A L
E P
O C
K E
T
S C
A L
E P
O C
K E
T
12" MIN.
1 SLOPE MAINS AND BRANCHES DOWN 1" PER 40 FEET IN DIRECTION OF
2 LIMIT UNTRAPPED, COUNTERFLOW, RUNOUTS TO 10 FEET MAXIMUM.
3 END OF MAIN SHOWN, LOW POINT IN STEAM MAIN SIMILAR.
FLOW UNLESS SHOWN OTHERWISE.
SAME SIZE AS MAIN
NOTES :
STEAM MAIN
BACK 1/4" PER FOOT.
6" MIN.
TRAP SET - SEE DETAIL ON
THIS SHEET
FLOAT AND THERMOSTATIC
LP & GRAVITY
RETURN (NO LIFTING PERMITTED)
HP & MP RETURN
UNTRAPPED RUNOUT. SLOPE
SEE STEAM TRAP ASSEMBLY
DETAIL ON THIS SHEET
ECCENTRIC REDUCERS ARE
REQUIRED FOR ALL REDUCTIONS
IN SUPPLY STEAM PIPES
1. INSULATE ANCHOR AS INDICATED FOR COLD PIPING.
AND INSULATION THICKNESS
CUT TO SUIT PIPE DIA.
NOTES:
INSULATION
3/8" PLATE
PIPE & PIPE & INSULATION
1/2" U-BOLT
3/8" BASE PLATE
WELD
STRUCTURAL CHANNEL
ANCHOR BOLTS,
MIN. SIZE 5/8"
STRUCTURE
2 AT EACH PLATE.
OR ANGLES
(2"x2"x1/4")
STEAM LINE
(LIFTING PERMITTED)
2. COORDINATE ALL REQUIREMENTS WITH STRUCTURAL ENGINEER.
REDUCER IF COIL SIZE IS SMALLER
THAN RUN-OUT PIPE SIZE.
FULL SIZE RUN-OUT
PIPING
AHU CASING
SAME SIZE AS SEPARATOR INLET
SEPARATOR. FURNISHED BY HUMIDIFIER MANUFACTURER.
STEAM JACKETED HUMIDIFIER DISPERSION TUBES.
MODULATING HUMIDIFIER CONTROL VALVE.
STEAM JACKET TRAP. INVERTED BUCKET TYPE.
SHUT-OFF VALVE.
CHECK VALVE.
STEAM JACKET PIPING.
STEAM SUPPLY PIPE.
UNION.
SIZE AND SPACING PER MANUFACTURER.
0.375" TEST CONNECTION.
REFER TO MANUFACTURER'S
PIPING RECOMMENDATIONS
FOR FINAL LAYOUT
STRAINER.
57 6
LINE SIZE AUTOMATIC TWO-POSITION ISOLATION
VALVE BY ATC. REFER TO SHEET M701 FOR CONTROL
SEQUENCE.
TEMPERATURE SWITCH. FURNISHED BY HUMIDIFIER15
SEPARATOR TRAP. INVERTED BUCKET TYPE.
HEADER TRAP. INVERTED BUCKET TYPE.
MANUFACTURER.
FURNISHED BY HUMIDIFIER MANUFACTURER.
FURNISHED BY HUMIDIFIER MANUFACTURER. TYPE, QTY,
HEADER. FACTORY OR FIELD FABRICATED. COORDINATE
WITH FIELD CONDITIONS, QTY OF TUBES, ROUND VS
RECTANGULAR DUCTWORK, ETC.
17 17 PIPE TO DRAIN. PROVIDE WASTE WATER TEMPERING
DEVICE. PIPE COOLING WATER FROM COLD WATER STUB
INDICATED.
WATER COIL
AIR VENT
WHEN COIL
IS NOT
SELF-VENTING
DRAIN WHEN COIL IS
NOT SELF-DRAINING
TEST PLUG
(TYP.)
PIPE HANGER SHALL SUPPORT
PIPING INDEPENDENT OF COIL
REDUCER, IF REQUIRED
DRAIN
WATER COIL
AIR VENT
WHEN COIL
IS NOT
SELF-VENTING
TEST PLUG
(TYP.)
PIPE HANGER SHALL SUPPORT
PIPING INDEPENDENT OF COIL
WATER COIL
REDUCER, IF REQUIRED
DRAIN WHEN COIL IS
NOT SELF-DRAINING (TYP.)
DRAIN
NOTE:
1.
2.
3.
WHEN COIL IS INCLUDED IN CASING MOUNTED ON VIBRATION ISOLATORS THE FIRST
2 HANGERS FOR EACH PIPE SHALL BE SPRING & NEOPRENE TYPE. TYPE "H" FOR
4" DIA. PIPE & SMALLER. TYPE "H-P" FOR 5" DIA. PIPE & LARGER.
PIPING SHALL BE INSTALLED IN SUCH MANNER THAT IT WILL NOT BLOCK THE
SWING OR USE OF ACCESS DOORS OR PANELS; NEITHER SHALL IT BLOCK THE
SERVICING OF FILTERS, VALVES, OR EQUIPMENT.
THE FLOW ELEMENT MAY BE INSTALLED IN THE SUPPLY PIPING IF THE REQUIRED
MINIMUM UPSTREAM AND DOWNSTREAM DIMENSIONS CANNOT BE OBTAINED IN THE
RETURN PIPING.
MV
MV
MV
MV
MVMV
MV
BUTTERFLY VALVE (TYP.)
STRAINER WITH BLOW DOWN (TYP.)
CHS
CHR
MV
CHS
CHR
MANUAL BALANCING VALVE (TYP.)
AUTOMATIC 2-WAY
MODULATING CONTROL
VALVE
0.75" BYPASS WITH AUTOMATIC
FLOW CONTROL VALVE
0.75" BYPASS WITH AUTOMATIC
FLOW CONTROL VALVE
DOUBLE COIL
SINGLE COIL
(4-57 RANGE) SET AT 5 GPM
AUTOMATIC 2-WAY
MODULATING CONTROL
VALVE
(4-57 PSIG RANGE) SET AT 5 GPM
INSTALLATION OF THERMOMETER WELLS
DRAIN VALVE AND AIR VENT
CONNECTIONS (HYDRONIC SYSTEMS)
PRESSURE TRANSMITTER
INSTALLATION
STEAM LINE DRIP POCKET
STEAM TRAP ASSEMBLY
TYPICAL STEAM LINE & DRIP PIPING
AHU MOUNTED STEAM HUMIDIFIER
CHILLED WATER COILS -
PIPING CONNECTIONS
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o t o n e h a lf in c h o n e fo o t th re e q u a rt er s in ch o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o t th re e in c h e s o n e fo o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
FULLY SPRINKLERED
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
JPA Project No.
Dwg. ofHEAPY PROJECT No.: 2017-05154 FIRM LICENSE No.: 01528
/9
/2
:3
:2
A
M
Renovate TCU-ICU Space Bldg. 330
03/09/2020
DETAILS
M503
PCWW JS
17005.00
552-18-102
Dayton, Ohio
NOTES:
SUPPLY
LOCATION
NO.
UNIT
NO.
AREA SERVED FAN MIN
O.A.SUPPLY IN.
CFM
S.P. (1)
EXTERNAL
S.P. (2)
IN.
TOTAL
FAN
TYPE OF SYSTEM
NOTES:
RATING
MERV
NO.
FILTER
SYSTEMCFM
HOUSING
MAX. S.P. DROP
INITIAL FINAL
(1)
VELOCITYTYPE
FACE
MAX.
NOTE
SEE
EXTERNAL STATIC PRESSURE REQUIRED AT DUCT CONNECTIONS TO INLET AND OUTLET OF AHU. MEASUREMENTS SHALL BE TAKEN WITHIN 3 FT. OF INLET AND
OUTLET AT A POINT OF MAXIMUM ACCURACY.
TOTAL FAN S.P = EXTERNAL STATIC PRESSURE + SPECIFIED INTERNAL LOSSES + UNSPECIFIED INTERAL LOSSES. MANUFACTURER SHALL PROVIDE SUBMITTAL SHOWING ACTUAL LOSSES OF ALL EQUIPMENT PROVIDED. REFER TO FAN SCHEDULE FOR ADDITIONAL FAN SELECTION INFORMATION.
STATIC PRESSURE REQUIREMENTS BASED ON 500 FPM FACE VELOCITY. FINAL PRESSURE DROPS BASED ON VA'S
FILTER HOUSING TO BE PART OF AIR HANDLING UNIT ASSEMBLY.
P/N
POSITIVE (P)
PRESSURE
NEGATIVE (N)SYSTEM
SYSTEMS
UNIT
330-AFM1
NO.
ALL
LOCATION
DUCT/
SIZE
96" X 77"
WxH
& TYPE
FAN SIZE
DUCT INVOLVED
SUPPLY AIR DUCTS FROM OUTLET OF AH-UNIT
AIR TERMINAL UNITS TO SUPPLY AIR DEVICES
SUPPLY AIR DUCTS FROM OUTLET OF
RETURN AIR DUCTS FROM CEILING REGISTERS
ALL DUCTWORK EXCEPT AS LISTED BELOW.
TO INLET OF AH-UNIT
OUTSIDE AIR AND GENERAL EXHAUST DUCTS
TO INLET OF AIR TERMINAL UNITS.
P
N
N
OR
P
0.1"
DROP
S.P.
MIN.
CFM
MAX.
NOTES
RECTANGULAR
DUCT
SMACNA LEAKAGE CLASS
-2"
2"
-2"
A
A
A
CONST.
SMACNA
W.G.
4"
2"
CLASS
SEAL
SMACNA
A
CLASS
A 6 3
ROUND
DUCT
COIL
NO.
NOTES:
SYSTEM CFM
Wb
ENT. AIR °FMAX.
LOSS
FACE
VEL
MAX.
S.P.
FPM.
Db
LVG. AIR °F
Db FLUIDWb
LOSS
MAX.
FT.
TEMP.
CIRCULATING FLUID
INGPM
°F
OUT
TEMP.
°F
MINIMUM
MBH
TOTAL (1)
MBH
MINIMUM
SENS. (1)
1 COIL CAPACITY BASED ON STANDARD AIR AT 0 FT. ALTITUDE.
2 FIELD MEASURE EXISTING COILS/CASING TO ENSURE DIMENSIONS PRIOR TO ORDERING NEW COILS.
330-PF12 330-AHU12
N/A
EFFICIENCY
RECOMMENDED CHANGE OVER PRESSURE DROP.
6 3
6 3
6 3
6 3
AUTO
VALVE
CV
AUTO
VALVE
TYPE
19,330
SYSTEM
NOTES :
1 COORDINATE EXACT SIZE IN THE FIELD PRIOR TO ORDERING.
DAMPER
DESIGN ALTITUDE: 1004 FT.
Db ( F)
OUTDOOR DESIGN TEMPERATURES
BED ROOM
INDOOR AREA DESIGN CONDITIONS
CONTROL CENTER
BED ROOM (ISOLATION)
ALL OTHER AREAS
90.3 73.6 0.6
SUMMER
% HUMIDITY
DEG. F Db WINTER DEG. F Wb SUMMER DEG. F Db SUMMER
Db ( F)
75 60
% HUMIDITY
WINTER
MEDICATION ROOM, NOURISHMENT 30
60UNOCCUPIED MODE (NOTE 2) 80 - -
72NIGHT SETBACK MODE (NOTE 1) 76 50 30
NOTES:
REFERS TO NIGHT SETBACK MODE FOR ZONE TEMPERATURE CONTROL OF AIR TERMINAL
UNITS & DISCHARGE AIR RESET OF AIR HANDLING UNIT. REFER TO AIR TERMINAL UNIT
AND AHU CONTROL SEQUENCES ON SHEET M701.
REFERS TO OCCUPANCY STATUS FOR CONTROL OF AIR TERMINAL UNITS. REFER TO AIR
TERMINAL UNIT SCHEDULE ON SHEET M602 AND CONTROL SEQUENCES ON SHEET M701.
64OIT 81 60 30
330-AHU12 330-SF12MECH. ROOM 3.5" 6.5" VAV21,700 7,300TCU/ICU 3RD FLOOR
330-CC12a 330-AHU12 12,360 300 45 59
WATER
70.40.3 90.7 54.554.6 10 642.7 473.691.2 43.02-WAY
330-FF12
330-AF12
HOUSING
1,2
SIDE ACCESS
8 0.33" 0.66" 50035%
HOUSING
SIDE ACCESS
11 500 1,265%
HOUSING
1,2
SIDE ACCESS
14 0.37" 0.74" 50095%
SECOND FLOOR
0.27" 0.54"
CHILLED
NOTES
NOTES
0 7,30048" X 77" 0.1" 1N/A 330-AHU12330-AHU12 MIN OUTSIDE AIR
EGGCRATE CEILING REGISTERCR1
DAMPER
OPPOSED BLADE
SURFACE
TYPE MOUNTING
DESCRIPTION
EGGCRATE CEILING GRILLE
STANDARD SQ. PLAQUE CEILING
DIFFUSER ROUND NECK
SYMBOL
CD1
CG1
LAY-IN
FINISH
E.C.L.STEEL ALUM.
MATERIAL
ACCESSORIES
W.B.E.
NOTES
REGISTER 0 DEG REFLECTION
FIXED BLADE RETURN/EXHAUST
TR2
OPPOSED BLADE
DAMPER
EGGCRATE CEILING GRILLECG2
STANDARD SQ. PLAQUE CEILING
DIFFUSER ROUND NECK
CD2
TR1
OPPOSED BLADE
DAMPER
EGGCRATE CEILING REGISTERCR2
DAMPER
OPPOSED BLADE
NOTES:
PROVIDE 48" LONG DEVICE WITH 1 - 1" SLOT. PROVIDE WITH CENTER NOTCH TO ACCOMMODATE CEILING GRID.
PROVIDE 24" LONG DEVICE WITH 1 - 1" SLOT. PROVIDE WITH CENTER NOTCH TO ACCOMMODATE CEILING GRID.
PROVIDE 48" LONG DEVICE WITH 2 - 1" SLOT. PROVIDE WITH CENTER NOTCH TO ACCOMMODATE CEILING GRID.
PROVIDE 24" LONG DEVICE WITH 2 - 1" SLOT. PROVIDE WITH CENTER NOTCH TO ACCOMMODATE CEILING GRID.
LINEAR PLENUM SLOT
ADJUSTABLE BLADE DIFFUSER
CD3 1
DEFLECTION SUPPLY REGISTER
ADJUSTABLE BLADE DOUBLE
DISTANCE
ABSORP.
(MAX.)
330-SH12
HUMID.
NO.
330-AHU12
SYSTEM
24"
CFM
19,330
°F
Db
54.5 30
ON-OFF
VALVE
ENT. ENT.
PSIG
VALVE
CONTROL
STEAM
VALVE
ON-OFF &
CONTROL
LBS/HR
LBS/HR
TRAP
LEAVING AIR
7075 60 30
7075 60 20
7075 60
330-AHU12
330-AHU12
19,330
19,330
AHU IS EXISTING TO REMAIN. SCHEDULED DATA IS FOR BALANCING AND GENERAL INFORMATION PURPOSES.
330-AFM2 1330-AHU12330-AHU12 MAX OUTSIDE AIR 0 21,700
VOLT-
PHASE
MIN.
SEER
UNIT ELECTRIC
°FBTUH
NOTES
O.A.
TEMP.EFFECT
MIN. REFRIG.
UNIT NO. LOCATION
330-CU1 ROOF 24,000 95 21.4 208-1 20 125
MCA MOCP
1 PROVIDE LOW AMBIENT WIND BAFFLE TO PROVIDE OPERATION DOWN TO -20 DEG F.
1 UNIT TO BE CONNECTED TO OUTDOOR UNIT 330-CU1
NO.
UNIT
(1)
NOTES :
TYPE
CFM
FAN
APPROXIMATE SIZE
CAPACITY
(BTUH)
COOLING
E.S.P.
FAN MOTOR
VOLT-
PHASE
MCA WL H
(BTUH)
CAPACITY
HEATING
NOTES
330-FC1
WALL
MOUNTED 124,000570 15208-11 47 12
FREE
DISCN/A
MOCP
330-CC12b 330-AHU12 8,430 350 45 59
WATER
0.4 20 435.6 320.062.2 20.62-WAY70.490.7 54.554.6
CHILLED
LINEAR PLENUM SLOT
ADJUSTABLE BLADE DIFFUSER
CD4 2
LINEAR PLENUM SLOT
ADJUSTABLE BLADE DIFFUSER
CD5 3
LINEAR PLENUM SLOT
ADJUSTABLE BLADE DIFFUSER
CD6 4
1,2
1,2
MOTORS SHALL BE ENERGY EFFICIENT TYPE.
NOTES :
NO.
FAN
LOCATION CFM S.P.
FAN FAN
DESCRIPTION
TYPE
FAN
TYPE
MIN.
DIA.
WHEEL
DRIVERPM VOLT-NOM.
HP (2) PHASE
MOTOR
NOTE
SEE
MAX. BHP VFD
MOTORS SHALL BE ECM TYPE.2
ROOF330-EF1 1,660 3.8" 12.25" 2,860 BELT 21.7 460-3 1,2YESUSF BIW
BELT DRIVE
UTILITY SET FAN
ROOF330-EF2 2,350 3.8" 15" 2,300 BELT 32.5 460-3 1,2YESUSF BIWBELT DRIVE
UTILITY SET FAN
AIR
BALANCE
CFM
1,505
2,130
330-AHU12330-SF12 21,800 6.5" 27" 1,710 BELT 4034 460-3 3,4YESCF AFBELT DRIVE DWDI 19,790
330-AHU12330-RF12 17,120 2" 36" 840 BELT 1512.8 460-3 3,4YESICF AFBELT DRIVE
HORIZONTAL IN-LINE
13,145
REPLACE FAN MOTOR WITH PREMIUM EFFICIENCY, INVERTER DUTY RATED MOTOR3
CAPABLE OF VFD CONTROL/OPERATION. CONFIRM MOTOR FRAME SIZE PRIOR TO
ORDERING. FAN IS EXISTING TO REMAIN. FAN INFORMATION PROVIDES FAN
MOTOR SELECTION AND BALANCING.
EXISTING FAN SHALL BE CLEANED AND INSPECTED PRIOR TO PLACING BACK INTO SERVICE.4
FAN SCHEDULE
AIR FILTER SCHEDULE
DUCT PRESSURE CLASS & LEAKAGE TABLE
AIR FLOW MEASURING DEVICE SCHEDULE
CHILLED WATER COOLING COIL SCHEDULE
HVAC DESIGN DATA AIR HANDLING UNIT SCHEDULE AIR DISTRIBUTION DEVICES
STEAM HUMIDIFIER SCHEDULE
AIR COOLED COND. UNIT SCHEDULE
NOTES:
DX FAN COIL UNITS
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o t o n e h a lf in c h o n e fo o t th re e q u a rt er s in ch o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o t th re e in c h e s o n e fo o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
FULLY SPRINKLERED
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
JPA Project No.
Dwg. ofHEAPY PROJECT No.: 2017-05154 FIRM LICENSE No.: 01528
/9
/2
:3
:2
A
M
Renovate TCU-ICU Space Bldg. 330
03/09/2020
SCHEDULES & DIAGRAMS
M601
PCWW JS
17005.00
552-18-102
Dayton, Ohio
THE FOLLOW ING INFORMATION SHALL BE ITEMIZED AND
PROVIDED TO COR FOR ALL PIECES OF EQUIPMENT:
1. MODEL NUMBER (NOMENCLATURE)
2. TAG
3. MANUFACTURER
4. PART NUMBER
5. SERIAL NUMBER
THE FOLLOW ING INFORMATION SHALL BE ITEMIZED AND
PROVIDED TO COR FOR ALL PIECES OF EQUIPMENT:
1. MODEL NUMBER (NOMENCLATURE)
2. TAG
3. MANUFACTURER
4. PART NUMBER
5. SERIAL NUMBER
3 PROVIDE HOSPITAL GRADE SOUND ATTENUATOR WHERE REQUIRED TO CONFORM TO THE MAXIMUM NC35 REQUIREMENT.
5 HEATING COIL CAPACITY BASED ON WINTER MINIMUM CFM.
ABSORPTION COFFICIENT (REFERENCE 10 [-12] WATTS) WITH 3" S.P. DIFFERENTIAL ACROSS UNIT AT MAXIMUM CFM SETTING.
1 PROVIDE DUCT TRANSITION AT UNIT INLET WHERE UNIT INLET SIZE AND DUCT RUNOUT SIZE ARE DIFFERENT.
THE MINIMUM PRESSURE REQUIRED AT THE UNIT INLET TO OBTAIN THE RATED CFM.
6 CONTROL TYPES: V.V.R.: VARIABLE VOLUME REHEAT TERMINAL; C.V.R.: CONSTANT VOLUME REHEAT TERMINAL
2 THE UNIT MAXIMUM SP IS THE PRESSURE DIFFERENCE BETWEEN THE UNIT INLET AND DISCHARGE INCLUDING REHEAT COIL AND SOUND ATTENUATOR. IT IS ALSO
4 UNIT NOISE LEVEL SELECTION SHALL NOT EXCEED A ROOM NC OF 35 FROM BOTH AIRBORNE AND RADIATED NOISE, BASED ON A 10 DB ROOM
NOTES :
7 AIR TERMINAL UNIT WITH LISTED CFM SHALL BE CONTROLLED THRU ECC WITH PROGRAMMABLE OCCUPIED/UNOCCUPIED TIMES AND/OR BE CONNECTED TO OCCUPANCY SENSOR(S). PROVIDE OCCUPANCY SENSORS AND ASSOCIATED WIRING WHERE NOT PROVIDED BY DIV. 26.
REFER TO DIV. 26 SPECIFICATIONS FOR PRODUCT REQUIREMENTS. REFER TO "HVAC DESIGN DATA" SCHEDULE ON SHEET M601 FOR UNOCCUPIED TEMPERATURES.
3 PROVIDE HOSPITAL GRADE SOUND ATTENUATOR WHERE REQUIRED TO CONFORM TO THE MAXIMUM NC35 REQUIREMENT.
5 HEATING COIL CAPACITY BASED ON WINTER MINIMUM CFM.
ABSORPTION COFFICIENT (REFERENCE 10 [-12] WATTS) WITH 3" S.P. DIFFERENTIAL ACROSS UNIT AT MAXIMUM CFM SETTING.
1 PROVIDE DUCT TRANSITION AT UNIT INLET WHERE UNIT INLET SIZE AND DUCT RUNOUT SIZE ARE DIFFERENT.
THE MINIMUM PRESSURE REQUIRED AT THE UNIT INLET TO OBTAIN THE RATED CFM.
6 CONTROL TYPES: V.V.R.: VARIABLE VOLUME REHEAT TERMINAL; C.V.R.: CONSTANT VOLUME REHEAT TERMINAL
2 THE UNIT MAXIMUM SP IS THE PRESSURE DIFFERENCE BETWEEN THE UNIT INLET AND DISCHARGE INCLUDING REHEAT COIL AND SOUND ATTENUATOR. IT IS ALSO
4 UNIT NOISE LEVEL SELECTION SHALL NOT EXCEED A ROOM NC OF 35 FROM BOTH AIRBORNE AND RADIATED NOISE, BASED ON A 10 DB ROOM
NOTES :
7 AIR TERMINAL UNIT WITH LISTED CFM SHALL BE CONTROLLED THRU ECC WITH PROGRAMMABLE OCCUPIED/UNOCCUPIED
TIMES AND/OR BE CONNECTED TO OCCUPANCY SENSOR(S). PROVIDE OCCUPANCY SENSORS AND ASSOCIATED WIRING WHERE NOT PROVIDED BY DIV. 26.
REFER TO DIV. 26 SPECIFICATIONS FOR PRODUCT REQUIREMENTS. REFER TO "HVAC DESIGN DATA" SCHEDULE ON SHEET M601 FOR UNOCCUPIED TEMPERATURES.
8 REFER TO DEDUCT ALTERNATE SCHEDULE FOR ATU'S IMPACTED BY DEDUCT ALTERNATE.
8 DEDUCT ALTERNATES 1 & 2 ONLY IMPACT ATU'S LISTED IN THIS SCHEDULE. REFER TO OTHER SCHEDULE FOR REMAINING ATU'S.
AIR TERMINAL UNIT SCHEDULEAIR TERMINAL UNIT SCHEDULE - DEDUCT ALTERNATES 1 & 2
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o t o n e h a lf in c h o n e fo o t th re e q u a rt er s in ch o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o t th re e in c h e s o n e fo o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
FULLY SPRINKLERED
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
JPA Project No.
Dwg. ofHEAPY PROJECT No.: 2017-05154 FIRM LICENSE No.: 01528
/9
/2
:3
:3
A
M
Renovate TCU-ICU Space Bldg. 330
03/09/2020
SCHEDULES & DIAGRAMS
M602
PCWW JS
17005.00
552-18-102
Dayton, Ohio
8 8
THE FOLLOW ING INFORMATION SHALL BE ITEMIZED AND
PROVIDED TO COR FOR ALL PIECES OF EQUIPMENT:
1. MODEL NUMBER (NOMENCLATURE)
2. TAG
3. MANUFACTURER
4. PART NUMBER
5. SERIAL NUMBER
PREHEAT COIL 330-PH12 LEAVING AIR TEMPERATURE SENSOR
C
E
PRE FILTER 330-PF12 PRESSURE DROP
COOLING COIL 330-CC12 LEAVING AIR TEM PERATURE SENSOR
MIXED AIR TEMPERATURE SENSOR
SUPPLY AIR DUCT SM OKE DETECTOR (FIRE SYSTEM SHUTDOW N)
7 T-3
T-5
DP-1
T-2
DSD-2
X
X
X
X
XX
X
M ODULATING OUTSIDE AIR DAMPERD-1
FREEZESTATT-1 X
D XM ODULATING RETURN AIR DAMPERD-2
RELIEF AIR FLOW M EASURING STATIONVPS14 X
RETURN AIR DUCT SM OKE DETECTOR (FIRE SYSTEM SHUTDOW N)DSD-115 X
RETURN AIR TEMPERATURE SENSORT-616 X
RETURN AIR HUMIDITY SENSORRAH-117 X
XM ODULATING RELIEF AIR DAMPERD-4
AFTER FILTER 330-AF12 PRESSURE DROPPP-321 X
M ODULATING SUPPLY AIR DAMPERMJ X
-P
F
2 T-3
P R
E H
E A
T
330-PH12
T-4
DP-1
PRE
FILTER 1
N.O.
M
C
D-1
C O
IL
T-1
DM
N.O.
D-9
T-6 RAH-1
DSD-1
T-2
G
(N.O.)
V-2
HW S
HW R
RETURN FAN
330-RF12
DP-3
-A
F
AFTER
FILTER
OUTSIDE AIR TEMPERATURE (GLOBAL)OAT
X
DSD-2
N.C.
M
E
D-4
T-5
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
CONTROL PANEL(S) 330-AHU12 LIST(S)
SUPPLY FAN START-STOP
M ODULATING HEATING COIL HOT W ATER VALVE
SUPPLY FAN VARIABLE SPEED MOTOR CONTROLLER
M ODULATING COOLING COIL CHILLED W ATER VALVE
VSM C1A
VSM C1
V-1
V-2
B
G
F
RETURN AIR FLOW M EASURING STATION
M AXIM UM OUTSIDE AIR FLOW M EASURING STATIO N (330-AFM 1)
SUPPLY FAN 330-SF3302 STATUS CURRENT SW ITCH
VPS-2
C1
DEVICE
VPS
TAGID
POINT
DESCRIPTION
DEVICE
X
X
X
X
X
POINT TYPE
DI DO AI AO
X
X
V-3H XHUMIDIFIER ON-OFF SHUT OFF
I XM ODULATING HUM IDIFIER CONTROL VALVEV-4
SUPPLY AIR HUM IDITY HIGH LIM ITH-219 X
RETURN FAN 330-RF12 STATIC CURRENT SW ITCHC322 X
SUPPLY AIR STATIC PRESSURE SENSORSPS-423 X
(APPLIES TO ALL CONTROL SHEETS)
EXPLICITLY SHOW N ON THE ELECTRICAL DRAW INGS, SHALL BE PROVIDED UNDER
CONDUIT, TRANSFORM ERS, RELAYS AND FUSES.
ACCESSORY HARDW ARE, SHALL BE PROVIDED FOR A COMPLETE AND FUNCTIONAL
ALL INPUT AND OUTPUT POINTS, AND THEIR REQUIRED INTERFACE AND
THE M INUM UM POINTS REQUIRED FOR CONTROL AND MONITORING.
POINTS LIST IS SHOW N AS AN AID TO THE CONTRACTOR INDICATING
THE ATC W ORK. THIS W ORK SHALL INCLUDE BUT NOT BE LIM ITED TO W IRING,
BULB W ELLS FOR TEMPERATURE SENSING AS INDICATED SHALL BE FURNISHED
UNDER THE ATC W ORK AND INSTALLED AS PART OF THE HVAC PIPING W ORK.
PIPING W ORK SHALL INCLUDE PROPERLY SIZED W ELDOLET OR THREADOLET
FITTINGS PLACED AS DIRECTED BY THE CONTROL SYSTEM SUPPLIER.
ACCOM PLISH THE SEQUENCES OF CONTROL SPECIFIED, THESE POINTS, ALONG W ITH
ADDITIONAL DIRECT DIGITAL CONTROL PANEL(S) (IF REQUIRED), SHALL ALSO BE
CONTROL SYSTEM. IF OR W HEN ADDITIONAL POINTS ARE REQUIRED TO
PROVIDED.
A COMPLETE SYSTEM OF AUTOM ATIC TEMPERATURE CONTROLS SHALL BE INSTALLED
UNDER THIS CONTRACT AS REQUIRED TO ACCOM PLISH THE SEQUENCE OF CONTROL
FOR VARIOUS ITEMS OF EQUIPMENT AND SYSTEMS AS DESCRIBED HEREINAFTER.
THE SYSTEM SHALL BE A DIRECT DIGITAL CONTROL SYSTEM UTILIZING ELECTRIC
ELECTRICAL W ORK INCLUDES A POW ER SOURCE TO THE MOTOR STARTERS. ALL
ACTUATION; ALL NEW GRAPHICS PROVIDED UNDER THIS CONTRACT SHALL M ATCH
HVAC POW ER SOURCES REQUIRED BEYOND THESE STARTERS OR BEYOND SOURCES
5 DIAGRAM S, SEQUENCES, AND POINTS LIST SHOW N ON THIS SHEET ARE INTENDED TO
REPRESENT A SINGLE TYPICAL AIR HANDLING SYSTEM . NOT ALL SYSTEM S HAVE THE
SAM E QUANTITY OF POINTS. REFER TO FLOOR PLANS FOR MORE INFORMATION.
M IN OUTSIDE AIR
C O
IL
C
O O
L
IN
G
330-CC12A
SUPPLY FAN
330-SF12
CHS
CHR
F
V-1 (N.C.)
330-AFM1
VPS-1
C1 VSM C1
A B
VSM C2 C3
22LK
SUPPLY AIR STATIC PRESSURE SENSORSPS-524 X
SUPPLY AIR STATIC PRESSURE SENSORSPS-625 X
SUPPLY AIR STATIC PRESSURE SENSORSPS-726 X
VPS27 X
VPS28 X
VPS29 X
RETURN FAN START-STO PVSM C2K
RETURN FAN VARIABLE SPEED MOTOR CONTROLLERVSM C2L
X
X
VPS
SPS-7 SUPPLY AIR TO
TERMINAL UNITS
SPS-6 SUPPLY AIR TO
TERMINAL UNITS
SPS-5 SUPPLY AIR TO
TERMINAL UNITS
SPS-4 SUPPLY AIR TO
TERMINAL UNITS
RELIEF AIR
SAFETIES - ALL CONTROLS SHALL INCORPORATE THE FOLLOW ING HARDW IRED
SAFETIES. ALL SAFETIES SHALL ASSUM E TO BE EXISTING, IF SAFETY IS PROVEN
TO BE IN DISREPAIR DURING CHECK-OUT, CONTACT THE COR FOR FURTHER
DIRECTION. AT A M INIM UM, THE FOLLOW ING SAFETIES SHALL BE PROVEN TO BE
OPERATIONAL UPON FINAL CHECKOUT.
LOW TEM PERATURE LIMIT "FREEZESTAT" SHALL STOP THE AIR HANDLING UNIT
FAN IF A TEM PERATURE BELOW 38 DEG. F IS DETECTED.
SMOKE DETECTORS SHALL STOP THE AIR HANDLING UNIT FAN W HEN SM OKE IS
DETECTED AND OPERATE THE ASSOCIATED DAM PERS ACCORDINGLY.
SUPPLY DUCT HIGH STATIC PRESSURE SW ITCH SHALL DISABLE THE UNITS FANS
IF DUCT STATIC PRESSURE RISES ABOVE THE M AXIM UM W ORKING PRESSURE
OF THE DUCTW ORK. THIS SW ITCH W ILL REQUIRE A M ANUAL RESET.
M ODE CONTROL - THE AIR HANDLING UNIT SHALL BE CAPABLE OF OPERATING IN
THE FOLLOW ING MODES: OCCUPIED AND UNOCCUPIED MODES. THE UNIT SHALL
BE AUTOM ATICALLY INITIATED THROUGH TIM E-OF-DAY SCHEDULES,
APPLICATION PROGRAM S, OR THROUGH OPERATOR COM MANDS.
OCCUPIED M ODE - THE SUPPLY FAN SHALL BE INDEXED TO START. THE
TEMPERATURE CONTROLS SHALL FUNCTION AS SPECIFIED DURING THE
OCCUPIED OPERATION.
UNOCCUPIED - THE AIR HANDLING UNIT CONTROLS SHALL FUNCTION AS
SPECIFIED, EXCEPT THE OUTSIDE AIR DAM PERS AND EXHAUST AIR DAMPERS
CONTROLS SHALL CYCLE TO M AINTAIN A REDUCED SPACE TEM PERATURE
SETPOINT (LOW EST SPACE TEM P) OF 55 DEG. F. W HEN THE UNIT IS SHUT DOW N,
ALL CONTROL DEVICES SHALL GO TO THEIR NORM AL POSITIONS (I.E., OUTSIDE
AND RELIEF AIR DAMPERS CLOSED, HEATING VALVE OPEN, HUMIDIFIER VALVE
CLOSED).
FAN CONTROL - W HENEVER THE UNIT IS INDEXED TO START, THE FOLLOW ING
SEQUENCE SHALL BE EXECUTED: ELECTRIC TO PNEUM ATIC SOLENOID VALVE
SHALL BE ENERGIZED TO OPEN OUTSIDE, EXHAUST, AND BOTH ISOLATION
SMOKE DAM PERS. W HEN DAM PERS ARE FULLY OPEN AS INDICATED BY THE
PNEUM ATIC END SW ITCH, THE SUPPLY AIR EXHAUST FANS SHALL BE STARTED.
ONCE THE FAN STATUS HAS BEEN PROVEN, THE PREHEAT, HOT DECK, COLD
DECK AND HUM IDIFIER CONTROL SHALL BE ENABLED. W HENEVER THE UNIT IS
DE-ENERGIZED, THE FOLLOW ING SEQUENCE SHALL BE EXECUTED: THE SUPPLY
AND EXHAUST FAN SHALL STOP. THE OUTSIDE, RELIEF AIR AND SMOKE
ISOLATION DAM PERS SHALL FULLY CLOSE. THE COOLING COIL SHALL FULLY
CLOSE TO THE COIL. THE PREHEAT COIL VALVE SHALL REMAIN UNDER
CONTROL. IF THE LOW TEM PERTURE LIM IT SAFETY "FREEZESTAT" HAS TRIPPED,
THE HEATING COIL VALVE SHALL FULLY OPEN TO THE COIL.
M ORNING W ARM-UP - THE OUTSIDE AIR DAM PERS SHALL REMAIN COM PLETELY
CLOSED, AND THE RETURN DAM PERS SHALL REM AIN FULLY OPEN. THIS M ODE
SHALL CONTINUE UNTIL THE RETURN TEM PERATURE RISES ABOVE 68 DEG. F.,
AT W HICH TIM E THE DAM PERS SHALL BE POSITIONED TO M INIM UM.
M INIMUM FRESH AIR - UPON INITIALLY SW ITCHING INTO THE OCCUPIED MODE,
THE MINIMUM OUTSIDE AIR DAM PERS SHALL OPEN FULLY, M AXIM UM OUTSIDE
AIR DAM PER AND RELIEF AIR DAM PER SHALL REM AIN CLOSED AND RETURN AIR
DAMPER OPEN FULLY.
PREHEAT COIL VALVE - ON A FALL IN THE DISCHARGE AIR TEMPERATURE
BELOW SETPOINT, THE PREHEAT CONTROL VALVE SHALL MODULATE OPEN TO
M AINTAIN SETPOINT. COOLING COIL VALVE SHALL BE FULLY CLOSED BEFORE
THE PREHEAT VALVE OPENS. W HEN THE UNIT IS OFF, THE PREHEAT COIL
VALVE OPENS FULLY TO THE COIL AND RETURNS TO CONTROL AFTER THE FAN
IS STARTED.
EXISTING.
C O
IL
C
O O
L
IN
G
330-CC12B
CHS
CHR
M
V-5 (N.C.)
1. DDC ZONE CONTROL IS SPECIFIED. PROVIDE ZONE TEMPERATURE SENSOR AND M ODULATING OUTPUT FOR EACH
ZONE, AS SHOW N IN VVR, CVE, CVR, AND CONTROL TERMINAL DIAGRAM ON SHEET M 602.
2. ETR = EXISTING TO REM AIN. PROVIDED FOR INFORMATION ONLY.
GENERAL NOTES
AIR HANDLING UNIT 330-AHU12
EXISTING SEQUENCE OF OPERATION FOR 330-AHU12
M
N
M INIMUM OUTSIDE AIR FLOW M EASURING STATION (330-AFM1)VPS-1 X
COOLING COIL 330-CC3302 LEAVING AIR TEMPERATURE SENSORT-4 XETR
ETR
SUPPLY AIR DUCT SM OKE DETECTOR (FIRE SYSTEM SHUTDOW N)DSD-5 XETR
SUPPLY AIR DUCT SM OKE DETECTOR (FIRE SYSTEM SHUTDOW N)DSD-3 XETR
SUPPLY AIR DUCT SM OKE DETECTOR (FIRE SYSTEM SHUTDOW N)DSD-4 XETR
VPS X
ETR
ETR
ETR
ETR
SUPPLY AIR FLOW M EASURING STATION
SUPPLY AIR FLOW M EASURING STATION
SUPPLY AIR FLOW M EASURING STATION
SUPPLY AIR FLOW M EASURING STATION
HUMIDIFIER 330-SH12 STEAM JACKET CONDENSATE TEMPERATURE SENSORT-7 X
M ODULATING SUPPLY AIR DAMPERM XETR
M ODULATING COOLING COIL CHILLED W ATER VALVEV-5 X
ENTHALPY ECONOM IZER CONTROL - THE OUTSIDE AIR TEMPERATURE AND
HUMIDITY, AND RETURN AIR TEMPERATURE AND HUMIDITY SHALL BE
M EASURED, AND THE ENTHALPY OF EACH DETERM INED. IF THE ENTHALPY OF
THE OUTSIDE AIR IS LESS THAN THE RETURN AIR, THE ECONOMIZER SHALL BE
ENABLED. W HEN THE ENTHALPY OF THE OUTSIDE AIR IS HIGHER THAN THE
RETURN AIR ENTHALPY, AND MECHANICAL COOLING IS AVAILABLE, THE
ECONOM IZER IS DISABLED.
ECONOM IZER CYCLE - W HEN THE UNIT OPERATES IN THE OCCUPIED MODE,
M INIMUM OUTSIDE AIR IS PROVIDED. FOR ECONOMIZER CYCLE, THE AM OUNT OF
OUTSIDE AIR AND RELIEF AIR ARE INCREASED AS REQUIRED TO M AINTAIN THE
UNIT DISCHARGE AIR TEM PERATURE SETPOINT. A M IXED AIR SENSOR AND
M IXED AIR LOW LIMIT CONTROL LOOP SHALL PREVENT THE MIXED AIR
TEMPERATURE FROM FALLING BELOW 50 DEG. F. AS THE MIXED AIR
TEMPERATURE APPROACHES THE LOW LIMIT, THE OUTSIDE AIR DAM PER SHALL
BE M ODULATED TOW ARD THE FULLY CLOSED POSITION AND THE RETURN AIR
DAMPER TOW ARD THE FULLY OPEN POSITION.
HOT DECK COIL VALVE - AS THE DISCHARGE AIR TEMPERATURE DROPS BELOW
SETPOINT, THE HOT DECK HEATING COIL VALVE SHALL MODULATE OPEN TO
SATISFY THE SETPOINT CALCULATED BY THE RESET PROGRAM.
ZONE TEMPERATURE HOT DECK AIR RESET - THE AIR HANDLING UNIT
CONTROLS SHALL PROVIDE A HOT DECK DISCHARGE AIR TEM PERATURE
CONTROL BASED ON ZONE DEM AND DEVIATION FROM SETPOINT. A M INIMUM OF
4 ZONES SHALL BE SAM PLED AND THE ZONE FURTHEST FROM SETPOINT
GOVERNS.
COLDEST ZONE DISCHARGE AIR TEM P
79 80 75 100
COLD DECK COIL VALVE - AS THE DISCHARGE AIR TEM PERATURE RISES ABOVE
SETPOINT, THE COLD DECK COOLING COIL VALVE SHALL M ODULATE OPEN TO
SATISFY THE SETPOINT CALCULATED BY THE RESET PROGRAM. THE PREHEAT
COIL VALVE SHALL CLOSE FULLY BEFORE COOLING VALVE OPENS.
ZONE TEMPERATURE COLD DECK AIR RESET - THE AIR HANDLING UNIT
CONTROLS SHALL PROVIDE A COLD DECK DISCHARGE AIR TEM PERATURE
CONTROL BASED ON ZONE DEM AND DEVIATION FROM SETPOINT. A M INIMUM OF
4 ZONES SHALL BE SAM PLED AND THE ZONE FURTHEST FROM SETPOINT
GOVERNS.
W ARMEST ZONE DISCHARGE AIR TEM P
71 55 75 50
FAN VOLUM E CONTROL - THE INLET VANE DAM PERS ON THE SUPPLY AND
EXHAUST FAN SHALL BE M ODULATED TO M AINTAIN THE REQUIRED AIR VOLUM E
AT THE SUPPLY AIR FLOW MEASURING STATIONS.
HUMIDIFIER CONTROL - THE HUMIDIFIER SHALL BE SUBJECTED TO A W ARM -UP
SW ITCH TO KEEP THE VALVE CLOSED UNTIL THE CONDENSATE APPROACHES
STEAM TEM PERATURE. A TW O-POSITION POSITIVE SHUT-OFF VALVE SHALL BE
USED TO CUT OFF THE STEAM SUPPLY TO THE HUM IDIFIER W HEN
HUMIDIFICATION IS NOT REQUIRED. A RETURN AIR HUMIDITY SENSOR SHALL
M ODULATE THE HUM IDIFIER VALVE TO MAINTAIN 30 PERCENT RELATIVE
HUMIDITY. A HIGH LIM IT HUM IDITY SENSOR SET AT 80 PERCENT RELATIVE
HUMIDITY SHALL OVERRIDE THE CONTROL UPON HIGH HUMIDITY READING.
HUMIDIFIER SHALL BE KEPT OFF W HENEVER THE SUPPLY FAN IS NOT RUNNING,
DURING NIGHT CYCLE, AND W HENEVER THE OUTSIDE TEMPERATURE IS ABOVE
55 DEG. F.
DSD-3
VPS
DSD-4
VPS
DSD-5
VPS
M
J
M
N
V-4 (N.C.)
H
V-3 (N.C.)
I
STEAM
H-2
LPS
HUMIDIFIER
10 FT. M INIMUM
330-SH12
T-7
MPR
VPS
VPS
N.C.
M
C
D-2
MAX OUTSIDE AIR
330-AFM213
O XM ODULATING O UTSIDE AIR DAMPERD-2
RETURN AIR
VPS-2
1. M ODIFY EXISTING CONTROL SEQUENCES AS REQUIRED TO
INCORPORATE ALL NEW COM PONENTS.
2. SUPPLY FAN VFD SHALL M ODULATE TO MAINTAIN 1.0" DUCT STATIC
PRESSURE (FIELD ADJUSTABLE), SENSED BY SPS-4 THRU SPS-7.
3. RETURN FAN VFD SHALL MODULATE TO MAINTAIN M INIMUM OUTSIDE AIR
PLUS A PRESSURIZATION CONSTANT (200 CFM ADJUSTABLE) BY USING
THE SUPPLY AND OUTSIDE AIR FLOW MEASURING STATIONS.
4. PREHEAT COIL VALVE SHALL M ODULATE TO MAINTAIN DISCHARGE AIR
TEMPERATURE PER THE EXISTING SEQUENCE.
5. HOT DECK IS BEING REM OVED. BOTH DECKS ARE NOW COLD DECKS
AND CHILLED W ATER CONTROL VALVES SHALL MODULATE TO M AINTAIN
DISCHARGE AIR TEM PERATURE.
6. NEW HUM IDIFIER SHALL BE CONTROLLED PER EXISTING SEQUENCE.
NEW CONTROLS FOR 330-AHU12
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o t o n e h a lf in c h o n e fo o t th re e q u a rt er s in ch o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o t th re e in c h e s o n e fo o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
FULLY SPRINKLERED
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
JPA Project No.
Dwg. ofHEAPY PROJECT No.: 2017-05154 FIRM LICENSE No.: 01528
/9
/2
:3
:4
A
M
Renovate TCU-ICU Space Bldg. 330
03/09/2020
CONTROLS & AUTOMATION
M701
PCWW JS
17005.00
552-18-102
Dayton, Ohio
OS1
AIRFLOW AND PRESSURE DIFFERENTIAL MONITORING
OF NEGATIVE PRESSURE INFECTION CONTROL ROOMS
NEW ROOF ISOLATION ROOM EXHAUST FANS
AIR FLOW
SENSOR
ROOM SPACE
TEMPERATURE
SENSOR WALL
TO DDC LAN
TRUNK
CONTROL TERMINAL
CONTROL DAMPER
VVR OR CVR
HI
D1
LO
HEATING COIL, WHERE APPLICABLE
SUPPLY AIR
CONTROL VALVE (V-1) 24
VAC (SEE NOTE *)
DISCHARGE AIR
TEMPERATURE
SENSOR
24 VOLT POWER
SUPPLY FROM LOCAL
LO HI
(REFER TO AIR TERMINAL UNIT SCHEDULE
OCCUPANCY SENSOR, WHERE APPLICABLE
ON SHEET M602)
(REFER TO AIR TERMINAL UNIT
SCHEDULE ON SHEET M602)
* REFER TO AIR TERMINAL UNIT
SCHEDULE ON SHEET M602 FOR
VALVE TYPE (2-WAY OR 3-WAY)
MTD. 48" AFF
ATU CONTROLLER
DDC PANEL
EXHAUST FAN
DISCHARGE
EXHAUST AIR
STARTER *
CURRENT SENSING RELAY *
WALL
CORRIDORISOLATION
ROOM
1 EXHAUST FAN 330-EF1 AND 330-EF2 CONTROLS
1.1
1.2
1.3
2 PRESSURE MONITORING
2.1
ROOF
WALL
CORRIDORANTE
ROOM
WALL
CORRIDORISOLATION
ROOM
2X PER FAN
ISOLATION ROOM AND ANTE ROOM SHALL EACH BE MAINTAINED AT
MINIMUM 0.01" W.C. NEGATIVE PRESSURE TO THE CORRIDOR.
FULLY INTEGRATE PRESSURE MONITOR INTO CAMPUS DDC SYSTEM.
PROVIDE A PRESSURE MONITOR WITH DISPLAY NEAR THE ISOLATION
ROOM IDENTIFICATION SIGN IN CORRIDOR TO MONITOR BOTH
PRESSURE SENSORS.
PROVIDE DIFFERENTIAL PRESSURE SENSOR BETWEEN ISOLATION
ROOM AND CORRIDOR, AND BETWEEN ANTE ROOM AND CORRIDOR
TO CONTINUOUSLY MONITOR PRESSURIZATION.
IN THE EVENT OF SMOKE DETECTION, FANS SHALL CONTINUE
RUNNING TO MAINTAIN NEGATIVE PRESSURE IN THE SPACE BEING
SERVED.
ISOLATION ROOM EXHAUST FANS SHALL RUN CONTINUOUSLY AT FULL
SPEED AND BE ON SAME SCHEDULE AS 1-AHU42.
EXHAUST FAN SHALL BE STARTED AND STOPPED BY THE DCP OR
REMOTELY AT THE ECC. H-O-A SWITCH SHALL BE KEPT IN THE "AUTO"
POSITION. "HAND" AND "OFF" SHALL BE USED ONLY FOR
MAINTENANCE.
2.2
2.3
2.4
WHEN ROOM TEMPERATURE AT T-1 IS BELOW SETPOINT, THE CONTROL DAMPER ACTUATOR D-1 SHALL MODULATE THE DAMPER TO REDUCE AIRFLOW TO THE SUMMER MINIMUM SETTING. ON A FURTHER DROP IN ROOM TEMPERATURE AT T-1, THE CONTROL DAMPER SHALL BE MODULATED UPWARD TO THE WINTER MINIMUM
AIRFLOW AND THE HOT WATER VALVE V-1 SHALL MODULATE OPEN TO COIL TO MAINTAIN TEMPERATURE
SETPOINT.
AS ROOM TEMPERATURE RISES ABOVE SETPOINT, HOT WATER VALVE V-1 SHALL CLOSE. IF THE ROOM
TEMPERATURE CONTINUES TO RISE ABOVE SETPOINT, DAMPER D-1 SHALL MODULATE FROM SUMMER
(COOLING) MINIMUM AIRFLOW TO MAXIMUM AIRFLOW TO MAINTAIN ROOM TEMPERATURE.
EACH TERMINAL UNIT SHALL INCLUDE AN AIRFLOW SENSOR FOR CALCULATING CFM, AND A DISCHARGE AIR
TEMPERATURE SENSOR.
EXTEND 24 VOLT POWER TO THE TERMINAL BOX CONTROLLER FROM THE ASSOCIATED AIR HANDLING UNIT DDC
CONTROL PANEL.
ROOM SPACE TEMPERATURE SET POINT SHALL BE ADJUSTABLE FROM THE FRONT END COMPUTER INTERFACE.
COORDINATE AND ADJUST OCCUPANCY SCHEDULES AND TEMPERATURE RANGE WITH COR.
WHEN ROOM TEMPERATURE AT T-1 IS BELOW SETPOINT, HOT WATER VALVE V-1 SHALL MODULATE OPEN TO COIL TO MAINTAIN TEMPERATURE SETPOINT. BOX DAMPER D-1 SHALL REMAIN AT CONSTANT MAXIMUM CFM.
EACH TERMINAL UNIT SHALL INCLUDE AN AIRFLOW SENSOR FOR CALCULATING CFM, AND A DISCHARGE AIR
TEMPERATURE SENSOR.
EXTEND 24 VOLT POWER TO THE TERMINAL BOX CONTROLLER FROM THE ASSOCIATED AIR HANDLING UNIT DDC
CONTROL PANEL.
ROOM SPACE TEMPERATURE SET POINT SHALL BE ADJUSTABLE FROM THE FRONT END COMPUTER INTERFACE.
COORDINATE AND ADJUST OCCUPANCY SCHEDULES AND TEMPERATURE RANGE WITH COR.
DURING THE OCCUPIED MODE OF OPERATION, WHEN ROOM TEMPERATURE AT T1 IS BELOW SETPOINT, THE CONTROL DAMPER ACTUATOR, D1 SHALL MODULATE THE DAMPER TO REDUCE AIRFLOW TO THE SUMMER MINIMUM SETTING. ON A FURTHER DROP IN ROOM TEMPERATURE AT T1, THE CONTROL DAMPER SHALL BE MODULATED UPWARD TO THE WINTER MINIMUM AIRFLOW AND THE HOT WATER VALVE V1 SHALL MODULATE
OPEN TO COIL TO MAINTAIN TEMPERATURE SETPOINT.
DURING THE OCCUPIED MODE OF OPERATION, AS ROOM TEMPERATURE RISES ABOVE SETPOINT, HOT WATER VALVE V1 SHALL CLOSE. IF THE ROOM TEMPERATURE CONTINUES TO RISE ABOVE SETPOINT, DAMPER D1 SHALL MODULATE FROM SUMMER (COOLING) MINIMUM AIRFLOW TO MAXIMUM AIRFLOW TO MAINTAIN ROOM
TEMPERATURE.
EACH TERMINAL UNIT SHALL INCLUDE AN AIRFLOW SENSOR FOR CALCULATING CFM, AND A DISCHARGE AIR
TEMPERATURE SENSOR
EXTEND 24 VOLT POWER TO THE TERMINAL BOX CONTROLLER FROM THE ASSOCIATED AIR HANDLING UNIT DDC
CONTROL PANEL.
ROOM SPACE TEMPERATURE SET POINT SHALL BE ADJUSTABLE FROM THE FRONT END COMPUTER INTERFACE.
OCCUPANCY SENSOR OS1 PROVIDED UNDER DIV. 26 SHALL DETERMINE OCCUPIED/UNOCCUPIED MODES OF
OPERATION. TO INVOKE UNOCCUPIED SEQUENCE (1.7 BELOW), OCCUPANCY SENSORS FOR
GIVEN TERMINAL UNIT ZONE MUST SATISFY THIS CONDITION. EXTEND LOW VOLTAGE WIRING FROM ALL
APPLICABLE OCCUPANCY SENSOR(S) TO THE TERMINAL BOX CONTROLLER.
DURING THE UNOCCUPIED MODE OF OPERATION, THE CONTROL DAMPER ACTUATOR D1 SHALL POSITION TO THE UNOCCUPIED AIRFLOW SETTING (REFER TO AIR TERMINAL UNIT SCHEDULE, SHEET M601).
DURING THE UNOCCUPIED MODE OF OPERATION, WHEN THE ROOM TEMPERATURE AT T1 IS BELOW THE UNOCCUPIED HEATING SETPOINT (REFER TO HVAC DESIGN DATA SCHEDULE, SHEET M601), THE CONTROL SHALL INDEX TO THE OCCUPIED HEATING MODE OF OPERATION. THE CONTROL SHALL REVERT TO UNOCCUPIED OPERATION (SEE 2.7 ABOVE) WHEN ROOM TEMPERATURE T1 RISES 2 DEGREES (ADJUSTABLE) ABOVE THE
UNOCCUPIED HEATING SETPOINT.
VARIABLE VOLUME REHEAT TERMINAL CONTROL
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
VARIABLE VOLUME REHEAT TERMINAL CONTROL
2 CONSTANT VOLUME REHEAT TERMINAL CONTROL
2.1
2.2
2.3
2.4
2.5
3.1
3.2
3.3
3.4
3.5
3.6
DURING THE UNOCCUPIED MODE OF OPERATION, WHEN THE ROOM TEMPERATURE AT T1 IS ABOVE THE UNOCCUPIED COOLING SETPOINT (REFER TO HVAC DESIGN DATA SCHEDULE, SHEET M601), THE CONTROL SHALL INDEX TO THE OCCUPIED COOLING MODE OF OPERATION. THE CONTROL SHALL REVERT TO UNOCCUPIED OPERATION (SEE 1.7 ABOVE) WHEN ROOM TEMPERATURE T1 REDUCES 2 DEGREES (ADJUSTABLE) BELOW THE
UNOCCUPIED COOLING SETPOINT.
1.9
ALL SPACES ON A
VVR AND CVR TERMINAL CONTROLS
VVR CONTROL SEQUENCES WITH OCCUPANCY SENSING
CVR & VVR CONTROL SEQUENCES WITHOUT OCCUPANCY SENSING
T2
T1
C
PS PS
PM
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o t o n e h a lf in c h o n e fo o t th re e q u a rt er s in ch o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o t th re e in c h e s o n e fo o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
FULLY SPRINKLERED
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
JPA Project No.
Dwg. ofHEAPY PROJECT No.: 2017-05154 FIRM LICENSE No.: 01528
/9
/2
:3
:4
A
M
Renovate TCU-ICU Space Bldg. 330
03/09/2020
CONTROLS & AUTOMATION
M702
PCWW JS
17005.00
552-18-102
Dayton, Ohio
| Sheets |
| M001 - LEGEND & GENERAL NOTES |
| M300 - SECTIONS |
| M501 - DETAILS |
| M502 - DETAILS |
| M503 - DETAILS |
| M601 - SCHEDULES & DIAGRAMS |
| M602 - SCHEDULES & DIAGRAMS |
| M701 - CONTROLS & AUTOMATION |
| M702 - CONTROLS & AUTOMATION |
| MD102 - PARTIAL SECOND FLOOR PLAN - REMOVALS |
| MD103 - PARTIAL THIRD FLOOR PLAN - REMOVALS |
| MH102 - PARTIAL SECOND FLOOR PLAN - NEW WORK |
| MH103 - PARTIAL THIRD FLOOR PLAN - DUCTWORK |
| MH104 - ROOF PLAN |
| MP103 - PARTIAL THIRD FLOOR PLAN - PIPING |
| Sheets |
| M001 - LEGEND & GENERAL NOTES |
| M300 - SECTIONS |
| M501 - DETAILS |
| M502 - DETAILS |
| M503 - DETAILS |
| M601 - SCHEDULES & DIAGRAMS |
| M602 - SCHEDULES & DIAGRAMS |
| M701 - CONTROLS & AUTOMATION |
| M702 - CONTROLS & AUTOMATION |
| MD102 - PARTIAL SECOND FLOOR PLAN - REMOVALS |
| MD103 - PARTIAL THIRD FLOOR PLAN - REMOVALS |
| MH102 - PARTIAL SECOND FLOOR PLAN - NEW WORK |
| MH103 - PARTIAL THIRD FLOOR PLAN - DUCTWORK |
| MH104 - ROOF PLAN |
| MP103 - PARTIAL THIRD FLOOR PLAN - PIPING |
| Sheets |
| M001 - LEGEND & GENERAL NOTES |
| M300 - SECTIONS |
| M501 - DETAILS |
| M502 - DETAILS |
| M503 - DETAILS |
| M601 - SCHEDULES & DIAGRAMS |
| M602 - SCHEDULES & DIAGRAMS |
| M701 - CONTROLS & AUTOMATION |
| M702 - CONTROLS & AUTOMATION |
| MD102 - PARTIAL SECOND FLOOR PLAN - REMOVALS |
| MD103 - PARTIAL THIRD FLOOR PLAN - REMOVALS |
| MH102 - PARTIAL SECOND FLOOR PLAN - NEW WORK |
| MH103 - PARTIAL THIRD FLOOR PLAN - DUCTWORK |
| MH104 - ROOF PLAN |
| MP103 - PARTIAL THIRD FLOOR PLAN - PIPING |
| Sheets |
| M001 - LEGEND & GENERAL NOTES |
| M300 - SECTIONS |
| M501 - DETAILS |
| M502 - DETAILS |
| M503 - DETAILS |
| M601 - SCHEDULES & DIAGRAMS |
| M602 - SCHEDULES & DIAGRAMS |
| M701 - CONTROLS & AUTOMATION |
| M702 - CONTROLS & AUTOMATION |
| MD102 - PARTIAL SECOND FLOOR PLAN - REMOVALS |
| MD103 - PARTIAL THIRD FLOOR PLAN - REMOVALS |
| MH102 - PARTIAL SECOND FLOOR PLAN - NEW WORK |
| MH103 - PARTIAL THIRD FLOOR PLAN - DUCTWORK |
| MH104 - ROOF PLAN |
| MP103 - PARTIAL THIRD FLOOR PLAN - PIPING |
| Sheets |
| M001 - LEGEND & GENERAL NOTES |
| M300 - SECTIONS |
| M501 - DETAILS |
| M502 - DETAILS |
| M503 - DETAILS |
| M601 - SCHEDULES & DIAGRAMS |
| M602 - SCHEDULES & DIAGRAMS |
| M701 - CONTROLS & AUTOMATION |
| M702 - CONTROLS & AUTOMATION |
| MD102 - PARTIAL SECOND FLOOR PLAN - REMOVALS |
| MD103 - PARTIAL THIRD FLOOR PLAN - REMOVALS |
| MH102 - PARTIAL SECOND FLOOR PLAN - NEW WORK |
| MH103 - PARTIAL THIRD FLOOR PLAN - DUCTWORK |
| MH104 - ROOF PLAN |
| MP103 - PARTIAL THIRD FLOOR PLAN - PIPING |
| Sheets |
| M001 - LEGEND & GENERAL NOTES |
| M300 - SECTIONS |
| M501 - DETAILS |
| M502 - DETAILS |
| M503 - DETAILS |
| M601 - SCHEDULES & DIAGRAMS |
| M602 - SCHEDULES & DIAGRAMS |
| M701 - CONTROLS & AUTOMATION |
| M702 - CONTROLS & AUTOMATION |
| MD102 - PARTIAL SECOND FLOOR PLAN - REMOVALS |
| MD103 - PARTIAL THIRD FLOOR PLAN - REMOVALS |
| MH102 - PARTIAL SECOND FLOOR PLAN - NEW WORK |
| MH103 - PARTIAL THIRD FLOOR PLAN - DUCTWORK |
| MH104 - ROOF PLAN |
| MP103 - PARTIAL THIRD FLOOR PLAN - PIPING |
| Sheets |
| M001 - LEGEND & GENERAL NOTES |
| M300 - SECTIONS |
| M501 - DETAILS |
| M502 - DETAILS |
| M503 - DETAILS |
| M601 - SCHEDULES & DIAGRAMS |
| M602 - SCHEDULES & DIAGRAMS |
| M701 - CONTROLS & AUTOMATION |
| M702 - CONTROLS & AUTOMATION |
| MD102 - PARTIAL SECOND FLOOR PLAN - REMOVALS |
| MD103 - PARTIAL THIRD FLOOR PLAN - REMOVALS |
| MH102 - PARTIAL SECOND FLOOR PLAN - NEW WORK |
| MH103 - PARTIAL THIRD FLOOR PLAN - DUCTWORK |
| MH104 - ROOF PLAN |
| MP103 - PARTIAL THIRD FLOOR PLAN - PIPING |
| Sheets |
| M001 - LEGEND & GENERAL NOTES |
| M300 - SECTIONS |
| M501 - DETAILS |
| M502 - DETAILS |
| M503 - DETAILS |
| M601 - SCHEDULES & DIAGRAMS |
| M602 - SCHEDULES & DIAGRAMS |
| M701 - CONTROLS & AUTOMATION |
| M702 - CONTROLS & AUTOMATION |
| MD102 - PARTIAL SECOND FLOOR PLAN - REMOVALS |
| MD103 - PARTIAL THIRD FLOOR PLAN - REMOVALS |
| MH102 - PARTIAL SECOND FLOOR PLAN - NEW WORK |
| MH103 - PARTIAL THIRD FLOOR PLAN - DUCTWORK |
| MH104 - ROOF PLAN |
| MP103 - PARTIAL THIRD FLOOR PLAN - PIPING |
| Sheets |
| M001 - LEGEND & GENERAL NOTES |
| M300 - SECTIONS |
| M501 - DETAILS |
| M502 - DETAILS |
| M503 - DETAILS |
| M601 - SCHEDULES & DIAGRAMS |
| M602 - SCHEDULES & DIAGRAMS |
| M701 - CONTROLS & AUTOMATION |
| M702 - CONTROLS & AUTOMATION |
| MD102 - PARTIAL SECOND FLOOR PLAN - REMOVALS |
| MD103 - PARTIAL THIRD FLOOR PLAN - REMOVALS |
| MH102 - PARTIAL SECOND FLOOR PLAN - NEW WORK |
| MH103 - PARTIAL THIRD FLOOR PLAN - DUCTWORK |
| MH104 - ROOF PLAN |
| MP103 - PARTIAL THIRD FLOOR PLAN - PIPING |
| Sheets |
| M001 - LEGEND & GENERAL NOTES |
| M300 - SECTIONS |
| M501 - DETAILS |
| M502 - DETAILS |
| M503 - DETAILS |
| M601 - SCHEDULES & DIAGRAMS |
| M602 - SCHEDULES & DIAGRAMS |
| M701 - CONTROLS & AUTOMATION |
| M702 - CONTROLS & AUTOMATION |
| MD102 - PARTIAL SECOND FLOOR PLAN - REMOVALS |
| MD103 - PARTIAL THIRD FLOOR PLAN - REMOVALS |
| MH102 - PARTIAL SECOND FLOOR PLAN - NEW WORK |
| MH103 - PARTIAL THIRD FLOOR PLAN - DUCTWORK |
| MH104 - ROOF PLAN |
| MP103 - PARTIAL THIRD FLOOR PLAN - PIPING |
| Sheets |
| M001 - LEGEND & GENERAL NOTES |
| M300 - SECTIONS |
| M501 - DETAILS |
| M502 - DETAILS |
| M503 - DETAILS |
| M601 - SCHEDULES & DIAGRAMS |
| M602 - SCHEDULES & DIAGRAMS |
| M701 - CONTROLS & AUTOMATION |
| M702 - CONTROLS & AUTOMATION |
| MD102 - PARTIAL SECOND FLOOR PLAN - REMOVALS |
| MD103 - PARTIAL THIRD FLOOR PLAN - REMOVALS |
| MH102 - PARTIAL SECOND FLOOR PLAN - NEW WORK |
| MH103 - PARTIAL THIRD FLOOR PLAN - DUCTWORK |
| MH104 - ROOF PLAN |
| MP103 - PARTIAL THIRD FLOOR PLAN - PIPING |
| Sheets |
| M001 - LEGEND & GENERAL NOTES |
| M300 - SECTIONS |
| M501 - DETAILS |
| M502 - DETAILS |
| M503 - DETAILS |
| M601 - SCHEDULES & DIAGRAMS |
| M602 - SCHEDULES & DIAGRAMS |
| M701 - CONTROLS & AUTOMATION |
| M702 - CONTROLS & AUTOMATION |
| MD102 - PARTIAL SECOND FLOOR PLAN - REMOVALS |
| MD103 - PARTIAL THIRD FLOOR PLAN - REMOVALS |
| MH102 - PARTIAL SECOND FLOOR PLAN - NEW WORK |
| MH103 - PARTIAL THIRD FLOOR PLAN - DUCTWORK |
| MH104 - ROOF PLAN |
| MP103 - PARTIAL THIRD FLOOR PLAN - PIPING |
| Sheets |
| M001 - LEGEND & GENERAL NOTES |
| M300 - SECTIONS |
| M501 - DETAILS |
| M502 - DETAILS |
| M503 - DETAILS |
| M601 - SCHEDULES & DIAGRAMS |
| M602 - SCHEDULES & DIAGRAMS |
| M701 - CONTROLS & AUTOMATION |
| M702 - CONTROLS & AUTOMATION |
| MD102 - PARTIAL SECOND FLOOR PLAN - REMOVALS |
| MD103 - PARTIAL THIRD FLOOR PLAN - REMOVALS |
| MH102 - PARTIAL SECOND FLOOR PLAN - NEW WORK |
| MH103 - PARTIAL THIRD FLOOR PLAN - DUCTWORK |
| MH104 - ROOF PLAN |
| MP103 - PARTIAL THIRD FLOOR PLAN - PIPING |
| Sheets |
| M001 - LEGEND & GENERAL NOTES |
| M300 - SECTIONS |
| M501 - DETAILS |
| M502 - DETAILS |
| M503 - DETAILS |
| M601 - SCHEDULES & DIAGRAMS |
| M602 - SCHEDULES & DIAGRAMS |
| M701 - CONTROLS & AUTOMATION |
| M702 - CONTROLS & AUTOMATION |
| MD102 - PARTIAL SECOND FLOOR PLAN - REMOVALS |
| MD103 - PARTIAL THIRD FLOOR PLAN - REMOVALS |
| MH102 - PARTIAL SECOND FLOOR PLAN - NEW WORK |
| MH103 - PARTIAL THIRD FLOOR PLAN - DUCTWORK |
| MH104 - ROOF PLAN |
| MP103 - PARTIAL THIRD FLOOR PLAN - PIPING |
| Sheets |
| M001 - LEGEND & GENERAL NOTES |
| M300 - SECTIONS |
| M501 - DETAILS |
| M502 - DETAILS |
| M503 - DETAILS |
| M601 - SCHEDULES & DIAGRAMS |
| M602 - SCHEDULES & DIAGRAMS |
| M701 - CONTROLS & AUTOMATION |
| M702 - CONTROLS & AUTOMATION |
| MD102 - PARTIAL SECOND FLOOR PLAN - REMOVALS |
| MD103 - PARTIAL THIRD FLOOR PLAN - REMOVALS |
| MH102 - PARTIAL SECOND FLOOR PLAN - NEW WORK |
| MH103 - PARTIAL THIRD FLOOR PLAN - DUCTWORK |
| MH104 - ROOF PLAN |
| MP103 - PARTIAL THIRD FLOOR PLAN - PIPING |