610-311_6.24.2020_FW Primary Care Drawings GENERAL.pdf

PDF 17 MB Posted

Attached to
Y1DA--Expand First Floor B-1 for PACT - 610-311
Solicitation number
36C25020B0004
Issued by

About this file

This document package includes construction documents and specifications for an expansion of the first floor primary care clinic at the VA Northern Indiana Health Care System campus in Fort Wayne, Indiana. The project scope involves building a new addition over an existing basement area to accommodate additional sterile processing department space. The expansion will increase the size of the outpatient primary care clinic. Construction will be of Type I-B noncombustible materials according to NFPA 101 Life Safety Code requirements. Work is to be completed in multiple phases while maintaining operations in occupied areas of the facility. The solicitation number provided is 36C25020B0004 for the project titled "Y1DA--Expand First Floor B-1 for PACT - 610-311" being conducted by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10.

View the file

Other files

File Type Posted
2020.8.6. Add 3 088000 - Glazing.docx DOCX document
16.1045 - 2020.8.6. Add 3 Civil Sheets.pdf PDF
2020.8.6. Add 3 061000 - Rough Carpentry.docx DOCX document
36C25020B0004 0008.docx DOCX document
16.1045 - 2020.8.6 Addendum 3 Responses.pdf PDF
2020.8.6. Add 3 090600 - SCHEDULE OF FINISHES.docx DOCX document
16.1045 - 2020.8.6. Add 3 Arch Sheets.pdf PDF
2020.8.6. Add 3 083616.13 - BARN DOOR.doc DOC document
16.1045 - 2020.8.6 Revised Sheet MI102.pdf PDF
36C25020B0004 0007.docx DOCX document
36C25020B0004 0006.docx DOCX document
36C25020B0004 0005.pdf PDF
RFI - 7-30-2020.pdf PDF
Masking due to COVID.pdf PDF
RFI - 7-31-2020.pdf PDF
RFI - 7-29-2020.pdf PDF
08 44 13 - Glazed Aluminum Curtain Walls.pdf PDF
16.1045 - 2020.7.28 - Addendum 2.pdf PDF
16965 - PD101 - BASEMENT PLUMBING REMOVAL PLAN.pdf PDF
36C25020B0004 0004.pdf PDF
16965 - PL101 - BASEMENT PLUMBING PLAN.pdf PDF
RFI Form AHS 1 Plumbing.pdf PDF
RFI Form AHS 4 Plumbing.pdf PDF
RFI Form AHS 3 Plumbing.pdf PDF
RFI Form AHS 2 Plumbing.pdf PDF
16.1045 - 2020.7.16 - Addendum 1 Revised Sheets.pdf PDF
16.1045 - 2020.7.16 - Addendum 1 Description.pdf PDF
36C25020B0004 0003.pdf PDF
36C25020B0004 0002.docx DOCX document
Sign-in Sheet Sub-Contractors.pdf PDF
Sign-in Sheet Prime Contractors 7-7-2020.pdf PDF
36C25020B0004 0001.docx DOCX document
36C25020B0004.docx DOCX document
610-311 FW Primary Care Drawings STRUCTURAL.pdf PDF
610-311 FW Primary Care Drawings ARCHITECTURAL.pdf PDF
610-311 FW Primary Care Drawings MEP.pdf PDF
610-311 FW Primary Care Drawings CIVIL.pdf PDF
36C25020B0004_2.docx DOCX document
Wage Determination - Highway 6-12-20.pdf PDF
36C25020B0004_3.docx DOCX document
Spec Volume 1 - 610-311.pdf PDF
Wage Determination - Building 6-12-20.pdf PDF
Spec Volume 2 - 610-311.pdf PDF
Contractor Certification Regarding Safety and Environmental.pdf PDF
RFI Form.pdf PDF
Show all 45

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AREA

MAP

VICINITY MAP

CAMPUS MAP

FORT WAYNE VA CAMPUS

FORT WAYNE VA CAMPUS

N

N

N

AREA OF

EXPANSION

EXISTING

PRIMARY CARE -

1ST FLOOR AREA

R A

N D

A

LL

A D

R

IV

E

LAKE AVENUE

BUILDING 1

BLDG 2

BLDG 3

B 7

B 10

B 6B 5

DEDUCTIVE BID ALTERNATE SUMMARY

A.

B.

C.

D.

E.

F.

G.

H.

I.

OMIT ADDITIONAL PARKING AREA AND ALL ASSOCIATED SITE WORK FROM PROJECT SCOPE

OMIT FROM PROJECT SCOPE THE NEW PRIMARY CARE ENTRANCE VESTIBULE AND

ASSOCIATED ROOF, DOORS, CURTAIN WALL, ETC. OMIT ALSO THE SMALLER 'CONNECTION'

CANOPY; THE LARGER DROP OFF CANOPY IS TO REMAIN. THE MAIN PATH TO THE PRIMARY

CARE SUITE SHALL BE THROUGH THE BUILDING'S MAIN ENTRANCE.

OMIT EXTENSION OF STAIRWAY 1-C-ST1 ABOVE FIRST FLOOR ROOF. OMIT NEW STAIRWAY

AND HANDRAIL EXTENSION IN STAIR 1-C-ST2, EXISTING STAIR SHALL REMAIN. PROVIDE

ROOF HATCH IN STAIRWAY 1-C-ST1 FOR ROOF ACCESS, REFER TO SPECIFICATIONS. FIRST

FLOOR ROOF SHALL EXTEND TO PARAPET ABOVE OMITTED STAIRWAY EXTENSION TO

CREATE A SINGLE, LEVEL ROOF SURFACE.

OMIT INSULATED METAL WALL PANEL WHERE INDICATED ON GI106 FROM PROJECT SCOPE

AND REPLACE WITH 2" RIGID INSULATION AND BRICK VENEER; REFER TO SIMILAR WALL

SECTIONS FOR CONSTRUCTION. REMOVE SUNSHADES FROM SCOPE OF PROJECT.

OMIT SLIDING EXAM DOOR ASSEMBLIES AND STOREFRONT DOOR SYSTEMS, INCLUDING

ACCESS CONTROLS, FROM INTERIOR SCOPE OF PROJECT. PROVIDE HOLLOW METAL

FRAMES, SOLID CORE WOOD SWING DOORS, AND STORAGE LOCKSET IN LIEU OF OMITTED

SLIDING DOORS.

OMIT FROM PROJECT SCOPE 15'-0" (1 BAY) OF THE DROP OFF CANOPY FROM THE EAST END

OMIT FROM PROJECT SCOPE 30'-0" (2 BAYS) OF THE DROP OFF CANOPY FROM THE EAST

END

OMIT REMAINING PORTION OF LARGE DROP OFF CANOPY (3 BAYS).

OMIT SELECT LANDSCAPING COMPONENTS, REFER TO CIVIL DRAWINGS FOR ADDITIONAL

INFORMATION.

FULL DESCRIPTIONS AND ADDITIONAL INFORMATION INDICATED ON SHEETS GI105, GI106, GI107, AND

SPECIFICATIONS

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked By:

Building Number

Project Number

Drawing Number

Drawn By:

Revisions: Date

ARCHITECT/ENGINEERS:

VA NORTHERN INDIANA - FW

#1 o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

JAMES A. BROYLES, COR 610-311

GUIDON DESIGN INC.

905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN.

46204

317.800.6388 | WWW.GUIDONDESIGN.COMSUSTAINABLE ARCHITECTURE + ENGINEERING

PROJECT LEAD

Architect, Structural and Civil Engineer

VA NORTHERN INDIANA HEALTH CARE SYSTEM

FORT WAYNE CAMPUS

FORT WAYNE, INDIANA

MEP Engineer

4031 TRANSPORTATION DR.

FORT WAYNE, IN 46818

(260) 918-3045

DESIGN-AIRE ENGINEERING,

INC.

220 N COLLEGE AVE

INDIANAPOLIS, IN 46202

(317) 464-9090

Commissioning Agent

C U s e rs

\t s a n d e rs \D o c u m e n ts

\1 .1

F W

P ri m a ry

C a re A ts a n d e rs g u id o n d e s ig n .c o m

.r v t

CONSTRUCTION DOCUMENTS

GI000

TSKA/JG

COVER SHEET

2019/4/16

16.1045EXPAND BUILDING 1 - 1ST FLOOR

PRIMARY CARE

VA NORTHERN INDIANA HEALTHCARE SYSTEM,

FORT WAYNE, IN

VA PROJECT NO. 610-311

EXPAND BUILDING 1

1ST FLOOR PRIMARY CARE

CONSTRUCTION DOCUMENTS

APRIL 16, 2019

SHEET LIST

SHEET # SHEET NAME

LS501 LANDSCAPE DETAILS

ARCHITECTURAL

AS001 ARCHITECTURAL SYMBOLS AND ABBREVIATIONS

AD101 BASEMENT DEMOLITION PLAN

AD102 1ST FLOOR AND BASEMENT ROOF DEMOLITION PLAN

AD201 DEMOLITION BUILDING ELEVATIONS - SOUTH

AD202 DEMOLITION BUILDING ELEVATIONS - EAST, WEST, AND NORTH

AD311 DEMOLITION WALL SECTIONS

AD312 DEMOLITION WALL SECTIONS

AS100 OVERALL SITE PLAN

AS101 BASEMENT CONSTRUCTION PLAN

AS102 1ST FLOOR DIMENSION PLAN

AS103 1ST FLOOR CONSTRUCTION PLAN

AS104 1ST FLOOR ROOF AND 2ND FLOOR CONSTRUCTION PLAN

AS105 2ND FLOOR ROOF AND 3RD FLOOR CONSTRUCTION PLAN

AS106 ARCHITECTURAL SITE PLAN AND CANOPY PLAN

AS111 1ST FLOOR REFLECTED CEILING PLAN

AS201 BUILDING ELEVATIONS

AS202 BUILDING ELEVATIONS

AS203 BUILDING ELEVATION - WEST AND ENLARGED CANOPY ELEVATIONS

AS311 WALL SECTIONS - NEW 1ST FLOOR - VESTIBULE

AS312 WALL SECTIONS - NEW 1ST FLOOR - RELIEF AIR CHASE AND UTILITY

CHASE

AS313 WALL SECTIONS - NEW 1ST FLOOR

AS314 WALL SECTIONS

AS315 WALL SECTIONS - EXISTING 1ST FLOOR

AS321 STAIR PLANS AND SECTIONS

AS401 ENLARGED TOILET PLANS AND ELEVATIONS

AS402 ENLARGED PLANS AND ELEVATIONS

AS501 PLAN DETAILS

AS502 WALL SECTION DETAILS - BASE

AS503 WALL SECTION DETAILS - HEAD

AS504 WALL SECTION DETAILS - PARAPET

AS505 ROOF DETAILS

AS506 CANOPY & EXTERIOR SIGN DETAILS

AS601 DOOR AND WINDOW SCHEDULES

AS602 DOOR AND WINDOW ELEVATIONS AND DETAILS

AS603 FINISH SCHEDULES & SIGNAGE TYPES

AS604 SIGNAGE PLAN

AS901 INTERIOR SECTIONS AND DETAILS

AS902 INTERIOR SECTIONS AND DETAILS

AF101 1ST FLOOR FLOOR FINISH PLAN

AF102 1ST FLOOR WALL FINISH PLAN

AF103 ENLARGED FLOOR FINISH PLANS

AQ101 1ST FLOOR EQUIPMENT PLAN

FIRE PROTECTION

FP100 FIRE PROTECTION NOTES, DETAILS, & DIAGRAM

FP101 BASEMENT FIRE PROTECTION PLAN

FP102 FIRST FLOOR FIRE PROTECTION PLAN

PLUMBING

PD101 BASEMENT PLUMBING REMOVAL PLAN

PD102 FIRST FLOOR PLUMBING REMOVAL PLAN

PL100 PLUMBING, LEGEND, DETAILS & NOTES

PL101 FOUNDATION PLUMBING PLAN

PL102 BASEMENT PLUMBING PLAN

PL103 FIRST FLOOR PLUMBING PLAN

PL104 ROOF PLUMBING PLAN

PL105 DIAGRAMS & ENLARGED PLUMBING PLANS

PL106 WASTE & VENT PIPING DIAGRAM

MECHANICAL

MD101 BASEMENT MECHANICAL DUCT REMOVAL PLAN

MD102 FIRST FLOOR MECHANICAL DUCT REMOVAL PLAN

MD103 SECOND FLOOR MECHANICAL REMOVAL PLAN

MD111 BASEMENT MECHANICAL PIPING REMOVAL PLAN

MD112 FIRST FLOOR MECHANICAL PIPING REMOVAL PLAN

MH101 BASEMENT MECHANICAL DUCT PLAN

MH102 FIRST FLOOR MECHANICAL DUCT PLAN

MH103 SECOND FLOOR ROOF MECHANICAL PLAN

MH301 MECHANICAL SECTIONS

MI101 MECHANICAL ABBREVIATIONS AND LEGEND

MI102 MECHANICAL SCHEDULES

MI103 MECHANICAL DETAILS

MI104 MECHANICAL DETAILS

MI105 MECHANICAL DETAILS

MI106 MECHANICAL DETAILS

MI107 CHILLED WATER FLOW DIAGRAMS

MI108 HOT WATER FLOW DIAGRAM

MI109 TEMP CONTROL

MI110 TEMP CONTROL

MI111 TEMP CONTROL

MI112 TEMP CONTROL

MP101 BASEMENT MECHANICAL PIPING PLAN

MP102 FIRST FLOOR MECHANICAL PIPING PLAN

ELECTRICAL

ED100 ELECTRICAL GENERAL NOTES, LEGEND, AND KEY PLANS

ED101 FIRST FLOOR ELECTRICAL REMOVAL PLAN

EJ101 ELECTRICAL DATA & COMMUNICATIONS DETAILS

EJ102 ELECTRICAL DETAILS

EJ103 ELECTRICAL DETAILS

EJ104 LIGHTING SCHEDULE, MOTOR CONTROL SCHEDULE & DIAGRAMS

EL101 FIRST FLOOR LIGHTING PLAN

EP101 BASEMENT POWER AND SYSTEMS PLAN

EP102 FIRST FLOOR POWER PLAN

EP103 SECOND FLOOR AND ROOF POWER PLAN

EP104 PANEL SCHEDULES

EP105 PANEL SCHEDULES

EP110 ELECTRICAL ONE-LINE DIAGRAM

ES101 SITE LIGHTING PLAN

EY102 FIRST FLOOR SYSTEMS PLAN

EY103 FIRST FLOOR VGIA WIRLESS ACCESS PLAN

SHEET LIST

SHEET # SHEET NAME

GENERAL

GI000 COVER SHEET

GI101 BASEMENT LIFE SAFETY PLAN AND INFECTION CONTROL PLANS

GI102 1ST FLOOR LIFE SAFETY FLOOR PLAN

GI103 1ST FLOOR INFECTION CONTROL / PHASING PLANS

GI104 CONSTRUCTION LOGISTICS SITE PLAN

GI105 DEDUCTIVE BID ALTERNATES 'A' AND 'B'

GI106 DEDUCTIVE BID ALTERNATES 'C' AND 'D'

GI107 DEDUCTIVE BID ALTERNATES 'E' AND 'H'

CIVIL

VF101 TOPOGRAPHIC SURVEY

CC001 GENERAL CIVIL NOTES

CD101 DEMOLITION PLAN

CS101 SITE PLAN

CS102 SITE PLAN - ALTERNATE A

CS501 SITE DETAILS

CS502 SITE DETAILS

CG101 GRADING PLAN

CG102 GRADING SECTIONS

CG103 GRADING PLAN - ALTERNATE A

CU101 UTILITY PLAN

CU102 STORMWATER PROFILES

CU103 UTILITY PLAN ALT - ALTERNATE A

CU501 UTILITY DETAILS

CU502 UNDERGROUND STORAGE DETAILS

CU503 UNDERGROUND STORAGE DETAILS

CJ101 EROSION CONTROL PLAN

CJ501 EROSION CONTROL DETAILS

CJ502 SWPPP

LS101 LANDSCAPE PLAN

LS102 LANDSCAPE PLAN

Contact:Contact:Contact:Contact

Contact:

BCCLT

WILLIAM HOSMON, PE

MECHANICAL ENGINEER

MECHANICAL,

ELECTRICAL &

PLUMBING

GUIDON DESIGN INC.

MARK VANDERWOUDE, PE

STRUCTURAL ENGINEER

STRUCTURAL

ENGINEER

GUIDON DESIGN INC.

DAVID COUNSELL, PE

CIVIL ENGINEER

905 North Capitol Avenue Suite 100 Indianapolis, IN 46204 p: 317.800.6388 x 109 e:dcounsell@guidondesign.com

CIVIL

ENGINEER

VA NORTHERN INDIANA

HEALTH CARE SYSTEM

JAMES A. BROYLES

COR, ENGINEERING SERVICES

1700 E. 38th St.

Marion, IN 46953 p: 765-674-3321 x 73592 e: james.broyles@va.gov

OWNER

GUIDON DESIGN INC.

KARI ALLEN, AIA

HEALTHCARE ARCHITECT,

PROJECT MANAGER

905 North Capitol Avenue Suite 100 Indianapolis, IN 46204 p: 317.800.6388 x 112 e: kallen@guidondesign.com

ARCHITECT

905 North Capitol Avenue Suite 100 Indianapolis, IN 46204 p: 317.800.6388 x 119 e: mvanderwoude@guidondesign.com

4031 Transportation Drive Fort Wayne, In 46818 p: (812) 423-4407 e: hosmon@bcclt.com

UP

AREA OF 1ST FLOOR

PRIMARY CARE

EXPANSION

GENERATOR BUILDING 16

HOSPITAL BUILDING 1

1 EAST WING

N

EXISTING PRIMARY CARE

MAIN

ENTRANCE

GENERATOR BUILDING 16

CHILLER

B-C-100

ROOM

STAIR 1

B-C-ST1

LOUNGE

B-C-103

SPS ASSISTANT

OFFICE

B-C-103D

PREP/ASSEMBLY

B-C-106C

WOMENS LOCKER

ROOM

B-C-103A

MENS LOCKER

ROOM

B-C-103B

STERILIZER ACCESS

B-C-106D

WAREHOUSE

B-C-115

STERILE/

NON-STERILE

STORAGE

B-C-113

H A

C

B -C

-1

G

STORAGE (FUTURE

DUMBWAITER)

B-C-106F

STORAGE (FUTURE

EQUIP. ROOM)

B-C-113A

ELECTRICAL

B-C-108

LOUNGE, STAFF

B-C-109

O

IT

C

LO

S E

T

B -C

-1

PPE AREA

B-C-106A

CART PREP

B-C-106B

CONERENCE ROOM /

TRAINING

B-C-105

SPS DIRECTOR

B-C-104A

CUBICLE, CLERICAL

STAFF

B-C-104

OFFICE (FUTURE

ELEVATOR)

B-C-EL2

OFFICE (FUTURE

ELEVATOR)

B-C-EL1

STORAGE (FUTURE

EQUIP ROOM)

B-C-101

HAC

B-C-102A

STORAGE (FUTURE

DUMBWAITER)

B-C-102B

SCOPE

DECONTAMINATION

B-C-102C

SCOPE

STERILIZATION

B-C-106E

AUTOMATIC CART

WASH

B-C-102D

DECONTAMINATION

B-C-102

CORRIDOR

B-C-C2

VESTIBULE

B-C-110

MENS LOCKER

ROOM

B-C-109A

WOMENS LOCKER

ROOM

B-C-109B

O

FF

IC

E

(F U

TU

R

E E

LE

V

A

TO

R

B -C

-E L

PURCHASING

B-C-111

CORRIDOR

B-C-C3

LOGISTICS

CLERICAL

B-C-112

LOGISTICS

SUPERVISOR

B-C-112A

LOGISTICS

DIRECTOR

C-112B

H A

C

B -C

-1

OFFICE

B-C-116

STAIRS

B-C-ST2

PHARMACY

STORAGE

OIT

53A

BIOMETRICS

MAIL ROOM

49B

WATER TREATMENT

49C

45B

59A 59B 59C 58

EXIT

EXIT

EXIT

STAIR DOES NOT EXIT

IMMEDIATELY TO EXTERIOR

EXISTING EXTERIOR

RETAINING WALL

TRAVEL DISTANCE = 77'-6"

44A

42A

45A

60B

60A

46 47

63A

CORRIDOR

B-C-C1

STAIRS

B-C-ST2

WOMENS LOCKER

ROOM

B-C-103A

MENS LOCKER

ROOM

B-C-103B

SPS ASSISTANT

OFFICE

B-C-103D

PREP/ASSEMBLY

B-C-106C

STERILE/

NON-STERILE

STORAGE

B-C-113

HAC

B-C-106G

STORAGE (FUTURE

DUMBWAITER)

B-C-106F

STORAGE (FUTURE

EQUIP. ROOM)

B-C-113A

MENS LOCKER

ROOM

B-C-109A

WOMENS LOCKER

ROOM

B-C-109B

CORRIDOR

B-C-C3

HAC

B-C-114

OFFICE

B-C-116

OFFICE (FUTURE

ELEVATOR)

B-C-EL3

STORAGE (FUTURE

EQUIP ROOM)

B-C-101

STORAGE (FUTURE

DUMBWAITER)

B-C-102B

ROOM

WATER TREATMENT

49C

WAREHOUSE

B-C-115

STERILIZER ACCESS

B-C-106D

LOGISTICS

DIRECTOR

C-112B

LOGISTICS

CLERICAL

B-C-112

LOGISTICS

SUPERVISOR

B-C-112A

PURCHASING

B-C-111

VESTIBULE

B-C-110

CORRIDOR

B-C-C2

PPE AREA

B-C-106A

CONERENCE ROOM /

TRAINING

B-C-105

OIT CLOSET

B-C-107

SPS DIRECTOR

B-C-104A

CUBICLE, CLERICAL

STAFF

B-C-104

SCOPE

STERILIZATION

B-C-106E

OFFICE (FUTURE

ELEVATOR)

B-C-EL2

OFFICE (FUTURE

ELEVATOR)

B-C-EL1

HAC

B-C-102A

CORRIDOR

B-C-C1

LOUNGE

B-C-103

PPE AREA

B-C-103C

CHILLER

B-C-100

STAIR 1

B-C-ST1

ELECTRICAL

B-C-108

LOUNGE, STAFF

B-C-109

SCOPE

DECONTAMINATION

B-C-102C

DECONTAMINATION

B-C-102

AUTOMATIC CART

WASH

B-C-102D

CART PREP

B-C-106B

PHARMACY

STORAGE

OIT

53A

BIOMETRICS

MAIL ROOM

575859C59B59A

45B

49B 51 52

60A

60B

STAIR

B-1

STAIR

B-2

ABOVE CEILING WORK REQUIRED IN THIS AREA. REFER TO MEP DRAWINGS FOR ADDITIONAL INFORMATION

B1 B2

B3

B4

INFECTION CONTROL AND PHASING LEGEND

TEMPORARY WALLS TO BE PROVIDED AS A

BARRIER BETWEEN AREAS OF WORK AND

OCCUPIED PORTIONS OF THE BUILDING. SEE

PLAN AND PLAN NOTES

TEMPORARY CONSTRUCTION ACCESS

DOORS

BEYOND PRIMARY PROJECT SCOPE

BOUNDARY. REFER TO DRAWINGS AND

DETAILS FOR WORK REQUIRED IN THIS AREA.

PRIMARY CARE SUITE BOUNDARY

AREA OF PHASE 1 WORK. THE MAIN BODY OF

WORK SHALL BE COMPLETED DURING PHASE 1

INCLUDING THE 1ST FLOOR ADDITION.

WORK SHOWN IN THIS AREA BY VA - NOT IN CONTRACT

PHASING GENERAL NOTES

A.

B.

C.

D.

E.

F.

G.

H.

PROJECT SHALL BE COMPLETED IN 2 MAIN PHASES. SEE INFECTION CONTROL /

PHASING FLOOR PLAN FOR LOCATIONS.

SCHEDULE AND TIME OF CONSTRUCTION WORK FOR ALL PHASES SHALL BE

APPROVED BY COR AND NURSING STAFF BEFORE CONSTRUCTION MAY BEGIN.

PROVIDE PHASING INFORMATION FOR ABOVE CEILING WORK IN THE CONTRACTOR

PROVIDED CMP SCHEDULE. THIS INCLUDES WORK REQUIRED ABOVE AND BELOW

THE FLOOR PLAN OF THE PROJECT BOUNDARY.

ABOVE CEILING WORK OUTSIDE OF INDICATED PROJECT BOUNDARY AND IN THE

BASEMENT IS REQUIRED - COORDINATE WORK RESTRICTIONS WITH VA. CEILING

TILES SHALL BE REMOVED AND STORED IN A SAFE MANNER UNTIL CEILING TILES

CAN BE REINSTALLED. DAMAGED AND BROKEN CEILING TILES SHALL BE REPLACED

BY CONTRACTOR. FOR WORK IN VA OCCUPIED SPACES, CONTRACTOR SHALL

REPLACE CEILING TILES OR USE VA APPROVED TEMPORARY MATERIALS IN PLACE

OF CEILING TILES TO ALLOW VA ACTIVITES TO CONTINUE UNTIL CONTRACTORS

NEXT TASK IN A PARTICULAR AREA. CONTRACTOR TO SUBMIT SCHEDULE THAT

INDICATES WORK FOR SPECIFIC AREAS AND COORDINATE WITH THE VA FOR

ACCESS.

EXIT/ACCESS FOR ADJACENT OPERATIONAL AREAS SHALL BE MAINTAINED DURING

NORMAL BUSINESS HOURS. SEE SPECIFICATION FOR HOURS OF OPERATION.

WORK REQUIRING VIBRATION OR LOUD NOISE SHALL TAKE PLACE BETWEEN THE

HOURS OF 6:00 AM AND 5:00 PM AND AS AGREED UPON BY COR SO AS NOT TO

DISTURB SLEEPING PATIENTS IN OTHER AREAS OF THE HOSPITAL. EVERY EFFORT

SHALL BE MADE TO KEEP NOISE AND VIBRATION TO A MINIMUM.

GRAPHIC REPRESENTATION OF AREAS OF WORK AND/OR PHASING PLANS ARE

NOT SUITABLE FOR USE BY THE CONTRACTOR TO ESTIMATE DISTANCES /

QUANTITIES THAT MAY BE REQUIRED TO BE INSTALLED IN THE ACTUAL BUILDING.

CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY AND MEASURE ALL FIELD

CONDITIONS TO INCLUDE (E) ITEMS TO REMAIN THAT THE VA MIGHT NEED

ACCESSIBLE E.G. SWITCHES, CONTROLS, DOORS, ACCESS PANELS,

THERMOSTATS, AIR SUPPLY, AIR RETURN, ETC.

EXISTING PROJECT AREAS WILL BE OCCUPIED BY STAFF AND VETERANS

THROUGHOUT CONSTRUCTION. ALL/ANY WORK REQUIRED IN VA OCCUPIED SPACE

MUST BE SCHEDULED WITH THE COR.

REFER TO SPECIFICATION SECTION 01 00 00 GENERAL REQUIREMENTS FOR

ADDITIONAL INFORMATION.

REFERS TO SHEETS GI101 AND GI103

AREA OF PHASE 2A, 2B, AND 2C WORK, 1ST

FLOOR ONLY. PHASE 2 WORK IS WITHIN THE

EXISTING BUILDING AND SHALL BEGIN ONCE

PHASE 1 HAS BEEN COMPLETED.

CONTRACTOR SHALL BE REQUIRED TO

COORDINATE PHASE 2 WORK WITH THE COR

AND SUBPHASES SHALL NOT BE ASSUMED

TO BE PERFORMED SIMULTANEOUSLY.

INFECTION CONTROL PLAN NOTES #

INFECTION CONTROL PROJECT INFORMATION

CONSTRUCTION ACTIVITY - FIRE RISK: D

PATIENT RISK GROUP: HIGHEST

CLASS OF PRECAUTION MATRIX: IV

PROVIDE IC TEMPORARY BARRIER WALL CONSTRUCTION PER NFPA 241. REFER

TO DETAILS 2/GI102 AND 3/GI102.

PROVIDE IC TEMPORARY CONSTRUCTION DOOR WITH CARD READER ACCESS.

REFER TO ELEVATION 3/GI103. ACCESS CONTROL IS NOT A PART OF AND IS NOT

CONNECTED TO VA PACS/PIN SYSTEM.

DOOR OPENING SHALL BE CUT AND INSTALLED DURING OFF HOURS SUCH THAT

ROOMS REMAIN OPERATIONAL THROUGHOUT CONSTRUCTION.

INTENT IS THAT ABOVE CEILING WORK IN STERILE PROCESSING STORAGE IN

BASEMENT IS MINIMIZED.

TEMPORARY WALLS IN EXISTING EXAM ROOMS SHALL BE ALIGNED WITH

BULKHEAD ABOVE SUCH THAT ACOUSTIC CEILING GRID IS UNAFFECTED AND

ENCROACHMENT INTO OPERATIONAL ROOMS IS MINIMIZED, TYPICAL.

1.

2.

3.

4.

5.

REFER TO DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.

COORDINATE FULL SCOPE OF WORK WITH ENGINEERING DRAWINGS AND FIELD

VERIFICATION. CONTRACTOR IS RESPONSIBLE FOR SCOPE OF ABOVE CEILING

WORK REQUIRED ON THE 1ST FLOOR AND ON THE LOWER LEVEL.

COORDINATE LOCATION OF TEMPORARY INFECTION CONTROL (IC) BARRIER WALL

CONSTRUCTION AND INFECTION CONTROL (IC) MEASURES WITH COR AND

PATIENT SAFETY/ INFECTION CONTROL REPRESENTATIVE. TEMPORARY IC

BARRIER WALL CONSTRUCTION LOCATIONS IN DRAWINGS ARE APPROXIMATE.

CONTRACTOR SHALL PROVIDE DRAWING TO COR AND PATIENT SAFETY/

INFECTION CONTROL REPRESENTATIVE ONCE ICRA PROTOCOLS AND PLAN IS IN

PLACE.

PROVIDE A 24"X36" STICKY WALK OFF MAT AND HAND SANITIZER AT EACH

TEMPORARY DOOR LOCATION. MAT SHALL BE REPLACED OR CLEANED AS

DIRECTED BY VA.

PROVIDE THE REQUIRED VA AND OSHA TEMPORARY SIGNAGE AT EACH

TEMPORARY DOOR LOCATION.

CONTRACTOR SHALL SUPPLY SPILL KIT. SPILL KIT TO INCLUDE SHOP VAC, MULTI-

PURPOSE SPILL CONTROL SORBENTS TO ABSORB NON AGGRESSIVE LIQUIDS UP

TO 30 GALLONS.

THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING INGRESS/EGRESS TO THE

PROJECT AREA FROM THE EXTERIOR OF THE BUILDING AND WILL NOT BE

PERMITTED TO UTILIZE ANY PORTION OF THE EXISTING VA BUILDING TO MOVE

LABOR OR MATERIALS THROUGH.

- ALL NEW MATERIAL TRANSPORTED WITHIN EXISTING 1-EAST

SHALL BE COVERED WITH 4 MIL. POLY SHEET.

-FOR DEMOLITION MATERIAL REMOVED FROM EXISTING 1-EAST,

ROUTE SHALL BE VA APPROVED, IN ENCLOSED DUMPSTER CART

DESIGNED FOR SUCH PURPOSE, WITH A LID.

ALL MATERIAL, DEBRIS AND HAZARDOUS MATERIALS SHALL BE PROPERLY

STORED IN DESIGNATED AREAS AND APPROVED CONTAINERS. FLAMMABLE

MATERIALS SHALL NOT BE STORED IN THE FACILITY.

PROVIDE CONTAINMENT CART FOR ABOVE CEILING ACCESS OUTSIDE THE

INDICATED PHASE BOUNDARY.

ASBESTOS ABATEMENT: REVIEW THE 'Ft. Wayne VAMC Asbestos Reinspection

2016' DOCUMENT PROVIDED WITH THE CONSTRUCTION DOCUMENTS FOR

EXTERIOR WINDOW CAULK ASSUMED TO CONTAIN ASBESTOS. REFER TO

SPECIFICATIONS FOR ADDITIONAL INFORMATION.

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

INFECTION CONTROL GENERAL NOTES

REFERS TO SHEETS GI101 AND GI103

REFERS TO SHEETS GI101 AND GI103

BASEMENT ACCESS NOTES

B1.

B2.

B3.

B4.

CONTRACTOR'S ACCESS TO BASEMENT LEVEL WILL BE LIMITED.

AREAWAY: CONTRACTOR MAY UTILIZE THIS TO MOVE MATERIALS AND

EQUIPMENT.

STAIR B-C-ST1: THIS IS CONSIDERED TO BE A FINISHED SPACE AND AS

SUCH ANY DAMAGE CAUSED BY THE CONTRACTOR TO THE FINISHES OR

MATERIALS WILL BE REPAIRED BY THE CONTRACTOR TO THE

SATISFACTION OF THE VA. VA TO PROVIDE A KEY TO THIS STAIRWAY DOOR.

DOUBLE DOORS EAST END: ACKNOWLEDGED AS THE MOST PROBABLE

ACCESS POINT TO THE BASEMENT WHICH ALSO OPENS INTO FINISHED

SPACE. DAMAGE CAUSED BY THE CONTRACTOR TO THE FINISHES SHALL

BE REPAIRED BY THE CONTRACTOR. CONTRACTOR SHALL HAVE ACCESS

THROUGH THIS PAIR OF DOORS. ONLY WHEEL CARTS WITH NON-MARRING

WHEELS WILL BE ALLOWED INSIDE.

NO CONTRACTOR ACCESS AT THIS POINT.

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked By:

Building Number

Project Number

Drawing Number

Drawn By:

Revisions: Date

ARCHITECT/ENGINEERS:

VA NORTHERN INDIANA - FW

#1 o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

JAMES A. BROYLES, COR 610-311

GUIDON DESIGN INC.

905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204

317.800.6388 | WWW.GUIDONDESIGN.COM

SUSTAINABLE ARCHITECTURE + ENGINEERING

PROJECT LEAD

Architect, Structural and Civil Engineer

VA NORTHERN INDIANA HEALTH CARE SYSTEM

FORT WAYNE CAMPUS

FORT WAYNE, INDIANA

MEP Engineer

4031 TRANSPORTATION DR.

FORT WAYNE, IN 46818

(260) 918-3045

DESIGN-AIRE ENGINEERING, INC.

220 N COLLEGE AVE

INDIANAPOLIS, IN 46202

(317) 464-9090

Commissioning Agent

C U s e rs

\t s a n d e rs

\D o c u m e n ts

\1 .1

F W

P ri m a ry

C a re ts a n d e rs g u id o n d e s ig n .c o m

.r v t

CONSTRUCTION DOCUMENTS

GI101

TSKA/JG

BASEMENT LIFE SAFETY PLAN AND

INFECTION CONTROL PLANS

2019/4/16

16.1045EXPAND BUILDING 1 - 1ST FLOOR

PRIMARY CARE

SCALE: 1" = 100'-0"

KEY PLAN

SCALE: 1/16" = 1'-0"GI101

1 BASEMENT LIFE SAFETY FLOOR PLAN

SCALE: 1/16" = 1'-0"GI101

2 BASEMENT INFECTION CONTROL / PHASING FLOOR PLAN

N

115 114

120 120A

121B 121D 121E 121F 121G

109D

109C

194A 193

188 187A

186A

107A

108109

130127 128 129

126 128A 1

133 135

A157 A158

A163

A164

A102 A103 A118

A105 A120

A122 A121

A119

A117

A140

A143

A142

A141

A102A A101

A153

A151

A148

A150

A152

A147

A149

A155

A154

A145 A144

A127

A128

A132

A106

A108

A110

A107

A116

A114

A112

A111

A113

A115 A131 A133 A135 A136

A

A129

A138 A

A139

A124

A126A109

A137 A127A

A125

A123

A

A B

A

A104

A A

A B

A165 A166

A168

A169B

A169A

A159

A156E A156D

A156C

A156A

A156B

A156

A156F

123 123A 123B 123C

189190

BC

B

G

106107

A156D

STR #1

STR #2

UP

UP

DN

CODE CRITERIA

GENERAL: THIS SUMMARY OF CODE REQUIREMENTS IS BASED PRIMARILY ON NFPA 101 (LSC). DESIGN FEATURES NOT ADDRESSED BY NFPA 101 OR DOCUMENTS REFERENCED THEREIN SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE IBC OR AS OTHERWISE IDENTIFIED.

FOR DESIGN FEATURES THAT ARE ADDRESSED BY BOTH THE IBC AS WELL AS NFPA 101 OR A DOCUMENT REFERENCED BY NFPA 101, NFPA 101

SHALL BE USED EXCLUSIVELY IN INSTANCES OF CONFLICT.

LOCAL CODES: AS AN AGENCY OF THE FEDERAL GOVERNMENT, THE VA IS NOT SUBJECT TO LOCAL IMPOSITION OF CODE ENFORCEMENT PROCEDURES (DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS, FEES, ETC.). VA MUST FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ) AND THUS HAS THE RESPONSIBILITY TO GUARD PUBLIC HEALTH AND SAFETY THROUGH ENFORCING ITS ADOPTED CODES.

NOTES:

CONFLICTS BETWEEN NATIONALLY RECOGNIZED CODES AND STANDARDS AND VA REQUIREMENTS – SHOULD A CONFLICT EXIST BETWEEN VA REQUIREMENTS AND VA ADOPTED NATIONALLY RECOGNIZED CODES AND STANDARDS, THE CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF VA. THE RESOLUTION OF THE CONFLICT SHALL BE MADE BY THE AUTHORITY HAVING JURISDICTION FOR VA TO ENSURE A CONSISTENCY SYSTEM

WIDE.

CODE REVIEW

THE 2015 EDITION OF THE LIFE SAFETY CODE, NFPA 101, HAS BEEN USED TO REVIEW THIS PROJECT FOR COMPLIANCE WITH THE FIRE AND LIFE SAFETY REQUIREMENTS. FOR FEATURES NOT ADDRESSED BY NFPA 101 AND THE REFERENCED NATIONAL FIRE CODES, THE 2015 EDITION OF THE

INTERNATIONAL BUILDING CODE HAS BEEN USED.

PROJECT SCOPE

THE PROJECT SCOPE INCLUDES THE BUILDING OF A FIRST FLOOR ADDITION OVER A BASEMENT WHICH ACCOMMODATES A STERILE PROCESSING DEPARTMENT. THE ADDITION SHALL BE AN EXPANSION OF THE EXISTING OUTPATIENT PRIMARY CARE CLINIC. THE EXPANDED SPACE SHALL BE A BUSINESS OCCUPANCY, BUT THE OVERALL CONSTRUCTION SHALL ALIGN WITH I-2, INSTITUTIONAL OCCUPANCY REQUIREMENTS. THERE IS ONE WAITING AREA WITH AN OCCUPANCY COUNT OVER 50, WHICH WILL BE REVIEWED AS AN A-ASSEMBLY OCCUPANCY. OVERALL BUILDING INFRASTRUCTURE AND SYSTEMS SHALL BE MAINTAINED TO COMPLY WITH HEALTHCARE CHAPTER 19 AND IBC 2015.

THE CONSTRUCTION TYPE IS DETERMINED BASED UPON THE ALLOWABLE AREA AND HEIGHT REQUIREMENTS OF CHAPTER 5 OF THE 2015 IBC.

CONSTRUCTION TYPE AND MATERIALS SHALL BE PER CHAPTER 6 OF THE IBC FOR TYPE I-B CONSTRUCTION AS FOLLOWS:

1.OCCUPANCY TYPE:

EXISTING HOSPITAL: I-2 HOSPITAL OCCUPANCY IBC CHAPTER 3, HEALTHCARE LSC CHAPTER 18

BUILDING EXPANSION FLOOR 1: B BUSINESS IBC CHAPTER 3, BUSINESS LSC CHAPTER 38.

2.CONSTRUCTION TYPE:

EXISTING HOSPITAL: I-B (IBC CHAPTER 5), TYPE II (222) (LSC)

PROJECT SCOPE: I-B (IBC CHAPTER 5), TYPE II (222) (LSC)

3. FIRE RESISTIVE RATINGS TYPE IB/ I(222) CONSTRUCTION, CHAPTER 6 IBC/NFPA 101:

STRUCTURAL FRAME: NONCOMBUSTIBLE, 2-HOUR FIRE RESISTIVE

BEARING WALLS

EXTERIOR: NONCOMBUSTIBLE, 2 HOUR FIRE RESISTIVE

INTERIOR: NONCOMBUSTIBLE, 2-HOUR FIRE RESISTIVE

NON-BEARING WALLS AND PARTITIONS

EXTERIOR: NONCOMBUSTIBLE, 0-1-HOUR FIRE RESISTIVE

INTERIOR: NONCOMBUSTIBLE, 0 HOUR FIRE-RESISTIVE

FLOOR: NONCOMBUSTIBLE, 2-HOUR FIRE RESISTIVE

ROOF: NONCOMBUSTIBLE, 1-HOUR FIRE RESISTIVE

SHAFT ENCLOSURES 2-HOUR FIRE RESISTIVE (IBC 602.2) >4 STORIES (5 TOTAL STORIES PLANNED FOR FUTURE)

4. STRUCTURAL DESIGN SHALL COMPLY WITH CHAPTER 16 OF THE IBC 2015.

5. ALLOWABLE HEIGHT: 180 FT (IBC, TABLE 504.3)

6. ALLOWABLE NUMBER OF STORIES ABOVE GRADE PLAN: 5 (IBC, TABLE 504.4)

7. ALLOWABLE AREA: BASED UPON I-B I-2 OCCUPANCY AND NON-COMBUSTIBLE, TYPE I-B FULLY SPRINKLED: ALLOWABLE AREA: 45,000 (IBC, TABLE 506.2)

8. NO BUILDING SEPARATION IS CREATED OR MODIFIED.

9. OCCUPANCY SEPARATION: A 2 HOUR OCCUPANCY SEPARATION IS REQUIRED BETWEEN THE CLINIC SUITE AND MAIN HOSPITAL.

10. MEANS OF EGRESS SECTION.

• CLEAR WIDTH OF CORRIDORS SHALL BE CLEAR 44 INCHES.

• CLEAR WIDTH OF DOORS SHALL BE CLEAR 32 INCHES

• NOT LESS THAN 2 EXITS SHALL BE PROVIDED PER FLOOR.

• ADDITION OCCUPANCY LOAD: <500 THEREFORE 2 EXITS REQUIRED

• MAXIMUM TRAVEL DISTANCE: 300 FEET, (INCLUDES ADDITIONAL 50 FEET DUE TO AREA BEING PROTECTED BY A FIRE SPRINKLER SYSTEM)

• COMMON PATH OF TRAVEL SHALL NOT EXCEED 100 FEET

• DEAD END CORRIDORS SHALL NOT EXCEED 50 FEET.

• MEANS OF EGRESS SHALL BE ILLUMINATED BY EMERGENCY LIGHTING.

REFER TO VA MANUAL PG-18-3 FOR ADDITIONAL CODES, STANDARDS, GUIDELINES AND

REGULATIONS. BELOW LISTING IS NOT COMPREHENSIVE.

ICC, INTERNATIONAL BUILDING CODES, 2015 EDITION (IBC)

ASCE-07-10

ACI 318-11

ACI 530-11

AISC 341-10

AISC 360-10

PCI MNL 120-10, DESIGN HANDBOOK

NFPA 10, STANDARD FOR PORTABLE FIRE EXTINGUISHERS, 2013 EDITION

NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2013 EDITION

NFPA 14, STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE SYSTEM,

2016 EDITION

NFPA 20, STANDARD FOR THE INSTALLATION OF STATIONARY PUMPS FOR FIRE

PROTECTION, 2016 EDITION

NFPA 24, STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND

THEIR APPURTENANCE, 2016 EDITION.

NFPA 54 NATIONAL FUEL GAS CODE, 2015 EDITION

NFPA 70, NATIONAL ELECTRIC CODE, 2014 EDITION

NFPA 72, NATIONAL FIRE ALARM CODE, 2016 EDITION

NFPA 75, STANDARD FOR THE PROTECTION OF ELECTRICAL COMPUTER/DATA

PROCESSING EQUIPMENT, 2017 EDITION

NFPA 77, RECOMMENDED PRACTICE ON STATIC ELECTRICITY, 2014 EDITION

NFPA 80, STANDARD FOR FIRE DOORS AND FIRE WINDOWS, 2016 EDITION

NFPA 90A, STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND

VENTILATING SYSTEMS, 2015 EDITION.

NFPA 92, STANDARD FOR SMOKE CONTROL SYSTEMS, 2015 EDITION

NFPA 96

NFPA 99, STANDARD FOR HEALTHCARE FACILITIES, 2015 EDITION

NFPA,99B, STANDARD FOR HYPOBARIC FACILITIES, 2015 EDITION

NFPA 101, LIFE SAFETY CODE, 2015 EDITION

NFPA 110, STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS

NFPA 220, STANDARD TYPES OF BUILDING CONSTRUCTION, 2015 EDITION.

NFPA 241, STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION, &

DEMOLITION OPERATIONS, 2013 EDITION

NFPA 780, STANDARD FOR INSTALLATION OF LIGHTING PROTECTION SYSTEMS,

2017 EDITION

ASHRAE 0 - 2005 COMMISSIONING PROCESS

ASHRAE 1.1 - 2007 HVAC & R TECHNICAL REQUIREMENTS FOR COMMISSIONING PROCESS

ASHRAE 55- 2004 THERMAL ENVIRONMENTAL CONDITIONS FOR HUMAN OCCUPANCY

ASHRAE 62.1 - 2007 VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY

ASHRAE 90.1-2007 HVAC SYSTEMS

ASHRAE 180 - 2009 VENTILATION FOR HEALTH CARE FACILITIES

ANSI A117.1-2009 STANDARD ON ACCESSIBLE & USABLE BUILDINGS AND FACILITIES

ADA ACCESSIBILITY GUIDELINES (ADAAG), 2004

ADA STANDARDS FOR ACCESSIBLE DESIGN, 2010

MOST RECENT EDITION OF NFPA NATIONAL FIRE CODES WITH THE EXCEPTION OF

NFPA 5000 AND NFPA 900

OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS

ENERGY POLICY ACT OF 2005 (EPACT)

EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL ENVIRONMENTAL,

ENERGY, AND TRANSPORTATION MANAGEMENT.

GOVERNING CODESCODE ANALYSIS - NFPA 101, CHAPTER 38 FOR CLINIC, CHAPTER 19 FOR BUILDING

11. PROTECTION FROM ANY AREA HAVING A DEGREE OF HAZARD GREATER THAN THAT NORMAL TO THE GENERAL OCCUPANCY OF THE BUILDING OR STRUCTURE SHALL BE PROVIDED BY PROTECTING THE AREA WITH AUTOMATIC EXTINGUISHING SYSTEMS IN ACCORDANCE WITH SECTION 9.7(3). WHERE HAZARD IS SEVERE PER LSC CHAPTER 38, SUCH AS SOILED HOLDING, PROTECTION IS PROVIDED WITH AN AUTOMATIC EXTINGUISHING SYSTEM. THE SPACE SHALL ALSO BE ENCLOSED WITH SMOKE PARTITIONS IN ACCORDANCE WITH SECTION 8.4.

12. THE EXIT FOR EXISTING STAIR 1-B-ST3 WILL NO LONGER DISCHARGE DIRECTLY OUTSIDE THE BUILDING. PER LSC SECTION 7.7.2. THIS STAIR IS REQUIRED FOR EXITING FROM THE 5TH FLOOR AS THIS IS THE ONLY STAIR ON THIS, THE EAST SIDE OF THE BUILDING ON THE 5TH FLOOR.

THE EXIT FOR EXISTING STAIR 1-B-ST3 IS SHOWN TO DISCHARGE THROUGH INTERIOR BUILDING AREAS (THE LOBBY AREA) OF THE PRIMARY

CARE ADDITION AND WILL MEET THE FOLLOWING PROVISIONS:

- 7.7.2 EXIT DISCHARGE THROUGH INTERIOR BUILDING AREAS EXITS SHALL BE PERMITTED TO DISCHARGE THROUGH

INTERIOR BUILDING AREAS, PROVIDED THAT THE ALL THE FOLLOWING ARE MET:

(1) NOT MORE THAN 50% OF THE REQUIRED NUMBER OF EXITS, AND NOT MORE THAN 50% OF THE REQUIRED EGRESS CAPACITY, SHALL DISCHARGE THROUGH INTERIOR AREAS ON ANY LEVEL OF DISCHARGE.

(2) EACH LEVEL OF DISCHARGE SHALL DISCHARGE DIRECTLY OUTSIDE AT THE FINISHED GROUND LEVEL OR DISCHARGE DIRECTLY OUTSIDE AND PROVIDE ACCESS TO THE FINISHED GROUND LEVEL BY OUTSIDE STAIRS

OR OUTSIDE RAMPS.

(3) THE INTERIOR EXIT DISCHARGE SHALL LEAD TO A FREE AND UNOBSTRUCTED WAY TO THE EXTERIOR OF THE BUILDING, AND SUCH WAY SHALL BE READILY VISIBLE AND IDENTIFIABLE FROM THE POINT OF DISCHARGE

FROM THE EXIT.

(4) THE INTERIOR EXIT DISCHARGE SHALL BE PROTECTED BY THE FOLLOWING METHOD: (A) THE LEVEL OF DISCHARGE SHALL BE PROTECTED THROUGHOUT BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM IN

ACCORDANCE WITH SECTION 9.7.

(5) THE ENTIRE AREA ON THE LEVEL OF DISCHARGE SHALL BE SEPARATED FROM AREAS BELOW BY CONSTRUCTION HAVING A FIRE RESISTANCE RATING NOT LESS THAN THAT REQUIRED FOR THE EXIT

ENCLOSURE. FOR THIS PROJECT, THIS IS A 2-HOUR RATING.

IN ADDITION, THE BASEMENT FLOOR UP THROUGH FLOOR 4 DO NOT EXCEED THE 50% LIMIT TO NUMBER OF EXITS OR EGRESS CAPACITY AS

INDICATED IN NFPA 101 7.7.2 (1).

13. INTERIOR FINISH, SECTION. WALLS AND CEILINGS: INTERIOR FINISH FLAME SPREAD SHALL BE LIMITED PER CHAPTER 8 OF THE NFPA 101 TO CLASS A, B AND C MATERIALS. INTERIOR WALL AND CEILING FINISH SHALL BE CLASS A OR CLASS B IN EXITS, CORRIDORS AND LOBBIES; AND

CLASS A, CLASS B, OR CLASS C IN ALL OTHER AREAS.

- CLASS A: FLAME SPREAD 0-25; SMOKE DEVELOPED 0-450.

- CLASS B: FLAME SPREAD 26-75; SMOKE DEVELOPED 0-450.

- CLASS C: FLAME SPREAD 76-200; SMOKE DEVELOPED 0-450

FLOORS: INTERIOR FLOOR FINISH SHALL BE CLASS I OR CLASS II IN CORRIDORS AND EXITS.

FABRIC DRAPERIES, CURTAINS (EXCLUDING SHOWER CURTAINS, BUT INCLUDING CUBICLE CURTAINS), AND OTHER LOOSELY HANGING FABRICS AND FILMS SERVING AS FURNISHINGS OR DECORATIONS IN HEALTH CARE OCCUPANCIES MUST MEET THE FLAME

RESISTANCE REQUIREMENTS OF NFPA 701, STANDARD METHODS OF FIRE TESTS FOR FLAME-RESISTANT TEXTILES AND FILMS.

UPHOLSTERED FURNITURE AND MATTRESSES. UPHOLSTERED FURNITURE AND MATTRESSES MUST ALSO MEET SPECIFIED REQUIREMENTS, BASED ON NFPA 260, NFPA 261, NFPA 266, 16 CFR 1632, ASTME E1537, AND ASTME E1590

14. EXTINGUISHMENTS REQUIREMENTS, PORTABLE FIRE EXTINGUISHERS SHALL BE PROVIDED PER NFPA 10.

15. DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.

• FIRE ALARM SYSTEM SHALL BE PROVIDED. THE SYSTEM SHALL BE BY MANUAL MEANS.

• OCCUPANT NOTIFICATION SHALL BE THROUGH AUTOMATIC MEANS.

• SMOKE DETECTION SHALL BE PROVIDED PER NFPA 72.

• FIRE ALARM CONTROL PANEL MUST BE FROM THE LIFE SAFETY PANEL

• EMERGENCY RESPONDER NOTIFICATION SHALL BE NOTIFIED BY ALARM AND DETECTION SYSTEM.

16. FIRE SUPPRESSION/SPRINKLER SYSTEM: BUILDING IS REQUIRED TO BE SPRINKLED THROUGHOUT IN ACCORDANCE WITH NFPA 13.

THE SPRINKLER SYSTEM SHALL BE HYDRAULICALLY DESIGNED IN ACCORDANCE WITH 2013 EDITION OF NFPA 13 AND THE SIXTH EDITION OF THE DEPARTMENT OF VETERANS AFFAIRS FIRE PROTECTION DESIGN MANUAL: MINIMUM DESIGN REQUIREMENTS:

STORAGE MECHANICAL AND ELECTRICAL ROOMS SHALL BE PROTECTED AS:

ORDINARY HAZARD OCCUPANCY, GROUP 1: 0.15 GPM/FT2 OVER 1,500 FT2.

HOSE STREAM ALLOWANCE: 250 GPM

ALL OTHER AREAS SHALL BE PROTECTED AS:

LIGHT HAZARD OCCUPANCY: 0.10 GPM/FT2 OVER 1,500 FT2.

HOSE STREAM ALLOWANCE: 100 GPM

ALL SPRINKLERS WITHIN THE SMOKE ZONE SHALL BE QUICK RESPONSE SPRINKLERS.

17. CONSTRUCTION BARRIERS CONSTRUCTED ALONG MEANS OF EGRESS SHALL BE CONSTRUCTED AND MAINTAINED PER NFPA 241.

18. REQUIRED EGRESS CAPACITY IS BASED ON OCCUPANT LOAD PER EXIT. 475 TOTAL OCCUPANTS / 4 EXITS (2 HORIZONTAL EXITS, 2 STAIR

EXITS) = 119 OCCUPANTS PER EXIT.

IBC 1005.3.1 EXCEPTION FOR GROUP B AND FULLY SPRINKLED: STAIRWAY CAPACITY REQUIRED = 119 OCCUPANTS X 0.2" = 23.8" (1'-

11.8") STAIRWAY CAPACITY AVAILABLE >3'-0".

IBC 1005.3.2 EXCEPTION FOR GROUP B AND FULLY SPRINKLED: OTHER EGRESS COMPONENT CAPACITY REQUIRED = 119

OCCUPANTS X 0.15 = 17.85" (1'-5.85")

OTHER EGRESS COMPONENT CAPACITY >6'-0"

20005 SF

100201

B

2572 SF

15171

A CLINIC

WAITING

FECFEC

EXIT

EXIT

EXIT

EXIT

EXIT

EXIT

DIAGONAL DISTANCE = 263' -0 1/2"

EXIT SEPARATION DISTANCE = 157'-8"

EG

RES

S T

RAVE

L

DIS

TA

NCE

1' -9

PRIMARY CARE SUITE BOUNDARY

ELECTRICAL

1-C-140

DW

1-C-123

STAIRS

1-C-ST2

MED ROOM 1

1-C-124

TEAM ROOM

(FUTURE ELEV.)

1-C-EL3

TRAINING ROOM

EXAM 34

158A

HYBRID 33

158CONSULT 32

HYBRID 31

CONSULT 30

EXAM 29

154A

HYBRID 28

CONSULT 26

1-C-144

INTAKE 3

P. TOILET 3

SOILED UTILITY

162A

EQUIP STORAGE 3

STAIR

1E-1E

CLEAN UTILITY 2

CONSULT 35

PROCEDURE 2

PR. TOILET

167A

PROCEDURE 1

TELEDERM

169A

TELERETINAL

TELEHEALTH

SHARED MED APP

STORAGE

SHARED GROUP

ROOM 2

175A

NURSE MANAGER

MECHANICAL

PATIENT EDUCATION

STAIR

1-B-ST3

PATIENT CORR. 3

1E-3

STAIRS

1-C-ST1

SMALL

CONFERENCE

STAFF LOUNGE

MEN'S TESTING

138B

ELIGIBILITY

138A

PATIENT

REGISTRATION

MED ROOM 3

P. TOILET 2

1-C-132

DW

1-C-133

EXAM 21

1-C-136

EXAM 22

1-C-137

CONSULT 27

CLEAN UTILITY 1

1-C-145

EXAM 25

1-C-143

EXAM 24

1-C-142

HYBRID 23

1-C-138

EXAM 15

1-C-125EXAM 14

1-C-126

HYBRID 13

1-C-127

EXAM 12

1-C-128

CONSULT 11

1-C-129

OIT

1-C-139

INTAKE 2

1-C-130

CONSULT 19

1-C-119

CONSULT 18

1-C-120

CONSULT 17

1-C-121

CONSULT 16

1-C-122

TEAM ROOM

HYBRID 36

EQUIP. STOR.

1-C-118

INTAKE 1

1-C-103

MULTIPURPOSE

1-C-115

STAFF LOUNGE

1-C-116

M. STAFF TOILET

1-C-146

W. STAFF TOILET

1-C-147

OPEN OFFICE

1-C-117

OPEN OFFICE

1-C-148

PATIENT CORR. 1

1-C-C1

PATIENT CORR. 2

1-C-C2

RECEPTION

1-C-102

FAMILY TOILET

VESTIBULE

1-C-100

CORRIDOR

1E-1

CORRIDOR

1E-4

EXAM 37

HYBRID 7

1-C-111

HYBRID 4

1-C-107

EXAM 8

1-C-112

P. TOILET 1

1-C-110

EXAM 6

1-C-109

EXAM 5

1-C-108

EXAM 3

1-C-106

NEG. PRESSURE

HYBRID 1

1-C-104

EXAM 10

1-C-114

EXAM 9

1-C-113

EXAM 2

1-C-105

GENERATOR BUILDING 16

EGRESS TRAVEL DISTANCE 187' EGRESS TRAVEL DISTANCE 61'

WOMEN'S PUBLIC

TOILET

MEN'S PUBLIC

TOILET

EXIT

EXIT

EXIT

EXIT

176A

178101

LOCKERS

A169

FA

100A

MULTI-PURPOSE

WAITING

1-C-101

CONCIERGE

1-C-101A

KIOSKS

1-C-101C

COFFEE

1-C-101D

TEAM ROOM

(FUTURE ELEV.)

1-C-EL1-2

EGRESS CORRIDOR

1-C-C4

285 SF

A

327 SF

A

303 SF

A

514 SF

A

TEMPORARY FLOOR WILL NOT BE

RATED DUE TO RATING OF WALLS

AND DOOR OPENING

BASEMENT EXIT BELOW

TO GROUND LEVEL

PROVIDES DIRECT

DISCHARGE

BASEMENT

EXIT DOORS TO

GROUND LEVEL DOES

NOT PROVIDE DIRECT DISCHARGE

EXIT TO

GROUND LEVEL PROVIDES

DIRECT DISCHARGE

TABLE 7.2.2.2.1.2 OCCUPANCY LOAD

FOR OVERALL BUILDING EXPANSION

<20000 PERSONS PER FLOOR. STAIR

WIDTH REQUIREMENTS 44"

EXISTING FIRST FLOOR PER VA STATEMENT OF

CONDITIONS B-BUSINESS OCCUPANCY

FUTURE HAC

148A

CORRIDOR

1-C-C5

HYBRID 20

1-C-135

MED ROOM 2

1-C-141

STAFF CORR.

1-C-C3

STORAGE

1-C-134WAITING

FEC

FECFEC

FEC

FEC

FEC TEMPORARY FLOOR

WILL NOT BE RATED

DUE TO RATING OF

WALLS AND DOOR

OPENING

UTILITY SHAFT

RELIEF AIR CHASE

SHARED GROUP

ROOM

CODE ANALYSIS LEGEND

TOTAL OCCUPANCY

FEC

EXIT

OCCUPANCY LOAD FACTOR

EXITS REQUIRED

SQUARE FOOTAGE

OCCUPANCY TYPE

EXIT ACCESS

FIRE EXTINGUISHER AND CABINET

DIAGONAL DISTANCE

EXIT SEPARATION DISTANCE

EGRESS PATH

2 HR - FIRE SEPARATION

1 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREA

B

1500 SF

BEYOND PRIMARY PROJECT SCOPE

BOUNDARY, THOUGH WORK MAY NEED

TO BE COMPLETED IN THIS AREA TO

ACCOMMODATE PRIMARY SCOPE.

INDICATED WORK IN DRAWINGS AND

DETAILS IN THIS AREA SHALL BE

COMPLETED BY THE VA - N.I.C.

PRIMARY CARE SUITE BOUNDARY

AREA OF 1ST FLOOR

PRIMARY CARE

EXPANSION

GENERATOR BUILDING 16

HOSPITAL BUILDING 1

1 EAST WING

N

EXISTING PRIMARY CARE

MAIN

ENTRANCE

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked By:

Building Number

Project Number

Drawing Number

Drawn By:

Revisions: Date

ARCHITECT/ENGINEERS:

VA NORTHERN INDIANA - FW

#1 o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

JAMES A. BROYLES, COR 610-311

GUIDON DESIGN INC.

905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204

317.800.6388 | WWW.GUIDONDESIGN.COM

SUSTAINABLE ARCHITECTURE + ENGINEERING

PROJECT LEAD

Architect, Structural and Civil Engineer

VA NORTHERN INDIANA HEALTH CARE SYSTEM

FORT WAYNE CAMPUS

FORT WAYNE, INDIANA

MEP Engineer

4031 TRANSPORTATION DR.

FORT WAYNE, IN 46818

(260) 918-3045

DESIGN-AIRE ENGINEERING, INC.

220 N COLLEGE AVE

INDIANAPOLIS, IN 46202

(317) 464-9090

Commissioning Agent

C U s e rs

\t s a n d e rs

\D o c u m e n ts

\1 .1

F W

P ri m a ry

C a re ts a n d e rs g u id o n d e s ig n .c o m

.r v t

CONSTRUCTION DOCUMENTS

GI102

TSKA/JG

1ST FLOOR LIFE SAFETY FLOOR PLAN

2019/4/16

16.1045EXPAND BUILDING 1 - 1ST FLOOR

PRIMARY CARE

LIFE SAFETY OCCUPANCY COUNT

AREA SF OCC OCC FACTOR # OF OCC

FIRST FLOOR LEVEL

CLINIC 20005 SF B 100 201

WAITING 2572 SF A 15 171

SM. CONFERENCE 285 SF A 15 19

SHARED GROUP RM 1 327 SF A 15 22

SHARED GROUP RM 2 303 SF A 15 21

MULTIPURPOSE 514 SF A 15 35

24006 SF 469

24006 SF 469PRIMARY CARE SUITE TOTAL:

SCALE: 1/16" = 1'-0"GI102

1 1ST FLOOR LIFE SAFETY FLOOR PLAN

SCALE: 1" = 100'-0"

KEY PLANN

GROSS ADDITION TOTAL: 16,213 SF

TOTAL DOOR WIDTH CAPACITY = 475 PERSONS OVERALL CLINIC X 0.2 EQUALS 95"

DOOR WIDTH PROVIDED 60" + 36" + 36" = 132"

DN

CONTINUOUS FIRESAFE SEALANT

TOP AND BOTTOM, & BOTH SIDES

3 1/2" SOUND ATTENUATION BATT

5/8" TYPE X GYPSUM BOARD, JOINTS

SEALED WITH FIRE TAPE, BOTH SIDES

3 5/8" METAL STUD @ 16" O.C. WITH

RUNNER CHANNELS FASTENED

ALONG TOP AND BOTTOM

CONSTRUCTION

SIDE

PUBLIC

SIDE

UNDERSIDE OF STRUCTURAL DECK

UL LISTING: U465

COORDINATE WITH EXISTING

CEILING

PUBLIC

SIDE

45 MIN. FIRE RATED METAL DOOR

ASSEMBLY AND FRAME WITH SEALS,

CARD READER AND HARDWARE

TRIATEK MONITOR

HAND SANITIZER

SEAL ALL EDGES TO PROHIBIT THE

MIGRATION OF DUST, DIRT, AIR, AND

ODORS

SEAL ALL EDGES TO PROHIBIT THE

MIGRATION OF DUST, DIRT, AIR, AND

ODORS

REFER TO TEMPORARY BARRIER TYPE FOR

REQUIRED CONDITION TO STRUCTURE

ABOVE

VA / OSHA TEMPORARY SIGNAGE

MED ROOM 2

1-C-141

ELECTRICAL

1-C-140

DW

1-C-123

STAIRS

1-C-ST2

TEAM ROOM

(FUTURE ELEV.)

1-C-EL3

TRAINING ROOM

EXAM 34

158A

HYBRID 33

CONSULT 32

HYBRID 31

CONSULT 30

EXAM 29

154A

HYBRID 28

CONSULT 26

1-C-144

INTAKE 3

P. TOILET 3

SOILED UTILITY

162A

EQUIP STORAGE 3

STAIR

1E-1E

CLEAN UTILITY 2

CONSULT 35

PROCEDURE 2

PR. TOILET

167APROCEDURE 1

TELEDERM

169A

TELERETINAL

TELEHEALTH

SHARED MED APP

STORAGE

NURSE MANAGER

MECHANICAL

PATIENT EDUCATION

STAIR

1-B-ST3

PATIENT CORR. 3

1E-3

STAIRS

1-C-ST1

SMALL

CONFERENCE

STAFF LOUNGE

MEN'S TESTING

138B

ELIGIBILITY

138A

176A

MED ROOM 3

P. TOILET 2

1-C-132

DW

1-C-133

EXAM 21

1-C-136

EXAM 22

1-C-137

CONSULT 27

CLEAN UTILITY 1

1-C-145

EXAM 25

1-C-143

EXAM 24

1-C-142

HYBRID 23

1-C-138

EXAM 15

1-C-125

EXAM 14

1-C-126

HYBRID 13

1-C-127

EXAM 12

1-C-128

CONSULT 11

1-C-129

OIT

1-C-139

INTAKE 2

1-C-130

CONSULT 19

1-C-119

CONSULT 18

1-C-120

CONSULT 17

1-C-121

CONSULT 16

1-C-122

MED ROOM 1

1-C-124

TEAM ROOM

HYBRID 36

EQUIP. STOR.

1-C-118

INTAKE 1

1-C-103

MULTIPURPOSE

1-C-115

STAFF LOUNGE

1-C-116

M. STAFF TOILET

1-C-146

W. STAFF TOILET

1-C-147

OPEN OFFICE

1-C-117

OPEN OFFICE

1-C-148

PATIENT CORR. 1

1-C-C1

PATIENT CORR. 2

1-C-C2

RECEPTION

1-C-102

FAMILY TOILET

VESTIBULE

1-C-100

BOUNDARY OF PRIMARY

CARE SUITE

GENERATOR BUILDING 16

NEG. PRESSURE

HYBRID 1

1-C-104

EXAM 2

1-C-105

EXAM 3

1-C-106

HYBRID 4

1-C-107

EXAM 5

1-C-108

EXAM 6

1-C-109

P. TOILET 1

1-C-110

HYBRID 7

1-C-111

EXAM 8

1-C-112

EXAM 9

1-C-113

EXAM 10

1-C-114

CORRIDOR

1E-4

EXAM 37

SHARED GROUP

ROOM 2

175A

CORRIDOR

1E-1

MEN'S PUBLIC

TOILET

WOMEN'S PUBLIC

TOILET

WORK SHOWN IN THIS

AREA BY VA - NOT IN

CONTRACT

WORK SHOWN IN THIS

AREA BY VA - NOT IN

CONTRACT

TEAM ROOM

(FUTURE ELEV.)

1-C-EL1-2

EGRESS CORRIDOR

1-C-C4

WAITING

WAITING

1-C-101

COFFEE

1-C-101D

CONCIERGE

1-C-101A

KIOSKS

1-C-101C

HYBRID 20

1-C-135

STAFF CORR.

1-C-C3

WORK SHOWN IN THIS

AREA BY VA - NOT IN

CONTRACT

STORAGE

1-C-134

FUTURE HAC

148A

5 5

DO NOT UTILIZE ANY PORTION

OF THE EXISTING VA BUILDING

TO MOVE LABOR OR

MATERIALS THROUGH

2B2A 2C

UTILITY

SHAFT

RELIEF AIR

CHASE

1 1

TYP. TYP. TYP. TYP.

SHARED GROUP

ROOM

1 1

2 2

4'-0" MIN.

INFECTION CONTROL PLAN NOTES #

INFECTION CONTROL PROJECT INFORMATION

CONSTRUCTION ACTIVITY - FIRE RISK: D

PATIENT RISK GROUP: HIGHEST

CLASS OF PRECAUTION MATRIX: IV

PROVIDE IC TEMPORARY BARRIER WALL CONSTRUCTION PER NFPA 241. REFER

TO DETAILS 2/GI102 AND 3/GI102.

PROVIDE IC TEMPORARY CONSTRUCTION DOOR WITH CARD READER ACCESS.

REFER TO ELEVATION 3/GI103. ACCESS CONTROL IS NOT A PART OF AND IS NOT

CONNECTED TO VA PACS/PIN SYSTEM.

DOOR OPENING SHALL BE CUT AND INSTALLED DURING OFF HOURS SUCH THAT

ROOMS REMAIN OPERATIONAL THROUGHOUT CONSTRUCTION.

INTENT IS THAT ABOVE CEILING WORK IN STERILE PROCESSING STORAGE IN

BASEMENT IS MINIMIZED.

TEMPORARY WALLS IN EXISTING EXAM ROOMS SHALL BE ALIGNED WITH

BULKHEAD ABOVE SUCH THAT ACOUSTIC CEILING GRID IS UNAFFECTED AND

ENCROACHMENT INTO OPERATIONAL ROOMS IS MINIMIZED, TYPICAL.

1.

2.

3.

4.

5.

REFER TO DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.

COORDINATE FULL SCOPE OF WORK WITH ENGINEERING DRAWINGS AND FIELD

VERIFICATION. CONTRACTOR IS RESPONSIBLE FOR SCOPE OF ABOVE CEILING

WORK REQUIRED ON THE 1ST FLOOR AND ON THE LOWER LEVEL.

COORDINATE LOCATION OF TEMPORARY INFECTION CONTROL (IC) BARRIER WALL

CONSTRUCTION AND INFECTION CONTROL (IC) MEASURES WITH COR AND

PATIENT SAFETY/ INFECTION CONTROL REPRESENTATIVE. TEMPORARY IC

BARRIER WALL CONSTRUCTION LOCATIONS IN DRAWINGS ARE APPROXIMATE.

CONTRACTOR SHALL PROVIDE DRAWING TO COR AND PATIENT SAFETY/

INFECTION CONTROL REPRESENTATIVE ONCE ICRA PROTOCOLS AND PLAN IS IN

PLACE.

PROVIDE A 24"X36" STICKY WALK OFF MAT AND HAND SANITIZER AT EACH

TEMPORARY DOOR LOCATION. MAT SHALL BE REPLACED OR CLEANED AS

DIRECTED BY VA.

PROVIDE THE REQUIRED VA AND OSHA TEMPORARY SIGNAGE AT EACH

TEMPORARY DOOR LOCATION.

CONTRACTOR SHALL SUPPLY SPILL KIT. SPILL KIT TO INCLUDE SHOP VAC, MULTI-

PURPOSE SPILL CONTROL SORBENTS TO ABSORB NON AGGRESSIVE LIQUIDS UP

TO 30 GALLONS.

THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING INGRESS/EGRESS TO THE

PROJECT AREA FROM THE EXTERIOR OF THE BUILDING AND WILL NOT BE

PERMITTED TO UTILIZE ANY PORTION OF THE EXISTING VA BUILDING TO MOVE

LABOR OR MATERIALS THROUGH.

- ALL NEW MATERIAL TRANSPORTED WITHIN EXISTING 1-EAST

SHALL BE COVERED WITH 4 MIL. POLY SHEET.

-FOR DEMOLITION MATERIAL REMOVED FROM EXISTING 1-EAST,

ROUTE SHALL BE VA APPROVED, IN ENCLOSED DUMPSTER CART

DESIGNED FOR SUCH PURPOSE, WITH A LID.

ALL MATERIAL, DEBRIS AND HAZARDOUS MATERIALS SHALL BE PROPERLY

STORED IN DESIGNATED AREAS AND APPROVED CONTAINERS. FLAMMABLE

MATERIALS SHALL NOT BE STORED IN THE FACILITY.

PROVIDE CONTAINMENT CART FOR ABOVE CEILING ACCESS OUTSIDE THE

INDICATED PHASE BOUNDARY.

ASBESTOS ABATEMENT: REVIEW THE 'Ft. Wayne VAMC Asbestos Reinspection

2016' DOCUMENT PROVIDED WITH THE CONSTRUCTION DOCUMENTS FOR

EXTERIOR WINDOW CAULK ASSUMED TO CONTAIN ASBESTOS. REFER TO

SPECIFICATIONS FOR ADDITIONAL INFORMATION.

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

INFECTION CONTROL GENERAL NOTES

REFERS TO SHEETS GI101 AND GI103

REFERS TO SHEETS GI101 AND GI103

INFECTION CONTROL AND PHASING LEGEND

TEMPORARY WALLS TO BE PROVIDED AS A

BARRIER BETWEEN AREAS OF WORK AND

OCCUPIED PORTIONS OF THE BUILDING. SEE

PLAN AND PLAN NOTES

TEMPORARY CONSTRUCTION ACCESS

DOORS

BEYOND PRIMARY PROJECT SCOPE

BOUNDARY. REFER TO DRAWINGS AND

DETAILS FOR WORK REQUIRED IN THIS AREA.

PRIMARY CARE SUITE BOUNDARY

AREA OF PHASE 1 WORK. THE MAIN BODY OF

WORK SHALL BE COMPLETED DURING PHASE 1

INCLUDING THE 1ST FLOOR ADDITION.

WORK SHOWN IN THIS AREA BY VA - NOT IN CONTRACT

PHASING GENERAL NOTES

A.

B.

C.

D.

E.

F.

G.

H.

PROJECT SHALL BE COMPLETED IN 2 MAIN PHASES. SEE INFECTION CONTROL /

PHASING FLOOR PLAN FOR LOCATIONS.

SCHEDULE AND TIME OF CONSTRUCTION WORK FOR ALL PHASES SHALL BE

APPROVED BY COR AND NURSING STAFF BEFORE CONSTRUCTION MAY BEGIN.

PROVIDE PHASING INFORMATION FOR ABOVE CEILING WORK IN THE CONTRACTOR

PROVIDED CMP SCHEDULE. THIS INCLUDES WORK REQUIRED ABOVE AND BELOW

THE FLOOR PLAN OF THE PROJECT BOUNDARY.

ABOVE CEILING WORK OUTSIDE OF INDICATED PROJECT BOUNDARY AND IN THE

BASEMENT IS REQUIRED - COORDINATE WORK RESTRICTIONS WITH VA. CEILING

TILES SHALL BE REMOVED AND STORED IN A SAFE MANNER UNTIL CEILING TILES

CAN BE REINSTALLED. DAMAGED AND BROKEN CEILING TILES SHALL BE REPLACED

BY CONTRACTOR. FOR WORK IN VA OCCUPIED SPACES, CONTRACTOR SHALL

REPLACE CEILING TILES OR USE VA APPROVED TEMPORARY MATERIALS IN PLACE

OF CEILING TILES TO ALLOW VA ACTIVITES TO CONTINUE UNTIL CONTRACTORS

NEXT TASK IN A PARTICULAR AREA. CONTRACTOR TO SUBMIT SCHEDULE THAT

INDICATES WORK FOR SPECIFIC AREAS AND COORDINATE WITH THE VA FOR

ACCESS.

EXIT/ACCESS FOR ADJACENT OPERATIONAL AREAS SHALL BE MAINTAINED DURING

NORMAL BUSINESS HOURS. SEE SPECIFICATION FOR HOURS OF OPERATION.

WORK REQUIRING VIBRATION OR LOUD NOISE SHALL TAKE PLACE BETWEEN THE

HOURS OF 6:00 AM AND 5:00 PM AND AS AGREED UPON BY COR SO AS NOT TO

DISTURB SLEEPING PATIENTS IN OTHER AREAS OF THE HOSPITAL. EVERY EFFORT

SHALL BE MADE TO KEEP NOISE AND VIBRATION TO A MINIMUM.

GRAPHIC REPRESENTATION OF AREAS OF WORK AND/OR PHASING PLANS ARE

NOT SUITABLE FOR USE BY THE CONTRACTOR TO ESTIMATE DISTANCES /

QUANTITIES THAT MAY BE REQUIRED TO BE INSTALLED IN THE ACTUAL BUILDING.

CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY AND MEASURE ALL FIELD

CONDITIONS TO INCLUDE (E) ITEMS TO REMAIN THAT THE VA MIGHT NEED

ACCESSIBLE E.G. SWITCHES, CONTROLS, DOORS, ACCESS PANELS,

THERMOSTATS, AIR SUPPLY, AIR RETURN, ETC.

EXISTING PROJECT AREAS WILL BE OCCUPIED BY STAFF AND VETERANS

THROUGHOUT CONSTRUCTION. ALL/ANY WORK REQUIRED IN VA OCCUPIED SPACE

MUST BE SCHEDULED WITH THE COR.

REFER TO SPECIFICATION SECTION 01 00 00 GENERAL REQUIREMENTS FOR

ADDITIONAL INFORMATION.

REFERS TO SHEETS GI101 AND GI103

AREA OF PHASE 2A, 2B, AND 2C WORK, 1ST

FLOOR ONLY. PHASE 2 WORK IS WITHIN THE

EXISTING BUILDING AND SHALL BEGIN ONCE

PHASE 1 HAS BEEN COMPLETED.

CONTRACTOR SHALL BE REQUIRED TO

COORDINATE PHASE 2 WORK WITH THE COR

AND SUBPHASES SHALL NOT BE ASSUMED

TO BE PERFORMED SIMULTANEOUSLY.

AREA OF 1ST FLOOR

PRIMARY CARE

EXPANSION

GENERATOR BUILDING 16

HOSPITAL BUILDING 1

1 EAST WING

N

EXISTING PRIMARY CARE

MAIN

ENTRANCE

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked By:

Building Number

Project Number

Drawing Number

Drawn By:

Revisions: Date

ARCHITECT/ENGINEERS:

VA NORTHERN INDIANA - FW

#1 o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

JAMES A. BROYLES, COR 610-311

GUIDON DESIGN INC.

905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204

317.800.6388 | WWW.GUIDONDESIGN.COM

SUSTAINABLE ARCHITECTURE + ENGINEERING

PROJECT LEAD

Architect, Structural and Civil Engineer

VA NORTHERN INDIANA HEALTH CARE SYSTEM

FORT WAYNE CAMPUS

FORT WAYNE, INDIANA

MEP Engineer

4031 TRANSPORTATION DR.

FORT WAYNE, IN 46818

(260) 918-3045

DESIGN-AIRE ENGINEERING, INC.

220 N COLLEGE AVE

INDIANAPOLIS, IN 46202

(317) 464-9090

Commissioning Agent

C U s e rs

\t s a n d e rs

\D o c u m e n ts

\1 .1

F W

P ri m a ry

C a re ts a n d e rs g u id o n d e s ig n .c o m

.r v t

CONSTRUCTION DOCUMENTS

GI103

TSKA/JG

1ST FLOOR INFECTION CONTROL /

PHASING PLANS

2019/4/16

16.1045EXPAND BUILDING 1 - 1ST FLOOR

PRIMARY CARE

SCALE: 1 1/2" = 1'-0"GI103

2 TEMPORARY 1 HR FIRE RATED SMOKE BARRIER WALL CONSTRUCTION NFPA 241

SCALE: 1/4" = 1'-0"GI103

3 TEMPORARY INFECTION CONTROL WALL AND DOOR

SCALE: 3/32" = 1'-0"GI103

1 1ST FLOOR INFECTION CONTROL / PHASING FLOOR PLAN

SCALE: 1" = 100'-0"

KEY PLAN

X X

X X

X X

X

X XX X X X X X X X X X X X X X X X X X X X X X X X X X X X

X

X

X X

X X

X X

X X

X X

X X

X XX X X

X

X

X

X

X

X

X

X X

X X

X

X

X X

X X

X

X

X

X

X

X

X

X

X XX X X

X

X

X

X

X

X

X

X

X

AREA OF 1ST FLOOR

PRIMARY CARE

EXPANSION

GENERATOR BUILDING 16

HOSPITAL BUILDING 1

1 EAST WING

N

EXISTING PRIMARY CARE

MAIN

ENTRANCE

STAGING & PARKING LEGEND

FIRST FLOOR EXPANSION

EXISTING AREA OF

BUILDING 1

FENCING WITH GATE

EXISTING BUILDING 1

PROVIDE

CONSTRUCTION

FENCE WITH

GATES AS NOTED

AROUND SITE

FUTURE DOCK.

DO NOT INSTALL ANY

IMPROVEMENTS IN

THIS AREA

CONTRACTOR SHALL AVOID

SOIL COMPACTION AS

PRACTICABLE THIS AREA

PROVIDE CONCRETE WASHOUT

LOCATION. COORDINATE LOCATION

WITH COR.

X X

BUILDING 1

EXPANSION

THIS GATE SHALL BE

CONTRACTOR'S SOLE

ACCESS POINT

X

NO CONTRACTOR TRAFFIC BEYOND

THIS BOUNDARY

SOLE CONTRACTOR

ENTRANCE TO FACILITY

CONTRACTOR'S SECURED AREA.

CONTRACTORS SHALL PARK WITHIN FENCED WORK AREA ONLY

GENERATOR BUILDING 16

LAKE AVE

CONSTRUCTION

SIGN

CONTRACTOR TO PROVIDE

BARRICADE AND SIGNAGE INSIDE

OF BUILDING 16 TO ALERT VA

STAFF TO NOT USE DOORS ON

EAST END OF BUILDING 16

PROVIDE GATE

FOR EMERGENCY

EXIT

NO CONTRACTOR

ACCESS

C

ALL LETTERING

TO BE

PAINTED BLACK

WITH

EXCEPTION OF

PROJECT TITLE

WHICH IS TO BE

BLUE

PAINT BORDER

MEMBER

BLACK ENAMEL

2"x4" [51x102mm]

FRAME AND

BRACES IN

SAME PLANE

METAL FACE

WHITE ENAMEL

2"x4" [51x102mm]

FRAME AND

BRACE IN BACK

BORDER MEMBER

PAINTED BLACK

BACKGROUND TO

BE PAINTED WHITE

METAL FACE

STRETCH METAL

FACE TIGHT, TURN

OVER FRAME AND

SECURE WITH FLAT

HEAD DEFORMED

NAILS.

LETTERING TO BE

HELVETICA STYLE 1 1/2"

[38mm] HIGH TO BE

CENTERED HORIZONTAL

NOTE:

ANY SEAM IN METAL TO

BE FLAT SEAM - SEAMS TO BE

HORIZONTAL AND OCCUR

BETWEEN LINES OF LETTERING.

4"x4" [102x102mm]

POSTS

PAINTED

WHITE

SECTION ON CENTERLINEELEVATION

A/E TO PROVIDE DIGITAL

LOGO AND ADDRESS

THIS SPACE FOR PROJECT TITLE

LETTERING TO BE HELVETICA TYPE 5"

HIGH CENTERED BETWEEN LETTERING

ABOVE AND BELOW ONE OR TWO LINES

DESIGNED AND SUPERVISED BY:

DEPARTMENT OF VETERANS

AFFAIRS WASHINGTON D.C.

GENERAL CONTRACTOR

L

GC TO PROVIDE DIGITAL

LOGO AND ADDRESS

8'-0"

2"

M

A X

6' -0

M A

X

3' -0

A

V E

R A

G E

4' -0

M

IN

CONSTRUCTION LOGISTICS GENERAL NOTES

CONTRACTOR TO PROTECT CLEANOUTS FROM DAMAGE AND

MATERIAL.

CONSTRUCTION FENCE LOCATION AND LAYOUT IS INDICATED

FOR PRICING PURPOSES. FINAL DIMENSIONS AND LAYOUT OF

FENCE TO BE DETERMINED BY CONTRACTOR WITH

APPROVED OF VA COR.

A.

B.

BLUE

BLUE

OUTLINE

WITH WHITE

INTERIOR

JOINT

BRACING

RED

WHITE

BLUE

BRACING SEE

CONSTRUCTION

SIGN DETAIL

01010-1

4"x4" POST

IF SIGN IS INSTALLED

ON GRADE

FIN. GRADE

WOOD STRIPS

ELEVATION

CONTRACTOR'S NAME

THE LIFE YOU SAVE MAY BE YOUR OWN

WITHOUT A LOST TIME ACCIDENT

0 DAYSHAS WORKED

THIS PROJECT

ON SAFETY

in

ZERO

4'-0"

3' -0

V

A R

IE

S

0 0

-3

/4

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked By:

Building Number

Project Number

Drawing Number

Drawn By:

Revisions: Date

ARCHITECT/ENGINEERS:

VA NORTHERN INDIANA - FW

#1 o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

JAMES A. BROYLES, COR 610-311

GUIDON DESIGN INC.

905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204

317.800.6388 | WWW.GUIDONDESIGN.COM

SUSTAINABLE ARCHITECTURE + ENGINEERING

PROJECT LEAD

Architect, Structural and Civil Engineer

VA NORTHERN INDIANA HEALTH CARE SYSTEM

FORT WAYNE CAMPUS

FORT WAYNE, INDIANA

MEP Engineer

4031 TRANSPORTATION DR.

FORT WAYNE, IN 46818

(260) 918-3045

DESIGN-AIRE ENGINEERING, INC.

220 N COLLEGE AVE

INDIANAPOLIS, IN 46202

(317) 464-9090

Commissioning Agent

C U s e rs

\t s a n d e rs

\D o c u m e n ts

\1 .1

F W

P ri m a ry

C a re ts a n d e rs g u id o n d e s ig n .c o m

.r v t

CONSTRUCTION DOCUMENTS

GI104

TSKA/JG

CONSTRUCTION LOGISTICS SITE PLAN

2019/4/16

16.1045EXPAND BUILDING 1 - 1ST FLOOR

PRIMARY CARE

SCALE: 1" = 100'-0"

KEY PLAN

N

SCALE: 3/64" = 1'-0"GI104

1 CONSTRUCTION LOGISTICS SITE PLAN

SCALE: 1" = 1'-0"GI104

2 CONSTRUCTION SIGN

SCALE: 1 1/2" = 1'-0"GI104

3 SAFETY SIGN

DN

LAKE AVENUE

DN

UP

B

DASHED LINES INDICATE APPROXIMATE

AREA OF REDUCED SCOPE OF WORK. THIS

PLAN REFLECTS CONDITION UPON

ACCEPTANCE OF ALTERNATE 'B'.

A

DASHED…