This document is a mechanical schedule for an HVAC system expansion project at the VA Northern Indiana Health Care System facility in Fort Wayne, Indiana. It provides specifications for various mechanical equipment including air handling units, terminal units, exhaust fans, pumps, and grilles/diffusers. Key details include the project number 610-311 to expand the first floor of Building 1 for PACT services, with the Department of Veterans Affairs Veterans Health Administration VISN 10 listed as the agency. Equipment specifications are given for terminal units, cabinet unit heaters, mini split systems, air handlers, exhaust fans, pumps, and grilles/diffusers to be used. Manufacturers, models, sizes, capacities, voltages, and other technical details are included for each piece of mechanical equipment.
View the file
Other files
Show all 45
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked By:
Building Number
Project Number
Drawing Number
Drawn By:
Revisions: Date
ARCHITECT/ENGINEERS:
VA NORTHERN INDIANA - FW
#1 o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
JAMES A. BROYLES, COR 610-311
VA NORTHERN INDIANA HEALTH CARE SYSTEM
FORT WAYNE CAMPUS
FORT WAYNE, INDIANA
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN.
46204
317.800.6388 | WWW.GUIDONDESIGN.COMSUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural and Civil Engineer MEP Engineer
4031 TRANSPORTATION DR.
FORT WAYNE, IN 46818
(260) 918-3045
DESIGN-AIRE ENGINEERING,
INC.
220 N COLLEGE AVE
INDIANAPOLIS, IN 46202
(317) 464-9090
Commissioning Agent
C U s e rs
\F re g o z o
\D o c u m e n ts \1
M
E P fr e g o z o
Z E
.r v t
1 AMENDMENT NO. 3 2020/08/07
CONSTRUCTION DOCUMENTS
MI102
RRMWJH
MECHANICAL SCHEDULES
2019/4/16
16.1045EXPAND BUILDING 1 - 1ST FLOOR
PRIMARY CARE
HVAC ROOM SCHEDULE
ROOM
NUMBER ROOM NAME AREA
CEILING
HEIGHT SUPPLY
RETUR
N
EXHAUS
T ACH PRESSURIZATION
8' - 0" 540 CFM 540 CFM 0 CFM NEUTRAL
1-C-100 VESTIBULE 235 SF 10' - 0" 1080 CFM 1080 CFM 0 CFM 28 NEUTRAL
1-C-101 WAITING 1492 SF 9' - 0" 2025 CFM 0 CFM 2530 CFM 11 NEGATIVE
1-C-101A CONCIERGE 27 SF 8' - 4" 30 CFM 0 CFM 40 CFM 11 NEGATIVE
1-C-101C KIOSKS 44 SF 8' - 4" 40 CFM 0 CFM 50 CFM 8 NEGATIVE
1-C-101D COFFEE 42 SF 8' - 6" 30 CFM 0 CFM 50 CFM 8 NEGATIVE
1-C-102 RECEPTION 202 SF 8' - 0" 275 CFM 0 CFM 345 CFM 13 NEGATIVE
1-C-103 INTAKE 1 33 SF 9' - 0" 30 CFM 30 CFM 0 CFM 6 NEUTRAL
1-C-104 NEG. PRESSURE HYBRID 1 121 SF 8' - 0" 155 CFM 0 CFM 220 CFM 14 NEGATIVE
1-C-105 EXAM 2 120 SF 8' - 0" 130 CFM 130 CFM 0 CFM 8 NEUTRAL
1-C-106 EXAM 3 120 SF 8' - 0" 130 CFM 130 CFM 0 CFM 8 NEUTRAL
1-C-107 HYBRID 4 120 SF 8' - 0" 130 CFM 130 CFM 0 CFM 8 NEUTRAL
1-C-108 EXAM 5 120 SF 8' - 0" 130 CFM 130 CFM 0 CFM 8 NEUTRAL
1-C-109 EXAM 6 120 SF 8' - 0" 130 CFM 130 CFM 0 CFM 8 NEUTRAL
1-C-110 P. TOILET 1 59 SF 8' - 0" 0 CFM 0 CFM 80 CFM 10 NEGATIVE
1-C-111 HYBRID 7 120 SF 8' - 0" 130 CFM 130 CFM 0 CFM 8 NEUTRAL
1-C-112 EXAM 8 120 SF 8' - 0" 130 CFM 130 CFM 0 CFM 8 NEUTRAL
1-C-113 EXAM 9 120 SF 8' - 0" 130 CFM 130 CFM 0 CFM 8 NEUTRAL
1-C-114 EXAM 10 120 SF 8' - 0" 130 CFM 130 CFM 0 CFM 8 NEUTRAL
1-C-115 MULTIPURPOSE 508 SF 8' - 0" 1725 CFM 1725 CFM 0 CFM 25 NEUTRAL
1-C-116 STAFF LOUNGE 342 SF 9' - 0" 1050 CFM 1050 CFM 0 CFM 20 NEUTRAL
1-C-117 OPEN OFFICE 118 SF 8' - 0" 125 CFM 125 CFM 0 CFM 8 NEUTRAL
1-C-117 OPEN OFFICE 2487 SF 8' - 0" 2575 CFM 2575 CFM 0 CFM 8 NEUTRAL
1-C-118 EQUIP. STOR. 33 SF 8' - 0" 0 CFM 0 CFM 0 CFM 0 NEUTRAL
1-C-119 CONSULT 19 117 SF 8' - 0" 125 CFM 125 CFM 0 CFM 8 NEUTRAL
1-C-120 CONSULT 18 118 SF 8' - 0" 125 CFM 125 CFM 0 CFM 8 NEUTRAL
1-C-121 CONSULT 17 118 SF 8' - 0" 125 CFM 125 CFM 0 CFM 8 NEUTRAL
1-C-123 DW 41 SF 8' - 0" 0 CFM 0 CFM 0 CFM 0 NEUTRAL
1-C-124 MED ROOM 1 72 SF 8' - 0" 125 CFM 100 CFM 0 CFM 13 POSITIVE
1-C-125 EXAM 15 122 SF 8' - 0" 130 CFM 130 CFM 0 CFM 8 NEUTRAL
1-C-126 EXAM 14 118 SF 8' - 0" 130 CFM 130 CFM 0 CFM 8 NEUTRAL
1-C-127 HYBRID 13 118 SF 8' - 0" 130 CFM 130 CFM 0 CFM 8 NEUTRAL
1-C-128 EXAM 12 116 SF 8' - 0" 130 CFM 130 CFM 0 CFM 8 NEUTRAL
1-C-129 CONSULT 11 121 SF 8' - 0" 135 CFM 135 CFM 0 CFM 8 NEUTRAL
1-C-130 INTAKE 2 36 SF 8' - 0" 55 CFM 55 CFM 0 CFM 11 NEUTRAL
1-C-132 P. TOILET 2 70 SF 8' - 0" 75 CFM 0 CFM 95 CFM 10 NEGATIVE
1-C-133 DW 40 SF 8' - 0" 0 CFM 0 CFM 0 CFM 0 NEUTRAL
1-C-134 STORAGE 44 SF 8' - 0" 0 CFM 0 CFM 0 CFM 0 NEUTRAL
1-C-135 HYBRID 20 120 SF 8' - 0" 130 CFM 130 CFM 0 CFM 8 NEUTRAL
1-C-136 EXAM 21 120 SF 8' - 0" 130 CFM 130 CFM 0 CFM 8 NEUTRAL
1-C-137 EXAM 22 120 SF 8' - 0" 130 CFM 130 CFM 0 CFM 8 NEUTRAL
1-C-138 HYBRID 23 120 SF 8' - 0" 130 CFM 130 CFM 0 CFM 8 NEUTRAL
1-C-139 OIT 63 SF 8' - 0" 250 CFM 250 CFM 0 CFM 30 NEUTRAL
1-C-140 ELECTRICAL 50 SF 8' - 0" 125 CFM 125 CFM 0 CFM 19 NEUTRAL
1-C-141 MED ROOM 2 72 SF 8' - 0" 125 CFM 100 CFM 0 CFM 13 POSITIVE
1-C-142 EXAM 24 120 SF 8' - 0" 130 CFM 130 CFM 0 CFM 8 NEUTRAL
1-C-143 EXAM 25 120 SF 8' - 0" 130 CFM 130 CFM 0 CFM 8 NEUTRAL
1-C-144 CONSULT 26 120 SF 8' - 0" 130 CFM 130 CFM 0 CFM 8 NEUTRAL
1-C-145 CLEAN UTILITY 1 103 SF 8' - 0" 190 CFM 150 CFM 0 CFM 14 POSITIVE
1-C-146 M. STAFF TOILET 176 SF 8' - 0" 190 CFM 0 CFM 235 CFM 10 NEGATIVE
1-C-147 W. STAFF TOILET 178 SF 8' - 0" 190 CFM 0 CFM 235 CFM 10 NEGATIVE
1-C-148 OPEN OFFICE 1692 SF 8' - 0" 1975 CFM 1975 CFM 0 CFM 9 NEUTRAL
1-C-154 SPECIALTY 30 SF 8' - 0" 130 CFM 130 CFM 0 CFM 33 NEUTRAL
1-C-C1 PATIENT CORR. 1 838 SF 9' - 0" 2925 CFM 2925 CFM 0 CFM 23 NEUTRAL
1-C-C2 PATIENT CORR. 2 660 SF 8' - 0" 540 CFM 540 CFM 0 CFM 6 NEUTRAL
1-C-C3 STAFF CORR. 603 SF 8' - 0" 485 CFM 485 CFM 0 CFM 6 NEUTRAL
1-C-C4 EGRESS CORRIDOR 149 SF 8' - 0" 0 CFM 0 CFM 0 CFM 0 NEUTRAL
1-C-C5 CORRIDOR 120 SF 8' - 0" 95 CFM 95 CFM 0 CFM 6 NEUTRAL
1-C-EL1-2 TEAM ROOM (FUTURE ELEV.) 189 SF 8' - 0" 200 CFM 200 CFM 0 CFM 8 NEUTRAL
1-C-ST1 STAIRS 254 SF 10' - 0" 0 CFM 0 CFM 0 CFM 0 NEUTRAL
1-C-ST2 STAIRS 95 SF 10' - 0" 100 CFM 100 CFM 0 CFM 6 NEUTRAL
1-C-ST2 STAIRS 192 SF 10' - 0" 0 CFM 0 CFM 0 CFM 0 NEUTRAL
1E-1 CORRIDOR 702 SF 8' - 0" 60 CFM 60 CFM 0 CFM 1 NEUTRAL
148 WAITING 521 SF 8' - 0" 450 CFM 0 CFM 550 CFM 8 NEGATIVE
148A FUTURE HAC 56 SF 8' - 0" 0 CFM 0 CFM 0 CFM 0 NEUTRAL
149 FAMILY TOILET 79 SF 8' - 0" 85 CFM 0 CFM 105 CFM 10 NEGATIVE
151 P. TOILET 3 59 SF 8' - 0" 110 CFM 0 CFM 135 CFM 17 NEGATIVE
167A PR. TOILET 82 SF 8' - 0" 90 CFM 0 CFM 110 CFM 10 NEGATIVE
168 MED ROOM 3 70 SF 8' - 0" 325 CFM 275 CFM 0 CFM 35 POSITIVE
NOTES:
1. THE #'S AFTER THE "VAV-" CORRESPOND TO THE ROOM NUMBER IN WHICH THE THERMOSTAT IS LOCATED.
2. UNIT SHALL BE PRESSURE INDEPENDENT.
3. SEE PIPING PLANS FOR LEFT AND RIGHT HAND COIL CONNECTIONS.
4. COIL ENTERING HOT WATER TEMPERATURE SHALL BE 180°F AVERAGE RETURN.
5. STANDARD TWO ROW REHEAT COIL UNLESS MENTIONED OTHERWISE.
6. PROVIDE 24V CONTROL TRANSFORMER FOR EACH VAV TERMINAL UNIT.
7. REHEAT COIL WATER PRESSURE DROP SHALL NOT EXCEED 2'.
8. PROVIDE DDC CONTROL FOR VAV TERMINAL UNIT.
9. COIL TEMPERATURE SHALL BE 55°F E.A.T.
10. EXISTING CONTROLS ARE INVENSYS, BY HAVEL BROTHERS.
SCHEDULE OF TERMINAL UNITS
SYMBOL
BASIS OF
DESIGN MODEL MODEL SIZE INLET SIZE
MINIMUM
AIRFLOW
DESIGN
AIRFLOW
MAXIMUM
BOX CFM
AIR
PRESSURE
DROP
NOMINAL
HEATING
CAPACITY
(MBH)
NOMINAL
GPM
HOT WATER
PRESSURE
DROP L.A.T. NOTES
VAV-1-C-101A TRANE VCWF 14 14" 1260 CFM 1260 CFM 3000 CFM 0.16 in-wg 80.89 6.46 GPM 1.67 114 °F ALL APPLY
VAV-1-C-101B TRANE VCWF 14 14" 1320 CFM 1320 CFM 3000 CFM 0.18 in-wg 83.17 6.65 GPM 1.76 113 °F ALL APPLY
VAV-1-C-104 TRANE VCWF 06 6" 155 CFM 155 CFM 500 CFM 0.02 in-wg 7.86 0.78 GPM 1.06 102 °F ALL APPLY
VAV-1-C-105 TRANE VCWF 06 6" 95 CFM 130 CFM 500 CFM 0.02 in-wg 6.03 0.60 GPM 0.67 114 °F ALL APPLY
VAV-1-C-106 TRANE VCWF 06 6" 95 CFM 130 CFM 500 CFM 0.02 in-wg 6.03 0.60 GPM 0.67 114 °F ALL APPLY
VAV-1-C-107 TRANE VCWF 06 6" 95 CFM 130 CFM 500 CFM 0.02 in-wg 6.03 0.60 GPM 0.67 114 °F ALL APPLY
VAV-1-C-108 TRANE VCWF 06 6" 95 CFM 130 CFM 500 CFM 0.02 in-wg 6.03 0.60 GPM 0.67 114 °F ALL APPLY
VAV-1-C-109 TRANE VCWF 06 6" 95 CFM 130 CFM 500 CFM 0.02 in-wg 6.03 0.60 GPM 0.67 114 °F ALL APPLY
VAV-1-C-111 TRANE VCWF 06 6" 95 CFM 130 CFM 500 CFM 0.02 in-wg 6.03 0.60 GPM 0.67 114 °F ALL APPLY
VAV-1-C-112 TRANE VCWF 06 6" 95 CFM 130 CFM 500 CFM 0.02 in-wg 6.03 0.60 GPM 0.67 114 °F ALL APPLY
VAV-1-C-113 TRANE VCWF 06 6" 95 CFM 130 CFM 500 CFM 0.02 in-wg 6.03 0.60 GPM 0.67 114 °F ALL APPLY
VAV-1-C-114 TRANE VCWF 06 6" 95 CFM 130 CFM 500 CFM 0.02 in-wg 6.03 0.60 GPM 0.67 114 °F ALL APPLY
VAV-1-C-115A TRANE VCWF 12 12" 240 CFM 975 CFM 2000 CFM 0.25 in-wg 37.42 3.74 GPM 0.75 132 °F ALL APPLY
VAV-1-C-115B TRANE VCWF 12 12" 240 CFM 750 CFM 2000 CFM 0.16 in-wg 22.37 3.79 GPM 0.78 110 °F ALL APPLY
VAV-1-C-116 TRANE VCWF 12 12" 240 CFM 1050 CFM 2000 CFM 0.28 in-wg 41.72 4.17 GPM 0.92 128 °F ALL APPLY
VAV-1-C-117A TRANE VCWF 12 12" 650 CFM 1300 CFM 2000 CFM 0.39 in-wg 48.19 4.81 GPM 1.20 124 °F ALL APPLY
VAV-1-C-117B TRANE VCWF 14 14" 650 CFM 1275 CFM 3000 CFM 0.17 in-wg 54.57 5.45 GPM 1.20 132 °F ALL APPLY
VAV-1-C-119 TRANE VCWF 06 6" 130 CFM 250 CFM 500 CFM 0.06 in-wg 7.14 0.71 GPM 0.90 106 °F ALL APPLY
VAV-1-C-122 TRANE VCWF 06 6" 130 CFM 250 CFM 500 CFM 0.06 in-wg 7.14 0.71 GPM 0.90 106 °F ALL APPLY
VAV-1-C-124 TRANE VCWF 06 6" 65 CFM 125 CFM 500 CFM 0.02 in-wg 6.03 0.60 GPM 0.67 114 °F ALL APPLY
VAV-1-C-125 TRANE VCWF 06 6" 100 CFM 130 CFM 500 CFM 0.02 in-wg 6.20 0.62 GPM 0.70 112 °F ALL APPLY
VAV-1-C-126 TRANE VCWF 06 6" 100 CFM 130 CFM 500 CFM 0.02 in-wg 6.20 0.62 GPM 0.70 112 °F ALL APPLY
VAV-1-C-127 TRANE VCWF 06 6" 100 CFM 130 CFM 500 CFM 0.02 in-wg 6.20 0.62 GPM 0.70 112 °F ALL APPLY
VAV-1-C-128 TRANE VCWF 06 6" 100 CFM 130 CFM 500 CFM 0.02 in-wg 6.20 0.62 GPM 0.70 112 °F ALL APPLY
VAV-1-C-129 TRANE VCWF 06 6" 70 CFM 135 CFM 500 CFM 0.02 in-wg 5.86 0.59 GPM 0.63 115 °F ALL APPLY
VAV-1-C-135 TRANE VCWF 06 6" 100 CFM 130 CFM 500 CFM 0.02 in-wg 6.20 0.62 GPM 0.70 112 °F ALL APPLY
VAV-1-C-136 TRANE VCWF 06 6" 100 CFM 130 CFM 500 CFM 0.02 in-wg 6.20 0.62 GPM 0.70 112 °F ALL APPLY
VAV-1-C-137 TRANE VCWF 06 6" 100 CFM 130 CFM 500 CFM 0.02 in-wg 6.20 0.62 GPM 0.70 112 °F ALL APPLY
VAV-1-C-138 TRANE VCWF 06 6" 100 CFM 130 CFM 500 CFM 0.02 in-wg 6.20 0.62 GPM 0.70 112 °F ALL APPLY
VAV-1-C-139 TRANE VCCF 06 6" 60 CFM 250 CFM 500 CFM 0.05 in-wg N/A 0.00 GPM N/A 55 °F ALL APPLY
VAV-1-C-141 TRANE VCWF 06 6" 60 CFM 125 CFM 500 CFM 0.02 in-wg 5.86 0.59 GPM 0.63 115 °F ALL APPLY
VAV-1-C-142 TRANE VCWF 06 6" 100 CFM 130 CFM 500 CFM 0.02 in-wg 6.20 0.62 GPM 0.70 112 °F ALL APPLY
VAV-1-C-143 TRANE VCWF 06 6" 100 CFM 130 CFM 500 CFM 0.02 in-wg 6.20 0.62 GPM 0.70 112 °F ALL APPLY
VAV-1-C-145 TRANE VCWF 06 6" 130 CFM 260 CFM 500 CFM 0.07 in-wg 7.14 0.71 GPM 0.90 106 °F ALL APPLY
VAV-1-C-147 TRANE VCWF 08 8" 200 CFM 400 CFM 900 CFM 0.15 in-wg 15.85 1.58 GPM 0.20 128 °F ALL APPLY
VAV-1-C-148A TRANE VCWF 14 14" 500 CFM 1000 CFM 3000 CFM 0.05 in-wg 29.44 2.70 GPM 1.94 109 °F ALL APPLY
VAV-1-C-148B TRANE VCWF 14 14" 510 CFM 1025 CFM 3000 CFM 0.05 in-wg 29.70 2.70 GPM 1.94 109 °F ALL APPLY
VAV-1-C-154 TRANE VCCF 06 6" 60 CFM 130 CFM 500 CFM 0.01 in-wg N/A 0.00 GPM N/A 55 °F ALL APPLY
VAV-1-C-C1A TRANE VCWF 14 14" 320 CFM 1475 CFM 3000 CFM 0.21 in-wg 59.82 5.97 GPM 1.43 130 °F ALL APPLY
VAV-1-C-C1B TRANE VCWF 14 14" 320 CFM 1450 CFM 3000 CFM 0.20 in-wg 58.97 5.89 GPM 1.39 130 °F ALL APPLY
VAV-1-C-C2 TRANE VCCF 10 10" 425 CFM 655 CFM 1400 CFM 0.18 in-wg 32.90 3.29 GPM 1.61 126 °F ALL APPLY
VAV-1-C-C3 TRANE VCCF 10 10" 325 CFM 485 CFM 1400 CFM 0.11 in-wg 27.31 2.73 GPM 1.14 132 °F ALL APPLY
VAV-1-C-EL 1-2 TRANE VCWF 06 6" 85 CFM 260 CFM 500 CFM 0.07 in-wg 7.14 0.71 GPM 0.90 106 °F ALL APPLY
VAV-1-C-EL 3 TRANE VCWF 06 6" 60 CFM 100 CFM 500 CFM 0.01 in-wg 5.86 0.59 GPM 0.63 115 °F ALL APPLY
VAV-141 TRANE VCWF 14 14" 1350 CFM 1350 CFM 3000 CFM 0.18 in-wg 80.21 5.34 GPM 1.16 110 °F ALL APPLY
VAV-148 TRANE VCWF 12 12" 525 CFM 525 CFM 2000 CFM 0.09 in-wg 41.72 4.17 GPM 0.92 128 °F ALL APPLY
VAV-168A TRANE VCWF 08 8" 415 CFM 415 CFM 900 CFM 0.16 in-wg 25.58 2.55 GPM 0.48 112 °F ALL APPLY
VAV-175A-EAST TRANE VCWF 12 12" 275 CFM 860 CFM 2000 CFM 0.10 in-wg 22.63 1.90 GPM 1.98 104 °F ALL APPLY
VAV-175A-WEST TRANE VCWF 12 12" 300 CFM 700 CFM 2000 CFM 0.07 in-wg 20.43 1.80 GPM 1.79 109 °F ALL APPLY
NOTES:
1. PROVIDE UNIT WITH FACTORY MOUNTED VALVING, TEMP. CONTROL VALVE PROVIDED UNDER SPEC SECTION 230900.
2. PROVIDE WITH DISCONNECT SWITCH.
SCHEDULE OF CABINET UNIT HEATERS
SYMBOL BASIS OF DESIGN MODEL
CAPACITY
(MBH) CFM E.A.T. L.A.T. E.W.T. L.W.T. GPM P.D. MOTOR H.P. NOTES
CUH-1C100 TRANE FFCB02 17.79 190 32°F 138°F 180°F 136°F 1 1.34 0.13 ALL APPLY
CUH-1CST1 TRANE FFBB10 40.56 426 60°F 148°F 180°F 139°F 2 1.17 0.22 ALL APPLY
CUH-1CST2 TRANE FFBB10 40.56 426 60°F 148°F 180°F 139°F 2 1.17 0.22 ALL APPLY
NOTES:
1. PROVIDE WITH REMOTE MOUNTED LCD DISPLAY WITH TEMPERATURE SETTING AND FAN SPEED CONTROL.
2. CONTRACTOR SHALL PIPE UNITS PER MANUFACTURER RECOMMENDATIONS.
3. PROVIDE UNIT WITH CONDENSATE PUMP.
SCHEDULE OF MINI SPLIT SYSTEMS
SYMBOL MANUFACTURER MODEL CFM
COOLING
CAPACITY
(BTUH)
HEATING
CAPACITY
(BTUH)
REFRIGERANT
TYPE
MIN.
OPERATING
TEMP.
MIN.
EFFICIENCY
(SEER) VOLTAGE PHASE MCA NOTES
SS-1C139 MITSUBISHI MSZ-GL12NA/MUZ-GL12NA 235 CFM 13,600 18,100 410A 5 °F 23.1 115 1 1 / 9 1,2,3
SS-1C154 MITSUBISHI MSZ-GL06NA-U1/MXZ-C 235 CFM 6,000 7,200 410A 5 °F 20.0 115 1 1/17.2 1,2,3
NOTES:
1. BASIS OF DESIGN
2. RETURN FAN MOTORS SHALL BE TEFC AND SUPPLY FAN MOTORS SHALL BE ODP.
3. PROVIDE UNIT WITH 40% (MERV 8) PRE-FILTERS AND 40% (MERV 14) FINAL FILTERS.
4. PROVIDE UNITS WITH FIXED PITCH V-BELT DRIVES SELECTED FOR A SERVICE FACTOR OF 2.0.
5. CONTRACTOR SHALL PROVIDE ONE ADDITIONAL SET OF BELTS AND SHEAVES FOR FINAL AIR BALANCING, COORDINATION WITH BALANCE CONTRACTOR.
SCHEDULE OF AIR HANDLER UNITS
SYMBOL
BASIS OF
DESIGN MODEL
AIRFLOW
TOTAL (CFM)
SUPPLY
FAN HP
SUPPLY
FAN TSP
(IN)
SUPPLY
FAN FRPM
RETURN
FAN HP
RETURN
FAN TSP
(IN)
RETURN
FAN FRPM
ELECTRICAL
CHARCTERISTICS NOTES
AHU-1-E2 HAAKON CUSTOM 15,000 7.5 (*4) 5.8 1750 2 (*4) 1.75 1150 460/3 ALL APPLY
AHU-1 DAIKIN CAH021GDGC 10,000 25 8.3 1750 460/3 1,3,4,5
NOTES:
1. FURNISH WITH BACKDRAFT DAMPER AND DISCONNECT.
SCHEDULE OF EXHAUST FANS
SYMBOL AREA SERVED
BASIS OF
DESIGN Model HP
FAN
RPM CFM S.P.
FAN
MOUNTING
ELECTRICAL
CHARACTERISTICS NOTES
EF-2 WAITING (1-C-101 & 148) & RECEPTION
(1-C-102)
Greenheck SWB-115-15 1 1/2 1849 3,320 0.2 ROOF 115/1/60 ALL APPLY
EF-3 STAFF TOILET (1-C-146 & 1-C-147), P. TOILET
(1-C-110 & 1-C-132) & FAMILY TOILET (149)
Greenheck BSQ-90-5 1/2 1840 750 0.7 INLINE 115/1/60 ALL APPLY
EF-4 NEG PRESSURE HYBRID 1 (1-C-104) Greenheck BSQ-70-4 1/4 1416 220 0.3 INLINE 115/1/60 ALL APPLY
EF-5 PUBLIC TOILET (141 & 143) & STAFF LOUNGE
(139)
Greenheck BSQ-120-7 3/4 1816 1,815 0.3 INLINE 115/1/60 ALL APPLY
EF-6 P. TOILET (151 & 168) Greenheck BSQ-70-4 1/4 1392 245 0.2 INLINE 115/1/60 ALL APPLY
EF-7 SOILED UTILITY (162A) Greenheck BSQ-70-4 1/4 1227 200 0.2 INLINE 115/1/60 ALL APPLY
NOTES:
1. FINAL IMPELLER SIZE SHALL BE THE RESPONSIBILITY OF THE PUMP MANUFACTURER.
2. PROVIDE PUMP FOR VARIABLE FLOW OPERATION. VFD FURNISHED UNDER SPEC SECTION 230900.
SCHEDULE OF PUMPS
SYMBOL SERVICE BASIS OF DESIGN MODEL
IMPELLER
DIAMETER GPM HEAD/FT
MOTOR
HP EFFICIENCY RPM INLET SIZE
DISCHARGE
SIZE
SHAFT
SEALS
ELECTRICAL
CHARACTERISTICS NOTES
CONDP-1 RELOCATED AHU-1 COND. SHIPCO 40032 N/A 9 92 3 N/A 1750 2 3/4 MECHANICAL 460/3 1,2
CONDP-E1 HX-E1 AND HX-E2 COND. SHIPCO 40033 N/A 22.5 92 3 N/A 1750 2 1 1/2 MECHANICAL 460/3 1,2
CWP-1 RELOCATED CH-1 AND AHU-1 BELL AND GOSSETT e-80 5.375 125 90 7.5 63.4 3600 2.5 2.5 MECHANICAL 460/3 1,2
CWP-2 RELOCATED CH-1 AND AHU-1 BELL AND GOSSETT e-80 5.375 125 90 7.5 63.4 3600 2.5 2.5 MECHANICAL 460/3 1,2
HCWP-1-E2 PRE-HEAT COIL TACO KV2006 5.4 53 26 1 57 1760 2 2 MECHANICAL 460/3 1,2
HWP-1-E1 HEAT EXCHANGER TACO KV4013 11.8 250 55 7.5 72 1160 4 4 MECHANICAL 460/3 1,2
HWP-1-E2 HEAT EXCHANGER TACO KV4013 11.8 250 55 7.5 72 1160 4 4 MECHANICAL 460/3 1,2
NOTES:
1. COORDINATE AND VERIFY COLOR WITH ARCHITECT.
2. ALL GRILLES AND DIFFUSERS SHALL BE PROVIDED WITH VOLUME DAMPERS.
3. COORDINATE AND VERIFY ALL CEILING TYPES WITH DRAWINGS AND ARCHITECT BEFORE ORDERING - REFER TO REFLECTED CEILING PLAN.
4. SHOP DRAWING MUST INCLUDE PERFORMANCE DATA OR THEY WILL BE REJECTED.
SCHEDULE OF GRILLES & DIFFUSERS
SYMBOL
BASIS OF
DESIGN MODEL SIZE TYPE
INLET
SIZE
AIRFLOW
SCHEDULE
(CFM)
THROW
@100 FPM
AIR
PRESSURE
DROP N.C. THROWS MOUNTING REMARKS
E-1 PRICE 80 24x24 EGGCRATE 22x22 1805 - 0.034 <15 - LAY-IN ALL APPLY
E-2 PRICE 80 12x12 EGGCRATE 10x10 240 - 0.021 <15 - LAY-IN ALL APPLY
R-1 PRICE 80 24x24 EGGCRATE 22x22 1805 - 0.034 <15 - LAY-IN ALL APPLY
R-2 PRICE 80 12x12 EGGCRATE 10x10 240 - 0.021 <15 - LAY-IN ALL APPLY
R-3 TITUS 355FL 14x8 LOUVERED 12x6 164 - 0.045 <15 - WALL 1,2,4
R-4 TITUS 355FL 14x10 LOUVERED 12x8 228 - 0.045 <15 - WALL 1,2,4
S-1 PRICE SPD 24x24 PLAQUE 8" 244 4 0.057 <15 4 LAY-IN ALL APPLY
S-2 PRICE SPD 24x24 PLAQUE 10" 382 6 0.031 <15 4 LAY-IN ALL APPLY
S-3 PRICE SPD 24x24 PLAQUE 12" 550 7 0.127 21 4 LAY-IN ALL APPLY
S-4 PRICE SPD 24x24 PLAQUE 6" 98 2 0.016 <15 4 LAY-IN ALL APPLY
S-5 PRICE SPD 12x12 PLAQUE 6" 118 4 0.085 <15 4 LAY-IN ALL APPLY
S-6 TITUS ML-39 48" SLOT PLENUM 236 21 0.032 18 1 PLENUM ALL APPLY
S-7 TITUS 301FL 10x8 LOUVERED 8x6 130 7 0.077 <15 1 WALL 1,2,4
S-8 TITUS 301FL 14x10 LOUVERED 12x8 285 10 0.077 15 1 WALL 1,2,4
NOTES:
1. PROVIDE WITH INSECT SCREEN.
2. PROVIDE WITH COUNTER BALANCE BACKDRAFT DAMPER.
SCHEDULE OF LOUVERS
SYMBOL
BASIS OF
DESIGN MODEL DESCRIPTION TYPE CFM
A.P.D. (IN
H2O)
VELOCITY
(FPM)
FACE AREA
(SQ FT)
DUCT
CONN. SIZE
(IN.)
MOUNTIN
G NOTES
LV-1 RUSKIN ELF375DX INTAKE FIXED DRAINABLE 21,500 0.18 905 23.74 72x84 WALL 1
LV-2 RUSKIN ELF375DX RELIEF FIXED DRAINABLE 15,000 0.10 691 21.70 66x84 WALL 1
LV-3 RUSKIN ELF375DX EXHAUST FIXED DRAINABLE 750 0.09 686 1.09 20x18 WALL 1,2
LV-4 RUSKIN ELF375DX EXHAUST FIXED DRAINABLE 220 0.08 648 0.34 12x12 WALL 1,2
LV-5 RUSKIN ELF375DX EXHAUST FIXED DRAINABLE 1815 0.09 680 2.67 46x18 WALL 1,2
LV-6 RUSKIN ELF375DX EXHAUST FIXED DRAINABLE 245 0.04 454 0.54 18x12 WALL 1,2
LV-7 RUSKIN ELF375DX EXHAUST FIXED DRAINABLE 200 0.07 588 0.34 12x12 WALL 1,2
SCHEDULE OF COOLING COILS
USAGE LOCATION
TOTAL
CAPACITY
(MBH)
SENSIBLE
CAPACITY
(MBH)
TOTAL
(CFM)
E.A.T.
(DB)
E.A.T.
(WB)
L.A.T
.(DB)
L.A.T.
(WB)
E.W.T
L.W.T
. GPM TYPE
COIL FIN
MATERIAL ROWS
FACE
AREA (SQ
FT)
FACE
VELOCIT
Y (FPM)
A.P.D. (IN
H2O)
W.P.D.
(FT H2O)
CHILLED
WATER
AHU-1-E2 861.3 502.3 15000 83°F 70°F 52°F 51.4°F 44°F 56°F 143.56 W ALUMINUM 8 30 500 0.85 13.4
CHILLED
WATER
AHU-1 673.901 398.488 10000 91.1°F 74.4°F 54.7°F 54.5°F 44.0°F 55.8°F 124 W ALUMINUM 12 20.13 497 0.82 16.6
SCHEDULE OF PRE-HEAT COILS
USAGE LOCATION
TOTAL HEATING
CAPACITY (MBH) CFM
E.A.T.
(DB)
L.A.T
.(DB) E.W.T. L.W.T. GPM TYPE
COIL FIN
MATERIAL ROWS
FACE AREA
(SQ FT)
FACE VELOCITY
(FPM)
A.P.D.
(IN. H2O)
W.P.D.
(FT. H2O)
PRE-HEAT AHU-1-E2 766.3 15000 45°F 92.3°F 180°F 150°F 52.76 HW ALUMINUM 1 30 500 0.11 9.2
SCHEDULE OF STEAM TO LIQUID SHELL AND TUBE HEAT EXCHANGER
SYMBOL
BASIS OF
DESIGN MODEL
TUBE SIDE SHELL SIDE
NOTESGPM E.W.T. L.W.T. PRESSURE DROP FLOW RATE
STEAM
PRESSURE
HX-E1 TACO E12208-S 250 160°F 180°F 0.73 FT. H2O 2540 LBS/HR 15 PSI
HX-E2 TACO E12208-S 250 160°F 180°F 0.73 FT. H2O 2540 LBS/HR 15 PSI
NOTES:
1. PROVIDE WITH CONTINUOUS ENCLOSURE INBETWWEN FIN TUBES, COORDINATE WITH ARCHITECT.
2. ENCLOSURE SHALL BE PROVIDED BY THE LINEAR RADIANT PANEL SUPPLIER.
3. LINEAR RADIANT PANEL SHALL BE INSTALLED PER MANUFACTURERS SPECIFICATIONS.
4. LINEAR RADIANT PANEL SHALL BE MODIFIED PER MANUFACTURERES SPECIFICATIONS TO FIT WITHIN CEILING WHEN
NECESSARY.
SCHEDULE OF LINEAR RADIANT PANELS
SYMBOL
BASIS OF
DESIGN MODEL BTU/FT
NUMBER OF
PASSES LENGTH WIDTH GPM NOTES
LRP-1 STERLING LINEAR RADIANT PANEL 155 2 16' - 0" 1' - 0" 0.5 ALL APPLY
LRP-2 STERLING LINEAR RADIANT PANEL 225 2 11' - 0" 1' - 0" 0.25 ALL APPLY
LRP-3 STERLING LINEAR RADIANT PANEL 190 2 9' - 0" 1' - 0" 0.5 ALL APPLY
LRP-4 STERLING LINEAR RADIANT PANEL 190 2 8' - 0" 1' - 0" 0.5 ALL APPLY
LRP-5 STERLING LINEAR RADIANT PANEL 135 2 9' - 0" 1' - 0" 0.25 ALL APPLY
LRP-6 STERLING LINEAR RADIANT PANEL 145 2 8' - 0" 1' - 0" 0.35 ALL APPLY
NOTES:
1. FURNISH HUMIDIFIERS WITH HUMIDISTAT PROVIDE UNDER SPEC SECTION 230900.
2. MINIMUM HUMIDITY LEVEL SHALL BE SET AT 35% RELATIVE HUMIDITY (ADJ).
3. FURNISH PRESSURE SWITCH, SWITCH SHALL LOCK OUT HUMIDIFIER OPERATION WHEN FAN IS NOT IN OPERATION PROVIDE UNDER SPEC SECTION 230900.
SCHEDULE OF HUMIDIFIERS
USAGE LOCATION BASIS OF DESIGN
CAPACITY
(LBS/HR)
STEAM
PRESSURE
NUMBER OF
TUBE
CENTERS
ABSORBTION
DISTANCE CONTROL A.P.D. NOTES
HUMIDIFIER AHU-1-E2 ULTRA-SORB MODEL XV 123.1 15 PSI 6 0' - 9" ELECTRIC 0.05 ALL APPLY
HUMIDIFIER AHU-1 ULTRA-SORB MODEL LV 219 15 PSI 13 0' - 11" ELECTRIC 0.003 ALL APPLY
NOTES:
1. PROVIDE WITH WALL SLEEVE/CASE.
2. PROVIDE WITH SINGLE POINT POWER KIT.
3. PROVIDE REMOTE MOUNTED PROGRAMMABLE THERMOSTAT.
4. PROVIDE EXTRUDED ALUMINUM ARCHITECTURAL GRILLE, COLOR SELECTED BY ARCHITECT.
5. PROVIDE INBUILT CIRCUIT BREAKER.
6. PROVIDE WITH FIELD SUPPLIED WALL SLEEVE SUPPORTS.
7. PROVIDE 6" LONG, 1/2" O.D. STAINLESS STEEL EXTERNAL DRAIN.
SCHEDULE OF PTAC UNITS
SYMBOL BASIS OF DESIGN MODEL CFM (HI/LO)
COOLING
CAPACITY (BTUH)
HEATING CAPACITY
(BTUH)
HOT WATER
GPM
HOT WATER
COIL
PRESSURE
DROP (FT. WC) PHASE VOLTAGE NOTES
PTAC-1 APPLIED COMFORT 16WC15R00E2 360/310 14,200 18,500 1.9 1.8 1 280 ALL APPLY
NOTES:
1. MAKEUP WATER SHALL BE 40°F.
2. UNIT CONFIGURATION SHALL BE VERTICAL.
3. TUBE BUNDLE SHALL BE TRIAGLE PITCH, 1/2" DIAMETER, THICKNESS OF 16 GAUGE, MADE OF 304 STAINLESS STEEL.
4. SUPPLY WITH BLOWDOWN SEPERATOR.
SCHEDULE OF STEAM TO STEAM EXCHANGER
SYMBOL
BASIS OF
DESIGN MODEL
HEATING
CAPACITY (MBH)
SOURCE STEAM
FLOW RATE
SOURCE STEAM
PRESSURE
SOURCE STEAM
PRESSURE DROP
PRODUCED STEAM
FLOW RATE
PRODUCED STEAM
PRESSURE NOTES
SHX-E1 CEMLINE V45USG1018 145.75 155 LB/HR 25 PSIG 5 PSIG 125 LB/HR 10 PSIG ALL APPLY
NOTES:
1. WITH OUT STRAINER
SCHEDULE OF AIR SEPERATOR
SYMBOL USAGE BASIS OF DESIGN MODEL SIZE CAPACITY NOTES
AS-E1 HOT WATER TACO AC04 250 416 ALL APPLY
SCHEDULE OF EXPANSION TANK
SYMBOL USAGE
BASIS OF DESIGN
MANUFACTURER MODEL VOLUME NOTES
ET-E1 HOT WATER TACO CA-140 37 -
NOTES:
1. REFER TO SPEC SECTION 232500.
SCHEDULE OF ONE SHOT FEEDER
SYMBOL
BASIS OF
DESIGN MODEL
TANK
GALLONS
DISCHARGE
PRESSURE NOTES
CF-E1 NEPTUNE DBF 5 150 PSI -
SCHEDULE OF AHU-1 RECOVERY COIL
USAGE LOCATION
TOTAL HEATING
CAPACITY (MBH) CFM
E.A.T.(D B)
L.A.T.(D
B) E.W.T. L.W.T. GPM TYPE
COIL FIN
MATERIAL ROWS
FACE AREA
(SQ FT)
FACE
VELOCITY
(FPM)
A.P.D. (IN
WC)
W.P.D. (FT
WC)
RECOVERY AHU-1 80.434 10000 91.1°F 83.7°F 82.8°F 84.5°F 100 W ALUMINUM 8 20.13 497 0.79 10.8
No.
STATE OF
19447
I
W I L
L I AM
J HOSMO
N
R
EG
I STERED
P R O F
ESS I ONAL ENG
I N E E R
N D I A N A
2020/7/16
SCHEDULE OF STEAM PRE-HEAT COILS
USAGE LOCATION
TOTAL HEATING
CAPACITY (MBH) CFM E.A.T. (DB) L.A.T. (DB)
STEAM FLOW
(LB/HR)
COIL FIN
MATERIAL
(3) ROWS
FACE AREA
(SQ FT) (3)
FACE
VELOCITY
(3) A.P.D. (3)
PRE-HEAT AHU-1 80.434 10000 -3 °F 57 °F 664.39 COPPER 2 11.54 873 CFM 0.46
SCHEDULE OF CONDENSATE COOLER
SYMBOL BASIS OF DESIGN MODEL
HOT WATER FLOW
RATE
CC-1 TACO DRANE-KOOL
ER
6 GPM
CC-1 DRI DRANE-KOOL
ER
6 GPM