2020.8.6. Add 3 088000 - Glazing.docx

DOCX document 46 KB Posted

Attached to
Y1DA--Expand First Floor B-1 for PACT - 610-311
Solicitation number
36C25020B0004
Issued by

About this file

This document contains specifications for glazing materials and installation for the VA Northern Indiana Healthcare System project to Expand Building 1, First Floor Primary Care in Fort Wayne, Indiana. The specifications require clear, heat-treated, coated, laminated, insulating, and fire-protective glass units to meet standards for thickness, light transmission, solar heat gain, fire ratings, and safety glazing. Metal accessories must match aluminum finishes. Installation methods include dry, wet/dry and wet techniques for sealants, gaskets and tapes. The project also includes a monolithic and insulating/laminated glass schedule.

The related federal contract opportunity is solicitation number 36C25020B0004 for the Y1DA--Expand First Floor B-1 for PACT project at the VA Northern Indiana Healthcare System in Fort Wayne, Indiana.

View the file

Other files

File Type Posted
16.1045 - 2020.8.6. Add 3 Civil Sheets.pdf PDF
2020.8.6. Add 3 061000 - Rough Carpentry.docx DOCX document
36C25020B0004 0008.docx DOCX document
16.1045 - 2020.8.6 Addendum 3 Responses.pdf PDF
2020.8.6. Add 3 090600 - SCHEDULE OF FINISHES.docx DOCX document
16.1045 - 2020.8.6. Add 3 Arch Sheets.pdf PDF
2020.8.6. Add 3 083616.13 - BARN DOOR.doc DOC document
16.1045 - 2020.8.6 Revised Sheet MI102.pdf PDF
36C25020B0004 0007.docx DOCX document
36C25020B0004 0006.docx DOCX document
36C25020B0004 0005.pdf PDF
RFI - 7-30-2020.pdf PDF
Masking due to COVID.pdf PDF
RFI - 7-31-2020.pdf PDF
RFI - 7-29-2020.pdf PDF
08 44 13 - Glazed Aluminum Curtain Walls.pdf PDF
16.1045 - 2020.7.28 - Addendum 2.pdf PDF
16965 - PD101 - BASEMENT PLUMBING REMOVAL PLAN.pdf PDF
36C25020B0004 0004.pdf PDF
16965 - PL101 - BASEMENT PLUMBING PLAN.pdf PDF
RFI Form AHS 1 Plumbing.pdf PDF
RFI Form AHS 4 Plumbing.pdf PDF
RFI Form AHS 3 Plumbing.pdf PDF
RFI Form AHS 2 Plumbing.pdf PDF
16.1045 - 2020.7.16 - Addendum 1 Revised Sheets.pdf PDF
16.1045 - 2020.7.16 - Addendum 1 Description.pdf PDF
36C25020B0004 0003.pdf PDF
36C25020B0004 0002.docx DOCX document
Sign-in Sheet Sub-Contractors.pdf PDF
Sign-in Sheet Prime Contractors 7-7-2020.pdf PDF
36C25020B0004 0001.docx DOCX document
36C25020B0004.docx DOCX document
610-311 FW Primary Care Drawings STRUCTURAL.pdf PDF
610-311 FW Primary Care Drawings ARCHITECTURAL.pdf PDF
610-311_6.24.2020_FW Primary Care Drawings GENERAL.pdf PDF
610-311 FW Primary Care Drawings MEP.pdf PDF
610-311 FW Primary Care Drawings CIVIL.pdf PDF
36C25020B0004_2.docx DOCX document
Wage Determination - Highway 6-12-20.pdf PDF
36C25020B0004_3.docx DOCX document
Spec Volume 1 - 610-311.pdf PDF
Wage Determination - Building 6-12-20.pdf PDF
Spec Volume 2 - 610-311.pdf PDF
Contractor Certification Regarding Safety and Environmental.pdf PDF
RFI Form.pdf PDF
Show all 45

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VA Northern Indiana Healthcare System, Fort Wayne VA: 610-311 Expand Bldg 1 - 1st Floor Primary Care Fort Wayne, IN 46845 03-30-2018 Const. Document Submission 10-01-2015

SECTION 08 80 00

GLAZING

PART 1 - GENERAL

1.1 DESCRIPTION:

A. This section specifies the following:

1. Glass.

2. Plastic glazing.

1.2 RELATED WORK:

A. Sustainable Design Requirements: Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS.

B. Factory glazed by manufacturer in following units:

1.Mirrors: Section 10 28 00, TOILET, BATH, AND LAUNDRY ACCESSORIES.
2.Aluminum Windows: Section 08 51 13, ALUMINUM WINDOWS.

3. Color of spandrel glass, tinted (heat absorbing or light reducing) glass, and reflective (metallic coated) glass: Section 09 06 00, SCHEDULE FOR FINISHES.

1.3 LABELS:

A.Temporary labels:
1.Provide temporary label on each light of glass and plastic material identifying manufacturer or brand and glass type, quality and nominal thickness.
2.Label in accordance with NFRC label requirements.
3.Temporary labels are to remain intact until glass is approved by Contracting Officer Representative (COR).
B.Permanent labels:
1.Locate in corner for each pane.
2.Label in accordance with ANSI Z97.1 and SGCC label requirements.
a.Tempered glass.
b.Laminated glass or have certificate for panes without permanent label.
c.Organic coated glass.

3. Fire rated glazing assemblies: Mark in accordance with IBC.

1.4 PERFORMANCE REQUIREMENTS:

A.General: Design glazing system consistent with guidance and practices presented in the GANA Glazing Manual, GANA Laminated Glazing Manual, and GANA Sealant Manual, as applicable to project. Installed glazing is to withstand applied loads, thermal stresses, thermal movements, building movements, permitted tolerances, and combinations of these conditions without failure, including loss or glass breakage attributable to defective manufacture, fabrication, or installation; failure of sealants or gaskets to remain watertight and airtight; deterioration of glazing materials; unsafe engagement of the framing system; deflections beyond specified limits; or other defects in construction.
B.Glazing Unit Design: Design glass, including engineering analysis meeting requirements of authorities having jurisdiction. Thicknesses listed are minimum. Coordinate thicknesses with framing system manufacturers.
1.Design glass in accordance with ASTM E1300, and for conditions beyond the scope of ASTM E1300, by a properly substantiated structural analysis.
2.Design Wind Pressures: In accordance with ASCE 7.
3.Wind Design Data: In accordance with ASCE 7.
4.Maximum Lateral Deflection: For glass supported on all four edges, limit center-of-glass deflection at design wind pressure to not more than the structural capacity of the glazing unit, the threshold at which frame engagement is no longer safely assured, 1/100 times the short-side length, or 19 mm (0.75 inch) , whichever is less.
C.Building Enclosure Vapor Retarder and Air Barrier:
1.Utilize the inner pane of multiple pane sealed units for the continuity of the air barrier and vapor retarder seal.
2.Maintain a continuous air barrier and vapor retarder throughout the glazed assembly from glass pane to heel bead of glazing sealant.

1.5 SUBMITTALS:

A. In accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

B. Sustainable Design Submittals, as described below:

1. Volatile organic compounds per volume as specified in PART 2 PRODUCTS.

C. Manufacturer's Certificates:

1.Certificate stating that fire-protection and fire-resistive glazing units meet code requirements for fire-resistance-rated assembly and applicable safety glazing requirements.
2.Certificate on solar heat gain coefficient when value is specified.
3.Certificate on "R" value when value is specified.
4.Certificate test reports confirming compliance with specified bullet resistive rating.
5.Certificate that blast resistant glass meets the specified requirements.
D.Manufacturer Warranty.
E.Manufacturer's Literature and Data:
1.Glass, each kind required.
2.Insulating glass units.
3.Elastic compound for metal sash glazing.
4.Glazing cushion.
5.Sealing compound.
6.Plastic glazing material, each type required.
F.Samples:
1.Size: 305 mm by 305 mm (12 inches by 12 inches).
2.Tinted glass.
G.Preconstruction Adhesion and Compatibility Test Report: Submit glazing sealant manufacturer’s test report indicating glazing sealants were tested for adhesion to glass and glazing channel substrates and for compatibility with glass and other glazing materials.

1.6 DELIVERY, STORAGE AND HANDLING:

A.Delivery: Schedule delivery to coincide with glazing schedules so minimum handling of crates is required. Do not open crates except as required for inspection for shipping damage.
B.Storage: Store cases according to printed instructions on case, in areas least subject to traffic or falling objects. Keep storage area clean and dry.
C.Handling: Unpack cases following printed instructions on case. Stack individual windows on edge leaned slightly against upright supports with separators between each.
D.Protect laminated security glazing units against face and edge damage during entire sequence of fabrication, handling, and delivery to installation location. Provide protective covering on exposed faces of glazing plastics, and mark inside as "INTERIOR FACE" or "PROTECTED FACE":
1.Treat security glazing as fragile merchandise and packaged and shipped in export wood cases with width end in upright position and blocked together in a mass. Storage and handling to comply with manufacturer's directions and as required to prevent edge damage or other damage to glazing resulting from effects of moisture, condensation, temperature changes, direct exposure to sun, other environmental conditions, and contact with chemical solvents.
2.Protect sealed-air-space insulating glazing units from exposure to abnormal pressure changes, as could result from substantial changes in altitude during delivery by air freight. Provide temporary breather tubes which do not nullify applicable warranties on hermetic seals.
3.Temporary protections: The glass front and polycarbonate back of glazing are to be temporarily protected with compatible, peelable, heat-resistant film which will be peeled for inspections and reapplied and finally removed after doors and windows are installed at destination. Since many adhesives will attack polycarbonate, the film used on exposed polycarbonate surfaces is to be approved and applied by manufacturer.
4.Edge protection: To cushion and protect glass clad, from contamination or foreign matter, the four (4) edges are to be sealed the depth of glazing with continuous standardthickness thermoplastic rubber tape. Alternatively, continuous channel shaped extrusion of thermoplastic rubber are to be used, with flanges extending into face sides of glazing.
5.Protect "Constant Temperature" units including every unit where glass sheet is directly laminated to or directly sealed with metaltube type spacer bar to polycarbonate sheet, from exposures to ambient temperatures outside the range of 16 to 24 degrees C (60 to 75 degrees F), during the fabricating, handling, shipping, storing, installation, and subsequent protection of glazing.

1.7 PROJECT CONDITIONS:

Field Measurements: Field measure openings before ordering tempered glass products to assure for proper fit of field measured products.

1.8 warranty:

A. Construction Warranty: Comply with the FAR clause 52.24621 “Warranty of Construction”.

B. Manufacturer Warranty: Manufacturer shall warranty their glazing from the date of installation and final acceptance by the Government as follows. Submit manufacturer warranty.

1.Insulating glass units to remain sealed for ten (10) years.
2.Laminated glass units to remain laminated for five (5) years.

1.9 APPLICABLE PUBLICATIONS:

A. Publications listed below form a part of this specification to extent referenced. Publications are referenced in text by basic designation only.

B. American Architectural Manufacturers Association (AAMA):

800Test Methods for Sealants
810.1-77Expanded Cellular Glazing Tape
C.American National Standards Institute (ANSI):
Z97.1-14Safety Glazing Material Used in Building Safety Performance Specifications and Methods of Test
D.American Society of Civil Engineers (ASCE):
7-10Wind Load Provisions
E.ASTM International (ASTM):
C542-05(R2011)Lock-Strip Gaskets
C716-06Installing Lock-Strip Gaskets and Infill Glazing Materials
C794-10Adhesion-in-Peel of Elastomeric Joint Sealants
C864-05(R2011)Dense Elastomeric Compression Seal Gaskets, Setting Blocks, and Spacers
C920-14aElastomeric Joint Sealants
C964-07(R2012)Standard Guide for Lock-Strip Gasket Glazing
C1036-11(R2012)Flat Glass
C1048-12Heat-Treated Flat Glass-Kind HS, Kind FT Coated and Uncoated Glass.
C1172-14Laminated Architectural Flat Glass
C1349-10Standard Specification for Architectural Flat Glass Clad Polycarbonate
C1376-10Pyrolytic and Vacuum Deposition Coatings on Flat Glass
D635-10Rate of Burning and/or Extent and Time of Burning of Self-Supporting Plastic in a Horizontal Position
D4802-10Poly (Methyl Methacrylate) Acrylic Plastic Sheet
E84-14Surface Burning Characteristics of Building Materials
E119-14Standard Test Methods for Fire Test of Building Construction and Material
E1300-12aLoad Resistance of Glass in Buildings
E1886-13aStandard Test Method for Performance of Exterior Windows, Curtain Walls, Doors, and Impact Protective Systems Impacted by Missile(s) and Exposed to Cyclic Pressure Differentials
E1996-14aStandard Specification for Performance of Exterior Windows, Curtain Walls, Doors, and Impact Protective Systems Impacted by Windborne Debris in Hurricanes
E2141-12Test Methods for Assessing the Durability of Absorptive Electrochromic Coatings on Sealed Insulating Glass Units
E2190-10Insulating Glass Unit
E2240-06Test Method for Assessing the Current-Voltage Cycling Stability at 90 Degree C (194 Degree F) of Absorptive Electrochromic Coatings on Sealed Insulating Glass Units
E2241-06Test Method for Assessing the Current-Voltage Cycling Stability at Room Temperature of Absorptive Electrochromic Coatings on Sealed Insulating Glass Units
E2354-10Assessing the Durability of Absorptive Electrochromic Coatings within Sealed Insulating Glass Units
E2355-10Test Method for Measuring the Visible Light Transmission Uniformity of an Absorptive Electrochromic Coating on a Glazing Surface
F1233-08Standard Test Method for Security Glazing Materials and Systems
F1642-12Test Method for Glazing and Glazing Systems Subject to Airblast Loadings
F.Code of Federal Regulations (CFR):
16 CFR 1201-10Safety Standard for Architectural Glazing Materials
G.Glass Association of North America (GANA):
2010 EditionGANA Glazing Manual
2008 EditionGANA Sealant Manual
2009 EditionGANA Laminated Glazing Reference Manual
2010 EditionGANA Protective Glazing Reference Manual
H.International Code Council (ICC):
IBCInternational Building Code

I. Insulating Glass Certification Council (IGCC) J. Insulating Glass Manufacturer Alliance (IGMA):

TB-3001-13Guidelines for Sloped Glazing
TM-3000North American Glazing Guidelines for Sealed Insulating Glass Units for Commercial and Residential Use

K. Intertek Testing Services – Warnock Hersey (ITS-WHI) L. National Fire Protection Association (NFPA):

80-16Fire Doors and Windows
252-12Fire Tests of Door Assemblies
257-12Standard on Fire Test for Window and Glass Block Assemblies
M.National Fenestration Rating Council (NFRC)
N.Safety Glazing Certification Council (SGCC) 2012:
Certified Products Directory (Issued Semi-Annually).
O.Underwriters Laboratories, Inc. (UL):
9-08(R2009)Fire Tests of Window Assemblies
263-14Fire Tests of Building Construction and Materials
752-11Bullet-Resisting Equipment.
P.Unified Facilities Criteria (UFC):
4-010-01-03(R2007)DOD Minimum Antiterrorism Standards for Buildings
Q.U.S. Veterans Administration:
Physical Security Design Manual for VA Facilities (VAPSDG); Life Safety Protected
Physical Security Design Manual for VA Facilities (VAPSDG); Mission Critical Facilities
Architectural Design Manual for VA Facilities (VASDM)

R. Environmental Protection Agency (EPA):

40 CFR 59(2014) National Volatile Organic Compound Emission Standards for Consumer and Commercial Products

PART 2 - PRODUCT

2.1 GLASS:

A.Provide minimum thickness stated and as additionally required to meet performance requirements.
1.Provide minimum 6 mm (1/4 inch) thick glass units unless otherwise indicated.
B.Obtain glass units from single source from single manufacturer for each glass type.
C.Clear Glass:
1.ASTM C1036, Type I, Class 1, Quality q3 .

2.2 HEAT-TREATED GLASS:

A.Clear Tempered Glass:
1.ASTM C1048, Kind FT, Condition A, Type I, Class 1, Quality q3.

2.3 COATED GLASS:

A.Reflective-Coated Low-E Coated Tempered Glass:
1.ASTM C1376 and ASTM C1048, Kind FT, Condition C, Type I, Class 1, Quality q3 with reflective metallic coating.
B.Silicone Coated Spandrel Glass:
1.ASTM C1048, Kind HS or FT, Condition B, Type I, Quality q3 with silicone coating applied over glass surface.
2.Pattern as.

2.5 PLASTIC GLAZING:

A.Clear Acrylic Sheet:
1.ASTM D4802. Type UVF, Category A-1, clear, smooth both sides, and formulated with ultraviolet absorber.
2.Thickness, as .3mm (.125 inches).

2.6 LAMINATED GLASS:

A.Laminated Glass: ASTM C1172. Two or more lites of glass bonded with polyvinyl butyral, ionomeric polymer, or cast-in-place and cured-transparent-resin interlayer complying with interlayer manufacturer's written instructions.
B.Interlayer: Use 1.5 mm (0.060 inch) thick interlayer for:
1.Horizontal or sloped glazing.
2.Acoustical glazing.
3.Assemblies requiring heat strengthened or fully tempered glass.

2.7 INSULATING GLASS UNITS:

A.Provide factory fabricated, hermetically sealed glass unit consisting of two panes of glass separated by a dehydrated air space and comply with ASTM E2190.
B.Assemble units using glass types specified in Insulating Glass Schedule.

2.8 FIRE PROTECTION AND FIRE RESISTANCE GLAZING:

A.Fire-Protection-Rated Glazing: Glazing units tested for use in fire door assemblies or fire windows, UL, ITS-WHI or equivalent listed and labeled by testing agency in accordance with IBC, for fire-protection ratings as indicated on construction documents, based upon positive-pressure testing per NFPA 257 or UL 9, and complying with NFPA 80.
1.Hose-Stream Test: Units must comply, except units having fire-protection rating of 20 minutes.
2.Labeling: Permanently label fire-protection-rated glazing units in accordance with IBC.
3.Safety Glazing: Comply with 16 CFR 1201, Category II.
4.Fire-Protection-Rated Laminated Glass with Intumescent Interlayers: Units made from multiple lites of uncoated, ultra-clear (low-iron) float glass, in intumescent interlayers, of thickness and rating scheduled.
B.Fire-Resistance-Rated Glazing: Glazing units tested for use in fire wall assemblies, UL, ITS-WHI or equivalent listed and labeled by testing agency in accordance with IBC for fire-resistance ratings of wall assemblies as indicated on construction documents , based upon testing according to NFPA 252 and ASTM E119 or UL 263.
1.Labeling: Permanently label fire-resistance-rated glazing units in accordance with IBC.
2.Safety Glazing: Comply with 16 CFR 1201, Category II.
3.Fire-Resistance-Rated Laminated Glass with Intumescent Interlayers: Units made from multiple lites of uncoated, ultra-clear low-iron float glass, in intumescent interlayers, of thickness and rating scheduled.

2.9 GLAZING ACCESSORIES:

A.As required to supplement the accessories provided with the items to be glazed and to provide a complete installation. Ferrous metal accessories exposed in the finished work are to have a finish that will not corrode or stain while in service. Fire rated glazing to be installed with glazing accessories in accordance with the manufacturer’s installation instructions.
B.Setting Blocks: ASTM C864:
1.Silicone type.

2. Channel shape; having 6 mm (1/4 inch) internal depth.

3.Shore A hardness of 80 to 90 Durometer.
4.Block lengths: 50 mm (2 inches) except 100 to 150 mm (4 to 6 inches) for insulating glass.
5.Block width: Approximately 1.6 mm (1/16 inch) less than the full width of the rabbet.
6.Block thickness: Minimum 4.8 mm (3/16 inch). Thickness sized for rabbet depth as required.
C.Spacers: ASTM C864:
1.Channel shape having a 6 mm (1/4 inch) internal depth.
2.Flanges not less 2.4 mm (3/32 inch) thick and web 3 mm (1/8 inch) thick.
3.Lengths: 25 to 76 mm (1 to 3 inches).
4.Shore A hardness of 40 to 50 Durometer.
D.Glazing Tapes:
1.Semisolid polymeric based closed cell material exhibiting pressuresensitive adhesion and withstanding exposure to sunlight, moisture, heat, cold, and aging.
2.Shape, size and degree of softness and strength suitable for use in glazing application to prevent water infiltration.

3. Complying with AAMA 800 for the following types:

a. AAMA 810.1, Type 1, for glazing applications in which tape acts as the primary sealant.

b. AAMA 810.1, Type 2, for glazing applications in which tape is used in combination with a full bead of liquid sealant.

E.Spring Steel Spacer: Galvanized steel wire or strip designed to position glazing in channel or rabbeted sash with stops.
F.Glazing Gaskets: ASTM C864:
1.Firm dense wedge shape for locking in sash.
2.Soft, closed cell with locking key for sash key.
3.Flanges may terminate above the glazingbeads or terminate flush with top of beads.
G.Lock-Strip Glazing Gaskets: ASTM C542, shape, size, and mounting as indicated.
H.Glazing Sealants: ASTM C920, silicone neutral cure:
1.Type S.
2.Class 25 or 50 as recommended by manufacturer for application.
3.Grade NS.
4.Shore A hardness of 25 to 30 Durometer.

5. VOC Content: For sealants used inside the weatherproofing system, not more than 250 g/L or less when calculating according to 40 CFR 59, (EPA Method 24).

I.Structural Sealant: ASTM C920, silicone acetoxy cure:
1.Type S.
2.Class 25.
3.Grade NS.
4.Shore a hardness of 25 to 30 Durometer.
J.Neoprene, EPDM, or Vinyl Glazing Gasket: ASTM C864.
1.Channel shape; flanges may terminate above the glazing channel or flush with the top of the channel.
2.Designed for dry glazing.
K.Color:
1.Color of glazing compounds, gaskets, and sealants used for aluminum color frames to match color of the finished aluminum and be nonstaining.
2.Color of other glazing compounds, gaskets, and sealants which will be exposed in the finished work and unpainted are to be black, gray, or neutral color.
L.Smoke Removal Unit Targets: Adhesive targets affixed to glass to identify glass units intended for removal for smoke control. Comply with requirements of local Fire Department.

PART 3 - EXECUTION

3.1 EXAMINATION:

A.Verification of Conditions:
1.Examine openings for glass and glazing units; determine they are proper size; plumb; square; and level before installation is started.
2.Verify that glazing openings conform with details, dimensions and tolerances indicated on manufacturer is approved shop drawings.
B.Review for conditions which may adversely affect glass and glazing unit installation, prior to commencement of installation. Do not proceed with installation until unsatisfactory conditions have been corrected.
C.Verify that wash down of adjacent masonry is completed prior to erection of glass and glazing units.

3.2 PREPARATION:

A.For sealant glazing, prepare glazing surfaces in accordance with GANA Sealant Manual.
B.Determine glazing unit size and edge clearances by measuring the actual unit to receive the glazing.
C.Shop fabricate and cut glass with smooth, straight edges of full size required by openings to provide GANA recommended edge clearances.
D.Verify that components used are compatible.
E.Clean and dry glazing surfaces.
F.Prime surfaces scheduled to receive sealants, as determined by preconstruction sealant-substrate testing.

3.3 INSTALLATION – GENERAL:

A.Install in accordance with GANA Glazing Manual, GANA Sealant Manual, IGMA TB-3001, and IGMA TM-3000 unless specified otherwise.
B.Glaze in accordance with recommendations of glazing and framing manufacturers, and as required to meet the Performance Test Requirements specified in other applicable sections of specifications.
C.Set glazing without bending, twisting, or forcing of units.
D.Do not allow glass to rest on or contact any framing member.
E.Glaze doors and operable sash, in a securely fixed or closed and locked position, until sealant, glazing compound, or putty has thoroughly set.
F.Tempered Glass: Install with roller distortions in horizontal position unless otherwise directed.
G.Plastic:
1.Use dry glazing method.
2.Use only neoprene or EPDM gaskets.
H.Laminated Glass:
1.Tape edges to seal interlayer and protect from glazing sealants.
2.Do not use putty or glazing compounds.
I.Insulating Glass Units:
1.Glaze in compliance with glass manufacturer's written instructions.
2.When glazing gaskets are used, they are to be of sufficient size and depth to cover glass seal or metal channel frame completely.
3.Do not use putty or glazing compounds.
4.Do not grind, nip, cut, or otherwise alter edges and corners of fused glass units after shipping from factory.
5.Install with tape or gunnable sealant in wood sash.
J.Fire Protective and Fire Resistance Glass:
1.Wire Glass: Glaze in accordance with NFPA 80.
2.Other fire protective and fire-resistant glass: Glaze in accordance with manufacturer’s installation instructions and NFPA 80.

3.5 INSTALLATION DRY METHOD (TAPE AND GASKET SPLINE GLAZING):

A.Cut glazing tape to length; install on glazing pane. Seal corners by butting and sealing junctions with butyl sealant.
B.Place setting blocks at 1/4 points with edge block no more than 150 mm (6 inches) from corners.
C.Rest glazing on setting blocks and push against fixed stop with sufficient pressure to attain full contact.
D.Install removable stops without displacing glazing spline. Exert pressure for full continuous contact.
E.Do not exceed edge pressures stipulated by glass manufacturers for installing glass lights.
F.Trim protruding tape edge.

3.6 INSTALLATION WET/DRY METHOD (PREFORMED TAPE AND SEALANT)

A.Cut glazing tape to length and set against permanent stops, 5 mm (3/16 inch) below sight line. Seal corners by butting tape and dabbing with butyl sealant.
B.Apply heel bead of butyl sealant along intersection of permanent stop with frame ensuring full perimeter seal between glass and frame to complete the continuity of the air and vapor seal.
C.Place setting blocks at 1/4 points with edge block no more than 152 mm (6 inches) from corners.
D.Rest glazing on setting blocks and push against tape and heel bead of sealant with sufficient pressure to achieve full contact at perimeter of pane or glass unit.
E.Install removable stops, with spacer strips inserted between glazing and applied stops, 6 mm (1/4 inch) below sight line. Place glazing tape on glazing pane or unit with tape flush with sight line.
F.Fill gap between glazing and stop with sealant to depth equal to bite of frame on glazing, but not more than 9 mm (3/8 inch) below sight line. Sealant type is to be compatible with glazing tape.
G.Apply cap bead of sealant along void between the stop and the glazing, to uniform line, flush with sight line. Tool or wipe sealant surface smooth.

3.7 INSTALLATION WET METHOD (SEALANT AND SEALANT):

A.Place setting blocks at 1/4 points and install glazing pane or unit.
B.Install removable stops with glazing centered in space by inserting spacer shims both sides at 600 mm (24 inch) intervals, 6 mm (1/4 inch) below sight line.
C.Fill gaps between glazing and stops with sealant to depth of bite on glazing, but not more than 9 mm (3/8 inch) below sight line to ensure full contact with glazing and continue the air and vapor seal.
D.Apply sealant to uniform line, flush with sight line. Tool or wipe sealant surface smooth.

3.8 INSTALLATION INTERIOR WET/DRY METHOD (TAPE AND SEALANT):

A.Cut glazing tape to length and install against permanent stops, projecting 1.6 mm (1/16 inch) above sight line.
B.Place setting blocks at 1/4 points with edge block no more than 150 mm (6 inches) from corners.
C.Rest glazing on setting blocks and push against tape to ensure full contact at perimeter of pane or unit.
D.Install removable stops, spacer shims inserted between glazing and applied stops at 600 mm (24 inch) intervals, 6 mm (1/4 inch) below sight line.
E.Fill gaps between pane and applied stop with sealant to depth equal to bite on glazing, to uniform and level line. Sealant type is to be compatible with glazing tape.
F.Trim protruding tape edge.

3.9 INSTALLATION INTERIOR WET METHOD (COMPOUND AND COMPOUND):

A.Install glazing resting on setting blocks. Install applied stop and center pane by use of spacer shims at 600 mm (24 inch) centers, kept 6 mm (1/4 inch) below sight line.
B.Locate and secure glazing pane using glazers' clips.
C.Fill gaps between glazing and stops with glazing compound until flush with sight line. Tool surface to straight line.

3.10 REPLACEMENT AND CLEANING:

A.Clean new glass surfaces removing temporary labels, paint spots, and defacement after approval by COR.
B.Replace cracked, broken, and imperfect glass, or glass which has been installed improperly.
C.Leave glass, putty, and other setting material in clean, whole, and acceptable condition.

3.11 PROTECTION:

A. Protect finished surfaces from damage during erection, and after completion of work. Strippable plastic coatings on colored anodized finish are not acceptable.

3.12 MONOLITHIC GLASS SCHEDULE:

A. Glass Type MG#1: Clear fully tempered float glass.

1. Unit Thickness: 6 mm (0.23 inch).

2. Safety glazing label required.

3.13 INSULATING LAMINATED GLASS SCHEDULE (FORCE PROTECTION AND PHYSICAL SAFETY):

A.Glass Type IL#3: Low-E-coated, clear insulating laminated glass.
1.Overall Unit Thickness: 25 mm (1 inch) .
2.Outdoor Lite: Clear annealed float glass, except heat-strengthened float glass where required, and fully tempered float glass where indicated.
a.Minimum Thickness of Outdoor Lite: 6 mm (0.23 inch).
3.Interspace Content: Argon.
4.Indoor Lite: Clear laminated glass with two lites of annealed float glass, except heat-strengthened float glass where required, and fully tempered float glass where indicated.
a.Minimum Thickness of Each Glass Lite: 6 mm (0.23 inch).
b.Interlayer Thickness: 1.52 mm (0.060 inch).
5.Low-E Coating: Sputtered on second surface.
6.Visible Light Transmittance: 70-65 percent minimum.
7.Solar Heat Gain Coefficient: 30 maximum.
8.Safety glazing label required.

3.14 FIRE-PROTECTIVE AND FIRE-RESISTANCE GLAZING SCHEDULE:

A.Glass Type FR#1: Fire-protection-rated Fire-resistance-rated laminated glass with intumescent interlayers.
1.Thickness: 6 mm (0.23 inch).
2.Rating: 45-, 60-, 90-, 120- minute.
3.Application: Fire-protection-rated door and window assemblies, Fire-resistance-rated wall assemblies.

- - - E N D - - - 08 80 00 - 16