This document contains a revised response to a solicitation for fire alarm testing and monitoring services at a Department of Veterans Affairs medical center. The solicitation requires testing for all new devices installed under the project scope and 10% of existing device types, per NFPA 72 standards. Coordination is required with the Contracting Officer's Representative and facility fire and life safety specialist to ensure compliance. Alarm signals were received for buildings 77 and 69 on August 24, 2021, with response times of 33 seconds and 25 seconds respectively. The related federal contract opportunity is for renovation of Building 77 to provide customer service space. The magnitude of construction is estimated between $500,000 and $1,000,000. The soliciting agency is the VA Veterans Health Administration VISN 9.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Solicitation 36C24921B0018 VA Revised Response 12/10/2021
Testing is required for all new devices installed under project scope and 10% of existing devices types in that system per NFPA 72. See attached "JHQVAMC Fire Alarm Report Building 77 & 69 August 2021" for reference. Coordinate with COR and facility fire life safety specialist to ensure compliance.
VA Security received an alarm signal for building 77 and 69.
Simplex monitoring received an alarm signal for building 77 on 8/24/21 at 17:04:43. Alarm was sent at 17:04:10. 33 seconds.
Simplex monitoring received an alarm signal for building 69 on 8/24/21 at 17:05:25. Alarm was sent at 17:05:00. 25 seconds.
Account # 212-8419 Zone 810 Building 77 - Zone 811 Building 69