About this file

This document contains a revised response to a solicitation for fire alarm testing and monitoring services at a Department of Veterans Affairs medical center. The solicitation requires testing for all new devices installed under the project scope and 10% of existing device types, per NFPA 72 standards. Coordination is required with the Contracting Officer's Representative and facility fire and life safety specialist to ensure compliance. Alarm signals were received for buildings 77 and 69 on August 24, 2021, with response times of 33 seconds and 25 seconds respectively. The related federal contract opportunity is for renovation of Building 77 to provide customer service space. The magnitude of construction is estimated between $500,000 and $1,000,000. The soliciting agency is the VA Veterans Health Administration VISN 9.

View the file

Other files

File Type Posted
36C24921B0018 0005.docx DOCX document
36C24921B0018 0004.docx DOCX document
Drawing_BLDG77_FIRE_FA102_Amdt001.pdf PDF
01 00 00 GENERAL REQUIREMENTS AMEND 001 12-06-21.pdf PDF
Government Answers to Industry Questions V2 12-07-2021.pdf PDF
Spec_BLDG 77_07 81 00 APPLIED FIREPROOFING_Amdt001.pdf PDF
PN621-20-113 QA Attachment.pdf PDF
621-20-103 SOW AMEND 001 12-06-2021.pdf PDF
Spec_BLDG77_01 33 23_Attachment - Submittal Register_Amdt001.pdf PDF
Spec_BLDG77_00 01 10 TABLE OF CONTENTS_Amdt001.pdf PDF
Drawing_BLDG77_STRC_S-501_Amdt001.pdf PDF
36C24921B0018 0003.docx DOCX document
Amend Rpt 001_621-20-103 Bldg 77 for Cust Serv_12.06.2021.pdf PDF
36C24921B0018 0002.docx DOCX document
SITE VIST - MOU Renovate Bldg. 77 for Customer Service_SignInSheet.pdf PDF
36C24921B0018 0001.docx DOCX document
WD TN20210111 1-1-2021.pdf PDF
621-20-103 Bid Drawings_Revised 11-03-2021.pdf PDF
621-20-103 Bid Specs Volume 2.pdf PDF
VHA Supp Contract Req Ensuring Adequate COVID-19 Safety Protocols for Federal Contractors.pdf PDF
Contractor EMR Certification Form.docx DOCX document
36C24921B0018_1.docx DOCX document
621-20-103 Bid Specs Volume 1 Rev 11-03-2021.pdf PDF
RFI Form - Renovate Bldg. 77.docx DOCX document
Show all 24

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Solicitation 36C24921B0018 VA Revised Response 12/10/2021

Testing is required for all new devices installed under project scope and 10% of existing devices types in that system per NFPA 72. See attached "JHQVAMC Fire Alarm Report Building 77 & 69 August 2021" for reference. Coordinate with COR and facility fire life safety specialist to ensure compliance.

VA Security received an alarm signal for building 77 and 69.

Simplex monitoring received an alarm signal for building 77 on 8/24/21 at 17:04:43. Alarm was sent at 17:04:10. 33 seconds.

Simplex monitoring received an alarm signal for building 69 on 8/24/21 at 17:05:25. Alarm was sent at 17:05:00. 25 seconds.

Account # 212-8419 Zone 810 Building 77 - Zone 811 Building 69