This document package includes construction drawings and details for the renovation of Building 77 at the Veterans Affairs Medical Center in Mountain Home, Tennessee, as well as the related federal contract opportunity solicitation. The drawings show proposed structural, mechanical, and architectural details for renovating the building to accommodate a new customer service area, including installation of new cold-formed metal framing to support mechanical equipment and infill concrete slabs. The related solicitation is for contract number 36C24921B0018, with a value between $500,000 and $1,000,000, to renovate Building 77 for customer service use. The soliciting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9. The response due date and award date are not provided.

View the file

Other files

Show all 24

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A

A

DETAIL A-A

1/2" DIA. ADHESIVE ANCHORS

W. 3" EMBED IN HORIZ.

SHORT SLOTTED HOLES IN

STEEL ANGLE INTO EXIST.

CONCRETE ARCH

L8x4x7/16 CONT STEEL

ANGLE LEDGER

COLD FORMED

METAL JOIST

BOX BEAM

NOTE: LOCATE VERTICAL AND

HORIZONTAL

REINFORCEMENT IN EXIST.

CONCRETE BEAM USING NON-

DESTRUCTIVE TECHNIQUES.

ADJUST LOCATION OF

ANCHORS TO AVOID

REINFORCEMENT

3/8" STIFFENER PLATE

6" 6"

3/16

COLD FORMED METAL

JOIST BOX BEAM

SURFACE - SEE PLAN

ATTACHMENT TO STEEL ANGLE

COLD FORMED STEEL TRACK

A

A

DETAIL A-A

1/2" DIA. ADHESIVE ANCHORS

W. 3" EMBED IN HORIZ.

SHORT SLOTTED HOLES IN

STEEL ANGLE INTO EXIST.

CONCRETE ARCH

L8x4x7/16 CONT STEEL

ANGLE LEDGER

COLD FORMED

METAL JOISTS

1'-0" 1'-0"

NOTE: LOCATE VERTICAL AND

HORIZONTAL REINFORCEMENT IN

EXIST. CONCRETE BEAM USING NON-

DESTRUCTIVE TECHNIQUES. ADJUST

LOCATION OF ANCHORS TO AVOID

REINFORCEMENT

6" SPLICE AS REQUIRED

SURFACE - SEE PLAN

ATTACHMENT TO STEEL ANGLE

COLD FORMED STEEL TRACK

A

A

DETAIL A-A

3/8" DIA. ADHESIVE

ANCHORS W. 3 1/8" EMBED

IN STEEL ANGLE INTO

EXIST. BRICK VENEER

L6x4x5/16 CONT STEEL

ANGLE LEDGER

COLD FORMED

METAL JOISTS

1'-0" 1'-0"

6" SPLICE AS REQUIRED

ATTACHMENT TO

STEEL ANGLE

COLD FORMED

STEEL TRACK

A

A

DETAIL A-A

1/2" DIA. ADHESIVE ANCHORS W. 3" EMBED IN

HORIZ. LONG SLOTTED HOLES IN STEEL ANGLE

INTO EXIST. CONCRETE ARCH

L8x6x7/16 x 12" LONG SEAT (LLV)

UNISTRUT P1000, ATTACH

TO HSS W. #12 SELF

DRILLING SCREWS AT EACH

END AND @ 12" O.C. MAX IN

BETWEEN

NOTE:

1. LOCATE VERTICAL AND HORIZONTAL REINFORCEMENT

IN EXIST. CONCRETE BEAM USING NON-DESTRUCTIVE

TECHNIQUES. ADJUST LOCATION OF ANCHORS TO

AVOID REINFORCEMENT.

2. HORIZ SLOTTED HOLES PROVIDED IN VERTICAL LEG

OF SEAT TO ASSIST IN FIELD FIT UP

3/8" STIFFENER

PLATE

/2

3/16

5 1/2" 1/2"HSS8x4x1/4 BEAM B

B

SOUND BAFFLE, LIGHT BAFFLE, OR

PENDANT LIGHT - SEE PLANS AND

ARCHITECTURAL AND ELECTRICAL

DRAWINGS. SEE MANUFACTURER'S

INSTRUCTION FOR ATTACHMENT TO

UNISTRUT OR HSS BEAM

2 1/2" 7" 2 1/2"

6" 6"

(3/16)

3"

1/2x 5 1/2x 12 PLATE1/2” DIA. THROUGH BOLTS IN

HORIZ. SHORT SLOTTED HOLES,

SNUG-TIGHT

DETAIL B-B

SOUND BAFFLE

3/16 3@12

TYP.

3/16

TYP.

EXIST. BEAM,

SEE PLAN

EXIST. BEAM,

SEE PLAN

L6x4x1/4

L6x4x1/4

L x x /4

L x x /4

EXIST. W-

SECTION BEAM,

SEE PLAN

EXIST. W-

SECTION BEAM,

SEE PLAN

3/16

TYP.

A A

VIEW A-A

PLAN VIEW

NOTES:

1. COORDINATE SIZE AND LOCATION OF NEW STEEL FRAMING WITH EQUIPMENT CURB BY MECHANICAL

CONTRACTOR. CURB SHALL BE SUPPORTED ON ALL SIDES.

2. ANCHOR EQUIPMENT AND CURB TO NEW STEEL FRAMING OR CONCRETE SLAB AS REQUIRED FOR WIND

AND/OR SEISMIC FORCES. COORDINATE WITH EQUIPMENT/CURB MANUFACTURER.

3. NOTIFY CONTRACTING OFFICER IF EQUIPMENT SIZE AND/OR WEIGHT (INCLUDING CURB) EXCEEDS WEIGHT

NOTED ON PLANS.

4. ALL EXTERIOR STRUCTURAL STEEL TO BE HOT-DIPPED GALVANIZED w/MIN. G60 COATING.

5. FIELD VERIFY EXISTING CEMENTITIOUS FIREPROOFING AT THESE LOCATIONS. REMOVE FIREPROOFING AS

REQUIRED TO ALLOW NEW STEEL INSTALLATION. REPLACE REMOVED OR DAMAGED FIREPROOFING AT EXISTING MEMBERS AND APPLY NEW FIREPROOFING TO NEW STEEL MEMBERS. MATCH EXISTING.

COPE HORIZONTAL

LEG OF ANGLEMAX

1"

M A

X

/2

MECHANICAL UNIT

AND CURB

MECHANICAL UNIT

ATTACHMENT PER MFR'S

INSTRUCTIONS W. THROUGH

BOLT INTO ANGLE OR ADHESIVE

INTO CONCRETE

CONCRETE OR INSULATION

ON METAL DECK.

CONTRACTOR TO FIELD

VERIFY AND ADJUST

ATTACHMENT AS SPECIFIED

BY EQUIP MFR. TO WORK

WITH EITHER CONDITION

PROVIDE CONTROL JOINTS AT CORNERS

TO AVOID REENTRANT CORNERS

WIDTH

PANEL

L E

N G

T H

P A

N E

L

C J

C J

C J

C J

CJ

CJ

C J

CJ

CONTROL JOINTS SHALL BE DETERMINED BY THE CONTRACTOR USING THE FOLLOWING

GUIDELINES PROVIDED IN THIS DETAIL.

INDIVIDUAL SLAB PANELS ARE DEFINED AS SECTIONS OF SLAB BOUNDED BY CONTROL JOINTS

THAT FORM A SQUARE OR RECTANGLE.

MATCH EXISTING JOINT LAYOUT IN STUCTURED CONCRETE FLOOR SLAB BELOW. THEN LOCATE

CONTROL JOINTS SUCH THAT THE ASPECT RATIO OF EACH PANEL IS AS CLOSE TO 1:1

(WIDTH/LENGTH) AS POSSIBLE BUT NO GREATER THAN 1:1.5. PANELS SHALL NOT EXCEED 6'-0" IN

WIDTH OR LENGTH.

INFORMATION SHOWN WITHIN THIS DETAIL IS ONLY INTENDED TO PROVIDE A SCHEMATIC

CONTROL JOINTS LAYOUT TO ILLUSTRATE HOW JOINTS ARE TO BE LOCATED.

SEE DETAIL D3/S-501 FOR TYPICAL INFILL SLAB CONTROL JOINT.

CONTACT THE COR FOR FURTHER GUIDANCE OF CONTROL JOINT LOCATIONS IF NEEDED.

L E

N G

T H

P A

N E

L

WIDTH

PANEL

NOTES:

1.

2.

3.

4.

5.

6.

CJ

C J

6'-0" MAX. (TYP.)

SAW CUT JOINT 1/8" WIDE x

ONE-QUARTER SLAB

THICKNESS DEEP, FILL

JOINT WITH SEALANT. DO

NOT CUT REINFORCEMENT

EXISTING CONCRETE SLAB

NOTES:

1.

2.

SLAB SHALL BE SAWN AS SOON AS THE CONCRETE WILL SAFELY SUPPORT WORKERS AND EQUIPMENT.

FILL JOINT WITH SEALANT AFTER SLAB HAS CURED.

INFILL SLAB

F E

A T

H E

R E

D G

E M

IN

V A

R

IE

S

M

A X

ROUGHEN AND CLEAN EXISTING

SURFACE, APPLY BONDING AGENT

OR ADHESIVE

PROVIDE CONTROL JOINTS

PER F3/S-501 COLD FORMED

METAL JOISTS

BEARING ON

STUD WALL

EACH END

COLD FORMED

STEEL TRACK

STRONG BACK,

MIN. TWO PER

SPAN

COLD FORMED BOX

BEAM WITH STUD

PACK EACH END

WINDOW OR DOOR

COLD FORMED

STEEL KICKER

COLD FORMED STEEL

PARAPET/ SOFFIT

COLD FORMED

STEEL STUD WALL

ACT CEILING

COLD FORMED STEEL

KICKER ALTERNATE OR

ADDITIONAL LOCATION

COLD FORMED BOX

BEAM ALTERNATE OR

ADDITIONAL LOCATION

WITH STUD PACK EACH

END

FOR DEDUCTIVE ALTERNATE #2,

REMOVE BOX BEAM AND

REPLACE WITH METAL WALL

STUDS AND HEADERS OVER

DOOR OPENINGS.

EXISTING

ATRIUM WALL

GAP

1"

COLD FORMED METAL

JOISTS BEARING ON STUD

WALL EACH END

COLD FORMED

STEEL TRACK

COLD FORMED

STEEL KICKER

AS REQURED COLD FORMED

STEEL WALL

COLD FORMED

STEEL STUD WALL

ACT CEILING

SURFACE - SEE

PLAN

GAP

1"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

VAMC MOUNTAIN HOME, TN

B

IM

/1

V

A C u s to m e r

S e rv ic e B

L D

G

/1

V

A B

L D

G S

T R

C v .r v t

/3

/2

:0 :0

P

M

S-501

SECTIONS AND DETAILS RENOVATE BUILDING 77 FOR

CUSTOMER SERVICE

621-20-103

JUNE 23, 2021 R NEW A BOOTH

BID DOCUMENTS

Revisions: Date:

Revision 1 2021/12/06

SCALE: N.T.S.B1

BEAM AND LEDGER AT CONCRETE

SCALE: N.T.S.D1

JOISTS AND LEDGER AT CONCRETE

SCALE: N.T.S.F1

JOISTS AND LEDGER AT BRICK

SCALE: N.T.S.B3

BAFFLE AND LIGHT SUPPORT BEAM AT CONCRETE BEAM

SCALE: N.T.S.B6

TYPICAL FRAME AT MECHANICAL UNIT SUPPORT

SCALE: N.T.S.F3

TYPICAL FRAME AT MECHANICAL UNIT SUPPORT

SCALE: N.T.S.D3

TOPPING SLAB

SCALE: N.T.S.D7

JOISTS AT EDGE OF OFFICES

SCALE: N.T.S.F7

JOISTS AT EDGE OF WAITING AREA

Sheets
S-501 - SECTIONS AND DETAILS