This federal solicitation requests bids for a chilled water loop upgrade project at a Veterans Affairs medical center. The contractor will install a new pump in parallel with two existing pumps to increase pumping capacity. The contractor will also install a new Eaton VFD to match two existing VFDs, rewire the power feed, and integrate new DDC controls with BACnet communication into the existing BAS. The project is a 100% SDVOSB set-aside with a 120-day period of performance from notice to proceed. The solicitation was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
H-Max™ HVAC Drives
Quick Start Guide
Effective September 2011
Supersedes August 2011
H-Max HVAC Drives
MN04008004E—September 2011 www.eaton.com i
Disclaimer of Warranties and Limitation of Liability
The information, recommendations, descriptions, and safety notations in this document are based on Eaton Electrical Inc. and/or Eaton Corporation’s (“Eaton”) experience and judgment, and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted.
Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser.
THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR
IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR
MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING
CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE
OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME
PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental, or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations, and descriptions contained herein.
The information contained in this manual is subject to change without notice.
Cover Photo: Eaton H-Max HVAC Drives ii H-Max HVAC Drives
Support Services
The goal of Eaton is to ensure your greatest possible satisfaction with the operation of our products. We are dedicated to providing fast, friendly, and accurate assistance. That is why we offer you so many ways to get the support you need. Whether it’s by phone, fax, or e-mail, you can access Eaton’s support information 24 hours a day, seven days a week.
Our wide range of services is listed below.
You should contact your local distributor for product pricing, availability, ordering, expediting, and repairs.
Web Site
Use the Eaton Web site to find product information. You can also find information on local distributors or Eaton’s sales offices.
Web Site Address www.eaton.com/electrical
EatonCare Customer Support Center
Call the EatonCare Support Center if you need assistance with placing an order, stock availability or proof of shipment, expediting an existing order, emergency shipments, product price information, returns other than warranty returns, and information on local distributors or sales offices.
Voice: 877-ETN-CARE (386-2273) (8:00 a.m.–6:00 p.m. EST)
FAX: 800-752-8602
After-Hours Emergency: 800-543-7038 (6:00 p.m.–8:00 a.m. EST) If you are in the U.S. or Canada, and have OI or PLC questions, you can take advantage of our toll-free line for technical assistance with hardware and software product selection, system design and installation, and system debugging and diagnostics. Technical support engineers are available for calls during regular business hours.
Technical Resource Center
Voice: 877-ETN-CARE (386-2273) (8:00 a.m.–5:00 p.m. EST)
FAX: 828-651-0549
e-mail: TRC@Eaton.com
European PanelMate Support Center
This engineering company, located in Zurich, Switzerland, provides high-level quality support and repair assistance for your PanelMate products. You will receive technical and application support.
For Customers in Europe, contact:
BFA Solutions, Ltd.
Voice: +41 1 806.64.44 (9:00 a.m.–5:00 p.m. CET) e-mail: gk@bfa.ch www.bfa.ch
Repair and Upgrade Service
Additional support is also available from our well-equipped Repair and Upgrade Service department. If you have questions regarding the repair or upgrade of an OI product, contact your local distributor.
Repair and Upgrade Service (support for OI)
Voice:
877-ETN-CARE (877-386-2273) (8:00 a.m.–5:00 p.m. EST) 414-449-7100 (8:00 a.m.–5:00 p.m. EST)
FAX: 614-882-3414
e-mail: TRC@eaton.com
HVAC Application
The Eaton HVAC drive contains a preloaded application for instant use.
The parameters of this application are listed in the complete Application Manual.
The Application Manual can be found at http://www.eaton.com/Electrical/ USA/ProductsandServices/AutomationandControl/ AdjustableFrequencyDrives/H-Max/index.htm.
Specific Functions of Eaton HVAC Application
The Eaton HVAC application is an easy-to-use application for not only basic pump and fan applications where only one motor and one drive is needed, but also offers extensive possibilities for PID control.
Features
Startup Wizard for extremely fast setup for basic pump or fan applications
Mini-Wizards to ease the setup of applications
Hand/Off/Auto button for easy change between Hand (keypad), OFF, and Auto (Remote control) place. The auto control place is selectable by parameter (I/O or Fieldbus)
Control page for easy operation and monitoring of the most essential values
Run interlock input (damper interlock). Drive will not start before this input is activated
Different pre-heat modes used to avoid condensation problems
Maximum output frequency 320 Hz
Real-time clock and timer functions available (optional battery required). Possible to program three time channels to achieve different functions on the drive (for example, Start/Stop and Preset frequencies)
External PID-controller available. Can be used to control a valve using the drive’s I/O, for example
Sleep mode function which automatically enables and disables drive running with user defined levels to save energy
Two-zone PID-controller (two different feedback signals;
minimum and maximum control)
Two setpoint sources for the PID-control. Selectable with digital input
PID setpoint boost function
Feed forward function to improve the response to the process changes
Process value supervision
Multi-pump control
Pressure loss compensation for compensating pressure losses in the pipework, for example, when sensor is incorrectly placed near the pump or fan
2 H-Max HVAC Drives
Example of Control Connections
Control Connections
Slot A
A
+10V
AI–1+
Vin
AI–2+
AI–2–
24Vout
GND
DIN1
DIN2
DIN3
24Vout
GND
DIN4
DIN5
DIN6
AO–1+
AO–1–
DATA–
Reference Output Analog Input Voltage (Range 0–10 Vdc) (can be programmed to current 4–20 mA) Analog Output Common (Ground)
Analog Input Common PI Setpoint or Feedback Control Voltage Output (0.1A max.)
I/O Ground
START/STOP (Contact closed = start)
External Fault (Closed = fault) Run Interlock Permissive IP Interlock (Closed = OK) DIN1–DIN6 Common
Control Voltage Output (0.1A max.)
I/O Ground
Fire Mode (Contact closed = fire mode)
Force Bypass (Contact closed = bypass)
DIN1–DIN6 Common
Output Frequency (0–20 mA)
Analog Output Common (Ground)
RS-485 DATA–
Speed Select 0–100% (Preset speed)
U (T1)
V (T2)
W (T3)
R+
R–
L1
L2
L3
Three-Phase Input Input (Single-Phase not available)
Three-Phase Output
DB
Chopper
Terminal Factory Default Signal
Resistor
Analog Input Current (Range 4–20 mA) (can be programmed to voltage 0–10 Vdc) PI Setpoint or Feedback
B DATA+
RO1 Bypass Run
RO2 Drive Run
RO3 Fault
24 Vdc/8A 250 Vac/8A 125 Vdc/0.4A
Relay Board 1 Default Signal
Slot B
Analog
RS-485 DATA+
Factory Jumper
COM
CMB
30 24 Vdcin Auxiliary Input Voltage
Circuit Breaker
Optional
Motor
RJ-45 BACnet/IP Ethernet Industrial Protocol Modbus/TCP Transmission Control Protocol (Ethernet Based)
5% DC Link Reactor
Programmable BACnet, Modbus, FLN, N2
ON
CURRENT
CURRENT
CURRENT
RS485
AO1
AI2
AI1
OFF
VOLTAGE
VOLTAGE
VOLTAGE
Test
Keypad of the Drive
The control keypad is the interface between the Eaton H-MAX frequency converter and the user. With the control keypad it is possible to control the speed of a motor, to supervise the state of the equipment and to set the frequency converter’s parameters.
There are two different keypads used with the H-MAX drive.
The North American Keypad is slightly different than the EMEA Keypad. Functionality is quite similar. The EMEA keypad does not support the bypass functionality commonly used in the United States.
US Keypad Buttons
EMEA Keypad Buttons
Switching Between Drive and Bypass
Move Cursor Left Back when Pressed for two Seconds
Stop Button/Fault Reset Start Button
Change Control Place Between Hand-Off-Auto
Move Cursor Right
Increase Value Scroll Menu Up
Decrease Value Scroll Menu Down
Enter Menu Confirm Selection
Back Fault Reset
Move Cursor Left
Stop Button Start Button
Change Control Place Between Hand-Off-Auto
Move Cursor Right
Increase Value Scroll Menu Up
Decrease Value Scroll Menu Down
Enter Menu Confirm Selection
4 H-Max HVAC Drives
Keypad Display
The keypad display indicates the status of the motor and the drive and any irregularities in motor or drive functions. On the display, the user sees information about his present location in the menu structure and the item displayed.
Main Menu
The data on the control keypad are arranged in menus and submenus. Use the up and down arrows to move between the menus. Enter the group/item by pressing the OK button and return to the former level by pressing the Back/Reset button.
The
Location field indicates your current location. The
Status field gives information about the present status of the drive. See “Control Connections” on
Main Menu
Using the Graphical Keypad
Editing Values
Change value of a parameter following the procedure below:
1. Locate the parameter.
2. Enter the
Edit mode.
3. Set new value with the up/down arrow buttons. You can also move from digit to digit with the arrow buttons left/right if the value is numerical and then change the value with the up/down arrow buttons.
4. Confirm change with OK button or ignore change by returning to previous level with Back/Reset button.
Status Field
STOP/RUN
STOP E-Energy Hand I/O
Direction Run Mode
Hand/Off/Auto
Control Place
PC/IO/KEYPAD/FIELDBUS
Location Field (Parameter ID number and current menu location)
Activated Group/Item Press OK to Enter
Editing Values on Graphical Keypad
HOA Control Button
The HOA (Hand-Off-Auto) button is used for two functions:
to quickly access the Control page and to easily change between the Hand (Keypad), Off, and Auto (Remote) control places.
Control Place control place is the source of control where the drive can be started and stopped. Every control place has its own parameter for selecting the frequency reference source. In the HVAC drive, the
Hand control place is always the keypad.
Auto control place is determined by parameter P2.1.1 (Keypad, I/O Terminal, I/O three-wire, or Fieldbus CTRL). The selected control place can be seen on the status bar of the keypad.
Local Control
The keypad is always used as control place while in hand control. Hand control has higher priority than auto control.
Therefore, if, for example, bypassed by parameter P2.1.17 through digital input while in
Remote
, the control place will still switch to Keypad if
Hand is selected. Switching between Hand, Off, and Auto Control can be done by pressing the HOA button on the keypad.
Changing Control Place
Change of control place from to
Auto
(keypad).
1. Anywhere in the menu structure, push the HOA button.
2. Push the arrow up or the arrow down button to select
Hand/Off/Auto and confirm with the OK button.
3. On the next display, select
Off
, or
Auto and again confirm with the
OK
button.
4. The display will return to the same location as it was when the
HOA
button was pushed. However, if the Remote control place was changed to Hand (Keypad) you will be prompted for keypad reference.
STOP READY I/O
STOP READY I/O
STOP READY I/O
OK OK
OK
STOP READY I/O
STOP READY I/O
OR:
BACK
RESET
6 H-Max HVAC Drives
Accessing the Control Page
Control page is meant for easy operation and monitoring of the most essential values.
1. Anywhere in the menu structure, push the
2. Push the arrow up or the arrow down button to select
Control page and confirm with the
3. The control page appears. If keypad control place and keypad reference are selected to be used, you can set the
Keypad reference after having pressed the button. If other control places or reference values are used, the display will show Frequency reference which is not editable. The other values on the page are Multimonitoring values. You can choose which values appear here for monitoring (for this procedure, see Application Manual).
Accessing Control Page
Help Texts
The graphical keypad features instant help and information displays for various items.
All parameters offer an instant help display. Select Help and press the OK button.
Text information is also available for faults, alarms and the Startup Wizard.
Help Text Example
STOP READY Keypad
Edit
OK
OK
STOP READY Keypad
0.00 Hz
STOP READY Keypad
0.00 Hz
OK
STOP READY I/O
STOP READY I/O STOP READY I/O
OK OK
STOP READY I/O
Eaton H-Max—Startup
Startup Wizard
In the
Startup Wizard
, you will be prompted for essential information needed by the drive so that it can start controlling your process. In the Wizard, you will need the following keypad buttons:
Left/Right arrows. Use these to easily move between digits and decimals.
Up/Down arrows. Use these to move between options in menu and to change value.
OK button. Confirm selection with this button.
Back/Reset button. Pressing this button, you can return to the previous question in the Wizard. If pressed at the first question, the Startup Wizard will be cancelled.
Once you have connected power to your Eaton H-Max frequency converter, follow these instructions to easily set up your drive.
Note
These questions appear if battery is installed.
Now the Startup Wizard is done.
The Startup Wizard can be re-initiated by pressing and holding the back/reset button for two seconds. The Startup Wizard will appear upon next power up.
Run Startup Wizard Yes No
Language Select Depends on language package
Daylight Saving
Russia
US
EU
OFF
Time hh:mm:ss
Day dd.mm.
Year yyyy
BACK
RESET
Application H-Max Standard
PID
Multi-Pump
Bypass Enabled Disabled
Motor Nominal Current Min: 0.26A Max: Drive Dependent
Motor Nominal Voltage Min: 180.0V Max: 690.0V
Motor Nominal Frequency Min: 8 Hz Max: 320 Hz
Motor Nominal Speed Min: 24 RPM Max: 19200 RPM
Min Frequency Min: 0 Hz Max: 60 Hz
Max Frequency Min: 12 Hz Max: 320 Hz
Accel Time 1 Min: 0.1s Max: 3000s
Decel Time 1 Min: 0.1s Max: 3000s
StartSourceHand Keypad FieldbusCTRL I/O Three-Wire I/O Terminal
StartSourceAuto I/O Terminal Keypad FieldbusCTRL I/O Three-Wire
SpeedSetptHand Keypad Ref P1D1 Activated
AI1 + AI2
AI2
AI1
Fieldbus
SpeedSetptAuto PID1 Activated
AI1 + AI2
AI2
AI1
Fieldbus Keypad Ref
8 H-Max HVAC Drives
PID Mini-Wizard
The PID Mini-Wizard is activated in the Quick Setup menu.
This Wizard presupposes that you are going to use the PID controller in the “one feedback/one setpoint” mode. The control place will be I/O A and the default process unit “%”.
The PID Mini-Wizard asks for the following values to be set:
Multi-Pump
If Multi-Pump is the selected application, parameter group
2.16 will be visible in the menu structure. Default values may need to be adjusted to meet your application needs.
FeedBack1 Srce AI2
AI1
Not Used ProceDataIn8 ProceDataIn7 ProceDataIn6 ProceDataIn5 ProceDataIn4 ProceDataIn3 ProceDataIn2 ProceDataIn1
AI6
AI5
AI4
AI3
Process Unit Selection (Several Selections)
Process Unit Min —
Process Unit Max —
P-Gain Min: 0% Max: 200%
6 Integration Time Min: 0.00s Max: 600.00s
7 SetPT1 Source Keypad SP1 Not Used ProceDataIn8 ProceDataIn7 ProceDataIn6 ProceDataIn5 ProceDataIn4 ProceDataIn3 ProceDataIn2 ProceDataIn1
AI6
AI5
AI4
AI3
AI2
AI1
Parameter Group Name
Parameter Number
Parameter Name
Parameter Group 2.16:
Multi-Pump
P2.16.1 Number of motors
P2.16.2 Interlock function
P2.16.3 Include FC
P2.16.4 Autochange
P2.16.5 Autochange interval
P2.16.6 Autochange frequency limit
P2.16.7 Autochange motor limit
P2.16.8 Bandwidth
P2.16.9 Bandwidth delay
Menu Structure
H-Max HVAC Drives MN04008004E—September 2011 www.eaton.com 9
Menu Structure
For more information, the complete Application Manual can be referenced at:
http://www.eaton.com/Electrical/USA/ProductsandServices/AutomationandControl/ AdjustableFrequencyDrives/H-Max/index.htm.
Keypad Menus
Monitor Basic Diagnostics Active Faults
Timer Functions Reset Faults
Multimonitor Fault History
Parameters Basic Parameters Total Counters
Analog Inputs Trip Counters
Digital Inputs Software Info
Analog Outputs I/O & Hardware Basic I/O
Digital Outputs Slot D
Drive Control Slot E
Motor Control Real Time Clock
Protections Power Unit Settings
Fixed Frequencies Keypad
Fire Mode RS485
Multi-Pump
Braking Ethernet
Fieldbus User Settings —
Second Parameter Set Favorites —
Timer Functions
Parameter List
10 H-Max HVAC Drives MN04008004E—September 2011 www.eaton.com
Parameter List
Parameter Group Name Parameter Number Parameter Name ID
Parameter Group 2.1—Basic Parameters
Basic P2.1.1 Application 213
P2.1.2 ByPass 214
P2.1.3 HOA Control Stc 1359
P2.1.4 Start Srce Hand 1300
P2.1.5 Speed Setpt Hand 1301
P2.1.6 Start Srce Auto 1302
P2.1.7 Speed Setpt Auto 1303
P2.1.8 Min Frequency 101
P2.1.9 Max Frequency 102
P2.1.10 Accel Time 1 103
P2.1.11 Decel Time 1 104
P2.1.12 Motor Nom Currnt 113
P2.1.13 Motor Nom Voltg 110
P2.1.14 Motor Nom Freq 111
P2.1.15 Motor Nom Speed 112
P2.1.16 MotorPowerFactor 120
P2.1.17 Current Limit 107
P2.1.18 Service Factor 1357
Parameter Group 2.2—Analog Inputs
Analog Input 1 P2.2.1.1 AI1 Signal selection 377
P2.2.1.2 AI1 Signal Inv 387
P2.2.1.3 AI1 Signal Range 379
P2.2.1.4 AI1 Custom Min 380
P2.2.1.5 AI1 Custom Max 381
P2.2.1.6 AI1 Filter Time 378
Analog Input 2 P2.2.2.1 AI2 Signal selection 388
P2.2.2.2 AI2 Signal Inv 398
P2.2.2.3 AI2 Signal Range 390
P2.2.2.4 AI2 Custom Min 391
P2.2.2.5 AI2 Custom Max 392
P2.2.2.6 AI2 Filter Time 389
Analog Input 3 P2.2.3.1 AI3 Signal selection 141
P2.2.3.2 AI3 Signal Inv 151
P2.2.3.3 AI3 Signal Range 143
P2.2.3.4 AI3 Custom Min 144
P2.2.3.5 AI3 Custom Max 145
P2.2.3.6 AI3 Filter Time 142
H-Max HVAC Drives MN04008004E—September 2011 www.eaton.com 11
Parameter Group 2.2—Analog Inputs, continued
Analog Input 4 P2.2.4.1 AI4 Signal selection 152
P2.2.4.2 AI4 Signal Inv 162
P2.2.4.3 AI4 Signal Range 154
P2.2.4.4 AI4 Custom Min 155
P2.2.4.5 AI4 Custom Max 156
P2.2.4.6 AI4 Filter Time 153
Analog Input 5 P2.2.5.1 AI5 Signal selection 188
P2.2.5.2 AI5 Signal Inv 198
P2.2.5.3 AI5 Signal Range 190
P2.2.5.4 AI5 Custom Min 191
P2.2.5.5 AI5 Custom Max 192
P2.2.5.6 AI5 Filter Time 189
Analog Input 6 P2.2.6.1 AI6 Signal selection 199
P2.2.6.2 AI6 Signal Inv 209
P2.2.6.3 AI6 Signal Range 201
P2.2.6.4 AI6 Custom Min 202
P2.2.6.5 AI6 Custom Max 203
P2.2.6.6 AI6 Filter Time 200
Parameter Group 2.2—Basic Parameters
Basic P2.2.7.1 Ref Scale Min. 1307
P2.2.7.2 Ref Scale Max. 1308
Parameter Group 2.3—Digital Inputs
Digital Input 1 P2.3.1.1 DI1 Open Invert Not accessible
P2.3.1.2 DI1 Function Not accessible
Digital Input 2 P2.3.2.1 DIN 2 Invert 1419
P2.3.2.2 DIN2 Function 1320
Digital Input 3 P2.3.3.1 DIN 3 Invert 1420
P2.3.3.2 DIN3 Function 1321
Digital Input 4 P2.3.4.1 DIN 4 Invert 1421
P2.3.4.2 DIN4 Function 1322
Digital Input 5 P2.3.5.1 DIN 5 Invert 1422
P2.3.5.2 DIN5 Function 1323
Digital Input 6 P2.3.6.1 DIN 6 Invert 1423
P2.3.6.2 DIN6 Function 1324
Digital Input Ext 1 P2.3.7.1 Ext-D1 Terminal 1325
P2.3.7.2 Ext-D1 Function 1326
Digital Input Ext 2 P2.3.8.1 Ext-D2 Terminal 1327
P2.3.8.2 Ext-D2 Function 1328
Parameter Group Name Parameter Number Parameter Name ID
12 H-Max HVAC Drives MN04008004E—September 2011 www.eaton.com
Parameter Group 2.3—Basic Parameters
Basic P2.3.9.1 Start logic 1304
P2.3.9.2 INTLK Timeout 1305
P2.3.9.3 Delay Time 1306
P2.3.9.4 Intrlk Stop Mode 1356
P2.3.9.5 Interlock 1 Text 1315
P2.3.9.6 Interlock 2 Text 1316
P2.3.9.7 Interlock 3 Text 1317
Parameter Group 2.4—Analog Outputs
Analog Output 1 P2.4.1.1 AO1 Function 10050
P2.4.1.2 AO1 Filter Time 10051
P2.4.1.3 AO1 Min Signal 10052
P2.4.1.4 AO1 MinScale 10053
P2.4.1.5 AO1 MaxScale 10054
P2.4.1.6 AO1 Invert 10060
Parameter Group 2.5—Digital Outputs
Digital Output 1 P2.5.1.1 RO1 function 11001
P2.5.1.2 RO1 Invert 11020
P2.5.1.3 RO1 ON delay 11002
P2.5.1.4 RO1 OFF delay 11003
Digital Output 2 P2.5.2.1 RO2 function 11004
P2.5.2.2 RO2 Invert 11021
P2.5.2.3 RO2 ON delay 11005
P2.5.2.4 RO2 OFF delay 11006
Digital Output 3 P2.5.3.1 RO3 function 11007
Supervision P2.5.9.1 Superv1 Item 1622
P2.5.9.2 Supervision #1 mode 1623
P2.5.9.3 Supervision #1 limit 1624
P2.5.9.4 Supervision #1 limit hysteresis 1625
P2.5.9.5 Superv2 Item 1626
P2.5.9.6 Supervision #2 mode 1627
P2.5.9.7 Supervision #2 limit 1628
P2.5.9.8 Supervision #2 limit hysteresis 1629
H-Max HVAC Drives MN04008004E—September 2011 www.eaton.com 13
Parameter Group 2.6—Drive Control
Basic P2.6.1.1 Start Function 505
P2.6.1.2 Stop Function 506
P2.6.1.3 InhibitDirection 1336
P2.6.1.4 Reference Unit 1362
P2.6.1.5 Keypad Reference 184
P2.6.1.6 Keypad Direction 123
P2.6.1.7 Keypad Reference copy 181
P2.6.1.8 Keypad Stop Button 114
P2.6.1.9 Accel Time 2 502
P2.6.1.10 Decel Time 2 503
P2.6.1.11 RampselectMode 1333
P2.6.1.12 Accel2Threshold 526
P2.6.1.13 Decel2Threshold 1334
P2.6.1.14 S-Ramp 1 Shape 500
P2.6.1.15 S-Ramp 2 Shape 501
Skip Frequencies P2.6.2.1 Range 1 Low Lim 509
P2.6.2.2 Range 1 High Lim 510
P2.6.2.3 Range 2 Low Lim 511
P2.6.2.4 Range 2 High Lim 512
P2.6.2.5 Range 3 Low Lim 513
P2.6.2.6 Range 3 High Lim 514
P2.6.2.7 Range 4 Low Lim 1337
P2.6.2.8 Range 4 High Lim 1338
P2.6.2.9 Range 5 Low Lim 1339
P2.6.2.10 Range 5 High Lim 1340
P2.6.2.11 Range 6 Low Lim 1341
P2.6.2.12 Range 6 High Lim 1342
P2.6.2.13 RampTimeFactor 518
Parameter Group 2.7—Motor Control
Motor Control P2.7.1 V/Hz RatioSelect 108
P2.7.2 Field WeakngPnt 602
P2.7.3 Voltage at FWP 603
P2.7.4 V/Hz Mid Freq 604
P2.7.5 V/Hz Mid Voltage 605
P2.7.6 Zero Freq Voltg 606
P2.7.7 Switching Freq 601
14 H-Max HVAC Drives MN04008004E—September 2011 www.eaton.com
Parameter Group 2.8—Faults
Faults P2.8.1.1 AI Low Fault 700
P2.8.1.2 Undervoltage Flt 727
P2.8.1.3 OutputPhase Flt 702
P2.8.1.4 Motor Duty Cycle 708
P2.8.1.5 Underload Flt 713
P2.8.1.6 Motor Therm Prot 704
P2.8.1.7 MotAmbient Temp 705
P2.8.1.8 ZeroSpeedCooling 706
P2.8.1.9 ThermTimeConst 707
P2.8.1.10 Thermistor Fault 732
P2.8.1.11 External Fault 701
P2.8.1.12 FieldbusComm Flt 733
P2.8.1.13 InputPhaseFault 730
P2.8.1.14 MotorStall Flt 709
P2.8.1.15 PID1 Supervision 749
P2.8.1.16 PID2 Supervision 757
P2.8.1.17 SlotCommFlt 734
P2.8.1.18 Preset Alarm Freq 183
Automatic Reset P2.8.2.1 Automatic Reset 731
P2.8.2.2 Restart function 719
P2.8.2.3 Wait Time 717
P2.8.2.4 Trial Time 718
P2.8.2.5 Number of trials 759
P2.8.2.6 Undervoltage Flt 720
P2.8.2.7 Overvoltage Flt 721
P2.8.2.8 Overcurrent Flt 722
P2.8.2.9 AI Low Fault 723
P2.8.2.10 UnitOverTemp Flt 724
P2.8.2.11 MotorOverTempFlt 725
P2.8.2.12 External Fault 726
P2.8.2.13 IGBT temp 1358
H-Max HVAC Drives MN04008004E—September 2011 www.eaton.com 15
Parameter Group 2.9—PID Controller
PID Controller 1, Basic Settings P2.9.1.1.1 Gain, PID Controller 1 118
P2.9.1.1.2 Integration Time, PID Controller 1 119
P2.9.1.1.3 Derivation Time, PID Controller 1 132
P2.9.1.1.4 ProcessUnitSel, PID Controller 1 1036
P2.9.1.1.5 ProcessUnitMin, PID Controller 1 1033
P2.9.1.1.6 ProcessUnitMax, PID Controller 1 1034
P2.9.1.1.7 ProcessUnitDecimals, PID Controller 1 1035
P2.9.1.1.8 Error Inversion, PID Controller 1 340
P2.9.1.1.9 Dead Band, PID Controller 1 1056
P2.9.1.1.10 Dead band delay, PID Controller 1 1057
PID Controller 1, Setpoints P2.9.1.2.1 Keypad SP 1, PID Controller 1 167
P2.9.1.2.2 Keypad SP 2, PID Controller 1 168
P2.9.1.2.3 Ramp Time, PID Controller 1 1068
P2.9.1.2.4 SetPt 1 Source, PID Controller 1 332
P2.9.1.2.5 SetPt 1 min, PID Controller 1 1069
P2.9.1.2.6 SP 1 maximum, PID Controller 1 1070
P2.9.1.2.7 SP 1 Sleep Freq, PID Controller 1 1016
P2.9.1.2.8 SP 1 Sleep delay, PID Controller 1 1017
P2.9.1.2.9 SP 1 WakeUpLevel, PID Controller 1 1018
P2.9.1.2.10 SP 1 boost, PID Controller 1 1071
P2.9.1.2.11 SP 2 Source, PID Controller 1 431
P2.9.1.2.12 SP 2 minimum, PID Controller 1 1073
P2.9.1.2.13 SP 2 maximum, PID Controller 1 1074
P2.9.1.2.14 SP 2 Sleep Freq, PID Controller 1 1075
P2.9.1.2.15 SP 2 Sleep delay, PID Controller 1 1076
P2.9.1.2.16 SP 2 WakeUpLevel, PID Controller 1 1077
P2.9.1.2.17 SP 2 boost, PID Controller 1 1078
PID Controller 1, Feedbacks P2.9.1.3.1 Function, PID Controller 1 333
P2.9.1.3.2 Gain, PID Controller 1 1058
P2.9.1.3.3 FeedBack 1 Srce, PID Controller 1 334
P2.9.1.3.4 FB 1 Minimum, PID Controller 1 336
P2.9.1.3.5 FB 1 Maximum, PID Controller 1 337
P2.9.1.3.6 FB 2 Source, PID Controller 1 335
P2.9.1.3.7 FB 2 Minimum, PID Controller 1 338
P2.9.1.3.8 FB 2 Maximum, PID Controller 1 339
PID Controller 1, Feedforward P2.9.1.4.1 Function, PID Controller 1 1059
P2.9.1.4.2 Gain, PID Controller 1 1060
P2.9.1.4.3 FF 1 Source, PID Controller 1 1061
P2.9.1.4.4 FF1 Minimum, PID Controller 1 1062
P2.9.1.4.5 FF1 Maximum, PID Controller 1 1063
P2.9.1.4.6 FF 2 Source, PID Controller 1 1064
P2.9.1.4.7 FF2 Minimum, PID Controller 1 1065
P2.9.1.4.8 FF2 Maximum, PID Controller 1 1066
16 H-Max HVAC Drives MN04008004E—September 2011 www.eaton.com
Parameter Group 2.9—PID Controller, continued
PID Controller 1, Process Supervision P2.9.1.5.1 Enable Superv, PID Controller 1 735
P2.9.1.5.2 Upper limit, PID Controller 1 736
P2.9.1.5.3 Lower limit, PID Controller 1 758
P2.9.1.5.4 Delay, PID Controller 1 737
PID Controller 1, Pressure Loss Compensation P2.9.1.6.1 Enable SP 1, PID Controller 1 1529
P2.9.1.6.2 SP 1 Max Comp., PID Controller 1 1530
P2.9.1.6.3 Enable SP 2, PID Controller 1 1531
P2.9.1.6.4 SP 2 Max Comp., PID Controller 1 1532
PID Controller 2, Basic Settings P2.9.2.1.1 Gain, PID Controller 2 1631
P2.9.2.1.2 Integration Time, PID Controller 2 1632
P2.9.2.1.3 Derivation Time, PID Controller 2 1633
P2.9.2.1.4 ProcessUnitSel, PID Controller 2 1635
P2.9.2.1.5 ProcessUnitMin, PID Controller 2 1664
P2.9.2.1.6 ProcessUnitMax, PID Controller 2 1665
P2.9.2.1.7 ProcessUnitDecimals, PID Controller 2 1666
P2.9.2.1.8 Error Inversion, PID Controller 2 1636
P2.9.2.1.9 Dead Band, PID Controller 2 1637
P2.9.2.1.10 Dead band delay, PID Controller 2 1638
PID Controller 2, Setpoints P2.9.2.2.1 Keypad SP 1, PID Controller 2 1640
P2.9.2.2.2 Keypad SP 2, PID Controller 2 1641
P2.9.2.2.3 Ramp Time, PID Controller 2 1642
P2.9.2.2.4 SetPt 1 Source, PID Controller 2 1643
P2.9.2.2.5 SetPt 1 min, PID Controller 2 1644
P2.9.2.2.6 SP 1 maximum, PID Controller 2 1645
P2.9.2.2.7 SP 2 Source, PID Controller 2 1646
P2.9.2.2.8 SP 2 minimum, PID Controller 2 1647
P2.9.2.2.9 SP 2 maximum, PID Controller 2 1648
PID Controller 2, Feedbacks P2.9.2.3.1 Function, PID Controller 2 1650
P2.9.2.3.2 Gain, PID Controller 2 1651
P2.9.2.3.3 FeedBack 1 Srce, PID Controller 2 1652
P2.9.2.3.4 FB 1 Minimum, PID Controller 2 1653
P2.9.2.3.5 FB 1 Maximum, PID Controller 2 1654
P2.9.2.3.6 FB 2 Source, PID Controller 2 1655
P2.9.2.3.7 FB 2 Minimum, PID Controller 2 1656
P2.9.2.3.8 FB 2 Maximum, PID Controller 2 1657
PID Controller 2, Process Supervision P2.9.2.4.1 Enable Superv, PID Controller 2 1659
P2.9.2.4.2 Upper limit, PID Controller 2 1660
P2.9.2.4.3 Lower limit, PID Controller 2 1661
P2.9.2.4.4 Delay, PID Controller 2 1662
H-Max HVAC Drives MN04008004E—September 2011 www.eaton.com 17
Parameter Group 2.10—Fixed Frequencies
Fixed Frequencies P2.10.1 Preset Freq 1 105
P2.10.2 Preset Freq 2 106
P2.10.3 Preset Freq 3 126
P2.10.4 Preset Freq 4 127
P2.10.5 Preset Freq 5 128
P2.10.6 Preset Freq 6 129
P2.10.7 Preset Freq 7 130
Parameter Group 2.11—Fire Mode
Fire Mode P2.11.1 Firemode Freq 1598
Parameter Group 2.12—Multi-Pump
Multi-Pump P2.12.1 Number of motors 1001
P2.12.2 Interlock function 1032
P2.12.3 Include FC 1028
P2.12.4 Autochange 1027
P2.12.5 Autochange interval 1029
P2.12.6 Autochange: frequency limit 1031
P2.12.7 Autochange: motor limit 1030
P2.12.8 Bandwidth 1097
P2.12.9 Bandwidth delay 1098
Parameter Group 2.13—Braking
Braking P2.13.1 DC Brake Current 507
P2.13.2 DC Time Stop 508
P2.13.3 DC BrakeFreqStop 515
P2.13.4 StartMagnTime 516
P2.13.5 StartMagnCurrent 517
P2.13.6 Preheat Current 1335
Parameter Group 2.14—Fieldbus
Fieldbus P2.14.1 FB Data Out1 Sel 852
P2.14.2 FB Data Out2 Sel 853
P2.14.3 FB Data Out3 Sel 854
P2.14.4 FB Data Out4 Sel 855
P2.14.5 FB Data Out5 Sel 856
P2.14.6 FB Data Out6 Sel 857
P2.14.7 FB Data Out7 Sel 858
P2.14.8 FB Data Out8 Sel 859
Parameter Group 2.15—Second Param Set
Motor 2 P2.15.1.1 Motor Nom Currnt, Set2 1347
P2.15.1.2 Motor Nom Voltg, Set2 1348
P2.15.1.3 Motor Nom Freq, Set2 1349
P2.15.1.4 Motor Nom Speed, Set2 1350
P2.15.1.5 MotorPowerFactor, Set2 1351
P2.15.1.6 Current Limit, Set2 1352
P2.15.1.7 Motor Therm Prot, Set2 1353
18 H-Max HVAC Drives MN04008004E—September 2011 www.eaton.com
Parameter Group 2.15—Second Param Set, continued
Drive Control 2 P2.15.2.1 Min Frequency, Set2 1343
P2.15.2.2 Max Frequency, Set2 1344
P2.15.2.3 Accel Time 1, Set2 1345
P2.15.2.4 Decel Time 1, Set2 1346
P2.15.2.5 V/Hz RatioSelect, Set2 1355
Parameter Group 2.16—Timer Functions
Interval 1 P2.16.1.1 ON Time, Interval 1 1670
P2.16.1.2 Off Time, Interval 1 1671
P2.16.1.3 From Day, Interval 1 1672
P2.16.1.4 To Day, Interval 1 1673
P2.16.1.5 Assign to channel, Interval 1 1674
Interval 2 P2.16.2.1 ON Time, Interval 2 1675
P2.16.2.2 Off Time, Interval 2 1676
P2.16.2.3 From Day, Interval 2 1677
P2.16.2.4 To Day, Interval 2 1678
P2.16.2.5 Assign to channel, Interval 2 1679
Interval 3 P2.16.3.1 ON Time, Interval 3 1680
P2.16.3.2 Off Time, Interval 3 1681
P2.16.3.3 From Day, Interval 3 1682
P2.16.3.4 To Day, Interval 3 1683
P2.16.3.5 Assign to channel, Interval 3 1684
Interval 4 P2.16.4.1 ON Time, Interval 4 1685
P2.16.4.2 Off Time, Interval 4 1686
P2.16.4.3 From Day, Interval 4 1687
P2.16.4.4 To Day, Interval 4 1688
P2.16.4.5 Assign to channel, Interval 4 1689
Interval 5 P2.16.5.1 ON Time, Interval 5 1690
P2.16.5.2 Off Time, Interval 5 1691
P2.16.5.3 From Day, Interval 5 1692
P2.16.5.4 To Day, Interval 5 1693
P2.16.5.5 Assign to channel, Interval 5 1694
Timer 1 P2.16.6.1 Duration 1695
P2.16.6.2 Assign to channel 1696
Timer 2 P2.16.7.1 Duration 1697
P2.16.7.2 Assign to channel 1698
Timer 3 P2.16.8.1 Duration 1699
P2.16.8.2 Assign to channel 1700
Diagnostics
H-Max HVAC Drives MN04008004E—September 2011 www.eaton.com 19
Diagnostics
Under this menu, you can find Active faults, Reset faults, Fault history, Counters and Software info.
Active Faults
Reset Faults
Fault History
Fault Codes
Fault Codes and Descriptions
Menu Function Note
Active faults When a fault/faults appear(s), the display with the name of the fault starts to blink. Press OK to return to the Diagnostics menu. The Active faults submenu shows the number of faults. Select the fault and push OK to see the fault-time data.
The fault remains active until it is cleared with the Reset button (push for 2s) or with a reset signal from the I/O terminal or Fieldbus or by choosing Reset faults (see below). The memory of active faults can store the maximum of 10 faults in the order of appearance.
Menu Function Note
Reset faults In this menu you can reset faults. For closer instructions. CAUTION! Remove external Control signal before resetting the fault to prevent unintentional restart of the drive.
Menu Function Note
Fault history 40 latest faults are stored in the Fault history. Entering the Fault history and clicking OK on the selected fault shows the fault time data (details).
Fault Code
Fault ID Fault Name Possible Cause Remedy
1 1 Overcurrent (hardware fault)
AC drive has detected too high a current (>4*IH) in the motor cable:
• Sudden heavy load increase
• Short circuit in motor cables
• Unsuitable motor
• Check loading
• Check motor
• Check cables and connections
• Make identification run
• Check ramp times
2 Overcurrent (software fault)
2 10 Overvoltage (hardware fault)
The DC-link voltage has exceeded the limits defined:
• Too short a deceleration time
• Brake chopper is disabled
• High overvoltage spikes in supply
• Start/Stop sequence too fast
• Make deceleration time longer
• Use brake chopper or brake resistor
(available as options)
• Activate overvoltage controller
• Check input voltage
11 Overvoltage (software fault)
3 20 Earth fault (hardware fault)
Current measurement has detected that the sum of motor phase current is not zero:
• Insulation failure in cables or motor
Check motor cables and motor
21 Earth fault (software fault)
5 40 Charging switch The charging switch is open, when the START command has been given:
• Faulty operation
• Component failure
• Reset the fault and restart
• Should the fault re-occur, contact the distributor near to you
20 H-Max HVAC Drives MN04008004E—September 2011 www.eaton.com
Fault Codes and Descriptions, continued
Fault Code
Fault ID Fault Name Possible Cause Remedy
7 60 Saturation Various causes:
• Defective component
• Brake resistor short-circuit or overload
• Cannot be reset from keypad
• Switch off power
• DO NOT RECONNECT POWER! Contact factory
• If this fault appears simultaneously with
F1, check motor cables and motor
8 600 System fault Communication between control board and power unit has failed
Reset the fault and restart. Should the fault re-occur, contact the distributor near you
602 Watchdog has reset the CPU
603 Voltage of auxiliary power in power unit is too low
604 Phase fault: Voltage of an output phase does not follow the reference
605 CPLD has faulted but there is no detailed information about the fault
606 Control and power unit software are incompatible
Update software. Should the fault re-occur, contact the distributor near you
607 Software version cannot be read. There is no software in power unit
Update power unit software. Should the fault re-occur, contact the distributor near you
608 CPU overload. Some part of the software (for example application) has caused an overload situation. The source of fault has been suspended
Reset the fault and restart. Should the fault re-occur, contact the distributor near you
609 Memory access has failed. For example, retain variables could not be restored
610 Necessary device properties cannot be read
647 Software error Update software. Should the fault re-occur, contact the distributor near you648 Invalid function block used in application.
System software and application are not compatible
649 Resource overload:
• Error when loading parameter initial values
• Error when restoring parameters
• Error when saving parameters
9 80 Undervoltage (fault)
DC link voltage is under the voltage limits defined:
• Most probable cause: Too low a supply voltage
• AC drive internal fault
• Defect input fuse
• External charge switch not closed Note: This fault is activated only if the drive is in Run state.
In case of temporary supply voltage break reset the fault and restart the AC drive. Check the supply voltage. If it is adequate, an internal failure has occurred. Contact the distributor near you
81 Undervoltage (alarm)
10 91 Input phase Input line phase is missing Check supply voltage, fuses and cable
11 100 Output phase supervision
Current measurement has detected that there is no current in one motor phase
Check motor cable and motor
H-Max HVAC Drives MN04008004E—September 2011 www.eaton.com 21
Fault Codes and Descriptions, continued
Fault Code
Fault ID Fault Name Possible Cause Remedy
12 110 Brake chopper supervision (hardware fault)
• No brake resistor installed
• Brake resistor is broken
• Brake chopper failure
Check brake resistor and cabling. If these are OK, the chopper is faulty. Contact the distributor near you111 Brake chopper saturation alarm
13 120 AC drive undertemperature (fault)
Too low temperature measured in power unit’s heatsink or board. Heat- sink temperature is under –10°C
121 AC drive overtemperature (alarm)
14 130 AC drive overtemperature (fault, heatsink)
Too high temperature measured in power unit’s heatsink or board. Heat- sink temperature is over 100°C
• Check the correct amount and flow of cooling air
• Check the heatsink for dust
• Check the ambient temperature
• Make sure that the switching frequency is not too high in relation to ambient temperature and motor load
131 AC drive overtemperature (alarm, heatsink)
132 AC drive overtemperature (fault, board)
133 AC drive overtemperature (alarm, board)
15 140 Motor stalled Motor is stalled Check motor and load
16 150 Motor overtemperature Motor is overloaded Decrease motor load. If no motor overload exists, check the temperature model parameters
17 160 Motor underload Motor is underloaded Check load
19 180 Power overload (short-time supervision)
Drive power is too high Decrease load
181 Power overload (long-time supervision)
25 — Motor control fault Start angle identification has failed.
Generic motor control fault
32 312 Fan cooling Fan lifetime is up Change fan and reset fan lifetime counter
33 — Fire mode enabled Fire mode of the drive is enabled. The drive’s protections are not in use
37 360 Device changed (same type)
Option board changed for one previously inserted in the same slot. The board’s parameter settings are saved
Device is ready for use. Old parameter settings will be used
38 370 Device changed (same type)
Option board added. The option board was previously inserted in the same slot. The board’s parameter settings are saved
Device is ready for use. Old parameter settings will be used
39 380 Device removed Optional board removed from slot Device no longer available
40 390 Device unknown Unknown device connected (power unit/option board)
Device no longer available
41 400 IGBT temperature IGBT temperature (unit temperature + I2T) is too high
• Check loading
• Check motor size
• Make identification run
43 420 Encoder fault Encoder 1 channel A is missing • Check encoder connections
• Check encoder and encoder cable
• Check encoder board
• Check encoder frequency in open loop
421 Encoder 1 channel B is missing
422 Both encoder 1 channels are missing
423 Encoder reversed
424 Encoder board missing
22 H-Max HVAC Drives MN04008004E—September 2011 www.eaton.com
Fault Codes and Descriptions, continued
Fault Code
Fault ID Fault Name Possible Cause Remedy
44 430 Device changed (different type)
Option board changed for one not present in the same slot before. No parameter settings are saved
Set the option board parameters again
45 440 Device changed (different type)
Option board added. The option board was not previously present in the same slot. No parameter settings are saved
Set the option board parameters again
51 1051 External fault Digital input —
52 1052 Keypad communication fault
The connection between the control keypad and frequency converter is broken
Check keypad connection and possible keypad cable1352
53 1053 Fieldbus communication fault
The data connection between the Fieldbus master and Fieldbus board is broken
Check installation and Fieldbus master
54 1354 Slot A fault Defective option board or slot Check board and slot
1454 Slot B fault
1654 Slot D fault
1754 Slot E fault
65 1065 PC communication fault The data connection between the PC and frequency converter is broken
66 1066 Thermistor fault The thermistor input has detected an increase of motor temperature
• Check motor cooling and load
• Check thermistor connection (if thermistor input is not in use it has to be short circuited)
69 1310 Fieldbus mapping error Non-existing ID number is used for mapping values to Fieldbus Process Data Out
Check parameters in Fieldbus Data Mapping menu
1311 Not possible to convert one or more values for Fieldbus Process Data Out
The value being mapped may be of undefined type. Check parameters in Fieldbus Data Mapping menu
1312 Overflow when mapping and converting values for Fieldbus Process Data Out (16-bit)
101 1101 Process supervision fault
(PID1)
PID controller: Feedback value outside of supervision limits (and the delay if set)
105 1105 Process supervision fault
(PID2)
PID controller: Feedback value outside of supervision limits (and the delay if set)
Eaton is a registered trademark of Eaton Corporation.
All other trademarks are property of their respective owners.
Eaton Corporation
Electrical Sector 1111 Superior Ave.
Cleveland, OH 44114 United States
877-ETN-CARE (877-386-2273)
Eaton.com
© 2011 Eaton Corporation All Rights Reserved Printed in USA Publication No. MN04008004E / Z11541 September 2011
Eaton is dedicated to ensuring that reliable, efficient and safe power is available when it’s needed most. With unparalleled knowledge of electrical power management across industries, experts at Eaton deliver customized, integrated solutions to solve our customers’ most critical challenges.
Our focus is on delivering the right solution for the application.
But, decision makers demand more than just innovative products.
They turn to Eaton for an unwavering commitment to personal support that makes customer success a top priority. For more information, visit www.eaton.com/electrical.
Document ID:
File details come from the government source that posted it. Updated .