This solicitation is for installation services to add a new pump to an existing OR chilled water loop at a VA medical center. The contractor will provide all labor, tools, and materials to install a new pump that matches the two existing pumps and will be controlled in parallel via the existing building automation system. The contractor will also install a new VFD and disconnect for the new pump located near the existing VFDs, and rewire the power feed for the existing pumps so they are not on the same electrical panel. Integration with the existing BACnet compatible BAS is required. The solicitation is set aside 100% for SDVOSB and has a performance period of 120 days from notice to proceed.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Moses Engineering 2209 NW 40th Terrace, Suite A
Gainesville, FL 32605 352.372.1911 moses-eng.com
SUBMITTAL REVIEW & TRANSMITTAL
Date:
To:
From:
Project Name:
M&A Project #:
WE ARE SENDING YOU THE FOLLOWING ITEMS BY
☐ Email ☐ Posted to FTP site ☐ Posted to SharePoint/Procore
ITEM
DATE
DESCRIPTION
Specification:
Specification Title:
Submitted Item:
GC’s Submittal#:
REVIEW
☐ Approved ☐ Approved as Noted ☐ Rejected Approval is only for conformance with design concept of the Project and compliance with the information given in the Contract Documents. Contractor is responsible for quantities and dimensions to be confirmed and correlated at the Project site. Approval does not relieve Contractor from full compliance with the Contract Documents.
COMMENTS
END OF SUBMITTAL REVIEW & TRANSMITTAL
Document1
August 17, 2020 Lin Riley, Valor Construction Joe Klubertanz WPB VAMC New OR CW Loop and Chillers 19010
25 00 00 Controls Product Data 25 00 00
1. Please supply bypass valve with pressure drop in the range of 2-4 psi. This will assist with controllability.
2. Provide graphics examples in separate package for approval.
3. Provide LAN layout for as-built.
Corporate | 4501 Beverly Avenue | Jacksonville, FL 32210 | P 904.642.5303 | F 904.641.8722 | www.BrooksSolutions.net
Tallahassee | 2815-1 Industrial Plaza Dr. | Tallahassee, FL 32301 | P 850.701.2350 | F 850.701.2355 FL: CA C058729 HVAC EQUIPMENT | BUILDING AUTOMATION | ENERGY SOLUTIONS | SERVICE | PARTS GA: CN 209606
VA West Palm Beach, Florida OR Chilled Water Loop
DDC Controls Submittals July 13, 2020
Prepared for Valor Construction
Management, LLC.
Prepared by Chad Poole Resubmit 8/8/20
M:\2019\19010 WPB VAMC New OR CW Loop and Chillers\3 Construction\Approval Submittals\In
BUILDING AUTOMATION SYSTEM ARCHITECTURE
(VA WEST PALM BEACH NEW OR LOOP )
BO
BI
AI
AO
BO
BI
AI
AO
BACnet MS/TP
DEVICE
BACnet MS/TP
DEVICE
BACnet MS/TP
DEVICE
ECLYPSE™ Connected System Controller
Overview The ECLYPSE Connected System Controller (ECY-CSC) is a modular and scalable platform used to control a wide range of HVAC applications. It supports multi-protocol communications, including BACnet/IP, and is a listed BACnet Building Controller (B-BC).
The ECY-CSC consists of a control, automation and connectivity server, power supply, and I/O extension modules.
This programmable controller provides advanced functionality, such as customizable control logic, Web-based design and visualization interface (ENVYSION embedded), logging, alarming, and scheduling.
Applications The ECY-CSC is typically used as:
£ A controller for medium/large sized Air
Handling Units (AHU), central plant, lighting, power monitoring, and other applications.
£ Small building server and equipment controller with embedded ENVYSION. For example, it can be used to control and serve a boiler room.
Features & Benefits Connectivity The different types of connections supported by the ECY-CSC are as follows:
IP wired connection Internal switch with two Ethernet ports allows the controllers to be wired in a star or daisy-chain topology. With a daisy-chain topology:
£ Fewer wire runs to a centralized switch are required, thereby achieving installation and cost reduction.
£ A laptop can be connected to the second Ethernet port for direct programming, configuration, and commissioning using EC-gfxProgram or ENVYSION.
IP wireless (Wi-Fi) connection £ Wi-Fi Client - Connection to the building’s existing Wi-Fi network or to another controller’s Wi-Fi Hotspot or Access Point.
£ Wi-Fi Access Point - extending the building’s wired IP network to your Wi-Fi Client devices.
D a t a s h e e t
2 / 18 ECLYPSE™ Connected System Controller
£ Wi-Fi Hotspot - your own wireless area network, for wireless communication between the controllers, or with a mobile device or laptop for configuration, commissioning and servicing.
Both IP wired and wireless (Wi-Fi) connection The availability of both Ethernet ports and USB ports for the Wi-Fi Adapter, allows for simultaneous wired IP and Wi-Fi communication on the same controller, which means you can choose and combine these connection methods.
For example, Wi-Fi can be used between two controllers to jump a large atrium.
Connect from anywhere Control technicians, facility managers, occupants, and others can easily connect to the system, on-site or off-site, using the different available tools:
£ ENVYSION to create and view the graphical interface £ EC-gfxProgram to create custom control sequences £ myDC Control to view, edit, and configure system operating parameters
IP Communication £ Increased speed and improved handling of numerous trend logs that enable applications, such as advanced analytics that require a large amount of data.
£ Experience faster response and save time when programming, configuring, creating and viewing graphics, and upgrading your system.
£ Control technicians can connect the ECLYPSE Wi-Fi Adapter to the ECY-CSC thereby creating a Wi-Fi Hotspot network.
The control technician can then connect wirelessly to the system using a mobile device or laptop, for faster, easier system configuration, programming, commissioning, and servicing.
£ Hostname management allows the controller to be addressed by a nickname to facilitate network management.
Open to Web Services With the RESTful API, the ECY-CSC’s data can be accessed from different applications, such as energy dashboards, analytics tools, and mobile applications. The RESTful API documentation explains the implementation protocol for this interface.
HTML5 Visual Interface The ECY-CSC comes embedded with both ENVYSION Studio and Viewer, and xpressENVYSION.
ENVYSION – Web-based graphic design and vi-sualization interface ENVYSION is a web-based graphic design and visualization interface used to create and deliver interactive graphical user interfaces and an optimal user experience for building owners and facility managers to better manage facility data.
Programmability Supports Distech Controls’ EC-gfxProgram, which makes Building Automation System (BAS) programming effortless, by allowing you to visually assemble building blocks to create a custom control sequence for any HVAC , lighting, or building automation application.
Batch EC-gfxProgram Projects and Firmware Download EC-gfxProgram projects can be downloaded in batch to multiple controllers, for greater time savings. Batch firmware update can also be performed on multiple controllers.
Simplified Network Commissioning The XpressNetwork Utility saves you time and expense by giving you increased control over multiple ECLYPSE controllers through device discovery and batch operations such as configuring, programming, and updating multiple ECLYPSE controllers on the network.
ECLYPSE™ Connected System Controller 3 / 18
In addition, with the embedded step by step Commissioning Wizard, all configuration operations can be setup and applied in one go.
Increase productivity using the xpressNetwork Companion mobile app, making it easier to identify and locate a controller on the network.
Use the QR Code marked on ECLYPSE controllers to easily collect key controller data and to facilitate its network integration with xpressNetwork Utility.
Scalable and Modular The ECY-CSC is sized to cost-effectively meet the requirements of any HVAC application from small to medium to large systems. The most capable Connected System Controller model can be expanded to support up to 20 input/ output (I/O) modules (up to 320 I/Os) while being able to adapt to new requirements as the need arises.
A connecting cable is used to connect successive rows of modules within a controls’ cabinet to provide power and communication.
ECY-RS485 communication module An ECY-RS485 communication module adds two extra RS-485 trunks to support more BACnet MS/TP and Modbus RTU devices.
ECY-MBUS communication module An ECY-MBUS communication module has one M-Bus port for meter integration, thus eliminating the need for a third-party gateway (from M-Bus to BACnet/IP).
BACnet/IP Device The ECY-CSC is BTL-listed as a BACnet Building Controller (B-BC) and is certified WSP B-BC (Europe) and AMEV AS-A & AS-B (German-speaking countries). It supports BACnet/IP for faster communication in comparison to the traditional twisted pair communication bus.
Multi-Protocol Support The ECY-CSC supports a range of communication protocols such as BACnet MS/ TP, Modbus RTU, and Modbus TCP.
BACnet MS/TP and Modbus RTU communications are made by connecting directly to separate RS-485 ports. The ECY- CSC integrates up to three RS-485 ports when equipped with one ECY-RS485 extension module allowing the controller to support more than one trunk or communication protocol at a time.
MS/TP to IP routing
Integrate full MS/TP trunks into a supervisory system like the EC-NetAX Supervisor, without the need for other hardware components such as an external BACnet MS/TP to IP router.
Modbus RTU and TCP Modbus RTU and TCP communication can be used to integrate a wide variety of Modbus devices such as power and water meters, Variable Frequency Drives, air flow sensors, and more, without the need for additional hardware such as a gateway.
FIPS 140-2 Level 1 Compliant FIPS 140-2 Level 1 compliance provides an enhanced level of security to protect data the controller is collecting and sharing making it suitable for use in the most sensitive environments.
Weather Forecast The weather forecast is directly available from the internet to be shown on a connected ECx- Display or to be used by the controller’s code.
Smart Room Control Support The Smart Room Control solution is an end-to-end system for the control of HVAC equipment, lighting, and shades/sunblinds, achieving the highest levels of comfort for occupants while cutting costs from installation time and wiring/ material requirements to energy consumption.
This solution combines:
£ Lighting and shade/sunblind expansion modules to control lights (on/off or dimming) and shades/sunblinds (up/down and angle rotation).
£ Multi-sensor combining motion and luminosity (Lux) sensors and an Infrared receiver that works with a convenient remote control.
£ The ECLYPSE platform is compatible with Distech Controls line of Bluetooth® low energy technology enabled devices (Allure UNITOUCH™ and EC-Multi-Sensor-BLE) and mobile application providing state-of-the-art occupant management.
£ Allure™ Series Communicating room sensors for increased occupant comfort settings using integrated sensors for temperature, humidity, CO2, and motion.
4 / 18 ECLYPSE™ Connected System Controller
Allure™ Series Communicating Sensor Support These controllers work with a wide range of sensors, such as the Allure Series Communicating Sensors that are designed to provide intelligent sensing and control devices for increased user experience and energy efficiency.
£ Allure EC-Smart-Vue £ Allure EC-Smart-Comfort £ Allure EC-Smart-Air £ Allure UNITOUCH
Mobility The controller can be remotely accessed to program, configure, or maintain the installation thus reducing costs associated with on-site visits. Through a mobile device or PC, a range of tasks can be performed using the following free-to-use tools and interfaces:
£ ENVYSION web-based graphic design and visualization interface £ EC-gfxProgram graphical programming interface £ myDC Control mobile application
Hand/Off/Auto Switches and Potentiometers The front assembly of Hand/Off/Auto (HOA) equipped I/O models allow users to override the control outputs for commissioning and maintenance purposes.
Universal outputs have potentiometers providing manual analog signal and output control to override voltage or current signal.
High-Efficiency Design The power supply uses the latest high-efficiency switch-mode circuitry to make more power available to operate additional modules and for cooler operation.
Hot-Swappable Tool-Less Design and Unique Latching Mechanism The I/O modules are hot-swappable for replacement without interrupting power and communications to other modules.
The front assembly of I/O modules separate from the wiring base by pushing the two latches up to unlock a module’s front assembly and then opening and pulling the hinged gull-wing covers.
The latch design locks the front assembly to the wiring base.
The hinged gull-wing design protects and cover the stacked dual row I/O terminal strips.
Ease of Installation The ECY-CSC modules are plug & play devices.
They are equipped with HD-15 connectors that transmits power and communications to the next module for fast and easy assembly.
I/O Status LEDs The status LEDs on the I/O modules allows the user to confirm the status of the inputs/outputs and facilitate commissioning and troubleshooting.
Auto-Addressing The auto-addressing feature eliminates the need to manually assign an address to each I/O module therefore reducing installation and configuration time.
Digital Inputs Up to 120Hz The ECY-16DI module supports pulsed signals up to 120Hz for equipment status monitoring and alarm point monitoring, commonly used in energy metering applications.
ECLYPSE™ Connected System Controller 5 / 18
Color-Coded, Rising Cage Terminals Terminal blocks are uniquely identified and color-coded for clarity and to prevent wiring mistakes. The rising cage clamp terminal block connectors offer a more robust and secure wire connection, designed to withstand activity and vibrations.
Robust Protection The I/O modules are protected against mis-wiring and faults to prevent damage caused by incorrect wiring or other mishaps.
The power supply module contains over-voltage and over-current output protection to protect the electronics in unstable power supply conditions and against mis-wiring.
Alarms, Trend Log, Schedule Support Embedded alarms, trend log and schedule support allows for fully distributed data and logic providing a more robust system. Embedded trend logs simplify system troubleshooting when compared to a centralized system.
Email Notifications Service Technicians & facility managers can receive automatic email notifications for system status and alarms to ensure faster system servicing and response time. Email notification text can be customized to provide pertinent information about the issue at hand.
6 / 18 ECLYPSE™ Connected System Controller
Model Selection The ECLYPSE Connected System Controller consists of a power supply, a control, automation and connectivity server, I/O extension modules, and communication modules to create a controller tailored to its application. The different models for each are shown in the tables below.
Power Supply A power supply module must be added after each HD15 cable (see Accessories below).
ECY-PS24 24VAC/VDC power supply module for the ECLYPSE Connected System Controller.
ECY-PS100-240 100 to 240VAC power supply module for the ECLYPSE Connected System Controller.
Control, Automation and Connectivity Servers Connected System Controller for medium/large sized AHU and plant applications and small building server/controller applications.
Model With Embedded
ENVYSION
Application Maximum Number of Points Supported
BACnet MS/TP to IP Routing Support – Maximum Number of BACnet MS/TP Devices
Maximum Number of Modbus Devices (RTU or TCP)
ECY-S1000-28 Small size equipment such as a large rooftop unit or a small
AHU.
28 No1 3
ECY-S1000E-28
ECY-S1000-28-MS 28 Yes2 3
ECY-S1000E-28-MS
ECY-S1000-48 Medium size equipment such as an AHU or a small size plant room.
48 No1 10
ECY-S1000E-48
ECY-S1000-48-MS 48 Yes2 10
ECY-S1000E-48-MS
ECY-S1000 Large size equipment such as large plant rooms and large data centers.
3204 Yes2 963
ECY-S1000E
1. Upgrade and enable the functionality of your ECLYPSE controller’s RS-485 ports with our capacity-based upgrade to ECYS1000-48MS.
2. Up to 50 BACnet MS/TP devices recommended on each RS-485 port.
3. Up to 32 Modbus RTU devices recommended on each RS-485 port. The maximum amount of Modbus TCP devices is limited to available system resources (too many devices can affect system performance).
4. The ECY-S1000 models support a maximum of 320 points OR up to a maximum of 20 IO modules.
ECLYPSE™ Connected System Controller 7 / 18
I/O Modules Selection Inputs Outputs
Ba si c Po w er
C on su m pt io n2 , WQ ua nt ity
Digital Analog
VD
C P ow er
S up pl y
Q ua nt ity
Digital Analog
H O
A
C on ta ct
C ou nt er
0H z Pu ls e
C ou nt in g to
0V D
C to
VD
C to
0m
A R es is ta nc e Th er m is to r
0-
7V
AC
0-
VD
C Fo rm -C
, 1 0A
VA
C T ria c, .5
A or
2V D
C
PW
M Fl oa tin g to
0V D
C to
0m
A1
ECY-8UI 8 0.94
ECY-16DI 16 0.94
ECY-6UO 6 UO1
UO2
UO3
0.94
ECY-6UO-HOA 6 UO1
UO2
UO3
0.94
ECY-8DOR 8 0.94
ECY-8DOR-HOA 8 0.94
ECY-4UI4UO 4 4 UO1
UO2
UO3
0.94
ECY-4UI4UO-HOA 4 4 UO1
UO2
UO3
0.94
ECY-8UI6UO 8 6 UO1
UO2
UO3
0.94
ECY-8UI6UO-HOA 8 6 UO1
UO2
UO3
0.94
ECY-8UI6DOT 8 6 0.94
ECY-8UI6DOT-HOA 8 6 0.94
1. 0 to 10VDC is available on UO1 to UO6. 0 to 20 mA is available on UO1, UO2, and UO3; this option is individually selected through an on-board DIP switch setting.
2. External loads excluded. See the ECLYPSE Selection Tool to calculate the number of Input/Output Extension Modules that can operate with a power supply.
Communication Modules Selection Communications Module Description ECY-RS485 ECLYPSE Communication module with two RS-485 ports for Modbus
RTU or BACnet MS/TP.
ECY-MBUS ECLYPSE Communication module with one M-Bus port, supporting up to
20 M-Bus meters. Upgrade license for the ECY-MBUS communication module to support up to 60 M-Bus meters.
Accessories ECLYPSE HD15 Cable 6ft (1.8m) cable for Connected System Controller multiple-row panel installations. An HD15 cable must always be followed by a power supply module. For more information, refer to the Hardware Installation Guide.
ECLYPSE Wi-Fi Adapter Wi-Fi Adapter for ECLYPSE Connected Controllers.
8 / 18 ECLYPSE™ Connected System Controller
Product Specifications Power Supply (ECY-PS24) Power Supply Input Voltage Range 24VAC/DC; ±15%; Class 2 Power Consumption 60VA Frequency Range 50 to 60Hz Overcurrent Protection Field replaceable fuse Fuse Type 4A, fast-acting, 5 × 20mm (GMA-4A)
Power Supply Output DC Voltage 18VDC regulated Rated Current Range 0 to 1.6A Rated Power 30W1
1. The total power consumption of all modules connected to the right of this power supply, and up to the next connected power supply, including any connected loads, must be less than this value. A separate transformer rated at 60VA minimum and 100VA maximum must be used for each ECY-PS24 power supply for it to operate at full capacity.
Hardware Power Distribution Direction Powered modules are connected to the right Backplane Bus Pass-through connection for data and control signals Status Indicator Green LED: power status
Mechanical Dimensions (H × W × D) 4.74 × 2.85 × 2.31" (120.31 × 72.38 × 58.56mm)
4.74" 120.31 3.18" 80.82
18.390.72
21.130.83
2.31" 58.56 72.38
Inches Millimeters
0.01" 0.40Inter-Connection Gap:
2.61" 66.190.06" 1.44
0.17" 4.24 2.85"
5.20" 132.00
Front BackProfile
Shipping weight 0.75lbs (0.34kg) Mounting DIN rail or screw mounting Enclosure Material1 FR/ABS Enclosure Rating Plastic housing, UL94-V0 flammability rating Plenum rating per UL1995
1. All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE) directive
ECLYPSE™ Connected System Controller 9 / 18
Environmental Operating Temperature 32 to 122°F (0 to 50°C) Storage Temperature -22 to 158°F (-30 to 70°C) Relative Humidity 0 to 90% non-condensing Ingress Protection Rating IP20 Nema Rating 1
Standards and Regulations
CE:
£ Emission EN61000-6-3: 2007; A1:2011; Generic standards for residential, commercial and light-industrial environments £ Immunity EN61000-6-1: 2007; Generic standards for residential, commercial and light-industrial environments FCC This device complies with FCC rules part 15, subpart B, class B UL Listed (CDN & US) UL916 Energy management equipment
Power Supply (ECY-PS100-240) Power Supply Input Voltage Range 100 to 240 VAC Universal; +10%/-15% Input Current 400mA typical Frequency Range 50 to 60Hz Standby Power consumption <0.5W Overcurrent Protection Field replaceable fuse Fuse Type 2.5A, Fast-acting, high-breaking, 250VAC, 5 × 20mm (TF2.5AH250V, IEC60127-2)
Power Supply Output DC Voltage 18VDC regulated Rated Current Range 0 to 2A Rated Power 40W1
1. The total power consumption of all modules connected to the right of this power supply, and up to the next connected power supply, including any connected loads, must be less than this value.
Hardware Power Distribution Direction Powered modules are connected to the right Backplane Bus Pass-through connection for data and control signals Status Indicator Green LED: power status
ECLYPSE™ Connected System Controller 11 / 18
Control, Automation and Connectivity Server (ECY-S1000) Power Supply Input Voltage 18VDC Power Consumption 8.9W; external loads excluded
Communications Ethernet Connection Speed 10/100 Mbps £ Addressing IPv4 or Hostname BACnet Profile BACnet Building Controller (B-BC)), AMEV AS-A and AS-B (pending) BACnet Listing BTL, WSP B-BC BACnet Interconnectivity BBMD forwarding capabilities
BACnet/IP to BACnet MS/TP routing BACnet Transport Layer IP & MS/TP (optional) Web Server Protocol HTML5 Web Server Application Interface REST API Supported BACnet MS/TP and Modbus RTU and TCP Connectivity:
£ BACnet MS/TP or Modbus RTU 1 × RS-485 serial communications ports
Each RS-485 port supports one communication protocol at a time £ RS-485 Wiring 1-pair + Common/shield £ RS-485 EOL Resistor Built-in £ RS-485 Baud Rates 9600, 19 200, 38 400, or 76 800 bps £ RS-485 Addressing Controller’s Web Configuration Interface £ Modbus TCP Devices must be on the same subnet Supported Wireless Connectivity:
£ Wireless Adapter Optional, USB Port Connection £ Wi-Fi Communication Protocol IEEE 802.11b/g/n and 802.11s £ Wi-Fi Network Types Client, Access Point, Hotspot
Supported Smart Room Control Components1
Maximum number of standard devices supported per controller combined 12 £ Allure EC-Smart-Vue Series 122
£ Allure EC-Smart-Comfort Series 6 £ Allure EC-Smart-Air Series 62
£ EC-Multi Sensor 4 £ ECx-Light-4 / ECx-Light-4D / ECx-Light-DALI 4 £ ECx-Blind-4 / ECx-Blind-4LV 4 Maximum number of Bluetooth low energy devices per controller combined 6 £ Allure UNITOUCH 2 £ EC-Multi-Sensor-BLE 4
A mixed architecture with standard room devices and Bluetooth low energy enabled devices is not recommended.
1. For more details about supported quantities, see the ECLYPSE Selection Tool.xlsm spreadsheet file available for download from SmartSource.
2. A controller can support a maximum of 2 Allure sensor models equipped with a CO2 sensor. Any remaining connected sensors must be without a CO2 sensor.
12 / 18 ECLYPSE™ Connected System Controller
Hardware Processor Sitara ARM processor CPU Speed 1GHz Memory 4GB Non-volatile Flash (applications & storage)
512MB RAM
Real Time Clock (RTC) Real Time Clock with rechargeable battery
Supports SNTP network time synchronization RTC Battery 20 hours charge time, 20 days discharge time
Up to 500 charge / discharge cycles Cryptographic Module FIPS 140-2 Level 1 Compliant Communications Ports:
£ Ethernet 2 switched RJ-45 Ethernet ports
Supported Protocols BACnet/IP, Modbus TCP, NTP, and REST £ USB Connections 2 × USB 2.0 Ports
1 × Micro-USB 2.0 Ports £ RS-485 Serial Communications Screw terminals
Supported Protocols BACnet MS/TP or Modbus RTU £ Subnet RJ-45 Status Indicators Green LED: Power status, Subnet TX, RS-485 TX, and Ethernet Traffic
Orange LED: Controller status, Subnet RX, RS-485 RX, and Ethernet Speed
Mechanical Dimensions (H × W × D) 4.74 × 3.57 × 2.31" (120.31 × 90.67 × 58.56mm)
3.18" 80.82
18.540.73
21.080.83
3.33" 84.47
0.4" 1.092.31" 58.563.57" 90.67
Inches Millimeters
Inter-Connection Gap: 0.01" 0.40
5.13" 130.29
0.06" 1.44
4.74" 120.31
0.39" 9.98 Front BackProfile
Shipping weight 0.85lbs (0.39kg) Mounting DIN rail or screw mounting Enclosure Material FR/ABS Enclosure Rating1 Plastic housing, UL94-V0 flammability rating
Plenum rating per UL1995
1. All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE) directive
Environmental Operating Temperature 32 to 122°F (0 to 50°C)
ECLYPSE™ Connected System Controller 13 / 18
Storage Temperature -22 to 158°F (-30 to 70°C) Relative Humidity 0 to 90% non-condensing Ingress Protection Rating IP20 Nema Rating 1
Standards and Regulations
CE:
£ Emission EN61000-6-3: 2007+A1:2011; Generic standards for residential, commercial and light-industrial environments £ Immunity EN61000-6-1: 2007; Generic standards for residential, commercial and light-industrial environments FCC This device complies with FCC rules part 15, subpart B, class B UL Listed (CDN & US) UL916 Energy management equipment
I/O Modules Power Supply Input Voltage 18VDC Power Consumption Calculate power supply requirements with the ECLYPSE Selection Tool
Hardware Status Indicator Green LEDs: inputs and outputs
For ECY-8UI, ECY-16DI, ECY-6UO, ECY-6UO-HOA, ECY-4UI4UO, ECY-4UI4UO-
HOA, ECY-8UI6UO, ECY-8UI6UO-HOA, ECY-8UI6DOT, & ECY-8UI6DOT-HOA
Models:
Mechanical Dimensions (H × W × D) 4.74 × 3.20 × 2.31" (120.31 × 81.17 × 58.56mm)
2.95" 74.99
4.74" 120.31
3.20" 81.17 2.31" 58.56
3.18" 80.82
18.540.73
21.080.83
Inches Millimeters
Inter-Connection Gap: 0.01" 0.40
Front BackProfile 0.06" 1.44
4.80" 121.75
Shipping weight 0.85lbs (0.39kg) Mounting DIN rail or screw mounting Hot-swappable Yes
14 / 18 ECLYPSE™ Connected System Controller
Enclosure Material FR/ABS Enclosure Rating1 Plastic housing, UL94-V0 flammability rating; Plenum rating per UL1995
1. All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE) directive
Environmental Operating Temperature 32 to 122°F (0 to 50°C) Storage Temperature -22 to 158°F (-30 to 70°C) Relative Humidity 0 to 90% non-condensing Ingress Protection Rating IP20 in accordance with IEC 60537 Nema Rating 1
Standards and Regulations
CE:
£ Emission EN61000-6-3: 2007; A1:2011; Generic standards for residential, commercial and light-industrial environments £ Immunity EN61000-6-1: 2007; Generic standards for residential, commercial and light-industrial environments FCC This device complies with FCC rules part 15, subpart B, class B UL Listed (CDN & US) UL916 Energy management equipment
I/O Modules - Universal Inputs (UI) General Input Type Universal; software configurable Current Input Option Selection DIP switch Input Resolution 16-bit analog to digital converter Power Supply Output 18VDC; 20mA maximum per 0 to 20 mA input
Contact Type Dry contact
Counter Type Dry contact Maximum Frequency 1Hz maximum, Minimum Duty Cycle 500milliseconds On / 500milliseconds Off
0 to 10VDC Range 0 to 10VDC (40kΩ input impedance)
0 to 5VDC Range 0 to 5VDC (high input impedance)
0 to 20mA Range 0 to 20mA
249Ω DIP-switch configurable internal resistor
ECLYPSE™ Connected System Controller 15 / 18
Resistance/Thermistor Range 0 to 350 KΩ Supported Thermistor Types Any that operate in this range Pre-configured Temperature Sensor Types:
£ Thermistor 10KΩ Type 2, 3 (10KΩ @ 77ºF; 25ºC) £ Platinum Pt1000 (1KΩ @ 32ºF; 0ºC) £ Nickel RTD Ni1000 (1KΩ @ 32ºF; 0ºC)
RTD Ni1000 (1KΩ @ 69.8ºF; 21ºC)
I/O Modules - Digital Inputs (DI) General Input Type Dry contact or Open-Collector Low Threshold < 2.5V High Threshold > 3.0V
Pulse/Counter Pulse Input S0 output compatible Maximum Frequency 120Hz Minimum Duty Cycle 4.167milliseconds On / 4.167milliseconds Off
I/O Modules - Universal Outputs (UO) General Output Type Universal; software configurable Output Resolution 10-bit digital to analog Converter Output Protection Built-in snubbing diode to protect against back-EMF, for example when used with a 12VDC relay Load Resistance Minimum 200Ω for 0 to 10VDC and 0 to 12VDC outputs
Maximum 500Ω for 0 to 20mA output Auto-reset Fuse 60mA @ 140ºF; 60ºC
0 or 12VDC (On/Off) Range 0 or 12VDC
PWM
Range Adjustable period from 2 to 65seconds
Floating Minimum Pulse On/Off Time 500milliseconds Drive Time Period Adjustable
0 to 10VDC Range 0 to 10VDC linear
0 to 20mA Range 0 to 20mA
Overview The ECY-CSC is sized to cost-effectively meet the requirements of any HVAC application from small to medium to large systems. The most capable Connected System Controller model can be expanded to support up to 20 input/output (I/O) modules (up to 320 I/Os) while being able to adapt to new requirements as the need arises.
A connecting cable is used to connect successive rows of modules within a controls’ cabinet to provide power and communication.
Features & Benefits = Support for a range of communication protocols such as BACnet
MS/TP, Modbus RTU, Modbus TCP, and M-Bus = With the RESTful API, data can be accessed from different appli-cations, such as energy dashboards, analytics tools, and mobile applications
= Expandable as needs increase to support up to 20 input/output (I/ O) modules (up to 320 I/Os)
= Integrates up to three RS-485 ports = Lighting and shade/sunblind expansion modules to control lights and shades/sunblinds = Compatible with Distech Controls line of Bluetooth® low energy technology enabled devices and mobile application providing state-of-the- art occupant management
= Multi-sensor compatibility combines motion and luminosity (Lux) sensors
= Available remote access to program, configure, or maintain the in-stallation, reducing costs associated with on-site visits
= Terminal blocks are uniquely identified and color-coded for clarity and to prevent wiring mistakes
= Embedded alarms, trend log and schedule support allows for fully distributed data and logic
= Automatic email notifications for system status and alarms to en-sure faster system servicing and response time
Control, Automation and Connectivity Servers
ECY-S1000 Series
S p e c i f i c a t i o n s
2 / 3 ECY-S1000
Example: ECY-S1000E-28-MS
Series WebServer License Points Limit BACnet MS/TP Routing
ECY-S1000
[blank] : No Embedded Graphics E : With Embedded Graphics
-28 : 28 Points HW (3 Modbus) -48 : 48 Points HW (10 Modbus) [blank] : No Limits (320 typ., 96 Modbus)
[blank] : No BACnet MS/TP Routing Option -MS : With BACnet MS/TP Routing1
1. Option already included in no limits license, please specify [blank]
Accessories ECLYPSE Wi-Fi Adapter Wi-Fi Adapter for ECLYPSE Connected Controllers.
ECLYPSE Open-To-Wireless™ Adapter EnOcean communication protocol adapter for ECLYPSE Connected Controllers.
Product Specifications Power Supply Input
Voltage 18VDC Power Consumption 8.9W; external loads excluded
Communications Ethernet Connection Speed 10/100 Mbps
Addressing IPv4 or Hostname BACnet Profile BACnet Building Controller (B-
BC)), AMEV AS-A and AS-B BACnet Listing BTL, WSP B-BC
BACnet Interconnectivity BBMD forwarding capabilities BACnet MS/TP to BACnet/IP routing
BACnet Transport Layer IP & MS/TP (optional) Web Server Protocol HTML5
Web Server Application Interface
REST API
BACnet MS/TP or Modbus
RTU
1 × RS-485 serial communications ports
RS-485 Wiring 1-pair + Common/shield RS-485 EOL Resistor Built-in
RS-485 Baud Rates 9600, 19 200, 38 400, or 76 800 bps
RS-485 Addressing Controller’s Web Configuration Interface
Modbus TCP Devices must be on the same subnet
Wireless Adapter Optional, USB Port Connection Wi-Fi Communication Protocol IEEE 802.11b/g/n and 802.11s
Wi-Fi Network Types Client, Access Point, Hotspot
Supported Smart Room Control Components Maximum number of standard room devices supported per controller combined1
Allure EC-Smart-Vue Series2 12 Allure EC-Smart-Comfort
Series
Allure EC-Smart-Air Series2 6 EC-Multi Sensor 4
ECx-Light-4 / ECx-Light-4D / ECx-Light-DALI
ECx-Blind-4 / ECx-Blind-4LV 4 Maximum number of Bluetooth low energy room devices per controller combined 3
Allure UNITOUCH™ 2 EC-Multi-Sensor-BLE 4
1. For more details about supported quantities, see the ECLYPSE Selection Tool.xlsm spreadsheet file available for download from SmartSource.
2. A controller can support a maximum of 2 Allure sensor models equipped with a CO2 sensor. Any remaining connected sensors must be without a CO2 sensor.
3. A mixed architecture with standard room devices and Bluetooth low energy enabled devices is not recommended.
Hardware Processor Sitara ARM processor
CPU Speed 1GHz Memory 4GB Non-volatile Flash
(applications & storage)
512MB RAM
Real Time Clock (RTC) Real Time Clock with rechargeable battery Supports SNTP network time synchronization
RTC Battery 20 hours charge time, 20 days discharge time Up to 500 charge / discharge cycles
Cryptographic Module FIPS 140-2 Level 1 Compliant Ethernet 2 switched RJ-45 Ethernet ports
(Supported Protocols: BACnet/ IP, Modbus TCP, NTP, and
REST)
USB Connections 2 × USB 2.0 Ports 1 × Micro-USB 2.0 Ports
RS-485 Serial Communications Screw terminals (Supported Protocols: BACnet MS/TP or Modbus RTU)
3 / 3 ECY-S1000_SP_10_EN
Subnet RJ-45 Green LED Power status, Subnet TX, RS-485 TX, and Ethernet Traffic Orange LED Controller status, Subnet RX, RS-485 RX, and Ethernet Speed
Open-to-Wireless Adapter Communication Protocol EnOcean wireless standard1
Connector Type USB Number of Wireless Inputs2 18
1. Available when an optional external ECLYPSE Open-to-Wireless Adapter is connected to the controller. Refer to the Open-to-Wireless Application Guide for a list of supported EnOcean wireless modules.
2. Some wireless modules may use more than one wireless input from the controller.
Mechanical Dimensions (H × W × D) 4.74 × 3.57 × 2.31" (120.31 ×
90.67 × 58.56mm) Shipping weight 0.85lbs (0.39kg)
Mounting DIN rail or screw mounting Enclosure Material FR/ABS Enclosure Rating1 Plastic housing, UL94-V0 flammability rating Plenum rating per UL1995
1. All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE) directive
Environmental Operating Temperature 32 to 122°F (0 to 50°C)
Storage Temperature -22 to 158°F (-30 to 70°C), Relative Humidity 0 to 90% non-condensing
Ingress Protection Rating IP20 Nema Rating 1
Standards and Regulations CE Emission EN61000-6-3: 2007+A1:2011 CE Immunity EN61000-6-1: 2007
FCC Compliance with FCC rules part 15, subpart B, class B
UL Listed (CDN & US) UL916 Energy management equipment
3.18" 80.82
18.540.73
21.080.83
3.33" 84.47
0.4" 1.093.57" 90.67
Inches Millimeters
Inter-Connection Gap: 0.01" 0.40
5.13" 130.29
0.06" 1.44
4.74" 120.31
0.39" 9.98 Front Back
2.31" 58.56
Specifications subject to change without notice.
ECLYPSE, Distech Controls, the Distech Controls logo, EC-Net, Allure, and Allure UNITOUCH are trademarks of Distech Controls Inc. BACnet is a registered trademark of ASHRAE;
BTL is a registered trademark of the BACnet Manufacturers Association. The Bluetooth® word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of such marks is under license. All other trademarks are property of their respective owners.
©, Distech Controls Inc., 2015 - 2019. All rights reserved.
Global Head Office - 4205 place de Java, Brossard, QC, Canada, J4Y 0C4 - EU Head Office - ZAC de Sacuny, 558 avenue Marcel Mérieux, 69530 Brignais, France
Overview The ECLYPSE Connected Terminal Unit Controller (ECY-TU/PTU) is designed to control terminal units such as fan coil units, chilled beams, ceilings, and heat pumps.
It integrates a control, automation and connectivity server, a power supply, and dedicated I/Os in one convenient package.
Each model supports BACnet/IP communication and is listed as a BACnet Building Controller (B-BC).
These products feature wired and wireless advanced IP connectivity for efficient and reliable installation.
The ECY-TU/PTU comes with an embedded web server that enables web-based application configuration and an HTML5 visualization in-terface. It also features embedded scheduling, alarming, and logging.
Control logic and graphic user interface can be customized as re-quired for the application.
Moreover, as part of the Smart Room Control solution, these con-trollers can control lighting fixtures (DALI, ON/OFF, dimming) and shades/sunblind motors (24 VDC or 100-240 VAC, up/down and an-gle rotation) through additional expansion modules.
Features & Benefits = Utilizes BACnet/IP and IT standards, delivering empowered IP connectivity and open integration with building management sys-tems
= No external transformer required = Uses cryptographic modules making it FIPS 140-2 Level 1 Com-pliant = Via its RESTful API, data can be accessed from different applica-tions, such as energy dashboards, analytics tools, and mobile ap-plications
= Comes with ENVYSION™ Viewer and the associated preloaded rooftop unit applications and graphics pre-installed
= xpressENVYSION offers a simplified and streamlined experience in a workflow oriented, drag & drop GUI environment
= Supports EC-gfxProgram, which makes Building Automation Sys-tem (BAS) programming effortless
= Supports Smart Room Control for an end-to-end system for the control of HVAC equipment, lighting, and shades/sunblinds
= Embedded alarms, trend log and schedule support allows for fully distributed data and logic providing a more robust system
= Automatic email notifications for system status and alarms to en-sure faster system servicing and response time
ECLYPSE™ Connected Terminal Unit Controller
S p e c i f i c a t i o n s
2 / 5 ECY-PTU
Example: ECY-PTU-208 (SI)
Series Supply Voltage Input Model Units
ECY-
PTU : 100-240 VAC
TU :1 24 VAC
-107 : 12 Points, 3 Line-Powered Relay Outputs, 2 Line-Powered Triac Outputs -207 : 16 Points, 3 Line-Powered Relay Outputs, 2 Line-Powered Triac Outputs, 4 Analog Outputs -208 : 16 Points, 3 Line-Powered Relay Outputs, 2 24 VAC Triac Outputs, 4 Analog Outputs, 24 VAC Power Supply Outputs -203 :2 16 Points, 3 Unpowered Relay Outputs, 2 24 VAC Triac Outputs, 2 Analog Outputs, 2 Digital/Analog Outputs, 24 VAC Power Supply Outputs
(SI) : Preloaded Apps in SI (Metric) units (IMP) : Preloaded Apps in Imperial (US) units
1. Only available with the 203 Model
2. Only available with the 24 VAC Supply Voltage Input
Product Specifications Power Supply Input (ECY-PTU-107, ECY-PTU-207, and ECY-PTU-208)
Voltage Range 100-240 VAC; ±10% Frequency Range 50 to 60Hz
Overcurrent Protection 4.0 A external circuit breaker type C
Device Insulation Type Double Insulation Overvoltage Category II - 2.5 kV
Power Consumption 5 W plus all external loads Maximum Consumption 4 A
Power Supply Input
(ECY-TU-203)
Voltage Range 24 VAC; ±15%; Class 2 Frequency Range 50 to 60Hz
Overcurrent Protection 2.0 A fast acting, 5x20mm (GMA-2A) internal fuse
Device Insulation Type Double Insulation Overvoltage Category II - 2.5 kV
Power Consumption 5 W plus all external loads Maximum Consumption 2 A
Communications Ethernet Connection Speed 10/100 Mbps
Addressing IPv4 or Hostname BACnet Profile BACnet Building Controller (B-
BC)), AMEV AS-A and AS-B BACnet Listing BTL, WSP B-BC
BACnet Interconnectivity BBMD forwarding capabilities BACnet Transport Layer IP
Web Server Protocol HTML5 Web Server Application
Interface
REST API
Wireless Adapter Optional, USB Port Connection Wi-Fi Communication Protocol IEEE 802.11b/g/n
Wi-Fi Network Types Client, Access Point, Hotspot
Subnetwork Communication RS-485
Cable Cat 5e, 8 conductor twisted pair Connector RJ-45
Connection Topology Daisy-chain Maximum number of standard room devices supported per controller combined1
Allure EC-Smart-Vue Series2 4 Allure EC-Smart-Comfort
Series
Allure EC-Smart-Air Series2 4 EC-Multi Sensor 4
ECx-Light-4 / ECx-Light-4D / ECx-Light-DALI1
ECx-Blind-4 / ECx-Blind-4LV1 4 Maximum number of Bluetooth low energy room devices per controller combined 3
Allure UNITOUCH™ 2 EC-Multi-Sensor-BLE 4
1. For more details about supported quantities, see the ECLYPSE Selection Tool.xlsm spreadsheet file available for download from SmartSource.
2. A controller can support a maximum of 2 Allure sensor models equipped with a CO2 sensor. Any remaining connected sensors must be without a CO2 sensor.
3. A mixed architecture with standard room devices and Bluetooth low energy enabled devices is not recommended.
Hardware Processor Sitara ARM processor
CPU Speed 600MHz Memory 4GB Non-volatile Flash
(applications & storage)
512MB RAM
Real Time Clock (RTC) Real Time Clock with rechargeable battery Supports SNTP network time synchronization
RTC Battery 20 hours charge time, 20 days discharge time Up to 500 charge / discharge cycles
Cryptographic Module FIPS 140-2 Level 1 Compliant Ethernet 2 × switched RJ-45 Ethernet ports with integrated fail-safe for daisy-chaining
ECY-PTU 3 / 5
USB Connections 2 × USB 2.0 Ports 1 × Micro-USB 2.0 Ports
Subnet RJ-45 Green LED Power status and Ethernet
Traffic Orange LED Controller status and Ethernet
Speed
Open-to-Wireless Adapter Communication Protocol EnOcean wireless standard1
Connector Type USB Number of Wireless Inputs2 18
1. Available when an optional external ECLYPSE Open-to-Wireless Adapter is connected to the controller. Refer to the Open-to-Wireless Application Guide for a list of supported EnOcean wireless modules.
2. Some wireless modules may use more than one wireless input from the controller.
Mechanical Dimensions (H × W × D)
142 × 145 × 57 mm (5.60 × 5.71 × 2.24")
Dimensions with Terminal Covers
(H × W × D)
195 × 145 × 57 mm (7.67 × 5.71 × 2.24")
Shipping Weight 0.6 kg [1.32 lbs] Enclosure Material1 FR/ABS
Enclosure Rating Plastic housing, UL94-5VB flammability rating Plenum rating per UL1995
Mounting Din-rail or wall-mounting
1. All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE) directive
Environmental Operating Temperature +5°C to +40°C
(+41°F to +104°F) Storage Temperature -20°C to +70°C
(-4°F to +158°F) Relative Humidity 0 to 90% non-condensing
Ingress Protection Rating IP30 (with terminal block covers and strain relief)
Nema Rating 1 Altitude < 2000 m (6560 ft)
Pollution Degree 2
Standards and Regulations CE Emission EN61000-6-3: 2007+A1:2011 CE Immunity EN61000-6-1: 2007
CE Electrical Safety EN 60730-1 : 2011 FCC Compliance with FCC rules part
15, subpart B, class B UL Listed (CDN & US) UL 61010-1 Energy management equipment
Universal Inputs (UI) General
Input Type Universal; software configurable
Contact Type Dry contact (0 – 3.3VDC)
Counter Type Dry contact (0 – 3.3VDC)
Maximum Frequency 1Hz maximum Minimum Duty Cycle 500milliseconds On /
500milliseconds Off
0 to 10VDC Range 0 to 10VDC (40kΩ input impedance)
Resistance/Thermistor Thermistor 10KΩ Type 2, 3 (10KΩ @ 77ºF;
25ºC)
Sensor Inputs (SI) General
Input Type Sensor; software configurable
Contact Type Dry contact (0 – 3.3VDC)
Counter Type Dry contact (0 – 3.3VDC)
Maximum Frequency 1Hz maximum Minimum Duty Cycle 500milliseconds On /
500milliseconds Off
Resistance/Thermistor Thermistor 10KΩ Type 2, 3 (10KΩ @ 77ºF;
25ºC) Accuracy ±0.1°C @ 25°C (±0.18°F @
77°F)
Digital Inputs (DI) General
Input Type Digital; software configurable
Contact Type Dry contact (0 – 3.3VDC)
Counter Type Dry contact (0 – 3.3VDC)
Maximum Frequency 1Hz maximum Minimum Duty Cycle 5 milliseconds On / 5 milliseconds Off
Power Supply (Vref) Output (Vref) 5 VDC for polarization (I < 1 mA)
Triac Outputs General (ECY-PTU-107 and ECY-PTU-207)
Output Type Triac Voltage Range 0 or 100-240 VAC (same as device power supply) Maximum Current per Output 0.5 A continuous
1 A @ 15% duty cycle for a 10-minute period
Inrush Current 3.0 A maximum (<20 milliseconds)
Common Terminal 1 per pair of outputs
4 / 5 ECY-PTU
General (ECY-PTU-208 and ECY-TU-203)
Output Type Triac Power Source Internal on-board 24 VAC power supply Voltage Range See on-board 24 VAC power supply Current See on-board 24 VAC power supply Common Terminal 1 per pair of outputs
Digital (On/Off) (ECY-PTU-107 and ECY-PTU-207)
Voltage Range 0 or 100-240 VAC (same as device power supply)
Digital (On/Off) (ECY-PTU-208 and ECY-TU-203)
Voltage Range 0 or 24 VAC
PWM
Application Typically Thermal Valve Control
Range Adjustable period from 2 to 65 seconds
Floating Minimum Outputs 2 consecutive outputs
Minimum Pulse On/Off Time 500 milliseconds Drive Time Period Adjustable
Powered Relay Outputs General (ECY-PTU-107, ECY-PTU-207, and ECY-PTU-208)
Output Type Digital Application Typically Fan Speeds
Supplied Voltage Same as device power supply Current 3.0 A max. (inductive or resistive load) for the total sum of the 3 outputs
Resting State Normally Open Common Terminal Shared
Unpowered Relay Outputs General
(ECY-TU-203)
Output Type Digital Application Typically Fan Speeds
Supplied Voltage None Supported Voltage 100-277 VAC
Current 3.0 A max. (inductive or resistive load) for the total sum of the 3 outputs
Protection Must be protected with an external circuit breaker or fast acting, high breaking fuse in accordance with the controlled load (3 A max. / min voltage according to the controlled load)
Resting State Normally Open Common Terminal Shared
Digital Relay Contact Outputs General
Output Type Digital Application Typically Electric Heater Protection Must be protected with an external circuit breaker or fast acting, high breaking fuse in accordance with the controlled load (10 A max. / min voltage according to the controlled load)
Contact Type Dry contact
Voltage Range
(ECY-PTU-107 / ECY-
PTU-207 / ECY-PTU-208)
100-240 VAC
Voltage Range
(ECY-TU-203)
100-277 VAC
Current 9.0 A max. on a resistive load (2 kW @ 230 VAC)
Resting State Normally Open Common Terminal Dedicated digital
Analog Outputs General (ECY-PTU-207, ECY-PTU-208 and ECY-TU-203)
Output Type Analog Voltage Range 0-10 VDC linear
Current 5 mA max Current sourcing Maximum 5 mA at 10 VDC
(minimum resistance 2 kΩ) Current sinking Maximum 2 mA at 1 VDC
(minimum resistance 5 kΩ)
24 VAC Outputs (ECY-PTU-208 and ECY-TU-203) Power Source Internal on-board 24 VAC power supply Voltage Range See on-board 24 VAC power supply Current See on-board 24 VAC power supply
On-board 24 VAC Power Supply General (ECY-PTU-208 and ECY-TU-203)
Power Source Internal on-board 24 VAC power supply
Voltage Range 24 VAC; ± 10% Frequency 50 Hz
Current 700 mA max. on a resistive load
(16 VA @ 24 VAC)
Peak current 850 mA Short-circuit protection (ECY-
PTU-208)
Integrated Fail Safe
Short-circuit protection (ECY-
TU-203)
Fuse
Overload protected Yes
5 / 5 ECY-PTU_SP_16_EN
Digital-Analog Outputs General
(ECY-TU-203)
Output Type Digital Triac or Analog; software configurable
Triac Output Mode See Triac Output specifications Analog Output Mode See Analog Output specifications
Dimensions 5.71145.00
5.54140.84
5.60142.22
Front
2.2456.88
Profile
Millimeters [Inches]
0.246.04
5.07128.76
0.246.04
5.08129.01
0.317.990.317.99
Back 0.051.38
Figure 1: ECY-PTU without terminal block covers 145.00
194.85
Front Profile
5.71
7.67
Front
2.2456.88
Profile
Millimeters [Inches]
1.30
0.317.99 Back
5.07128.76
1.3033.04
33.04
5.08129.01
Back 0.317.99
Figure 2: ECY-PTU with terminal covers
Specifications subject to change without notice.
ECLYPSE, Distech Controls, the Distech Controls logo, EC-Net, Allure, and Allure UNITOUCH are trademarks of Distech Controls Inc. BACnet is a registered trademark of ASHRAE;
BTL is a registered trademark of the BACnet Manufacturers Association. The Bluetooth® word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of such marks is under license. All other trademarks are property of their respective owners.
©, Distech Controls Inc., 2015 - 2019. All rights reserved.
Global Head Office - 4205 place de Java, Brossard, QC, Canada, J4Y 0C4 - EU Head Office - ZAC de Sacuny, 558 avenue Marcel Mérieux, 69530 Brignais, France
*P er fo ra te d su b-pa ne ls a va il ab le in th e ac ce ss or y se ct io n.
Wall-Mount Enclosures 2
Wall-Mount Enclosures 2
P ho n e
-6
F a x (9
-4
P ho n e
-6
F a x (9
-4
(800) 888-5538 sales@functionaldevices.com www.functionaldevices.com
T R A N
SF
O R M
ER
S
102815
TRANSFORMER
9.50" .50"
1.711" 1.
4"
Mounting Hole = .350" x .175"
3.743"
2.256"
2.506"
3.
6"
PRIMARY WIRES SECONDARY WIRES
Blk
Wht
Yel/Wht
Yel
Secondary Yel/Wht wire in phase with Primary Blk wire.
120V 60Hz 24Vac 75VA
2.873"
VA Rating:
Frequency:
Mounting:
Over Current Protection:
Dimensions:
Wire Length:
Operating Temperature:
MTBF:
Construction:
Weight:
Approvals:
50/60 Hz Foot & Single Threaded Hub Circuit Breaker 3.743˝ x 2.506˝ x 3.016˝ (w/ .500˝ NPT Hub) 9.5˝ Typical w/ .5˝ Strip -30 to 140° F 100,000 Hours @ 77° F Split-Bobbin
3.40 lbs.
Class 2 UL5085-3 Listed, C-UL, CE, RoHS
TR75VA001
Transformer 75 VA, 120 to 24 Vac, Circuit Breaker, Foot and Single Threaded Hub Mount
Class 2
SPECIFICATIONS
(800) 888-5538 sales@functionaldevices.com www.functionaldevices.com
T R A N
SF
O R M
ER
S
102815
TRANSFORMER
1.
5"
8.00"
4.085"
1.900"
Mounting Hole = .350" x .175"
.50"
2.515"
2.486"
3.
0"
PRIMARY WIRES SECONDARY WIRES
Blk
Wht
Yel/Wht
Yel
Secondary Yel/Wht wire in phase with Primary Blk wire.
120V 60Hz 24Vac 100VA
3.082"
VA Rating:
Frequency:
Mounting:
Over Current Protection:
Dimensions:
Wire Length:
Operating Temperature:
MTBF:
Construction:
Weight:
Approvals:
50/60 Hz Foot & Single Threaded Hub Circuit Breaker 4.085˝ x 2.515˝ x 3.030˝ (w/ .500˝ NPT Hub) 8˝ Typical w/ .5˝ Strip -30 to 140° F 100,000 Hours @ 77° F Split-Bobbin
3.80 lbs.
Class 2 UL5085-3 Listed, C-UL, CE, RoHS
TR100VA001
Transformer 100 VA, 120 to 24 Vac, Circuit Breaker, Foot and Single Threaded Hub Mount
Class 2
SPECIFICATIONS
Sw itches &
Pilot Lights Signaling Lights
Relays & Sockets
Tim ers
Contactors Term inal Blocks Circuit Breakers
773800-262-IDEC (4332) • USA & Canada
RHRelays & Sockets
RH Series Compact Power Relays
Key features
| • | SPDT through 4PDT, 10A contacts |
| • | Compact power type relays |
| • | Miniature power relays with a large capacity |
| • | 10A contact capacity |
| • | Compact size saves space |
Part Number Selection Part Number
Contact Model Blade Terminal
PCB Termi-nal
Coil Voltage Code (Standard Stock in bold)
SPDT
Standard RH1B-U 0 RH1V2-U 0
AC6V, AC12V, AC24V, AC110V, AC120V,
AC220V, AC240V DC6V, DC12V, DC24V,
DC48V, DC110V
With Indicator RH1B-UL 0 —
With Check Button RH1B-UC 0 —
With Indicator and Check Button RH1B-ULC 0 —
Top Bracket Mounting RH1B-UT 0 —
With Diode (DC coil only) RH1B-UD 0 RH1V2-UD 0 DC6V, DC12V, DC24V, DC48V, DC110V
With Indicator and Diode (DC coil only) RH1B-ULD 0 — DC12V, DC24V, DC48V, DC110V
DPDT
Standard RH2B-U 0 RH2V2-U 0
AC6V, AC12V, AC24V, AC110-120V,
AC220-240V
DC6V, DC12V, DC24V, DC48V, DC100-110V
With Indicator RH2B-UL 0 RH2V2-UL 0
With Check Button RH2B-UC 0 —
With Indicator and Check Button RH2B-ULC 0 —
Top Bracket Mounting RH2B-UT 0 —
With Diode (DC coil only) RH2B-UD 0 RH2V2-UD 0
DC6V, DC12V, DC24V, DC48V, DC100-110V
With Indicator and Diode (DC coil only) RH2B-ULD 0…