h-max-application-manual-mn04008006e.pdf

PDF 2 MB Posted

Attached to
Y1DA--FY23: NRM-Tier 1 (PROJ: 548-23-122) D/B Install Additional Pump on OR Chilled Water Loop
Solicitation number
36C24823R0051_1
Issued by

About this file

This federal contract opportunity solicitation requests bids for a chilled water loop upgrade project at a Department of Veterans Affairs medical facility. The contractor will be required to install a new pump on an existing OR chilled water loop in parallel with two existing pumps to increase pumping capacity. The contractor must also install a new Eaton VFD to match existing units and provide all associated electrical work. New DDC controls with BACnet communication must be integrated into the facility's existing BACnet-compatible BAS. The contractor must provide all necessary engineering and technical assistance. The performance period is 120 days from notice to proceed. The solicitation is fully set aside for Service-Disabled Veteran-Owned Small Businesses.

View the file

Other files

File Type Posted
Award Announcement 36C24823C0052_1.pdf PDF
548-23-122 QAs.pdf PDF
16-104 18-5-18 RECORD PDF PACKAGE CH1-2.pdf PDF
Doors - Windows.Wood Doors.Ash.jpg JPG image
03 30 53.pdf PDF
Brooks controls - approved by Moses lr.pdf PDF
h-max-installation-manual-mn04008005e.pdf PDF
IOM1206 - Daikin Trailblazer (AGZ).pdf PDF
36C24823R0051 0003.pdf PDF
19010 Electrical - SandS.pdf PDF
WPB-VA_S-SHEETS.txt TXT text file
A100 - SS.pdf PDF
19010 Mechical - SandS.pdf PDF
Grundfosliterature-5104627.pdf PDF
h-max-quick-start-guide-mn04008004e.pdf PDF
Structural.pdf PDF
A210 - SS.pdf PDF
36C24823R0051 0002.pdf PDF
S06 36C24823R0051 0001.pdf PDF
Attachment 3 548-23-122 01321615 Spec.docx DOCX document
Attachment 1 548-23-122 010000 Spec.docx DOCX document
Attachment 14 Site Plan.pdf PDF
Attachment 11 548-23-122 AE Instructions DB.docx DOCX document
Attachment 4 548-23-122 013323 Spec.docx DOCX document
Attachment 13 Location Plan.pdf PDF
Attachment 9 Combatting COVID 19.pdf PDF
Attachment 6 Experience Information Sheet.pdf PDF
Attachment 2 548-23-122 014219 Spec.docx DOCX document
Attachment 12 Design Manual Index.pdf PDF
Attachment 10 548-23-122 001121 SpecSOW.docx DOCX document
Attachment 8 WD FL20220220 09.30.2022.pdf PDF
S02 36C24823R0051 for SAM.docx DOCX document
Attachment 5 Project Price Breakdown.xlsx XLSX spreadsheet
Attachment 7 VA Info and Info System Security.pdf PDF
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

H-Max™ HVAC Drives

Application Manual Effective January 2012

New Information

H-Max HVAC Drives

H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com i

Disclaimer of Warranties and Limitation of Liability

The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation’s (“Eaton”) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted.

Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser.

THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR

IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR

MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING

CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE

OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME

PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES.

In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice.

Cover Photo: Eaton H-Max HVAC Drives ii H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com

Support Services

The goal of Eaton is to ensure your greatest possible satisfaction with the operation of our products. We are dedicated to providing fast, friendly, and accurate assistance. That is why we offer you so many ways to get the support you need. Whether it’s by phone, fax, or e-mail, you can access Eaton’s support information 24 hours a day, seven days a week.

Our wide range of services is listed below.

You should contact your local distributor for product pricing, availability, ordering, expediting, and repairs.

Web Site Use the Eaton Web site to find product information. You can also find information on local distributors or Eaton’s sales offices.

Web Site Address www.eaton.com/electrical

EatonCare Customer Support Center Call the EatonCare Support Center if you need assistance with placing an order, stock availability or proof of shipment, expediting an existing order, emergency shipments, product price information, returns other than warranty returns, and information on local distributors or sales offices.

Voice: 877-ETN-CARE (386-2273) (8:00 a.m.–6:00 p.m. EST)

FAX: 800-752-8602

After-Hours Emergency: 800-543-7038 (6:00 p.m.–8:00 a.m. EST) If you are in the U.S. or Canada, and have OI or PLC questions, you can take advantage of our toll-free line for technical assistance with hardware and software product selection, system design and installation, and system debugging and diagnostics. Technical support engineers are available for calls during regular business hours.

Technical Resource Center Voice: 877-ETN-CARE (386-2273) (8:00 a.m.–5:00 p.m. EST)

FAX: 828-651-0549

e-mail: TRC@Eaton.com

European PanelMate Support Center This engineering company, located in Zurich, Switzerland, provides high-level quality support and repair assistance for your PanelMate products. You will receive technical and application support.

For Customers in Europe, contact:

BFA Solutions, Ltd.

Voice: +41 1 806.64.44 (9:00 a.m.–5:00 p.m. CET) e-mail: gk@bfa.ch www.bfa.ch

Repair and Upgrade Service Additional support is also available from our well-equipped Repair and Upgrade Service department. If you have questions regarding the repair or upgrade of an OI product, contact your local distributor.

Repair and Upgrade Service (support for OI) Voice:

877-ETN-CARE (877-386-2273) (8:00 a.m.–5:00 p.m. EST) 414-449-7100 (8:00 a.m.–5:00 p.m. EST)

FAX: 614-882-3414

e-mail: TRC@eaton.com

H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com iii

Table of Contents

SAFETY

Definitions and Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . x

Hazardous High Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . x

Warnings and Cautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . x

Important Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . x

H-MAX SERIES OVERVIEW

How to Use this Manual

Receiving and Inspection

Catalog Number Selection

Power Ratings and Product Selection

HVAC APPLICATION

Specific Functions of Eaton HVAC Application

Example of Control Connections

KEYPAD OF THE DRIVE

Keypad Display

Using the Graphical Keypad

Monitor

EATON H-MAX—STARTUP

Startup Wizard

PID Mini-Wizard

Multi-Pump

MENU STRUCTURE

Menu Structure

PARAMETER FUNCTIONS

Parameter Functions

PARAMETERS

Basic Parameters

Analog Inputs

Digital Inputs

Analog Outputs

Digital Outputs

Drive Control

Protections

PID Controller iv H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com

Table of Contents, continued

I/O AND HARDWARE

Basic I/O

Power Unit Settings

Common Settings

Monitoring

USER SETTINGS

User Settings

PARAMETER DESCRIPTIONS

Parameter Descriptions

DIAGNOSTICS

Fault Codes

Counters

Software

COMMUNICATIONS

BACnet Protocol

Modbus Protocol

N2 Open System Protocol

H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com v

List of Figures

Rating Plate Approval Sticker Carton Labels (U.S. and Europe) Control Connections US Keypad Buttons EMEA Keypad Buttons Main Menu Editing Values on Graphical Keypad Accessing Control Page Parameter Copy Help Text Example Adding Item To Favorites Multi-Monitoring Page Principal Example Diagram of BACnet AC Drive Components (BACnet) BACnet Ethernet Cable RS-485 Cable Strip RS-485 Cable Strip (Aluminum Shield) H-Max AC Drive Terminals (BACnet) RS-485 Ground RS-485 Bus Termination Setup BACnet MS/TP Bus Termination Fault Tracing Diagram for BACnet MS/TP Fault Tracing Diagram for BACnet IP Basic Structure of Modbus Frame Principal Example Diagram of Modbus AC Drive Components (Modbus) Modbus Ethernet Cable RS-485 Cable Strip RS-485 Cable Strip (Aluminum Shield) H-Max AC Drive Terminals (Modbus) RS-485 Ground RS-485 Bus Termination Setup Modbus RTU Bus Termination ID Map Initialization Fault Tracing Diagram for Modbus RTU Fault Tracing Diagram for Modbus TCP AC Drive Components (N2) N2 Cable Strip N2 Cable Strip (Aluminum Shield) H-Max AC Drive Terminals (N2 Protocol) N2 Ground N2 Bus Termination Setup N2 Bus Termination Principal Example Diagram of Metasys N2 Fault Tracing Diagram for N2 vi H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com

List of Tables

H-Max Series Open Drives NEMA Type 1/IP21 or NEMA Type 12/IP44 NEMA Type 1/IP21 or NEMA Type 12/IP44 H-Max Series Adjustable Frequency Drive Option Boards Keypad Menus Basic Monitoring Functions Timer Monitoring Functions Multi-Monitor Functions Basic Settings Analog Input 1 Analog Input 2 Analog Input 3 Analog Input 4 Analog Input 5 Analog Input 6 Basic Settings Digital Input 1 Digital Input 2 Digital Input 3 Digital Input 4 Digital Input 5 Digital Input 6 Digital Input Ext 1 Digital Input Ext 2 Basic Settings Analog Output 1 Digital Output 1 Digital Output 2 Digital Output 3 Supervision Basic Settings Skip Frequencies Motor Control Faults Automatic Reset Basic Settings Setpoints Feedbacks Feedforward Process Supervision Pressure Loss Compensation Basic Settings Setpoints Feedbacks Process Supervision Fixed Frequencies

H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com vii

List of Tables, continued

Fire Mode Multi-Pump Braking Fieldbus Motor 2 Drive Control 2 Interval 1 Interval 2 Interval 3 Interval 4 Interval 5 Timer 1 Timer 2 Timer 3 Basic Parameters Real-Time Clock Fan Control Sine Filter Keypad

RS-485

Ethernet Modbus TCP BACnet IP Monitoring User Settings P2.1… P2.2… P2.3… P2.4… P2.5… P2.6… P2.7… P2.8… P2.9… P2.10… P2.11… P2.12… P2.13… P2.14… P2.15… P2.16… Active Faults Reset Faults Fault History Fault Codes and Descriptions Total Counters Trip Counters Software Information BACnet MS/TP Protocol BACnet IP Protocol viii H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com

List of Tables, continued

Parameters Monitoring Values Ethernet Common Settings (M4.8.1) BACnet IP Settings Monitoring Values BACnet MS/TP—Good Messages BACnet MS/TP—Bad Frames BACnet IP—Good Messages BACnet IP—Bad Frames Object Types and Properties Supported Binary Value Object Analog Value Object Control Word Bits Status Word Bits Typical Fault Conditions Modbus RTU Protocol Modbus TCP Protocol Parameters Monitoring Values Common Settings for Modbus TCP (Ethernet) Modbus TCP Settings Monitoring Values Parity Type FB Protocol Statuses Modbus RTU—Good Messages Modbus RTU—Bad Frames FB Protocol Statuses Modbus TCP—Good Messages Modbus TCP—Bad Frames Supported Functions Defined Coil Registers Defined Input Discrete Defined Input Holding Registers Parameter IDs Fieldbus Process Data IN Control Word Bits Fieldbus Process Data OUT Status Word Bits B1–B28 Status Word Bits B29-B31 (Descriptions of Bit Connections) Parameter Values in 16-bit IDMap Read/Write Registers Parameter Values in 32-Bit IDMap Read/Write Registers Operation Day Counter Resettable Operation Day Counter Energy Counter Resettable Energy Counter Fault History Typical Fault Conditions Process Data OUT Variables

H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com ix

List of Tables, continued

N2 Protocol Parameters Monitoring Values FB Protocol Statuses N2—Good Messages N2—Bad Frames Analog Inputs (AI) Binary Inputs (BI) Analog Outputs (AO) Binary Outputs (BO) Integral Integers (ADI) Typical Fault Conditions Process Data OUT Variables x H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com

Safety

Definitions and Symbols

WARNING

This symbol indicates high voltage. It calls your attention to items or operations that could be dangerous to you and other persons operating this equipment. Read the message and follow the instructions carefully.

This symbol is the “Safety Alert Symbol.” It occurs with either of two signal words: CAUTION or WARNING, as described below.

WARNING

Indicates a potentially hazardous situation which, if not avoided, can result in serious injury or death.

CAUTION

Indicates a potentially hazardous situation which, if not avoided, can result in minor to moderate injury, or serious damage to the product. The situation described in the CAUTION may, if not avoided, lead to serious results.

Important safety measures are described in CAUTION (as well as WARNING).

Hazardous High Voltage

WARNING

Motor control equipment and electronic controllers are connected to hazardous line voltages. When servicing drives and electronic controllers, there may be exposed components with housings or protrusions at or above line potential. Extreme care should be taken to protect against shock.

Stand on an insulating pad and make it a habit to use only one hand when checking components. Always work with another person in case an emergency occurs. Disconnect power before checking controllers or performing maintenance. Be sure equipment is properly grounded. Wear safety glasses whenever working on electronic controllers or rotating machinery.

Warnings and Cautions This manual contains clearly marked cautions and warnings which are intended for your personal safety and to avoid any unintentional damage to the product or connected appliances.

Please read the information included in cautions and warnings carefully.

WARNING

The relay outputs and other I/O-terminals may have a dangerous control voltage present even when H-Max is disconnected from mains.

WARNING

Be sure not to plug the Ethernet/BACnet IP cable to the terminal under the keypad! This might harm your personal computer.

WARNING

Be sure not to plug the Modbus TCP cable to the terminal under the keypad! This might harm your personal computer.

CAUTION

Remove external Control signal before resetting the fault to prevent unintentional restart of the drive.

Important Safety Information

Hazardous High Voltage

WARNING

The components of the power unit of H-Max are live when the AC drive is connected to mains potential.

Coming into contact with this voltage is extremely dangerous and may cause death or severe injury.

WARNING

The motor terminals U, V, W and the brake resistor terminals are live when H-Max is connected to mains, even if the motor is not running.

H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com xi

WARNING

After disconnecting the AC drive from the mains, wait until the indicators on the keypad go out (if no keypad is attached see the indicators on the cover). Wait 5 more minutes before doing any work on the connections of H-Max. Do not open the cover before this time has expired. After expiration of this time, use a measuring equipment to absolutely ensure that no voltage is present. Always ensure absence of voltage before starting any electrical work!

WARNING

The control I/O-terminals are isolated from the mains potential. However, the relay outputs and other I/O-terminals may have a dangerous control voltage present even when H-Max is disconnected from mains.

WARNING

Before connecting the AC drive to mains make sure that the front and cable covers of H-Max are closed.

WARNING

During a ramp stop (see the Application Manual), the motor is still generating voltage to the drive. Therefore, do not touch the components of the AC drive before the motor has completely stopped. Wait until the indicators on the keypad go out (if no keypad is attached see the indicators on the cover). Wait additional 5 minutes before starting any work on the drive.

Important Warnings

WARNING

H-Max AC drive is meant for fixed installations only.

WARNING

Do not perform any measurements when the AC drive is connected to the mains.

WARNING

The ground leakage current of H-Max AC drives exceeds 3.5mA AC. According to standard EN61800-5-1, a reinforced protective ground connection must be ensured. See chapter 1.3.

WARNING

If the AC drive is used as a part of a machine, the machine manufacturer is responsible for providing the machine with a supply disconnecting device (EN 60204-1).

WARNING

Only spare parts delivered by Eaton can be used.

WARNING

At power-up, power brake or fault reset the motor will start immediately if the start signal is active, unless the pulse control for Start/Stop logic has been selected.

Furthermore, the I/O functionalistic (including start inputs) may change if parameters, applications or software are changed.Disconnect, therefore, the motor if an unexpected start can cause danger.

WARNING

The motor starts automatically after automatic fault reset if the auto restart function is activated. See the Application Manual for more detailed information.

WARNING

Prior to measurements on the motor or the motor cable, disconnect the motor cable from the AC drive.

WARNING

Do not touch the components on the circuit boards.

Static voltage discharge may damage the components.

WARNING

Check that the EMC level of the AC drive corresponds to the requirements of your supply network.

xii H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com

Additional Cautions

CAUTION

The H-Max AC drive must always be grounded with an grounding conductor connected to the grounding terminal marked with .

The ground leakage current of H-Max exceeds 3.5 mA AC.

According to EN61800-5-1, one or more of the following conditions for the associated protective circuit shall be satisfied:

a) The protective conductor shall have a cross-sectional area of at least 10 mm2 Cu or 16 mm2 Al, through its total run.

b) Where the protective conductor has a cross-sectional area of less than 10 mm2 Cu or 16 mm2 Al, a second protective conductor of at least the same cross-sectional area shall be provided up to a point where the protective conductor has a cross-sectional area not less than 10 mm2 Cu or 16 mm2 Al.

c) Automatic disconnection of the supply in case of loss of continuity of the protective conductor.

The cross-sectional area of every protective grounding conductor which does not form part of the supply cable or cable enclosure shall, in any case, be not less than:

— 2.5 mm2 if mechanical protection is provided or

— 4 mm2 if mechanical protection is not provided. The ground fault protection inside the AC drive protects only the drive itself against ground faults in the motor or the motor cable. It is not intended for personal safety.

The ground fault protection inside the Ac drive protects only the drive itself against ground faults in the motor or the motor cable. It is not intended for personal safety.

Due to the high capacitive currents present in the AC drive, fault current protective switches may not function properly.

Do not perform any voltage withstand tests on any part of H-Max. There is a certain procedure according to which the tests shall be performed. Ignoring this procedure may result in damaged product.

H-Max Series Overview

H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com 1

H-Max Series Overview

This chapter describes the purpose and contents of this manual, the receiving inspection recommendations and the H-Max Series Open Drive catalog numbering system.

How to Use this Manual

The purpose of this manual is to provide you with information necessary to install, set and customize parameters, start up, troubleshoot and maintain the Eaton H-Max Series adjustable frequency drive (AFD). To provide for safe installation and operation of the equipment, read the safety guidelines at the beginning of this manual and follow the procedures outlined in the following chapters before connecting power to the H-Max Series AFD. Keep this operating manual handy and distribute to all users, technicians and maintenance personnel for reference.

Receiving and Inspection

The H-Max Series AFD has met a stringent series of factory quality requirements before shipment. It is possible that packaging or equipment damage may have occurred during shipment. After receiving your H-Max Series AFD, please check for the following:

Check to make sure that the package includes the Installation Manual (MN04008005E), Quick Start Guide (MN04008004E) and accessory packet. The accessory packet includes:

● Rubber grommets

● EMC grounding clamps for power cables

● Control cable grounding clamps

● EMC jumper locking clips

● M4 screw for EMC level change (FS7 only)

● Additional grounding screw

● Real time clock battery

● UL conduit plate

Inspect the unit to ensure it was not damaged during shipment.

Make sure that the part number indicated on the nameplate corresponds with the catalog number on your order.

If shipping damage has occurred, please contact and file a claim with the carrier involved immediately.

If the delivery does not correspond to your order, please contact your Eaton Electrical representative.

Note: Do not destroy the packing. The template printed on the protective cardboard can be used for marking the mounting points of the H-Max AFD on the wall or in a cabinet.

2 H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com

Rating Plate

Approval Sticker

Carton Labels (U.S. and Europe)

Type:

Input:

Output:

Power (IL):

Chassis:

HMX34AG3D421-B

Vin/Uin 3~AC, 380-480, 50/60 Hz, 3.4 A Vout/Uout 3~AC, 0- Vin/Uin, 0-320 Hz, 3.4 A @ 40°C, 2.7A @ 50°C 1.5HP: 480V / 1.1kW: 400V

NEMA Type 1/IP21

M a d e in F in la n d

S/N:123456789012

VAC LISTED

9D42

Code:12345678901234567890123456789012345

B.ID: 09391

S/N:123456789012

U.S. Carton Label Europe Carton Label

AC DRIVE 0020510471

Type: HMX34AG01221-B

S/N: V12345678901

Code:

07W09

Style: H34AG01221EB

Frequency inverter Frequenzumrichter Convertiesseur des fréquences

EATON CORPORATION

1 234567 890128

Powering Business Worldwide

Marks:

AC DRIVE 0020510471

Type: HMX34AG01221-B

S/N: V12345678901

Code:

07W09

Frequency inverter Frequenzumrichter Convertiesseur des fréquences

1 234567 890128

Powering Business Worldwide

Marks:

EATON GmbH

INPUT: Uin 3~ AC,380-480V, 50/60 Hz,12A

OUTPUT: 3~ AC, 0 -Uin, 0-320 Hz, 12A

Power (IL): 5.5kW: 400V/7.5HP: 480V

Firmware:

Application:

Style: H34AG01221MB

Article: 126943

INPUT: Uin 3~ AC,380-480V, 50/60 Hz,12A

OUTPUT: 3~ AC, 0 -Uin, 0-320 Hz, 12A

Power (IL): 1.5HP: 480V/1.1kW: 400V

Firmware:

Application:

Made in Finland

LISTED

9D42

POWER CONVERSION EQUIPMENT

Made in Finland

LISTED

9D42

POWER CONVERSION EQUIPMENT

H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com 3

Catalog Number Selection

H-Max Series Open Drives

Notes

All boards are varnished (conformed coated). Corrosion resistant.

Battery included in all drives for real-time clock. Three year lifetime.

Keypad kit includes HOA bypass.

Keypad kit includes HOA, back reset for Europe application.

EMI/RFI filters included.

DC link choke included.

Standard Onboard Communications RS-485 Communications

BACnet MS/TP = Master slave/token protocol (Universal BACnet) RS-485 Modbus RTU RS-485, ASCII or RTU, remote terminal unit 32 nodes N2 = Johnson Controls® Metasys® N2 network

Onboard Ethernet-Based Communications (port left side of keypad)

BACnet/IP Ethernet industrial protocol Modbus/TCP Transmission control protocol (Ethernet-based)

Amperes 200–240 Volts 380–480 Volts 3D7 = 3.7A—0.75 hp, 0.55 kW 4D8 = 4.8A—1 hp, 0.75 kW 6D6 = 6.6A—1.5 hp, 1.1 kW 8D0 = 8A—2 hp, 1.5 kW 011 = 11A—3 hp, 2.2 kW 012 = 12A—4 hp, 3 kW 018 = 18A—5 hp, 4 kW 024 = 24A—7.5 hp, 5.5 kW 031 = 31A—10 hp, 7.5 kW 048 = 48A—15 hp, 11 kW 062 = 62A—20 hp, 15 kW 075 = 75A—25 hp, 18.5 kW 088 = 88A—30 hp, 22 kW 105 = 105A—40 hp, 30 kW 140 = 140A—50 hp, 37 kW 170 = 170A—60 hp, 45 kW 205 = 205A—75 hp, 55 kW 261 = 261A—100 hp, 75 kW 310 = 310A—125 hp, 90 kW

3D4 = 3.4A—1.5 hp, 1.1 kW 4D8 = 4.8—2 hp, 1.5 kW 5D6 = 5.6A—3 hp, 2.2 kW 8D0 = 8A—4 hp, 3 kW 9D6 = 9.6A—5 hp, 4 kW 012 = 12A—7.5 hp, 5.5 kW 016 = 16A—10 hp, 7.5 kW 023 = 23A—15 hp, 11 kW 031 = 31A—20 hp, 15 kW 038 = 38A—25 hp, 18.5 kW 046 = 46A—30 hp, 22 kW 061 = 61A—40 hp, 30 kW 072 = 72A—50 hp, 37 kW 087 = 87A—60 hp, 45 kW 105 = 105A—75 hp, 55 kW 140 = 140A—100 hp, 75 kW 170 = 170A—125 hp, 90 kW 205 = 205A—150 hp, 110 kW 261 = 261A—200 hp, 132 kW 310 = 310A—250 hp, 160 kW

Input Options Frame and Voltage Specific

2 = EMC C2

HMX 3 4 A G 3D4 2 1 - N

Phase 3 = Three-phase

Product HMX = HVAC drive

Voltage 2 = 200–240V 4 = 380–480V

Software Series A–Z

Keypad G = Graphical panel

Braking/Application N = No brake chopper

(low overload)

Enclosure 1 = Open NEMA Type 1 IP21 2 = Open NEMA Type 12 IP44

4 H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com

Power Ratings and Product Selection

H-Max Series Drives—208–230 Volt

NEMA Type 1/IP21 or NEMA Type 12/IP44

Note

1 For sizing reference, full-load motor running currents—UL508C.

FS

Frame Size

Drive Rated Current and hp

Drive Input Amps

NEC Motor 60 Hz 230V Amps 1

De-Rated Assigned Motor Ratings _ Can Be:

Drive Rating Low Overload Full Load Amps at 40°C

230V 60 Hz Horsepower

Low Overload Full Load Amps at 50°C

Open Drive kW 230V 50 Hz

1 = N1 = IP21

2 = N12 = IP44

Catalog Number

FS4 3.7 0.75 3.2 3.2 2.6 0.55 HMX32AG3D72_-N

4.8 1 4.3 4.2 3.7 0.75 HMX32AG4D82_-N

6.6 1.5 6 6 4.6 1.1 HMX32AG6D62_-N

8 2 7.2 6.8 6.6 1.5 HMX32AG8D02_-N

11 3 9.7 9.6 8 2.2 HMX32AG0112_-N

12.5 4 10.9 N/A 9 3 HMX32AG0122_-N

FS5 18 5 16.1 15.2 12.5 4 HMX32AG0182_-N

24 7.5 21.7 22 18 5.5 HMX32AG0242_-N

31 10 27.7 28 25 7.5 HMX32AG0312_-N

FS6 48 15 43.8 42 31 11 HMX32AG0482_-N

62 20 57 54 48 15 HMX32AG0622_-N

FS7 75 25 69 68 62 18.5 HMX32AG0752_-N

88 30 82.1 80 75 22 HMX32AG0882_-N

105 40 99 104 88 30 HMX32AG1052_-N

FS8 140 50 133 130 114 37 HMX32AG1402_-N

170 60 163 154 140 45 HMX32AG1702_-N

205 75 198 192 170 55 HMX32AG2052_-N

FS9 261 100 256 248 211 75 HMX32AG2612_-N

310 125 303 N/A 251 90 HMX32AG3102_-N

H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com 5

H-Max Series Drives—380–480 Volt

NEMA Type 1/IP21 or NEMA Type 12/IP44

H-Max Series Adjustable Frequency Drive Option Boards

Note

1 For sizing reference, full-load motor running currents—UL508C.

FS

Frame Size

Drive Input Rated Current and hp

Drive Input Amps

NEC Motor 60 Hz 460V Amps 1

De-Rated Assigned Motor Ratings _ Can Be:

Low Overload Full Load Amps at 40°C

460V 60 Hz Horsepower

Low Overload Full Load Amps at 50°C

Open Drive kW 400V 50 Hz

1 = N1 = IP21

2 = N12 = IP44

Catalog Number

FS4 3.4 1.5 3.4 3 2.6 1.1 HMX34AG3D42_-N

4.8 2 4.6 3.4 3.4 1.5 HMX34AG4D82_-N

5.6 3 5.4 4.8 4.3 2.2 HMX34AG5D62_-N

8.0 5 8.1 7.6 5.6 3.0 HMX34AG8D02_-N

9.6 5 9.3 N/A 8 4 HMX34AG9D62_-N

12 7.5 11.3 11 9.6 5.5 HMX34AG0122_-N

FS5 16 10 15.4 14 12 7.5 HMX34AG0162_-N

23 15 21.3 21 16 11 HMX34AG0232_-N

31 20 28.4 27 23 15 HMX34AG0312_-N

FS6 38 25 36.7 34 31 18.5 HMX34AG0382_-N

46 30 43.6 40 38 22 HMX34AG0462_-N

61 40 58.2 52 46 30 HMX34AG0612_-N

FS7 72 50 67.5 65 61 37 HMX34AG0722_-N

87 60 85.3 77 72 45 HMX34AG0872_-N

105 75 100.6 96 87 55 HMX34AG1052_-N

FS8 140 100 139.4 124 105 75 HMX34AG1402_-N

170 125 166.5 156 140 90 HMX34AG1702_-N

205 150 200 180 170 110 HMX34AG2052_-N

FS9 261 200 258 240 205 132 HMX34AG2612_-N

310 250 303 302 251 160 HMX34AG3102_-N

Option Board Part Number

Assigned to Control Module Slot: Description

XMX-IO-B1-A D or E Expanded 6 digital output—two outputs are programmable as digital inputs or outputs

XMX-IO-B2-A D or E Expanded relay outputs—two programmable relays (each with a NO and NC contact) and thermistor input

XMX-IO-B4-A D or E Expanded analog inputs and outputs—one analog input and two analog outputs (isolated)

XMX-IO-B5-A D or E Expanded relay outputs—contains three programmable relays (one NO contact each)

XMX-IO-B9-A D or E Accepts up to five AC inputs (42–240 Vac) and one relay output (NO)

XMX-IO-BF-A D or E Expanded analog and digital output—one analog, one digital, and one relay output (NO)

XMX-COM-C4-A D or E LonWorks® communication

HVAC Application

6 H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com

HVAC Application

The Eaton HVAC drive contains a preloaded application for instant use and supports HVAC specific terminology and functionality. In addition, the H-Max drive uses a patented Active Energy Control algorithm. In addition to your drive efficiency, the controller works to minimize losses in your motor throughout the defined speed range delivering industry-leading energy efficiency.

Specific Functions of Eaton HVAC Application

The Eaton HVAC application is an easy-to-use application for not only basic pump and fan applications where only one motor and one drive is needed, but also offers extensive possibilities for PID control.

Features

● Startup Wizard for extremely fast setup for basic pump or fan applications

● Mini-Wizards to ease the setup of applications

● Hand/Off/Auto button for easy change between Hand (keypad), OFF, and Auto (Remote control) place. The auto control place is selectable by parameter (I/O or Fieldbus)

● Control page for easy operation and monitoring of the most essential values

● Run interlock input (damper interlock). Drive will not start before this input is activated

● Different pre-heat modes used to avoid condensation problems

● Maximum output frequency 320 Hz

● Real-time clock and timer functions available (optional battery required). Possible to program three time channels to achieve different functions on the drive (for example, Start/Stop and Preset frequencies)

● External PID-controller available. Can be used to control a valve using the drive’s I/O, for example

● Sleep mode function which automatically enables and disables drive running with user defined levels to save energy

● Two-zone PID-controller (two different feedback signals;

minimum and maximum control)

● Two setpoint sources for the PID-control. Selectable with digital input

● PID setpoint boost function

● Feed forward function to improve the response to the process changes

● Process value supervision

● Multi-pump control

● Pressure loss compensation for compensating pressure losses in the pipework, for example, when sensor is incorrectly placed near the pump or fan

HVAC Application

H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com 7

Example of Control Connections

Control Connections

Slot A

A

+10V

AI–1+

Vin

AI–2+

AI–2–

24Vout

GND

DIN1

DIN2

DIN3

24Vout

GND

DIN4

DIN5

DIN6

AO–1+

AO–1–

DATA–

Reference Output Analog Input Voltage (Range 0–10 Vdc) (can be programmed to current 4–20 mA) Analog Output Common (Ground)

Analog Input Common PI Setpoint or Feedback Control Voltage Output (0.1A max.)

I/O Ground

START/STOP (Contact closed = start)

External Fault (Closed = fault) Run Interlock Permissive IP Interlock (Closed = OK) DIN1–DIN6 Common

Control Voltage Output (0.1A max.)

I/O Ground

Fire Mode (Contact closed = fire mode)

Force Bypass (Contact closed = bypass)

DIN1–DIN6 Common

Output Frequency (0–20 mA)

Analog Output Common (Ground)

RS-485 DATA–

Speed Select 0–100% (Preset speed)

U (T1)

V (T2)

W (T3)

R+

R–

L1

L2

L3

Three-Phase Input Input (Single-Phase not available)

Three-Phase Output

DB

Chopper

Terminal Factory Default Signal

Resistor

Analog Input Current (Range 4–20 mA) (can be programmed to voltage 0–10 Vdc) PI Setpoint or Feedback

B DATA+

RO1 Bypass Run

RO2 Drive Run

RO3 Fault

24 Vdc/8A 250 Vac/8A 125 Vdc/0.4A

Relay Board 1 Default Signal

Slot B

Analog

RS-485 DATA+

Factory Jumper

COM

CMB

30 24 Vdcin Auxiliary Input Voltage

Circuit Breaker

Optional

Motor

RJ-45 BACnet/IP Ethernet Industrial Protocol Modbus/TCP Transmission Control Protocol (Ethernet Based)

5% DC Link Reactor

Programmable BACnet, Modbus, FLN, N2

ON

CURRENT

CURRENT

CURRENT

RS485

AO1

AI2

AI1

OFF

VOLTAGE

VOLTAGE

VOLTAGE

Test

Keypad of the Drive

8 H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com

Keypad of the Drive

The control keypad is the interface between the Eaton H-MAX frequency converter and the user. With the control keypad it is possible to control the speed of a motor, to supervise the state of the equipment and to set the frequency converter’s parameters.

There are two different keypads used with the H-MAX drive.

The North American Keypad is slightly different than the EMEA Keypad. Functionality is quite similar. The EMEA keypad does not support the bypass functionality commonly used in the United States.

US Keypad Buttons

EMEA Keypad Buttons

Switching Between Drive and Bypass

Move Cursor Left Back when Pressed for two Seconds

Stop Button/Fault Reset Start Button

Change Control Place Between Hand-Off-Auto

Move Cursor Right

Increase Value Scroll Menu Up

Decrease Value Scroll Menu Down

Enter Menu Confirm Selection

Back Fault Reset

Move Cursor Left

Stop Button Start Button

Change Control Place Between Hand-Off-Auto

Move Cursor Right

Increase Value Scroll Menu Up

Decrease Value Scroll Menu Down

Enter Menu Confirm Selection

H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com 9

Keypad Display

The keypad display indicates the status of the motor and the drive and any irregularities in motor or drive functions. On the display, the user sees information about his present location in the menu structure and the item displayed.

Main Menu

The data on the control keypad are arranged in menus and submenus. Use the up and down arrows to move between the menus. Enter the group/item by pressing the OK button and return to the former level by pressing the Back/Reset button.

The Location field indicates your current location. The Status field gives information about the present status of the drive. See “Control Connections” on Page 7.

Main Menu

Using the Graphical Keypad

Editing Values

Change value of a parameter following the procedure below:

1. Locate the parameter.

2. Enter the Edit mode.

3. Set new value with the up/down arrow buttons. You can also move from digit to digit with the arrow buttons left/right if the value is numerical and then change the value with the up/down arrow buttons.

4. Confirm change with OK button or ignore change by returning to previous level with Back/ Reset button.

Status Field

STOP/RUN

STOP E-Energy Hand I/O

Direction Run Mode

Hand/Off/Auto

Control Place

PC/IO/KEYPAD/FIELDBUS

Location Field (Parameter ID number and current menu location)

Activated Group/Item Press OK to Enter

10 H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com

Editing Values on Graphical Keypad

HOA Control Button

The HOA (Hand-Off-Auto) button is used for two functions:

to quickly access the Control page and to easily change between the Hand (Keypad), Off, and Auto (Remote) control places.

Control Place

The control place is the source of control where the drive can be started and stopped. Every control place has its own parameter for selecting the frequency reference source. In the HVAC drive, the Hand control place is always the keypad.

The Auto control place is determined by parameter P2.1.1 (Keypad, I/O Terminal, I/O three-wire, or Fieldbus CTRL). The selected control place can be seen on the status bar of the keypad.

Local Control

The keypad is always used as control place while in hand control. Hand control has higher priority than auto control.

Therefore, if, for example, bypassed by parameter P2.1.17 through digital input while in Remote, the control place will still switch to Keypad if Hand is selected. Switching between Hand, Off, and Auto Control can be done by pressing the HOA button on the keypad.

Changing Control Place

Change of control place from Hand to Auto (keypad).

1. Anywhere in the menu structure, push the HOA button.

2. Push the arrow up or the arrow down button to select Hand/Off/Auto and confirm with the OK button.

3. On the next display, select Hand, Off, or Auto and again confirm with the OK button.

4. The display will return to the same location as it was when the HOA button was pushed. However, if the Remote control place was changed to Hand (Keypad) you will be prompted for keypad reference.

STOP READY I/O

STOP READY I/O

STOP READY I/O

OK OK

OK

STOP READY I/O

STOP READY I/O

OR:

BACK

RESET

H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com 11

Accessing the Control Page

The Control page is meant for easy operation and monitoring of the most essential values.

1. Anywhere in the menu structure, push the HOA button.

2. Push the arrow up or the arrow down button to select Control page and confirm with the OK button.

3. The control page appears. If keypad control place and keypad reference are selected to be used, you can set the Keypad reference after having pressed the OK button. If other control places or reference values are used, the display will show Frequency reference which is not editable. The other values on the page are Multimonitoring values. You can choose which values appear here for monitoring (for this procedure, see Application Manual).

Accessing Control Page

HOA

STOP READY Keypad

Edit

OK

OK

STOP READY Keypad

0.00 Hz

STOP READY Keypad

0.00 Hz

OK

STOP READY I/O

12 H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com

Copying Parameters

The parameter copy function can be used to copy parameters from one drive to another.

The parameters are first saved to the keypad, then the keypad is detached and connected to another drive. Finally, the parameters are downloaded to the new drive, restoring them from the keypad.

Before any parameters can successfully be copied from one drive to another, the drive has to be stopped when the parameters are downloaded.

● First, go into User settings menu and locate the Parameter backup submenu. In the Parameter backup submenu, there are three possible functions to be selected:

1. Restore factory defaults will re-establish the parameter settings originally made at the factory.

2. By selecting Save to keypad you can copy all parameters to the keypad.

3. Restore from keypad will copy all parameters from keypad to a drive.

Parameter Copy

Note: If the keypad is changed between drives of different sizes, the copied values of these parameters will not be used:

Motor nominal current (P2.1.12) Motor nominal voltage (P2.1.13) Motor nominal speed (P2.1.15) Motor power factor (P2.1.16) Motor nominal frequency (P2.1.14) Service factor (P2.1.18) Switching frequency (P2.7.7) Motor current limit (P2.1.17) Maximum frequency (P2.1.9)

STOP READY Keypad STOP READY Keypad STOP READY Keypad

H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com 13

Help Texts

The graphical keypad features instant help and information displays for various items.

All parameters offer an instant help display. Select Help and press the OK button.

Text information is also available for faults, alarms, and the Startup Wizard.

Help Text Example

Adding Item To Favorites

You might need to refer to certain parameter values or other items often. Instead of locating them one by one in the menu structure, you may want to add them to a folder called Favorites where they can easily be reached.

Adding Item To Favorites

STOP READY I/O STOP READY I/O

OK OK

STOP READY I/O

Basic Settings

Motor Nom Voltg

230.00 V

Motor Nom Speed 1430 rpm

Motor Nom Freq

50.00 Hz

Edit

Help

Motor Nom Freq

Add to favorites

Motor Nom Freq was added to favorites. Press OK to continue.

STOP READY I/O STOP READY I/O STOP READY I/O

14 H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com

Monitor

Multi-Monitor

On the multi-monitor page, you can collect nine values that you wish to monitor.

Multi-Monitoring Page

Change the monitored value by activating the value cell (with arrow buttons left/right) and clicking OK. Then choose a new item on the Monitoring values list and click OK again.

STOP READY I/O STOP READY I/O

STOP READY I/O STOP READY I/O

Eaton H-Max—Startup

H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com 15

Eaton H-Max—Startup

Startup Wizard

In the Startup Wizard, you will be prompted for essential information needed by the drive so that it can start controlling your process. In the Wizard, you will need the following keypad buttons:

Left/Right arrows. Use these to easily move between digits and decimals.

Up/Down arrows. Use these to move between options in menu and to change value.

OK button. Confirm selection with this button.

Back/Reset button. Pressing this button, you can return to the previous question in the Wizard. If pressed at the first question, the Startup Wizard will be cancelled.

Once you have connected power to your Eaton H-Max frequency converter, follow these instructions to easily set up your drive.

Note

1 These questions appear if battery is installed.

Now the Startup Wizard is done.

The Startup Wizard can be re-initiated by pressing and holding the back/reset button for two seconds. The Startup Wizard will appear upon next power up.

1 Run Startup Wizard Yes No

2 Language Select Depends on language package

3 Daylight Saving 1 Russia

US

EU

OFF

4 Time 1 hh:mm:ss

5 Day 1 dd.mm.

6 Year 1 yyyy

OK

BACK

RESET

7 Application H-Max Standard

PID

Multi-Pump

8 Bypass Enabled Disabled

9 Motor Nominal Current Min: 0.26A Max: Drive Dependent

10 Motor Nominal Voltage Min: 180.0V Max: 690.0V

11 Motor Nominal Frequency Min: 8 Hz Max: 320 Hz

12 Motor Nominal Speed Min: 24 RPM Max: 19200 RPM

13 Min Frequency Min: 0 Hz Max: 60 Hz

14 Max Frequency Min: 12 Hz Max: 320 Hz

15 Accel Time 1 Min: 0.1s Max: 3000s

16 Decel Time 1 Min: 0.1s Max: 3000s

17 StartSourceHand Keypad FieldbusCTRL I/O Three-Wire I/O Terminal

18 StartSourceAuto I/O Terminal Keypad FieldbusCTRL I/O Three-Wire

19 SpeedSetptHand Keypad Ref P1D1 Activated

AI1 + AI2

AI2

AI1

Fieldbus

20 SpeedSetptAuto PID1 Activated

AI1 + AI2

AI2

AI1

Fieldbus Keypad Ref

Eaton H-Max—Startup

16 H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com

PID Mini-Wizard

The PID Mini-Wizard is activated in the Quick Setup menu.

This Wizard presupposes that you are going to use the PID controller in the “one feedback/one setpoint” mode. The control place will be I/O A and the default process unit “%”.

The PID Mini-Wizard asks for the following values to be set:

Multi-Pump

If Multi-Pump is the selected application, parameter group

2.12 will be visible in the menu structure. Default values may need to be adjusted to meet your application needs.

1 FeedBack1 Srce AI2

AI1

Not Used ProceDataIn8 ProceDataIn7 ProceDataIn6 ProceDataIn5 ProceDataIn4 ProceDataIn3 ProceDataIn2 ProceDataIn1

AI6

AI5

AI4

AI3

2 Process Unit Selection (Several Selections)

3 Process Unit Min —

4 Process Unit Max —

5 P-Gain Min: 0% Max: 200%

6 Integration Time Min: 0.00s Max: 600.00s

7 SetPT1 Source Keypad SP1 Not Used ProceDataIn8 ProceDataIn7 ProceDataIn6 ProceDataIn5 ProceDataIn4 ProceDataIn3 ProceDataIn2 ProceDataIn1

AI6

AI5

AI4

AI3

AI2

AI1

Parameter Group Name

Parameter Number

Parameter Name

Parameter Group 2.12:

Multi-Pump

P2.12.1 Number of motors

P2.12.2 Interlock function

P2.12.3 Include FC

P2.12.4 Autochange

P2.12.5 Autochange interval

P2.12.6 Autochange: frequency limit

P2.12.7 Autochange: motor limit

P2.12.8 Bandwidth

P2.12.9 Bandwidth delay

Menu Structure

H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com 17

Menu Structure

Keypad Menus

Monitor Basic Diagnostics Active Faults

Timer Functions Reset Faults

Multimonitor Fault History

Parameters Basic Parameters Total Counters

Analog Inputs Trip Counters

Digital Inputs Software Info

Analog Outputs I/O & Hardware Basic I/O

Digital Outputs Slot D

Drive Control Slot E

Motor Control Real Time Clock

Protections Power Unit Settings

Fixed Frequencies Keypad

Fire Mode RS-485

Multi-Pump Ethernet

Braking User Settings —

Fieldbus Favorites —

Second Parameter Set

Timer Functions

Parameter Functions

18 H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com

Parameter Functions

Basic Monitoring Functions

Parameter Number Parameter Name Unit ID Description

V1.1.1 Output frequency Hz 1 Output Frequency of the Drive

V1.1.2 Frequency Reference Hz 25 Frequency Reference to Motor Control

V1.1.3 Motor Speed RPM rpm 2 Motor speed in rpm

V1.1.4 Motor Current A 3 Motor Current

V1.1.5 Motor Torque % 4 Calculated Shaft Torque

V1.1.6 Motor Power % % 5 Total Power Consumption of AC Drive

V1.1.7 Motor Voltage V 6 Motor Voltage

V1.1.8 DC-Link Voltage V 7 DC-Link Voltage

V1.1.9 Unit Temperature °C 8 Heatsink temperature

V1.1.10 Motor Temperature % 9 Calculated Motor Temperature

V1.1.11 Analog Input 1 % 13 Analog input signal scaled according to the range or custom min and max chosen in the I/O config menu

V1.1.12 Analog Input 2 % 14 Analog input signal scaled according to the range or custom min and max chosen in the I/O config menu

V1.1.13 Analog Output 1 % 26 Value of analog output in % of the signal range

V1.1.14 DI1, DI2, DI3 Binary 15 This monitor value shows the status of the I/Os

V1.1.15 DI4, DI5, DI6 Binary 16 This monitor value shows the status of the I/Os

V1.1.16 PID1 Setpoint % 20 Setpoint value fed to the PID controller in process units

V1.1.17 PID1 Feedback % 21 Feedback Value fed to the PID controller in process units

V1.1.18 PID1 Error % 22 Error value of the PID controller. Deviation of the feedback from setpoint in process units.

V1.1.19 PID2 Setpoint % 83 Setpoint value fed to the PID controller in process units

V1.1.20 PID2 Feedback % 84 Feedback Value fed to the PID controller in process units

V1.1.21 PID2 Error % 85 Error value of the PID controller. Deviation of the feedback from setpoint in process units.

V1.1.22 Drive Status Word BitCoded 43 Bitcoded status of the drive. B1=Ready, B2=Run, B3=Fault, B6=RunEnable, B7=Alarm Active, B12=Run Request, B13=Motor Regulator Active

V1.1.23 Motor Speed % % 1360 Percent of full motor speed

V1.1.24 Last Active Fault Num 37 The fault code of the latest activated fault that has not been reset

H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com 19

Timer Monitoring Functions

Multi-Monitor Functions

Note: The “x” in the parameter number represents the assembled monitoring window. Values range from 1 to 9.

Parameter Number Parameter Name Unit ID Description

V1.2.1 TC1, TC2, TC3 ON/OFF 1703 This monitor value shows the status of the time channels

V1.2.2 Interval 1 ON/OFF 1704 This monitor value shows the status of the timer interval

V1.2.3 Interval 2 ON/OFF 1705 This monitor value shows the status of the timer interval

V1.2.4 Interval 3 ON/OFF 1706 This monitor value shows the status of the timer interval

V1.2.5 Interval 4 ON/OFF 1707 This monitor value shows the status of the timer interval

V1.2.6 Interval 5 ON/OFF 1708 This monitor value shows the status of the timer interval

V1.2.7 Timer 1 sec 1709 If the timer has been activated, this monitor value shows the remaining time of the timer.

V1.2.8 Timer 2 sec 1710 If the timer has been activated, this monitor value shows the remaining time of the timer.

V1.2.9 Timer 3 sec 1711 If the timer has been activated, this monitor value shows the remaining time of the timer.

V1.2.10 Real Time Clock h/m/s 1712 Time of Day (Military Time)

Parameter Number Parameter Name Unit ID Description

V1.3.x.1 Drive Status Word Binary 43 Bitcoded status of the drive. B1=Ready, B2=Run, B3=Fault, B6=RunEnable, B7=Alarm Active, B12=Run Request, B13=Motor Regulator Active

V1.3.x.2 Analog Input 1 % 13 Analog input signal scaled according to the range or custom min and max chosen in the I/O config menu

V1.3.x.3 Analog Input 2 % 14 Analog input signal scaled according to the range or custom min and max chosen in the I/O config menu

V1.3.x.4 Analog Output 1 % 26 Value of analog output in % of the signal range

V1.3.x.5 AutoChange N/A 1720 No Function

V1.3.x.6 DC-Link Voltage V 7 DC-Link Voltage of the Drive

V1.3.x.7 DI1, DI2, DI3 Binary 15 This monitor value shows the status of the I/Os

V1.3.x.8 DI4, DI5, DI6 Binary 16 This monitor value shows the status of the I/Os

V1.3.x.9 RO1, RO2, RO3 Binary 17 This monitor value shows the status of the I/Os

V1.3.x.10 Frequency Reference Hz 25 Frequency Reference to Motor Control

V1.3.x.11 Interval 1 ON/OFF 1704 This monitor value shows the status of the timer interval

V1.3.x.12 Interval 2 ON/OFF 1705 This monitor value shows the status of the timer interval

V1.3.x.13 Interval 3 ON/OFF 1706 This monitor value shows the status of the timer interval

V1.3.x.14 Interval 4 ON/OFF 1707 This monitor value shows the status of the timer interval

V1.3.x.15 Interval 5 ON/OFF 1708 This monitor value shows the status of the timer interval

V1.3.x.16 Motor Current A 3 Motor Current

V1.3.x.17 Motor Power KW KW 73 Calculated Power Consumption of the Motor

V1.3.x.18 Motor Power % % 5 Total Power Consumption of AC Drive

V1.3.x.19 Motor Speed RPM rpm 2 Motor speed in rpm

V1.3.x.20 Motor Torque % 4 Calculated Shaft Torque

V1.3.x.21 Motor Voltage V 6 Motor Voltage

20 H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com

Multi-Monitor Functions, continued

Note: The “x” in the parameter number represents the assembled monitoring window. Values range from 1 to 9.

Parameter Number Parameter Name Unit ID Description

V1.3.x.22 Motor Running Binary 30 This monitor value shows if the motor is running

V1.3.x.23 Motor Temperature % 9 Calculated Motor Temperature

V1.3.x.25 PID1 Status Words 24 This monitor value shows if the PID is Active

V1.3.x.26 PID2 Status Words 87 This monitor value shows if the PID is Active

V1.3.x.27 PID1 Error % 22 Error value of the PID controller. Deviation of the feedback from setpoint in process units.

V1.3.x.28 PID1 Feedback % 21 Feedback Value fed to the PID controller in process units

V1.3.x.29 PID1 Output % 23 Output value delivered from the PID controller in process units

V1.3.x.30 PID1 Setpoint % 20 Setpoint value fed to the PID controller in process units

V1.3.x.31 PID2 Error % 85 Error value of the PID controller. Deviation of the feedback from setpoint in process units.

V1.3.x.32 PID2 Feedback % 84 Feedback Value fed to the PID controller in process units

V1.3.x.33 PID2 Output % 86 Output value delivered from the PID controller in process units

V1.3.x.34 PID2 Setpoint % 83 Setpoint value fed to the PID controller in process units

V1.3.x.35 Real Time Clock h/m/s 1712 Time of Day (Military Time)

V1.3.x.36 Run Request Chain Words 1361 This monitor value shows the status of a run request

V1.3.x.37 TC1, TC2, TC3 ON/OFF 1703 This monitor value shows the status of the time channels

V1.3.x.38 Timer 1 sec 1709 If the timer has been activated, this monitor value shows the remaining time of the timer.

V1.3.x.39 Timer 2 sec 1710 If the timer has been activated, this monitor value shows the remaining time of the timer.

V1.3.x.40 Timer 3 sec 1711 If the timer has been activated, this monitor value shows the remaining time of the timer.

V1.3.x.41 Unit Temperature °C 8 Heatsink temperature

V1.3.x.42 Motor Speed % % 1360 Motor Speed in %

V1.3.x.43 Last Active Fault Num 37 The fault code of the latest activated fault that has not been reset

V1.3.x.44 Run Time Hours Hrs 1364 Drive Run Time in Hours

V1.3.x.45 Power On Hours Hrs 1363 Power On Time in Hours

V1.3.x.46 Frequency Reference Hz 1365 Frequency Reference to Motor Control

V1.3.x.53 Energy Counter varies 2291 Amount of Energy taken from the Supply Network, No Reset

V1.3.x.55 Run Time a d hh:min N/A Run Time of Drive

V1.3.x.56 Power On Time a d hh:min N/A Power On Time of Drive

V1.3.x.57 Start Command Counter Num 2295 The number of times the power unit has been started

V1.3.x.58 Energy Counter varies 2296 Resettable Energy Counter

V1.3.x.60 Run Time N/A N/A N/A

V1.3.x.61 Run Time N/A N/A N/A

V1.3.x.62 Run Time N/A N/A N/A

V1.3.x.63 Power On Time N/A N/A N/A

V1.3.x.64 Power On Time N/A N/A N/A

V1.3.x.65 Power On Time N/A N/A N/A

Parameters

H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com 21

Parameters

Basic Parameters

Basic Settings

Parameter Number Parameter Name

Change in Run Min. Max. Default ID Values

P2.1.1 Application N 0 2 0 213 0 = H-MAX Standard

1 = PID

2 = Multi-Pump

P2.1.2 ByPass N 0 1 1 214 0 = Disabled 1 = Enabled

P2.1.3 HOA Control Stc N 0 1 0 1359 0 = Keypad Ctrl 1 = I/O Terminal

P2.1.4 Start Srce Hand N 0 3 0 1300 0 = Keypad 1 = I/O Terminal 2 = I/O 3-wire 3 = FieldbusCTRL

P2.1.5 Speed Setpt Hand N 2 7 2 1301 2 = Keypad Ref 3 = Fieldbus

4 = AI1

5 = AI2

6 = AI1 + AI2

7 = PID1 Activated

P2.1.6 Start Srce Auto N 0 3 1 1302 0 = Keypad 1 = I/O Terminal 2 = I/O 3-wire 3 = FieldbusCTRL

P2.1.7 Speed Setpt Auto (see P2.1.5)

N 2 7 4 1303 2 = Keypad Ref 3 = Fieldbus

4 = AI1

5 = AI2

6 = AI1 + AI2

7 = PID1 Activated

P2.1.8 Min Frequency N 0,00 Hz Max frequency 12,00 Hz 101 See Range

P2.1.9 Max Frequency N Min frequency 320,00 Hz 50,00/60,00 102 See Range

P2.1.10 Accel Time 1 Y 0.1 s 3000,0 s 60,0 s 103 See Range

P2.1.11 Decel Time 1 Y 0.1 s 3000,0 s 60,0 s 104 See Range

P2.1.12 Motor Nom Currnt N varies varies varies 113 See Range

P2.1.13 Motor Nom Voltg N 180,0 V 690,0 V varies 110 See Range

P2.1.14 Motor Nom Freq N 12,00 Hz 320,00 Hz 50,00/60,00 111 See Range

P2.1.15 Motor Nom Speed N 24 rpm 19200 rpm 1440/1750 112 See Range

P2.1.16 MotorPowerFactor N 0,30 1,00 0,82 120 See Range

P2.1.17 Current Limit N…

This is the start of the file's text. The full file is on GovTribe.