This federal contract opportunity solicitation requests bids for a chilled water loop upgrade project at a Department of Veterans Affairs medical facility. The contractor will be required to install a new pump on an existing OR chilled water loop in parallel with two existing pumps to increase pumping capacity. The contractor must also install a new Eaton VFD to match existing units and provide all associated electrical work. New DDC controls with BACnet communication must be integrated into the facility's existing BACnet-compatible BAS. The contractor must provide all necessary engineering and technical assistance. The performance period is 120 days from notice to proceed. The solicitation is fully set aside for Service-Disabled Veteran-Owned Small Businesses.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
H-Max™ HVAC Drives
Application Manual Effective January 2012
New Information
H-Max HVAC Drives
H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com i
Disclaimer of Warranties and Limitation of Liability
The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation’s (“Eaton”) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted.
Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser.
THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR
IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR
MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING
CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE
OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME
PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES.
In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice.
Cover Photo: Eaton H-Max HVAC Drives ii H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com
Support Services
The goal of Eaton is to ensure your greatest possible satisfaction with the operation of our products. We are dedicated to providing fast, friendly, and accurate assistance. That is why we offer you so many ways to get the support you need. Whether it’s by phone, fax, or e-mail, you can access Eaton’s support information 24 hours a day, seven days a week.
Our wide range of services is listed below.
You should contact your local distributor for product pricing, availability, ordering, expediting, and repairs.
Web Site Use the Eaton Web site to find product information. You can also find information on local distributors or Eaton’s sales offices.
Web Site Address www.eaton.com/electrical
EatonCare Customer Support Center Call the EatonCare Support Center if you need assistance with placing an order, stock availability or proof of shipment, expediting an existing order, emergency shipments, product price information, returns other than warranty returns, and information on local distributors or sales offices.
Voice: 877-ETN-CARE (386-2273) (8:00 a.m.–6:00 p.m. EST)
FAX: 800-752-8602
After-Hours Emergency: 800-543-7038 (6:00 p.m.–8:00 a.m. EST) If you are in the U.S. or Canada, and have OI or PLC questions, you can take advantage of our toll-free line for technical assistance with hardware and software product selection, system design and installation, and system debugging and diagnostics. Technical support engineers are available for calls during regular business hours.
Technical Resource Center Voice: 877-ETN-CARE (386-2273) (8:00 a.m.–5:00 p.m. EST)
FAX: 828-651-0549
e-mail: TRC@Eaton.com
European PanelMate Support Center This engineering company, located in Zurich, Switzerland, provides high-level quality support and repair assistance for your PanelMate products. You will receive technical and application support.
For Customers in Europe, contact:
BFA Solutions, Ltd.
Voice: +41 1 806.64.44 (9:00 a.m.–5:00 p.m. CET) e-mail: gk@bfa.ch www.bfa.ch
Repair and Upgrade Service Additional support is also available from our well-equipped Repair and Upgrade Service department. If you have questions regarding the repair or upgrade of an OI product, contact your local distributor.
Repair and Upgrade Service (support for OI) Voice:
877-ETN-CARE (877-386-2273) (8:00 a.m.–5:00 p.m. EST) 414-449-7100 (8:00 a.m.–5:00 p.m. EST)
FAX: 614-882-3414
e-mail: TRC@eaton.com
H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com iii
Table of Contents
SAFETY
Definitions and Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . x
Hazardous High Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . x
Warnings and Cautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . x
Important Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . x
H-MAX SERIES OVERVIEW
How to Use this Manual
Receiving and Inspection
Catalog Number Selection
Power Ratings and Product Selection
HVAC APPLICATION
Specific Functions of Eaton HVAC Application
Example of Control Connections
KEYPAD OF THE DRIVE
Keypad Display
Using the Graphical Keypad
Monitor
EATON H-MAX—STARTUP
Startup Wizard
PID Mini-Wizard
Multi-Pump
MENU STRUCTURE
Menu Structure
PARAMETER FUNCTIONS
Parameter Functions
PARAMETERS
Basic Parameters
Analog Inputs
Digital Inputs
Analog Outputs
Digital Outputs
Drive Control
Protections
PID Controller iv H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com
Table of Contents, continued
I/O AND HARDWARE
Basic I/O
Power Unit Settings
Common Settings
Monitoring
USER SETTINGS
User Settings
PARAMETER DESCRIPTIONS
Parameter Descriptions
DIAGNOSTICS
Fault Codes
Counters
Software
COMMUNICATIONS
BACnet Protocol
Modbus Protocol
N2 Open System Protocol
H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com v
List of Figures
Rating Plate Approval Sticker Carton Labels (U.S. and Europe) Control Connections US Keypad Buttons EMEA Keypad Buttons Main Menu Editing Values on Graphical Keypad Accessing Control Page Parameter Copy Help Text Example Adding Item To Favorites Multi-Monitoring Page Principal Example Diagram of BACnet AC Drive Components (BACnet) BACnet Ethernet Cable RS-485 Cable Strip RS-485 Cable Strip (Aluminum Shield) H-Max AC Drive Terminals (BACnet) RS-485 Ground RS-485 Bus Termination Setup BACnet MS/TP Bus Termination Fault Tracing Diagram for BACnet MS/TP Fault Tracing Diagram for BACnet IP Basic Structure of Modbus Frame Principal Example Diagram of Modbus AC Drive Components (Modbus) Modbus Ethernet Cable RS-485 Cable Strip RS-485 Cable Strip (Aluminum Shield) H-Max AC Drive Terminals (Modbus) RS-485 Ground RS-485 Bus Termination Setup Modbus RTU Bus Termination ID Map Initialization Fault Tracing Diagram for Modbus RTU Fault Tracing Diagram for Modbus TCP AC Drive Components (N2) N2 Cable Strip N2 Cable Strip (Aluminum Shield) H-Max AC Drive Terminals (N2 Protocol) N2 Ground N2 Bus Termination Setup N2 Bus Termination Principal Example Diagram of Metasys N2 Fault Tracing Diagram for N2 vi H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com
List of Tables
H-Max Series Open Drives NEMA Type 1/IP21 or NEMA Type 12/IP44 NEMA Type 1/IP21 or NEMA Type 12/IP44 H-Max Series Adjustable Frequency Drive Option Boards Keypad Menus Basic Monitoring Functions Timer Monitoring Functions Multi-Monitor Functions Basic Settings Analog Input 1 Analog Input 2 Analog Input 3 Analog Input 4 Analog Input 5 Analog Input 6 Basic Settings Digital Input 1 Digital Input 2 Digital Input 3 Digital Input 4 Digital Input 5 Digital Input 6 Digital Input Ext 1 Digital Input Ext 2 Basic Settings Analog Output 1 Digital Output 1 Digital Output 2 Digital Output 3 Supervision Basic Settings Skip Frequencies Motor Control Faults Automatic Reset Basic Settings Setpoints Feedbacks Feedforward Process Supervision Pressure Loss Compensation Basic Settings Setpoints Feedbacks Process Supervision Fixed Frequencies
H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com vii
List of Tables, continued
Fire Mode Multi-Pump Braking Fieldbus Motor 2 Drive Control 2 Interval 1 Interval 2 Interval 3 Interval 4 Interval 5 Timer 1 Timer 2 Timer 3 Basic Parameters Real-Time Clock Fan Control Sine Filter Keypad
RS-485
Ethernet Modbus TCP BACnet IP Monitoring User Settings P2.1… P2.2… P2.3… P2.4… P2.5… P2.6… P2.7… P2.8… P2.9… P2.10… P2.11… P2.12… P2.13… P2.14… P2.15… P2.16… Active Faults Reset Faults Fault History Fault Codes and Descriptions Total Counters Trip Counters Software Information BACnet MS/TP Protocol BACnet IP Protocol viii H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com
List of Tables, continued
Parameters Monitoring Values Ethernet Common Settings (M4.8.1) BACnet IP Settings Monitoring Values BACnet MS/TP—Good Messages BACnet MS/TP—Bad Frames BACnet IP—Good Messages BACnet IP—Bad Frames Object Types and Properties Supported Binary Value Object Analog Value Object Control Word Bits Status Word Bits Typical Fault Conditions Modbus RTU Protocol Modbus TCP Protocol Parameters Monitoring Values Common Settings for Modbus TCP (Ethernet) Modbus TCP Settings Monitoring Values Parity Type FB Protocol Statuses Modbus RTU—Good Messages Modbus RTU—Bad Frames FB Protocol Statuses Modbus TCP—Good Messages Modbus TCP—Bad Frames Supported Functions Defined Coil Registers Defined Input Discrete Defined Input Holding Registers Parameter IDs Fieldbus Process Data IN Control Word Bits Fieldbus Process Data OUT Status Word Bits B1–B28 Status Word Bits B29-B31 (Descriptions of Bit Connections) Parameter Values in 16-bit IDMap Read/Write Registers Parameter Values in 32-Bit IDMap Read/Write Registers Operation Day Counter Resettable Operation Day Counter Energy Counter Resettable Energy Counter Fault History Typical Fault Conditions Process Data OUT Variables
H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com ix
List of Tables, continued
N2 Protocol Parameters Monitoring Values FB Protocol Statuses N2—Good Messages N2—Bad Frames Analog Inputs (AI) Binary Inputs (BI) Analog Outputs (AO) Binary Outputs (BO) Integral Integers (ADI) Typical Fault Conditions Process Data OUT Variables x H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com
Safety
Definitions and Symbols
WARNING
This symbol indicates high voltage. It calls your attention to items or operations that could be dangerous to you and other persons operating this equipment. Read the message and follow the instructions carefully.
This symbol is the “Safety Alert Symbol.” It occurs with either of two signal words: CAUTION or WARNING, as described below.
WARNING
Indicates a potentially hazardous situation which, if not avoided, can result in serious injury or death.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, can result in minor to moderate injury, or serious damage to the product. The situation described in the CAUTION may, if not avoided, lead to serious results.
Important safety measures are described in CAUTION (as well as WARNING).
Hazardous High Voltage
WARNING
Motor control equipment and electronic controllers are connected to hazardous line voltages. When servicing drives and electronic controllers, there may be exposed components with housings or protrusions at or above line potential. Extreme care should be taken to protect against shock.
Stand on an insulating pad and make it a habit to use only one hand when checking components. Always work with another person in case an emergency occurs. Disconnect power before checking controllers or performing maintenance. Be sure equipment is properly grounded. Wear safety glasses whenever working on electronic controllers or rotating machinery.
Warnings and Cautions This manual contains clearly marked cautions and warnings which are intended for your personal safety and to avoid any unintentional damage to the product or connected appliances.
Please read the information included in cautions and warnings carefully.
WARNING
The relay outputs and other I/O-terminals may have a dangerous control voltage present even when H-Max is disconnected from mains.
WARNING
Be sure not to plug the Ethernet/BACnet IP cable to the terminal under the keypad! This might harm your personal computer.
WARNING
Be sure not to plug the Modbus TCP cable to the terminal under the keypad! This might harm your personal computer.
CAUTION
Remove external Control signal before resetting the fault to prevent unintentional restart of the drive.
Important Safety Information
Hazardous High Voltage
WARNING
The components of the power unit of H-Max are live when the AC drive is connected to mains potential.
Coming into contact with this voltage is extremely dangerous and may cause death or severe injury.
WARNING
The motor terminals U, V, W and the brake resistor terminals are live when H-Max is connected to mains, even if the motor is not running.
H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com xi
WARNING
After disconnecting the AC drive from the mains, wait until the indicators on the keypad go out (if no keypad is attached see the indicators on the cover). Wait 5 more minutes before doing any work on the connections of H-Max. Do not open the cover before this time has expired. After expiration of this time, use a measuring equipment to absolutely ensure that no voltage is present. Always ensure absence of voltage before starting any electrical work!
WARNING
The control I/O-terminals are isolated from the mains potential. However, the relay outputs and other I/O-terminals may have a dangerous control voltage present even when H-Max is disconnected from mains.
WARNING
Before connecting the AC drive to mains make sure that the front and cable covers of H-Max are closed.
WARNING
During a ramp stop (see the Application Manual), the motor is still generating voltage to the drive. Therefore, do not touch the components of the AC drive before the motor has completely stopped. Wait until the indicators on the keypad go out (if no keypad is attached see the indicators on the cover). Wait additional 5 minutes before starting any work on the drive.
Important Warnings
WARNING
H-Max AC drive is meant for fixed installations only.
WARNING
Do not perform any measurements when the AC drive is connected to the mains.
WARNING
The ground leakage current of H-Max AC drives exceeds 3.5mA AC. According to standard EN61800-5-1, a reinforced protective ground connection must be ensured. See chapter 1.3.
WARNING
If the AC drive is used as a part of a machine, the machine manufacturer is responsible for providing the machine with a supply disconnecting device (EN 60204-1).
WARNING
Only spare parts delivered by Eaton can be used.
WARNING
At power-up, power brake or fault reset the motor will start immediately if the start signal is active, unless the pulse control for Start/Stop logic has been selected.
Furthermore, the I/O functionalistic (including start inputs) may change if parameters, applications or software are changed.Disconnect, therefore, the motor if an unexpected start can cause danger.
WARNING
The motor starts automatically after automatic fault reset if the auto restart function is activated. See the Application Manual for more detailed information.
WARNING
Prior to measurements on the motor or the motor cable, disconnect the motor cable from the AC drive.
WARNING
Do not touch the components on the circuit boards.
Static voltage discharge may damage the components.
WARNING
Check that the EMC level of the AC drive corresponds to the requirements of your supply network.
xii H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com
Additional Cautions
CAUTION
The H-Max AC drive must always be grounded with an grounding conductor connected to the grounding terminal marked with .
The ground leakage current of H-Max exceeds 3.5 mA AC.
According to EN61800-5-1, one or more of the following conditions for the associated protective circuit shall be satisfied:
a) The protective conductor shall have a cross-sectional area of at least 10 mm2 Cu or 16 mm2 Al, through its total run.
b) Where the protective conductor has a cross-sectional area of less than 10 mm2 Cu or 16 mm2 Al, a second protective conductor of at least the same cross-sectional area shall be provided up to a point where the protective conductor has a cross-sectional area not less than 10 mm2 Cu or 16 mm2 Al.
c) Automatic disconnection of the supply in case of loss of continuity of the protective conductor.
The cross-sectional area of every protective grounding conductor which does not form part of the supply cable or cable enclosure shall, in any case, be not less than:
— 2.5 mm2 if mechanical protection is provided or
— 4 mm2 if mechanical protection is not provided. The ground fault protection inside the AC drive protects only the drive itself against ground faults in the motor or the motor cable. It is not intended for personal safety.
The ground fault protection inside the Ac drive protects only the drive itself against ground faults in the motor or the motor cable. It is not intended for personal safety.
Due to the high capacitive currents present in the AC drive, fault current protective switches may not function properly.
Do not perform any voltage withstand tests on any part of H-Max. There is a certain procedure according to which the tests shall be performed. Ignoring this procedure may result in damaged product.
H-Max Series Overview
H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com 1
H-Max Series Overview
This chapter describes the purpose and contents of this manual, the receiving inspection recommendations and the H-Max Series Open Drive catalog numbering system.
How to Use this Manual
The purpose of this manual is to provide you with information necessary to install, set and customize parameters, start up, troubleshoot and maintain the Eaton H-Max Series adjustable frequency drive (AFD). To provide for safe installation and operation of the equipment, read the safety guidelines at the beginning of this manual and follow the procedures outlined in the following chapters before connecting power to the H-Max Series AFD. Keep this operating manual handy and distribute to all users, technicians and maintenance personnel for reference.
Receiving and Inspection
The H-Max Series AFD has met a stringent series of factory quality requirements before shipment. It is possible that packaging or equipment damage may have occurred during shipment. After receiving your H-Max Series AFD, please check for the following:
Check to make sure that the package includes the Installation Manual (MN04008005E), Quick Start Guide (MN04008004E) and accessory packet. The accessory packet includes:
● Rubber grommets
● EMC grounding clamps for power cables
● Control cable grounding clamps
● EMC jumper locking clips
● M4 screw for EMC level change (FS7 only)
● Additional grounding screw
● Real time clock battery
● UL conduit plate
Inspect the unit to ensure it was not damaged during shipment.
Make sure that the part number indicated on the nameplate corresponds with the catalog number on your order.
If shipping damage has occurred, please contact and file a claim with the carrier involved immediately.
If the delivery does not correspond to your order, please contact your Eaton Electrical representative.
Note: Do not destroy the packing. The template printed on the protective cardboard can be used for marking the mounting points of the H-Max AFD on the wall or in a cabinet.
2 H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com
Rating Plate
Approval Sticker
Carton Labels (U.S. and Europe)
Type:
Input:
Output:
Power (IL):
Chassis:
HMX34AG3D421-B
Vin/Uin 3~AC, 380-480, 50/60 Hz, 3.4 A Vout/Uout 3~AC, 0- Vin/Uin, 0-320 Hz, 3.4 A @ 40°C, 2.7A @ 50°C 1.5HP: 480V / 1.1kW: 400V
NEMA Type 1/IP21
M a d e in F in la n d
S/N:123456789012
VAC LISTED
9D42
Code:12345678901234567890123456789012345
B.ID: 09391
S/N:123456789012
U.S. Carton Label Europe Carton Label
AC DRIVE 0020510471
Type: HMX34AG01221-B
S/N: V12345678901
Code:
07W09
Style: H34AG01221EB
Frequency inverter Frequenzumrichter Convertiesseur des fréquences
EATON CORPORATION
1 234567 890128
Powering Business Worldwide
Marks:
AC DRIVE 0020510471
Type: HMX34AG01221-B
S/N: V12345678901
Code:
07W09
Frequency inverter Frequenzumrichter Convertiesseur des fréquences
1 234567 890128
Powering Business Worldwide
Marks:
EATON GmbH
INPUT: Uin 3~ AC,380-480V, 50/60 Hz,12A
OUTPUT: 3~ AC, 0 -Uin, 0-320 Hz, 12A
Power (IL): 5.5kW: 400V/7.5HP: 480V
Firmware:
Application:
Style: H34AG01221MB
Article: 126943
INPUT: Uin 3~ AC,380-480V, 50/60 Hz,12A
OUTPUT: 3~ AC, 0 -Uin, 0-320 Hz, 12A
Power (IL): 1.5HP: 480V/1.1kW: 400V
Firmware:
Application:
Made in Finland
LISTED
9D42
POWER CONVERSION EQUIPMENT
Made in Finland
LISTED
9D42
POWER CONVERSION EQUIPMENT
H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com 3
Catalog Number Selection
H-Max Series Open Drives
Notes
All boards are varnished (conformed coated). Corrosion resistant.
Battery included in all drives for real-time clock. Three year lifetime.
Keypad kit includes HOA bypass.
Keypad kit includes HOA, back reset for Europe application.
EMI/RFI filters included.
DC link choke included.
Standard Onboard Communications RS-485 Communications
BACnet MS/TP = Master slave/token protocol (Universal BACnet) RS-485 Modbus RTU RS-485, ASCII or RTU, remote terminal unit 32 nodes N2 = Johnson Controls® Metasys® N2 network
Onboard Ethernet-Based Communications (port left side of keypad)
BACnet/IP Ethernet industrial protocol Modbus/TCP Transmission control protocol (Ethernet-based)
Amperes 200–240 Volts 380–480 Volts 3D7 = 3.7A—0.75 hp, 0.55 kW 4D8 = 4.8A—1 hp, 0.75 kW 6D6 = 6.6A—1.5 hp, 1.1 kW 8D0 = 8A—2 hp, 1.5 kW 011 = 11A—3 hp, 2.2 kW 012 = 12A—4 hp, 3 kW 018 = 18A—5 hp, 4 kW 024 = 24A—7.5 hp, 5.5 kW 031 = 31A—10 hp, 7.5 kW 048 = 48A—15 hp, 11 kW 062 = 62A—20 hp, 15 kW 075 = 75A—25 hp, 18.5 kW 088 = 88A—30 hp, 22 kW 105 = 105A—40 hp, 30 kW 140 = 140A—50 hp, 37 kW 170 = 170A—60 hp, 45 kW 205 = 205A—75 hp, 55 kW 261 = 261A—100 hp, 75 kW 310 = 310A—125 hp, 90 kW
3D4 = 3.4A—1.5 hp, 1.1 kW 4D8 = 4.8—2 hp, 1.5 kW 5D6 = 5.6A—3 hp, 2.2 kW 8D0 = 8A—4 hp, 3 kW 9D6 = 9.6A—5 hp, 4 kW 012 = 12A—7.5 hp, 5.5 kW 016 = 16A—10 hp, 7.5 kW 023 = 23A—15 hp, 11 kW 031 = 31A—20 hp, 15 kW 038 = 38A—25 hp, 18.5 kW 046 = 46A—30 hp, 22 kW 061 = 61A—40 hp, 30 kW 072 = 72A—50 hp, 37 kW 087 = 87A—60 hp, 45 kW 105 = 105A—75 hp, 55 kW 140 = 140A—100 hp, 75 kW 170 = 170A—125 hp, 90 kW 205 = 205A—150 hp, 110 kW 261 = 261A—200 hp, 132 kW 310 = 310A—250 hp, 160 kW
Input Options Frame and Voltage Specific
2 = EMC C2
HMX 3 4 A G 3D4 2 1 - N
Phase 3 = Three-phase
Product HMX = HVAC drive
Voltage 2 = 200–240V 4 = 380–480V
Software Series A–Z
Keypad G = Graphical panel
Braking/Application N = No brake chopper
(low overload)
Enclosure 1 = Open NEMA Type 1 IP21 2 = Open NEMA Type 12 IP44
4 H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com
Power Ratings and Product Selection
H-Max Series Drives—208–230 Volt
NEMA Type 1/IP21 or NEMA Type 12/IP44
Note
1 For sizing reference, full-load motor running currents—UL508C.
FS
Frame Size
Drive Rated Current and hp
Drive Input Amps
NEC Motor 60 Hz 230V Amps 1
De-Rated Assigned Motor Ratings _ Can Be:
Drive Rating Low Overload Full Load Amps at 40°C
230V 60 Hz Horsepower
Low Overload Full Load Amps at 50°C
Open Drive kW 230V 50 Hz
1 = N1 = IP21
2 = N12 = IP44
Catalog Number
FS4 3.7 0.75 3.2 3.2 2.6 0.55 HMX32AG3D72_-N
4.8 1 4.3 4.2 3.7 0.75 HMX32AG4D82_-N
6.6 1.5 6 6 4.6 1.1 HMX32AG6D62_-N
8 2 7.2 6.8 6.6 1.5 HMX32AG8D02_-N
11 3 9.7 9.6 8 2.2 HMX32AG0112_-N
12.5 4 10.9 N/A 9 3 HMX32AG0122_-N
FS5 18 5 16.1 15.2 12.5 4 HMX32AG0182_-N
24 7.5 21.7 22 18 5.5 HMX32AG0242_-N
31 10 27.7 28 25 7.5 HMX32AG0312_-N
FS6 48 15 43.8 42 31 11 HMX32AG0482_-N
62 20 57 54 48 15 HMX32AG0622_-N
FS7 75 25 69 68 62 18.5 HMX32AG0752_-N
88 30 82.1 80 75 22 HMX32AG0882_-N
105 40 99 104 88 30 HMX32AG1052_-N
FS8 140 50 133 130 114 37 HMX32AG1402_-N
170 60 163 154 140 45 HMX32AG1702_-N
205 75 198 192 170 55 HMX32AG2052_-N
FS9 261 100 256 248 211 75 HMX32AG2612_-N
310 125 303 N/A 251 90 HMX32AG3102_-N
H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com 5
H-Max Series Drives—380–480 Volt
NEMA Type 1/IP21 or NEMA Type 12/IP44
H-Max Series Adjustable Frequency Drive Option Boards
Note
1 For sizing reference, full-load motor running currents—UL508C.
FS
Frame Size
Drive Input Rated Current and hp
Drive Input Amps
NEC Motor 60 Hz 460V Amps 1
De-Rated Assigned Motor Ratings _ Can Be:
Low Overload Full Load Amps at 40°C
460V 60 Hz Horsepower
Low Overload Full Load Amps at 50°C
Open Drive kW 400V 50 Hz
1 = N1 = IP21
2 = N12 = IP44
Catalog Number
FS4 3.4 1.5 3.4 3 2.6 1.1 HMX34AG3D42_-N
4.8 2 4.6 3.4 3.4 1.5 HMX34AG4D82_-N
5.6 3 5.4 4.8 4.3 2.2 HMX34AG5D62_-N
8.0 5 8.1 7.6 5.6 3.0 HMX34AG8D02_-N
9.6 5 9.3 N/A 8 4 HMX34AG9D62_-N
12 7.5 11.3 11 9.6 5.5 HMX34AG0122_-N
FS5 16 10 15.4 14 12 7.5 HMX34AG0162_-N
23 15 21.3 21 16 11 HMX34AG0232_-N
31 20 28.4 27 23 15 HMX34AG0312_-N
FS6 38 25 36.7 34 31 18.5 HMX34AG0382_-N
46 30 43.6 40 38 22 HMX34AG0462_-N
61 40 58.2 52 46 30 HMX34AG0612_-N
FS7 72 50 67.5 65 61 37 HMX34AG0722_-N
87 60 85.3 77 72 45 HMX34AG0872_-N
105 75 100.6 96 87 55 HMX34AG1052_-N
FS8 140 100 139.4 124 105 75 HMX34AG1402_-N
170 125 166.5 156 140 90 HMX34AG1702_-N
205 150 200 180 170 110 HMX34AG2052_-N
FS9 261 200 258 240 205 132 HMX34AG2612_-N
310 250 303 302 251 160 HMX34AG3102_-N
Option Board Part Number
Assigned to Control Module Slot: Description
XMX-IO-B1-A D or E Expanded 6 digital output—two outputs are programmable as digital inputs or outputs
XMX-IO-B2-A D or E Expanded relay outputs—two programmable relays (each with a NO and NC contact) and thermistor input
XMX-IO-B4-A D or E Expanded analog inputs and outputs—one analog input and two analog outputs (isolated)
XMX-IO-B5-A D or E Expanded relay outputs—contains three programmable relays (one NO contact each)
XMX-IO-B9-A D or E Accepts up to five AC inputs (42–240 Vac) and one relay output (NO)
XMX-IO-BF-A D or E Expanded analog and digital output—one analog, one digital, and one relay output (NO)
XMX-COM-C4-A D or E LonWorks® communication
HVAC Application
6 H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com
HVAC Application
The Eaton HVAC drive contains a preloaded application for instant use and supports HVAC specific terminology and functionality. In addition, the H-Max drive uses a patented Active Energy Control algorithm. In addition to your drive efficiency, the controller works to minimize losses in your motor throughout the defined speed range delivering industry-leading energy efficiency.
Specific Functions of Eaton HVAC Application
The Eaton HVAC application is an easy-to-use application for not only basic pump and fan applications where only one motor and one drive is needed, but also offers extensive possibilities for PID control.
Features
● Startup Wizard for extremely fast setup for basic pump or fan applications
● Mini-Wizards to ease the setup of applications
● Hand/Off/Auto button for easy change between Hand (keypad), OFF, and Auto (Remote control) place. The auto control place is selectable by parameter (I/O or Fieldbus)
● Control page for easy operation and monitoring of the most essential values
● Run interlock input (damper interlock). Drive will not start before this input is activated
● Different pre-heat modes used to avoid condensation problems
● Maximum output frequency 320 Hz
● Real-time clock and timer functions available (optional battery required). Possible to program three time channels to achieve different functions on the drive (for example, Start/Stop and Preset frequencies)
● External PID-controller available. Can be used to control a valve using the drive’s I/O, for example
● Sleep mode function which automatically enables and disables drive running with user defined levels to save energy
● Two-zone PID-controller (two different feedback signals;
minimum and maximum control)
● Two setpoint sources for the PID-control. Selectable with digital input
● PID setpoint boost function
● Feed forward function to improve the response to the process changes
● Process value supervision
● Multi-pump control
● Pressure loss compensation for compensating pressure losses in the pipework, for example, when sensor is incorrectly placed near the pump or fan
HVAC Application
H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com 7
Example of Control Connections
Control Connections
Slot A
A
+10V
AI–1+
Vin
AI–2+
AI–2–
24Vout
GND
DIN1
DIN2
DIN3
24Vout
GND
DIN4
DIN5
DIN6
AO–1+
AO–1–
DATA–
Reference Output Analog Input Voltage (Range 0–10 Vdc) (can be programmed to current 4–20 mA) Analog Output Common (Ground)
Analog Input Common PI Setpoint or Feedback Control Voltage Output (0.1A max.)
I/O Ground
START/STOP (Contact closed = start)
External Fault (Closed = fault) Run Interlock Permissive IP Interlock (Closed = OK) DIN1–DIN6 Common
Control Voltage Output (0.1A max.)
I/O Ground
Fire Mode (Contact closed = fire mode)
Force Bypass (Contact closed = bypass)
DIN1–DIN6 Common
Output Frequency (0–20 mA)
Analog Output Common (Ground)
RS-485 DATA–
Speed Select 0–100% (Preset speed)
U (T1)
V (T2)
W (T3)
R+
R–
L1
L2
L3
Three-Phase Input Input (Single-Phase not available)
Three-Phase Output
DB
Chopper
Terminal Factory Default Signal
Resistor
Analog Input Current (Range 4–20 mA) (can be programmed to voltage 0–10 Vdc) PI Setpoint or Feedback
B DATA+
RO1 Bypass Run
RO2 Drive Run
RO3 Fault
24 Vdc/8A 250 Vac/8A 125 Vdc/0.4A
Relay Board 1 Default Signal
Slot B
Analog
RS-485 DATA+
Factory Jumper
COM
CMB
30 24 Vdcin Auxiliary Input Voltage
Circuit Breaker
Optional
Motor
RJ-45 BACnet/IP Ethernet Industrial Protocol Modbus/TCP Transmission Control Protocol (Ethernet Based)
5% DC Link Reactor
Programmable BACnet, Modbus, FLN, N2
ON
CURRENT
CURRENT
CURRENT
RS485
AO1
AI2
AI1
OFF
VOLTAGE
VOLTAGE
VOLTAGE
Test
Keypad of the Drive
8 H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com
Keypad of the Drive
The control keypad is the interface between the Eaton H-MAX frequency converter and the user. With the control keypad it is possible to control the speed of a motor, to supervise the state of the equipment and to set the frequency converter’s parameters.
There are two different keypads used with the H-MAX drive.
The North American Keypad is slightly different than the EMEA Keypad. Functionality is quite similar. The EMEA keypad does not support the bypass functionality commonly used in the United States.
US Keypad Buttons
EMEA Keypad Buttons
Switching Between Drive and Bypass
Move Cursor Left Back when Pressed for two Seconds
Stop Button/Fault Reset Start Button
Change Control Place Between Hand-Off-Auto
Move Cursor Right
Increase Value Scroll Menu Up
Decrease Value Scroll Menu Down
Enter Menu Confirm Selection
Back Fault Reset
Move Cursor Left
Stop Button Start Button
Change Control Place Between Hand-Off-Auto
Move Cursor Right
Increase Value Scroll Menu Up
Decrease Value Scroll Menu Down
Enter Menu Confirm Selection
H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com 9
Keypad Display
The keypad display indicates the status of the motor and the drive and any irregularities in motor or drive functions. On the display, the user sees information about his present location in the menu structure and the item displayed.
Main Menu
The data on the control keypad are arranged in menus and submenus. Use the up and down arrows to move between the menus. Enter the group/item by pressing the OK button and return to the former level by pressing the Back/Reset button.
The Location field indicates your current location. The Status field gives information about the present status of the drive. See “Control Connections” on Page 7.
Main Menu
Using the Graphical Keypad
Editing Values
Change value of a parameter following the procedure below:
1. Locate the parameter.
2. Enter the Edit mode.
3. Set new value with the up/down arrow buttons. You can also move from digit to digit with the arrow buttons left/right if the value is numerical and then change the value with the up/down arrow buttons.
4. Confirm change with OK button or ignore change by returning to previous level with Back/ Reset button.
Status Field
STOP/RUN
STOP E-Energy Hand I/O
Direction Run Mode
Hand/Off/Auto
Control Place
PC/IO/KEYPAD/FIELDBUS
Location Field (Parameter ID number and current menu location)
Activated Group/Item Press OK to Enter
10 H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com
Editing Values on Graphical Keypad
HOA Control Button
The HOA (Hand-Off-Auto) button is used for two functions:
to quickly access the Control page and to easily change between the Hand (Keypad), Off, and Auto (Remote) control places.
Control Place
The control place is the source of control where the drive can be started and stopped. Every control place has its own parameter for selecting the frequency reference source. In the HVAC drive, the Hand control place is always the keypad.
The Auto control place is determined by parameter P2.1.1 (Keypad, I/O Terminal, I/O three-wire, or Fieldbus CTRL). The selected control place can be seen on the status bar of the keypad.
Local Control
The keypad is always used as control place while in hand control. Hand control has higher priority than auto control.
Therefore, if, for example, bypassed by parameter P2.1.17 through digital input while in Remote, the control place will still switch to Keypad if Hand is selected. Switching between Hand, Off, and Auto Control can be done by pressing the HOA button on the keypad.
Changing Control Place
Change of control place from Hand to Auto (keypad).
1. Anywhere in the menu structure, push the HOA button.
2. Push the arrow up or the arrow down button to select Hand/Off/Auto and confirm with the OK button.
3. On the next display, select Hand, Off, or Auto and again confirm with the OK button.
4. The display will return to the same location as it was when the HOA button was pushed. However, if the Remote control place was changed to Hand (Keypad) you will be prompted for keypad reference.
STOP READY I/O
STOP READY I/O
STOP READY I/O
OK OK
OK
STOP READY I/O
STOP READY I/O
OR:
BACK
RESET
H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com 11
Accessing the Control Page
The Control page is meant for easy operation and monitoring of the most essential values.
1. Anywhere in the menu structure, push the HOA button.
2. Push the arrow up or the arrow down button to select Control page and confirm with the OK button.
3. The control page appears. If keypad control place and keypad reference are selected to be used, you can set the Keypad reference after having pressed the OK button. If other control places or reference values are used, the display will show Frequency reference which is not editable. The other values on the page are Multimonitoring values. You can choose which values appear here for monitoring (for this procedure, see Application Manual).
Accessing Control Page
HOA
STOP READY Keypad
Edit
OK
OK
STOP READY Keypad
0.00 Hz
STOP READY Keypad
0.00 Hz
OK
STOP READY I/O
12 H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com
Copying Parameters
The parameter copy function can be used to copy parameters from one drive to another.
The parameters are first saved to the keypad, then the keypad is detached and connected to another drive. Finally, the parameters are downloaded to the new drive, restoring them from the keypad.
Before any parameters can successfully be copied from one drive to another, the drive has to be stopped when the parameters are downloaded.
● First, go into User settings menu and locate the Parameter backup submenu. In the Parameter backup submenu, there are three possible functions to be selected:
1. Restore factory defaults will re-establish the parameter settings originally made at the factory.
2. By selecting Save to keypad you can copy all parameters to the keypad.
3. Restore from keypad will copy all parameters from keypad to a drive.
Parameter Copy
Note: If the keypad is changed between drives of different sizes, the copied values of these parameters will not be used:
Motor nominal current (P2.1.12) Motor nominal voltage (P2.1.13) Motor nominal speed (P2.1.15) Motor power factor (P2.1.16) Motor nominal frequency (P2.1.14) Service factor (P2.1.18) Switching frequency (P2.7.7) Motor current limit (P2.1.17) Maximum frequency (P2.1.9)
STOP READY Keypad STOP READY Keypad STOP READY Keypad
H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com 13
Help Texts
The graphical keypad features instant help and information displays for various items.
All parameters offer an instant help display. Select Help and press the OK button.
Text information is also available for faults, alarms, and the Startup Wizard.
Help Text Example
Adding Item To Favorites
You might need to refer to certain parameter values or other items often. Instead of locating them one by one in the menu structure, you may want to add them to a folder called Favorites where they can easily be reached.
Adding Item To Favorites
STOP READY I/O STOP READY I/O
OK OK
STOP READY I/O
Basic Settings
Motor Nom Voltg
230.00 V
Motor Nom Speed 1430 rpm
Motor Nom Freq
50.00 Hz
Edit
Help
Motor Nom Freq
Add to favorites
Motor Nom Freq was added to favorites. Press OK to continue.
STOP READY I/O STOP READY I/O STOP READY I/O
14 H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com
Monitor
Multi-Monitor
On the multi-monitor page, you can collect nine values that you wish to monitor.
Multi-Monitoring Page
Change the monitored value by activating the value cell (with arrow buttons left/right) and clicking OK. Then choose a new item on the Monitoring values list and click OK again.
STOP READY I/O STOP READY I/O
STOP READY I/O STOP READY I/O
Eaton H-Max—Startup
H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com 15
Eaton H-Max—Startup
Startup Wizard
In the Startup Wizard, you will be prompted for essential information needed by the drive so that it can start controlling your process. In the Wizard, you will need the following keypad buttons:
Left/Right arrows. Use these to easily move between digits and decimals.
Up/Down arrows. Use these to move between options in menu and to change value.
OK button. Confirm selection with this button.
Back/Reset button. Pressing this button, you can return to the previous question in the Wizard. If pressed at the first question, the Startup Wizard will be cancelled.
Once you have connected power to your Eaton H-Max frequency converter, follow these instructions to easily set up your drive.
Note
1 These questions appear if battery is installed.
Now the Startup Wizard is done.
The Startup Wizard can be re-initiated by pressing and holding the back/reset button for two seconds. The Startup Wizard will appear upon next power up.
1 Run Startup Wizard Yes No
2 Language Select Depends on language package
3 Daylight Saving 1 Russia
US
EU
OFF
4 Time 1 hh:mm:ss
5 Day 1 dd.mm.
6 Year 1 yyyy
OK
BACK
RESET
7 Application H-Max Standard
PID
Multi-Pump
8 Bypass Enabled Disabled
9 Motor Nominal Current Min: 0.26A Max: Drive Dependent
10 Motor Nominal Voltage Min: 180.0V Max: 690.0V
11 Motor Nominal Frequency Min: 8 Hz Max: 320 Hz
12 Motor Nominal Speed Min: 24 RPM Max: 19200 RPM
13 Min Frequency Min: 0 Hz Max: 60 Hz
14 Max Frequency Min: 12 Hz Max: 320 Hz
15 Accel Time 1 Min: 0.1s Max: 3000s
16 Decel Time 1 Min: 0.1s Max: 3000s
17 StartSourceHand Keypad FieldbusCTRL I/O Three-Wire I/O Terminal
18 StartSourceAuto I/O Terminal Keypad FieldbusCTRL I/O Three-Wire
19 SpeedSetptHand Keypad Ref P1D1 Activated
AI1 + AI2
AI2
AI1
Fieldbus
20 SpeedSetptAuto PID1 Activated
AI1 + AI2
AI2
AI1
Fieldbus Keypad Ref
Eaton H-Max—Startup
16 H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com
PID Mini-Wizard
The PID Mini-Wizard is activated in the Quick Setup menu.
This Wizard presupposes that you are going to use the PID controller in the “one feedback/one setpoint” mode. The control place will be I/O A and the default process unit “%”.
The PID Mini-Wizard asks for the following values to be set:
Multi-Pump
If Multi-Pump is the selected application, parameter group
2.12 will be visible in the menu structure. Default values may need to be adjusted to meet your application needs.
1 FeedBack1 Srce AI2
AI1
Not Used ProceDataIn8 ProceDataIn7 ProceDataIn6 ProceDataIn5 ProceDataIn4 ProceDataIn3 ProceDataIn2 ProceDataIn1
AI6
AI5
AI4
AI3
2 Process Unit Selection (Several Selections)
3 Process Unit Min —
4 Process Unit Max —
5 P-Gain Min: 0% Max: 200%
6 Integration Time Min: 0.00s Max: 600.00s
7 SetPT1 Source Keypad SP1 Not Used ProceDataIn8 ProceDataIn7 ProceDataIn6 ProceDataIn5 ProceDataIn4 ProceDataIn3 ProceDataIn2 ProceDataIn1
AI6
AI5
AI4
AI3
AI2
AI1
Parameter Group Name
Parameter Number
Parameter Name
Parameter Group 2.12:
Multi-Pump
P2.12.1 Number of motors
P2.12.2 Interlock function
P2.12.3 Include FC
P2.12.4 Autochange
P2.12.5 Autochange interval
P2.12.6 Autochange: frequency limit
P2.12.7 Autochange: motor limit
P2.12.8 Bandwidth
P2.12.9 Bandwidth delay
Menu Structure
H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com 17
Menu Structure
Keypad Menus
Monitor Basic Diagnostics Active Faults
Timer Functions Reset Faults
Multimonitor Fault History
Parameters Basic Parameters Total Counters
Analog Inputs Trip Counters
Digital Inputs Software Info
Analog Outputs I/O & Hardware Basic I/O
Digital Outputs Slot D
Drive Control Slot E
Motor Control Real Time Clock
Protections Power Unit Settings
Fixed Frequencies Keypad
Fire Mode RS-485
Multi-Pump Ethernet
Braking User Settings —
Fieldbus Favorites —
Second Parameter Set
Timer Functions
Parameter Functions
18 H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com
Parameter Functions
Basic Monitoring Functions
Parameter Number Parameter Name Unit ID Description
V1.1.1 Output frequency Hz 1 Output Frequency of the Drive
V1.1.2 Frequency Reference Hz 25 Frequency Reference to Motor Control
V1.1.3 Motor Speed RPM rpm 2 Motor speed in rpm
V1.1.4 Motor Current A 3 Motor Current
V1.1.5 Motor Torque % 4 Calculated Shaft Torque
V1.1.6 Motor Power % % 5 Total Power Consumption of AC Drive
V1.1.7 Motor Voltage V 6 Motor Voltage
V1.1.8 DC-Link Voltage V 7 DC-Link Voltage
V1.1.9 Unit Temperature °C 8 Heatsink temperature
V1.1.10 Motor Temperature % 9 Calculated Motor Temperature
V1.1.11 Analog Input 1 % 13 Analog input signal scaled according to the range or custom min and max chosen in the I/O config menu
V1.1.12 Analog Input 2 % 14 Analog input signal scaled according to the range or custom min and max chosen in the I/O config menu
V1.1.13 Analog Output 1 % 26 Value of analog output in % of the signal range
V1.1.14 DI1, DI2, DI3 Binary 15 This monitor value shows the status of the I/Os
V1.1.15 DI4, DI5, DI6 Binary 16 This monitor value shows the status of the I/Os
V1.1.16 PID1 Setpoint % 20 Setpoint value fed to the PID controller in process units
V1.1.17 PID1 Feedback % 21 Feedback Value fed to the PID controller in process units
V1.1.18 PID1 Error % 22 Error value of the PID controller. Deviation of the feedback from setpoint in process units.
V1.1.19 PID2 Setpoint % 83 Setpoint value fed to the PID controller in process units
V1.1.20 PID2 Feedback % 84 Feedback Value fed to the PID controller in process units
V1.1.21 PID2 Error % 85 Error value of the PID controller. Deviation of the feedback from setpoint in process units.
V1.1.22 Drive Status Word BitCoded 43 Bitcoded status of the drive. B1=Ready, B2=Run, B3=Fault, B6=RunEnable, B7=Alarm Active, B12=Run Request, B13=Motor Regulator Active
V1.1.23 Motor Speed % % 1360 Percent of full motor speed
V1.1.24 Last Active Fault Num 37 The fault code of the latest activated fault that has not been reset
H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com 19
Timer Monitoring Functions
Multi-Monitor Functions
Note: The “x” in the parameter number represents the assembled monitoring window. Values range from 1 to 9.
Parameter Number Parameter Name Unit ID Description
V1.2.1 TC1, TC2, TC3 ON/OFF 1703 This monitor value shows the status of the time channels
V1.2.2 Interval 1 ON/OFF 1704 This monitor value shows the status of the timer interval
V1.2.3 Interval 2 ON/OFF 1705 This monitor value shows the status of the timer interval
V1.2.4 Interval 3 ON/OFF 1706 This monitor value shows the status of the timer interval
V1.2.5 Interval 4 ON/OFF 1707 This monitor value shows the status of the timer interval
V1.2.6 Interval 5 ON/OFF 1708 This monitor value shows the status of the timer interval
V1.2.7 Timer 1 sec 1709 If the timer has been activated, this monitor value shows the remaining time of the timer.
V1.2.8 Timer 2 sec 1710 If the timer has been activated, this monitor value shows the remaining time of the timer.
V1.2.9 Timer 3 sec 1711 If the timer has been activated, this monitor value shows the remaining time of the timer.
V1.2.10 Real Time Clock h/m/s 1712 Time of Day (Military Time)
Parameter Number Parameter Name Unit ID Description
V1.3.x.1 Drive Status Word Binary 43 Bitcoded status of the drive. B1=Ready, B2=Run, B3=Fault, B6=RunEnable, B7=Alarm Active, B12=Run Request, B13=Motor Regulator Active
V1.3.x.2 Analog Input 1 % 13 Analog input signal scaled according to the range or custom min and max chosen in the I/O config menu
V1.3.x.3 Analog Input 2 % 14 Analog input signal scaled according to the range or custom min and max chosen in the I/O config menu
V1.3.x.4 Analog Output 1 % 26 Value of analog output in % of the signal range
V1.3.x.5 AutoChange N/A 1720 No Function
V1.3.x.6 DC-Link Voltage V 7 DC-Link Voltage of the Drive
V1.3.x.7 DI1, DI2, DI3 Binary 15 This monitor value shows the status of the I/Os
V1.3.x.8 DI4, DI5, DI6 Binary 16 This monitor value shows the status of the I/Os
V1.3.x.9 RO1, RO2, RO3 Binary 17 This monitor value shows the status of the I/Os
V1.3.x.10 Frequency Reference Hz 25 Frequency Reference to Motor Control
V1.3.x.11 Interval 1 ON/OFF 1704 This monitor value shows the status of the timer interval
V1.3.x.12 Interval 2 ON/OFF 1705 This monitor value shows the status of the timer interval
V1.3.x.13 Interval 3 ON/OFF 1706 This monitor value shows the status of the timer interval
V1.3.x.14 Interval 4 ON/OFF 1707 This monitor value shows the status of the timer interval
V1.3.x.15 Interval 5 ON/OFF 1708 This monitor value shows the status of the timer interval
V1.3.x.16 Motor Current A 3 Motor Current
V1.3.x.17 Motor Power KW KW 73 Calculated Power Consumption of the Motor
V1.3.x.18 Motor Power % % 5 Total Power Consumption of AC Drive
V1.3.x.19 Motor Speed RPM rpm 2 Motor speed in rpm
V1.3.x.20 Motor Torque % 4 Calculated Shaft Torque
V1.3.x.21 Motor Voltage V 6 Motor Voltage
20 H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com
Multi-Monitor Functions, continued
Note: The “x” in the parameter number represents the assembled monitoring window. Values range from 1 to 9.
Parameter Number Parameter Name Unit ID Description
V1.3.x.22 Motor Running Binary 30 This monitor value shows if the motor is running
V1.3.x.23 Motor Temperature % 9 Calculated Motor Temperature
V1.3.x.25 PID1 Status Words 24 This monitor value shows if the PID is Active
V1.3.x.26 PID2 Status Words 87 This monitor value shows if the PID is Active
V1.3.x.27 PID1 Error % 22 Error value of the PID controller. Deviation of the feedback from setpoint in process units.
V1.3.x.28 PID1 Feedback % 21 Feedback Value fed to the PID controller in process units
V1.3.x.29 PID1 Output % 23 Output value delivered from the PID controller in process units
V1.3.x.30 PID1 Setpoint % 20 Setpoint value fed to the PID controller in process units
V1.3.x.31 PID2 Error % 85 Error value of the PID controller. Deviation of the feedback from setpoint in process units.
V1.3.x.32 PID2 Feedback % 84 Feedback Value fed to the PID controller in process units
V1.3.x.33 PID2 Output % 86 Output value delivered from the PID controller in process units
V1.3.x.34 PID2 Setpoint % 83 Setpoint value fed to the PID controller in process units
V1.3.x.35 Real Time Clock h/m/s 1712 Time of Day (Military Time)
V1.3.x.36 Run Request Chain Words 1361 This monitor value shows the status of a run request
V1.3.x.37 TC1, TC2, TC3 ON/OFF 1703 This monitor value shows the status of the time channels
V1.3.x.38 Timer 1 sec 1709 If the timer has been activated, this monitor value shows the remaining time of the timer.
V1.3.x.39 Timer 2 sec 1710 If the timer has been activated, this monitor value shows the remaining time of the timer.
V1.3.x.40 Timer 3 sec 1711 If the timer has been activated, this monitor value shows the remaining time of the timer.
V1.3.x.41 Unit Temperature °C 8 Heatsink temperature
V1.3.x.42 Motor Speed % % 1360 Motor Speed in %
V1.3.x.43 Last Active Fault Num 37 The fault code of the latest activated fault that has not been reset
V1.3.x.44 Run Time Hours Hrs 1364 Drive Run Time in Hours
V1.3.x.45 Power On Hours Hrs 1363 Power On Time in Hours
V1.3.x.46 Frequency Reference Hz 1365 Frequency Reference to Motor Control
V1.3.x.53 Energy Counter varies 2291 Amount of Energy taken from the Supply Network, No Reset
V1.3.x.55 Run Time a d hh:min N/A Run Time of Drive
V1.3.x.56 Power On Time a d hh:min N/A Power On Time of Drive
V1.3.x.57 Start Command Counter Num 2295 The number of times the power unit has been started
V1.3.x.58 Energy Counter varies 2296 Resettable Energy Counter
V1.3.x.60 Run Time N/A N/A N/A
V1.3.x.61 Run Time N/A N/A N/A
V1.3.x.62 Run Time N/A N/A N/A
V1.3.x.63 Power On Time N/A N/A N/A
V1.3.x.64 Power On Time N/A N/A N/A
V1.3.x.65 Power On Time N/A N/A N/A
Parameters
H-Max HVAC Drives MN04008006E—January 2012 www.eaton.com 21
Parameters
Basic Parameters
Basic Settings
Parameter Number Parameter Name
Change in Run Min. Max. Default ID Values
P2.1.1 Application N 0 2 0 213 0 = H-MAX Standard
1 = PID
2 = Multi-Pump
P2.1.2 ByPass N 0 1 1 214 0 = Disabled 1 = Enabled
P2.1.3 HOA Control Stc N 0 1 0 1359 0 = Keypad Ctrl 1 = I/O Terminal
P2.1.4 Start Srce Hand N 0 3 0 1300 0 = Keypad 1 = I/O Terminal 2 = I/O 3-wire 3 = FieldbusCTRL
P2.1.5 Speed Setpt Hand N 2 7 2 1301 2 = Keypad Ref 3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1 + AI2
7 = PID1 Activated
P2.1.6 Start Srce Auto N 0 3 1 1302 0 = Keypad 1 = I/O Terminal 2 = I/O 3-wire 3 = FieldbusCTRL
P2.1.7 Speed Setpt Auto (see P2.1.5)
N 2 7 4 1303 2 = Keypad Ref 3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1 + AI2
7 = PID1 Activated
P2.1.8 Min Frequency N 0,00 Hz Max frequency 12,00 Hz 101 See Range
P2.1.9 Max Frequency N Min frequency 320,00 Hz 50,00/60,00 102 See Range
P2.1.10 Accel Time 1 Y 0.1 s 3000,0 s 60,0 s 103 See Range
P2.1.11 Decel Time 1 Y 0.1 s 3000,0 s 60,0 s 104 See Range
P2.1.12 Motor Nom Currnt N varies varies varies 113 See Range
P2.1.13 Motor Nom Voltg N 180,0 V 690,0 V varies 110 See Range
P2.1.14 Motor Nom Freq N 12,00 Hz 320,00 Hz 50,00/60,00 111 See Range
P2.1.15 Motor Nom Speed N 24 rpm 19200 rpm 1440/1750 112 See Range
P2.1.16 MotorPowerFactor N 0,30 1,00 0,82 120 See Range
P2.1.17 Current Limit N…