Asbestos Containing Materials Report.pdf
PDF 4 MB Posted
- Attached to
- Z1DA--Project: 619-23-101 - Replace Roof Systems for Main Hospital, Building 1 Federal contract opportunity
- Solicitation number
- 36C24725R0030
About this file
This is an asbestos-containing materials (ACM) survey report prepared by Environmental Health Consultants, LLC for Building 1 at the Central Alabama Veterans Health Care System's West Campus in Montgomery, Alabama. The survey, conducted in June 2023, focused on examining the roof surfaces and identified one asbestos-containing material: black and/or gray pipe flashing sealant around roof penetrations, containing 5% Chrysotile asbestos. The report found approximately 3 square feet of this sealant in good condition, with additional assumed locations at 10 other penetrations. The material is classified as NESHAP category II non-friable.
The survey involved collecting 44 bulk samples from various roofing materials across seven roof sections, analyzed by Hayes Microbial Consulting using Polarized Light Microscopy (PLM). The investigation was conducted to support a planned roof replacement project, with samples taken from multiple core locations across the roof surfaces. All other tested materials, including membrane fibrous materials, insulation, boards, caulking, gypcrete, and various sealants, were found to contain no detectable asbestos. The survey was performed by EPA and Alabama accredited asbestos building inspector Kamau McAbee (Accreditation #AIN0623BE7945A0).
View the file
Other files for this federal contract opportunity
Show all 31
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ASBESTOS CONTAINING MATERIALS
SURVEY REPORT
BUILDING 1 ROOF
CENTRAL ALABAMA VETERANS HEALTH CARE SYSTEM – WEST CAMPUS
MONTGOMERY, ALABAMA
PREPARED FOR
Beaufort Engineering Services, Inc.
2712 Bull Street, Beaufort, South Caroline 29902
PREPARED BY
ENVIRONMENTAL HEALTH
CONSULTANTS, LLC
Report Date: August 22, 2023
ASBESTOS-CONTAINING MATERIALS SURVEY
(Roof Only) for
Building 1 Central Alabama Veterans Health Care System – West Campus
Montgomery Alabama
Prepared For:
Ms. Suzel A. Doty Project Manager
Beaufort Engineering Services, Inc.
2712 Bull Street
Beaufort, South Carolina 29902
Prepared By:
Environmental Health Consultants, LLC
701 East Pratt Street Baltimore, Maryland 21202
EHC Job Order No.: 004-B
August 22, 2023
Beaufort Engineering Services Asbestos-Containing Materials Survey Report Building 1 Roof, Central Alabama Veterans Healthcare Center
Environmental Health Consultants, LLC ES-1 August 21, 2023
Executive Summary
Environmental Health Consultants, LLC (EHC) was retained by the Beaufort Engineering Services (BES) (client) to conduct an asbestos containing materials survey (ACM) survey of the roof on building 1 located at Central Alabama Healthcare Center, Montgomery, Alabama (subject site).
The subject site is a multi-story healthcare building. EHC performed a survey of the flat roofing surfaces in June of 2023 and identified the following asbestos-containing building materials:
Black and/or gray pipe flashing sealant around roof penetrations (see photo)
Environmental Health Consultants, LLC i August 21, 2023
Table of Contents
Executive Summary ................................................................................................................................ ES-1
1.0 Introduction
2.0 Site Description
3.0 Asbestos-Containing Materials Survey
3.1 BUILDING SURVEY
3.2 METHODS
3.3 ANALYTICAL RESULTS
4.0 FINDINGS
5.0 Disclaimer
Appendices
Appendix A: Licenses and Accreditations
Appendix B: Asbestos Certificate of Analysis
Appendix C: Asbestos Bulk Sample Location Drawing
Environmental Health Consultants, LLC Page 1 August 22, 2023
1.0 Introduction
Environmental Health Consultants, LLC (EHC) was retained by the Beaufort Engineering Services (client) to conduct an asbestos-containing material (ACM) survey on the roof of Building 1 located at the Central Alabama Veterams Healthcare Center, Montgomery, Alabama (subject site).
The scope of work included a visual observation of the building and property, bulk sampling and analysis, quantification of suspect asbestos-containing materials, generation of this report documenting the findings.
2.0 Site Description
EHC understands that this investigation is in support of a planned roof replacement. The investigation was limited to accessible portions of the roof as noted on the design development plans.
3.0 Asbestos-Containing Materials Survey
3.1 Building Survey
EHC’s Environmental Protection Agency (EPA) and Alabama accredited asbestos building inspector Mr.
Kamau McAbee (Accreditation#AIN0623BE7945A0), conducted a destructive ACM survey of the subject site in June of 2023. Licenses and accreditations are included in Appendix A.
Representative accessible areas of the building were investigated, and suspect materials were sampled and quantified. Assumptions were made, as appropriate, concerning the presence and quantity of asbestos containing materials within inaccessible areas. Sample information was recorded on field sampling forms and chain of custody forms, and material quantity and location data were recorded on a building wide basis using dedicated field data sheets. Multiple samples of most materials were collected in order to reflect differences in physical appearance, location, dimension, etc.
3.2 Methods
Bulk samples were collected using hand tools and were placed in re-sealable plastic bags. Unique identifiers were assigned to the samples and were recorded on the bags and on the bulk survey sampling sheets. The suspect asbestos bulk samples were submitted for analysis, along with chain-of-custody forms, to Hayes Microbial Consulting, LLC (Hayes). Hayes is accredited by the American Industrial Hygiene Association (AIHA #188863) and the National Institute of Standards and Technology through the National Voluntary Laboratory Accreditation Program (NVLAP) Bulk Asbestos Analysis (NVLAP # 500096-0).
Polarized Light Microscopy (PLM) was used to analyze the bulk samples for the presence of asbestos. All PLM analysis was performed following the methodologies documented in the EPA method 600/R-93/116, July 1993, “Method for the Determination of Asbestos in Bulk Building Materials”.
Environmental Health Consultants, LLC Page 2 August 22, 2023
3.3 Analytical Results
EHC collected a total of forty-four (44) bulk samples of suspect ACMs from the subject site. Individual layers identified by the laboratory for each bulk sample were also analyzed. The EPA defines an asbestos containing material as "any material containing greater than one percent asbestos as determined using the method specified in appendix A, subpart F, 40 CFR part 763, section 1, PLM.”
Core samples were collected from the following roofing surfaces.
Roof Number Core Number Sample Identifier
Roof 1 Core 1 1A, 2B Roof 2 Core 2 5C, 6A, 7D Roof 3 Core 3 11A, 12D, 13B Roof 4 Core 4 15A, 16H, 17I, 18A Roof 4 Core 5 No samples collected. Identical to Core 4 and 6 Roof 4 Core 6 20H, 21A Roof 5 Core 7 23H, 24D, 25H, 26I, 27B, 28H, 29A Roof 5 Core 8 No samples collected. Identical to to Core 7 Roof 6 Core 9 41A, 42I Roof 6 Core 10 31A, 32H, Roof 6 Core 11 33A, 34I
Note: EHC understands that Roof 7 is identical to Roof 4. Roof 7 was inaccessible for sampling.
The analytical results for suspect asbestos containing building materials are summarized in Table 3.
Materials determined to be asbestos containing materials have been identified in red. Sampling details and certificates of analysis are included in Appendix B. Sampling locations are included in Appendix C.
Table 3 – Homogenous Material Table
Material Description
Membrane
Roof Insulation
Sample Numbers
1A, 6A, 11A, 15A, 18A, 21A, 29A, 31A, 33A, 41A
2B, 13B, 27B, 5C
Sample Results
No asbestos detected
No asbestos detected
Material
Stone Sealant
Roof Board
43M, 44M
7D, 12D, 24D
Sample
Environmental Health Consultants, LLC Page 3 August 22, 2023
Table 3 – Homogenous Material Table
Material
Pipe Flashing Sealant
Flashing Caulk
3E, 8E
4F, 9F, 19F, 21F
Sample Results
5% Chrysotile (3E), (8E)
No asbestos detected
Material
Penetration Sealant
Roof Gypcrete
10G, 14G, 36G
16H, 20H, 23H, 28H, 32H
Sample Results
No asbestos detected Sample
Results No asbestos detected
Material
Roof Gypsum
Shingle Sealant
(Beige)
17I, 26I, 34I, 42I
30J, 35J
Sample Results
No asbestos detected Sample
Results No asbestos detected
Material
Shingle Sealant (Black)
Pipe Sealant
37K, 38K
39L, 40L
Sample
4.0 Findings
Based on the laboratory results the following building materials were determined to be asbestos containing materials.
Black and/or gray flashing sealant around pipe roof penetrations. Approximately 3 square feet of pipe flashing sealant was observed in good condition. Additional locations of ACM pipe flashing sealant are assumed in 10 locations. The pipe flashing sealant is classified as NESHAP category II non-friable.
Environmental Health Consultants, LLC Page 4 August 22, 2023
5.0 Disclaimer
This report has been prepared by Environmental Health Consultants, LLC (EHC), exclusively for our Client and their Authorized Representatives. The findings and recommendations presented are based upon discussions with the Client of the present conditions, and may not necessarily indicate future conditions.
If any building material not included in this survey is identified during renovation, it should be assumed to contain asbestos unless proven otherwise by sampling and laboratory analysis.
EHC implies no warranty to the accuracy of information provided them by the Client or outside agents and transmitted herein. The locations and conditions of hazardous materials included in the report are based on the site observations performed during the survey.
Appendix A Licenses and Accreditations has examined the documentation of asbestos training and qualifications of the person named below and confers this
Certificate of Accreditation Asbestos Inspector
Kamau McAbee
Alabama Accreditation Number
AIN0623BE7945A0
Certificate Expiration Date
June 7, 2024
This certificate has been issued pursuant to the authority granted to The University of Alabama SafeState Program by the Alabama Asbestos Contractor Accreditation Act, Alabama Act No. 89-517, May, 1989 and Alabama Act No. 97-626, May, 1997.
Environmental Services Manager Associate Director for Environmental Programs
Appendix B Asbestos Certificate of Analysis
Sample No Material Description Sampling Location Result 1A Membrane Fibrous - Multicolored Roof 1 Core 1 None Detected 2B Insulation - Yellow Roof 1 Core 1 None Detected
2B.a Adhesive - Cream Roof 1 Core 1 None Detected 3E Flashing - Sealant - Silver/Black Roof 1 on Pipe Penetration 5% Chrysotile 4F Flashing - Caulk/Gray Roof 1 None Detected 5C Insulation - White Roof 2 Core 2 None Detected 6A Membrane Fibrous - Multicolored Roof 2 Core 2 None Detected 7D Board - White Roof 2 Core 2 None Detected 8E Flashing - Sealant/Black Roof 2 None Detected 9F Flashing - Caulk/Gray Roof 2 None Detected
10G Penetration - Sealant/White Roof 2 None Detected 11A Membrane Fibrous - Multicolored Roof 3 Core 3 None Detected
11A.a Tar - Black Roof 3 Core 3 None Detected 12D Board - White Roof 3 Core 3 None Detected 13B Insulation - Yellow Roof 3 Core 3 None Detected 14G Penetration- Sealant/White Roof 3 None Detected 15A Membrane Fibrous - Multicolored Roof 4 Core 4 None Detected 16H Gypcrete - Gray Roof 4 Core 4 None Detected 17I Gypsum - White Roof 4 Core 4 None Detected 18A Membrane Fibrous - Multicolored Roof 4 Core 4 None Detected
18A.a Bulk Material - Off White Roof 4 Core 4 None Detected 19F Flashing - Caulk/White Roof 4 None Detected 20H Gypcrete - Gray Roof 4 Core 6 None Detected 21A Membrane Fibrous Roof 4 Core 6 None Detected
21A.a Bulk Material - Off White Roof 4 Core 6 None Detected 22F Flashing - Caulk/White Roof 4 None Detected 23H Gypcrete - Gray Roof 5 Core 7 None Detected
24D.a Board: Brittle - White Roof 5 Core 7 None Detected 24D.b Board: Tar - Black Roof 5 Core 7 None Detected 25H Gypcrete - Gray Roof 5 Core 7 None Detected 26I Gypsum - White Roof 5 Core 7 None Detected 27B Insulation - Yellow Roof 5 Core 7 None Detected 28H Gypcrete - Gray Roof 5 Core 7 None Detected 29A Membrane Fibrous - Multicolored Roof 5 Core 7 None Detected 30J Shingle Sealant - White Roof 6 None Detected 31A Membrane Fibrous - Multicolored Roof 6 Core 10 None Detected 32H Gypcrete - Gray Roof 6 Core 10 None Detected 33A Membrane Fibrous - Multicolored Roof 6 Core 11 None Detected
33A.a Tar - Black Roof 6 Core 11 None Detected 34I Gypsum - White Roof 6 Core 11 None Detected 35J Shingle Sealant - White Roof 6 None Detected 36G Penetration - Sealant/White Roof 6 None Detected 37K Shingle Sealant - Black Roof 6 None Detected 38K Shingle Sealant - Black Roof 6 None Detected 39L Pipe Sealant - Red Roof 6 None Detected 40L Pipe Sealant - Red Roof 6 None Detected 41A Membrane Fibrous - Multicolored Roof 6 Core 9 None Detected 42I Gypsum - White Roof 6 Core 9 None Detected
42I.a Tar - Black Roof 6 Core 9 None Detected 43M Stone Sealant - White Roof 6 None Detected 44M Stone Sealant - White Roof 6 None Detected
Central Alabama Veterans Health Care System – West Campus Montgomery Alabama Building 1 Roof Only
#23027166
Analysis Report prepared for
Environmental Health Consultants, LLC
701 E. Pratt Street, Hall 3A Baltimore, MD 21202
Phone: (740) 274-1222
Montgomery VAMC
Collected: June 27, 2023 Received: July 6, 2023
Reported: July 11, 2023
We would like to thank you for trusting Hayes Microbial for your analytical needs!
We received 44 samples by FedEx in good condition for this project on July 6th, 2023.
The results in this analysis pertain only to this job, collected on the stated date, and should not be used in the interpretation of any other job. Information supplied by the customer can affect the validity of results. These results apply only to the samples as received. This report may not be duplicated, except in full, without the written consent of Hayes Microbial Consulting, LLC.
All information provided to Hayes Microbial is confidential information relating to our customers and their clients. We will not disclose, copy, or distribute any information verbally or written, except to those designated by the customer(s). We take confidentiality very seriously. No changes to the distribution list will be made without the express consent of the customer.
This laboratory bears no responsibility for sample collection activities, analytical method limitations, or your use of the test results. Interpretation and use of test results are your responsibility. Any reference to health effects or interpretation of mold levels is strictly the opinion of Hayes Microbial. In no event, shall Hayes Microbial or any of its employees be liable for lost profits or any special, incidental or consequential damages arising out of the use of these test results.
Steve Hayes, BSMT(ASCP) Laboratory Director Hayes Microbial Consulting, LLC.
EPA Laboratory ID: VA01419
Lab ID: #188863
DPH License: #PH-0198
Hayes Microbial Consulting, LLC. 3005 East Boundary Terrace, Suite F. Midlothian, VA. 23112 (804) 562-3435 contact@hayesmicrobial.com Page: 1 of 6
# Sample Material Description Non-Asbestos Fibers Asbestos Fibers
1 1A - Membrane Fibrous / Roof 1 - Core 1 Membrane / Multi-colored 10% Synthetic Fibers None Detected
2 2B - Insulation - Yellow / Roof 1 - Core 1 Insulation / Yellow 5% Cellulose Fibers None Detected
Adhesive / Cream None Detected
3 3E - Flashing - Sealant / Roof 1 - Core 1 Sealant / Silver/Black 5% Chrysotile
4 4F - Flashing - Caulk / Roof 1 - Core 1 Caulk / Gray None Detected
5 5C - Insulation - White / Roof 2 - Core 2 Insulation / White 5% Cellulose Fibers None Detected
6 6A - Membrane Fibrous / Roof 2 - Core 2 Membrane / Multi-colored 10% Synthetic Fibers None Detected
7 7D - Board / Roof 2 - Core 2 Drywall / White 5% Cellulose Fibers 5% Fiberglass
None Detected
8 8E - Flashing - Sealant / Roof 2 - Core 2 Sealant / Black None Detected
9 9F - Flashing - Caulk / Roof 2 - Core 2 Caulk / Gray None Detected
10 10G - Penetration - Sealant / Roof 2 - Core 2 Sealant / White None Detected
11 11A - Membrane Fibrous / Roof 3 - Core 3 Membrane / Multi-colored 10% Synthetic Fibers None Detected
Tar / Black 5% Synthetic Fibers None Detected
12 12D - Board / Roof 3 - Core 3 Drywall / White 5% Cellulose Fibers 5% Fiberglass
None Detected
Kamau McAbee Environmental Health Consultants, LLC 701 E. Pratt Street, Hall 3A Baltimore, MD 21202
(740) 274-1222
Montgomery VAMC
#23027166
Asbestos PLM Bulk
EPA 600/R-93, M-4/82-020
Project Analyst:
Angie Llatas-Campos, Date:
07 - 11 - 2023 Reviewed By:
Samuel Settle, Collected:Jun 27, 2023 Received: Jul 6, 2023 Reported: Jul 11, 2023
3005 East Boundary Terrace, Suite F. Midlothian, VA. 23112 (804) 562-3435 contact@hayesmicrobial.com Page: 2 of 6
13 13B - Insulation - Yellow / Roof 3 - Core 3 Insulation / Yellow None Detected
14 14G - Penetration - Sealant / Roof 3 Sealant / White None Detected
15 15A - Membrane Fibrous / Roof 4 - Core 4 Membrane / Multi-colored 10% Synthetic Fibers None Detected
16 16H - Gypcrete - Grey / Roof 4 - Core 4 Brittle / Gray None Detected
17 17I - Gypsum - White / Roof 4 - Core 4 Brittle / White None Detected
18 18A - Membrane Fibrous / Roof 4 - Core 4 Membrane / Multi-colored 10% Synthetic Fibers None Detected
Bulk Material / Off-White None Detected
19 19F - Flashing - Caulk / Roof 4 Caulk / White None Detected
20 20H - Gypcrete - Gray / Roof 4 - Core 6 Brittle / Gray None Detected
21 21A - Membrane Fibrous / Roof 4 - Core 6 Membrane / Multi-colored 10% Synthetic Fibers None Detected
Bulk Material / Off-White None Detected
22 22F - Flashing - Caulk / Roof 4 Caulk / White None Detected
23 23H - Gypcrete - Gray / Roof 5 - Core 7 Brittle / Gray None Detected
24 24D - Board / Roof 5 - Core 7 Brittle / Off-White None Detected
Tar / Black None Detected
Kamau McAbee Environmental Health Consultants, LLC 701 E. Pratt Street, Hall 3A Baltimore, MD 21202
(740) 274-1222
Montgomery VAMC
#23027166
Asbestos PLM Bulk
EPA 600/R-93, M-4/82-020
3005 East Boundary Terrace, Suite F. Midlothian, VA. 23112 (804) 562-3435 contact@hayesmicrobial.com Page: 3 of 6
25 25H - Gypcrete - Gray / Roof 5 - Core 7 Tar / Black 5% Fiberglass None Detected
Lab Note: Gypcrete Material Not Observed. Bag labeled 25A.
26 26I - Gypsum - White / Roof 5 - Core 7 Brittle / Off-White None Detected
27 27B - Insulation - Yellow / Roof 5 - Core 7 Insulation / Yellow None Detected
28 28H - Gypcrete - Gray / Roof 5 - Core 7 Brittle / Gray None Detected
29 29A - Membrane Fibrous / Roof 5 - Core 7 Membrane / Multi-colored 10% Synthetic Fibers None Detected
30 30J - Shingle Sealant - Beige / Roof 6 Sealant / White 5% Fiberglass None Detected
31 31A - Membrane Fibrous / Roof 6 - Core 10 Membrane / Multi-colored 10% Synthetic Fibers None Detected
32 32H - Gypcrete - Gray / Roof 6 - Core 10 Brittle / Gray None Detected
33 33A - Membrane Fibrous / Roof 6 - Core 11 Membrane / Multi-colored 5% Synthetic Fibers None Detected
Tar / Black 5% Cellulose Fibers None Detected
34 34I - Gypsum - White / Roof 6 - Core 11 Brittle / White None Detected
35 35J - Shingle Sealant - Beige / Roof 6 Sealant / White 10% Synthetic Fibers None Detected
36 36G - Penetration - Sealant / Roof 6 Sealant / White None Detected
Kamau McAbee Environmental Health Consultants, LLC 701 E. Pratt Street, Hall 3A Baltimore, MD 21202
(740) 274-1222
Montgomery VAMC
#23027166
Asbestos PLM Bulk
EPA 600/R-93, M-4/82-020
3005 East Boundary Terrace, Suite F. Midlothian, VA. 23112 (804) 562-3435 contact@hayesmicrobial.com Page: 4 of 6
37 37K - Shingle Sealant Black / Roof 6 Sealant / Black None Detected
38 38K - Shingle Sealant Black / Roof 6 Sealant / Black None Detected
39 39L - Pipe Sealant - Red / Roof 6 Sealant / Red None Detected
40 40L - Pipe Sealant - Red / Roof 6 Sealant / Red None Detected
41 41A - Membrane Fibrous / Roof 6 - Core 9 Membrane / Multi-colored 10% Synthetic Fibers None Detected
42 42I - Gypsum - White / Roof 6 - Core 9 Brittle / White None Detected
Tar / Black None Detected
43 43M - Stone Sealant / Roof 6 Sealant / White None Detected
44 44M - Stone Sealant / Roof 6 Sealant / White None Detected
Kamau McAbee Environmental Health Consultants, LLC 701 E. Pratt Street, Hall 3A Baltimore, MD 21202
(740) 274-1222
Montgomery VAMC
#23027166
Asbestos PLM Bulk
EPA 600/R-93, M-4/82-020
3005 East Boundary Terrace, Suite F. Midlothian, VA. 23112 (804) 562-3435 contact@hayesmicrobial.com Page: 5 of 6
Analysis Details All samples were received in acceptable condition unless otherwise noted on the report. This report must not be used by the client to claim product certification, approval, or endorsement by AIHA, NIST, NVLAP, NY ELAP, or any agency. The results relate only to the items tested. Hayes Microbial Consulting reserves the right to dispose of all samples after a period of 60 days in compliance with state and federal guidelines.
PLM Analysis All Polarized Light Microscopy (PLM) results include an inherent uncertainty of measurement associated with estimating percentages by PLM.
Materials with interfering matrix, low asbestos content, or small fiber size may require additional analysis via TEM Analysis.
TEM Analysis Analysis by TEM is capable of providing positive identification of asbestos type(s) and semi-quantitation of asbestos content.
Definitions 'None Detected' - Below the detected reporting limit of 1% unless point counting is performed, then the detected reporting limit is .25%.
New York ELAP Per NY ELAP198.6 (NOB), TEM is the only reliable method to declare an NOB material as Non-Asbestos Containing.
Any NY ELAP samples that are subcontracted to another laboratory will display the name and ELAP Lab Identification number in the report page heading of those samples. The original report provided to Hayes Microbial Consulting is available upon request.
Kamau McAbee Environmental Health Consultants, LLC 701 E. Pratt Street, Hall 3A Baltimore, MD 21202
(740) 274-1222
Montgomery VAMC
#23027166
Asbestos Analysis Information
3005 East Boundary Terrace, Suite F. Midlothian, VA. 23112 (804) 562-3435 contact@hayesmicrobial.com Page: 6 of 6
Appendix C Asbestos Bulk Sample Location Drawing
Central Alabama Veterans Health Care System West Campus
2215 Perry Hill Road, Montgomery, AL 36109
Project: Replace Roof on Building #1
Date: July 10, 2023
Core 6
Core 5
Core 4
Core 8
Core 7
Core 10 Core 9
Core 11 Core 3
Core 2 Core 1
Roof 4
Roof 6
Roof 1
Roof 3 Roof 2 Roof 5
Roof 3
Roof 7
(Inaccessible for sampling)
(Sample 3E – ACM Flashing Sealant)