Asbestos Containing Materials Report.pdf

PDF 4 MB Posted

Attached to
Z1DA--Project: 619-23-101 - Replace Roof Systems for Main Hospital, Building 1 Federal contract opportunity
Solicitation number
36C24725R0030
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 7

About this file

This is an asbestos-containing materials (ACM) survey report prepared by Environmental Health Consultants, LLC for Building 1 at the Central Alabama Veterans Health Care System's West Campus in Montgomery, Alabama. The survey, conducted in June 2023, focused on examining the roof surfaces and identified one asbestos-containing material: black and/or gray pipe flashing sealant around roof penetrations, containing 5% Chrysotile asbestos. The report found approximately 3 square feet of this sealant in good condition, with additional assumed locations at 10 other penetrations. The material is classified as NESHAP category II non-friable.

The survey involved collecting 44 bulk samples from various roofing materials across seven roof sections, analyzed by Hayes Microbial Consulting using Polarized Light Microscopy (PLM). The investigation was conducted to support a planned roof replacement project, with samples taken from multiple core locations across the roof surfaces. All other tested materials, including membrane fibrous materials, insulation, boards, caulking, gypcrete, and various sealants, were found to contain no detectable asbestos. The survey was performed by EPA and Alabama accredited asbestos building inspector Kamau McAbee (Accreditation #AIN0623BE7945A0).

View the file

Other files for this federal contract opportunity

Other files attached to Z1DA--Project: 619-23-101 - Replace Roof Systems for Main Hospital, Building 1, newest first.
File Type Posted
36C24725R0030 0012.pdf PDF
Government Official Respose.pdf PDF
36C24725R0030 0011.pdf PDF
36C24725R0030 0010.docx DOCX document
Revised SOW.pdf PDF
36C24725R0030 0009.docx DOCX document
Revised_2.1 Price Offer Schedule.pdf PDF
Attachment 3 - Revised Past Performance Questionnaire -PPQ.docx DOCX document
36C24725R0030 0008.docx DOCX document
RIR-1903.pdf PDF
Core Info.pdf PDF
36C24725R0030 0007.docx DOCX document
Official Government Response_619-23-101_36C24725R0030.pdf PDF
36C24725R0030 0006.docx DOCX document
36C24725R0030 0005.docx DOCX document
36C24725R0030 0004.docx DOCX document
36C24725R0030 0003.docx DOCX document
Roof Site Visit Sign In Sheet_2.pdf PDF
Roof Site Visit Sign In Sheet_1.pdf PDF
Rooftop Solar Pannel Energy System.pdf PDF
36C24725R0030 0002.docx DOCX document
36C24725R0030 0001.docx DOCX document
Attachment 8 - Replace Roof on Building 1 Construction Drawings.pdf PDF
Attachment 7 - Replace Roof on Building 1_Final_ Specifications.pdf PDF
Attachment 4 - Itemized Cost Breakdown.xlsx XLSX spreadsheet
Attachment 1 - Experience Modification Rate Form.pdf PDF
Attachment 5 - DBA Wage Rates_AL20240093 09 06 2024.pdf PDF
Attachment 6 - INVOICING.docx DOCX document
Attachment 3 - CONTRACTOR PAST PERFORMANCE FORM.docx DOCX document
36C24725R0030_1.docx DOCX document
Attachment 2 - 852.219-75 VA NOTICE OF LIMITATIONS ON SUBCONTRACTING Jan 2023 Dev form.pdf PDF
Show all 31

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ASBESTOS CONTAINING MATERIALS

SURVEY REPORT

BUILDING 1 ROOF

CENTRAL ALABAMA VETERANS HEALTH CARE SYSTEM – WEST CAMPUS

MONTGOMERY, ALABAMA

PREPARED FOR

Beaufort Engineering Services, Inc.

2712 Bull Street, Beaufort, South Caroline 29902

PREPARED BY

ENVIRONMENTAL HEALTH

CONSULTANTS, LLC

Report Date: August 22, 2023

ASBESTOS-CONTAINING MATERIALS SURVEY

(Roof Only) for

Building 1 Central Alabama Veterans Health Care System – West Campus

Montgomery Alabama

Prepared For:

Ms. Suzel A. Doty Project Manager

Beaufort Engineering Services, Inc.

2712 Bull Street

Beaufort, South Carolina 29902

Prepared By:

Environmental Health Consultants, LLC

701 East Pratt Street Baltimore, Maryland 21202

EHC Job Order No.: 004-B

August 22, 2023

Beaufort Engineering Services Asbestos-Containing Materials Survey Report Building 1 Roof, Central Alabama Veterans Healthcare Center

Environmental Health Consultants, LLC ES-1 August 21, 2023

Executive Summary

Environmental Health Consultants, LLC (EHC) was retained by the Beaufort Engineering Services (BES) (client) to conduct an asbestos containing materials survey (ACM) survey of the roof on building 1 located at Central Alabama Healthcare Center, Montgomery, Alabama (subject site).

The subject site is a multi-story healthcare building. EHC performed a survey of the flat roofing surfaces in June of 2023 and identified the following asbestos-containing building materials:

Black and/or gray pipe flashing sealant around roof penetrations (see photo)

Environmental Health Consultants, LLC i August 21, 2023

Table of Contents

Executive Summary ................................................................................................................................ ES-1

1.0 Introduction

2.0 Site Description

3.0 Asbestos-Containing Materials Survey

3.1 BUILDING SURVEY

3.2 METHODS

3.3 ANALYTICAL RESULTS

4.0 FINDINGS

5.0 Disclaimer

Appendices

Appendix A: Licenses and Accreditations

Appendix B: Asbestos Certificate of Analysis

Appendix C: Asbestos Bulk Sample Location Drawing

Environmental Health Consultants, LLC Page 1 August 22, 2023

1.0 Introduction

Environmental Health Consultants, LLC (EHC) was retained by the Beaufort Engineering Services (client) to conduct an asbestos-containing material (ACM) survey on the roof of Building 1 located at the Central Alabama Veterams Healthcare Center, Montgomery, Alabama (subject site).

The scope of work included a visual observation of the building and property, bulk sampling and analysis, quantification of suspect asbestos-containing materials, generation of this report documenting the findings.

2.0 Site Description

EHC understands that this investigation is in support of a planned roof replacement. The investigation was limited to accessible portions of the roof as noted on the design development plans.

3.0 Asbestos-Containing Materials Survey

3.1 Building Survey

EHC’s Environmental Protection Agency (EPA) and Alabama accredited asbestos building inspector Mr.

Kamau McAbee (Accreditation#AIN0623BE7945A0), conducted a destructive ACM survey of the subject site in June of 2023. Licenses and accreditations are included in Appendix A.

Representative accessible areas of the building were investigated, and suspect materials were sampled and quantified. Assumptions were made, as appropriate, concerning the presence and quantity of asbestos containing materials within inaccessible areas. Sample information was recorded on field sampling forms and chain of custody forms, and material quantity and location data were recorded on a building wide basis using dedicated field data sheets. Multiple samples of most materials were collected in order to reflect differences in physical appearance, location, dimension, etc.

3.2 Methods

Bulk samples were collected using hand tools and were placed in re-sealable plastic bags. Unique identifiers were assigned to the samples and were recorded on the bags and on the bulk survey sampling sheets. The suspect asbestos bulk samples were submitted for analysis, along with chain-of-custody forms, to Hayes Microbial Consulting, LLC (Hayes). Hayes is accredited by the American Industrial Hygiene Association (AIHA #188863) and the National Institute of Standards and Technology through the National Voluntary Laboratory Accreditation Program (NVLAP) Bulk Asbestos Analysis (NVLAP # 500096-0).

Polarized Light Microscopy (PLM) was used to analyze the bulk samples for the presence of asbestos. All PLM analysis was performed following the methodologies documented in the EPA method 600/R-93/116, July 1993, “Method for the Determination of Asbestos in Bulk Building Materials”.

Environmental Health Consultants, LLC Page 2 August 22, 2023

3.3 Analytical Results

EHC collected a total of forty-four (44) bulk samples of suspect ACMs from the subject site. Individual layers identified by the laboratory for each bulk sample were also analyzed. The EPA defines an asbestos containing material as "any material containing greater than one percent asbestos as determined using the method specified in appendix A, subpart F, 40 CFR part 763, section 1, PLM.”

Core samples were collected from the following roofing surfaces.

Roof Number Core Number Sample Identifier

Roof 1 Core 1 1A, 2B Roof 2 Core 2 5C, 6A, 7D Roof 3 Core 3 11A, 12D, 13B Roof 4 Core 4 15A, 16H, 17I, 18A Roof 4 Core 5 No samples collected. Identical to Core 4 and 6 Roof 4 Core 6 20H, 21A Roof 5 Core 7 23H, 24D, 25H, 26I, 27B, 28H, 29A Roof 5 Core 8 No samples collected. Identical to to Core 7 Roof 6 Core 9 41A, 42I Roof 6 Core 10 31A, 32H, Roof 6 Core 11 33A, 34I

Note: EHC understands that Roof 7 is identical to Roof 4. Roof 7 was inaccessible for sampling.

The analytical results for suspect asbestos containing building materials are summarized in Table 3.

Materials determined to be asbestos containing materials have been identified in red. Sampling details and certificates of analysis are included in Appendix B. Sampling locations are included in Appendix C.

Table 3 – Homogenous Material Table

Material Description

Membrane

Roof Insulation

Sample Numbers

1A, 6A, 11A, 15A, 18A, 21A, 29A, 31A, 33A, 41A

2B, 13B, 27B, 5C

Sample Results

No asbestos detected

No asbestos detected

Material

Stone Sealant

Roof Board

43M, 44M

7D, 12D, 24D

Sample

Environmental Health Consultants, LLC Page 3 August 22, 2023

Table 3 – Homogenous Material Table

Material

Pipe Flashing Sealant

Flashing Caulk

3E, 8E

4F, 9F, 19F, 21F

Sample Results

5% Chrysotile (3E), (8E)

No asbestos detected

Material

Penetration Sealant

Roof Gypcrete

10G, 14G, 36G

16H, 20H, 23H, 28H, 32H

Sample Results

No asbestos detected Sample

Results No asbestos detected

Material

Roof Gypsum

Shingle Sealant

(Beige)

17I, 26I, 34I, 42I

30J, 35J

Sample Results

No asbestos detected Sample

Results No asbestos detected

Material

Shingle Sealant (Black)

Pipe Sealant

37K, 38K

39L, 40L

Sample

4.0 Findings

Based on the laboratory results the following building materials were determined to be asbestos containing materials.

Black and/or gray flashing sealant around pipe roof penetrations. Approximately 3 square feet of pipe flashing sealant was observed in good condition. Additional locations of ACM pipe flashing sealant are assumed in 10 locations. The pipe flashing sealant is classified as NESHAP category II non-friable.

Environmental Health Consultants, LLC Page 4 August 22, 2023

5.0 Disclaimer

This report has been prepared by Environmental Health Consultants, LLC (EHC), exclusively for our Client and their Authorized Representatives. The findings and recommendations presented are based upon discussions with the Client of the present conditions, and may not necessarily indicate future conditions.

If any building material not included in this survey is identified during renovation, it should be assumed to contain asbestos unless proven otherwise by sampling and laboratory analysis.

EHC implies no warranty to the accuracy of information provided them by the Client or outside agents and transmitted herein. The locations and conditions of hazardous materials included in the report are based on the site observations performed during the survey.

Appendix A Licenses and Accreditations has examined the documentation of asbestos training and qualifications of the person named below and confers this

Certificate of Accreditation Asbestos Inspector

Kamau McAbee

Alabama Accreditation Number

AIN0623BE7945A0

Certificate Expiration Date

June 7, 2024

This certificate has been issued pursuant to the authority granted to The University of Alabama SafeState Program by the Alabama Asbestos Contractor Accreditation Act, Alabama Act No. 89-517, May, 1989 and Alabama Act No. 97-626, May, 1997.

Environmental Services Manager Associate Director for Environmental Programs

Appendix B Asbestos Certificate of Analysis

Sample No Material Description Sampling Location Result 1A Membrane Fibrous - Multicolored Roof 1 Core 1 None Detected 2B Insulation - Yellow Roof 1 Core 1 None Detected

2B.a Adhesive - Cream Roof 1 Core 1 None Detected 3E Flashing - Sealant - Silver/Black Roof 1 on Pipe Penetration 5% Chrysotile 4F Flashing - Caulk/Gray Roof 1 None Detected 5C Insulation - White Roof 2 Core 2 None Detected 6A Membrane Fibrous - Multicolored Roof 2 Core 2 None Detected 7D Board - White Roof 2 Core 2 None Detected 8E Flashing - Sealant/Black Roof 2 None Detected 9F Flashing - Caulk/Gray Roof 2 None Detected

10G Penetration - Sealant/White Roof 2 None Detected 11A Membrane Fibrous - Multicolored Roof 3 Core 3 None Detected

11A.a Tar - Black Roof 3 Core 3 None Detected 12D Board - White Roof 3 Core 3 None Detected 13B Insulation - Yellow Roof 3 Core 3 None Detected 14G Penetration- Sealant/White Roof 3 None Detected 15A Membrane Fibrous - Multicolored Roof 4 Core 4 None Detected 16H Gypcrete - Gray Roof 4 Core 4 None Detected 17I Gypsum - White Roof 4 Core 4 None Detected 18A Membrane Fibrous - Multicolored Roof 4 Core 4 None Detected

18A.a Bulk Material - Off White Roof 4 Core 4 None Detected 19F Flashing - Caulk/White Roof 4 None Detected 20H Gypcrete - Gray Roof 4 Core 6 None Detected 21A Membrane Fibrous Roof 4 Core 6 None Detected

21A.a Bulk Material - Off White Roof 4 Core 6 None Detected 22F Flashing - Caulk/White Roof 4 None Detected 23H Gypcrete - Gray Roof 5 Core 7 None Detected

24D.a Board: Brittle - White Roof 5 Core 7 None Detected 24D.b Board: Tar - Black Roof 5 Core 7 None Detected 25H Gypcrete - Gray Roof 5 Core 7 None Detected 26I Gypsum - White Roof 5 Core 7 None Detected 27B Insulation - Yellow Roof 5 Core 7 None Detected 28H Gypcrete - Gray Roof 5 Core 7 None Detected 29A Membrane Fibrous - Multicolored Roof 5 Core 7 None Detected 30J Shingle Sealant - White Roof 6 None Detected 31A Membrane Fibrous - Multicolored Roof 6 Core 10 None Detected 32H Gypcrete - Gray Roof 6 Core 10 None Detected 33A Membrane Fibrous - Multicolored Roof 6 Core 11 None Detected

33A.a Tar - Black Roof 6 Core 11 None Detected 34I Gypsum - White Roof 6 Core 11 None Detected 35J Shingle Sealant - White Roof 6 None Detected 36G Penetration - Sealant/White Roof 6 None Detected 37K Shingle Sealant - Black Roof 6 None Detected 38K Shingle Sealant - Black Roof 6 None Detected 39L Pipe Sealant - Red Roof 6 None Detected 40L Pipe Sealant - Red Roof 6 None Detected 41A Membrane Fibrous - Multicolored Roof 6 Core 9 None Detected 42I Gypsum - White Roof 6 Core 9 None Detected

42I.a Tar - Black Roof 6 Core 9 None Detected 43M Stone Sealant - White Roof 6 None Detected 44M Stone Sealant - White Roof 6 None Detected

Central Alabama Veterans Health Care System – West Campus Montgomery Alabama Building 1 Roof Only

#23027166

Analysis Report prepared for

Environmental Health Consultants, LLC

701 E. Pratt Street, Hall 3A Baltimore, MD 21202

Phone: (740) 274-1222

Montgomery VAMC

Collected: June 27, 2023 Received: July 6, 2023

Reported: July 11, 2023

We would like to thank you for trusting Hayes Microbial for your analytical needs!

We received 44 samples by FedEx in good condition for this project on July 6th, 2023.

The results in this analysis pertain only to this job, collected on the stated date, and should not be used in the interpretation of any other job. Information supplied by the customer can affect the validity of results. These results apply only to the samples as received. This report may not be duplicated, except in full, without the written consent of Hayes Microbial Consulting, LLC.

All information provided to Hayes Microbial is confidential information relating to our customers and their clients. We will not disclose, copy, or distribute any information verbally or written, except to those designated by the customer(s). We take confidentiality very seriously. No changes to the distribution list will be made without the express consent of the customer.

This laboratory bears no responsibility for sample collection activities, analytical method limitations, or your use of the test results. Interpretation and use of test results are your responsibility. Any reference to health effects or interpretation of mold levels is strictly the opinion of Hayes Microbial. In no event, shall Hayes Microbial or any of its employees be liable for lost profits or any special, incidental or consequential damages arising out of the use of these test results.

Steve Hayes, BSMT(ASCP) Laboratory Director Hayes Microbial Consulting, LLC.

EPA Laboratory ID: VA01419

Lab ID: #188863

DPH License: #PH-0198

Hayes Microbial Consulting, LLC. 3005 East Boundary Terrace, Suite F. Midlothian, VA. 23112 (804) 562-3435 contact@hayesmicrobial.com Page: 1 of 6

# Sample Material Description Non-Asbestos Fibers Asbestos Fibers

1 1A - Membrane Fibrous / Roof 1 - Core 1 Membrane / Multi-colored 10% Synthetic Fibers None Detected

2 2B - Insulation - Yellow / Roof 1 - Core 1 Insulation / Yellow 5% Cellulose Fibers None Detected

Adhesive / Cream None Detected

3 3E - Flashing - Sealant / Roof 1 - Core 1 Sealant / Silver/Black 5% Chrysotile

4 4F - Flashing - Caulk / Roof 1 - Core 1 Caulk / Gray None Detected

5 5C - Insulation - White / Roof 2 - Core 2 Insulation / White 5% Cellulose Fibers None Detected

6 6A - Membrane Fibrous / Roof 2 - Core 2 Membrane / Multi-colored 10% Synthetic Fibers None Detected

7 7D - Board / Roof 2 - Core 2 Drywall / White 5% Cellulose Fibers 5% Fiberglass

None Detected

8 8E - Flashing - Sealant / Roof 2 - Core 2 Sealant / Black None Detected

9 9F - Flashing - Caulk / Roof 2 - Core 2 Caulk / Gray None Detected

10 10G - Penetration - Sealant / Roof 2 - Core 2 Sealant / White None Detected

11 11A - Membrane Fibrous / Roof 3 - Core 3 Membrane / Multi-colored 10% Synthetic Fibers None Detected

Tar / Black 5% Synthetic Fibers None Detected

12 12D - Board / Roof 3 - Core 3 Drywall / White 5% Cellulose Fibers 5% Fiberglass

None Detected

Kamau McAbee Environmental Health Consultants, LLC 701 E. Pratt Street, Hall 3A Baltimore, MD 21202

(740) 274-1222

Montgomery VAMC

#23027166

Asbestos PLM Bulk

EPA 600/R-93, M-4/82-020

Project Analyst:

Angie Llatas-Campos, Date:

07 - 11 - 2023 Reviewed By:

Samuel Settle, Collected:Jun 27, 2023 Received: Jul 6, 2023 Reported: Jul 11, 2023

3005 East Boundary Terrace, Suite F. Midlothian, VA. 23112 (804) 562-3435 contact@hayesmicrobial.com Page: 2 of 6

13 13B - Insulation - Yellow / Roof 3 - Core 3 Insulation / Yellow None Detected

14 14G - Penetration - Sealant / Roof 3 Sealant / White None Detected

15 15A - Membrane Fibrous / Roof 4 - Core 4 Membrane / Multi-colored 10% Synthetic Fibers None Detected

16 16H - Gypcrete - Grey / Roof 4 - Core 4 Brittle / Gray None Detected

17 17I - Gypsum - White / Roof 4 - Core 4 Brittle / White None Detected

18 18A - Membrane Fibrous / Roof 4 - Core 4 Membrane / Multi-colored 10% Synthetic Fibers None Detected

Bulk Material / Off-White None Detected

19 19F - Flashing - Caulk / Roof 4 Caulk / White None Detected

20 20H - Gypcrete - Gray / Roof 4 - Core 6 Brittle / Gray None Detected

21 21A - Membrane Fibrous / Roof 4 - Core 6 Membrane / Multi-colored 10% Synthetic Fibers None Detected

Bulk Material / Off-White None Detected

22 22F - Flashing - Caulk / Roof 4 Caulk / White None Detected

23 23H - Gypcrete - Gray / Roof 5 - Core 7 Brittle / Gray None Detected

24 24D - Board / Roof 5 - Core 7 Brittle / Off-White None Detected

Tar / Black None Detected

Kamau McAbee Environmental Health Consultants, LLC 701 E. Pratt Street, Hall 3A Baltimore, MD 21202

(740) 274-1222

Montgomery VAMC

#23027166

Asbestos PLM Bulk

EPA 600/R-93, M-4/82-020

3005 East Boundary Terrace, Suite F. Midlothian, VA. 23112 (804) 562-3435 contact@hayesmicrobial.com Page: 3 of 6

25 25H - Gypcrete - Gray / Roof 5 - Core 7 Tar / Black 5% Fiberglass None Detected

Lab Note: Gypcrete Material Not Observed. Bag labeled 25A.

26 26I - Gypsum - White / Roof 5 - Core 7 Brittle / Off-White None Detected

27 27B - Insulation - Yellow / Roof 5 - Core 7 Insulation / Yellow None Detected

28 28H - Gypcrete - Gray / Roof 5 - Core 7 Brittle / Gray None Detected

29 29A - Membrane Fibrous / Roof 5 - Core 7 Membrane / Multi-colored 10% Synthetic Fibers None Detected

30 30J - Shingle Sealant - Beige / Roof 6 Sealant / White 5% Fiberglass None Detected

31 31A - Membrane Fibrous / Roof 6 - Core 10 Membrane / Multi-colored 10% Synthetic Fibers None Detected

32 32H - Gypcrete - Gray / Roof 6 - Core 10 Brittle / Gray None Detected

33 33A - Membrane Fibrous / Roof 6 - Core 11 Membrane / Multi-colored 5% Synthetic Fibers None Detected

Tar / Black 5% Cellulose Fibers None Detected

34 34I - Gypsum - White / Roof 6 - Core 11 Brittle / White None Detected

35 35J - Shingle Sealant - Beige / Roof 6 Sealant / White 10% Synthetic Fibers None Detected

36 36G - Penetration - Sealant / Roof 6 Sealant / White None Detected

Kamau McAbee Environmental Health Consultants, LLC 701 E. Pratt Street, Hall 3A Baltimore, MD 21202

(740) 274-1222

Montgomery VAMC

#23027166

Asbestos PLM Bulk

EPA 600/R-93, M-4/82-020

3005 East Boundary Terrace, Suite F. Midlothian, VA. 23112 (804) 562-3435 contact@hayesmicrobial.com Page: 4 of 6

37 37K - Shingle Sealant Black / Roof 6 Sealant / Black None Detected

38 38K - Shingle Sealant Black / Roof 6 Sealant / Black None Detected

39 39L - Pipe Sealant - Red / Roof 6 Sealant / Red None Detected

40 40L - Pipe Sealant - Red / Roof 6 Sealant / Red None Detected

41 41A - Membrane Fibrous / Roof 6 - Core 9 Membrane / Multi-colored 10% Synthetic Fibers None Detected

42 42I - Gypsum - White / Roof 6 - Core 9 Brittle / White None Detected

Tar / Black None Detected

43 43M - Stone Sealant / Roof 6 Sealant / White None Detected

44 44M - Stone Sealant / Roof 6 Sealant / White None Detected

Kamau McAbee Environmental Health Consultants, LLC 701 E. Pratt Street, Hall 3A Baltimore, MD 21202

(740) 274-1222

Montgomery VAMC

#23027166

Asbestos PLM Bulk

EPA 600/R-93, M-4/82-020

3005 East Boundary Terrace, Suite F. Midlothian, VA. 23112 (804) 562-3435 contact@hayesmicrobial.com Page: 5 of 6

Analysis Details All samples were received in acceptable condition unless otherwise noted on the report. This report must not be used by the client to claim product certification, approval, or endorsement by AIHA, NIST, NVLAP, NY ELAP, or any agency. The results relate only to the items tested. Hayes Microbial Consulting reserves the right to dispose of all samples after a period of 60 days in compliance with state and federal guidelines.

PLM Analysis All Polarized Light Microscopy (PLM) results include an inherent uncertainty of measurement associated with estimating percentages by PLM.

Materials with interfering matrix, low asbestos content, or small fiber size may require additional analysis via TEM Analysis.

TEM Analysis Analysis by TEM is capable of providing positive identification of asbestos type(s) and semi-quantitation of asbestos content.

Definitions 'None Detected' - Below the detected reporting limit of 1% unless point counting is performed, then the detected reporting limit is .25%.

New York ELAP Per NY ELAP198.6 (NOB), TEM is the only reliable method to declare an NOB material as Non-Asbestos Containing.

Any NY ELAP samples that are subcontracted to another laboratory will display the name and ELAP Lab Identification number in the report page heading of those samples. The original report provided to Hayes Microbial Consulting is available upon request.

Kamau McAbee Environmental Health Consultants, LLC 701 E. Pratt Street, Hall 3A Baltimore, MD 21202

(740) 274-1222

Montgomery VAMC

#23027166

Asbestos Analysis Information

3005 East Boundary Terrace, Suite F. Midlothian, VA. 23112 (804) 562-3435 contact@hayesmicrobial.com Page: 6 of 6

Appendix C Asbestos Bulk Sample Location Drawing

Central Alabama Veterans Health Care System West Campus

2215 Perry Hill Road, Montgomery, AL 36109

Project: Replace Roof on Building #1

Date: July 10, 2023

Core 6

Core 5

Core 4

Core 8

Core 7

Core 10 Core 9

Core 11 Core 3

Core 2 Core 1

Roof 4

Roof 6

Roof 1

Roof 3 Roof 2 Roof 5

Roof 3

Roof 7

(Inaccessible for sampling)

(Sample 3E – ACM Flashing Sealant)

File details come from the government source that posted it. Updated .