7 of 7 Salem Stormwater Drawings_Addendum A.pdf
PDF 3 MB Posted
- Attached to
- Z2NZ-- 658-23-108 Correct Stormwater Drainage
- Solicitation number
- 36C24626B0031
About this file
This document is a set of civil engineering detail drawings for a Storm Water Drainage project at the U.S. Department of Veterans Affairs facility located at 1970 Roanoke Boulevard, Salem, VA 24153-6404. The drawings, prepared by Mabbett & Associates, Inc., represent 100% Final Design phase documentation dated January 28, 2026, with an addendum revision per bidders' questions dated September 30, 2026.
The technical specifications and construction details encompass multiple stormwater management components including surface pond outlet control structures, filter sock sediment control installations for both natural ground and pavement areas, pipe outlet protection with riprap sizing requirements, precast reinforced concrete manholes conforming to ASTM C-478 with 4000 PSI concrete, catch basin installations with cascading grates and hoods, temporary silt fences and silt barriers, trench drain systems, infiltration ponds, subsurface detention systems, concrete median curbs, and utility connections for water, electrical, and communications infrastructure. Design specifications require gray iron castings conforming to ASTM A48 Class 35B, H-20 wheel load design capacity, buoyancy calculations for flotation resistance with contractor-furnished anchoring if necessary, and mechanical joint restraints for pipe connections. The drawings provide detailed dimensional specifications, installation procedures, material standards, and reference multiple 2016 Road & Bridge Standards specifications, with cross-references to sheets CK501 through CK505 and related utility coordination sheets CU101 through CU112.
View the file
Other files
Show all 33
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NTS
NTS
NTS
NTS
SEE FILTER SOCK DETAIL FOR
SEDIMENT CONTROL
STAKE
STAKE
SEE DETAIL C4 FOR
FILTER SOCK FOR
SEDIMENT CONTROL
SEE DETAIL C4 FOR
FILTER SOCK FOR
SEDIMENT CONTROL
SOIL/SEDIMENT
STOCKPILE AREA
SOIL/SEDIMENT
STOCKPILE AREA
NTS
SURFACE POND OUTLET
CONTROL STRUCTURE. SEE
SHEET CK501, DETAILS E8 & F1
4'-0"MIN.
2'-0"Ø
1"
1" 1-1
4"
2'-1 78"
7/8"
4"
AA
PLAN
SECTION A-A
FINISH
1"
2' - 2 34" 4"
4"
34-3/4"
4" 5 8"
2'-10 58"
FRAME & COVER
NOTE:
ALL CASTINGS SHALL
BE MANUFACTURED
FROM GRAY IRON
CONFORMING TO ASTM
A48 CLASS 35B
FRAME AND COVER
PRECAST REINFORCED CONCRETE
MANHOLE TO CONFORM TO ASTM
C - 478 CONCRETE OF 4000 PSI AT
28 DAYS
EXISTING GRADE
CONCRETE COLLAR
APPROVED GRADE RING
PIPE INVERT
MULTIPLES OF
2', 3', OR 4'
6" SCREENED GRAVEL
#4 @ 18"
EW MID-DEPTH
6" MIN.
6" (TYP.)
6" (TYP.)
Ø2'-2 34"
Ø2'- 0 18"
Ø2'-1 78"
FINISH
2'-0 18"
NTS
≤5' OF DEPTH
≥5' OF DEPTH
CONNECTING PIPE
TOPSOIL
GRASS
SUBGRADE
NOTES:
1. LIGHTLY ROLL OR COMPACT TOPSOIL TO 4" MINIMUM
2. COMPACT SUBGRADE TO A MIN. OF 85% PER ASTM D698
3. SEEDING
NTS
NTS
2" X 2" WOODEN STAKES PLACED 10.0' O.C.
FILTER SOCK (8", 9" OR 12")
WORK AREA PROTECTION AREA
SECTION - NATURAL GROUND AREAS
WORK AREA
FILTER SOCK (8", 12" OR 18")
CONCRETE BLOCK OR SANDBAG PLACED 10.0' O.C.
PAVEMENT SURFACE
PROTECTION AREA
SECTION - PAVEMENT AREAS
NOTES::
1. SOCK SIZE TO BE PER MANUFACTURER'S RECOMMENDATION FOR THE APPLICATION.
2. FILTER MATERIAL TO BE PER MANUFACTURER'S RECOMMENDATION FOR THE
APPLICATION.
3. COMPOST MATERIAL TO BE DISPERSED ON SITE, AS DETERMINED BY THE VA COR AFTER
SITE IS PERMANENTLY STABILIZED.
WORK AREA
WORK AREA
PROTECTION AREA
PROTECTION AREA
FILTER SOCK (8", 9" OR 12")
FILTER SOCK (8", 12" OR 18")
CONCRETE BLOCK OR SANDBANG PLACED 10.0' O.C. (TYP.)
2" X 2" WOODEN STAKES PLACED 10.0' O.C. (TYP.)
WATER FLO
W
FLO
W
PLAN - PAVEMENT AREASPLAN - NATURAL GROUND AREA
NTS
NOTE: SOIL STOCKPILE SHALL BE COVERED WITH A SECURED TARPAULIN WHEN NOT IN USE.
OVERFLOW
ELEVATION
FILTER
MATERIAL
`T
SECTION
THICKNESS (`T') = 2.25 x D50 RIPRAP SIZING - 6" (150mm) MIN.
`D
4.0 x
`D
MI
N.
PLAN
La = 4.5 x `D' MIN.
`D'=PIPE DIAMETER
0.5 X `D'
PIPE OUTLET PROTECTION SIZING TABLE
PIPE SIZE (IN) RIP RAP SIZING (D50) LENGTH(FT) WIDTH(FT)
6 3 2.5 2.0 12 5 5.0 4.0 15 6 6.25 5.0 18 8 7.5 6.0 24 10 10.0 8.0 30 12 13.0 10.0 36 14 15.0 12.0
NOTES:
1. 'La' = LENGTH OF APRON. DISTANCE 'La' SHALL BE OF SUFFICIENT
LENGTH TO DISSIPATE ENERGY.
2. APRON SHALL BE SET AT A ZERO GRADE AND ALIGNED STRAIGHT.
3. FILTER MATERIAL SHALL BE FILTER OR 6" (150mm) THICK MINIMUM
GRADED GRAVEL LAYER.
ROCK d50
50% SHALL BE LARGER
THAN 6" (150mm) MIN. DIA.
RECEIVING
ELEVATION
PIPE FLEXIBLE ADAPTOR COUPLING
NEW PIPE (MATERIAL VARIES)
S.S. TIE BAND
EXISTING PIPE (MATERIAL VARIES)
NOTES:
1. REMOVE WATERPROOFING FROM STRUCTURE BEFORE
APPLYING MORTAR. WATERPROOF AGAIN AFTER MORTAR HAS
SET.
2. EXISTING MANHOLE OR CATCH BASIN SHALL BE CORE-DRILLED
FOR PIPE INSTALLATION. IF PIPE DIAMETER IS SO LARGE THAT
CORE DRILLING IS PROHIBITED, THE CONTRACTOR MAY
SAW-CUT THE STRUCTURE TO CREATE PIPE OPENING. THE NEW
OPENING MUST THEN BE SEALED AND WATERTIGHT BOTH INSIDE
AND OUTSIDE THE STRUCTURE.
3. PIPES THAT REQUIRE A COUPLING CAN BE OF DIFFERENT SIZES
OR SIMILAR SIZES.
OUTLET CONTROL
STRUCTURE (OCS) GRATE ELEVATION
OCS-1
OCS-2
OCS-3
OCS-5
OCS-6
OCS-7
1097.0
1104.5
1104.5
1077.5 1070.5
1074.5
NEW PIPE TO EXISTING STRUCTURE STUB WITH DIFFERENT PIPE SIZING
NEW PIPE (MATERIAL VARIES)
PIPE FLEXIBLE ADAPTOR COUPLING
EXISTING PIPE STUB (MATERIAL VARIES)
S.S. TIE BAND
NEW PIPE TO EXISTING STRUCTURE STUB WITH SAME PIPE SIZING
NOTE:
ADAPTOR COUPLINGS ARE MADE
FROM PARTS SUCH AS A ONE
STEPPED MOULDED EPDM RUBBER
BODY WITH TWO DIFFERENT
DIAMATERS ON EACH SIDE AND TWO
STAINLESS STEEL CLAMP BANDS
WHICH WHEN TIGHTENED CREATE A
SECURE CONNECTION.
NOTE:
WHEN INSTALLING, SLIDE COUPLING
OVER THE PIPES AND USE A
SCREWDRIVER OR NUT DRIVER TO
TIGHTEN THE STEEL CLAMPS. MAKE
SURE TO NOT OVERTIGHTEN.
CHECK PIPES ARE ALIGNED. CLAMPS
SHOULD BE TIGHTENED TO THE
TORQUE OF 60 INCH-LBS.
Heavy Duty, Built Up Type Frame, Cascade Grate
D
24 1/4
29 1/4
D
32 3/4
24 1/4
NOTES:
- Dimensions are approximate & in inches
- Gray Iron, Class 35B
- Conforms to ASTM A48 / A48M-03 specifications
FRAME
HEIGHT
NTS
2.0
2.0
PLAN VIEW
BARREL SECTION
CONCENTRIC
CONE OR
TRUNCATED
CONE
BASE SECTION
SECTION VIEW
NOTE:
1. CASCADE GRATES SHALL BE INSTALLED ON GRADIENT OF
GUTTER IF PROFILE GRADE EXCEEDS 5%. GRATES SHALL BE
DEPRESSED 2" BELOW NORMAL GUTTER GRADE. PARALLEL
BAR GRATES SHALL BE INSTALLED ON A LEVEL GRADIENT.
2. THE CONTRACTOR SHALL SUBMIT BUOYANCY CALCULATIONS
TO VERIFY THE STRUCTURE'S RESISTANCE TO FLOTATION. IF
ANCHORING IS NEEDED FOR RESISTANCE TO FLOTATION, THE
CONTRACTOR SHALL FURNISH AND INSTALL ANCHORING
METHODS.
12" THICK 34" CRUSHED
STONE BASE
PRECAST CONCRETE BASE
SECTION WITH PIPE
OPENINGS AS APPROVED
BY THE ENGINEER.
ALL PIPES TO HAVE A
WATERTIGHT SEAL
FLEXIBLE SLEEVE CAST IN
PRECAST STRUCTURE TO
BE INTERFACE LOCK JOINT
OR EQUAL.
JOINTS OF WATERTIGHT CATCH
BASIN MUST MEET AASHTO
M1988.
SIDEWALL OF CATCH BASIN TO
BE BACKFILLED WITH
SELECT BACKFILL, AASHTO
M145 AS REVISED, CLASS A-3
OR BETTER.
CEMENT MORTAR (TYPE
II CEMENT) BRING TO
GRADE WITH BRICK WITH
A MIN. OF 1 COURSE AND
A MAX. OF 3 COURSES.
FRAME AND GRATE - EQUAL WITH
MAXIMUM OPENING SIZE OF 2 14 "
WHERE DEPTH OF COVER IS
NOT SUFFICIENT TO USE
CONCENTRIC OR
TRUNCATED CONE. A FLAT
TOP MAY BE USED.
NOTE:
WHERE THE CATCH BASIN IS
INSTALLED ADJACENT TO
BITUMINOUS CONCRETE OF TYPE V
SLOPED CURB. SET CENTERLINE OF
CATCH BASIN FRAME 1'-6" OFF FACE
OF CURB.
EXTERIOR OF STRUCTURE
SHALL BE TREATED WITH 2
COATS OF APPROVED DAMP
PROOF MATERIAL.
DESIGN NOTES:
1. ALL CONCRETE TO HAVE A MIN. OF
4,000 PSI COMPRESSIVE STRENGTH AT
28 DAYS.
2. DESIGN LOAD FOR H-20 WHEEL
LOAD.
3. CATCH BASIN TO CONFORM TO
ASTM-C478 SPECIFICATIONS.
4. REINFORCE TO 0.12 IN SQ./LF..
2.0 MI
N
18"
8"
2"
1"
BACK
VIEW
6"
9"
1 4"
FOR 1/2" BOLT
10"
11 14"
"3
8"
2 1 2"
SIDE
VIEW
PIPE
NOTE: ASSEMBLED WITH 1/2" DIA.
BY 5" HEX HEAD BRASS BOLT &
BRASS HEX NUT.
1 78"
TOP
VIEW
14"
HINGE
HINGE
R 4'-6 12"
CEMENT CASTING OF
CATCH BASIN
WALL
PIPE
CEMENT CASTING OF
CATCH BASIN WALL
R 1"
R 5/16"
CATCH BASIN
CONNECTION OUTLET
NTS
NOTE:
CASCADE GRATES SHALL BE INSTALLED ON GRADIENT OF GUTTER
IF PROFILE GRADE EXCEEDS 5%. GRATES SHALL BE DEPRESSED 2"
BELOW NORMAL GUTTER GRADE. PARALLEL BAR GRATES SHALL BE
INSTALLED ON A LEVEL GRADIENT.
CATCH BASIN HOOD
CATCH BASIN HOOD
NOTES::
1. THE CONTRACTOR SHALL SUBMIT BUOYANCY CALCULATIONS TO VERIFY THE
STRUCTURE'S RESISTANCE TO FLOTATION. IF ANCHORING IS NEEDED FOR RESISTANCE
TO FLOTATION, THE CONTRACTOR SHALL FURNISH AND INSTALL ANCHORING METHODS.
A
A
CK501
CIVIL DETAILS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
Correct Storm Water Drainage
1970 Roanoke Boulevard Salem, VA 24153-6404
658-23-108
01.28.2026 RBB KRS/PEH
100% FINAL DESIGN
# Revisions Date
Scientists I Engineers I Program Managers
Mabbett & Associates, Inc.
105 Central Street Stoneham, MA 02180-1248
T. 781-275-6050 www.mabbett.com
Mabbett
C
K d w g
Page of 59
1 ADDENDUM A - REVISION PER BIDDERS' QUESTIONS 9/30/2026
2016 ROAD & BRIDGE STANDARDS
NTS
2016 ROAD & BRIDGE STANDARDS
2016 ROAD & BRIDGE STANDARDS
MANHOLE OUTER
DIA.
INLET PIPE
OUTLET PIPE
SEE
DETAIL A
INSTALLED PLAN VIEW
DETAIL A
WEIR WALL
ANCHOR
SEE GENERAL
NOTES 1 & 5
B A
S E
S
E C
T I O
N
F
T
T
H R
O U
G H
F
T
WEIR (HEIGHT PER
PLANS) CAST INTO
BASE SECTION
GENERAL NOTES
1. STEEL REINFORCEMENT CONFORMS TO LATEST ASTM SPECIFICATION: ASTM A-615, GRADE 60 BLACK DEFORMED BARS ASTM
A-185 WELDED WIRE FABRIC 0.12 Sq. In./ Linear Ft. and 0.12 Sq. In. (Both Ways) Base Bottom
2. CONCRETE: fc = 4,000 psi @ 28 DAYS MINIMUM, TYPE III CEMENT
3. BUTYL RUBBER JOINT SEALANT PROVIDED CONFORMS TO ASTM C-990
4. HS-20 DESIGN LOADING
5. ONE POUR MONOLITHIC BASE SECTION
6. THE CONTRACTOR SHALL SUBMIT BUOYANCY CALCULATIONS TO VERIFY THE STRUCTURE'S RESISTANCE TO FLOTATION. IF
ANCHORING IS NEEDED FOR RESISTANCE TO FLOTATION, THE CONTRACTOR SHALL FURNISH AND INSTALL ANCHORING METHODS.
WEIR WALL
DETAIL B
MANHOLE
WALL
WEIR
WALL
ANCHORS
EQUAL EQUAL
4' 5"
4"
NTS
APPLY
TACK
COAT
2.
3.
4.
1.01.0
NOTES:
1. PAVEMENT TO BE BITUMINOUS CONCRETE LAID IN 2 COURSES.
2. 2" BITUMINOUS CONCRETE SURFACE COURSE
3. 3" BITUMINOUS CONCRETE BINDER COURSE
4. 8" BASE COURSE
5. 12" SUBBASE COURSE
6. ALL TRENCHES SHALL BE BACKFILLED AND TEMPORARILY PAVED OR STEEL PLATED AT
THE END OF EACH WORKING DAY.
7. BACKFILL MATERIAL TO BE PLACED IN 0.67' MAX. LIFTS AT 95% MODIFIED PROCTOR
COMPACTION.
SAW-CUT EXIST PAVE.
SAW-CUT EXIST PAVE.
SAW-CUT EXISTING PAVEMENT, APPLY TACK COAT, INFRARED JOINTS
AFTER PLACING PAVEMENT
DISTANCE AS REQUIRED
APPLY TACK COAT
5.
NTS
PAVEMENT EDGE.
FULL DEPTH SEVERANCE
WITH A SAW BLADE
CONCRETE PAVEMENT
NEW PORTLAND CEMENT
EXISTING CONCRETE
SEE NOTE 2
FULL-DEPTH SEVERANCE
WITH A SAW BLADE
NOTES:
1. PAVEMENT TO BE A MINIMUM 7" OF PORTLAND CEMENT CONCRETE WITH A MINIMUM 8"
OF AGGREGATE BASE COURSE. THE THICKNESS OF THE AGGREGATE BASE COURSE MAY
NEED TO BE INCREASED IF POOR SUBGRADE AND WEATHER CONDITIONS ARE ENCOUNTERED
DURING CONSTRUCTION.
2. REMOVE 8" OF EXISTING SUBBASE AND REPLACE WITH NEW SUBBASE AND COMPACT
TO 95% OF THE MODIFIED PROCTOR TEST RESULTS.
3. CONCRETE PAVEMENT SHALL MEET THE MINIMUM REQUIREMENTS OF VDOT
SPECIFICATION 214 AND 217.
4. USE S.S. SUPPORT CHAIRS FOR REBAR.
5. PAVED CONCRETE STRENGTH SHALL BE A MINIMUM OF 3,000 PSI.
9"
TYP
9"
TYP
MIN. PATCH WIDTH 4'-0"
1-1/4" STAINLESS STEEL
BAR - 18" LONG SPACING
- 18" O.C.
#4 REBAR AT 12" O.C.
E.W. AT MIDSPAN
EXISTING
CONCRETE
NTS
PAVEMENT EDGE.
FULL DEPTH SEVERANCE
WITH A SAW BLADE
CONCRETE PAVEMENT
NEW PORTLAND CEMENT
EXISTING CONCRETE
SEE NOTE 2
FULL DEPTH SEVERANCE
WITH A SAW BLADE
NOTES:
1. PAVEMENT TO BE A MINIMUM 5" OF PORTLAND CEMENT CONCRETE WITH A MINIMUM 6"
OF AGGREGATE BASE COURSE. THE THICKNESS OF THE AGGREGATE BASE COURSE MAY
NEED TO BE INCREASED IF POOR SUBGRADE AND WEATHER CONDITIONS ARE ENCOUNTERED
DURING CONSTRUCTION.
2. REMOVE 8" OF EXISTING SUBBASE AND REPLACE WITH NEW SUBBASE AND COMPACT
TO 95% OF THE MODIFIED PROCTOR TEST RESULTS.
3. CONCRETE PAVEMENT SHALL MEET THE MINIMUM REQUIREMENTS OF VDOT
SPECIFICATION 214 AND 217.
4. USE S.S. SUPPORT CHAIRS FOR REBAR.
5. PAVED CONCRETE STRENGTH SHALL BE A MINIMUM OF 3,000 PSI.
9"
TYP
9"
TYP
MIN. PATCH WIDTH 4'-0"
1-1/4" STAINLESS STEEL
BAR - 18" LONG SPACING
- 18" O.C.
W 2.9 X W 2.9
MESH WIRE
EXISTING
CONCRETE
NTS
RECOMMENDED MIN.
TRENCH WIDTH
PIPE DIA. MIN. TRENCH WIDTH
23" 26" 28" 30" 34" 39" 48" 56" 64" 80" 96"
6" 8" 10" 12" 15" 18"
24" 30" 36" 48" 60"
W = TRENCH WIDTH
D = PIPE DIAMETER
W
PIPE
INITIAL BACKFILL
SCREENED GRAVEL
TO BE PLACED AND
COMPACTED
SEPARATELY
SCREENED GRAVEL
EXISTING
SOIL
NOTES:
1. INITIAL BACKFILL & BEDDING MATERIAL SHALL BE CLASS I OR CLASS II.
2. ALL PIPE SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH ASTM D2321 ,
"STANDARD PRACTICE FOR UNDERGROUND INSTALLATION OF THERMOPLASTIC
PIPE FOR SEWERS AND OTHER GRAVITY-FLOW APPLICATIONS."
3. REFER TO SPECIFICATIONS 31 20 11 AND 33 40 00 FOR ADDITIONAL
INFORMATION.
4. 6" MIN. IF LEDGE IS ENCOUNTERED, THEN PROVIDE TO THE EXTENT OF OVER
BLOW.
FINAL BACKFILL PLACED AND
COMPACTED TO 95% IN 8" LAYERS
6" + 1/2D
2 D HAUNCHING AREA
6" BEDDING AREA
D
EXCAVATION DEPTH VARIES WITH
SOIL CONDITIONS. SEE NOTE 4.
NTS
NOTES:
1. PREPARE SOIL BEFORE INSTALLING BLANKETS, INCLUDING APPLICATION OF LIME, FERTILIZER, AND SEED. NOTE: WHEN USING CELL-O-SEED DO NOT SEED PREPARED AREA. CELL-O-SEED MUST BE INSTALLED WITH PAPER SIDE DOWN.
2. BEGIN AT THE TOP OF THE SLOPE BY ANCHORING THE BLANKET IN 6" DEEP X 6" WIDE TRENCH. BACKFILL AND COMPACT
THE TRENCH AFTER STAPLING.
3. ROLL THE BLANKETS (A) DOWN OR (B) HORIZONTALLY ACROSS THE SLOPE.
4. THE EDGES OF PARALLEL BLANKETS MUST BE STAPLED WITH APPROXIMATELY 2" OVERLAP. REFER TO GENERAL STAPLE PATTERN GUIDE FOR CORRECT STAPLE PATTERN RECOMMENDATIONS FOR SLOPE INSTALLATIONS.
5. WHEN BLANKETS MUST BE SPLICED DOWN THE SLOPE, PLACE BLANKETS END OVER END (SHINGLE STYLE) WITH APPROXIMATELY 4" OVERLAP. STAPLE THROUGH OVERLAPPED AREA, APPROXIMATELY 12' APART.
6. EROSION CONTROL BLANKET FOR USE ON SLOPES SHALL BE A BIODEGRADABLE DOUBLE NET WOVEN BLANKET WITH JUTE NETTING AND COCONUT FIBER MATRIX SPECIFICALLY MANUFACTURED FOR THE PURPOSE (NORTH AMERICAN
GREEN) ERONET S150 OR APPROVED EQUAL.
7. ONCE PERMANENT STABALIZATION IS ACHIEVED, REMOVE ANY NON -BIODEGRADABLE MESH, IF USED.
3B
3A
NTS
NTS
2016 ROAD & BRIDGE STANDARDS
NTS
OUTLET CONTROL
STRUCTURE (OCS) WEIR ELEVATION
OCS-4
OCS-8
OCS-10
OCS-9
1067.5
979.2 1078.5
1078.5
A
NTS
TOPSOIL AND SEED
NOTES:
1. SEE UTILITY PLANS FOR PIPE SIZES.
2. ALL COVERS SHALL BE H-20 LOAD RATED MIN. IN HEAVY LOAD AREAS
PVC CLEANOUT COVER IN
LAWN AREAS (4" BELOW F.G.)
CAST IRON COVER W/ BRONZE
PLUG IN PAVED AREAS (FLUSH
W/ PVMNT.)
COMPACTED SUBGRADE OR
UNDISTURBED NATIVE SOIL
UNDER PAVEMENT/GRASS PAVERS (HEAVY LOAD AREAS)UNDER LAWN
PVC WYE (45º BEND)
DRAIN PIPE
D.I. RISER (30" DEEP) W/
NO-HUB COUPLING TO PVC
PIPE IN PAVED AREAS
SAND BEDDING (12" MIN.
SURROUND)
PVC RISER
PVC FITTING (45º BEND)
PVC PIPE
A
TEE WYE AND DOUBLE WYE ELBOW
NOTES:
1. REFER TO SPECIFICATION 33 40 00 FOR ADDITIONAL INFORMATION
NTS
A
CK502
CIVIL DETAILS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
Correct Storm Water Drainage
1970 Roanoke Boulevard Salem, VA 24153-6404
658-23-108
01.28.2026 RBB KRS/PEH
100% FINAL DESIGN
# Revisions Date
Scientists I Engineers I Program Managers
Mabbett & Associates, Inc.
105 Central Street Stoneham, MA 02180-1248
T. 781-275-6050 www.mabbett.com
Mabbett
C
K d w g
Page of 59
NTS
NTS
2016 ROAD & BRIDGE STANDARDS
2016 ROAD & BRIDGE STANDARDS
NTS
NTS
CATCHBASIN
GRATE
POLYPROPYLENE
BOOT
CATCHBASIN
FRAME
OPTIONAL
OVERFLOW
DUMP STRAPS
EXPANSION RESTRAINT
" NYLON ROPE 2"
FLAT WASHERS)
DUMP STRAPS
SILT SACK
CATCHBASIN GRATE
BAG DETAIL
CROSS
SECTION
NOTES:
1. INSPECT AT MINIMUM WEEKLY OR AFTER RAIN EVENT.
2. MAINTAIN AS NECESSARY.
3. REPLACE SILT SACKS ONCE THE BAG IS FILLED HALF WAY WITH DEBRIS.
4. DO NOT EMPTY SILT SACK CONTENTS INTO CATCH BASIN.
2016 ROAD & BRIDGE STANDARDS
2016 ROAD & BRIDGE STANDARDS
NTS
NOTES::
1. THE CONTRACTOR SHALL SUBMIT BUOYANCY CALCULATIONS TO VERIFY THE
STRUCTURE'S RESISTANCE TO FLOTATION. IF ANCHORING IS NEEDED FOR RESISTANCE
TO FLOTATION, THE CONTRACTOR SHALL FURNISH AND INSTALL ANCHORING METHODS.
A
CK503
CIVIL DETAILS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
Correct Storm Water Drainage
1970 Roanoke Boulevard Salem, VA 24153-6404
658-23-108
01.28.2026 RBB KRS/PEH
100% FINAL DESIGN
# Revisions Date
Scientists I Engineers I Program Managers
Mabbett & Associates, Inc.
105 Central Street Stoneham, MA 02180-1248
T. 781-275-6050 www.mabbett.com
Mabbett
C
K d w g
Page of 59
1 ADDENDUM A - REVISION PER BIDDERS' QUESTIONS 9/30/2026
A
NTS
NTS
NTS
COMPRESSIVE
ALUMINUM SLOT
RISER WITH 5 IN
WIDE GRATE
STRENGTH CONCRETE
1/8" RECESS INTO
FINISHED PAVEMENT
PAVEMENT
H
ID
BASE MATERIAL
AS SOIL BACKFILL
STABLE, UNDISTURBED
EARTH OR COMPACTED
FILL
Nominal
Diameter, ID, in.
Depth of Invert, H, in.
Minimum Maximum
9.00 30.00
11.00 32.00
13.00 34.00
15.50 48.00
18.75 51.00
22.00 54.00
28.75 60.00
35.00 66.00
41.25 72.00
NOTES:
1. BACKFILL DESIGN SHOULD BE USED FOR NON-VEHICULAR LOADS ONLY.
2. ENSURE CONCRETE BACKFILL IS PROPERLY KNIFED UNDER THE LIP OF
THE SLOT FOR PROPER DESIGN SUPPORT.
3. SURFACE PAVEMENT ADJOINING THE SLOT SHOULD BE A NON-EROSIVE
MATERIAL.
4. SITE ENGINEER TO PROVIDE SITE SPECIFIC BACKFILL DETAILS, SUCH AS
PAVEMENT TYPE.
5. SLOT RECESS IS NOT INCLUDED IN DEPTH OF INVERT TABLES.
6. PAVED CONCRETE STRENGTH SHALL BE A MINIMUM OF 3,000 PSI.
H. (SEE TABLE)
MIN. AND MAX. COVERAGE TO BE CONFIRMED WITH MANUFACTURER
SEE "H" VALUE ON TABLE BELOW
SEE GRADING AND UTILITY PLANS
SEE GRADING AND UTILITY PLANS
SEE TABLE BELOW
PER
MANUFACTURER
SPECIFICATIONS
PER
MANUFACTURER
SPECIFICATIONS
SEE TABLE
4. THE CONTRACTOR SHALL SUBMIT BUOYANCY CALCULATIONS TO VERIFY THE STRUCTURE'S RESISTANCE TO
FLOTATION. IF ANCHORING IS NEEDED FOR RESISTANCE TO FLOTATION, THE CONTRACTOR SHALL FURNISH
AND INSTALL ANCHORING METHODS.
STANDARD GRATE INFORMATION
OPEN AREA,
SQ IN
37.44
NOTES:
1. ALL DIMENSIONS ARE FOR REFERENCE ONLY
2. GRATE MEETS HS-25 LOAD RATING PER AASHTO M306-10
3. THE SIZE OF OPENINGS MEET THE REQUIREMENTS OF THE
AMERICAN DISABILITY ACT, AS STATED IN FEDERAL REGISTER
PART III, DEPARTMENT OF JUSTICE, 28 CFR PART 36
Ø 1.00 in
Ø 0.41 in THRU 0.50 in
0.50 in
OPEN AREA, %
39.5
2.00 in
1.72 in
0.81 in
1.12 in
NOTE: ALL DIMENSIONS
ARE ± 1/2 FOOT.
4.81 in
19.69 in
NTS
2016 ROAD & BRIDGE STANDARDS
2016 ROAD & BRIDGE STANDARDS
NTS
PER MANUFACTURER'S RECOMMENDATIONS
MIN. AND MAX. COVERAGE TO BE CONFIRMED WITH MANUFACTURER
SEE GRADING AND UTILITY PLANS
SEE GRADING AND UTILITY PLANS
SEE EARTHWORK
SPECIFICATIONS
PER MANUFACTURER
SPECIFICATIONS
PER MANUFACTURER
SPECIFICATIONS
H. (SEE TABLE)
SEE TABLE
SEE "H" VALUE ON TABLE BELOW
SEE TABLE BELOW
4. THE CONTRACTOR SHALL SUBMIT BUOYANCY CALCULATIONS TO VERIFY THE STRUCTURE'S RESISTANCE TO
FLOTATION. IF ANCHORING IS NEEDED FOR RESISTANCE TO FLOTATION, THE CONTRACTOR SHALL FURNISH
AND INSTALL ANCHORING METHODS.
MANUFACTURER
A
A
CK504
CIVIL DETAILS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
Correct Storm Water Drainage
1970 Roanoke Boulevard Salem, VA 24153-6404
658-23-108
01.28.2026 RBB KRS/PEH
100% FINAL DESIGN
# Revisions Date
Scientists I Engineers I Program Managers
Mabbett & Associates, Inc.
105 Central Street Stoneham, MA 02180-1248
T. 781-275-6050 www.mabbett.com
Mabbett
C
K d w g
Page of 59
1 ADDENDUM A - REVISION PER BIDDERS' QUESTIONS 9/30/2026
STRUCTURE NAME INTERNAL HEIGHT "H"
(FT)
SIS-1
SIS-2A
7.0
3.0
CHAMBER TOTAL
STORAGE (CF)
30,561
5,187 22,295
19,452
2.5 2,077
SYSTEM INVERT
ELEVATION
1063.0
977.5 1074.0
1078.5
SIS-2B
SIS-3A
SIS-3B
7.0
7.0
977.5
STRUCTURE NAME INTERNAL HEIGHT "H"
(FT)
SDS-3 6.0
CHAMBER TOTAL
STORAGE (CF)
8,600
SYSTEM INVERT
ELEVATION
983.5
NEW DUCTILE IRON PIPE
COUPLING/PUSH ON JOINT
EXISTING PIPE
EXISTING WATER MAIN
MECHANICAL JOINT GATE VALVE & JOINTS
CAST IRON VALVE BOX
2-8" X 4" X 16" CONCRETE BLOCKS
WATER MAIN
TAPPING SLEEVE
MECHANICAL JOINTS
NEW DUCTILE
IRON PIPE
ACCESS TUBE
MASONRY RING
MECHANICAL JOINT
TAPPING GATE VALVE
VALVE BOX AND COVER
FINISHED GRADE
COUPLING MECHANICAL JOINT
A
SPACER
A
0.75
B
B
SECTION A-A SECTION B-B
0.125
0.125
EX. WATER PIPE
PROP. WATER PIPE
EX./PROP. GRADE
3 F T
MI
N.
C
OV
ER
3 F T
MI
N.
C
OV
ER
NEW DUCTILE IRON PIPE
EXISTING/PROPOSED GRADE
PROPOSED DRAINAGE PIPE
PROPOSED WATER, ELECTRICAL
OR COMMUNICATION INTERSECTING
UTILITY SECTION TO BE RELOCATED.
REFER TO CU101 TO CU112 SHEETS.
MI
N.
O F
1.5 F
T
VE
RT
IC
AL
CL
EA
RA
NC
E
BACKFILL
NOTES:
1. ASSUMED WORKING PRESSURE = 200 LB/IN^2
2. ASSUMED ALLOWABLE SOIL BEARING PRESSURE = 1,200 LB/FT^2
3. ALL BEARING SURFACES TO BE CARRIED TO UNDISTURBED GROUND
4. CONCRETE TO BE 3000 PSI MIN.
5. BLOCKS THICKNESS SHALL EQUAL PIPE DIAMETER PLUS 4" (A VALUE)
6. IN AREAS WHERE NOT ENOUGH SPACE IS AVAILABLE FOR THRUST BLOCK INSTALLATION, THE
CONTRACTOR SHALL PROVIDE MECHANICAL JOINT RESTRAINTS AS A SUBSTITUTE TO CONCRETE
THRUST BLOCKS
7. REFER TO SPECIFICATION 33 10 00 FOR ADDITIONAL DETAILS
X
X
X
X
BENDS
TEES
SECTION X-X CAPS
6"
W
W
6"
W/2 W/2
L
L
L
W
A
I N
L
PIPE SIZE 22.5° 45° 90°
TEE, WYE, DEAD END
L W
AREA
(SF)
L W
AREA
(SF)
L W
AREA
(SF)
L W
AREA
(SF)
8" 24" 20" 3.3 24" 39" 6.4 24" 72" 11.8 24" 51" 8.4
10" 26" 29" 5.1 26" 56" 10 26" 103" 18.5 26" 73" 13.1
SOIL TYPE: *ASSUMED TO BE DENSE FINE TO COARSE SAND (θ = 35°) TO BE CONFIRMED PER
CONTRACTOR'S GEOTECHNICAL INVESTIGATION
NTS
4" 20" 6"
0.8
20" 12"
1.6 20"
22" 3.0
20" 16"
2.1
6"
22" 13"
1.8
22" 24"
3.6 22"
44" 6.7
22" 31"
4.7
A
CK505
CIVIL DETAILS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
Correct Storm Water Drainage
1970 Roanoke Boulevard Salem, VA 24153-6404
658-23-108
01.28.2026 RBB KRS/PEH
100% FINAL DESIGN
# Revisions Date
Scientists I Engineers I Program Managers
Mabbett & Associates, Inc.
105 Central Street Stoneham, MA 02180-1248
T. 781-275-6050 www.mabbett.com
Mabbett
C
K d w g
Page of 59