This memorandum provides details regarding a forthcoming federal solicitation for construction services. The Department of Veterans Affairs intends to issue a Request for Proposal to award a single firm fixed-price contract for construction renovation services at the Lebanon VA Medical Center in Lebanon, Pennsylvania. The scope of work involves renovating and constructing a state-of-the-art education center and associated support spaces on the second floor of Building 22, and includes demolition, construction of floors, lights, ceilings, systems, doors, and associated structural components. The period of performance is anticipated to be 545 calendar days from notice to proceed. The estimated magnitude of construction costs is between $2,000,000 to $5,000,000. The solicitation is designated as a 100% service-disabled veteran-owned small business set aside, with a July 2020 anticipated issue date. Questions regarding the solicitation must be submitted in writing by a specified deadline.
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MEMORANDUM
\\ad.wrallp.com\bwraproj\42108-000\Engineering\3 Design\3H Geotech\Geotech Memo Report_July 2019.docx
Date: July 31, 2019
To: Collin Polt (Derby), Karl Rickert Work Order Number: 42108.000
From: Jay Burtis Contract Number: 595-15-201
Subject: Renovation Foundation Recommendations Project: Lebanon VA Building 22 Renovations
CC: Brad Jones, Andrew Connelly, Monica Paylor, Greg Koepping
Introduction
Whitman, Requardt and Associates, LLP (WRA) is providing geotechnical engineering services for the renovation of Building 22 at the Lebanon Veteran Administration (VA) Medical Center in Lebanon, PA. The renovations to the existing 3-story building include a 3-story addition to the front of the building to replace the main entrance. The building addition will include a new elevator that will be adjacent to the existing elevator. The new elevator and the existing elevator consist of overhead geared traction elevators.
The purpose of this geotechnical memo report is to present the subsurface information and define the general subsurface conditions at the site, and to evaluate those conditions with regard to geotechnical engineering considerations for the proposed construction. This report includes geotechnical design recommendations for support of the proposed building addition and new elevator on deep foundations.
Site Geology
The project site is located within the Great Valley Section of the Ridge and Valley Province. The Great Valley Section is a very broad lowland which has carbonate rocks including limestone and dolomite. Karst topography, including sinkhole and surface depressions, is common within this region.
The site is underlain by the Late Cambrian Period Richland Formation. Rock of the Richland Formation is gray, finely crystalline, Dolomite that is locally interbedded with Limestone, Chert and Quartz. In this region, the Richland Formation can be over 1000 feet thick.
Kochanov (1988) compiled karst features within Lebanon County, including many that are underlain by the Richland Formation. Several sinkholes were mapped within ¼ mile east and west of the project location. Less than 1000 feet south of the site, a geologic contact trending roughly east-west marks the boundary between the Richland Formation that underlies the site and the Snitz Creek Formation to the south. Areas near geologic contacts are often associated with a higher susceptibility to development of karst topography.
Subsurface Conditions
On September 29, 2018 a subsurface exploration program consisting of one Standard Penetration (SPT) boring was performed by Navarro & Wright of New Cumberland, PA in the footprint of the proposed elevator addition. Test boring B-1 was located approximately 8 feet away from the face of the building and 9 feet southwest of the sidewalk leading into the building in a grassy area. The boring location plan is attached. A WRA geotechnical engineer was present for the duration of the drilling.
Test boring B-1 was drilled until auger refusal was encountered at a depth of 15.5 feet below the ground surface. After 4 inches of topsoil, the top 8.5 feet of soil encountered was fill material consisting of a brown and tan/orange lean clay and fine gravel with uncorrected blow counts ranging from 10 to 6 blows per foot (bpf). From 8.5 feet to 15.5 feet below the ground surface, the soil was an orange silt with black and tan silt seams with two blow count samples of 6 bpf. Soil
July 31, 2019 Page 2 WRA W.O. # 42108.000
\\ad.wrallp.com\bwraproj\42108-000\Engineering\3 Design\3H Geotech\Geotech Memo Report_July 2019.docx was moist to dry until 15 feet below the ground surface where the ground water table was encountered. The ground water table was encountered above the top of rock which was at a depth of 15.5 feet below the ground surface, or at elevation 530 feet. Rock was cored for a depth of 10 feet, with rock core sample recovery of 9.4 feet. The encountered rock consisted of limestone with calcite veins and was moderately weathered to fresh and hard. The Rock Quality Designation (RQD) ranged from 44% to 94%, generally increasing in value with depth. The test boring log and photographs of the rock cores are attached.
Existing and Proposed Construction
There are existing buried utilities in the area of work, including 10-inch chilled water supply and return lines, and buried electrical lines for a heated sidewalk and for site lighting systems. There are other buried utilities in the general vicinity of the proposed construction. The existing utilities should be reviewed with respect to the proposed construction and relocated if necessary. The site utility and grading plan drawing is attached.
We reviewed the Building No. 22 structural drawings, dated November 25, 1947. It is our understanding that the existing building is a reinforced concrete structure supported on shallow foundations consisting of spread footings bearing on rock. The existing building has a finished first floor at El. 546 feet and a below grade level noted as “pipe space” at El. 540 feet. As noted on the drawings, some of the existing building foundations in the area of the proposed building addition and new elevator are founded as deep as El. 529.1 feet. These existing building foundations are therefore located at depths of up to 16’-10” below the first floor.
The new building addition will consist of concrete slab-on-grade and masonry wall construction, with upper level floors consisting of concrete slab on metal deck and open web steel joist construction, and light gauge steel roof trusses.
The addition will have a first-floor slab at El. 546 feet and no below grade levels, other than the new elevator which will have a pit depth of 4-feet below the first-floor slab. The structural engineer provided wall loads of 7 kips per linear foot and maximum column loads of 50 kips for the new construction. The foundation plan, structural sections, details and notes are attached.
We understand that a deep foundation system is preferred for support of the new construction due to issues associated with the depth of the existing building foundations. Shallow foundations could provide adequate support; however, to avoid overstressing the existing foundations, the new spread footing foundations would need to be lowered to match the depth of adjacent spread footing foundations. Due to the required excavation depth of more than 16 feet, a shallow foundation system will require installation of an excavation support system. A deep foundation system will greatly reduce the extent of excavation and the below-grade construction that would be required for new spread footing construction.
Geotechnical Recommendations
The new elevator and building addition may be supported on deep foundations consisting of drilled and grouted micropiles extending into hard limestone rock. The new building addition may be constructed upon a perimeter grade beam supported on micropile foundations, and the new elevator may be supported upon a mat slab supported on micropile foundations.
For this project, we recommend using a performance specification for the micropile foundations. The performance specification requires that the Contractor prepare micropile design calculations and working drawings for review and approval by the Engineer. Since VA MasterFormat 2004 does not include a micropile foundation specification, we will prepare a micropile performance specification as requested for this project.
For initial design and cost estimating purposes, we estimate that a micropile consisting of a 5.5-inch O.D. steel casing with a 0.415-inch wall thickness and a minimum 5-ft. grouted bond zone in hard limestone rock will provide an allowable 55-kip compressive load capacity. Much higher capacities can be achieved with larger diameter micropiles and/or longer micropiles. For the new foundations at the building addition and elevator, we estimate a micropile tip elevation ranging from El. 524 feet to El. 529 feet.
July 31, 2019 Page 3 WRA W.O. # 42108.000
\\ad.wrallp.com\bwraproj\42108-000\Engineering\3 Design\3H Geotech\Geotech Memo Report_July 2019.docx
Seismic Site Classification
We have reviewed the available subsurface information and evaluated the site in accordance with ASCE/SEI 7-16 “Minimum Design Loads for Buildings and Other Structures”. For seismic loading we have determined that Site Class C should be used for design of the proposed building addition. The site coefficients may be determined as a function of the Site Class and may be used to calculate the design spectral response parameters. The seismic design parameters provided on the attached “ATC Hazards by Location” report were obtained for this project using the ATC Hazards by Location website https://hazards.atcouncil.org/ for determination of seismic hazard design loading, as provided by the U.S. Geological Survey Seismic Design Web Services.
James Jay Burtis III, P.E.
Attachments
Boring Location Plan Test Boring Log Rock Core Photographs Civil Grading Plan Structural Drawings ATC Hazards Report https://hazards.atcouncil.org/ https://hazards.atcouncil.org/ https://earthquake.usgs.gov/ws/designmaps/ https://earthquake.usgs.gov/ws/designmaps/
SCALE: 1"=20'
SUBSURFACE UTILITY DESIGNATING WORKSHEET
VA LEBANON-BUILDING #22
LEBANON COUNTY, PENNSYLVANIA
A/I/DATA PROJECT #18232 SHEET 1 OF 1
DRAFTED BY: GMZ CHECKED BY: KLS DRAWING DATE: 09/04/2018
FIELD DESIGNATING PERFORMED:
08/24/2018
BY: JPW, BDB
DRAWING PREPARED FOR:
WHITMAN, REQUARDT & ASSOCIATES, LLP
801 SOUTH CAROLINE STREET
BALTIMORE, MD 21231
SITE ADDRESS:
1700 S LINCOLN AVENUE
LEBANON, PENNSYLVANIA
ACCURATE INFRASTRUCTURE DATA, INC.
1123 HANZLIK AVEUNE, BALTIMORE, MD 21237
PHONE: 410-686-5091 FAX: 410-686-5093
8'
9'
Boring, B-1
Boring Location Plan
S-1
S-2
S-3
S-4
S-5
R-1
R-2
R-3
R-4
67%
44%
71%
94%
EL
545.0 0.0
EL
544.7 0.3
EL
539.0 6.0
EL
536.5 8.5
EL
530.0 15.0
EL
529.5 15.5
EL
519.5 25.5
Water Table at 15' Auger Refusal at 15.5'
4" Topsoil FILL, Brown, moist, stiff, LEAN CLAY with fine gravel, contains organics (CL)
FILL, Tan/orange, dry, firm, Silty LEAN CLAY, trace gravel chips (CL)
Orange, dry, firm, SILT, with black and tan silt seams (ML)
Orange, wet, firm, SILT, with black and tan silt seams (ML) Limestone with Calcite veins, gray, very fine grained, subangular, thickly bedded, moderately weathered to fresh, hard
Bottom of Boring @ 25.5 FT
WaterTime
Boring No. B-1
SAMPLE IDENTIFICATION
Boring No. B-1
0-4 5-10 11-30 31-50 50-80
OVER 80
VERY LOOSE
LOOSE
MEDIUM DENSE
DENSE
VERY DENSE
EXTREMELY DENSE
PROJECT:
LOCATION: Lebanon , Pennsylvania
DRILLING BY: N&W
3.25
DENSITY
VERY SOFT
SOFT
MEDIUM STIFF
STIFF
VERY STIFF
HARD
0-2 3-4 5-8 9-15 16-30
OVER 30
42108-000
362062.9
2345361.5
545.0
9/29/2018
9/29/2018
Kurt Bassett
Greg Koepping
TEST BORING LOG
CORE
9/29/2018
- S - SPLIT SPOON
- ST - SHELBY TUBE
- RC - ROCK CORE
- DS -DENNISON
Casing SPT
1.5
GROUNDWATER DATA (ft) SAMPLER
PROJECT: Lebanon VA Building 22 LOCATION: Lebanon , Pennsylvania
DRILLING BY: N&W
WO #:
NORTH:
EAST:
ELEVATION:
START DATE:
END DATE:
DRILLER:
LOGGED BY:
Date
EQUIPMENT CASING
Cave-In TYPE
SIZE, ID (in)
HAMMER WT. (lb)
HAMMER FALL (in)
RIG: Track Rig (Auto Hammer)
BLOWS/FT CONSISTENCY
HSA - HOLLOW STEM AUGERS
SSA - SOLID STEM AUGERS
DC - DRIVING CASING
MD - MUD DRILLING
HA - HAND AUGER
DRILLING METHOD BLOWS/FT
S A
M P
LE
N
U M
B E
R
S A
M P
LE
R
E C
O V
E R
Y in
B
LO
W S
/6
R
Q D
ELEV.
DEPTH G
R
A P
H
IC
NOTES:
S A
M P
LE
T
Y P
E
D E
P T
H
F T
DESCRIPTION AND CLASSIFICATION
(moisture, density, color, proportions, etc.)
Photograph 1: All Rock Core Samples
Lebanon VA Renovate Building 22
42108.000 9/29/2018
Photograph 2: Rock Cores ½
Photograph 3: Rock Cores 2/2
Project Title
DE
PA
RT
M
EN
T
OF
VE
TE
RA
NS
A
FF
AI
RSDrawing Title Date
Project No.
Drawing No.
Dwg. Of
Approved: Associate Director for Operations:
Approved: Director, Medical Center:
Drawn:Building No: Checked:
Location:
Additions:
Revisions:
1 5 6 7 8
21 3 4 5 6 7 8
A B
C D
E o n e q u a r t e r i n c h o n e f o t o n e e i g h t i o t t h r e e e i g h t h s i n o t o n e h a l f i n o t o n e a d a l f i n o t o n e i n o t t h r e e q u a r t e r s i n o t t h r c h e s o t
DELLC
JOB No.
2 3 4
Consultants:
Date
95% CD SUBMISSION
FULLY SPRINKLERED
& ASSOCIATES, INC.
BURDETTE KOEHLER MURPHY
RICKERT ENGINEERING, INC.
BUILDING COST CONSULTANTS
COST ESTIMATING
12917 - 30TH AVENUE
PLATTSMOUTH, NEBRASKA 68048
402.298.8260 - FAX 402.298.8290
MECHANICAL / ELECTRICAL
CONSULTING ENGINEERING
1416 CLARKVIEW ROAD
BALTIMORE, MARYLAND 21209
410.323.0600 - FAX 410.377.2543
STRUCTURAL ENGINEERING
8813 WALTHAM WOODS ROAD, SUITE 500
BALTIMORE, MARYLAND 21234
410.663.5110 - FAX 410.663.5114
FIRE PROTECTION ENGINEERING
8815 CENTRE PARK DR., SUITE 200
COLUMBIA, MARYLAND 21045
410.750.2246 - FAX 410.750.2588
KOFFEL ASSOCIATES, INC.
WHITMAN, REQUARDT & ASSOCIATES,LLP
CIVIL ENGINEERING
801 SOUTH CAROLINE STREET
BALTIMORE, MD 21231
410.235.3450 - FAX: 410.243.5716
ROBERT L. SEYMOUR & ASSOCIATES, INC.
VERTICAL TRANSPORTATION CONSULTANTS
182 THOMAS JOHNSON DR. SUITE 200
FREDERICK, MARYLAND 21702
301.662.8112 - FAX 301.662.8117
LEBANON RENOVATE
BUILDING 22
BWJ
AKC
08/05/2019
595-15-201
170801D
LEBANON VA
MEDICAL CENTER
LEBANON, PA
1SOURCE SAFETY AND HEALTH
ASBESTOS ABATEMENT
140 SOUTH VILLAGE AVENUE, SUITE 130
EXTON, PA 19341
610.524.5525 - FAX: 610.524.0565
ARCHITECTURE
PLANNING
ENGINEERING
2215 Conowingo Rd, Suite 100
Bel Air, Maryland 21015-1436
410.803.0009 fax 410.836.6611
SITE UTILITY AND GRADING
PLAN
L-2
1 2 3 4 12 13 14
FOUNDATION & FIRST FLOOR FRAMING PLAN
SCALE: 1/8" = 1'-0"
S101
4 1/2"
[529.10]
[529.10]
[537.00]
[537.00]
[536.80] [534.90]
[536.80]
1. ELEVATION TOP OF THE EXISTING AND NEW FIRST FLOOR SLAB
SHALL BE 546.00.
2. THE EXISTING FIRST FLOOR IS A 2 1/2" THICK CONCRETE SLAB
SUPPORTED ON ONE-WAY CONCRETE PAN JOISTS SPACED AT 25"
ON CENTER.
3. THE NEW SLAB ON GRADE SHALL BE 5" MINIMUM THICK CONCRETE
REINFORCED WITH 6X6-W1.4XW1.4 WELDED WIRE FABRIC ON A 10
MIL POLYETHYLENE VAPOR BARRIER ON 6" DRAINAGE FILL.
4. ELEVATION TOP OF THE NEW ELEVATOR PIT SLAB SHALL BE 542.00.
5. ELEVATION BOTTOM OF EXISTING FOOTING ARE NOTED THUS
[534.90].
6. ELEVATION TOP OF NEW PILE CAPS ARE 542.83 UNLESS NOTED
OTHERWISE.
7. ELEVATION BOTTOM OF NEW GRADE BEAMS = ELEVATION TOP OF
NEW PILE CAPS.
17'-7"
6 9 11
11'-8" 19'-9" 20'-5" 10'-2 1/2" 10'-2 1/2" 20'-5" 19'-9" 10'-0" 19'-3" 4 1/2" TYPICAL
A
B
C
D
E
F
G
H
X
29'-3" 100'-9" 29'-3"
160'-0"
S202
A
B
C
D
E
F
G
H
1 2 3 4 5 7 8 10 11 12 13 14
19'-9" 13'-8" 11'-8" 11'-11" 11'-8" 13'-8" 19'-9"11'-0"17'-7" 9'-4" 19'-3"
48'-4" 13'-8" 36'-0" 13'-8" 48'-4"
S202
CJ
[534.90]
C J
C J
S201
G B
GB-1 GB-1
G B
PC-2
PC-2
PC-2
PC-2
1'-4" TYP.
Project TitleDrawing Title Date
Project No.
Drawing No.
Dwg. Of
Approved: Associate Director for Operations:
Approved: Director, Medical Center:
Drawn:Building No: Checked:
Location:
Additions:
Revisions:
o n e q u a r t e r i n o t o n e e i g h e f o o t t h r e e e i g h t h s i n c o t o n e h a l f i n o t o n e a n d o l f i n o t o n e i n o t t h r e e q u a r t e r s i n o t t h r e e i n c h e e f o o t
DELLC
JOB No.
Consultants:Date
Bel Air, Maryland 21015-1457
2215 Conowingo Rd, Suite 100 fax 410.836.6611
410.803.0009
ARCHITECTURE
PLANNING
ENGINEERING
95% CD SUBMISSION
FULLY SPRINKLERED
LEBANON RENOVATE
BUILDING 22
KR
07/27/2019
595-15-201
NJC
LEBANON VA
MEDICAL CENTER
LEBANON, PA
& ASSOCIATES, INC.
BURDETTE KOEHLER MURPHY
RICKERT ENGINEERING, INC.
BUILDING COST CONSULTANTS
COST ESTIMATING
12917 - 30TH AVENUE
PLATTSMOUTH, NEBRASKA 68048
402.298.8260 - FAX 402.298.8290
MECHANICAL / ELECTRICAL
CONSULTING ENGINEERING
1416 CLARKVIEW ROAD
BALTIMORE, MARYLAND 21209
410.323.0600 - FAX 410.377.2543
STRUCTURAL ENGINEERING
8813 WALTHAM WOODS ROAD, SUITE 301
BALTIMORE, MARYLAND 21234
410.663.5110 - FAX 410.663.5114
FIRE PROTECTION ENGINEERING
8815 CENTRE PARK DR., SUITE 200
COLUMBIA, MARYLAND 21045
410.750.2246 - FAX 410.750.2588
KOFFEL ASSOCIATES, INC.
WHITMAN, REQUARDT & ASSOCIATES,LLP
CIVIL ENGINEERING
801 SOUTH CAROLINE STREET
BALTIMORE, MD 21231
410.235.3450 - FAX: 410.243.5716
ROBERT L. SEYMOUR & ASSOCIATES, INC.
VERTICAL TRANSPORTATION CONSULTANTS
182 THOMAS JOHNSON DR. SUITE 200
FREDERICK, MARYLAND 21702
301.662.8112 - FAX 301.662.8117
1SOURCE SAFETY AND HEALTH
ASBESTOS ABATEMENT
140 SOUTH VILLAGE AVENUE, SUITE 130
EXTON, PA 19341
610.524.5525 - FAX: 610.524.0565
170801D
DE
PA
RT
M
EN
T
OF
VE
TE
RA
NS
A
FF
AI
RS
FOUNDATION AND FIRST
FLOOR FRAMING PLAN
S101
PLAN NORTH
TRUE NORTH
1ST FLOOR
2ND FLOOR
3RD FLOOR
SECTION
SCALE: 1/4" = 1'-0"
S202
ELEVATOR PIT
546.00
557.00
568.00
542.00
PENTHOUSE ROOF
584.42
TOP OF WALL
580.67
S202
S202
S202
SECTION
SCALE: 1/4" = 1'-0"
S202
FOOTING
AT G-5
FOOTING AT H-5
FOOTING AT H-7
H G
2'-6"
1'-0"
1'-0"
S202
CEILING
CEILING
1"
HSS6X2X1/4 CONTINUOUS
AT TRUSS BEARING (TYP.)
1/2" MINIMUM NON-
SHRINK GROUT
1/2" DIAMETER ANCHOR
BOLT WITH 2" HOOK AT
32" MAXIMUM O/C AND
12" MAXIMUM FROM ENDS.
ROOF BEARING DETAIL
SCALE: 3/4" = 1'-0"
S202
TRUSS BEARING
CORNER DETAIL
SCALE: 3/4" = 1'-0"
S202
PL1/4X2X0'-6"
3/16"
TYP.
L3X2X3/16 LLH
CONTINUOUS
TOP OF ELEVATOR
WALL DETAIL
SCALE: 3/4" = 1'-0"
S202
1/8"X1" STRAP ANCHOR
AT JOIST BEARING. BEND
OVER AND WELD TO THE
TOP OF THE JOIST
#4 AT 4'-0" O/C AND 16"
MAXIMUM FROM CORNERS
AND OPENINGS. FILL CELLS
AT BARS SOLID WITH GROUT
(TYPICAL).
JOIST BEARING
PL1/2X4X0'-8" LONG
ON 1/2" NON-SHRINK
GROUT (TYPICAL)
1'-0"
TYP. JOIST BEARING DETAIL
SCALE: 3/4" = 1'-0"
S202
Project TitleDrawing Title Date
Project No.
Drawing No.
Dwg. Of
Approved: Associate Director for Operations:
Approved: Director, Medical Center:
Drawn:Building No: Checked:
Location:
Additions:
Revisions:
o n e q u a r t e r i n o t o n e e i g h e f o o t t h r e e e i g h t h s i n c o t o n e h a l f i n o t o n e a n d o l f i n o t o n e i n o t t h r e e q u a r t e r s i n o t t h r e e i n c h e e f o o t
DELLC
JOB No.
Consultants:Date
Bel Air, Maryland 21015-1457
2215 Conowingo Rd, Suite 100 fax 410.836.6611
410.803.0009
ARCHITECTURE
PLANNING
ENGINEERING
95% CD SUBMISSION
FULLY SPRINKLERED
LEBANON RENOVATE
BUILDING 22
KR
07/27/2019
595-15-201
NJC
LEBANON VA
MEDICAL CENTER
LEBANON, PA
& ASSOCIATES, INC.
BURDETTE KOEHLER MURPHY
RICKERT ENGINEERING, INC.
BUILDING COST CONSULTANTS
COST ESTIMATING
12917 - 30TH AVENUE
PLATTSMOUTH, NEBRASKA 68048
402.298.8260 - FAX 402.298.8290
MECHANICAL / ELECTRICAL
CONSULTING ENGINEERING
1416 CLARKVIEW ROAD
BALTIMORE, MARYLAND 21209
410.323.0600 - FAX 410.377.2543
STRUCTURAL ENGINEERING
8813 WALTHAM WOODS ROAD, SUITE 301
BALTIMORE, MARYLAND 21234
410.663.5110 - FAX 410.663.5114
FIRE PROTECTION ENGINEERING
8815 CENTRE PARK DR., SUITE 200
COLUMBIA, MARYLAND 21045
410.750.2246 - FAX 410.750.2588
KOFFEL ASSOCIATES, INC.
WHITMAN, REQUARDT & ASSOCIATES,LLP
CIVIL ENGINEERING
801 SOUTH CAROLINE STREET
BALTIMORE, MD 21231
410.235.3450 - FAX: 410.243.5716
ROBERT L. SEYMOUR & ASSOCIATES, INC.
VERTICAL TRANSPORTATION CONSULTANTS
182 THOMAS JOHNSON DR. SUITE 200
FREDERICK, MARYLAND 21702
301.662.8112 - FAX 301.662.8117
1SOURCE SAFETY AND HEALTH
ASBESTOS ABATEMENT
140 SOUTH VILLAGE AVENUE, SUITE 130
EXTON, PA 19341
610.524.5525 - FAX: 610.524.0565
170801D
DE
PA
RT
M
EN
T
OF
VE
TE
RA
NS
A
FF
AI
RS
STRUCTURAL SECTIONS
AND DETAILS
S202
GENERAL NOTES
CODE
A. ALL CONSTRUCTION SHALL CONFORM TO THE PROVISIONS OF THE
INTERNATIONAL BUILDING CODE/2015.
DESIGN LIVE LOADS
A. THE MINIMUM DESIGN SUPERIMPOSED LOADS FOR ALL NEW
FRAMING IS AS FOLLOWS:
LIVE LOADS
FLOORS 100 PSF
ROOF 20 PSF
ROOF SNOW LOAD
Pg 30 PSF
Pf 26 PSF
Ce 1.0
I 1.1
Ct 1.1
WIND
BASIC WIND SPEED (3-SEC GUST) 120 MPH
RISK CATEGORY III
EXPOSURE B
Cpi -.18 AND +.18
EARTHQUAKE
RISK CATEGORY III
SEISMIC IMPORTANCE FACTOR 1.25
SS 0.172
S1 0.058
SITE CLASS D
SDS 0.184
SD1 0.092
SEISMIC DESIGN CATEGORY B
FOUNDATIONS
A. ALL FOOTINGS HAVE BEEN DESIGNED FOR AN ASSUMED SOIL
BEARING PRESSURE OF 2000 PSF. IT SHALL BE THE
CONTRACTORS RESPONSIBILITY TO VERIFY THE ASSUMED SOIL
BEARING PRESSURE. SHOULD THE PRESSURE BE FOUND TO BE
LESS THAN THE ASSUMED, THE CONTRACTOR SHALL IMMEDIATELY
NOTIFY THE ARCHITECT.
B. SELECT FILL SHALL CONFORM TO ASTM D 2487 SOIL
CLASSIFICATION GROUPS GW, GP, GM, SW, SP, AND SM; FREE
OF ROCK OR GRAVEL LARGER THAN 2 INCHES IN ANY DIMENSION,
DEBRIS, WASTE, FROZEN MATERIALS, VEGETATION AND OTHER
DELETERIOUS MATTER.
C. ALL FILL UNDER THE SLAB SHALL BE COMPACTED TO A RELATIVE
DENSITY OF AT LEAST 95 PERCENT OF MAXIMUM DRY DENSITY AS
DETERMINED BY AASHTO T-180. PLACE BACKFILL AND FILL SOIL
MATERIALS IN LAYERS NO MORE THAN 8 INCHES IN LOOSE DEPTH
FOR MATERIALS COMPACTED BY HEAVY COMPACTION EQUIPMENT,
AND NOT MORE THAN 4 INCHES IN LOOSE DEPTH FOR MATERIAL
COMPACTED BY HAND-OPERATED TAMPERS.
D. THE BOTTOM OF ALL EXTERIOR FOOTINGS SHALL BE A MINIMUM OF
2'-6" BELOW FINISH GRADE. FOOTINGS SHALL BEAR 1'-0"
MINIMUM INTO ORIGINAL GRADE. NO FOOTINGS SHALL BEAR ON
EXISTING FILL.
E. DRAINAGE FILL SHALL BE A WASHED, EVENLY GRADED MIXTURE OF
CRUSHED STONE, OR CRUSHED OR UNCRUSHED GRAVEL, WITH 100
PERCENT PASSING A 1-1/2 INCH SIEVE AND NOT MORE THAN 5
PERCENT PASSING A NO. 4 SIEVE.
F. THE CONTRACTOR SHALL EMPLOY AN INDEPENDENT INSPECTION
AGENCY APPROVED BY THE ARCHITECT TO VERIFY THE SOIL
BEARING CAPACITY AND THE COMPACTION OF ALL FILL.
PILES
A. THE CONTRACTOR SHALL PROVIDE MICROPILES IN ACCORDANCE
WITH THE MICROPILE SPECIFICATION SECTION. THE FOLLOWING
ESTIMATES SHALL BE MODIFIED AS REQUIRED TO MEET THE
SPECIFICATION.
B. CASED MICROPILES SHALL CONSIST OF A 5 1/2 INCH DIAMETER
STEEL CASING WITH A 5'-0" GROUTED BOND ZONE IN HARD
LIMESTONE FOR A MINIMUM ALLOWABLE CAPACITY OF 55-KIPS.
CAST IN PLACE CONCRETE
A. ALL CONCRETE WORK SHALL CONFORM TO THE PROVISIONS OF THE
"SPECIFICATION FOR STRUCTURAL CONCRETE FOR BUILDINGS"
ACI 301, AND TO THE "BUILDING CODE REQUIREMENTS FOR
STRUCTURAL CONCRETE" ACI 318.
B. ALL CONCRETE SHALL BE STONE AGGREGATE CONCRETE HAVING A
MINIMUM COMPRESSIVE STRENGTH OF 4,000 PSI AT 28 DAYS
UNLESS NOTED OTHERWISE. EXTERIOR CONCRETE SHALL HAVE
A MINIMUM COMPRESSIVE STRENGTH OF 5,000 PSI.
C. ALL REINFORCING BARS SHALL CONFORM TO ASTM A-615 GRADE
60. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A-185.
D. JOINT FILLER SHALL BE PREFORMED CORK STRIPS CONFORMING TO
ASTM D1752.
MASONRY
A. MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM TO ALL
REQUIREMENTS OF "SPECIFICATIONS FOR MASONRY STRUCTURES
(ACI 530.1-05/ASCE 6-05/TMS 602-05)", PUBLISHED BY THE
AMERICAN CONCRETE INSTITUTE.
B. BLOCK SHALL CONFORM TO ASTM C-90.
C. ALL REINFORCING BARS SHALL CONFORM TO ASTM A-615 GRADE
60.
D. MORTAR SHALL CONFORM TO ASTM C-270, TYPE S. NO CALCIUM
CHLORIDE SHALL BE USED.
E. GROUT SHALL CONFORM TO ASTM C-476. NO CALCIUM CHLORIDE
SHALL BE USED.
F. ALL MASONRY WALLS SHALL BE REINFORCED WITH HORIZONTAL
JOINT REINFORCEMENT SPACED VERTICALLY AT 16" ON CENTER
UNLESS OTHERWISE NOTED. PROVIDE PREFABRICATED CORNER
AND TEE PIECES AT ALL INTERSECTIONS. LAP REINFORCING
8" MINIMUM.
G. BRACE AND SHORE ALL MASONRY WALLS AS REQUIRED UNTIL ROOF
AND FLOOR DECKS HAVE BEEN COMPLETELY INSTALLED.
H. PROVIDE SOLID BLOCK OR FILL WALL SOLID WITH GROUT
DIRECTLY BELOW OR ABOVE ALL CHANGES IN WALL THICKNESS OR
CONSTRUCTION AS REQUIRED TO PROVIDE CONTINUOUS BEARING
FOR ALL FACE SHELLS.
I. LAP ALL REINFORCING BARS 48 BAR DIAMETERS MINIMUM.
J. PROVIDE HORIZONTAL JOINT REINFORCEMENT IN THE BLOCK WITH
WELDED EYES. ANCHOR VENEER TO WELDED EYES WITH W2.8 PINTLE
ANCHORS AT 16" O/C MAXIMUM EACH WAY. MAXIMUM MISALIGNMENT
OF BED JOINTS SHALL BE NO MORE THAN 1 1/4".
STRUCTURAL AND MISCELLANEOUS STEEL
A. ALL STRUCTURAL AND MISCELLANEOUS STEEL SHALL CONFORM TO
THE FIFTEENTH EDITION OF THE AISC "SPECIFICATION FOR THE
DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR
BUILDINGS" AND ALL ITS SUPPLEMENTS, AND TO THE AISC
"CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND
BRIDGES".
B. ALL STRUCTURAL STEEL SHALL CONFORM TO ASTM A-36 UNLESS
NOTED OTHERWISE. ALL WIDE FLANGE SECTIONS SHALL CONFORM
TO ASTM A992.
C. STEEL PIPES SHALL CONFORM TO ASTM A-53 TYPE E OR S GRADE
B.
D. ANCHOR BOLTS SHALL CONFORM TO ASTM F1554.
E. ALL WELDED CONNECTIONS SHALL BE DONE WITH E70XX
ELECTRODES. ALL WELDING SHALL CONFORM TO THE AMERICAN
WELDING SOCIETY STANDARD CODE FOR "WELDING IN BUILDING
CONSTRUCTION".
F. ALL BOLTED CONNECTIONS SHALL USE 3/4" DIAMETER MINIMUM
A-325N HIGH STRENGTH BOLTS. ALL CONNECTIONS SHALL
DEVELOP THE FULL UNIFORM LOAD CAPACITY THE BEAM CAN CARRY
WITH DUE CONSIDERATION TO CONCENTRATED LOADS AT THE ENDS
OF THE MEMBER. NO CONNECTION SHALL BE MADE WITH LESS
THAN TWO BOLTS.
G. ALL STRUCTURAL STEEL EXPOSED TO WEATHER SHALL BE HOT
DIPPED GALVANIZED IN ACCORDANCE WITH ASTM A123.
H. STEEL TO RECEIVE FIREPROOFING SHALL BE UNPAINTED.
I. THE CONTRACTOR SHALL EMPLOY AN APPROVED INDEPENDENT
INSPECTION AGENCY TO INSPECT THE STEEL AT BOTH THE SHOP
AND THE FIELD. INSPECTION SHALL INCLUDE ALL BOLTING
AND WELDING.
J. FIELD VERIFY EXISTING CONDITIONS AND DIMENSIONS PRIOR TO
FABRICATING STEEL.
STEEL JOIST
A. THE FABRICATION AND ERECTION OF THE STEEL JOISTS SHALL
CONFORM TO THE "STANDARD SPECIFICATIONS FOR OPEN WEB
STEEL JOISTS, K SERIES" AND "THE RECOMMENDED CODE OF
STANDARD PRACTICE FOR STEEL JOISTS AND JOIST GIRDERS" AS
PUBLISHED BY THE STEEL JOIST INSTITUTE.
B. ALL STEEL JOISTS SHALL BE SHOP PAINTED WITH AN APPROVED
CORROSION RESISTANT PRIMER. AFTER THE WORK HAS BEEN
ERECTED AND CONNECTED ALL WELDS AND PARTS WHERE THE PAINT
HAS BEEN DAMAGED SHALL BE CLEANED AND PRIMED WITH THE
APPROVED PRIMER.
C. JOIST SHALL BE DESIGNED FOR A NET UPLIFT LOAD OF 35 PSF.
STEEL JOIST
A. THE FABRICATION AND ERECTION OF THE STEEL JOISTS SHALL
CONFORM TO THE "STANDARD SPECIFICATIONS FOR OPEN WEB
STEEL JOISTS, K SERIES" AND "THE RECOMMENDED CODE OF
STANDARD PRACTICE FOR STEEL JOISTS AND JOIST GIRDERS" AS
PUBLISHED BY THE STEEL JOIST INSTITUTE.
B. ALL STEEL JOISTS SHALL BE SHOP PAINTED WITH AN APPROVED
CORROSION RESISTANT PRIMER. AFTER THE WORK HAS BEEN
ERECTED AND CONNECTED ALL WELDS AND PARTS WHERE THE PAINT
HAS BEEN DAMAGED SHALL BE CLEANED AND PRIMED WITH THE
APPROVED PRIMER.
C. JOIST SHALL BE DESIGNED FOR A NET UPLIFT LOAD OF 35 PSF.
LIGHTGAGE STRUCTURAL METAL FRAMING
A. LIGHTGAGE STRUCTURAL METAL FRAMING SHALL CONFORM TO THE
LATEST EDITION OF THE SPECIFICATION FOR THE "DESIGN OF
COLD-FORMED STEEL STRUCTURAL MEMBERS" AS PUBLISHED BY THE
AMERICAN IRON AND STEEL INSTITUTE.
B. COLD-FORMED METAL FRAMING SHALL BE FABRICATED FROM
GALVANIZED-STEEL SHEET CONFORMING TO ASTM A653 G90 WITH
A 33,000 PSI MINIMUM YIELD STRENGTH.
C. LIGHTGAGE MEMBER DESIGNATIONS ARE IN ACCORDANCE WITH THE
SECTIONS DEFINED BY THE STEEL STUD MANUFACTURERS
ASSOCIATION (SSMA).
D. LIGHTGAGE STUDS SHALL HAVE A MINIMUM THICKNESS OF 16 GA
AND A MINIMUM FLANGE OF 1 5/8".
E. SHOP DRAWINGS COMPLETE WITH MATERIAL DATA, ERECTION
PLANS AND ALL CONNECTION DETAILS SHALL BE SUBMITTED FOR
REVIEW.
F. THE TRUSSES SHALL BE DESIGNED FOR THE FOLLOWING LOADS:
TOP CHORD
DEAD LOAD 10 PSF
LIVE LOAD 30 PSF
BOTTOM CHORD
DEAD LOAD 10 PSF
LIVE LOAD 20 PSF
THE 20 PSF BOTTOM CHORD LIVE LOAD SHALL BE APPLIED
WHEREVER TWO OR MORE ADJACENT TRUSSES WITH THE SAME WEB
CONFIGURATION ARE CAPABLE OF CONTAINING A RECTANGLE 42
INCHES HIGH BY 2 FEET WIDE OR GREATER, LOCATED WITHIN
THE PLANE OF THE TRUSS.
THE BOTTOM CHORD LIVE LOAD SHALL BE 10 PSF MINIMUM.
SEE THE SUPERIMPOSED LOADS LISTED ABOVE FOR WIND AND
SNOW LOADS.
METAL FORM DECK
A. METAL DECK SHALL BE FABRICATED FROM GALVANIZED-STEEL
SHEET CONFORMING TO ASTM A653 G60 WITH A MINIMUM YIELD
STRENGTH OF 33 KSI.
B. METAL DECK SHALL HAVE THE FOLLOWING MINIMUM PROPERTIES:
t = 0.0239 in
I = 0.019 in^4/ft
Sp = 0.057 in^3/ft
Sn = 0.057 in^3/ft
WOOD FRAMING
A. PLYWOOD SHALL CONFORM TO THE PLYWOOD DESIGN SPECIFICATIONS
AND THE PERFORMANCE STANDARDS AND POLICIES FOR STRUCTURAL-
USE PANELS PUBLISHED BY THE AMERICAN PLYWOOD ASSOCIATION.
B. PROVIDE PLY CLIPS AT CENTERLINE OF PLYWOOD SPAN AT ALL
EDGES PARALLEL TO SPAN WHICH ARE NOT TONGUE AND GROOVE.
C. ROOF DECK SHALL BE FIRE RETARDANT APA RATED EXPOSURE 1,
3/4" 32/16 PLYWOOD.
D. PLYWOOD ROOF SHEATHING SHALL BE ANCHORED TO THE TOP CHORD
OF THE STEEL TRUSSES WITH 1 1/4" LONG TYPE S OR S-12 STEEL
SCREWS SPACED 6" ON CENTER AT THE PERIMETER OF EACH PANEL
AND AT 12" ON CENTER AT INTERMEDIATE SUPPORTS.
Project TitleDrawing Title Date
Project No.
Drawing No.
Dwg. Of
Approved: Associate Director for Operations:
Approved: Director, Medical Center:
Drawn:Building No: Checked:
Location:
Additions:
Revisions:
o n e q u a r t e r i n o t o n e e i g h e f o o t t h r e e e i g h t h s i n c o t o n e h a l f i n o t o n e a n d o l f i n o t o n e i n o t t h r e e q u a r t e r s i n o t t h r e e i n c h e e f o o t
DELLC
JOB No.
Consultants:Date
Bel Air, Maryland 21015-1457
2215 Conowingo Rd, Suite 100 fax 410.836.6611
410.803.0009
ARCHITECTURE
PLANNING
ENGINEERING
95% CD SUBMISSION
FULLY SPRINKLERED
LEBANON RENOVATE
BUILDING 22
KR
07/27/2019
595-15-201
NJC
LEBANON VA
MEDICAL CENTER
LEBANON, PA
& ASSOCIATES, INC.
BURDETTE KOEHLER MURPHY
RICKERT ENGINEERING, INC.
BUILDING COST CONSULTANTS
COST ESTIMATING
12917 - 30TH AVENUE
PLATTSMOUTH, NEBRASKA 68048
402.298.8260 - FAX 402.298.8290
MECHANICAL / ELECTRICAL
CONSULTING ENGINEERING
1416 CLARKVIEW ROAD
BALTIMORE, MARYLAND 21209
410.323.0600 - FAX 410.377.2543
STRUCTURAL ENGINEERING
8813 WALTHAM WOODS ROAD, SUITE 301
BALTIMORE, MARYLAND 21234
410.663.5110 - FAX 410.663.5114
FIRE PROTECTION ENGINEERING
8815 CENTRE PARK DR., SUITE 200
COLUMBIA, MARYLAND 21045
410.750.2246 - FAX 410.750.2588
KOFFEL ASSOCIATES, INC.
WHITMAN, REQUARDT & ASSOCIATES,LLP
CIVIL ENGINEERING
801 SOUTH CAROLINE STREET
BALTIMORE, MD 21231
410.235.3450 - FAX: 410.243.5716
ROBERT L. SEYMOUR & ASSOCIATES, INC.
VERTICAL TRANSPORTATION CONSULTANTS
182 THOMAS JOHNSON DR. SUITE 200
FREDERICK, MARYLAND 21702
301.662.8112 - FAX 301.662.8117
1SOURCE SAFETY AND HEALTH
ASBESTOS ABATEMENT
140 SOUTH VILLAGE AVENUE, SUITE 130
EXTON, PA 19341
610.524.5525 - FAX: 610.524.0565
170801D
DE
PA
RT
M
EN
T
OF
VE
TE
RA
NS
A
FF
AI
RS
GENERAL NOTES
S401
| Boring Location Plan |
| Sheets and Views |
| 18232 - VA Lebanon-1 |
| B-1 Boring Log |
| Rock Core Photos |
| VA Lebanon B22 L-2 |
| Sheets and Views |
| 42108000C1-04-Layout1 |
| 42108000C1-01-Layout1 |
| 42108000C1-02-Layout1 |
| 42108000C1-03-Layout1 |
| VA Lebanon B22 S101 |
| Sheets and Views |
| 17037 VA Lebanon B22-Border S101 |
| VA Lebanon B22 S202 |
| Sheets and Views |
| 17037 VA Lebanon B22-Border S202 |
| VA Lebanon B22 S401 |
| Sheets and Views |
| 17037 VA Lebanon B22-Border S401 |
| ATC Hazards by Location |
| Geotech Memo Report_July 2019(word) |
| B-1 Boring Log |
File details come from the government source that posted it. Updated .