Abatement Ward 9c Report.pdf
PDF 2 MB Posted
- Attached to
- Z1DA--528-18-109 WARD 9C RENOVATIONS
- Solicitation number
- 36C24222B0069
About this file
This asbestos survey report documents asbestos-containing materials found in Ward 9C of the Buffalo Veterans Affairs Medical Center. Homogeneous materials tested from floor tiles and associated mastic in Room 900C2 and 900C4 were found to not contain asbestos. The related federal contract opportunity is for renovations to Ward 9C at the Buffalo VAMC. The solicitation is seeking offers for asbestos abatement and renovations, with the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2 listed as the contracting agency.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| AA-102.pdf | ||
| A-406.pdf | ||
| AD-102.pdf | ||
| A-604.pdf | ||
| A-405.pdf | ||
| AA-101.pdf | ||
| A-404.pdf | ||
| AD-100.pdf | ||
| AA-100.pdf | ||
| A-109.pdf | ||
| 117300.pdf | ||
| A-108.pdf | ||
| 36C24222B0069 0005.docx | DOCX document | |
| 36C24222B0069 0004.docx | DOCX document | |
| 36C24222B0069 0003.docx | DOCX document | |
| 36C24222B0069 0002.docx | DOCX document | |
| 36C24222B0069 0001.docx | DOCX document | |
| 528-18-109 Pre Bid Attendance.pdf | ||
| SPECS 3.pdf | ||
| 36C24222B0069_1.docx | DOCX document | |
| SPECS 1.pdf | ||
| WAGE RATE.pdf | ||
| LIMITATION ON SUBCONTRACTING.docx | DOCX document | |
| SPECS 2.pdf | ||
| 528-18-109_9C DRAWINGS.pdf | ||
| FAR 52.225-2 Buy American Certification.docx | DOCX document |
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2.0 – ASBESTOS-CONTAINING MATERIALS
H:\2012\12108 VAMC Bflo., Remodel Ward 9C\10. Env Data and Env Assessment\10.f. Asbestos-Lead-PCB Assessment\VAMC- Ward9C_ACM-LBP-SurveyReport.docx
2.0 ASBESTOS-CONTAINING MATERIALS
This section includes information on all suspect ACM sampled. This section contains the following: Homogeneous Materials List containing the homogeneous materials identified, their corresponding sample numbers and whether or not they are ACM, as well as drawings identifying the approximate locations of asbestos bulk samples.
For each functional space, all ACM that was identified within that space has been inspected in order to determine its approximate quantity, condition, and whether it is friable or non-friable. Where possible, Watts visually inspected the identified ACM to assess its condition.
The condition of the ACM was classified as good, fair, or poor. The requirement for each designation is as follows:
Good Material with no visible damage or deterioration or showing very limited damage or deterioration.
Fair The surface of the material is crumbling, blistering, water-stained, gouged, punctured, or otherwise damaged with the damage covering less than one tenth of the surface if the damage is evenly distributed or up to 25% of the material if the damage is localized.
Poor The surface of the material is crumbling, blistering, water-stained, gouged, punctured, or otherwise damaged with the damage covering more than one tenth of the surface if the damage is evenly distributed, or more than 25% of the material if the damage is localized. Material with large areas hanging from the substrate, delaminated, heavily gouged, crushed, etc.
Results Type ACM NA – Not Analyzed M – Miscellaneous Y – Yes NAD – No Asbestos Detected T – Thermal System Insulation N – No S – Surfacing
H:\2012\12108 VAMC Bflo., Remodel Ward 9C\10. Env Data and Env Assessment\10.f. Asbestos-Lead-PCB Assessment\VAMC-
HOMOGENEOUS MATERIALS LIST
Ward 9C VAMC Buffalo
Buffalo, New York
Material Description Sample Location Type Sample Number
Results (% Asbestos) ACM
PLM TEM Y/N
12” x 12” Light Grey with Grey Streaks Floor
Tile
Room 900C2 Room 900C4
M 12108-01 12108-02
NAD
NAD
NAD
NAD
N
Black Mastic Associated with Light Grey Floor
Tile
Room 900C2
Room 900C4 M
12108-03
12108-04
<1% Chrysotile
<1%
Trace
N
12” x 12” White with Large and Small Streaks
Floor Tile
Room 907C
Room 915C
12108-05
12108-06
4.4% Chrysotile
NA/PS
NA
Y
Black Mastic Associated with Light Grey Floor
Room 907C
12108-07
12108-08
NAD
<0.25%
N
6” Green Covebase Room 907C Room 916C
M 12108-09 12108-10
NAD
NAD
NAD
NAD
N
Cream Mastic Associated With 6” Green Covebase
Room 907C Room 916C
M 12108-11 12108-12
NAD
NAD
NAD
NAD
N
12” x 12” Light Green with Olive Streaks Floor
Tile
Room 933C1 Room 935C
M 12108-13 12108-14
NAD
NAD
NAD
NAD
N
Black Mastic Associated with Light Green Floor
Room 933C1
Room 935C
12108-15
12108-16
1.1% Chrysotile
Grey Sink Undercoat Room 933C1 Room 933C1
M 12108-17 12108-18
NAD
NAD
NAD
NAD
N
Pink Sink Undercoat Room 910C1
12108-19
12108-20
10.8% Chrysotile
Grout Associated With 4” x 4” Ceramic Wall
Tile
Room 910C1 Room 916C Room 910C
Room 934C Restroom
M
12108-21 12108-22 12108-69 12108-70
NAD
NAD
NAD
NAD
NA
NA
NA
NA
N
Tan Adhesive Associated With
Ceramic Tile
Room 910C1 Room 910C
M 12108-23 12108-24
NAD
NAD
NAD
N
H:\2012\12108 VAMC Bflo., Remodel Ward 9C\10. Env Data and Env Assessment\10.f. Asbestos-Lead-PCB Assessment\VAMC-
Number
Results (% Asbestos) ACM
PLM TEM Y/N
2’x4’ Ceiling Tile with Long Fissures and
Pinholes
Room 900C2 Room 900C3
M 12108-25 12108-26
NAD
NAD
NAD
NAD
N
Grey Mastic on Duct Work
Room 900C2 M 12108-27 12108-28
NAD
NAD
NAD
NAD
N
Brown Cork Pipe Insulation
Room 900C4 M
12108- 29L1
12108- 30L1
Black Coating on Cork Pipe Insulation
Room 900C4 M
12108- 29L2
12108- 30L2
Red-Brown Mastic on Cork Pipe Insulation
Room 900C4 M 12108-31
12108-32
5.2% Chrysotile
Tan Duct Mastic Room 900C3 Room 900C3
12108-33 12108-34
NAD
NAD
NAD
NAD
N
2’x4’ Ceiling Tile with Long Fissures, Punctures and Pinholes
Room 900C3 Room 900C4
M 12108-35 12108-36
NAD
NAD
NAD
NAD
N
Wall Plaster Skim Coat
Room 900C3 Room 900C4 Room 900C2 Room 900C1
S
12124-37 12108-38 12108-39 12108-40 12108-41
NAD
NAD
NAD
NAD
NAD
NA
NA
NA
NA
NA
N
Wall Plaster Base Coat
Room 900C3 Room 900C4 Room 900C2 Room 900C1
S
12108-42 12018-43 12108-44 12108-45 12108-46
NAD
NAD
NAD
NAD
NAD
NA
NA
NA
NA
NA
N
Troweled Plaster on Duct Work
Room 900C2 M 12108-47 12108-48
NAD
NAD
NA
NA
N
Black Caulk at Windows Room 908C
Room 900C4 M
12108-49 12108-50
NAD
NAD
NAD
NAD
N
White Caulk at Sinks Room 934C Restroom M 12108-51 12108-52
NAD
NAD
NAD
H:\2012\12108 VAMC Bflo., Remodel Ward 9C\10. Env Data and Env Assessment\10.f. Asbestos-Lead-PCB Assessment\VAMC-
Number
Results (% Asbestos) ACM
PLM TEM Y/N
Grey Caulk at Exhaust Fan
Room 929C Room 921C
M 12108-53 12108-54
NAD
NAD
NAD
NAD
N
Drywall Room 933C Room 924C
M 12108-55 12108-56
NAD
NAD
NA
NA
N
Joint Compound Associated With Drywall
Room 933C Room 924C
M 12108-57 12108-58
NAD
NAD
NA
NA
N
Maroon Terrazzo Shower Basin
Room 920C M 12108-59 12108-60
NAD
NAD
NA
NA
N
Ceramic Floor Tile Grout
Room 919C M 12108-61 12108-62
NAD
NAD
NA
NA
N
Ceramic Floor Tile Mudset
Room 919C M 12108-63 12108-64
NAD
NAD
NA
NA
N
Ceramic Floor Tile Mastic Joints
Room 919C M 12108-65 12108-66
NAD
NAD
NAD
NAD
N
Yellow Carpet Mastic Room 904C M 12108-67 12108-68
NAD
NAD
NAD
NAD
N
12” x 12” Ceiling Tile Room 837C M 12108-71 12108-72
NAD
NAD
NAD
NAD
N
Brown Mastic Associated With 12” x
12” Ceiling Tile Room 837C M
12108-73 12108-74
NAD
NAD
NAD
H:\2012\12108 VAMC Bflo., Remodel Ward 9C\10. Env Data and Env Assessment\10.f. Asbestos-Lead-PCB Assessment\VAMC-
IDENTIFIED ASBESTOS-CONTAINING MATERIALS SUMMARY
Room Identified ACM Approximate
Quantity Condition
Friable/ Non-Friable
Eighth Floor
Ward 8C Pipe Insulation on Horizontal and Vertical
Pipes Above Ceiling (assumed asbestos-containing)
200 lf Good to
Fair Friable
Ninth Floor
Ward 9C Pipe Insulation on Horizontal and Vertical Pipes in Vertical Chases and Above Ceiling (assumed asbestos-containing)
1,300 lf Good to
Fair Friable
Room 900C4 Red-Brown Mastic on Cork Pipe Insulation Flexible Black Insulation Material Behind
Radiators
15 lf 6 sf
Good
Non-Friable
Room 900C2 Flexible Black Insulation Material Behind
Radiators 6 sf Good Non-Friable
Room 907C
12” x 12” White with Large and Small Streaks Floor Tile
Flexible Black Insulation Material Behind Radiators
166 sf
Room 908C
12” x 12” White with Large and Small Streaks Floor Tile
Flexible Black Insulation Material Behind
87 sf
Room 908C1
Black Mastic Associated with Light Green Floor Tile
Flexible Black Insulation Material Behind
120 sf
Radiators 6 sf Good Non-Friable
Room 910C1 Pink Sink Undercoat
Flexible Black Insulation Material Behind Radiators
1 sink
Friable
Room 911C
Floor Tile
Flexible Black Insulation Material Behind
275 sf
12 sf
H:\2012\12108 VAMC Bflo., Remodel Ward 9C\10. Env Data and Env Assessment\10.f. Asbestos-Lead-PCB Assessment\VAMC-
Quantity Condition
Friable/ Non-Friable
Room 911C1
12” x 12” White with Large and Small Streaks Floor Tile
Flexible Black Insulation Material Behind
28 sf
Room 912C
Floor Tile
Flexible Black Insulation Material Behind
196 sf
Room 913C
Floor Tile
Flexible Black Insulation Material Behind
190 sf
Room 913C1
Floor Tile 30 sf Good Non-Friable
Room 914C
12” x 12” White with Large and Small Streaks Floor Tile
Flexible Black Insulation Material Behind
197 sf
Room 914C1
Floor Tile
Flexible Black Insulation Material Behind
230 sf
Floor Tile
Flexible Black Insulation Material Behind
187 sf
12 sf
Room 915C1
Floor Tile 32 sf Good Non-Friable
Room 916C
12” x 12” White with Large and Small Streaks Floor Tile
Flexible Black Insulation Material Behind
200 sf
H:\2012\12108 VAMC Bflo., Remodel Ward 9C\10. Env Data and Env Assessment\10.f. Asbestos-Lead-PCB Assessment\VAMC-
Quantity Condition
Friable/ Non-Friable
Room 917C
12” x 12” White with Large and Small Streaks Floor Tile
Flexible Black Insulation Material Behind
195 sf
Room 918C
Radiators 6 sf Good Non-Friable
Room 920C
12” x 12” White with Large and Small Streaks Floor Tile
Flexible Black Insulation Material Behind
132 sf
Room 921C
Floor Tile
Flexible Black Insulation Material Behind
122 sf
Room 922C
Floor Tile
Flexible Black Insulation Material Behind
142 sf
Room 923C
Floor Tile
Flexible Black Insulation Material Behind
123 sf
Room 924C
Floor Tile
Flexible Black Insulation Material Behind
214 sf
Room 925C
Floor Tile
Flexible Black Insulation Material Behind
122 sf
Room 926C
Floor Tile
Flexible Black Insulation Material Behind
H:\2012\12108 VAMC Bflo., Remodel Ward 9C\10. Env Data and Env Assessment\10.f. Asbestos-Lead-PCB Assessment\VAMC-
Quantity Condition
Friable/ Non-Friable
Room 927C
12” x 12” White with Large and Small Streaks Floor Tile
Flexible Black Insulation Material Behind
134 sf
Room 928C
Floor Tile
Flexible Black Insulation Material Behind
133 sf
Room 929C
Floor Tile
Flexible Black Insulation Material Behind
131 sf
Room 930C
Floor Tile
Flexible Black Insulation Material Behind
112 sf
Room 931C
Floor Tile
Flexible Black Insulation Material Behind
Room 933C
Tile
Flexible Black Insulation Material Behind
282 sf
18 sf
Room 933C1
Tile 42 sf Good Non-Friable
Room 934C
Black Mastic Associated with Light Green Floor Tile
Flexible Black Insulation Material Behind
154 sf
Room 935C
Tile
Flexible Black Insulation Material Behind
130 sf
H:\2012\12108 VAMC Bflo., Remodel Ward 9C\10. Env Data and Env Assessment\10.f. Asbestos-Lead-PCB Assessment\VAMC-
Quantity Condition
Friable/ Non-Friable
Room 936C
Black Mastic Associated with Light Green Floor Tile
Flexible Black Insulation Material Behind
200 sf
Notes:
lf – linear feet sf – square feet
2.1 – LABORATORY REPORTS
2.2 – CHAIN-OF-CUSTODY FORMS
H:\2012\12108 VAMC Bflo., Remodel Ward 9C\10. Env Data and Env Assessment\10.f. Asbestos-Lead-PCB Assessment\VAMC-
BULK SAMPLE CHAIN-OF-CUSTODY FORM
The purpose of the chain-of-custody form is to reduce the possibility of misidentifying individual samples, to help trace any samples that may be lost, and to provide a record certifying that the samples were delivered to and received by the analytical laboratory.
An important feature of this form is the signature section at the bottom, identifying all persons who handled the samples.
2.3 – ASBESTOS SAMPLE LOCATION DRAWING
924C
926C
916C
910C911CS 7912C
914C1
933C1
908C1
908C
907C
934C
935C
936C
904C
905C
S 8
S 9
933C
923C
922C
921C
920C
928C
929C
930C
931C
918C
913C914C
919C
915C
915C1
913C1
914C2
917C
917D
910C1
911C1
923C1
922C1
921C1
927C1
927C
925C
900C3
900C2
900C4
900C1
WATTS
ARCHITECTURE &
ENGINEERING
95 Perry Street, Suite 300
Buffalo, New York 14203
(716) 206-5100 | (716) 206-5199 Fax
WATTS
ARCHITECTURE &
ENGINEERING
95 Perry Street, Suite 300
Buffalo, New York 14203
(716) 206-5100 | (716) 206-5199 Fax
File details come from the government source that posted it. Updated .