Z1DA--528-18-109 WARD 9C RENOVATIONS
Solicitation number
36C24222B0069
Issued by

About this file

This reflected ceiling plan drawing and related federal contract opportunity provide details for a 9th floor renovation at the Buffalo VA Medical Center. Key specifications include installing 2x2 acoustic ceiling tiles and gypsum ceilings throughout various rooms in Area C, coordinating locations for mechanical systems, lighting fixtures, plumbing fixtures, fire sprinklers, and ceiling-mounted patient lift tracks. The federal contract opportunity is a solicitation issued by the Department of Veterans Affairs for project number 528-18-109 to complete the ward 9C renovations at the Buffalo VAMC for a fully sprinklered building. The solicitation number is 36C24222B0069 and offers an opportunity to provide services for the ceiling installation and related construction work as specified in the reflected ceiling plan drawings.

View the file

Other files

File Type Posted
AA-102.pdf PDF
AD-102.pdf PDF
A-604.pdf PDF
A-405.pdf PDF
AA-101.pdf PDF
A-404.pdf PDF
AD-100.pdf PDF
AA-100.pdf PDF
A-109.pdf PDF
117300.pdf PDF
A-108.pdf PDF
36C24222B0069 0005.docx DOCX document
36C24222B0069 0004.docx DOCX document
Abatement Ward 9c Report.pdf PDF
36C24222B0069 0003.docx DOCX document
36C24222B0069 0002.docx DOCX document
36C24222B0069 0001.docx DOCX document
528-18-109 Pre Bid Attendance.pdf PDF
SPECS 3.pdf PDF
36C24222B0069_1.docx DOCX document
SPECS 1.pdf PDF
WAGE RATE.pdf PDF
LIMITATION ON SUBCONTRACTING.docx DOCX document
SPECS 2.pdf PDF
528-18-109_9C DRAWINGS.pdf PDF
FAR 52.225-2 Buy American Certification.docx DOCX document
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

S

S

OS

C B A

DD

C.1

5.1

CC

BB

AA

AREA 'A'

AREA 'C'

MATCHLINE

A R

E A

B

A R

E A

C

M

A T

C H

L

IN

E

AREA 'A'

AREA 'B'

STAIR

NO WORK

2' -6

/4

A-504

LARGE

EQUIP.

RM.

908C

PATIENT

ROOM

904C

CORRIDOR

900C

HSKPG

934C

DATA RM

933C

PATIENT

ROOM

932C

TLT. RM.

932-1C

TLT. RM.

931-1C

PATIENT

ROOM

931C

PATIENT

ROOM

905C

TLT. RM.

905-1C

TLT. RM.

904-1C

CLEAN

UTILITY

906C

SOILED

UTILITY

907C

CLEAN

LINEN

929C

NURSE

MANAGER

930C

N.STN.

930C-1

7'-6"

7'-6"

8'-0"

7'-6"

7'-6"

7'-6"

7'-6"

7'-6"

8'-11"

8'-11"

8'-11"

8'-11"

8'-11"

8'-11"

8'-11"

8'-11"

9'-0"

8'-0"

8'-0"

7'-6"

7'-8"

7'-6"

B

DD

C.1

5.1

CC

BB

AA

B

DD

C.1

5.1

CC

BB

AA

C B A

DD

C.1

5.1

CC

BB

AA

9'-0"

3'

/8

10' - 10 7/8"

4'

1/

8"

4'

1/

8"

4'

1/

8"

4'

1/

8"

3'

/8

3'

/8

/8

3'

/8

7' - 6"

7' - 0"

9B

9B

GENERAL CEILING NOTES - 9C

A. CONTRACTOR TO VERIFY DIMENSIONS IN FIELD PRIOR TO THE START OF CONSTRUCTION.

B. REFER TO MECHANICAL, ELECTRICAL AND FIRE PROTECTION WORK FOR CEILING MOUNTED DEVICES AND

LOCATIONS. SHOWN HERE FOR COORDINATION ONLY.

C. PRIME AND PAINT EXPOSED SURFACES OF GYPSUM SOFFIT / CEILING CONSTRUCTION - REFER TO ROOM

FINISH SCHEDULE.

D. PROVIDE BLOCKING FOR ANCHORING OF CEILING SUSPENSION SYSTEMS AS REQUIRED.

E. COORDINATE FINAL CEILING HEIGHTS AND MINIMUM REQUIRED CLEARANCES WITH WORK TO BE CONCEALED

ABOVE CEILING.

F. CONTRACTOR TO SUBMIT COORDINATION SHOP DRAWINGS FORE REVIEW AND RECEIVE APPROVAL PRIOR TO COMMENCEMENT OF WORK. COORDINATION DRAWINGS TO SHOW PLAN LOCATIONS AND ELEVATIONS OF HVAC, ELECTRICAL, PLUMBING, FIRE PROTECTION, MEDICAL GAS, STRUCTURAL, AND CEILINGS SYSTEMS.

G. REFER TO ROOM FINISH SCHEDULE ON SHEET A-603 FOR DETAILS REGARDING CEILING FINISHES.

H. EXISTING TO REMAIN TILE AND GRID AT ENTRY DAMAGED BY CONTRACTOR SHALL BE REPLACED IN-KIND.

I. CONTRACTOR IS EXPECTED TO BECOME FAMILIAR WITH MECHANICAL, ELECTRICAL, PLUMBING EQUIPMENT, DEVICE LOCATIONS, AND LAYOUTS PRIOR TO THE START OF THE CEILING INSTALLATION.

J. CONTRACTOR SHALL EXERT CARE WHEN DRILLING INTO SLAB ABOVE AS EXISTING ELECTRICAL CONDUIT ARE

BURIED IN THE SLAB ABOVE AND LOCATIONS ARE UNKNOWN.

K. CONTACT COR PROMPTLY IF REINFORCING BAR IS DAMAGED WHILE DRILLING INTO SLAB ABOVE.

L. IN PATIENT ROOMS, CENTER LIGHT FIXTURE ABOVE PLANNED BED LOCATION. CONFORM CEILING GRID TO

ACCOMMODATE.

M. ANCHORING OF ITEMS TO THE UNDERSIDE OF BEAMS IS STRICTLY PROHIBITED, INCLUDING CONDUIT, PLUMBING, DUCTWORK, TRACK, AND OTHER SIMILAR MATERIALS/SYSTEMS.

24" x 24" ACOUSTIC CEILING TILE

GYPSUM SOFFIT TO BE PAINTED

LED LIGHT FIXTURE.

COORDINATE WITH LIGHTING

DRAWINGS

HVAC. COORDINATE WITH HVAC

DRAWINGS

TOILET ROOM VENT

LIGHT FIXTURES. COORDINATE

WITH ELECTRICAL DRAWINGS

FIRE PROTECTION SPRINKLER

SYSTEM. COORDINATE WITH FIRE

PROTECTION DRAWINGS

EMERGENCY EXIT SIGN.

COORDINATE WITH LIGHTING

DRAWINGS

MECHANICAL VALANCE UNIT,

REFER TO HVAC DRAWINGS

WALL MOUNTED MECHANICAL

DIFFUSER, COORDINATE WITH

HVAC DRAWINGS

PATIENT LIFT RAIL

CUBICLE CURTAIN TRACK

X'-X" CEILING HEIGHT

REFLECTED CEILING PLAN LEGEND

NOTE: NOT ALL SYMBOLS MAY

BE USED IN EACH DRAWING

1 AT-1 2x2 ACOUSTIC CEILING TILE

2 AT-2 2x2 ACOUSTIC CEILING TILE @ TOILET ROOMS

3 GYPSUM CEILING - P-1

CEILING TYPE LEGEND

DRAWING NOTE

1. PATIENT LIFTS ARE INCLUDED IN THE SCOPE OF WORK, COORDINATE LOCATION OF CEILING MOUNTED TRACKS WITH ALL TRADES. PATIENT ROOMS 904C AND 905C ARE TO BE PROVIDED MOBILE FLOOR LIFTS AS CEILING MOUNTED LIFTS ARE NOT POSSIBLE DUE TO EXISTING ABOVE CEILING CONDITIONS; MOBILE LIFTS ARE TO MEET WEIGHT REQUIREMENTS LISTED IN SPECIFICATION SECTION 117300 – CEILING MOUNTED PATIENT LIFT SYSTEMS

2. PNEUMATIC TUBE SYSTEM IS N.I.C. CONTRACTOR SHALL COORDINATE FOR INSTALLATION BY OTHERS DURING

CONTRACT PERIOD. REFER TO COR FOR SCHEDULING.

AREA 'C'

KEY PLAN

WING 9C

95 Perry Street, Suite 300 Buffalo, NY 14203

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ARCHITECT: WARD 9C RENOVATIONS

3495 BAILEY AVENUE BUFFALO, NY 14215

528-18-109

528-18-109-

B

IM

/B u ff a lo

V A

W a rd

C

R e d e s ig n

C o n s tr u c ti o n /1

A R

C H

.r v t

/2 /2

:0

:3

A

M

A-406

9TH FLOOR - PARTIAL CEILING

PLAN - AREA 'C'

February 25, 2022 RAS AHE

1/4" = 1'-0"1

9TH FLOOR - AREA 'C'

0' 2' 4' 8' 16'

1/4" = 1'-0"

NORTH

Revisions: Date:

BID ADDENDUM #1 2022/10/28

Sheets
A-108 - 7C REFLECTED CEILING PLAN
A-109 - 8C REFLECTED CEILING PLAN
A-404 - 9TH FLOOR - PARTIAL CEILING PLAN - AREA 'A'
A-405 - 9TH FLOOR - PARTIAL CEILING PLAN - AREA 'B'
A-406 - 9TH FLOOR - PARTIAL CEILING PLAN - AREA 'C'
A-604 - EQUIPMENT SCHEDULE
AD-100 - 7TH FLOOR DEMOLITION CEILING PLAN
AD-102 - 8TH FLOOR DEMOLITION CEILING PLAN

File details come from the government source that posted it. Updated .