This one-line diagram depicts the electrical distribution system for the Mental Health Outpatient Renovation B5 Project 52A5-19-305 at the Brockton VA Medical Center. It shows the location of existing switchboards, panels, transformers and loads, as well as new equipment to be installed including a dry type transformer and distribution panel. The project will establish infrastructure to support phased renovations, with Phase 0 work coordinating demolition and new construction. Loads removed from the existing switchboard will be reconnected to the new low voltage panel. Additional details include routing a new feeder to the chiller and providing breakers for mechanical equipment. A 400A circuit will serve a temporary building during construction.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DP, 277/480V, 600A, 3Ø, 4W
400A 3P
100A 3P
600A 3P
200A 3P
50A 3P
TO
PUMP HWP-1
50A 3P
TO
PUMP HWP-2
225A 3P
30A 3P
TO
STREET LIGHTS
40A 3P
TO
AHU #1
200A 3P
350A 3P
DP-LV, 120/208V, 800A, 3Ø, 4W
22,000 AIC
225A 3P
150A 3P
800A 3P
TO
5N2081
225A 3P
225A 3P
50A 3P
TO
EXISTING LOAD
100A 3P
TO
CERAMICS
100A 3P
30A 3P
TO
COMPRESSOR
ROOM PUMP
225A 3P
225A 3P
TO
CERAMICS
400A 3P
TO
EXISTING LOAD
TO
EXISTING LOAD
TO
EXISTING LOAD
TO
EXISTING LOAD
400A 3P
L1C
SECTION 1
120/208V
225A
MCB
NEW 'XFMR-1'
225 KVA
480Δ-208Y/120V
L2C
SECTION 1
120/208V
225A
MCB
L1C
SECTION 2
120/208V
225A
MLO
L2C
SECTION 2
120/208V
225A
MLO
L1A
SECTION 1
120/208V
225A
MCB
L2A 120/208V
200A
MCB
L1B
SECTION 1
120/208V
225A
MCB
L2B
SECTION 1
120/208V
225A
MCB
L1B
SECTION 2
120/208V
225A
MLO
L2B
SECTION 2
120/208V
225A
MLO
L1A
SECTION 2
120/208V
225A
MLO
REFER TO DRY TYPE TRANSFORMER
SCHEDULE FOR FEEDER INFORMATION
(TYPICAL)
EXISTING UTILITY TRANSFORMER
MDP, 277/480V, 800A, 3Ø, 4W
600A 3P
300A 3P
800A 3P
TO
ATS-EQ
100A 3P
--A 3P
PREPARED
SPACE
TO
ATS-LS
EN
L
ATS-N
225A
EXISTING 200A FEEDER TO EMERGENCY
SWITCHBOARD IN BLDG. 70
SPARE TO
EML BUILDING
TO
CHILLER
SPARE
60A 3P
60A 3P
TO
PUMP CWP-1
TO
PUMP CWP-2
3 3 3
44444
TO
TEMP. BUILDING
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% [FINAL] BID
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
0" 1/4" 1/2" 1" 2" 3"
C :\U se rs
\m pe nt el la \D oc um en ts
\1
_B ro ck to n_
B0 5_
El ec
_R
_m pe nt el la .rv t 9/
/2
:4
7:
A M
EP652
NEW WORK ONE LINE DIAGRAM BUILDING 5 OUTPATIENT MENTAL
HEALTH RENOVATION
BROCKTON, MA
523A5-19-305
5-14-21 MP MP
NONE
NEW WORK ONE-LINE DIAGRAM E10
NOTES:
KEYED NOTES:
EXISTING LOADS MAINTAINED FROM DEMOLITION OF EXISTING
SWITCHBOARD SHALL BE EXTENDED, AS NECESSARY, AND
RECONNECTED TO NEW DISTRIBUTION PANEL 'DP-LV'.
PROVIDE NEW FEEDER TO CHILLER. UTILIZE EXISTING CONDUIT
FROM PANEL 'DP' OUT TO EXISTING CHILLER PAD AND EXTEND AS
NECESSARY TO NEW CHILLER LOCATION.
PROVIDE NEW CIRCUIT BREAKERS IN EXISTING DISTRIBUTION
PANEL.
REFER TO MECHANICAL EQUIPMENT SCHEDULE ON DRAWING E-601
FOR FEEDER INFORMATION.
UTILIZE EXISTING 400A-3P CIRCUIT BREAKER IN DISTRIBUTION
PANEL 'DP' AND PROVIDE NEW 400A FEEDER TO SERVE TEMPORARY
BUILDING. CONTRACTOR SHALL COORDINATE ROUTING OF FEEDER
TO OUTDOOR LOCATION OF THE TEMPORARY BUILDING AND THE
FINAL LOCATION FOR TERMINATION POINT OF THE FEEDER IN FIELD
PRIOR TO INSTALLATION.
1. SEE SHEET E-001 FOR LEGEND AND GENERAL NOTES.
2. REFER TO PHASING AND SEQUENCING PLANS,
SPECIFICATIONS AND GENERAL REQUIREMENTS IN
REFERENCE TO COORDINATION OF ALL WORK TO BE
PERFORMED. WORK ASSOCIATED WITH PHASE 0
SHALL ESTABLISH THE INFRASTRUCTURE REQUIRED
TO EXECUTE EACH INDIVIDUAL PHASE AND MAINTAIN
SYSTEMS IN FULL OPERATION. ALL DEMOLITION AND
NEW WORK SHALL BE COORDINATED WITH OTHER
ASSOCIATED TRADES.
Revisions: Date:
ADDENDUM 01 09-27-22
File details come from the government source that posted it. Updated .