This one-line diagram depicts the electrical distribution system for the Mental Health Outpatient Renovation B5 Project 52A5-19-305 at the Brockton VA Medical Center. It shows the location of existing switchboards, panels, transformers and loads, as well as new equipment to be installed including a dry type transformer and distribution panel. The project will establish infrastructure to support phased renovations, with Phase 0 work coordinating demolition and new construction. Loads removed from the existing switchboard will be reconnected to the new low voltage panel. Additional details include routing a new feeder to the chiller and providing breakers for mechanical equipment. A 400A circuit will serve a temporary building during construction.

View the file

Other files

File Type Posted
36C24121R0163 0012.pdf PDF
36C24121R0163 0011.docx DOCX document
36C24121R0163 0010.docx DOCX document
36C24121R0163 0009.pdf PDF
36C24121R0163 0008.docx DOCX document
S04 - Site Visit Sign In Sheet 2-9-2023.pdf PDF
S06 General Decision Number MA20230012 1-27-2023.pdf PDF
36C24121R0163 0007.docx DOCX document
S06 Limitations on Subcontracting Certificate of Compliance 11-2022.pdf PDF
VHA COVID-19 Operational Plan 1-27-2023 (1).pdf PDF
36C24121R0163 0006.pdf PDF
S02 MA20230012.pdf PDF
36C24121R0163 0005.pdf PDF
36C24121R0163 0004.pdf PDF
S06 36C24121R0163 0003.docx DOCX document
S06 w7-r Sanitary - Profiles - Sewers.pdf PDF
S06 523A5-19-305-MD111-1.pdf PDF
S06 220927 19101 ADDENDUM 01_R5.docx DOCX document
S06 523A5-19-305-MD101-2.pdf PDF
S06 VA Brockton and Jamaica Plain Dust and Soil Rpt _FINAL 021716.pdf PDF
S06 Sommerville High School Drawings Renovation 1-23-18 - Room Number Marku....pdf PDF
S06 w4-r Sanitary - Location Plan - Sanitary-Sewer-Water.pdf PDF
36C24121R0163 0002.docx DOCX document
S02 General Decision Number MA20220012 09-02-2022.pdf PDF
S02 General Decision Number MA20220012 08122022.txt TXT text file
36C24121R0163 0001.docx DOCX document
S04 Sign In Sheet B5 MH Outpatient.pdf PDF
S02 36C24121R0163 Final.docx DOCX document
36C24121R0163.docx DOCX document
523A5-19-305 - B5 Outpatient MH Renovation 100 Percent Final Bid Documents - SPECS.pdf PDF
523A5-19-305-100 Percent FINAL BD DWGS VOL 1_STAMPED_210514_19101.pdf PDF
523A5-19-305-100 Percent FINAL BD DWGS VOL 2_STAMPED_210514_19101.pdf PDF
S02 SSJ - B5 MH Outpatient_R1SIGNED PA-DW.pdf PDF
EMR FORM.docx DOCX document
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DP, 277/480V, 600A, 3Ø, 4W

400A 3P

100A 3P

600A 3P

200A 3P

50A 3P

TO

PUMP HWP-1

50A 3P

TO

PUMP HWP-2

225A 3P

30A 3P

TO

STREET LIGHTS

40A 3P

TO

AHU #1

200A 3P

350A 3P

DP-LV, 120/208V, 800A, 3Ø, 4W

22,000 AIC

225A 3P

150A 3P

800A 3P

TO

5N2081

225A 3P

225A 3P

50A 3P

TO

EXISTING LOAD

100A 3P

TO

CERAMICS

100A 3P

30A 3P

TO

COMPRESSOR

ROOM PUMP

225A 3P

225A 3P

TO

CERAMICS

400A 3P

TO

EXISTING LOAD

TO

EXISTING LOAD

TO

EXISTING LOAD

TO

EXISTING LOAD

400A 3P

L1C

SECTION 1

120/208V

225A

MCB

NEW 'XFMR-1'

225 KVA

480Δ-208Y/120V

L2C

SECTION 1

120/208V

225A

MCB

L1C

SECTION 2

120/208V

225A

MLO

L2C

SECTION 2

120/208V

225A

MLO

L1A

SECTION 1

120/208V

225A

MCB

L2A 120/208V

200A

MCB

L1B

SECTION 1

120/208V

225A

MCB

L2B

SECTION 1

120/208V

225A

MCB

L1B

SECTION 2

120/208V

225A

MLO

L2B

SECTION 2

120/208V

225A

MLO

L1A

SECTION 2

120/208V

225A

MLO

REFER TO DRY TYPE TRANSFORMER

SCHEDULE FOR FEEDER INFORMATION

(TYPICAL)

EXISTING UTILITY TRANSFORMER

MDP, 277/480V, 800A, 3Ø, 4W

600A 3P

300A 3P

800A 3P

TO

ATS-EQ

100A 3P

--A 3P

PREPARED

SPACE

TO

ATS-LS

EN

L

ATS-N

225A

EXISTING 200A FEEDER TO EMERGENCY

SWITCHBOARD IN BLDG. 70

SPARE TO

EML BUILDING

TO

CHILLER

SPARE

60A 3P

60A 3P

TO

PUMP CWP-1

TO

PUMP CWP-2

3 3 3

44444

TO

TEMP. BUILDING

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% [FINAL] BID

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

0" 1/4" 1/2" 1" 2" 3"

C :\U se rs

\m pe nt el la \D oc um en ts

\1

_B ro ck to n_

B0 5_

El ec

_R

_m pe nt el la .rv t 9/

/2

:4

7:

A M

EP652

NEW WORK ONE LINE DIAGRAM BUILDING 5 OUTPATIENT MENTAL

HEALTH RENOVATION

BROCKTON, MA

523A5-19-305

5-14-21 MP MP

NONE

NEW WORK ONE-LINE DIAGRAM E10

NOTES:

KEYED NOTES:

EXISTING LOADS MAINTAINED FROM DEMOLITION OF EXISTING

SWITCHBOARD SHALL BE EXTENDED, AS NECESSARY, AND

RECONNECTED TO NEW DISTRIBUTION PANEL 'DP-LV'.

PROVIDE NEW FEEDER TO CHILLER. UTILIZE EXISTING CONDUIT

FROM PANEL 'DP' OUT TO EXISTING CHILLER PAD AND EXTEND AS

NECESSARY TO NEW CHILLER LOCATION.

PROVIDE NEW CIRCUIT BREAKERS IN EXISTING DISTRIBUTION

PANEL.

REFER TO MECHANICAL EQUIPMENT SCHEDULE ON DRAWING E-601

FOR FEEDER INFORMATION.

UTILIZE EXISTING 400A-3P CIRCUIT BREAKER IN DISTRIBUTION

PANEL 'DP' AND PROVIDE NEW 400A FEEDER TO SERVE TEMPORARY

BUILDING. CONTRACTOR SHALL COORDINATE ROUTING OF FEEDER

TO OUTDOOR LOCATION OF THE TEMPORARY BUILDING AND THE

FINAL LOCATION FOR TERMINATION POINT OF THE FEEDER IN FIELD

PRIOR TO INSTALLATION.

1. SEE SHEET E-001 FOR LEGEND AND GENERAL NOTES.

2. REFER TO PHASING AND SEQUENCING PLANS,

SPECIFICATIONS AND GENERAL REQUIREMENTS IN

REFERENCE TO COORDINATION OF ALL WORK TO BE

PERFORMED. WORK ASSOCIATED WITH PHASE 0

SHALL ESTABLISH THE INFRASTRUCTURE REQUIRED

TO EXECUTE EACH INDIVIDUAL PHASE AND MAINTAIN

SYSTEMS IN FULL OPERATION. ALL DEMOLITION AND

NEW WORK SHALL BE COORDINATED WITH OTHER

ASSOCIATED TRADES.

Revisions: Date:

ADDENDUM 01 09-27-22