Attachment A - walk-in inventory2.xlsx

XLSX spreadsheet 65 KB Posted

Attached to
33330226RF0010043 INDEFINITE DELIVERY/INDEFINITE QUANTITY (IDIQ) Planned Maintenance and Inspection Services for Environmentally Controlled Walk-In Units
Solicitation number
33330226RF0010043
Issued by

About this file

This is an inventory spreadsheet documenting the condition and specifications of approximately 70 Environmentally Controlled Walk-In (ECW) units across Smithsonian Institution facilities located in Washington DC, Suitland MD, Front Royal VA, Edgewater MD, Chantilly VA, and Landover MD. The spreadsheet captures detailed technical data for each unit including interior and exterior dimensions, door specifications, operational status, environmental control settings (temperature, relative humidity, radiation levels), refrigeration system components (compressor, condenser, evaporator manufacturers and serial numbers), electrical configurations, safety features (fire suppression systems, alarms, emergency generators), and current condition ratings (Green for good condition, Yellow for minor issues requiring attention, Red for significant problems). The inventory also documents specific deficiencies and recommended repairs for each unit, such as air filter replacements, insulation repairs, drain line clearing, refrigerant charge adjustments, light bulb replacements, and in some cases complete system rebuilds or decontamination procedures.

The data reveals significant variation in equipment age, condition, and maintenance requirements across the SI portfolio. Units manufactured between 1987 and 2024 are documented, with many older units (pre-2010) showing substantial wear requiring major repairs or replacement. Common issues identified include clogged drain lines, deteriorated door gaskets, compromised insulation, mold contamination, failing compressors, and improper refrigerant charges. Multiple units rated Red require immediate attention, including complete refrigeration system rebuilds, box replacement, and decontamination. The inventory serves as the baseline assessment supporting the Smithsonian's IDIQ solicitation 33330226RF0010043 for planned maintenance and inspection services, which requires contractor-provided semi-annual PM&I services, emergency response capabilities, certified technicians, and comprehensive reporting on all ECW units through a potential ten-year performance period.

View the file

Other files

File Type Posted
Amendment 2.pdf PDF
RFI Responses 22 thru 26.pdf PDF
Sign In Sheet for Site Visit.pdf PDF
RFI Responses 1 thru 21.pdf PDF
33330226RF0010043 Final with (SF33).pdf PDF
Amendment 1.pdf PDF
33330226RF0010043 Final.pdf PDF
Attachment B - Walk-ins First Site Visit Survey Attributes.xlsx XLSX spreadsheet
Attachment C - first site visit.xlsx XLSX spreadsheet
Walk-in PMI Contract SOW .docx DOCX document
Bid Sheet for walk-in Solication.xlsx XLSX spreadsheet
Attachment A - walk-in inventory.xlsx XLSX spreadsheet
Attachment D - Asset Management (AMD) Requirements.docx DOCX document
Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

Date CompletedOFEO Tag NumberInterior Dimensions WxDxHExterior Dimensions WXDXHDoor Dimensions WXHFinal Rating of existing condition: Green, Yellow, or Red.Site: NMNH, NMAH, NMAAHC, NASM, NASM-UHC, NMAI, ACM, HMSG, SERC, SCBI, NMAA (FREER), DWRC, NZP, Capital Gallery Administrative HQ, Quad, NPM, Pennsy, or otherBuildingStreet address of site:Room # or location (SPACE ID)Condenser location if other (SPACE ID)Exterior walk-in?Is the walk-in operational?Are OEM manual and/or certification records available?Are inspection and/or service reports available?Any special safety or care instructions with the stored product or walk-in?Is unit being usedIs the unit operating at requested parameters (at time of inspection)Any and all desired environmental control condition(s) set point: Temperature (C/F)Relative HumidityRadiation levelLightingOtherOil LevelSight Glass (Refrigerant charge)What year was the walk-in manufactured?Power supply location (panel/breakers)Condition of electrical wiring and connectionsAmperage ratingsIs the Walk-in on the emergency generator?Is the Walk-in on a Building Automatic System (BAS)?If yes, Is the BAS local or on a central system?Does the walk-in have a local alarm?Does the Walk-in have a backup refrigeration system or a Redundant system?Safety features of the walk-in: Fire suppression system in the walk-inIf yes, what type (connected to the building system, local suppression tanks, or other)?Other safety feature(s) of the walk-in (e.g., trapped person alarm (visual or audible), door sensors, phone in walk-in, etc.)Structural manufacturer (If not part of the building)Controller manufacturer,Model #Serial #Compressor InfoCondition and /or other pertinent information:Condenser manufacturerModel #2Serial #3Condenser coilsCondition and /or other pertinent information:4Evaporator manufacturer
7/2/24FM0434730X83X12N/A4FX7FYellowNASMUHC14390 Air and Space Museum ParkwayChantilly, VA 20151218.39Outside by loading dock 5&6NOYesFacilitiesFacilitiesNeed to be badged inYesYes4C30%N/AGoodN/AGoodGoodN/AS4216P3 breakers 1-11Good150AYesYesLocalYesNoYesSprinkler systemHFC-125extinguishing systemImperial manufacturingEnvironmental specialtiesES 84-30CR1390-218.39Copeland MDL: ZF40K4E-TWD-951 SN: 11E961184GoodHeatCraftLZT045M6DT10E08223AircooledGoodN/A
6/2/24FM0432330ft x 83ft x 12Build into building4'x7'YellowNASMUHC Bldg14390 Air and Space Museum ParkwayChantilly, VA 20151218.37Outside By Loading Dock 5&6N/AYesFacilitiesYesYou need to be badged in for entry.YesYes15C 30%30%N/AGoodGoodGoodGoodN/AS4216P3 breakers 2-6Good150AYesYesLocalYesNoYesSprinklerHFC-125 extinguishing system releaseImperial manufacturingEnvironmental specialtiesES 8-31R1390-218.37Copeland MDL: 8T5K4E-TFD-230 S/N: 10D0627CDGoodHeatcraftLZT020M6DT10E08219Air cooledGoodHeatcraft
6/2/24FM0434830'X11'X12'N/A4'X7'GreenNASMUHC14390 Air and Space Museum ParkwayChantilly, VA 20151218.4Outside by loading dock 5&6N/AYesFacilitiesOnsite FacilitiesYou need to be badged inYesYes-4cGoodN/AGoodN/AGoodGoodN/APanel: S4216P3, Breaker: 8-12Good150YesYesLocalYesNoYesSprinkler SystemHFC-125 Extinguisher System ReleaseImperial manufacturingEnvironmental specialtiesES 11-30FZ1390-218.40Copeland Mdl# ZS30K4E-TDF-250, SN# 10D1588ADN/AHeatCraftLZT045M6DT10E08223Air CooledN/AN/A
7/3/24FM0432416'X17'X12'BUILD INTO THE WALL8'X8'GreenNASM-UHCNASM-UHC14391 Air and Space Museum ParkwayChantilly, VA 20151217.01Mechanical Space 320.06N/AYesPossible FacilitiesPossible FacilitiesNeed to be badged into boxYesYes16.0C40.00%N/AGoodN/AGoodGoodUnkownS4216P2 BREAKERS: 14,16,18Good150AYesYesLocalYesNoYESDRY CLEAR AGENT SUPPRESSION, HFC-125 EXTINGUISHERNeed to be badged inN/AEnvironmental specialtiesES 17-16CR1390-217.01Copeland MDL: zs19kae-Tfd-118 SN: 18D68F08LN/AHeatcraftLZT0700M6DT18E16205Air CooledN/ALarkin
7/3/24FM0432563'X30'12'N/A8'X8'YellowNASM-UHCUHC14392 Air and Space Museum ParkwayChantilly, VA 20151217.02320.06N/AYesFacilitiesFacilitiesNeed an escortYesYes12.8C 45.0%45%N/AGoodN/AGoodFullN/APANEL- S4216P2 BREAKERS-13,15,17Good150AYesYesLocalYesNoYesHFC-125 extinguishing systemN/AN/AEnvironmental specialtiesES31 - 55CR1390-217.02COPELAND MDL: ZS45K4E-TFD-250, SN: 18E4544ADN/AHeatcraftLZT060M60T18E17^87AircooledN/AN/A
7/3/24FM0432630'X80'X12'N/A3'X8'YellowNASM-UHCUHC14393 Air and Space Museum ParkwayChantilly, VA 20151217.05Mechanical Room 320.06NoYesFacilitiesFacilitiesNeed an escortYesYes18.0c35.00%N/AGoodN/AGoodGoodN/APANEL-S4216P2 BREAKERS:1-11Good150AYesYesLocalYesNoYESDRY CLEAR AGENT SUPPRESSION. HFC-125 extinguishing systemNeed to be badged inN/AEnvironmental specialtiesES80-30CR1390-217.05COPELAND MDL: ZB58K5E-TFD-260, SN: 18DC4206DN/AHeatcraftSZT025M60SPT18E17682AircooledN/AN/A
7/9/24FM0432785x63x12N/A8'x8'GreenNASM-UHCUHC14394 Air and Space Museum ParkwayChantilly, VA 20151220.08Mechanical Room# 320.06N/AYesFacilitiesFacilitiesN/AYesYes50F/45%GoodN/AGoodN/AGoodGoodN/AS7220L1/breaker 1,3,5Good150AYesYesLocalYesYesSprinkler systemLocal2 Phones inside of boxR-PLUS Cold StorageBahnsonES 64-87CR1836-220.08MDL:3DA3R10ME-TFD-C40 S/N:18E00348R, 18D00199RController located in Mechanical Room# 220.06KeepriteKESA080H8-HT4C-X2465182206575, 182206574AircooledN/ATrane
7/9/24FM04329N/A48'Wx18'H6'8'YellowNASM-UHCUHC14395 Air and Space Museum ParkwayChantilly, VA 20151214.31On roofNOYesFacilitiesFacilitiesYes, radiation is stored inside walk-in and we are not allowed in without special clearance/PPEYesYes72F35%HighN/AN/AN/ASystem A-Good, System B- N/AUnkownECR-C9 4214D1- Breakers 37,39,41Good150YesYesLocalYesYesYesWater sprinkler systemUnknownNorlakeSiemensN/AN/ASystem A compressor- ALLIANCE MDL- SXA051BABPA, SN: 17BJ9346N. System 2 compressor MDL: SXA051BABPA, SN: 17DJ9310NAir cooledOdysseyTWA120E40RAA17274PH5YAAircooledBoth systems use one condenser coilTrane
7/9/24FM0432884'Wx63'Dx12'HN/A8'x8'GreenNASM-UHCUHC14396 Air and Space Museum ParkwayChantilly, VA 20151320.09In mechanical room# 320.06NoYesFacilitiesFacilitiesNeed to be badged for entryYesYes37F/30%GoodN/AGoodN/AGoodGood2018S7320L1, Breakers: 1,3,5Good150AYesYesLocalYesYesYesWater sprinkler systemUnit has two interior phonesImperial BrownBahnson Environmental SpecialtiesES64-87CR1836-320.09Model: 3DF3R15ME-TFD-C40, SN# 18D01393R, 18D01392RNoKeepriteMDL# KESA120H8-HT4C-X2464SN# 182206572, 182206573Air CooledN/ATrane
10/25/24FM0463310'8"x7'7"x11'11'8"x8'9"x11'9"4'8"x8'1"GreenNMAINMAI300 Maryland Ave SW
Washington DC 20024Collections Room Basement 0026Loading DockN/AYesYesYesN/AYesYes-38FN/AN/AGoodN/AGoodGoodUnknownUnknownUnknownUnknownYesN/AN/AN/AYesYesWater Sprinkler SystemN/AThermalrite By EveridgeWatlowSD31N/ABitzer Compressors System A & B MDL: S4T-5.2Y, System A SN: 25H2007557, System B SN: 664201639N/ACentury RefrigerationWCBD10XLT709-03-064931-001-001Water CooledCondenser Rack is supened in the airCentury RefrigerationBoth systems MDL: A1517-206ESystem A SN: 12-16-126183-001-001, System B SN: 09-03-064931-002-001GoodN/AGoodN/AR507GoodGood
10/8/23FM043908'x12'10x8'7'x13'x8'5'1"x7'5"GreenCultural Resources CenterCRC Bldg4220 Silver Hill RdSuitland, MD 20746LL2131 Isolation RoomOn the RoofN/AYesYesYesNeed key to open doorYesYes-27FN/AN/AGoodN/AGoodGoodApprox. 2001N/AGoodN/AYesYesLocalYesN/AYesWater Sprinkler SystemPanic Alarm ButtonThermalRiteJohnson ControlsElectrical ThermostatN/ABitzer MDL: S4T-5.2Y-2NU258698112HeatCraftBCU1005ABEX6C2A15B00082Air CooledN/ABOHN

One stick of 1-3/8x3/4

10/8/24FM043834'2"x7'x7'8"5'x7'7"x8'5"3'x7'GreenCultural Resources CenterCRC Bldg4221 Silver Hill RdSuitland, MD 20746Trash/Recycling LL2117On top of boxN/AYesUnknownUnknownN/AYesYes?N/AN/AGoodN/AN/AGoodN/AN/AN/AN/AYesN/AN/AN/AN/AN/AN/AN/ABallyJohnson ControlsPenn Mechanical ThermostatN/ACopeland Compressor MDL: KANB-007E-CAV-800, SN: ET 16C62767RN/ARussellRLS075M44-DE15H00729270001001Air CooledN/AN/AN/A
10/9/24FM0439721.5'x11'x8'N/A3'X7'GreenCultural Resources CenterCRC Bldg4222 Silver Hill RdSuitland, MD 20746LL2098On the RoofN/AYesYesYesYesYesYes1.5c37%N/AGoodGoodN/AGoodApprox.2001UnknownUnknownUnknownYesYesLocalYesYesYesWater Sprinkler SystemAudio, Visual Alarms, & Panic Alarm ButtonBallySCE ControllerIEC 605293820372Copeland Scroll System A&B MDL: ZS15KAE-TF5-118, System A SN: 19H82C3IL, System B SN: 19H82C28LN/AHeatCraftSystem A&B MDL: BZT020M6CSystem A SN: T19K19956, System B SN: T19K19955Air CooledN/ABOHNSystem A&B MDL: ADT156AEK

Hot Gas Insulation: 1/2x1/2 (4sticks) Suction line: 7/8x1/2 (4sticks Needs one more “Durablock Pipe Supprt” With three cushion clamps (3/8,1/2,7/8) one of each. Also System B Hot Gas: 1/2x1/2 (2sticks) Suction line: 7/8x1/2 (2 sticks)

7/17/24FM0426818'x50'x11'N/A3'x7'YellowAmerican HistoryAmerican History1400 Constitution Ave NWWashington DC 20013BB018Mechanical SpaceNoYesYesYesN/AYesNo45F45RHN/APoorN/AGoodGood1998BB017DGood30AYesYesLocalYesNoYesWater Sprinkler SystemNeed to be badged in by end user; security key needed from security officeBally Case & CoolerWhite-Rodger's Mechanical ThermostatN/AN/ACopeland MDL# 2DC3-050E-TFD-800, SN# 01F69381RDates back from 2001HeatcraftTRH050H24NT96M01144Air CooledNoticed condenser coil slightly damagedSine air handlerSSH-9
10/1/24FM0438124'8"x58'8"x9'2"24'10"x66'x9'6"7'5"x8'2"GreenPaul E. Garber FacilityBldg 243904 Old Silver Hill RdSuitland, MD 20746-3190NASM Space Suit Storage 1Outside of buildingN/AYesUnknownUnknownNeed to be badged into Walk-inYesYesUnknown-Siemens ControlsUnknown-Siemens ControlsN/AGoodN/AN/AN/AApprox. 2006EP-01-07Good60AUnknownYesLocalYesN/AYesWater Sprinkler SystemAudio and Visuals AlarmsBallySiemens ControlledSimatic PanelN/AData Plate is not legibleSmall CondenserPossible York unit but date plate is gone.N/AN/AAir CooledN/AMunthersHCD-600-SMFBCS
10/1/24FM0438924'6"x62'2"x12'1"25'4"x63'x12'5"4'2"x8'1"GreenPaul E. Garber FacilityBldg. 243905 Old Silver Hill RdSuitland, MD 20746-3190NASMOutside next to buildingN/AYesUnknownUnknownNeed to be badged inYesYesUnknown-Siemens ControlledN/AN/AGoodN/AGoodGoodAprox. 2001UnknownUnknownUnknownUnknownYesLocalYesN/AYesWater Sprinkler SystemAudio & Visual AlarmsBallySiemens ControlledN/AN/ACopelandUnable to read Comp data plate.N/AN/AN/AAir CooledUnable to read Comp data plate.UnknownN/A
10/1/24FM0438824'6"x62'2"x12'1"25'4"x63'x12'5"Door 1 - 4'2"x8'1" Door 2 - 3'2"x6'7"GreenPaul E. Garber FacilityBldg. 243906 Old Silver Hill RdSuitland, MD 20746-3190NASM Small Objects StorageN/AN/AYesUnknownUnknownNeed to be badged inYesUnknownUnknown-Siemens ControlledN/AN/AGoodN/AN/AN/AApprox. 2001UnknownUnknownUnknownUnknownYesLocalYesN/AYesWater Sprinkler SystemAudio and Visual AlarmsBallySiemens ControlledN/AN/ACompressor MDL: SPA036B4BPA / SN:08BA7261NThis unit has a reversing valve.N/AN/AN/AAir CooledThis unit is a package unit.N/AN/A
10/1/24FM0438724'6"x37'10"x12'1"25'4"x38'6"x12'5"Door 1 - 3'2"x6'7" Door 2 - 4'2"x8'1"YellowPaul E. Garber FacilityBldg. 243907 Old Silver Hill RdSuitland, MD 20746-3190NASM Box 6 Art StorageOutside next to buildingN/AYesUnknownUnknownNeed to be badged inYesUnknownUnknown-Siemens ControlledUnknown-Siemens ControlledN/AGoodN/AN/AN/AApprox. 2001UnknownUnknownUnknownUnknownYesLocalYesN/AYesWater Sprinkler SystemAudio and Visual AlarmsBallySiemens ControlledN/AN/ACompressor MDL: ZR18K5E-PFV-130 / SN:16C3D684MN/AEmersonPFH020A-PL7Y16FG10072Air CooledN/AEmersonDME020E-PH7
10/1/24FM0438524'4"x78'11"x11'3"N/A6'4"x7'2"GreenPaul E. Garber FacilityBldg. 243908 Old Silver Hill RdSuitland, MD 20746-3190NASM Flight Material StorageOutside next to buildingN/AYesUnknownUnknownNeed to be badged inYesUnknownUnknown-Siemens ControlledUnknown-Siemens ControlledN/AGoodN/AN/AN/AApprox. 2001UnknownUnknownUnknownUnknownYesLocalYesYes, their are two independent refrigeration circuits that use the same condenser and air handler.YesWater Sprinkler SystemAudio and Visual AlarmsPart of the BuildingSiemens ControlledN/AN/ACircuit A & B Compressor MDL: GP813-NN3-GA, Circuit A SN: Z015RU1N, Circuit B SN: Z015RX8NN/AAmerica Standard Inc.TTA150B300CAZ071293AHAir CooledCondenser Coil has two refrigeration circuitsAmerica Standard Inc.TWE180B300CA
10/31/24FM04653N/AN/AN/AYellowACMAnacostia Community Museum1901 Fort Place SE, MRC 777Washington DC 20020122On the roofN/AN/AUnknownUnknownNeed to be badgedN/ANo60C50%N/AGoodN/AN/AN/A2016UnknownUnknownUnknownYesN/AN/AN/AN/AYesWater Sprinkler SystemMan Down ButtonKPS GlobalAllen Bradley2711C-T6T44421476Copeland2DA3R89KE-TFC-C40HeatCraftLDT0751M6CSA16C00202Air CooledN/AUnknownUnknown
10/31/24FM04654N/AN/AN/AGreenACMAnacostia Community Museum1901 Fort Place SE, MRC 777Washington DC 20020Warm Room RM#123?On the roofN/AYesUnknownUnknownNeed to be badged inNoYes70F50%N/AGoodN/APoorN/A2016Pane: PCR RM 124 / Breakers 7, 9, 14, 16, 18, 20, 22, 24Good30AUnknownYesLocalYesN/AYesWaterN/AKPS GlobalHarris Environmental SystemsJob#152368 No MDLN/AMDL: ERFA-031E-TAC-220 / SN: ET16C00460RN/ALarkinLST030M6CSA16C00204Air CooledUnknownUnknownN/A
7/17/24FM042709'X11'X8'11'7"xx8'5'x6.5'YellowHMSGHMSG7th St and Independence Ave SW Washington DC 20560GO7 BOn top of walk-inNOYesUnknownFacilitiesNeed to be badged in by end userYesYes60F40 RHN/AGoodN/AN/AGood2004UPGC,BREAKER 2,6,17,21Good20AYESYESLOCALYESNAYESWATER SPRINKLER SYSTEMN/ABally RefrigerationPARTLOW MRC 7000NANACOPELAND, MDL# RST70C1E/SN#19H09131EN/ARUSSELLREH100H22-DW04J26390101001AIR COOLEDCONDENSER COIL HAS A 7"GAP BETWEEN COIL AND DRYWALLRusselAA58-275B-A
7/17/24FM042668'x19'x8'N/A5'x7'YellowHMSGHMSG8th St and Independence Ave SW Washington DC 20560Walk-in is accessed through +60F walk-inOn top of walk-inNoYesYesYesNeed to be badged in by end userNoNo40F40RHN/AGoodN/AN/AGood2004Panel- UPGC, Breakers- 1,7,4,18,20,22Good20AYesYesLocalYesNoYesWater sprinkler systemN/ABally RefrigerationPARTLOW MRC7000N/AN/ACOPELAND MDL# CR32K6E-PFV-875, SN# 21HAT312MN/ARUSSELLREH251H22-DW04J26390104001Air CooledCondenser coil has some damage, refrigeration seems fine at the momentRUSSELLAA58-275B-A
10/23/24FM0591316'5"X13'4"X9'6"N/A3'3"X6'10"GreenQUADMuseum Of African Art1100 Independence Ave SWWashington DC 20560Sublevel 2 - 2139 Inside 2140 Eliot Elisofon ArchivesIn Large closet of the Library to the right of 2140 Eliot Elisofon ArchivesNoYesYes/Local - Also Welch & RusheYes/Local - Also Welch & RusheYes Badge InYesYes45F25%N/AGoodN/AGoodGoodUnknownUnknownGood30ANoNoN/AYesYesYesWater sprinklerAudible alarmUnknownPenn MechanicalN/AN/ACopeland Compressors System A & B MDL: KAGA - 0150TAC200, System A SN: CCC0610810, System B SN: CCK0514611GoodTrenton RefrigerationA & B MDL: TESA015H2-HT3A-BA SN: 060200733, System B SN: 060102316Air CooledGoodTrenton RefrigerationA & B MDL: TLP123A
10/24/24FM0437911'2"X16'8"X8'10"N/A3'3"X6'10"RedQUADMuseum Of Asian Art1101 Independence Ave SWWashington DC 20560Sublevel 2 - 2062 ArchivesN/A (Was on Top of Box)NoNoYes/Local FacilitiesYes/Local FacilitiesYes Badge InYesNoN/AN/AN/AGoodN/AN/AN/AUnknownRoom 2062A - Panel LDP2A / Breakers 19,21, & 23Good20AN/ANoNoNoNoYesWater sprinklerAudible alarmUnknownN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A
10/31/24FM046509'2"x12'6"x7'1"9'9"x13'6"x7'5"RedQUADQuad Loading Dock Near Ripley Center1102 Independence Ave SWWashington DC 20560Loading Dock- Compost RoomOn top of Walk-inN/ANoUnknownUnknownN/AYesNo40FN/AN/AGoodN/AN/AN/AUnknownNot able to locate power supplyN/AN/AUnknownNoN/AN/ANoYesWater Sprinkler SystemSafe gaurd door release safetyVictoryJohnson ControlsPenn Mechanical ThermostatN/ATecumseh Compressor MDL# AJA4512YXD SN# 04C041521897429X208VTecumsehAJA45122YXDXC18D2115292625AJA45122YXDXCAir CooledHeatcraftSM090AE
10/7/24N/A9'10"x8'11"x7'8"N/A3'9"x6'3"GreenCapital Gallery Administrative HQCapital Gallery600 Maryland Ave SWSuite 760E, MRC 500Washington DC 200243210 StagingMechanical RoomNoYesYes/LocalYes/LocalNoYesYes-18FN/AN/AGoodN/AGoodGood2006Panel L3B2 / 24,26,28Good50ANoYesLocalYesNoYesWater SprinklerTrapped person, Slip, Visual, & Audible AlarmsN/AClimate TechnologiesN/AN/AM/N: LAHA-032E-TAC-220 S/N: ET06D04139N/ALarkinSWN0310L6CT06D05014Water CooledN/AHeatcraftLCA6160AHB
10/7/24N/AN/AN/AN/AGreenCapital Gallery Administrative HQCapital Gallery600 Maryland Ave SWSuite 760E, MRC 500Washington DC 200243240 Archives Collections3220 Mechanical RoomNoN/AYes/LocalYes/LocalYes, you need to be badged in.YesYes60F - 62F50%N/AGoodN/AGoodGoodN/A3220 Mechanical RoomGoodN/AN/AYesLocalYesNoYesWater SprinklerTrapped person, Slip, Visual, & Audible AlarmsN/AN/AN/AN/AN/AN/ATraneMCCB017UA0A0UAK06A12388Water CooledN/AN/AN/A
10/17/24FM0436734'2"X32'9"X7'11"N/A3'2"X6'7"GreenPennsyMain Building3400 Pennsy Dr Hyattsville, MD 20785-160701FFF60 (You have to go through 01EEE58 & 01EEE60 To Access)RoofNoYesYes/Local FacilitiesYes/Local FacilitiesYes Badge InYesYes11C30%N/AGoodN/AGoodGood201501FFF55 CC#2Good30AUnknownYesLocalYesNoYesWater sprinklerVisual, audible, and trapped person alarmImperial BrownEnvironmental Growth ChambersEGC TC2N/AMDL#:ZB30CE-TFD-250 / SN#: 15B5466ADGoodCopelandFJAM-A40Z-TFD-01515BL0408UAir CooledGoodHeatcraft (Total of 4 Evaporators)LSC140BEK
10/18/24FM0437837'3"X37'3"X7'11"N/A3'2"X6'7"GreenPennsyMain Building3401 Pennsy Dr Hyattsville, MD 20785-160701FFF58 (You have to go through Cooler To Access)RoofNoYesYes/Local FacilitiesYes/Local FacilitiesYes Badge InYesYes26F30%N/AGoodN/AGoodGood201501FFF55 CC#1Good30AUnknownYesLocalYesNoYesWater sprinklerVisual, audible, and trapped person alarmImperial BrownEnvironmental Growth ChambersEGC TC2N/AMDL#:ZB45KCE-TFD-965 / SN#: 20E4041ADGoodCopelandFJAM-A60Z-TFD-01515CL0073UAir CooledGoodHeatcraft (Total Of 4 Evaporators)LSF160BEK
7/16/24FM0427310'x10'x811'x11'x95'X6'RedNMNHNMNH10th and Constitution Ave NW Washington DC 20560EG19Machine Room-Ground FloorNoNoPossibly FacilitiesPossibly FacilitiesNoNoNo-5FN/AN/AN/AN/APoorN/A2002PANEL: EWGNL7, BREAKERS: 19,21Good20AYesNoN/ANoNoYesWater sprinkler systemNoBally Refrigeration BoxesRanco, Mechanical T-StatN/AN/ACopeland, MDL: 2DF3F16KETFC200, SN# CCB0810528N/ABALLYBESA035L6-HT3B-303582201108AIR COOLEDFINS ARE BAD & DIRTY, DATES BACK 2008BallyBLP312VE-S2B-C0051
7/16/24FM0425710'x10'x8'11'x11'x9'5'x6'YellowNMNHNMNH11th and Constitution Ave NW Washington DC 20560WG-23NEXT TO WALK-INNOYesYesYesNoYesYes-10FN/AN/AGoodN/AN/AGood2001Electrician is working on it.Electrician is working on it.Electrician is working on it.Electrician is working on it.YesLocalYesNoYesWater sprinkler systemNoBALLY REFRIGERATIONDanfoss Mechanical ThermostatN/AN/ACopeland, MDL# CF09K6E-TF5-271, SN# 07J86495HN/ABallyBEHA025L6-HT3A-F82100797Air cooledN/ABallyBLP20SLE-S24-SD6NN
7/16/24FM042777'x5'x7'8'x15'x8'3'x7'RedNMNHNMNH12th and Constitution Ave NW Washington DC 20560CE-439CE-425NoNOFracilitiesFacilitiesNoNoNo-10cN/AN/AGoodN/AN/APoor2005EC4EL1,BREAKERS- 31,33, 15,5Good20AYESNoN/ANoNoYesWater sprinkler systemNoBally Refrigerated BoxesRanco Mechanical T-stat010-1000N/AN/ADATA PLATE IS WARN OFFHEATCRAFTBCU1012WBEX6D1A05K00034WATER COOLEDHAS BEEN OFF FOR OVER A YEARRussellUEU-236
10/24/24FM0460112'10"x12"x8'8"N/AN/ARedNMNHNMNH13th and Constitution Ave NW Washington DC 20560Compost Room By Loading DockN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AGoodN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AYesWater Sprinkler SystemN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A
9/17/24FM0437112'8"x31'9"x8'4"N/A3'8"x7'1"GreenMSCMuseum support Center4210 Silver Hill RdSuitland, MD 20746212Equipment Room 219NoYesYes-OFMRYes-OFMRNeed to be badged into walk-inYesYes55F27%N/AGoodN/AGoodGood2011Equipment Room #219, Both system on Panel: EPP-2, System A Breakers: 49,51,53. System B Breakers: 43,45,47Good35AYesYesLocalYesYesYesWater Sprinkler SystemAudible & Visual AlarmsKysor Panel SystemsSiemens ControlledN/AN/ASystem A Copeland Compressor MDL: EAVA-021E-TDA-220, SN: 10B04475R/ System B Copeland Compressor MDL: EAVA-021E-TAD-220, SN: 10B04474RN/AHeatcraft for both systemsSystem A MDL: WS0210H44/ System B MDL: WS0210H44System A SN: A10C00214/ System B SN: A10C002215Water Cooled CondensersEverything is controlled by siemensHeatcraftEvaporator 1A MDL: LCA6135BEB, 2A MDL: LCA6135BEB/ 1B Evaporator MDL: LCA6135BEB
9/18/24FM0437331'8"x81'5"x9'4"N/A3'8"x7'1"YellowMSCMuseum Support Center4211 Silver Hill RdSuitland, MD 20746213Equipment Roon 216N/AYesYes-OFMRYes-OFMRNeed to be badged to go into walk-inYesYes-4FN/AN/AGoodN/AGoodGood2011Both systems on Panel EPP-2, System A breakers: 19,21,23. System B breakers: 25,27,29Good60AYesYesLocalYesYesYesWater Sprinkler SystemAudible and Visual AlarmsKysor Panel SystemsSiemens ControlledN/AN/ASystem A Copeland Compressor 1 MDL: 3DB3F33KE-TFD-200, SN: 10C00578R, Compressor 2 MDL: 3DB3F33KE-TFD-200, SN: 10C00575R/ System B Copeland compressor 1 MDL: 3DB3F33KE-TFD-200, SN: 10C00576R, Compressor 2 MDL: 3DB3F33KE-TFD-200, SN: 10C00577REach system has two compressorsHeatCraft for Both SystemsSystem A & B MDL: LRU2015WBAL6D1System A: A10C00294, System B: A10C00295Water Cooled CondensersN/ARuskinAll evaporator coils have the same MDL number : CDTI50
9/17/24FM0437231'6"x30'2"x9'4"N/A3'8"x7'1"GreenMSCMuseum Support Center4212 Silver Hill RdSuitland, MD 20746211Equipment Room 219NoYesOFMRYesNeed to be badged into walk-inYesYes55F27%N/AGoodN/AGoodGood2011Both systems on Panel: EPP-2, System A Breakers 37,39,41. System B Breakers 31,33,35Good35AYesYesLocalYesYesYesWater Sprinker SystemAudible & Visual AlarmsKysor Panel SystemSiemens ControlledN/AN/ASystem A Copeland Compressor MDL: EAVA-021E-TAD-22, SN: 10B04476R/ System B Copeland Compressor MDL: EAVA-021E-TAD-220, SN:10B04473RN/AHeatcraft for both systemsSystem A MDL: WS0210H44, System B MDL: WS0210H44System A SN: A10C00217, System B SN: A10C00216Both are Water CooledEverything is controlled by SiemensHeatCraftSystem A & B Evaporator MDL: LCA6135BEB
9/18/24FM0437415'4"x27'8"x8'9"N/A3'8"x7'1"YellowMSCMuseum Support Center4213 Silver Hill RdSuitland, MD 20746148On top of BoxN/AYesYes-OFMRYes- OFMRNeed to be badged inYesYes35F51%N/AGoodN/AGoodBubblesUnknownBoth systems on Panel EPP-2, System A breakers 44,46,48. System B breakers:43,45,57Good35AYesYesLocalYesYesYesWater Sprinkler SystemN/AEnvironemental Growth ChambersSiemens ControlledN/AN/ACopeland Compressor System A & B MDL: LACA-032E-TAD-220. System A SN:10B01322R, System B SN: 10B01325RN/AHeatCraft for both systemsSystem A & B MDL: WS0310H4DSystem A: A10C00228, System B: A10C00227Water CooledN/ARuskinCDTI50
9/19/24FM043759'10"x15'6"x8'9"N/A3'8"x7'1"GreenMSCMuseum Support Center4214 Silver Hill RdSuitland, MD 20746147On top of BoxN/AYesYes-OFMRYes- OFMRNeed to be badged inYesYes-5N/AN/AGoodN/AGoodN/AUnknownBoth systems on panel EPP-2, System A breakers 26,28,30. System B breakers 20,22,24.Good35AYesYesLocalYesYesYesWater Sprinkler SystemN/AEnvironemental Growth ChambersSiemens ControlledN/AN/ABoth Copeland Compressor MDL: LAHA-032E-TAC-800, System A SN: 00C72220, System B SN: 22H62578RN/AHeatCraft for both systemsSystem A & B MDL: WS0310L63System A: A10C00094 System B: A10C00093Water CooledN/ARuskinCDTI50
9/19/24FM042768'4"x8'3"x7'2N/A4'2"x6'7"YellowMSCMuseum Support Center4215 Silver Hill RdSuitland, MD 20746G1004On the roofN/AYesYes-OFMRYes-OFMRN/AYesYes38FN/AN/AGoodN/AN/AGoodUnknownPanel: 124 IELI, Breaker: 23Good20AYesN/AN/AN/AN/AYesWater Sprinkler SystemAudible AlarmFoster Refrigereation Corp.Johnson ControlsPenn Mechanical ThermostatN/ACopeland Compressor MDL: ZS09KAE-TF5-118, SN: 21C5276HLN/ARussellRB0130E4SEBE172100847Air CooledN/ARussellRL6A117ADA
9/19/24FM042679'1"x6'3"x8'11"9x6'7"x9'2"3'2"x7'1"YellowMSCMuseum Support Center4216 Silver Hill RdSuitland, MD 20746G1005RoofNoYesOFMRYesNeed to be badged into walk-inYesYes-20FN/AN/AGoodN/AGoodGoodApprox. 2002Panel: 1L2-SECT-2 / Breakers: CKT30,32,34 / Timer & Controls on same panel but on breakers 33,35Good50AYesNoN/AN/ANoYesWater Sprinker SystemN/ABally EngineeRed StructuresPenn MechanicalN/AN/ACopeland Semi hermetic - MDL:3DA3F28KE-TFC-C00 / SN:22G01194RN/ARUSSELLRFDS06L4SEAE092300343Air CooledN/ARUSSELLRM6E311DDA
9/23/24FM0437613'10"x11'3"x13'4"N/A4'2"x7'1"GreenMSCOSTEO PREP LABORATORY4217 Silver Hill RdSuitland, MD 20746102On the roofN/AYesYes-OFMRYes-OFMRN/AYesYes0CN/AN/AGoodN/AGoodGoodUnkownBoth systems on Panel: ELP1Good40AYesYesLocalYesYesYesWater Sprinkler SystemN/ABallyJohnson ControlsPenn Mechanical ThermostatN/ASystem A Copeland Compressor MDL: CS20K6E-TF5-256 / SN: 16KAF144M, System B Copeland Compressor MDL: CS12K6E-TF5-256 / SN: 16HCF667MN/ATrentonSystem A MDL: TEHA035E6-HT3B-B, System B MDL: TEHA020E6-HT3B-BSystem A SN: 162405596 System B SN: 162405595Air CooledN/ATrentonSystem A MDL: TPLP532MAS1BR6-EC2 / System B MDL: TPLP317MAS1BR6-EC2
9/23/24FM0439426'5"x10'11"x13'4"N/A5'2"x7'1"GreenMSCOSTEO PREP LABORATORY4218 Silver Hill RdSuitland, MD 20746103On the roofN/AYesYes-OFMRYes-OFMRN/AYesYes-20CN/AN/AGoodN/AGoodGoodUnkownBoth systems on Panel: ELP1Good40AYesYesLocalYesYesYesWater Sprinkler SystemN/ABallyJohnson ControlsPenn Mechanical ThermostatN/ABoth Copeland Compressors MDL: 3DF3F40KE-TED-C40, System A SN: 16K03145R, System B SN: 16K03147RN/ATrentonSystem A MDL: TESA090L6-HT4B-6814, System B MDL: TESA090L6-HT4B-6814System A SN: 162405591, System B SN: 162405591Air CooledN/ATrentonSystem A MDL: TMP348LE-T4A-CC6NN, System B MDL: TMP356LE-T4A-CC6N
9/27/24FM043939'8"x9'1"x7'11"9'8"x8'5"x9'8"5'11"x6'6"YellowMSCOsteo Prep laboratory4219 Silver Hill RdSuitland, MD 20746Inside white fence next to the buildingNext to walk-inYesYesYes-OFMRYes-OFMRN/AYesYes-20cN/AN/APoorN/AGoodGoodApprox. 2002Panel: EPL1Good40AYesYesLocalYesN/AN/AN/AN/ABallyJohnson ControlsPenn Mechanical ThermostatN/ACopeland Scroll MDL: ZF11K4E-TF5-241, SN: 16F8303ADN/ATrentonTEZA035L8-HT3B-6816162405593Air CooledN/ATrentonTPLP314LES2BR6-EC2
9/27/24FM043929'8"x9'1"x7'11"9'8"x8'5"x9'8"5'11"x6'6"GreenMSCOsteo Prep laboratory4220 Silver Hill RdSuitland, MD 20746Inside white fence next to the buildingNext to walk-inYesYesYes-OFMRYes-OFMRN/AYesYes-20cN/AN/AGoodN/AGoodGoodApprox. 2002Panel: EPL1Good40AYesYesLocalYesN/AN/AN/AN/ABallyJohnson ControlsPenn Mechanical ThermostatN/ACopeland Scroll MDL: ZF11K4E-TF5-241, SN: 16F8306A0N/ATrentonTEZA035L8-HT3B-6816162405594Air CooledN/ATrentonTPLP314LES2BR6-EC2
10/2/24FM043827'2"10'3" 8'6"7'9"11'3"9'2"3'7"x7'1"GreenSmithsonian Gardens Greenhouse FacilityBlue Building inside Greenhouse Facility4220 Silver Hill RdSuitland, MD 20746Open space by the loading dockon the outsideN/AYesPossibly OFMRPossibly OFMRN/AYesYes38fN/AN/AGoodN/AN/AGoodApprox. from 2001Disconnect by front doorGood30AYesN/AN/AYesN/AYesWater Sprinkler SystemN/ABally RefrigerationRanco Mechanical ControllerN/AN/ACopeland MDL: CR18K6E-TF5-875, SN: 16EAC015MGoodBally RefrigerationBEHA015H2-HT3B-B92107650Air CooledN/ABally RefrigerationBLV150AD-S2B-3016-FD
10/2/24FM0439810'6"x22'x8'N/A3'x6'8"YellowSmithsonian Gardens Greenhouse FacilityBuilding 344220 Silver Hill RdSuitland, MD 20746Room #5 AAG Collection Storageon the outsideN/AN/APossibly OFMRPossibly OFMRN/AYesYes72F41%N/AGoodN/AN/AN/AApprox. from 2001Disconnect by unit.Good30AN/AYesLocalYesN/AYesWater Sprinkler SystemN/AN/ASiemensN/AN/AN/A Data tag could not be read.YellowLiebertN/AN/AAir CooledN/ALiebertBLV150AD-S2B-3016-FD
6/13/24FM0428122'x34'x10'N/A83"x96"GreenNZPCommissary3001 Connecticut Ave NWWashington DC 20008172A Freezer 1100M7NoYesUnknownHVAC/Facilities may have recordsShoe chemical bath entering commissary.

Escaped animal codes: Green - Non dangerous

Red - DangerousYesYes-4N/AN/AN/AN/AGreen System 1 1/4 Full
System 2 1/2 FullGreen System 1 Full; System 2 Full2003Room 100M7

Panel 4S5 System 1 breaker 2/4/6 System 2 breaker 1/3/5 Green 15a No Yes Local No Yes No N/A Sliding door manual release No visable data tag Siemens N/A N/A Copeland System 1 model - 2DL3-040ETFD200 System 2 model - 2DL3F20KE-TFD-800 System 1 Serial - CCH0513338

System 2 Serial - 19H60196RGreenBallyBW400L6-IT4A-1980System 1 - 050304601
System 2 - 050304602Water cooledSystem 1: Yellow - Accumulator is rusted and deteriorating.
System 2: Yellow - Condenser head cooling fan is Bad. Accumulator is rusted and deteriorating.BallyBB232P-ED-T4B-2423System 1 - 050304776
System 2 - 050304777GreenNoGreenGreenR-404AGreenN/AN/AGreenGreenN/AGreenGreenGreenSiemensN/AGreenGreenGreenYellow - Both systems need accumulator reinsulated and 1 length of insulation replaced.GreenN/AN/AProbe within toleranceGreenN/AWill quote to replace accumulator and section of insulation on both units, and head cooling fan on system 2 compressor.
6/12/24FM0428055'x26'x118"N/ASliding Door - 80"x95"; Person Door - 36"x78"GreenNZPCommissary3002 Connecticut Ave NWWashington DC 20008172C Vegetable Box100M7NoYesUnknownHVAC/Facilities may have recordsShoe chemical bath at entrance of commisary. Escaped animal codes: Green - Non dangerous Red - DangerousYesYes39FN/AN/AN/AN/AGreen - System 1: 3/4 of sight glass; Green - System 2: 3/4 of sight glassGreen - System 1 Full ; Green - System 2 Full2003Room 100M7 Panel 4S5 System 1 Breaker 8/10/12 System 2 Breaker 31/33/35GreenSystem 1 20A System 2 15ANoYesLocalNoYesYesWaterPush bar for person door. Manual release for sliding door.BallyBmil82-037205I-LL3-00108BCopeland Model - ZDL3R78KE-TFD-800 Serial - ZDL3-075ETFD200GreenBallyBW750M8-IT4A-1978System 1 - 050304598 System 2 - 050304597Water CooledSystem 1: Red - System intermittently short cycling due to going off on head pressure. Opened water regulating valve fully, no change.
System 2: GreenBallyBB374P-A-T4B-T52A1System 1 - 050304774 System 2 - 050304775GreenNoNoGreenSystem 1 R448A ; System 2 R-22GreenGreenN/AYellow - Sliding door opener is off at switch, door must be opened manually. Customer stated another contractor is working on repair.Yellow - Person door sweep is torn.N/AGreenGreenGreenN/ASliding door motor replacedGreenGreenGreenYellow - 3 lengths of insulation on drain needs replacedYellow - 13 bulbs need replacedN/AN/AProbes within toleranceGreenCustomer stated they saw system 1 short cycling. Unit is currently holding temp, charge is Good and unit is not currently short cycling.Drain line needs 3 lengths of insulation replaced. Person door needs door sweep replaced. 13 Light bulbs need replaced. Replace system 2 condenser and evap in order to convert refrigerant from R-22 to R448A. System 1 needs water cooled condenser cleaned and further evaluated.
6/17/24FM043229'x15'x12'N/A5'x11'GreenNZPNecropsy Bldg3003 Connecticut Ave NWWashington DC 20008Necropsy Lab SpaceOutside of buildingNoYesPossible FacilitiesPossible FacilitiesN/AYesYes4cN/AN/AGoodN/AN/AGoodUnknownPanel: NE1 Breakers: 13,15,17Good20AYesYesLocalYesNoYesSprinkler SystemN/AUnknownJohnson ControlsPenn Mechanical T-StatN/ACopeland MDL# ZS13KAE-TF5-118, SN# 22D5128GLGoodTrentonTEZA015H8-HT3D-8229241858Air cooledGoodTrenton
6/17/24FM0432116'x34'9'N/A7'x8'YellowNZPCommissary3004 Connecticut Ave NWWashington DC 20008FZR 2 172B100 M7N/AYesPossible FacilitiesPossible FacilitiesAnimal Escaped alarmYesYes-20CN/AN/AGoodN/AGoodGoodUnknownPanel: 4SF Breakes: 37,39,41/38,40,42Good20AYesYesLocalYesYesN/AN/AN/APart of BldgControlled Remotley Through SiemensN/AN/ACopeland MDL# 3DB3F33KE-TFD-800GoodBallyBW750L6-IT4A-1979050304599, 050304600Water CooledN/ABally
6/12/24FM042867.5x'16.5'x11.5'N/A36'x96.5"YellowNZPCommissary3005 Connecticut Ave NWWashington DC 20008174A Banana Box100M7NoYesUnknownHVAC/Facilities may have recordsShoe Chemical bath at entrance to commisary. Escaped animal codes: Green - Non-dangerous Red - DangerousNoYes55FN/AN/AN/AN/AGreen 3/4 Sight glassFull2004Room 100M7 Panel 4S5 Breaker 26/28/30Green15ANoYesLocalNoNoYesWaterPush button on interior of doorPart of buildingPennA421N/ACopeland Model - ERFA-031E-TAD-800 Serial - 20L60207RGreenBallyBW300M8-IT4A-202150401622Water CooledYellow - Was tripped on head pressure, reset and now operatingBally
6/13/24FM0427946'x31'/22.5'x10.5'N/ADouble door to box - 83"x96" ; Single door to 172A - 83"x96"; Single door to 172B - 83"x96"; Single door to 172C - 83"x96"YellowNZPCommissary3006 Connecticut Ave NWWashington DC 20008172 Meat Prep Room100M7NoYesUnknownHVAC/Facilities may have recordsShoe chemical bath entering commissary. Escaped animal codes: Green - Non dangerous Red - Dangerous
Emergency phone.YesYes38FN/AN/AN/AN/AGreen System 1 half full ; System 2 half fullSystem 1 Full; System 2 Full2004Room 100M7 Panel 4S5 System 1 Breaker 14/16/18 System 2 Breaker 26/28/30Greensystem 1 15a System 2 15aNoYesLocalNoYesYesWaterPush bar on main entrance doorPart of buildingBmil82-0526-0018F82-0526-00-00340H02F650Copeland Model # ZDC3-050ETFD200 System 1 Serial - CCJ0514010 System 2 Serial - CCJ0514009GreenBallyBW500M8-IT4A-2020System 1 - 050401620 System 2 - 050401619Water cooledGreenBallyBA255P-A-S1A-TSM2A1System 1a Serial - 050401973 System 1b Serial - 050401976 System 2a Serial - 050401974 System 2B Serial - 050401975GreenNoN/AGreenR-22GreenGreenN/AN/AGreenN/AGreenGreenYellow - Has possible water leak in a small spot near main door. Leak is coveRed up with tape and plastic. Ceiling is part of the building.
6/13/24FM0427814.5'x7.5'x11.5'N/A35 3/4"x96"RedNZPCommissary3007 Connecticut Ave NWWashington DC 20008174100M7NoNoUnknownHVAC/Facilities may have recordsChemical shoe bath entering commisary. Escaped animal codes: Green - Non Dangerous Red - DangerousNoNo40FN/AN/AN/AN/AYellow - Bottom of glass (may be due to running low on gas, oil should return to compressor once back online)Red2004Room 100M7 Panel 4S5 Breaker 25/27/29Green15ANoYesLocalNoNoYesWaterPush button inside doorPart of buildingDanfossAD169-00N/ACopeland Model - ERFA-031E-TAD-800 Serial - 21B62100RUnknownBallyBW300M8-IT4A-22150401621Water cooledunknownBally
6/26/249128411'x11'x7'N/A3'x8'YellowNZPResearch Building3008 Connecticut Ave NWWashington DC 200081st Floor HallwayOn the roofNoYesFacilitiesYesNoYesYes-18FN/AN/AGoodN/AN/AR448AUnknownPanel: PNL-PCC, Breaker 31Good20AYesYesLocalyesNoNoN/AN/ABallyJohnson ControlsPenn Mechanical ThermostatN/ACopeland MDL# ZF08K4E, SN# 16G2126ADN/ATrentonTEZA025L8-HT3B-F160352531TAir CooledN/ATrenton
6/25/24912867'X4'X6N/A3'X6'YellowNZPResearch Building3009 Connecticut Ave NWWashington DC 20008B05/Migration Bird Center LabOn top of the boxN/AYesFacilitiesFacilitiesN/AYesYes40FN/AN/APoorN/AN/ABubblesUnkownPanel: PNL-PA, Breaker: 13,15GoodUnknownYesNoN/ANoNoYesSprinkler SystemN/AN/AJohnson ControlsPenn Mechanical ThermostatN/ATecumseh MDL: AK168AT-038-PZ, SN: AKA446OYAAN/ATecumsehAKA4460YXAXC0A81074222Air CooledN/ABOHN
6/26/249120911'x6'x8'N/A3'x8'YellowNZPResearch Building3010 Connecticut Ave NWWashington DC 200081st Floor HallwayOn the roofNoYesPossibly facilitiesYesN/AYesYes40FN/AN/AGoodN/AN/AGoodUnkownUnknownGoodUnkownYesYesLocalYesNoYesSprinkler SystemNoBallyESP Controller on EvaporatorESP+N/ACopeland Mdl# ZB07KAE-TF5-118, SN# 20G17E62LN/ATrentonTEZA008H8-HT3D-B209447802Air CooledN/ATrenton
6/25/24FM0440011'X9'712'X10'X8'3'X6'RedNZPResearch Bldg3011 Connecticut Ave NWWashington DC 20008OutsideOn top of boxYesNoPossibly facilitiesPossibly facilitiesNoNoNoN/AN/AN/AN/AN/AN/AN/AN/AUnkownPoorUnkownN/AYesLocalN/ANoNoNoN/ACrownTonkaJohnson ControlsPenn Mechanical ThermostatN/ACopelandPoorRussellRLO400L44-EG04257416-0101Air CooledN/ARussel
6/25/2464147'x7'x8'N/A3'x6'RedNZPVet Hospital3012 Connecticut Ave NWWashington DC 20008HallwayOn top of BoxNoNoUnknownUnknownNoNoNoN/AN/AN/AN/AN/AN/AN/AAll Equipment ManufacteRed in 87', Box manufactuRed is unknownPanel: ELA RM213 Breaker: 31-35N/A15ANoN/AN/AN/AN/AYesSprinkler SystemN/AN/AJohnson ControlsPenn Mechanical T-statN/ACopeland MDL# KALA-0150-TAC, SN# 91F-74N/ACopelandC7AB-0150-TAC-00102K87Air CooledN/ABOHN
6/26/2443955'1" x 5'1" x 6'10"5'9" x 5'9" x 7'2"3' x 6'5"RedNZPLion & Tiger Building3013 Connecticut Ave NWWashington DC 20008Big Cat's KitchenNext to Walk-InNoNoUnknownUnknownNoNoUnit has been turn off for some time.N/AN/AN/AN/AN/AN/AN/ACondenser dates back to 99'Panel 2A, Breaker 27&28Poor30ampYesNoN/AN/ANoNoN/ANoUnknownJohnson Controls Mechanical ThermostatPennN/ACopelandMDL# CS14K6E-PFV-273, SN# 99FH7291H, 208VCopelandFJAL-A200-CFV-00109G99Air Cooled208-230vHeatCraft
6/26/2443967'2" x 5'5" x 7'7'10" x 6' x 8'3'x 6'7'YellowNZPGreat Apes Building3014 Connecticut Ave NWWashington DC 20008KitchenNext to Walk-InNoYesUnknownUnknownNoYesYesFN/AN/AOkayN/AN/ABubblesUnknownPanel PNL LVAA, Breaker 37, Panel In hallway.Okay20YesNoN/ANoNoYesWater SprinklerNoArtic, Walk-in MDL# 40 5.10x7.10, SN# 22089Saginomiya Mechanical ThermostatN/AN/ACopelandCompressor MDL# RST55C1E-CAV-109, SN# 1022736, 208-230VCopelandM4FF-0075-CAV-02010E407020Air Cooled208-230VKeepRite
9/5/24FM043497'1"x13'2"x7'6"8'x14'x8'4"3'x6'7"GreenSCBI2451500 Remount Rd, Front Royal, VA 22630Outside next to buildingOn top of boxYesYesOFMROFMRNOYesYes-10FN/AN/AGoodN/AGoodGoodApprox. 03/2024UnknownGoodUnknownYesYesLocalYesNoNoN/ANoPolar kingthermsolutionsKE2N/AZF11K4E-PFV-231Brand newCopelandFFAL-A26Z-CFV-07523HA0089UAir cooledBrand newHeat transfer product group
9/4/24FM007157'1"x10'11'x7'10"7'9"x11'7"x8'6"3'2x6'6"YellowSCBIResearch Biorepository Lab1501 Remount Rd, Front Royal, VA 22630Outside towards the left side of the buildingOn top of boxYesNoOFMROFMRNoNoNo-10FN/AN/AN/AN/AN//AN/AUnknownUnknownGoodUnknownYesYESLocalYesNoNoN/AN/AStandex RefrigerationJohnson ControlsPennN/ACopeland MDL# CF09K6E-PFV-295, SN# 18KAN037MN/ACopelandCPF200DC0-A19060125Air CooledSystem is a package unitN/A
9/4/24FM0398110'x12'10"x6'9"11'7"x13'6"x7'5.5"36"74"RedSCBICommissary1502 Remount Rd, Front Royal, VA 22630133 MDPOn top of the boxN/AYesOFMROFMRNoYesYes34FN/AN/AGoodN/AN/AHas BubblesApprox. from 2005Panel: 701 0133 Breakers: 32,34,36Good30AYesYesLocalNoNoNoN/AN/AW.A.Brown & Son, INCJohnson ControlsPennN/ACopeland, MDL: CS10K6E-TF5-277, SN# 05A20650HN/ACopelandFTAH-A101-TFC-00127A05Air CooledN/AHeatCraft
9/4/24903207'1"X6'1"X6'9"7'9-1/2"X6'9-1/2"X7'6"36"X73"YellowSCBI133/commisary1503 Remount Rd, Front Royal, VA 22630CommisaryOn top of boxNoYesN/AN/AN/AYesYes8fN/AN/AYesN/AN/AHalf fullN/APanel-701 0133 breakers 27 25 29Good30 ampNoYesLocalYesNoNoN/ANoW.A. BROWN & SON,INCWhite-RodgersN/AN/ACopeland MDL-CF06K6E-TF5-253Bad-roto lock rustedCopelandFJAL-B200_TFC-00108C20044UAircooledGoodTrenton
9/5/24FM042695'2"x7'2"x6'10"5'10"x7'10"x7'6"3'x6'5"GreenSCBIOutside Vet Hospital1504 Remount Rd, Front Royal, VA 22630Outside FrontMounted behind the walk-inYesYesUnknownUnknownNoYesYes37FN/AN/AYesN/AN/AGoodApprox. 2007Breakers located on the box by the condenserGood20AYesYesLocalNoNoNoN/AN/AU.S. CoolerJohnson ControlsPennN/ACopeland MDL# RS47C2-IAV-101, SN# 07G31808BN/ACopelandF3AH-A078-IAV-02007H40296UAir CooledN/AHTP SCOTTSBORO
8/27/24FM0425811'3x9'7x8'1010'2x10'1x9'23'2x6'6GreenSERCCharles Mathias Laboratory Building 100647 Contees Wharf RdEdgewater, MD 2103716On top of boxNoYesYes-OFMRYes-OFMRNoYesYes28.0cN/AN/AN/AN/AN/AGoodApprox. 29JAN2013Panel: A-LAB-B1W, Breakers: 31,33,35 & 37,39,41Good20A & 30AYesYesLocalYesNoYesWater Sprinkler SystemN/AEnvironmental Growth ChambersEGCTC2N/ACopeland Reciprocating MDL#RST70C1E-TA5-959 SN#24B02302EN/AHeatcraftHWN010X6CT13A06396Water CooledN/AN/A
8/28/24FM0436611'3x9'8x8'1110'2x10'1x9'23'2x6'7GreenSERCCharles Mathias Laboratory Building 100648 Contees Wharf RdEdgewater, MD 2103718On top of boxNoYesYes-OFMRYes-OFMRNoYesYes20.0cN/AN/AN/AN/AN/AGoodApprox. 29JAN2013Panel: A-LAB-B1W, Breakers: 32,34,36 & 38,40,42Good20A & 30AYesYesLocalYesNoYesWater Sprinkler SystemN/AEnvironmental Growth ChambersEGCTC2N/ACopeland Reciprocating MDL#RST70C1E-TA5-211 S#16K004823EN/AHeatcraftHWN0100X6CT17A09924Water CooledN/AN/A
8/28/24FM0436611'3x9'8x8'1110'2x10'1x9'23'2x6'7GreenSERCCharles Mathias Laboratory Building 100649 Contees Wharf RdEdgewater, MD 2103720On top of boxNoYesYes-OFMRYes-OFMRNoYesYes18.0cN/AN/AN/AN/AN/AGoodApprox. 29JAN2013Panel: AP-B1, Breakers: 29,31,33 & 35,37,39Good20A & 30AYesYesLocalYesNoYesWater Sprinkler SystemN/AEnvironmental Growth ChambersEGCTC2N/ACopeland Reciprocating MDL# RST70C1E-TA5-959, SN# 18B05587EN/AHeatcraftHWN010X6CT13A06394Water CooledN/AN/A
8/13/24FMO43657'7"x7'9.5"x8'49'Wx8'8"H3'3"Wx6'6"GreenSERCCharles Mathias Laboratory Building 100650 Contees Wharf RdEdgewater, MD 210371022On top of BoxN/AYesYes-OFMRYes- OFMRNoYesYes4CN/AN/AGoodN/AN/AGood29-Jan-13Panel: A-LAB-1W5, Breakers: 13,15,17 & 19,21,23Good30AYesYesLocalYesNoYesWater Sprinkler SystemN/AEnvironmental Growth Chamber MDL#2173-1, SIZE: 36P78Environmental Growth Chanber ControlerEGC- TC2N/ACopeland MDL# RST70C1E-TA5-959, SN# 19J09981EN/AHeatcraftHWN010X6CT13A06397Water Cooled CondenserN/AHeatcraft
8/13/24FM043647'5x8'4x10'108'8xN/Ax8x83'2"x6'6"GreenSERCCharles Mathias Laboratory Building 100651 Contees Wharf RdEdgewater, MD 210372024OnNoYesYes-OFMRYes-OFMRNoYesYes4cN/AN/APoorN/AN/AGood29-Jan-13Panel: A-LAB-2W6, Breakers: 11,13,15 & 17,19,21Good20A & 30AYesYesLocalYesNoYesWater Sprinkler SystemN/AEnvironmental Growth ChambersEnvironmental Growth ChambersEGC-TC2N/ACopeland MDL# RST70C1E-TA5-211, SN# 12L06382EN/AHEATCRAFTHWN010X6CT13A06395Water CooledN/AHeatcraft
8/27/24FM043506'1'x8'5"x6'11"8'3"x9'x8'7"3'3"x6'6"GreenSERCCharles Mathias Laboratory Buiding 100652 Contees Wharf RdEdgewater, MD 210376On top of the boxNoYesYes-OFMRYes-OFMRNoYesYes4.0CN/AN/AN/AN/AGoodGoodApprox. 89'Breaker Panel Located in front of the boxGood10A & 15AYesYesLocalYesNoNoN/AN/APercival ScientificPercival ScientificSeries 101N/ACopeland Scroll MDL# ZB21KCE-TF5-240, SN# 14G5954ADN/AKeeprite RefrigerationKXZA030H8-IT3A-19830142404642Water CooledN/AN/A
8/14/24FM043527'4"x8'4"x7'9'xN/Ax8'7"3'3"x6'3"GreenSERCCharles Mathias Laboratory Building 100653 Contees Wharf RdEdgewater, MD 2103710OnNoYesYes-OFMRYes-OFMRNoYesYes-10FN/AN/AGoodN/AN/AGood29-Jan-13There is a panel attached on the front of the box on breakers 2, 3, 4, 5, 8 6. This panel receives power from panel BSMT - PP In Room 0017 on breakers 23, 25, & 27.Good30AYesYesLocalYesNoN/AN/AN/ANorlake ScientificMasterBilt / Refrigerated Solutions Group05-02585E332201164Copeland M#ZF06KAE-TF5-118 S#22108C07LThis compressor has liquid injectionNorlake ScientificMS223296622110061Air CooledN/AMasterBilt / Refrigerated Solutions Group
8/14/24FM043516'9"x8'4"x6'11"8'1'"N/Ax9'3'3"x6'6"GreenSERCCharles Mathias Labortory Building 100654 Contees Wharf RdEdgewater, MD 210378On top of boxNoYesYes-OFMRYes-OFMRNoYesYes15.0cN/AN/AN/AN/AN/AGoodApprox 20+YearsBreaker Panel located in front of the boxGood10A&15AYesYesLocalYesNoNoN/AN/APercival ScientificPercival ScientificSeries 101N/ACopeland M#ZS11KAE-TF5-118 S#14J83F06LN/AKeepRite RefrigerationKXZA011H8-iT3A-19831142404643Water CooledN/AN/A
3005 Connecticut Ave NWWashington DC 20008