3-Z Asbestos Survey - 1904 E. Santa Fe St. - 02237230.pdf
PDF 1 MB Posted
- Solicitation number
- 3-C-025-18
- Issued by
- Johnson County, Kansas
About this file
This is an asbestos survey report conducted by Terracon Consultants, Inc. for the City of Olathe, Kansas regarding a Hertz Rental Car facility located at 1904 East Santa Fe Street in Olathe, Kansas. The survey was performed on May 30, 2025, and the report was completed on June 27, 2025, under Terracon Project Number 02237230. The survey involved visual and physical assessment of the building for asbestos-containing materials, with 45 bulk samples collected from 15 homogeneous areas throughout the approximately 576-square-foot standalone store with exterior canopy and 665-square-foot car wash, both constructed in the 1980s.
The survey identified one type of asbestos-containing material: roofing sealant containing 10-15% chrysotile asbestos located on the upper canopy perimeters and car wash roof, totaling an estimated 318 linear feet and classified as Category I Nonfriable under NESHAP regulations. The report recommends that all asbestos-containing materials be removed by a qualified abatement contractor prior to any demolition or renovation activities that may disturb these materials, in accordance with federal, state, and local regulations. Sample analysis was conducted by Eurofins International Asbestos Testing Laboratories using EPA-approved methods, and the survey was performed by Kansas state-accredited asbestos inspectors Ryan Slanczka and Blake Harris.
View the file
Other files
Show 40 more
Latest 50 of 54 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Facilities | Environmental | Geotechnical | Materials I
City of Olathe Public Improvements
Asbestos Survey
Hertz Rental Car
1904 East Santa Fe Street
Olathe, Kansas 66062
June 27, 2025 | Terracon Project Number: 02237230
Prepared for:
City of Olathe Kansas
100 East Santa Fe Street
Olathe, KS 66061
15620 W 113th Street
Lenexa, KS 66219
P (913) 492-7777
F (913) 492-7443
Terracon.com
Facilities | Environmental | Geotechnical | Materials i
June 27, 2025
City of Olathe, Kansas
100 East Santa Fe Street
Olathe, KS 66061
Attn: Ms. Therese Vink
P: (913) 971-9032
E: tmersmann@olatheks.org
Re: City of Olathe Public Improvements Asbestos Survey
Hertz Rental Car
1904 East Santa Fe Street
Olathe, Kansas 66062
Terracon Project No: 02237230
Dear Ms. Vink:
Terracon Consultants, Inc. (Terracon) is pleased to provide the City of Olathe, Kansas, with this report regarding an asbestos survey conducted at the above-referenced location in Olathe, Kansas.
Asbestos
Asbestos was identified at a concentration greater than 1% in samples collected from the following materials:
Material Description Material Location
NESHAP
Category
Estimated
Quantity
Roofing Sealant
Upper Canopy - North and
South Perimeters; Car
Wash Roof Perimeter and
Vent Pipe
Category I
Nonfriable 318 Linear Feet
Notes: NESHAP – National Emission Standards for Hazardous Air Pollutants
City of Olathe Public Improvements Asbestos Survey
Hertz Rental Car | Olathe, Kansas
June 27, 2025 | Terracon Project No. 02237230
Facilities | Environmental | Geotechnical | Materials ii
Please refer to Section 3.0 of the attached report for a detailed description of the asbestos survey, sampling activities, and findings.
Terracon appreciates the opportunity to provide this service to the City of Olathe, Kansas. If you have any questions regarding this report, please contact our office at
913-492-7777.
Sincerely, Terracon
Ryan Slanczka Clark Grisell
Senior Staff Scientist Environmental Group Manager
Building Environmental Sciences
Ryan Slanczka Clark Grisell
Facilities | Environmental | Geotechnical | Materials iii
Table Of Contents
1.0 Introduction 1
1.1 Reliance 1
2.0 Building Description 1
3.0 Asbestos-Containing Materials Survey 1
3.1 Visual Assessment 2
3.2 Physical Assessment 2
3.3 Sample Collection 2
3.4 Sample Analysis 2
3.5 Regulatory Overview 3
3.6 Findings 3
4.0 General Comments 4
Appendices
Appendix A Asbestos-Containing Materials By Homogeneous Area
Appendix B Asbestos Survey Sample Location Summary
Appendix C Asbestos Laboratory Analytical Results
Appendix D Certifications
Facilities | Environmental | Geotechnical | Materials 1
1.0 Introduction
Terracon Consultants, Inc. (Terracon) conducted an asbestos-containing material survey of the Hertz Rental Car located at 1904 East Santa Fe Street in Olathe, Kansas, on May
30, 2025. Building areas were visually assessed for suspect asbestos-containing materials (ACM). A reasonable effort was made to inspect accessible areas. Additional suspect materials could be present in walls, voids, or other concealed areas.
1.1 Reliance
This report is for the exclusive use of the City of Olathe, Kansas, for the project being discussed. Reliance by any other party on this report is prohibited without the written authorization of Terracon and the City of Olathe, Kansas.
2.0 Building Description
The subject building is an approximately 576-square-foot, single-story, standalone store
(with exterior canopy), reportedly constructed in 1981. The site also includes a 665-square-foot car wash, reportedly constructed in 1989. Interior flooring finishes include ceramic tiles over concrete. Interior walls throughout the building are drywall/joint compound wallboard, with ceramic tile finishes in the restrooms. Perimeter walls throughout the building are concrete block. The primary, observable ceiling system is a drop, grid ceiling with lay-in acoustic tiles below a metal deck. The building’s exterior has brick and exterior insulation and finish system (EIFS) siding. The roof consists of a single-ply tar and gravel system.
3.0 Asbestos-Containing Materials Survey
The survey was conducted by Mr. Ryan Slanczka and Mr. Blake Harris, State of Kansas-accredited asbestos inspectors. Copies of the asbestos inspectors’ accreditations are attached as Appendix D. The survey was conducted in general accordance with the sample collection protocols established in the United States Environmental Protection
Agency (USEPA) 40 Code of Federal Regulations (CFR) Part 763 Subpart E 763.86, the
Asbestos Hazard Emergency Response Act (AHERA). A summary of survey activities is provided below.
Facilities | Environmental | Geotechnical | Materials 2
3.1 Visual Assessment
Survey activities were initiated with visual observation of the interior and exterior of the building to identify homogeneous areas of suspect ACM. A homogeneous area (HA) consists of a building material that appears similar throughout in terms of color and texture, with consideration given to the date of application. The assessment was conducted in visually accessible areas of the building scheduled for renovation.
3.2 Physical Assessment
A physical assessment of each HA of suspect ACM was conducted to assess the friability and condition of the materials. A friable material is defined by the USEPA as a material that can be crumbled, pulverized, or reduced to powder by hand pressure when dry.
Friability was assessed by physically touching suspect materials.
3.3 Sample Collection
Based on the results of the visual observation, bulk samples of suspect ACM samples were collected in general accordance with USEPA AHERA sampling protocols. Samples of suspect materials were collected from randomly selected locations in each homogeneous area. Bulk samples were collected using wet methods, as applicable, to reduce the potential for fiber release. Samples were placed in sealable containers and labeled with unique sample numbers using an indelible marker.
Rubber, wood products, plastic products, glass, and steel are not considered suspect
ACM and were, therefore, not sampled. The selection of sample locations and frequency of sampling were based on Terracon’s observations and the assumption that like materials in the same area are homogeneous in content. Terracon collected 45 bulk samples from 15 homogeneous areas of suspect ACM.
3.4 Sample Analysis
Bulk samples were submitted under chain of custody to Eurofins International Asbestos
Testing Laboratories (Eurofins) of Mount Laurel, New Jersey, for analysis by PLM with dispersion staining techniques per USEPA Method 600/R-93/116. The percentage of asbestos, where applicable, was determined by microscopic visual estimation. Eurofins is accredited under the National Voluntary Laboratory Accreditation Program (NVLAP), Accreditation No. 101165.
Facilities | Environmental | Geotechnical | Materials 3
3.5 Regulatory Overview
The asbestos National Emission Standards for Hazardous Air Pollutants (NESHAP) regulation (40 CFR Part 61, Subpart M) regulates asbestos fiber emissions and asbestos waste disposal practices. The asbestos NESHAP regulation also requires the identification and classification of existing ACM according to friability prior to demolition or renovation activity. Friable ACM is a material containing more than 1% asbestos that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure.
The asbestos NESHAP regulation classifies ACM as regulated asbestos-containing materials (RACM), Category I non-friable ACM, or Category II non-friable ACM. RACM includes all friable ACM; Category I non-friable ACM that has become friable or will be or has been subjected to sanding, grinding, cutting, or abrading; and Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder in the course of renovation or demolition activity. Category I non-friable ACM are exclusively asbestos-containing packings, gaskets, resilient floor coverings, resilient floor covering mastics, and asphalt roofing products that contain more than 1% asbestos. Category II non-friable ACM are all other non-friable materials other than Category I non-friable ACM that contain more than 1% asbestos. Category II non-friable ACM generally includes but is not limited to cementitious material such as cement pipes, cement siding, cement panels, glazing, mortar, and grouts.
The Kansas Department of Health and Environment’s (KDHE) Asbestos Control Section within the Bureau of Air enforces the Asbestos NESHAP as adopted by reference at
Kansas Administrative Regulations (K.A.R.) 28-19-735. The owner or operator must provide KDHE with written notification at least 10 working days prior to the commencement of asbestos abatement activities that will disturb RACM in amounts greater than or equal to 10 square feet or 25 linear feet.
The United States Occupational Safety and Health Administration (USOSHA) asbestos standard for construction (29 CFR 1926.1101) regulates workplace exposure to asbestos. The OSHA standard classifies construction and maintenance activities that could disturb ACM and specifies work practices and precautions that employers must follow when engaging in each class of regulated work. The standard also specifies requirements for handling materials containing asbestos in concentrations less than or equal to one percent.
3.6 Findings
Asbestos was identified at a concentration greater than 1% in samples collected from the following materials:
Facilities | Environmental | Geotechnical | Materials 4
Material Description Material Location
NESHAP
Category
Estimated
Quantity
Roofing Sealant
Upper Canopy - North and
South Perimeters; Car
Wash Roof Perimeter and
Vent Pipe
Category I
Nonfriable 318 Linear Feet
Notes: NESHAP – National Emission Standards for Hazardous Air Pollutants
The above-listed Category I non-friable ACM that is damaged or could be damaged to the extent that it could be crumbled, pulverized, or reduced to powder when dry, making it friable, must be removed prior to any activities (renovation and/or demolition) that may disturb this material in accordance with applicable federal, state, and local regulations. Terracon recommends that all ACM be removed by an abatement contractor prior to any demolition or renovation work that may disturb it.
Asbestos was not detected at a concentration of 1% or less in any samples collected from the subject building.
A summary of identified asbestos-containing materials by homogeneous area is included in Appendix A. A summary of sample locations is included in Appendix B. Laboratory analytical reports are included in Appendix C.
4.0 General Comments
Terracon did not perform sampling that required demolition or destructive activities such as dismantling of equipment or removal of protective coverings. Reasonable efforts to access suspect materials within known areas of restricted access (e.g., crawl spaces) were made; however, confined spaces or areas that may pose a health or safety risk to
Terracon personnel were not sampled. Sampling did not include suspect materials that could not be safely reached with available ladders or manlifts. Terracon did not sample suspect materials that may be present in movable equipment such as freezers, kitchen equipment, and hoods. Terracon typically investigates for flooring beneath carpeting by lifting small corner sections of carpet. If tiles or sheet vinyl were seen, they have been identified in the report. If tiles or sheet vinyl were not seen at corners under the carpet, it does not imply that there is none beneath the carpeted floor. Terracon did not conduct a destructive investigation of the doors in the building to determine if the doors were insulated for fire-rating purposes.
This survey was conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions, and recommendations expressed in this report are based on conditions observed during Terracon’s survey of the building. The information contained in this report is relevant to the date on which
Facilities | Environmental | Geotechnical | Materials 5 this survey was performed, and should not be relied upon to represent conditions at a later date. This report has been prepared on behalf of and exclusively for use by the City of Olathe, Kansas, and is not a bidding document. Contractors or consultants reviewing this report must draw their own conclusions regarding further investigation or remediation deemed necessary. Terracon does not warrant the work of regulatory agencies, laboratories, or other third parties supplying information that may have been used in the preparation of this report. No warranty, express or implied, is made.
Appendix A
Asbestos-Containing Materials By Homogeneous Area
Appendix A
Identified Asbestos-Containing Materials By Homogeneous Area (HA)
1904 East Santa Fe Street, Olathe, Kansas
Terracon Project No. 02237230
HA Material Description Material Location % and Type
Asbestos*
NESHAP
Classification Condition
Estimated
Quantity**
15 Roofing Sealant
Upper Canopy - North and South Perimeters;
Car Wash Roof Perimeter and Vent Pipe
Black Sealant - 15%
Chrysotile
Category I
Nonfriable Good
Linear Feet
*% & Type Asbestos – this column contains both the analytical result of the sample with the highest concentration of asbestos detected in the samples that make up the HA, and the types of asbestos identified.
**Estimated quantities – quantities based on a cursory field evaluation, and actual quantities may vary significantly, especially if asbestos-containing materials are present in hidden and/or inaccessible areas not evaluated as part of this survey. This is not a bidding document; contractors are responsible for determining their own opinion of quantities.
Appendix B
Asbestos Survey Sample Location Summary
Appendix B
Asbestos Survey Sample Location Summary
1904 East Santa Fe Street, Olathe, Kansas
Terracon Project No. 02237230
HA
No.
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
1 Drywall with Joint Compound
01-WB5-01 NW Room, Ceiling
White Drywall with Brown Paper
None Detected
White Joint Compound
01-WB5-02 Central Room, South Wall
White Drywall with Brown Paper
White Joint Compound
01-WB5-03 South Room, South Wall
White Drywall with Brown Paper
White Joint Compound
2' x 2' Ceiling Tile with Pinholes and Divots
02-CT3-04 Central Room, Central Area White Ceiling Tile
None Detected 02-CT3-05 South Room, North Area White Ceiling Tile
02-CT3-06 South Room, South Area White Ceiling Tile
2' x 2' Ceiling Tile with Pinholes and Fissures
03-CT3-07 Central Room, South Area White Ceiling Tile
None Detected 03-CT3-08 Central Room, Central Area White Ceiling Tile
03-CT3-09 South Room, South Area White Ceiling Tile
4" x 4" Tan Ceramic Wall Tile with Adhesive and Grout 04-MA5-10 NW Room, West Wall
Tan Ceramic Tile
None Detected Yellow Adhesive
White Grout
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
4" x 4" Tan Ceramic Wall Tile with Adhesive and Grout
04-MA5-11 NW Room, North Wall
Tan Ceramic Tile
None Detected
Yellow Adhesive
White Grout
04-MA5-12 NW Room, East Wall
Tan Ceramic Tile
Yellow Adhesive
White Grout
12" x 12" Grey with Spots
Ceramic Floor Tile with Grout and Mortar
05-MA5-13 Central Room, West Area
Grey Ceramic Tile
None Detected
Grey Grout
White Mortar
05-MA5-14 South Room, North Area
Grey Ceramic Tile
Grey Grout
White Mortar
05-MA5-15 South Room, South Area
Grey Ceramic Tile
Grey Grout
White Mortar
12" x 12" Tan Ceramic Floor
Tile with Grout and Mortar 06-MA5-16 NW Room
Tan Ceramic Tile
None Detected Dark Grey Grout
Light Grey Mortar
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
12" x 12" Tan Ceramic Floor
Tile with Grout and Mortar
06-MA5-17 NW Room
Tan Ceramic Tile
None Detected
Dark Grey Grout
Light Grey Mortar
06-MA5-18 NW Room
Tan Ceramic Tile
Dark Grey Grout
Light Grey Mortar
8" x 8" Ceramic Floor Tile with
Grout and Mortar
07-MA5-19 NE Room
White/Brown Ceramic Tile
None Detected
Black Grout
Grey Mortar
07-MA5-20 NE Room
White/Brown Ceramic Tile
Black Grout
Grey Mortar
07-MA5-21 NE Room
White/Brown Ceramic Tile
Black Grout
Grey Mortar
Batt Insulation with Paper
Backing
08-AW1-22 South Room, SW Area
Tan/Black Tar Paper
None Detected
Pink Insulation
08-AW1-23 South Room, SW Area
Tan/Black Tar Paper
Pink Insulation
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
Batt Insulation with Paper
Backing 08-AW1-24 South Room, SW Area
Tan/Black Tar Paper
None Detected
Pink Insulation
9 CMU Mortar
09-MA2-25 NW Room, West Wall Grey Mortar
None Detected 09-MA2-26 Central Room, North Wall Grey Mortar
09-MA2-27 South Room, South Wall Grey Mortar
10 Brick Mortar
10-MA1-28 East Exterior, near Door Grey Mortar
None Detected 10-MA1-29 North Exterior, near NE Door Grey Mortar
10-MA1-30 West Exterior, near Door Grey Mortar
11 EIFS Siding
11-MS7-31 East Exterior, near Door Grey Cementitious Material
Insulation System (EIFS)
None Detected 11-MS7-32 North Exterior, Central Area Grey Cementitious Material
Insulation System (EIFS)
11-MS7-33 West Exterior, North Area Grey Cementitious Material
Insulation System (EIFS)
12 Door Caulk
12-CA2-34 North Exterior, NE Door Off-White Caulk with Black Paint
None Detected 12-CA2-35 North Exterior, NE Door Off-White Caulk with Black Paint
12-CA2-36 North Exterior, NW Door Off-White Caulk with Black Paint
13 Expansion Joint
13-MS5-37 South Exterior, East Area Black Expansion Joint
None Detected 13-MS5-38 South Exterior, Central Area Black Expansion Joint
13-MS5-39 South Exterior, West Area Black Expansion Joint
14 Roofing Material 14-RF5-40 Roof, West-Central Area
Black Tar with Rocks
None Detected
Black Tar Paper
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
14 Roofing Material
14-RF5-41 Roof, East-Central Area
Black Tar with Rocks
None Detected
Black Tar Paper
14-RF5-42 Roof, North Area, at Vent
Black Tar with Rocks
Black Tar Paper
15 Roofing Sealant
15-RF4-43
Upper Canopy, North Perimeter, Central Area Black Sealant 15% Chrysotile
15-RF4-44
Upper Canopy, South Perimeter, Central Area Black Sealant 15% Chrysotile
15-RF4-45 Carwash Roof, on Vent Pipe Black Sealant 10% Chrysotile
Asbestos-containing materials in BOLD.
Appendix C
Asbestos Laboratory Analytical Results
Approved by:
Approved Signatory Frank Ehrenfeld
Report for:
Ryan Slanczka Terracon Consultants- Lenexa 15620 W. 113th St Lenexa, KS 66219
Regarding:
Eurofins Built Environment Testing East, LLC Project: 02237230.14.2 - 1904 E Santa Fe St
EML ID: 4095650
All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. The results relate only to the samples as received and tested. The results include an inherent uncertainty of measurement associated with estimating percentages by polarized light microscopy. Measurement uncertainty data for sample results with >1% asbestos concentration can be provided when requested.
Eurofins Built Environment Testing East, LLC ("the Company"), a member of the Eurofins Built Environment Testing group of companies, shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results. In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor.
Dates of Analysis:
Asbestos PLM (Layer %): 06-10-2025
Service SOPs: Asbestos PLM (Layer %) (EPA 40CFR App E to Sub E of Part 763 & EPA METHOD 600/R-93-116, SOP EB-AS-S- 1267) NVLAP Lab Code 101165-0
EMLab ID: 4095650, Page 1 of 10Eurofins Built Environment Testing East, LLC
Eurofins Built Environment Testing East, LLC 9000 Commerce Parkway, Suite B, Mount Laurel, NJ 08054
(856) 231-9449 www.eurofinsus.com/Built Client: Terracon Consultants- Lenexa C/O: Ryan Slanczka Re: 02237230.14.2 - 1904 E Santa Fe St
Date of Receipt: 06-03-2025 Date of Report: 06-10-2025
Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM) Appx E Sub E 40 CFR 763 / EPA 600/R-93/116
Sample ID # Lab-ID version Sample Description Asbestos
Constituents Non-Asbestos Constituents Comment
01-WB5-01. Drywall with Joint Compound; NW Room, Ceiling 20428036-1
Layer 1 White Drywall with Brown Paper Homogeneity:Good
Not Detected 90% Non-Fibrous Material 10% Cellulose
Layer 2 White Joint Compound Homogeneity:Good
Not Detected 100% Non-Fibrous Material
01-WB5-02. Drywall with Joint Compound; Central Room, South Wall 20428037-1
Layer 1 White Drywall with Brown Paper Homogeneity:Good
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
01-WB5-03. Drywall with Joint Compound; South Room, South Wall 20428038-1
Layer 1 White Drywall with Brown Paper Homogeneity:Good
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
02-CT3-04. 2'x2' Ceiling Tile with Pinhole and Divots; Central Room, Central Area 20428039-1
Layer 1 White Ceiling Tile Homogeneity:Good
Not Detected 60% Cellulose 30% Glass Fibers 10% Non-Fibrous Material
02-CT3-05. 2'x2' Ceiling Tile with Pinhole and Divots; South Room, North Area 20428040-1
Layer 1 White Ceiling Tile Homogeneity:Good
Not Detected 60% Cellulose
02-CT3-06. 2'x2' Ceiling Tile with Pinhole and Divots; South Room, South Area 20428041-1
Layer 1 White Ceiling Tile Homogeneity:Good
Not Detected 60% Cellulose
03-CT3-07. 2'x2' Ceiling Tile with Pinhole and Fissures; Central Room, South Area 20428042-1
Layer 1 White Ceiling Tile Homogeneity:Good
Not Detected 60% Cellulose
03-CT3-08. 2'x2' Ceiling Tile with Pinhole and Fissures; Central Room, Central Area 20428043-1
Layer 1 White Ceiling Tile Homogeneity:Good
Not Detected 60% Cellulose
03-CT3-09. 2'x2' Ceiling Tile with Pinhole and Fissures; South Room, South Area 20428044-1
Layer 1 White Ceiling Tile Homogeneity:Good
Not Detected 60% Cellulose
Comments:
EMLab ID: 4095650, Page 2 of 10Eurofins Built Environment Testing East, LLC
The total percentage of sample components shown may be greater than 100% when some components are detected at <1%.
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers of that type were detected.
When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
(856) 231-9449 www.eurofinsus.com/Built Client: Terracon Consultants- Lenexa C/O: Ryan Slanczka Re: 02237230.14.2 - 1904 E Santa Fe St
Date of Receipt: 06-03-2025 Date of Report: 06-10-2025
Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM) Appx E Sub E 40 CFR 763 / EPA 600/R-93/116
Sample ID # Lab-ID version Sample Description Asbestos
Constituents Non-Asbestos Constituents Comment
04-MA5-10. 4"x4" Tan Ceramic Wall Tile with Adhesive and Grout; NW Room, West Wall 20428045-1
Layer 1 Tan Ceramic Tile Homogeneity:Good
Not Detected 100% Non-Fibrous Material
Yellow Adhesive
Layer 3
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
04-MA5-11. 4"x4" Tan Ceramic Wall Tile with Adhesive and Grout; NW Room, North Wall 20428046-1
Layer 1 Tan Ceramic Tile
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
04-MA5-12. 4"x4" Tan Ceramic Wall Tile with Adhesive and Grout; NW Room, East Wall 20428047-1
Layer 1 Tan Ceramic Tile
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
Comments:
EMLab ID: 4095650, Page 3 of 10Eurofins Built Environment Testing East, LLC
The total percentage of sample components shown may be greater than 100% when some components are detected at <1%.
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers of that type were detected.
When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(856) 231-9449 www.eurofinsus.com/Built Client: Terracon Consultants- Lenexa C/O: Ryan Slanczka Re: 02237230.14.2 - 1904 E Santa Fe St
Date of Receipt: 06-03-2025 Date of Report: 06-10-2025
Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM) Appx E Sub E 40 CFR 763 / EPA 600/R-93/116
Sample ID # Lab-ID version Sample Description Asbestos
Constituents Non-Asbestos Constituents Comment
05-MA5-13. 12"x12" Grey with Spots Ceramic Floor Tile with Grout and Mortar; Central Room, West Area 20428048-1(cont.)
Layer 1 Gray Ceramic Tile
Gray Grout
White Mortar Homogeneity:Good
Not Detected 100% Non-Fibrous Material
05-MA5-14. 12"x12" Grey with Spots Ceramic Floor Tile with Grout and Mortar; South Room, North Area 20428049-1
Layer 1 Gray Ceramic Tile
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
05-MA5-15. 12"x12" Grey with Spots Ceramic Floor Tile with Grout and Mortar; South Room, South Area 20428050-1
Layer 1 Gray Ceramic Tile
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
Comments:
EMLab ID: 4095650, Page 4 of 10Eurofins Built Environment Testing East, LLC
The total percentage of sample components shown may be greater than 100% when some components are detected at <1%.
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers of that type were detected.
When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(856) 231-9449 www.eurofinsus.com/Built Client: Terracon Consultants- Lenexa C/O: Ryan Slanczka Re: 02237230.14.2 - 1904 E Santa Fe St
Date of Receipt: 06-03-2025 Date of Report: 06-10-2025
Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM) Appx E Sub E 40 CFR 763 / EPA 600/R-93/116
Sample ID # Lab-ID version Sample Description Asbestos
Constituents Non-Asbestos Constituents Comment
06-MA5-16. 12"x12" Tan Ceramic Floor Tile with Grout and Mortar; NW Room 20428052-1(cont.)
Layer 1 Tan Ceramic Tile
Dark Gray Grout
Light Gray Mortar Homogeneity:Good
Not Detected 100% Non-Fibrous Material
06-MA5-17. 12"x12" Tan Ceramic Floor Tile with Grout and Mortar; NW Room 20428053-1
Layer 1 Tan Ceramic Tile
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
06-MA5-18. 12"x12" Tan Ceramic Floor Tile with Grout and Mortar; NW Room 20428054-1
Layer 1 Tan Ceramic Tile
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
Comments:
EMLab ID: 4095650, Page 5 of 10Eurofins Built Environment Testing East, LLC
The total percentage of sample components shown may be greater than 100% when some components are detected at <1%.
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers of that type were detected.
When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(856) 231-9449 www.eurofinsus.com/Built Client: Terracon Consultants- Lenexa C/O: Ryan Slanczka Re: 02237230.14.2 - 1904 E Santa Fe St
Date of Receipt: 06-03-2025 Date of Report: 06-10-2025
Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM) Appx E Sub E 40 CFR 763 / EPA 600/R-93/116
Sample ID # Lab-ID version Sample Description Asbestos
Constituents Non-Asbestos Constituents Comment
07-MA5-19. 8"x8" Ceramic Floor Tile with Grout and Mortar; NE Room 20428055-1(cont.)
Layer 1 White/ Brown Ceramic Tile
Black Grout
Gray Mortar Homogeneity:Good
Not Detected 100% Non-Fibrous Material
07-MA5-20. 8"x8" Ceramic Floor Tile with Grout and Mortar; NE Room 20428056-1
Layer 1 White/ Brown Ceramic Tile
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
07-MA5-21. 8"x8" Ceramic Floor Tile with Grout and Mortar; NE Room 20428057-1
Layer 1 White/ Brown Ceramic Tile
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
Comments:
EMLab ID: 4095650, Page 6 of 10Eurofins Built Environment Testing East, LLC
The total percentage of sample components shown may be greater than 100% when some components are detected at <1%.
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers of that type were detected.
When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(856) 231-9449 www.eurofinsus.com/Built Client: Terracon Consultants- Lenexa C/O: Ryan Slanczka Re: 02237230.14.2 - 1904 E Santa Fe St
Date of Receipt: 06-03-2025 Date of Report: 06-10-2025
Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM) Appx E Sub E 40 CFR 763 / EPA 600/R-93/116
Sample ID # Lab-ID version Sample Description Asbestos
Constituents Non-Asbestos Constituents Comment
08-AW1-22. Batt Insulation with Paper Backing; South Room, SW Area 20428058-1(cont.)
Layer 1 Tan/ Black Tar Paper Homogeneity:Good
Not Detected 60% Cellulose 40% Non-Fibrous Material
Homogeneity:Good
Not Detected 100% Glass Fibers
08-AW1-23. Batt Insulation with Paper Backing; South Room, SW Area 20428059-1
Layer 1 Tan/ Black Tar Paper Homogeneity:Good
Homogeneity:Good
Not Detected 100% Glass Fibers
08-AW1-24. Batt Insulation with Paper Backing; South Room, SW Area 20428060-1
Layer 1 Tan/ Black Tar Paper Homogeneity:Good
Homogeneity:Good
Not Detected 100% Glass Fibers
09-MA2-25. CMU Mortar; NW Room, West Wall 20428061-1
Layer 1 Gray Mortar Homogeneity:Good
Not Detected 100% Non-Fibrous Material
09-MA2-26. CMU Mortar; Central Room, North Wall 20428062-1
Layer 1 Gray Mortar Homogeneity:Good
Not Detected 100% Non-Fibrous Material
09-MA2-27. CMU Mortar; South Room, South Wall 20428063-1
Layer 1 Gray Mortar Homogeneity:Good
Not Detected 100% Non-Fibrous Material
10-MA1-28. Brick Mortar; East Exterior, near Door 20428064-1
Layer 1 Gray Mortar Homogeneity:Good
Not Detected 100% Non-Fibrous Material
10-MA1-29. Brick Mortar; North Exterior, near NE Door 20428065-1
Layer 1 Gray Mortar Homogeneity:Good
Not Detected 100% Non-Fibrous Material
10-MA1-30. Brick Mortar; West Exterior, near Door 20428066-1
Layer 1 Gray Mortar Homogeneity:Good
Not Detected 100% Non-Fibrous Material
11-MS7-31. EIFS Siding; East Exterior, near Door 20428067-1
Layer 1 Gray Cementitious Material Insulation System (EIFS) Homogeneity:Good
Not Detected 85% Non-Fibrous Material 15% Glass Fibers
EMLab ID: 4095650, Page 7 of 10Eurofins Built Environment Testing East, LLC
The total percentage of sample components shown may be greater than 100% when some components are detected at <1%.
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers of that type were detected.
When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(856) 231-9449 www.eurofinsus.com/Built Client: Terracon Consultants- Lenexa C/O: Ryan Slanczka Re: 02237230.14.2 - 1904 E Santa Fe St
Date of Receipt: 06-03-2025 Date of Report: 06-10-2025
Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM) Appx E Sub E 40 CFR 763 / EPA 600/R-93/116
Sample ID # Lab-ID version Sample Description Asbestos
Constituents Non-Asbestos Constituents Comment
11-MS7-32. EIFS Siding; North Exterior, Central Area 20428068-1
Layer 1 Gray Cementitious Material Insulation System (EIFS) Homogeneity:Good
11-MS7-33. EIFS Siding; West Exterior, North Area 20428069-1
Layer 1 Gray Cementitious Material Insulation System (EIFS) Homogeneity:Good
12-CA2-34. Door Caulk; North Exterior, NE Door 20428070-1
Layer 1 Off-White Caulk w/ Black Paint Homogeneity:Good
Not Detected 100% Non-Fibrous Material
12-CA2-35. Door Caulk; North Exterior, NE Door 20428071-1
Layer 1 Off-White Caulk w/ Black Paint Homogeneity:Good
Not Detected 100% Non-Fibrous Material
12-CA2-36. Door Caulk; North Exterior, NW Door 20428072-1
Layer 1 Off-White Caulk w/ Black Paint Homogeneity:Good
Not Detected 100% Non-Fibrous Material
13-MS5-37. Expansion Joint; South Exterior, East Area 20428073-1
Layer 1 Black Expansion Joint Homogeneity:Good
Not Detected 75% Non-Fibrous Material 25% Cellulose
13-MS5-38. Expansion Joint; South Exterior, Central Area 20428074-1
Layer 1 Black Expansion Joint Homogeneity:Good
13-MS5-39. Expansion Joint; South Exterior, West Area 20428075-1
Layer 1 Black Expansion Joint Homogeneity:Good
14-RF5-40. Roofing Mateiral; Roof, West-Central Area 20428076-1
Layer 1 Black Tar w/ Rocks
Homogeneity:Good
Not Detected 80% Cellulose 20% Non-Fibrous Material
14-RF5-41. Roofing Mateiral; Roof, East-Central Area 20428077-1
Layer 1 Black Tar w/ Rocks
Homogeneity:Good
EMLab ID: 4095650, Page 8 of 10Eurofins Built Environment Testing East, LLC
The total percentage of sample components shown may be greater than 100% when some components are detected at <1%.
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers of that type were detected.
When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(856) 231-9449 www.eurofinsus.com/Built Client: Terracon Consultants- Lenexa C/O: Ryan Slanczka Re: 02237230.14.2 - 1904 E Santa Fe St
Date of Receipt: 06-03-2025 Date of Report: 06-10-2025
Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM) Appx E Sub E 40 CFR 763 / EPA 600/R-93/116
Sample ID # Lab-ID version Sample Description Asbestos
Constituents Non-Asbestos Constituents Comment
14-RF5-42. Roofing Mateiral; Roof, North Area, at Vent 20428078-1(cont.)
Layer 1 Black Tar w/ Rocks
Homogeneity:Good
15-RF4-43. Roofing Sealant; Upper Canopy, North Perimeter, Central Area 20428079-1
Layer 1 Black Sealant Homogeneity:Good
15% Chrysotile 85% Non-Fibrous Material
15-RF4-44. Roofing Sealant; Upper Canopy, South Perimeter, Central Area 20428080-1
Layer 1 Black Sealant Homogeneity:Good
15% Chrysotile 85% Non-Fibrous Material
15-RF4-45. Roofing Sealant;
Carwash Roof, on Vent Pipe 20428081-1
Layer 1 Black Sealant Homogeneity:Good
10% Chrysotile 90% Non-Fibrous Material
Comments:
Analyst(s): Maxamillian Roselli
EMLab ID: 4095650, Page 9 of 10Eurofins Built Environment Testing East, LLC
The total percentage of sample components shown may be greater than 100% when some components are detected at <1%.
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers of that type were detected.
When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(856) 231-9449 www.eurofinsus.com/Built Client: Terracon Consultants- Lenexa C/O: Ryan Slanczka Re: 02237230.14.2 - 1904 E Santa Fe St
Date of Receipt: 06-03-2025 Date of Report: 06-10-2025
Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM) Appx E Sub E 40 CFR 763 / EPA 600/R-93/116
PROJECT ANALYST AND SIGNATORY REPORT
Project Analyst
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
Analyst: Maxamillian Roselli
EMLab ID: 4095650, Page 10 of 10Eurofins Built Environment Testing East, LLC
Appendix D
Certifications
Certificate # 000MO31910324
Blake Harris has on 09/06/2024 completed the requirements for asbestos accreditation under
Section 206 of TSCA Title II, 15 USC 2646
Online Asbestos Building Inspector Refresher (4 Hour) as approved by MO and the US EPA under 40 CFR 763 (AHERA) and passed the associated exam on 09/06/2024 with a score of at least 70%.
SSN: XXX-XX-9521
Expiration: 09/06/2025
PO BOX 786 – Lawrence, KS 66044 – 800.444.6382 www.metaenvironmental.net
| Appendices - Hertz Rental Car - 1904 E Santa Fe St |
| COC-4095650 |
| Ryan Slanczka KS Asbestos Inspector AHERA Cert. - 2024 |
| Blake Harris.MOIR Certificate 2024 |
| 2025-06-27T14:41:49+0000 | |
| Certified by Adobe Acrobat Sign |
File details come from the government source that posted it. Updated .