Facilities | Environmental | Geotechnical | Materials I
City of Olathe Public Improvements
Asbestos Survey
Townsquare Shopping Center - Building 6
118-126 South Clairborne Road
Olathe, Kansas 66062
August 18, 2025 | Terracon Project Number: 02237230
Prepared for:
City of Olathe Kansas
100 East Santa Fe Street
Olathe, KS 66061
15620 W 113th Street
Lenexa, KS 66219
P (913) 492-7777
F (913) 492-7443
Terracon.com
Facilities | Environmental | Geotechnical | Materials i
August 18, 2025
City of Olathe, Kansas
100 East Santa Fe Street
Olathe, KS 66061
Attn: Ms. Therese Vink
P: (913) 971-9032
E: tmersmann@olatheks.org
Re: City of Olathe Public Improvements Asbestos Survey
Townsquare Shopping Center - Building 6
118-126 South Clairborne Road
Olathe, Kansas 66062
Terracon Project No: 02237230
Dear Ms. Vink:
Terracon Consultants, Inc. (Terracon) is pleased to provide the City of Olathe, Kansas, with this report regarding an asbestos survey conducted at the above-referenced location in Olathe, Kansas.
Asbestos
Asbestos was identified at a concentration greater than 1% in samples collected from the following materials:
Material Description Material Location
NESHAP
Category
Estimated
Quantity
Faux-Brick Vinyl Sheet Wall Unit 126 - NE-Central
Hallway, East Restroom
Category I
Nonfriable 64 Square Feet
Grey Mortar with Remnant Sheet Floor Backing associated with 4" x 9" Ceramic Floor Tile with Grout and Mortar
Unit 118 - Dining Room, Bar West Entryway
Category II Nonfriable
13 Square Feet
Tan Floor Tile and Black Mastic associated with 12" x 12" Tan Floor Tile with Tan Mastic
Unit 126 - SE Hallway, NE Room
Category I Nonfriable
20 Square Feet
City of Olathe Public Improvements Asbestos Survey
Townsquare Shopping Center - Building 6 | Olathe, Kansas
August 18, 2025 | Terracon Project No. 02237230
Facilities | Environmental | Geotechnical | Materials ii
Material Description Material Location
NESHAP
Category
Estimated
Quantity
Brick Caulk Roof - NW Area, West Wall Category II Nonfriable
10 Linear Feet
Flashing Sealant Roof - NW Area, on Vent
Pipe, NW Corner, SW Corner Category I Nonfriable
46 Linear Feet
Tar Sealant
Roof - NE Area, on Pipe;
North-Central Area, on Pipe;
South Area, on HVAC
Category I Nonfriable
594 Linear Feet
Notes: NESHAP – National Emission Standards for Hazardous Air Pollutants
Please refer to Section 3.0 of the attached report for a detailed description of the asbestos survey, sampling activities, and findings.
Terracon appreciates the opportunity to provide this service to the City of Olathe, Kansas. If you have any questions regarding this report, please contact our office at
913-492-7777.
Sincerely, Terracon
Ryan Slanczka Clark Grisell
Senior Staff Scientist Environmental Group Manager
Building Environmental Sciences
Ryan Slanczka Clark Grisell
Facilities | Environmental | Geotechnical | Materials iii
Table Of Contents
1.0 Introduction 1
1.1 Reliance 1
2.0 Building Description 1
3.0 Asbestos-Containing Materials Survey 1
3.1 Visual Assessment 2
3.2 Physical Assessment 2
3.3 Sample Collection 2
3.4 Sample Analysis 2
3.5 Regulatory Overview 3
3.6 Findings 3
4.0 General Comments 4
Appendices
Appendix A Asbestos-Containing Materials By Homogeneous Area
Appendix B Asbestos Survey Sample Location Summary
Appendix C Asbestos Laboratory Analytical Results
Appendix D Certifications
Facilities | Environmental | Geotechnical | Materials 1
1.0 Introduction
Terracon Consultants, Inc. (Terracon) conducted an asbestos-containing material survey of the Townsquare Shopping Center - Building 6 located at 118-126 South Clairborne
Road in Olathe, Kansas, on May 15, 2025. Building areas were visually assessed for suspect asbestos-containing materials (ACM). A reasonable effort was made to inspect accessible areas. Additional suspect materials could be present in walls, voids, or other concealed areas.
1.1 Reliance
This report is for the exclusive use of the City of Olathe, Kansas, for the project being discussed. Reliance by any other party on this report is prohibited without the written authorization of Terracon and the City of Olathe, Kansas.
2.0 Building Description
The subject building is an approximately 16,000-square-foot, single-story community shopping center (with exterior metal canopy), reportedly constructed in 1975. Interior flooring finishes include faux-wood planks, ceramic tiles, sheet vinyl, carpeting, and vinyl tiles over concrete. Interior walls throughout the building are drywall/joint compound wallboard, with acoustic texture, wallpaper, and ceramic tile finishes in various areas. Perimeter walls throughout the building are concrete block and concrete block with concrete wall texture. The primary, observable ceiling system is a drop, grid ceiling with lay-in acoustic tiles below a metal deck. The building’s exterior has concrete block and fluted-block siding. The roof consists of a single-ply synthetic rubber membrane system.
3.0 Asbestos-Containing Materials Survey
The survey was conducted by Mr. Ryan Slanczka and Mr. Blake Harris, State of Kansas-accredited asbestos inspectors. Copies of the asbestos inspectors’ accreditations are attached as Appendix D. The survey was conducted in general accordance with the sample collection protocols established in the United States Environmental Protection
Agency (USEPA) 40 Code of Federal Regulations (CFR) Part 763 Subpart E 763.86, the
Asbestos Hazard Emergency Response Act (AHERA). A summary of survey activities is provided below.
Facilities | Environmental | Geotechnical | Materials 2
3.1 Visual Assessment
Survey activities were initiated with visual observation of the interior and exterior of the building to identify homogeneous areas of suspect ACM. A homogeneous area (HA) consists of a building material that appears similar throughout in terms of color and texture, with consideration given to the date of application. The assessment was conducted in visually accessible areas of the building scheduled for renovation.
3.2 Physical Assessment
A physical assessment of each HA of suspect ACM was conducted to assess the friability and condition of the materials. A friable material is defined by the USEPA as a material that can be crumbled, pulverized, or reduced to powder by hand pressure when dry.
Friability was assessed by physically touching suspect materials.
3.3 Sample Collection
Based on the results of the visual observation, bulk samples of suspect ACM samples were collected in general accordance with USEPA AHERA sampling protocols. Samples of suspect materials were collected from randomly selected locations in each homogeneous area. Bulk samples were collected using wet methods, as applicable, to reduce the potential for fiber release. Samples were placed in sealable containers and labeled with unique sample numbers using an indelible marker.
Rubber, wood products, plastic products, glass, and steel are not considered suspect
ACM and were, therefore, not sampled. The selection of sample locations and frequency of sampling were based on Terracon’s observations and the assumption that like materials in the same area are homogeneous in content. Terracon collected 160 bulk samples from 51 homogeneous areas of suspect ACM.
3.4 Sample Analysis
Bulk samples were submitted under chain of custody to Eurofins International Asbestos
Testing Laboratories (Eurofins) of Mount Laurel, New Jersey, for analysis by PLM with dispersion staining techniques per USEPA Method 600/R-93/116. The percentage of asbestos, where applicable, was determined by microscopic visual estimation. Eurofins is accredited under the National Voluntary Laboratory Accreditation Program (NVLAP), Accreditation No. 101165.
Facilities | Environmental | Geotechnical | Materials 3
3.5 Regulatory Overview
The asbestos National Emission Standards for Hazardous Air Pollutants (NESHAP) regulation (40 CFR Part 61, Subpart M) regulates asbestos fiber emissions and asbestos waste disposal practices. The asbestos NESHAP regulation also requires the identification and classification of existing ACM according to friability prior to demolition or renovation activity. Friable ACM is a material containing more than 1% asbestos that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure.
The asbestos NESHAP regulation classifies ACM as regulated asbestos-containing materials (RACM), Category I non-friable ACM, or Category II non-friable ACM. RACM includes all friable ACM; Category I non-friable ACM that has become friable or will be or has been subjected to sanding, grinding, cutting, or abrading; and Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder in the course of renovation or demolition activity. Category I non-friable ACM are exclusively asbestos-containing packings, gaskets, resilient floor coverings, resilient floor covering mastics, and asphalt roofing products that contain more than 1% asbestos. Category II non-friable ACM are all other non-friable materials other than Category I non-friable ACM that contain more than 1% asbestos. Category II non-friable ACM generally includes but is not limited to cementitious material such as cement pipes, cement siding, cement panels, glazing, mortar, and grouts.
The Kansas Department of Health and Environment’s (KDHE) Asbestos Control Section within the Bureau of Air enforces the Asbestos NESHAP as adopted by reference at
Kansas Administrative Regulations (K.A.R.) 28-19-735. The owner or operator must provide KDHE with written notification at least 10 working days prior to the commencement of asbestos abatement activities that will disturb RACM in amounts greater than or equal to 10 square feet or 25 linear feet.
The United States Occupational Safety and Health Administration (USOSHA) asbestos standard for construction (29 CFR 1926.1101) regulates workplace exposure to asbestos. The OSHA standard classifies construction and maintenance activities that could disturb ACM and specifies work practices and precautions that employers must follow when engaging in each class of regulated work. The standard also specifies requirements for handling materials containing asbestos in concentrations less than or equal to one percent.
3.6 Findings
Asbestos was identified at a concentration greater than 1% in samples collected from the following materials:
Facilities | Environmental | Geotechnical | Materials 4
Material Description Material Location
NESHAP
Category
Estimated
Quantity
Faux-Brick Vinyl Sheet Wall Unit 126 - NE-Central
Hallway, East Restroom Category I Nonfriable
64 Square Feet
Grey Mortar with Remnant Sheet Floor Backing associated with 4" x 9" Ceramic Floor Tile with Grout and Mortar
Unit 118 - Dining Room, Bar West Entryway
Category II Nonfriable
13 Square Feet
Tan Floor Tile and Black Mastic associated with 12" x 12" Tan
Floor Tile with Tan Mastic
Unit 126 - SE Hallway, NE Room
Category I Nonfriable
20 Square Feet
Brick Caulk Roof - NW Area, West Wall Category II Nonfriable
10 Linear Feet
Flashing Sealant Roof - NW Area, on Vent
Pipe, NW Corner, SW Corner Category I Nonfriable
46 Linear Feet
Tar Sealant Roof - NE Area, on Pipe;
North-Central Area, on Pipe;
South Area, on HVAC
Category I Nonfriable
594 Linear Feet
Notes: NESHAP – National Emission Standards for Hazardous Air Pollutants
The above-listed Category I non-friable ACM that is damaged or could be damaged to the extent that it could be crumbled, pulverized, or reduced to powder when dry, making it friable, must be removed prior to any activities (renovation and/or demolition) that may disturb this material in accordance with applicable federal, state, and local regulations. Terracon recommends that all ACM be removed by an abatement contractor prior to any demolition or renovation work that may disturb it.
The above-listed Category II non-friable ACM that has a high probability of becoming crumbled, pulverized, or reduced to powder when dry, making it friable, must be properly removed prior to any activities (renovation and/or demolition) that may disturb this material in accordance with applicable federal, state, and local regulations. USEPA believes that most demolition activities will subject Category II non-friable ACM to the asbestos NESHAP regulation.
Asbestos was not detected at a concentration of 1% or less in any samples collected from the subject building.
A summary of identified asbestos-containing materials by homogeneous area is included in Appendix A. A summary of sample locations is included in Appendix B. Laboratory analytical reports are included in Appendix C.
4.0 General Comments
Terracon did not perform sampling that required demolition or destructive activities such as dismantling of equipment or removal of protective coverings. Reasonable efforts to
Facilities | Environmental | Geotechnical | Materials 5 access suspect materials within known areas of restricted access (e.g., crawl spaces) were made; however, confined spaces or areas that may pose a health or safety risk to
Terracon personnel were not sampled. Sampling did not include suspect materials that could not be safely reached with available ladders or manlifts. Terracon did not sample suspect materials that may be present in movable equipment such as freezers, kitchen equipment, and hoods. Terracon typically investigates for flooring beneath carpeting by lifting small corner sections of carpet. If tiles or sheet vinyl were seen, they have been identified in the report. If tiles or sheet vinyl were not seen at corners under the carpet, it does not imply that there is none beneath the carpeted floor. Terracon did not conduct a destructive investigation of the doors in the building to determine if the doors were insulated for fire-rating purposes.
This survey was conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions, and recommendations expressed in this report are based on conditions observed during Terracon’s survey of the building. The information contained in this report is relevant to the date on which this survey was performed, and should not be relied upon to represent conditions at a later date. This report has been prepared on behalf of and exclusively for use by the City of Olathe, Kansas, and is not a bidding document. Contractors or consultants reviewing this report must draw their own conclusions regarding further investigation or remediation deemed necessary. Terracon does not warrant the work of regulatory agencies, laboratories, or other third parties supplying information that may have been used in the preparation of this report. No warranty, express or implied, is made.
Appendix A
Asbestos-Containing Materials By Homogeneous Area
Appendix A
Identified Asbestos-Containing Materials By Homogeneous Area (HA)
118-126 South Clairborne Road, Olathe, Kansas
Terracon Project No. 02237230
HA Material Description Material Location % and Type
Asbestos*
NESHAP
Classification Condition
Estimated
Quantity**
13 Faux-Brick Vinyl Sheet Wall Unit 126 - NE-Central
Hallway, East Restroom
Tan Sheet Flooring (wall) - 25% Chrysotile
Tan Mastic - None Detected
Category I Nonfriable
Good
Square Feet
Grey Mortar with Remnant Sheet Floor Backing associated with 4" x 9" Ceramic Floor Tile with
Grout and Mortar
Unit 118 - Dining Room, Bar West Entryway
Orange/Brown Ceramic Tile - None Detected
Grey Grout - None Detected Grey Mortar with Remnant Sheet Floor Backing - 5%
Chrysotile
Category II Nonfriable
Good
Square Feet
Tan Floor Tile and Black Mastic associated with 12" x 12" Tan Floor Tile with Tan
Mastic
Unit 126 - SE Hallway, NE Room
Tan Floor Tile - 2% Chrysotile Tan Mastic - None Detected Black Mastic - 2% Chrysotile
Category I Nonfriable
Good
Square Feet
49 Brick Caulk Roof - NW Area, West Wall Black Caulk - 10% Chrysotile
Tan/White Caulk - None Detected
Category II Nonfriable
Good
Linear Feet
50 Flashing Sealant Roof - NW Area, on Vent
Pipe, NW Corner, SW Corner
Black Roof Flashing with Grey/White Outer Coating -
10% Chrysotile Black Roof Flashing with Tan
Coating - 10% Chrysotile
Category I Nonfriable
Good
Linear Feet
51 Tar Sealant Roof - NE Area, on Pipe;
North-Central Area, on
Pipe; South Area, on HVAC
Black Tar Sealant with White Coating - 10% Chrysotile Black Tar Sealant - None
Detected
Category I Nonfriable
Good
Linear Feet
*% & Type Asbestos – this column contains both the analytical result of the sample with the highest concentration of asbestos detected in the samples that make up the HA, and the types of asbestos identified.
**Estimated quantities – quantities based on a cursory field evaluation, and actual quantities may vary significantly, especially if asbestos-containing materials are present in hidden and/or inaccessible areas not evaluated as part of this survey. This is not a bidding document; contractors are responsible for determining their own opinion of quantities.
Appendix B
Asbestos Survey Sample Location Summary
Appendix B
Asbestos Survey Sample Location Summary
118-126 South Clairborne Road, Olathe, Kansas
Terracon Project No. 02237230
HA
No.
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
Drywall with Joint
Compound
01-WB5-01
Unit 122 - West Rooms, Central Area, Interior
Wall
Pink Drywall with Brown Paper
None Detected
White Joint Compound
01-WB5-02 Unit 126 - NE Room, East Wall
White Drywall with Brown Paper
White Joint Compound
01-WB5-03 Unit 120 A/B - West Room, South Wall
White Drywall with Brown Paper
White Joint Compound
01-WB5-04
Unit 118 - Dining Room, South Wall, Central
Area
White Drywall with Brown Paper
White Joint Compound
2 Knock-down Texture
02-PL1-05 Unit 122 - Restroom Hallway, East Wall White Texture
None Detected
02-PL1-06 Unit 126 - Primary Room, East Wall White Texture
02-PL1-07 Unit 122 - NE Restroom, Ceiling White Texture
02-PL1-08 Unit 126 - Primary Room, NW Entryway Wall White Texture
02-PL1-09 Unit 126 - Primary Room, SE Area, East Wall White Texture
3 Knock-down Texture
03-PL1-10 Unit 120 A/B - SE Room, West Wall White Texture
None Detected
03-PL1-11 Unit 120 A/B - SE Room, North Wall White Texture
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
3 Knock-down Texture 03-PL1-12 Unit 120 A/B - SE Room, East Wall White Texture None Detected
4 Orange-Peel Wall Texture
04-PL1-13 Unit 118 - NE Hallway, North Wall, West Area White Texture
None Detected 04-PL1-14 Unit 118 - NE Hallway, East Wall White Texture
04-PL1-15
Unit 118 - NE Hallway, South Wall, Central
Area White Texture
5 Ornate-Style Wallpaper
05-SG5-16
Unit 120 A/B - West Room, NE Area, North
Wall White Wallpaper
None Detected 05-SG5-17 Unit 120 A/B - West Room, NE Area, North
Wall Black/White Wallpaper
05-SG5-18
Unit 120 A/B - West Room, NE Area, North
Wall Black/White Wallpaper
6 Concrete Wall Texture
06-SC5-19 Unit 122 - NE Restroom, East Wall
White Cementitious Material
None Detected
White Texture
06-SC5-20 Unit 122 - East Room, East Wall
White Cementitious Material
White Texture
06-SC5-21
Unit 126 - NE-Central Room, NE Closet, East
Wall White Cementitious Material
06-SC5-22 Unit 126 - Primary Room, SW Corner Wall White Cementitious Material
06-SC5-23 Unit 120 A/B - East Hallway, East Wall White Cementitious Material
06-SC5-24 Unit 120B - Exterior, East, at Door Beige Cementitious Material
06-SC5-25 Unit 126 - Exterior, East, at Door Beige Cementitious Material
2' x 2' Ceiling Tile with
Pinholes and Divots
07-CT3-26 Unit 126 - NE Rooms Grey Ceiling Tile with White
Surface
None Detected 07-CT3-27 Unit 122 - East Room Grey Ceiling Tile with White
Surface
07-CT3-28 Unit 122 - Central Room, NW Area Grey Ceiling Tile with White
Surface
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
8 2' x 4' Plain Ceiling Tile
08-CT4-29 Unit 126 - NE Room Grey Ceiling Tile with White
Surface
None Detected 08-CT4-30 Unit 126 - East Hallway, South Room Grey Ceiling Tile with White
Surface
08-CT4-31 Unit 126 - Primary Room, SE Area Grey Ceiling Tile with White
Surface
2' x 4' Ceiling Tile with
Pinholes and Fissures
09-CT4-32 Unit 122 - West Rooms Grey Ceiling Tile with White
Surface
None Detected 09-CT4-33 Unit 126 - SE Restroom Grey Ceiling Tile with White
Surface
09-CT4-34 Unit 120 A/B - NE Room, Central Area Grey Ceiling Tile with White
Surface
10 2'x4' Fiberglass Ceiling Tile
10-CT4-35 Unit 126 - SE Hallway Yellow Ceiling Tile
None Detected 10-CT4-36 Unit 118 - Dining Room, NW Area Yellow Ceiling Tile
10-CT4-37 Unit 118 - Dining Room, SW Area White/Yellow Ceiling Tile
2' x 4' Ceiling Tile with
Pinholes and Divots
11-CT4-38 Unit 120 A/B - NE Room, Central Area Off-White Ceiling Tile
None Detected 11-CT4-39 Unit 118 - Dining Room, SW Area Off-White Ceiling Tile
11-CT4-40 Unit 118 - Kitchen, West Area Off-White Ceiling Tile
4" Cove Base with Tan
Mastic
12-FC3-41 Unit 122 - East Room, South Wall
Grey Cove Base
None Detected
Beige Mastic
12-FC3-42
Unit 120 A/B - West Room, West Area, Interior
Wall
Grey Cove Base
Beige Mastic
12-FC3-43 Unit 118 - Dining Room, Behind Bar, East Wall
Black Cove Base
Beige Mastic
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
Faux-Brick Vinyl Sheet
Wall
13-FC1-44
Unit 126 - NE Central Hallway, East
Restroom
Tan Sheet Flooring 25% Chrysotile
Tan Mastic None Detected
13-FC1-45
Unit 126 - NE Central Hallway, East
Restroom
Tan Sheet Flooring 25% Chrysotile
Tan Mastic None Detected
13-FC1-46
Unit 126 - NE Central Hallway, East
Restroom
Tan Sheet Flooring 25% Chrysotile
Tan Mastic None Detected
12" x 12" Ceramic Wall Tile with Grout and Mastic
14-MA5-47 Unit 126 - SE Hallway, East Restroom
Beige/Grey Ceramic Tile
None Detected
Light Brown Grout
Beige Mastic
14-MA5-48 Unit 126 - SE Hallway, East Restroom
Beige/Grey Ceramic Tile
Light Brown Grout
Beige Mastic
14-MA5-49 Unit 126 - SE Hallway, East Restroom
Beige/Grey Ceramic Tile with
Black Paint
Light Brown Grout
Beige Mastic
12" x 12" Ceramic Tile with
Grout and White Mortar 15-MA5-50 Unit 122 - North Restroom, Wall
Brown/Beige Ceramic Tile
None Detected Tan Grout
White Mortar
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
12" x 12" Ceramic Tile with
Grout and White Mortar
15-MA5-51 Unit 126 - Kitchen, NE Area, Floor
Grey Ceramic Tile
None Detected
White Grout
White/Grey Mortar
15-MA5-52 Unit 126 - Primary Room, SW Corner, Floor
Brown/Beige Ceramic Tile
Tan Grout
White Mortar
12" x 12" Ceramic Tile with
Grout and Grey Mortar
16-MA5-53 Unit 122 - NE Restroom, Baseboard
White/Red Ceramic Tile
None Detected
Tan Grout
Grey Mortar
16-MA5-54 Unit 126 - East Restroom Hallway, Floor
Off-White/Grey Ceramic Tile
Tan Grout
Grey Mortar
16-MA5-55 Unit 126 - Kitchen, East Area, Floor
Grey/Red Ceramic Tile
White Grout
Grey Mortar
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
4" x 9" Ceramic Floor
Tile with Grout and
Mortar
17-MA5-56
Unit 118 - Dining Room, Bar West
Entryway
Orange/Brown Ceramic Tile None Detected
Grey Grout None Detected
Grey Mortar with Remnant
Sheet Floor Backing 5% Chrysotile
17-MA5-57
Unit 118 - Dining Room, Bar West
Entryway
Orange/Brown Ceramic Tile None Detected
Grey Grout None Detected
Grey Mortar with Remnant
Sheet Floor Backing 5% Chrysotile
17-MA5-58
Unit 118 - Dining Room, Bar West
Entryway
Orange/Brown Ceramic Tile None Detected
Grey Grout None Detected
Grey Mortar with Remnant
Sheet Floor Backing 5% Chrysotile
16" x 16" Ceramic Floor
Tile with Grout and Mortar
18-MA5-59 Unit 118 - Dining Room, Bar South Entryway
Tan Ceramic Tile
None Detected
Tan Grout
Grey Mortar
18-MA5-60 Unit 118 - Dining Room, Bar South Entryway
Tan Ceramic Tile
Tan Grout
Grey Mortar
18-MA5-61 Unit 118 - Dining Room, Bar South Entryway
Tan Ceramic Tile
Tan Grout
Grey Mortar
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
12" x 12" Ceramic Floor
Tile with Grout and Mortar
19-MA5-62 Unit 118 - NE Hallway, West Area
Off-White/Grey Ceramic Tile
None Detected
Tan Grout
Grey Mortar
19-MA5-63 Unit 118 - NE Hallway, West Area
Off-White/Grey Ceramic Tile
Tan Grout
Grey Mortar
19-MA5-64 Unit 118 - NE Hallway, West Area
Off-White/Grey Ceramic Tile
Tan Grout
Grey Mortar
6" x 24" Faux-Wood Plank
Ceramic Floor Tile with
Grout and Mortar
20-MA5-65 Unit 118 - Vestibule
Grey/White Ceramic Tile
None Detected
Grey Grout
White Mortar
20-MA5-66 Unit 118 - Vestibule
Grey/White Ceramic Tile
Grey Grout
White Mortar
20-MA5-67 Unit 118 - Vestibule
Grey/White Ceramic Tile
Grey Grout
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
12" x 12" Faux-Stone
Plastic Floor Tile with Tan
Adhesive
21-FT2-68 Unit 122 - Restroom Hallway
Tan Floor Tile
None Detected
Tan Adhesive
21-FT2-69 Unit 126 - SE Restroom
Tan Floor Tile
Tan Adhesive
21-FT2-70 Unit 122 - NE Restroom
Tan Floor Tile
Tan Adhesive
12" x12" Tan Floor Tile with Tan Mastic
22-FT2-71 Unit 126 - SE Hallway, NE Room
Tan Floor Tile 2% Chrysotile
Tan Mastic None Detected
22-FT2-72 Unit 126 - SE Hallway, NE Room
Tan Floor Tile 2% Chrysotile
Tan Mastic None Detected
22-FT2-73 Unit 126 - SE Hallway, NE Room
Tan Floor Tile 2% Chrysotile
Tan Mastic None Detected
Black Mastic 2% Chrysotile
12" x 12" Red Floor Tile with Mastic
23-FT2-74 Unit 120 A/B - West Room, SE Area
Red Floor Tile
None Detected
Clear Mastic
Tan Mastic
23-FT2-75 Unit 120 A/B - West Room, SE Area
Red Floor Tile
Clear Mastic
Tan Mastic
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
12" x 12" Red Floor Tile with Mastic 23-FT2-76 Unit 120 A/B - West Room, SE Area
Red Floor Tile
None Detected Clear Mastic
Tan Mastic
24 Faux-CFT Sheet Flooring
24-FC1-77 Unit 126 - East-Central Office Restroom
Grey/Brown Sheet Flooring
None Detected
Grey/Yellow Mastic
24-FC1-78 Unit 126 - East-Central Office Restroom
Grey/Brown Sheet Flooring
Grey/Yellow Mastic
24-FC1-79 Unit 126 - East-Central Office Restroom
Grey/Brown Sheet Flooring
Grey/Yellow Mastic
Faux-Wood Plank Sheet
Flooring
25-FC1-80 Unit 120 A/B - East Hallway, near Restroom
Wood Grain/Brown Sheet Flooring
None Detected
Grey/Yellow Mastic
25-FC1-81 Unit 120 A/B - West Room, Central Area
Wood Grain/Brown Sheet Flooring
Grey/Yellow Mastic
25-FC1-82 Unit 120 A/B - West Room, South-Central Area
Wood Grain/Brown Sheet Flooring
Grey/Yellow Mastic
Yellow/Tan Carpet Glue with Residual Black Mastic
26-MG7-83
Unit 126 - Primary Room, SW Area, near SW
Entrance Yellow/Black Mastic
None Detected 26-MG7-84 Unit 122 - West Rooms, Central Area Yellow/Black Mastic
26-MG7-85 Unit 126 - Primary Room, East Area Yellow/Black Mastic
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
Tan/Yellow Carpet
Adhesive
27-MG7-86 Unit 120 A/B - West Room, SE-Central Area Tan Adhesive
None Detected 27-MG7-87 Unit 120 A/B - East-Central Office Tan Adhesive
27-MG7-88 Unit 120 A/B - West Room, NE Area Tan Adhesive
28 Light Tan Carpet Adhesive
28-MG7-89 Unit 120 A/B - West Room, East-Central Area Tan Adhesive
None Detected 28-MG7-90 Unit 120 A/B - West Room, ESE Area Tan Adhesive
28-MG7-91 Unit 120 A/B - West Room, East Area Tan Adhesive
29 Tan Flooring Adhesive
29-MG7-92 Unit 118 - Dining Room, West-Central Area Tan Adhesive
None Detected 29-MG7-93 Unit 118 - Dining Room, NE Area Tan Adhesive
29-MG7-94 Unit 118 - Dining Room, SW Area Tan Adhesive
30 Black Flooring Material
30-MG5-95 Unit 118 - Dining Room, Bar West Entryway Black Flooring Material
None Detected 30-MG5-96 Unit 118 - Dining Room, Bar West Entryway Black Flooring Material
30-MG5-97 Unit 118 - Dining Room, Behind Bar Black Flooring Material
31 Concrete Slab
31-CP5-98 Unit 118 - Dining Room, West-Central Area
Grey Concrete
None Detected
Tan Mastic
31-CP5-99 Unit 122 - Central Room, SW Area Grey Concrete
31-CP5-100 Unit 120B - West Room, North Area Grey Concrete
32 Brown Epoxy
32-FC2-101 Unit 120 A/B - West Room, West-Central Area Brown Coating Epoxy
None Detected 32-FC2-102 Unit 120 A/B - SE Room Brown Coating Epoxy
32-FC2-103 Unit 120 A/B - East Hallway, near Restroom Brown Coating Epoxy
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
33 Expansion Joint
33-MS5-104 Unit 120 A/B - SE Room, East Area White Expansion Joint
None Detected 33-MS5-105 Unit 120 A/B - SE Room, East Area White Expansion Joint
33-MS5-106 Unit 120 A/B - West Room, SE Area White Expansion Joint
Fiber-Reinforced Panel
Mastic
34-MG8-107 Unit 126 - NE Room, Walls Off-White Panel Mastic
None Detected 34-MG8-108 Unit 126 - NE Room, Walls Off-White Panel Mastic
34-MG8-109 Unit 126 - NE Room, Walls Off-White Panel Mastic
35 Wall Mastic
35-MG5-110
Unit 126 - Primary Room, West Area, Lower
Panels Brown Mastic
None Detected 35-MG5-111 Unit 126 - Primary Room, West Area, Lower
Panels Brown Mastic
35-MG5-112
Unit 126 - Primary Room, West Area, Lower
Panels Brown Mastic
36 Glue Puck
36-MG5-113
Unit 126 - Primary Room, SE Area, behind
Mirrors Tan Glue
None Detected 36-MG5-114 Unit 126 - Primary Room, SE Area, behind
Mirrors Tan Glue
36-MG5-115
Unit 126 - Primary Room, SE Area, behind
Mirrors Tan Glue
Batt Insulation with Paper
Backing
37-AW1-116 Unit 118 - Dining Room, NW Area
Yellow Insulation
None Detected
Tan/Black Paper
37-AW1-117 Unit 118 - Dining Room, SW Area
Yellow Insulation
Tan/Black Paper
37-AW1-118 Unit 118 - Dining Room, SE Area
Pink Insulation
Tan/Black Paper
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
Bar-Top Leveling
Compound
38-FC6-119 Unit 118 - Dining Room, Bar-Top White Joint Compound with
Greyish Paint
None Detected 38-FC6-120 Unit 118 - Dining Room, Bar-Top White Joint Compound with
Greyish Paint
38-FC6-121 Unit 118 - Dining Room, Bar-Top White Joint Compound with
Greyish Paint
39 Stone Wall Mortar
39-MA3-122 Unit 126 - Primary Room, South Wall Grey Mortar
None Detected 39-MA3-123 Unit 126 - Primary Room, South Wall Grey Mortar
39-MA3-124 Unit 126 - Primary Room, South Wall Grey Mortar
40 Glass Block Grout
40-MA4-125 Unit 126 - Primary Room, near SW Entryway Grey Grout
None Detected 40-MA4-126 Unit 126 - Primary Room, near SW Entryway Grey Grout
40-MA4-127 Unit 126 - Primary Room, near SW Entryway Grey Grout
41 Stone Wall Finish
41-MA6-128 Unit 126 - Exterior, West, Column Tan Cementitious Material Wall
Finish
None Detected 41-MA6-129 Unit 126 - Exterior, East, Siding Tan/Grey Cementitious Material
Wall Finish
41-MA6-130 Unit 120B - Exterior, West, Siding Tan Cementitious Material Wall
Finish
42 Fluted-Stone Siding Mortar
42-MA3-131 Unit 126 - Exterior, SW, Siding Grey Mortar
None Detected 42-MA3-132 Unit 120B - Exterior, West, Column Grey Mortar
42-MA3-133 Unit 120A - Exterior, West, Siding Grey Mortar
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
43 Concrete Block Mortar
43-MA2-134 Unit 120A - Exterior, East, at Door Grey Mortar
None Detected 43-MA2-135 Unit 118 - Dining Room, West Wall, South of
Vestibule Tan Mortar
43-MA2-136 Unit 122 - West Room, West Wall, near Door Tan Mortar
44 Corrugated-Fiber Panel
44-MS5-137 Unit 126 - Exterior, West, Awning Black Fiberboard Panel Painted
Red
None Detected 44-MS5-138 Unit 126 - Exterior, West, Awning Black Fiberboard Panel Painted
Red
44-MS5-139 Unit 126 - Exterior, West, Awning Black Fiberboard Panel Painted
Red
Drywall with Joint
Compound
45-WB5-140 Unit 118 - Exterior, West
White Drywall with Brown Paper
None Detected
White Joint Compound
45-WB5-141 Unit 122 - Exterior, West
White Drywall with Brown Paper
White Joint Compound
45-WB5-142 Unit 126 - Exterior, West
White Drywall with Brown Paper
White Joint Compound
Dark Brown Expansion
Joint
46-MS5-143 Unit 126 - Exterior, West Dark Brown Expansion Joint
None Detected 46-MS5-144 Unit 126 - Exterior, West Dark Brown Expansion Joint
46-MS5-145 Unit 126 - Exterior, West Dark Brown Expansion Joint
47 Black Expansion Joint
47-MS5-146 Unit 118 - Exterior, NW Corner Black Expansion Joint
None Detected 47-MS5-147 Unit 118 - Exterior, NW Corner Black Expansion Joint
47-MS5-148 Unit 118 - Exterior, NW Corner Black Expansion Joint
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
48 Roofing Material
48-RF5-149 Roof - NE Area
Black Roofing Material
None Detected
Black/White Roofing Membrane
Black Tar
Black Tar Paper
Black Roofing Felt
Tan Fiberboard
Yellow Insulation
48-RF5-150 Roof - West-Central Area
Black Roofing Material
Black/White Roofing Membrane
Black Tar
Black Tar Paper
Black Roofing Felt
Tan Fiberboard
Yellow Insulation
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
48 Roofing Material 48-RF5-151 Roof - SE Area
Black Roofing Material
None Detected
Black/White Roofing Membrane
Black Tar
Black Tar Paper
Black Roofing Felt
Tan Fiberboard
Yellow Insulation
49 Brick Caulk
49-CA3-152 Roof - NW Area, West Wall
Black Caulk 10% Chrysotile
Tan/White Caulk None Detected
49-CA3-153 Roof - NW Area, West Wall
Black Caulk 10% Chrysotile
Tan/White Caulk None Detected
49-CA3-154 Roof - NW Area, West Wall
Black Caulk 10% Chrysotile
Tan/White Caulk None Detected
50 Flashing Sealant
50-RF7-155 Roof - NE Area, on Vent Pipe Black Roof Flashing with
Grey/White Outer Coating 10% Chrysotile
50-RF7-156 Roof - NW Corner Black Roof Flashing with
Grey/White Outer Coating 10% Chrysotile
50-RF7-157 Roof - SW Corner Black Roof Flashing with Tan
Coating 10% Chrysotile
51 Tar Sealant
51-RF4-158 Roof - NE Area, on Pipe Black Tar Sealant with White
Coating 10% Chrysotile
51-RF4-159 Roof - North-Central Area, on Pipe Black Tar Sealant with White
Coating 10% Chrysotile
51-RF4-160 Roof - South Area, on HVAC Black Tar Sealant None Detected
Asbestos-containing materials in BOLD.
Appendix C
Asbestos Laboratory Analytical Results
Approved by:
Approved Signatory Frank Ehrenfeld
Report for:
Ryan Slanczka Terracon Consultants- Lenexa 15620 W. 113th St Lenexa, KS 66219
Regarding:
Eurofins Built Environment Testing East, LLC Project: 02237230 - 118-126 S Clairborne Rd
EML ID: 4077654
All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. The results relate only to the samples as received and tested. The results include an inherent uncertainty of measurement associated with estimating percentages by polarized light microscopy. Measurement uncertainty data for sample results with >1% asbestos concentration can be provided when requested.
Eurofins Built Environment Testing East, LLC ("the Company"), a member of the Eurofins Built Environment Testing group of companies, shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results. In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor.
Dates of Analysis:
Asbestos PLM (Layer %): 05-27-2025 and 05-28-2025
Service SOPs: Asbestos PLM (Layer %) (EPA 40CFR App E to Sub E of Part 763 & EPA METHOD 600/R-93-116, SOP EB-AS-S- 1267) NVLAP Lab Code 101165-0
EMLab ID: 4077654, Page 1 of 27Eurofins Built Environment Testing East, LLC
Eurofins Built Environment Testing East, LLC 9000 Commerce Parkway, Suite B, Mount Laurel, NJ 08054
(856) 231-9449 www.eurofinsus.com/Built Client: Terracon Consultants- Lenexa C/O: Ryan Slanczka Re: 02237230 - 118-126 S Clairborne Rd
Date of Receipt: 05-19-2025 Date of Report: 05-28-2025
Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM) Appx E Sub E 40 CFR 763 / EPA 600/R-93/116
Sample ID # Lab-ID version Sample Description Asbestos
Constituents Non-Asbestos Constituents Comment
01-WB5-01. Drywall with Joint Compound; 122-West Rooms, Central Area, Interior Wall 20330091-1
Layer 1 Pink Drywall with Brown Paper Homogeneity:Good
Not Detected 83% Non-Fibrous Material 15% Cellulose 2% Glass Fibers
Layer 2 White Joint Compound Homogeneity:Good
Not Detected 100% Non-Fibrous Material
01-WB5-02. Drywall with Joint Compound; 126-NE Room, East Wall 20330092-1
Layer 1 White Drywall with Brown Paper Homogeneity:Good
Not Detected 85% Non-Fibrous Material
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
01-WB5-03. Drywall with Joint Compound; 120 A/B-West Room, South Wall 20330093-1
Layer 1 White Drywall with Brown Paper Homogeneity:Good
Not Detected 83% Non-Fibrous Material
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
01-WB5-04. Drywall with Joint Compound; 118-Dining Room, South Wall, Central Area 20330094-1
Layer 1 White Drywall with Brown Paper Homogeneity:Good
Not Detected 83% Non-Fibrous Material
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
02-PL1-05. Knock-Down Texture;
122-Restroom Hallway, East Wall 20330095-1
Layer 1 White Texture Homogeneity:Good
Not Detected 100% Non-Fibrous Material
02-PL1-06. Knock-Down Texture;
126-Primary Room, East Wall 20330096-1
Layer 1 White Texture Homogeneity:Good
Not Detected 100% Non-Fibrous Material
02-PL1-07. Knock-Down Texture;
122-NE Restroom, Ceiling 20330097-1
Layer 1 White Texture Homogeneity:Good
Not Detected 100% Non-Fibrous Material
02-PL1-08. Knock-Down Texture;
126-Primary Room, NE Entryway Wall 20330098-1
Layer 1 White Texture Homogeneity:Good
Not Detected 100% Non-Fibrous Material
Comments:
EMLab ID: 4077654, Page 2 of 27Eurofins Built Environment Testing East, LLC
The total percentage of sample components shown may be greater than 100% when some components are detected at <1%.
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers of that type were detected.
When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
(856) 231-9449 www.eurofinsus.com/Built Client: Terracon Consultants- Lenexa C/O: Ryan Slanczka Re: 02237230 - 118-126 S Clairborne Rd
Date of Receipt: 05-19-2025 Date of Report: 05-28-2025
Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM) Appx E Sub E 40 CFR 763 / EPA 600/R-93/116
Sample ID # Lab-ID version Sample Description Asbestos
Constituents Non-Asbestos Constituents Comment
02-PL1-09. Knock-Down Texture;
126-Primary Room, SE Area, East Wall 20330099-1
Layer 1 White Texture Homogeneity:Good
Not Detected 100% Non-Fibrous Material
03-PL1-10. Knock-Down Texture;
120 A/B-SE Room, West Wall 20330100-1
Layer 1 White Texture Homogeneity:Good
Not Detected 100% Non-Fibrous Material
03-PL1-11. Knock-Down Texture;
120 A/B-SE Room, North Wall 20330101-1
Layer 1 White Texture Homogeneity:Good
Not Detected 100% Non-Fibrous Material
03-PL1-12. Knock-Down Texture;
120 A/B-SE Room, East Wall 20330102-1
Layer 1 White Texture Homogeneity:Good
Not Detected 100% Non-Fibrous Material
04-PL1-13. Orange-Peel Wall Texture; 118-NE Hallway, North Wall, West Area 20330103-1
Layer 1 White Texture Homogeneity:Good
Not Detected 100% Non-Fibrous Material
04-PL1-14. Orange-Peel Wall Texture; 118-NE Hallway, East Wall 20330104-1
Layer 1 White Texture Homogeneity:Good
Not Detected 100% Non-Fibrous Material
04-PL1-15. Orange-Peel Wall Texture; 118-NE Hallway, South Wall, Central Area 20330105-1
Layer 1 White Texture Homogeneity:Good
Not Detected 100% Non-Fibrous Material
05-SG5-16. Ornate-Style Wallpaper;
120 A/B-West Room, NE Area, North Wall 20330106-1
Layer 1 White Wallpaper Homogeneity:Good
Not Detected 70% Non-Fibrous Material 30% Cellulose
05-SG5-17. Ornate-Style Wallpaper;
120 A/B-West Room, NE Area, North Wall 20330107-1
Layer 1 Black/White Wallpaper Homogeneity:Good
Not Detected 60% Non-Fibrous Material 40% Cellulose
05-SG5-18. Ornate-Style Wallpaper;
120 A/B-West Room, NE Area, North Wall 20330108-1
Layer 1 Black/White Wallpaper Homogeneity:Good
Not Detected 60% Non-Fibrous Material 40% Cellulose
06-SC5-19. Concrete Wall Texture;
122-NE Restroom, East Wall 20330109-1
Layer 1 White Cementitious Material Homogeneity:Good
Not Detected 90% Non-Fibrous Material 10% Glass Fibers
White Texture Homogeneity:Good
Not Detected 100% Non-Fibrous Material
Comments:
EMLab ID: 4077654, Page 3 of 27Eurofins Built Environment Testing East, LLC
The total percentage of sample components shown may be greater than 100% when some components are detected at <1%.
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers of that type were detected.
When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(856) 231-9449 www.eurofinsus.com/Built Client: Terracon Consultants- Lenexa C/O: Ryan Slanczka Re: 02237230 - 118-126 S Clairborne Rd
Date of Receipt: 05-19-2025 Date of Report: 05-28-2025
Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM) Appx E Sub E 40 CFR 763 / EPA 600/R-93/116
Sample ID # Lab-ID version Sample Description Asbestos
Constituents Non-Asbestos Constituents Comment
06-SC5-20. Concrete Wall Texture;
122-East Room, East Wall 20330110-1
Layer 1 White Cementitious Material Homogeneity:Good
10% Glass Fibers
White Texture Homogeneity:Good
Not Detected 100% Non-Fibrous Material
06-SC5-21. Concrete Wall Texture;
126-NE-CEntral Room, NE Closet, East Wall 20330111-1
Layer 1 White Cementitious Material Homogeneity:Good
Not Detected 90% Non-Fibrous Material 10% Glass Fibers
A
06-SC5-22. Concrete Wall Texture;
126-Primary Room, SW Corner Wall 20330112-1
Layer 1 White Cementitious Material Homogeneity:Good
Not Detected 90% Non-Fibrous Material 10% Glass Fibers
A
06-SC5-23. Concrete Wall Texture;
120 A/B-East Hallway, East Wall 20330113-1
Layer 1 White Cementitious Material Homogeneity:Good
Not Detected 90% Non-Fibrous Material 10% Glass Fibers
A
06-SC5-24. Concrete Wall Texture;
120B-Exterior, East, at Door 20330114-1
Layer 1 Beige Cementitious Material Homogeneity:Good
Not Detected 90% Non-Fibrous Material 10% Glass Fibers
A
06-SC5-25. Concrete Wall Texture;
126-Exterior, East, at Door 20330115-1
Layer 1 Beige Cementitious Material Homogeneity:Good
Not Detected 90% Non-Fibrous Material 10% Glass Fibers
A
07-CT3-26. 2'x2' Ceiling Tile w/ Pinholes & Divots; 126-NE Rooms 20330116-1
Layer 1 Gray Ceiling Tile with White Surface Homogeneity:Good
Not Detected 60% Cellulose 20% Glass Fibers 20% Non-Fibrous Material
07-CT3-27. 2'x2' Ceiling Tile w/ Pinholes & Divots; 122-East Room 20330117-1
Layer 1 Gray Ceiling Tile with White Surface Homogeneity:Good
Not Detected 60% Cellulose 20% Glass Fibers
07-CT3-28. 2'x2' Ceiling Tile w/ Pinholes & Divots; 122-Central Room, NW Area 20330118-1
Layer 1 Gray Ceiling Tile with White Surface Homogeneity:Good
Not Detected 50% Cellulose 30% Glass Fibers
08-CT4-29. 2'x4' Plain Ceiling Tile;
126-NE Room 20330119-1
Layer 1 Gray Ceiling Tile with White Surface Homogeneity:Good
Not Detected 50% Cellulose
08-CT4-30. 2'x4' Plain Ceiling Tile;
126-East Hallway, South Room 20330120-1
Layer 1 Gray Ceiling Tile with White Surface Homogeneity:Good
Not Detected 50% Cellulose
Comments: A)No other textured layer present. Cementitious material is textured.
EMLab ID: 4077654, Page 4 of 27Eurofins Built Environment Testing East, LLC
The total percentage of sample components shown may be greater than 100% when some components are detected at <1%.
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers of that type were detected.
When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(856) 231-9449 www.eurofinsus.com/Built Client: Terracon Consultants- Lenexa C/O: Ryan Slanczka Re: 02237230 - 118-126 S Clairborne Rd
Date of Receipt: 05-19-2025 Date of Report: 05-28-2025
Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM) Appx E Sub E 40 CFR 763 / EPA 600/R-93/116
Sample ID # Lab-ID version Sample Description Asbestos
Constituents Non-Asbestos Constituents Comment
08-CT4-31. 2'x4' Plain Ceiling Tile;
126-Primary Room, SE Area 20330121-1
Layer 1 Gray Ceiling Tile with White Surface Homogeneity:Good
Not Detected 50% Cellulose
09-CT4-32. 2'x4' Ceiling Tile w/ Pinholes & Fissures; 122-West Rooms 20330122-1
Layer 1 Gray Ceiling Tile with White Surface Homogeneity:Good
Not Detected 50% Cellulose 35% Glass Fibers 15% Non-Fibrous Material
09-CT4-33. 2'x4' Ceiling Tile w/ Pinholes & Fissures; 126-SE Restroom 20330123-1
Layer 1 Gray Ceiling Tile with White Surface Homogeneity:Good
Not Detected 50% Cellulose 35% Glass Fibers 15% Non-Fibrous Material
09-CT4-34. 2'x4' Ceiling Tile w/ Pinholes & Fissures; 120 A/B-NE Room, Central Area 20330124-1
Layer 1 Gray Ceiling Tile with White Surface Homogeneity:Good
Not Detected 50% Cellulose
10-CT4-35. 2'x4' Fiberglass Ceiling Tile; 126-SE Hallway 20330125-1
Layer 1 Yellow Ceiling Tile Homogeneity:Good
Not Detected 90% Glass Fibers 10% Non-Fibrous Material
10-CT436. 2'x4' Fiberglass Ceiling Tile; 118-Dining Room, NW Area 20330126-1
Layer 1 Yellow Ceiling Tile Homogeneity:Good
Not Detected 90% Glass Fibers
10-CT4-37. 2'x4' Fiberglass Ceiling Tile; 118-Dining Room, SW Area 20330127-1
Layer 1 White/ Yellow Ceiling Tile Homogeneity:Good
Not Detected 95% Glass Fibers 5% Non-Fibrous Material
11-CT4-38. 2'x4' Ceiling Tile w/ Pinholes & Divots; 120 A/B-NE Room, Central Area 20330128-1
Layer 1 Off-White Ceiling Tile Homogeneity:Good
Not Detected 60% Cellulose
11-CT4-39. 2'x4' Ceiling Tile w/ Pinholes & Divots; 118-Dining Room, SW Area 20330129-1
Layer 1 Off-White Ceiling Tile Homogeneity:Good
Not Detected 60% Cellulose
11-CT4-40. 2'x4' Ceiling Tile w/ Pinholes & Divots; 118-Kitchen, West Area 20330130-1
Layer 1 Off-White Ceiling Tile Homogeneity:Good
Not Detected 60% Cellulose
12-FC3-41. 4" Cove Base w/ Tan Mastic; 122-East Room, South Wall 20330131-1
Layer 1 Gray Cove Base Homogeneity:Good
Not Detected 100% Non-Fibrous Material
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
Comments:
EMLab ID: 4077654, Page 5 of 27Eurofins Built Environment Testing East, LLC
The total percentage of sample components shown may be greater than 100% when some components are detected at <1%.
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers of that type were detected.
When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(856) 231-9449 www.eurofinsus.com/Built Client: Terracon Consultants- Lenexa C/O: Ryan Slanczka Re: 02237230 - 118-126 S Clairborne Rd
Date of Receipt: 05-19-2025 Date of Report: 05-28-2025
Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM) Appx E Sub E 40 CFR 763 / EPA 600/R-93/116
Sample ID # Lab-ID version Sample Description Asbestos
Constituents Non-Asbestos Constituents Comment
12-FC3-42. 4" Cove Base w/ Tan Mastic; 120 A/B-West Room, West Area, Interior Wall 20330132-1
Layer 1 Gray Cove Base
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
12-FC3-43. 4" Cove Base w/ Tan Mastic; 118-Dining Room, behind Bar, East Wall 20330133-1
Layer 1 Black Cove Base
Homogeneity:Good
Not Detected 100% Non-Fibrous Material
13-FC1-44. Faux-Brick Vinyl Sheet Wall; 126-NE Central Hallway, East Restroom 20330134-1
Layer 1 Tan Sheet Flooring
25% Chrysotile 75% Non-Fibrous Material
Homogeneity:Good
No…