16-Asbestos Survey - Tract 51 (128-140 S. Clairborne).pdf
PDF 2 MB Posted
- Solicitation number
- 3-C-025-18
- Issued by
- Johnson County, Kansas
About this file
This is an asbestos survey report prepared by Terracon Consultants, Inc. for the City of Olathe, Kansas, related to the Townsquare Shopping Center Building 7 located at 128-140 South Clairborne Road. The survey was conducted on May 15, 2025, to identify asbestos-containing materials (ACM) in the approximately 45,350-square-foot single-story commercial building constructed in 1975, which is scheduled for demolition and site restoration as part of project 3-C-025-18 near Santa Fe Street and I-35. Terracon collected 160 bulk samples from 51 homogeneous areas and identified significant quantities of asbestos-containing materials including 18,675 square feet of floor tile and mastic in Unit 140, 845 square feet of ceramic tile mastic in Unit 134B, and various other ACMs totaling approximately 20,500+ square feet of Category I non-friable materials and 73 square feet of Regulated Asbestos-Containing Material (RACM) requiring professional abatement.
The survey findings indicate that all identified RACM and Category I non-friable ACM must be removed by a State of Kansas licensed abatement contractor prior to any demolition or renovation activities, in accordance with federal NESHAP regulations and Kansas Administrative Regulations. The materials identified include floor tiles, mastics, sheet flooring, wall mastic, roofing materials, flashing sealants, and tar sealants containing 2% chrysotile asbestos, with additional materials containing 1% or less asbestos that are subject to OSHA workplace exposure limits. The report was prepared exclusively for the City of Olathe's use and includes detailed regulatory compliance requirements, noting that KDHE notification is required at least 10 working days prior to commencement of abatement activities for materials exceeding 10 square feet or 25 linear feet.
View the file
Other files
Show 40 more
Latest 50 of 54 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Facilities | Environmental | Geotechnical | Materials I
City of Olathe Public Improvements
Asbestos Survey
Townsquare Shopping Center - Building 7
128-140 South Clairborne Road
Olathe, Kansas 66062
August 18, 2025 | Terracon Project Number: 02237230
Prepared for:
City of Olathe Kansas
100 East Santa Fe Street
Olathe, KS 66061
15620 W 113th Street
Lenexa, KS 66219
P (913) 492-7777
F (913) 492-7443
Terracon.com
Facilities | Environmental | Geotechnical | Materials i
August 18, 2025
City of Olathe, Kansas
100 East Santa Fe Street
Olathe, KS 66061
Attn: Ms. Therese Vink
P: (913) 971-9032
E: tmersmann@olatheks.org
Re: City of Olathe Public Improvements Asbestos Survey
Townsquare Shopping Center - Building 7
128-140 South Clairborne Road
Olathe, Kansas 66062
Terracon Project No: 02237230
Dear Ms. Vink:
Terracon Consultants, Inc. (Terracon) is pleased to provide the City of Olathe, Kansas, with this report regarding an asbestos survey conducted at the above-referenced location in Olathe, Kansas.
Asbestos
Asbestos was identified at a concentration greater than 1% in samples collected from the following materials:
Material Description Material Location
NESHAP
Category
Estimated
Quantity
Black Mastic associated with
6" x 6" Red Ceramic Floor Tile with Grout and Mortar
Unit 134B - NW-Central
Room, SW Room
Category I
Nonfriable
Square Feet
12" x 12" Beige with Tan Streaks
Floor Tile and Black Mastic
Unit 140 - Salesfloor, South
Breakroom, SE Office
Category I
Nonfriable
18,675
Square Feet
Black/Brown Mastic associated with 12" x 12" Beige Mottle Floor
Tile with Tan & Brown Mastic
Unit 140 - Salesfloor, Women’s Restroom
Category I Nonfriable
Included in Quantity of HA
City of Olathe Public Improvements Asbestos Survey
Townsquare Shopping Center - Building 7 | Olathe, Kansas
August 18, 2025 | Terracon Project No. 02237230
Facilities | Environmental | Geotechnical | Materials ii
Material Description Material Location
NESHAP
Category
Estimated
Quantity
Black Mastic associated with 12" x 12" Red Floor Tile
Unit 140 - Salesfloor Category I Nonfriable
Included in
Quantity of HA
12" x 12" Grey with Tan Streaks Floor Tile and Black Mastic
Unit 132 - Restroom Category I Nonfriable
Square Feet
12" x 12" Tan/Green Design-Print Floor Tile with Tan Mastic
Unit 134A - North Room Category I Nonfriable
Square Feet
Faux-CFT Sheet Flooring with
Paper Backing Unit 130B - Restrooms RACM
Square Feet
Black Mastic associated with Grey/Light Grey/Blue with Black and White Flecks Epoxy Flooring
Unit 132 - NE-Central Area, West-Central Area, SE Area
Category I Nonfriable
Square Feet
Black Wall Mastic Unit 140 - South Breakroom, West Wall Category I Nonfriable
Linear Feet
Roofing Material Roof - On East AHU over
Unit 128 Category I Nonfriable
Linear Feet
Flashing Sealant
Roof - NE Corner Breezeway Wall, East Perimeter Wall over Unit 128, South-Central Area Exhaust over Unit 140
Category I
Nonfriable
Linear Feet
Tar Sealant Roof - On Pipes over Units
138 and 140 Category I Nonfriable
Linear Feet
Notes: NESHAP – National Emission Standards for Hazardous Air Pollutants RACM - Regulated Asbestos-Containing Material
Asbestos was identified at a concentration of 1% or less in samples collected from the following materials:
Material Description Material Location
Joint Compound associated with Drywall Wallboard System
Throughout Subject Building
12" x 12" Red Floor Tile Unit 140 - Salesfloor
Please refer to Section 3.0 of the attached report for a detailed description of the asbestos survey, sampling activities, and findings.
Facilities | Environmental | Geotechnical | Materials iii
Terracon appreciates the opportunity to provide this service to the City of Olathe, Kansas. If you have any questions regarding this report, please contact our office at
913-492-7777.
Sincerely, Terracon
Ryan Slanczka Clark Grisell
Senior Staff Scientist Environmental Group Manager
Building Environmental Sciences
Ryan Slanczka Clark Grisell
Facilities | Environmental | Geotechnical | Materials iv
Table Of Contents
1.0 Introduction 1
1.1 Reliance 1
2.0 Building Description 1
3.0 Asbestos-Containing Materials Survey 1
3.1 Visual Assessment 2
3.2 Physical Assessment 2
3.3 Sample Collection 2
3.4 Sample Analysis 2
3.5 Regulatory Overview 3
3.6 Findings 3
4.0 General Comments 5
Appendices
Appendix A Asbestos-Containing Materials By Homogeneous Area
Appendix B Asbestos Survey Sample Location Summary
Appendix C Asbestos Laboratory Analytical Results
Appendix D Certifications
Facilities | Environmental | Geotechnical | Materials 1
1.0 Introduction
Terracon Consultants, Inc. (Terracon) conducted an asbestos-containing material survey of the Townsquare Shopping Center - Building 7 located at 128-140 South Clairborne
Road in Olathe, Kansas, on May 15, 2025. Building areas were visually assessed for suspect asbestos-containing materials (ACM). A reasonable effort was made to inspect accessible areas. Additional suspect materials could be present in walls, voids, or other concealed areas.
1.1 Reliance
This report is for the exclusive use of the City of Olathe, Kansas, for the project being discussed. Reliance by any other party on this report is prohibited without the written authorization of Terracon and the City of Olathe, Kansas.
2.0 Building Description
The subject building is an approximately 45,350-square-foot, single-story community shopping center (with exterior metal canopy), reportedly constructed in 1975. Interior flooring finishes include ceramic tiles, epoxy, sheet vinyl, carpeting, and vinyl tiles over concrete. Interior walls throughout the building are drywall/joint compound wallboard, with acoustic texture, wallpaper, and ceramic tile finishes in various areas. Perimeter walls throughout the building are concrete block and concrete block with an associated wall texture. The primary, observable ceiling system is a drop, grid ceiling with lay-in acoustic tiles below a metal deck. The building’s exterior has concrete block and fluted-block siding. The roof consists of a single-ply synthetic rubber membrane system.
3.0 Asbestos-Containing Materials Survey
The survey was conducted by Mr. Ryan Slanczka and Mr. Blake Harris, State of Kansas-accredited asbestos inspectors. Copies of the asbestos inspectors’ accreditations are attached as Appendix D. The survey was conducted in general accordance with the sample collection protocols established in the United States Environmental Protection
Agency (USEPA) 40 Code of Federal Regulations (CFR) Part 763 Subpart E 763.86, the
Asbestos Hazard Emergency Response Act (AHERA). A summary of survey activities is provided below.
Facilities | Environmental | Geotechnical | Materials 2
3.1 Visual Assessment
Survey activities were initiated with visual observation of the interior and exterior of the building to identify homogeneous areas of suspect ACM. A homogeneous area (HA) consists of a building material that appears similar throughout in terms of color and texture, with consideration given to the date of application. The assessment was conducted in visually accessible areas of the building scheduled for renovation.
3.2 Physical Assessment
A physical assessment of each HA of suspect ACM was conducted to assess the friability and condition of the materials. A friable material is defined by the USEPA as a material that can be crumbled, pulverized, or reduced to powder by hand pressure when dry.
Friability was assessed by physically touching suspect materials.
3.3 Sample Collection
Based on the results of the visual observation, bulk samples of suspect ACM samples were collected in general accordance with USEPA AHERA sampling protocols. Samples of suspect materials were collected from randomly selected locations in each homogeneous area. Bulk samples were collected using wet methods, as applicable, to reduce the potential for fiber release. Samples were placed in sealable containers and labeled with unique sample numbers using an indelible marker.
Rubber, wood products, plastic products, glass, and steel are not considered suspect
ACM and were, therefore, not sampled. The selection of sample locations and frequency of sampling were based on Terracon’s observations and the assumption that like materials in the same area are homogeneous in content. Terracon collected 160 bulk samples from 51 homogeneous areas of suspect ACM.
3.4 Sample Analysis
Bulk samples were submitted under chain of custody to Eurofins International Asbestos
Testing Laboratories (Eurofins) of Mount Laurel, New Jersey, for analysis by PLM with dispersion staining techniques per USEPA Method 600/R-93/116. The percentage of asbestos, where applicable, was determined by microscopic visual estimation. Eurofins is accredited under the National Voluntary Laboratory Accreditation Program (NVLAP), Accreditation No. 101165.
Facilities | Environmental | Geotechnical | Materials 3
3.5 Regulatory Overview
The asbestos National Emission Standards for Hazardous Air Pollutants (NESHAP) regulation (40 CFR Part 61, Subpart M) regulates asbestos fiber emissions and asbestos waste disposal practices. The asbestos NESHAP regulation also requires the identification and classification of existing ACM according to friability prior to demolition or renovation activity. Friable ACM is a material containing more than 1% asbestos that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure.
The asbestos NESHAP regulation classifies ACM as regulated asbestos-containing materials (RACM), Category I non-friable ACM, or Category II non-friable ACM. RACM includes all friable ACM; Category I non-friable ACM that has become friable or will be or has been subjected to sanding, grinding, cutting, or abrading; and Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder in the course of renovation or demolition activity. Category I non-friable ACM are exclusively asbestos-containing packings, gaskets, resilient floor coverings, resilient floor covering mastics, and asphalt roofing products that contain more than 1% asbestos. Category II non-friable ACM are all other non-friable materials other than Category I non-friable ACM that contain more than 1% asbestos. Category II non-friable ACM generally includes but is not limited to cementitious material such as cement pipes, cement siding, cement panels, glazing, mortar, and grouts.
The Kansas Department of Health and Environment’s (KDHE) Asbestos Control Section within the Bureau of Air enforces the Asbestos NESHAP as adopted by reference at
Kansas Administrative Regulations (K.A.R.) 28-19-735. The owner or operator must provide KDHE with written notification at least 10 working days prior to the commencement of asbestos abatement activities that will disturb RACM in amounts greater than or equal to 10 square feet or 25 linear feet.
The United States Occupational Safety and Health Administration (USOSHA) asbestos standard for construction (29 CFR 1926.1101) regulates workplace exposure to asbestos. The OSHA standard classifies construction and maintenance activities that could disturb ACM and specifies work practices and precautions that employers must follow when engaging in each class of regulated work. The standard also specifies requirements for handling materials containing asbestos in concentrations less than or equal to one percent.
3.6 Findings
Asbestos was identified at a concentration greater than 1% in samples collected from the following materials:
Facilities | Environmental | Geotechnical | Materials 4
Material Description Material Location
NESHAP
Category
Estimated
Quantity
Black Mastic associated with 6" x 6" Red Ceramic Floor Tile with Grout and Mortar
Unit 134B - NW-Central Room, SW Room
Category I Nonfriable
Square Feet
12" x 12" Beige with Tan Streaks Floor Tile and Black Mastic
Unit 140 - Salesfloor, South Breakroom, SE Office
Category I Nonfriable
18,675 Square Feet
Black/Brown Mastic associated with 12" x 12" Beige Mottle Floor Tile with Tan & Brown Mastic
Unit 140 - Salesfloor, Women’s Restroom
Category I Nonfriable
Included in
Quantity of HA
Black Mastic associated with 12" x 12" Red Floor Tile
Unit 140 - Salesfloor Category I Nonfriable
Included in Quantity of HA
12" x 12" Grey with Tan Streaks Floor Tile and Black Mastic
Unit 132 - Restroom Category I Nonfriable
Square Feet
12" x 12" Tan/Green Design-Print
Floor Tile with Tan Mastic Unit 134A - North Room
Category I
Nonfriable
Square Feet
Faux-CFT Sheet Flooring with Paper Backing
Unit 130B - Restrooms RACM
Square Feet
Black Mastic associated with Grey/Light Grey/Blue with Black and White Flecks Epoxy Flooring
Unit 132 - NE-Central Area, West-Central Area, SE Area
Category I Nonfriable
Square Feet
Black Wall Mastic Unit 140 - South Breakroom, West Wall
Category I
Nonfriable
Linear Feet
Roofing Material Roof - On East AHU over
Unit 128 Category I Nonfriable
Linear Feet
Flashing Sealant
Roof - NE Corner Breezeway
Wall, East Perimeter Wall over Unit 128, South-Central Area Exhaust over Unit 140
Category I Nonfriable
Linear Feet
Tar Sealant Roof - On Pipes over Units
138 and 140 Category I Nonfriable
Linear Feet
Notes: NESHAP - National Emission Standards for Hazardous Air Pollutants RACM - Regulated Asbestos-Containing Material
The above-listed RACM must be removed by a State of Kansas licensed abatement contractor prior to any activities (renovation and/or demolition) that may disturb the material in accordance with applicable federal, state, and local regulations.
The above-listed Category I non-friable ACM that is damaged or could be damaged to the extent that it could be crumbled, pulverized, or reduced to powder when dry, making it friable, must be removed prior to any activities (renovation and/or demolition) that may disturb this material in accordance with applicable federal, state, and local
Facilities | Environmental | Geotechnical | Materials 5 regulations. Terracon recommends that all ACM be removed by an abatement contractor prior to any demolition or renovation work that may disturb it.
Asbestos was identified at a concentration of 1% or less in samples collected from the following materials:
Material Description Material Location
Joint Compound associated with Drywall Wallboard
System Throughout Subject Building
12" x 12" Red Floor Tile Unit 140 - Salesfloor
Materials containing 1% or less asbestos are not regulated by NESHAP or AHERA;
however, the USOSHA personal exposure limits (0.1 f/cc of air as an eight-hour time-weighted average or 1.0 f/cc of air over 30 minutes) for asbestos apply when materials containing 1% asbestos or less are disturbed during renovations or demolitions. A listing of materials that contain 1% asbestos or less is provided above to enable the renovation/demolition contractor to make appropriate decisions concerning compliance issues with applicable USOSHA regulations.
Joint Compound and/or tape that is applied to a wallboard system becomes an integral part of that wallboard system. A composite analysis of the wall system (percent of asbestos in the joint compound, tape, and wallboard composite) should be conducted where a demolition or renovation is to be performed, and when allowed by regulations
(not allowed in some states). This is in addition to analysis by layers. State and local agencies should be consulted for additional regulatory requirements.
A summary of identified asbestos-containing materials by homogeneous area is included in Appendix A. A summary of sample locations is included in Appendix B. Laboratory analytical reports are included in Appendix C.
4.0 General Comments
Terracon did not perform sampling that required demolition or destructive activities such as dismantling of equipment or removal of protective coverings. Reasonable efforts to access suspect materials within known areas of restricted access (e.g., crawl spaces) were made; however, confined spaces or areas that may pose a health or safety risk to
Terracon personnel were not sampled. Sampling did not include suspect materials that could not be safely reached with available ladders or manlifts. Terracon did not sample suspect materials that may be present in movable equipment such as freezers, kitchen equipment, and hoods. Terracon typically investigates for flooring beneath carpeting by
Facilities | Environmental | Geotechnical | Materials 6 lifting small corner sections of carpet. If tiles or sheet vinyl were seen, they have been identified in the report. If tiles or sheet vinyl were not seen at corners under the carpet, it does not imply that there is none beneath the carpeted floor. Terracon did not conduct a destructive investigation of the doors in the building to determine if the doors were insulated for fire-rating purposes.
This survey was conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions, and recommendations expressed in this report are based on conditions observed during Terracon’s survey of the building. The information contained in this report is relevant to the date on which this survey was performed, and should not be relied upon to represent conditions at a later date. This report has been prepared on behalf of and exclusively for use by the City of Olathe, Kansas, and is not a bidding document. Contractors or consultants reviewing this report must draw their own conclusions regarding further investigation or remediation deemed necessary. Terracon does not warrant the work of regulatory agencies, laboratories, or other third parties supplying information that may have been used in the preparation of this report. No warranty, express or implied, is made.
Appendix A
Asbestos-Containing Materials By Homogeneous Area
Appendix A-1
Identified Asbestos-Containing Materials By Homogeneous Area (HA)
128-140 South Clairborne Road, Olathe, Kansas
Terracon Project No. 02237230
HA Material Description Material Location % and Type
Asbestos*
NESHAP
Classification Condition
Estimated
Quantity**
Black Mastic associated with 6" x 6" Red Ceramic Floor Tile with Grout and Mortar
Unit 134B - NW-Central Room, SW Room
Red Ceramic Tile - None Detected
Black Mastic - 2% Chrysotile Grey Grout - None Detected
Off-White Mortar - None Detected
Light Grey Mortar - None Detected
Category I Nonfriable
Damaged (Fair)
Square Feet
12" x 12" Beige with Tan
Streaks Floor Tile and Black Mastic
Unit 140 - Salesfloor, South Breakroom, SE Office
White Floor Tile - 2% Chrysotile
Beige Floor Tile - 2% Chrysotile Black Mastic - 2% Chrysotile
Category I Nonfriable
Damaged (Fair)
18,675 Square Feet
Black/Brown Mastic associated with 12" x 12"
Beige Mottle Floor Tile with Tan & Brown Mastic
Unit 140 - Salesfloor, Women’s Restroom
Beige Floor Tile - None Detected
Brown Mastic - None Detected Black/Brown Mastic - 2%
Chrysotile
Category I Nonfriable
Damaged (Fair)
Included in Quantity of HA
24 Black Mastic associated with 12" x 12" Red Floor Tile
Unit 140 - Salesfloor Red Floor Tile - <1% Chrysotile
Black Mastic - 3% Chrysotile Category I Nonfriable
Damaged (Fair)
Included in Quantity of HA
12" x 12" Grey with Tan
Streaks Floor Tile and Black Mastic
Unit 132 - Restroom
Tan Floor Tile with Grey Paint - 2% Chrysotile
Tan Floor Tile - 2% Chrysotile Black Mastic - 2% Chrysotile
Category I Nonfriable
Damaged (Fair)
Square Feet
12" x 12" Tan/Green
Design-Print Floor Tile with Tan Mastic
Unit 134A - North Room
Tan Floor Tile - 2% Chrysotile Green Floor Tile - 2%
Chrysotile Tan Mastic - None Detected
Beige Mastic - None Detected
Category I Nonfriable
Damaged (Fair)
Square Feet
Faux-CFT Sheet Flooring with Paper Backing Unit 130B - Restrooms
Tan Sheet Flooring - 25% Chrysotile
Yellow Mastic - None Detected
RACM
Damaged (Fair)
Square Feet
Asbestos*
NESHAP
Classification Condition
Estimated
Quantity**
Black Mastic associated with Grey/Light Grey/Blue with
Black and White Flecks Epoxy Flooring
Unit 132 - NE-Central Area, West-Central Area, SE Area
Grey Flooring Epoxy - None Detected
Black Mastic - 2% Chrysotile
Category I Nonfriable
Damaged (Fair)
Square Feet
48 Black Wall Mastic Unit 140 - South
Breakroom, West Wall Black Mastic - 3% Chrysotile
Category I Nonfriable
Good
Linear Feet
63 Roofing Material Roof - On East AHU over
Unit 128 Black Roofing Material - 20%
Chrysotile Category I Nonfriable
Good
Linear Feet
65 Flashing Sealant
Roof - NE Corner Breezeway Wall, East Perimeter Wall over Unit 128, South- Central Area Exhaust over
Unit 140
White Sealant - None Detected Grey Sealant - None Detected
Black Tar - 8% Chrysotile
Category I Nonfriable
Good
Linear Feet
66 Tar Sealant Roof - On Pipes over Units
138 and 140 Black/White Tar - 7%
Chrysotile Category I Nonfriable
Good
Linear Feet
*% & Type Asbestos – this column contains both the analytical result of the sample with the highest concentration of asbestos detected in the samples that make up the HA, and the types of asbestos identified.
**Estimated quantities – quantities based on a cursory field evaluation, and actual quantities may vary significantly, especially if asbestos-containing materials are present in hidden and/or inaccessible areas not evaluated as part of this survey. This is not a bidding document; contractors are responsible for determining their own opinion of quantities.
Appendix A-2
Materials Containing Asbestos at a Concentration of 1% or Less By HA
Asbestos* Condition
Joint Compound associated with Drywall
Wallboard System Throughout Subject Building
White Drywall with Brown Paper - None Detected White Joint Compound - 2% Chrysotile
Beige Tape - None Detected Sample Composite - <1% Chrysotile
Damaged (Fair)
24 12" x 12" Red Floor Tile Unit 140 - Salesfloor Red Floor Tile - <1% Chrysotile Damaged
(Fair)
*% & Type Asbestos – this column contains both the analytical result of the sample with the highest concentration of asbestos detected in the samples that make up the HA, and the types of asbestos identified.
<1% - Materials containing less than 1% asbestos are not regulated by NESHAP or AHERA; however, the USOSHA personal exposure limits (0.1 f/cc of air as an eight-hour time-weighted average or 1.0 f/cc of air over 30 minutes) for asbestos apply when materials containing 1% asbestos or less are disturbed during renovation or demolition. A listing of materials that contain 1% asbestos or less is provided above to enable the renovation/demolition contractor to make appropriate decisions concerning compliance issues with applicable USOSHA regulations.
Appendix B
Asbestos Survey Sample Location Summary
Appendix B
Asbestos Survey Sample Location Summary
HA
No.
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
Drywall with Joint
Compound
01-WB5-01 Unit 140 - Salesfloor, SW Area, East Wall
White Drywall with Brown Paper
None Detected
White Joint Compound
01-WB5-02 Unit 140 - Stockroom, North Wall
White Drywall with Brown Paper
None Detected
White Joint Compound
01-WB5-03 Unit 140 - Salesfloor, SW Area, West Wall
White Drywall with Brown Paper None Detected
White Joint Compound 2% Chrysotile
Beige Tape None Detected
Composite <1% Chrysotile
01-WB5-04 Unit 138 - East Wall
White Drywall with Brown Paper
None Detected White Joint Compound
Beige Tape
01-WB5-05 Unit 132 - West Wall, Central Area
White Drywall with Brown Paper
None Detected White Joint Compound
Beige Tape
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
Drywall with Joint
Compound
01-WB5-06
Unit 134B - North Room, West Wall, North
Area
White Drywall with Brown Paper
None Detected White Joint Compound
Beige Tape
01-WB5-07
Unit 130B - North Room, South Wall, near door to NE Room
White Drywall with Brown Paper
None Detected
White Joint Compound
2 Orange-Peel Wall Texture
02-PL1-08 Unit 134A - Hallway, West Wall, North Area White Texture
None Detected 02-PL1-09 Unit 134A - Hallway, West Wall, Central Area White Texture
02-PL1-10 Unit 134A - Hallway, West Wall, South Area White Texture
3 Plaster Wall Texture
03-PL1-11 Unit 132 - Restroom, North Wall White Texture
None Detected 03-PL1-12 Unit 132 - Restroom, East Wall White Texture
03-PL1-13 Unit 132 - Restroom, East Wall White Texture
4 Plaster Wall Texture
04-PL1-14
Unit 130B - WNW Room, West Wall, North
Area White Texture
None Detected 04-PL1-15 Unit 130B - WNW Room, West Wall, Central
Area White Texture
04-PL1-16
Unit 130B - WNW Room, West Wall, South
Area White Texture
5 Wallpaper
05-SG5-17 Unit 134A - North Room, North Area, East Wall Blue Wallpaper
None Detected 05-SG5-18 Unit 134A - North Room, North Area, East Wall Blue Wallpaper
05-SG5-19 Unit 134A - North Room, North Area, East Wall Blue Wallpaper
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
6 Concrete Wall Texture
06-SC5-20 Unit 140 - South Perimeter Wall White Concrete Wall Texture
None Detected
06-SC5-21 Unit 140 - South Perimeter Wall White Concrete Wall Texture
06-SC5-22 Unit 140 - East Perimeter Wall White Concrete Wall Texture
06-SC5-23 Unit 138 - South Perimeter Wall Tan Concrete Wall Texture
06-SC5-24 Unit 132 - South Perimeter Wall, Central Area Tan Concrete Wall Texture
06-SC5-25 Unit 128 - Exterior, East
Tan Concrete Wall Texture
Grey Concrete
06-SC5-26 Unit 140 - Exterior, SE Corner
Tan Concrete Wall Texture
Grey Concrete
2' x 4' Ceiling Tile with
Pinholes and Divots
07-CT4-27 Unit 134A - South Room, South Area White Ceiling Tile
None Detected 07-CT4-28 Unit 140 - South Breakroom White Ceiling Tile
07-CT4-29 Unit 134B - North Room, West Area White Ceiling Tile
2' x 4' Fiberglass Ceiling
Tile with Pinholes and
Fissures
08-CT4-30 Unit 132 - NW Area Yellow/White Ceiling Tile
None Detected 08-CT4-31 Unit 140 - South Breakroom Yellow/White Ceiling Tile
08-CT4-32 Unit 140 - Women's Restroom Yellow/White Ceiling Tile
2' x 4' Ceiling Tile with
Pinholes and Fissures
09-CT4-33 Unit 140 - Women's Restroom White Ceiling Tile
None Detected 09-CT4-34 Unit 134B - Central Room, Central Area White Ceiling Tile
09-CT4-35 Unit 132 - NW Area White Ceiling Tile
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
2' x 4' Ceiling Tile with
High-Density Pinholes and
Fissures
10-CT4-36 Unit 134A - North Room, South Area White Ceiling Tile
None Detected 10-CT4-37 Unit 130B - WNW Room, South Area White Ceiling Tile
10-CT4-38 Unit 134A - South Room, East Area White Ceiling Tile
2' x 4' Ceiling Tile with
Pinholes and Dents
11-CT4-39 Unit 134B - North Room, North Area White Ceiling Tile
None Detected 11-CT4-40 Unit 134A - South Room, South Area White Ceiling Tile
11-CT4-41 Unit 132 - West-Central Area White Ceiling Tile
2' x 2' Rough-Textured
Ceiling Tile with Pinholes
12-CT4-42 Unit 134A - East-Central Room, North Area White Ceiling Tile
None Detected 12-CT4-43 Unit 134A - East-Central Room, South Area White Ceiling Tile
12-CT4-44 Unit 134A - SE-Central Room, West Area White Ceiling Tile
13 2' x 4' Gypsum Ceiling Tile
13-CT4-45 Unit 134B - North Room, West Area White Ceiling Tile (Gypsum)
None Detected 13-CT4-46 Unit 134B - SW Room, Central Area White Ceiling Tile (Gypsum)
13-CT4-47 Unit 134B - SW-Central Room, NE Area White Ceiling Tile (Gypsum)
4" Cove Base with Tan and
Brown Mastic
14-FC3-48 Unit 140 - Salesfloor, North Wall
Brown Cove Base
None Detected
Tan Mastic
Brown Mastic
14-FC3-49 Unit 140 - SE Office
White Cove Base
Tan Mastic
Brown Mastic
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
4" Cove Base with Tan and
Brown Mastic 14-FC3-50 Unit 140 - SE Office
Brown Cove Base
None Detected Tan Mastic
Brown Mastic
4" Cove Base with Tan
Mastic
15-FC3-51 Unit 136 - North Area, East Wall
White/Grey Cove Base
None Detected
Tan Mastic
15-FC3-52
Unit 134B - North Room, East Wall, South
Area
Black Cove Base
Tan Mastic
15-FC3-53
Unit 130B - North Room, West Wall, North
Area
Grey Cove Base
Tan Mastic
4" Cove Base with Brown
Mastic
16-FC3-54 Unit 132 - SW Room, West Wall
Brown Cove Base
None Detected
Brown Mastic
16-FC3-55
Unit 134B - North Room, West Wall, Central
Area
Black Cove Base
Brown Mastic
16-FC3-56
Unit 134B - North Room, West Wall, Central
Area
Black Cove Base
Brown Mastic
6" x 6" Red Ceramic Wall
Tile with Grout and Mastic
17-MA5-57
Unit 134B - North Room, West Wall, Central
Area
Red Ceramic Tile
None Detected Yellow Mastic
Grey Grout
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
6" x 6" Red Ceramic Wall
Tile with Grout and Mastic
17-MA5-58
Unit 134B - North Room, West Wall, Central
Area
Red Ceramic Tile
None Detected
Yellow Mastic
Grey Grout
17-MA5-59
Unit 134B - South-Central Room, North Wall, near Door
Red Ceramic Tile
Yellow Mastic
Grey Grout
6" x 6" Red Ceramic Wall
Tile with Grout and Mortar
18-MA5-60 Unit 134B - WNW Room, West Wall
Red Ceramic Tile
None Detected
Grey Grout
18-MA5-61 Unit 134B - SW Room, West Wall, Central Area
Red Ceramic Tile
Yellow Mastic
Grey Grout
18-MA5-62 Unit 134B - SW Room, West Wall, South Area
Red Ceramic Tile
Yellow Mastic
Grey Grout
Grey/Red Ceramic Floor
Tile with Grout and Mortar 19-MA5-63 Unit 136 - SW Room
Red Ceramic Tile
None Detected
Yellow Mastic
Grey Grout
White Mortar
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
Grey/Red Ceramic Floor
Tile with Grout and Mortar
19-MA5-64 Unit 136 - SW Room
Red Ceramic Tile
None Detected
White Mortar
Grey Grout
19-MA5-65 Unit 136 - SW Room
Red Ceramic Tile
White Mortar
Grey Grout
6" x 6" Red Ceramic
Floor Tile with Grout and Mortar
20-MA5-66 Unit 134B - NW-Central Room
Red Ceramic Tile None Detected
Black Mastic 2% Chrysotile
Grey Grout None Detected
Off-White Mortar None Detected
20-MA5-67 Unit 134B - SW Room, NE Area
Red Ceramic Tile None Detected
Grey Grout None Detected
Light Grey Mortar None Detected
Black Mastic 2% Chrysotile
20-MA5-68 Unit 134B - SW Room, NE Area
Red Ceramic Tile None Detected
Grey Grout None Detected
Light Grey Mortar None Detected
Black Mastic 2% Chrysotile
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
12" x 12" Tan Ceramic
Floor Tile with Grout and
Mortar
21-MA5-69 Unit 130B - NE Room
Brown Ceramic Tile
None Detected
Grey Grout
Brown Mortar
21-MA5-70 Unit 130B - NE Room
Brown Ceramic Tile
Grey Grout
Brown Mortar
21-MA5-71 Unit 130B - NE Room
Brown Ceramic Tile
Grey Grout
Brown Mortar
12" x 12" Beige with
Tan Streaks Floor Tile with Black Mastic
22-FT2-72 Unit 140 - Salesfloor, NW Area
White Floor Tile 2% Chrysotile
Black Mastic 2% Chrysotile
22-FT2-73 Unit 140 - South Breakroom
Beige Floor Tile 2% Chrysotile
Black Mastic 2% Chrysotile
22-FT2-74 Unit 140 - SE Office
Beige Floor Tile 2% Chrysotile
Black Mastic 2% Chrysotile
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
12" x 12" Beige Mottle
Floor Tile with Tan &
Brown Mastic
23-FT2-75 Unit 140 - Salesfloor, Central Area
Beige Floor Tile
None Detected
Brown Mastic
23-FT2-76 Unit 140 - Women's Restroom
Beige Floor Tile None Detected
Black/Brown Mastic 2% Chrysotile
23-FT2-77 Unit 140 - Salesfloor, SW Area
Beige Floor Tile None Detected
Black/Brown Mastic 2% Chrysotile
12" x 12" Red Floor Tile with Black Mastic
24-FT2-78 Unit 140 - Salesfloor, West Area
Red Floor Tile < 1%
Chrysotile
Black Mastic 3% Chrysotile
24-FT2-79 Unit 140 - Salesfloor, West Area
Red Floor Tile < 1%
Chrysotile
Black Mastic 3% Chrysotile
24-FT2-80 Unit 140 - Salesfloor, West Area
Red Floor Tile < 1%
Chrysotile
Black Mastic 3% Chrysotile
12" x 12" Grey Mottle Floor
Tile with Tan Mastic
25-FT2-81 Unit 138 - SE Restroom
Grey Floor Tile
None Detected
Tan Mastic
25-FT2-82 Unit 138 - SE Restroom
Grey Floor Tile
Tan Mastic
White Joint Compound
25-FT2-83 Unit 138 - SE Restroom
Grey Floor Tile
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
12" x 12" White Mottle
Floor Tile with Tan Mastic
26-FT2-84 Unit 136 - NW Area
White Floor Tile with Black Paint
None Detected
Tan Mastic
26-FT2-85 Unit 136 - South Area
White Floor Tile with Black Paint
Tan Mastic
26-FT2-86 Unit 136 - SE Room
White Floor Tile
Tan Mastic
26-FT2-87 Unit 136 - NE Area
White Floor Tile with Black Paint
Tan Mastic
12" x 12" Grey with Tan
Streaks Floor Tile with
Black Mastic
27-FT2-88 Unit 132 - Restroom
Tan Floor Tile with Grey Paint 2% Chrysotile
Black Mastic 2% Chrysotile
27-FT2-89 Unit 132 - Restroom
Tan Floor Tile with Grey Paint 2% Chrysotile
Black Mastic 2% Chrysotile
27-FT2-90 Unit 132 - Restroom
Tan Floor Tile 2% Chrysotile
Black Mastic 2% Chrysotile
12" x 12" Light Grey with
Black Streaks Floor Tile with Tan Mastic
28-FT2-91 Unit 134A - North Room, North Area
Grey Floor Tile
None Detected
Tan Mastic
28-FT2-92 Unit 134A - North Room, North Area
Grey Floor Tile
Tan Mastic
28-FT2-93 Unit 134A - North Room, North Area
Grey Floor Tile
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
12" x 12" Tan/Green
Design-Print Floor Tile with Tan Mastic
29-FT2-94 Unit 134A - North Room, North Area
Tan Floor Tile 2% Chrysotile
Tan Mastic None Detected
Beige Mastic None Detected
29-FT2-95 Unit 134A - North Room, Central Area
Tan Floor Tile 2% Chrysotile
Tan Mastic None Detected
Beige Mastic None Detected
29-FT2-96 Unit 134A - North Room, Central Area
Green Floor Tile 2% Chrysotile
Tan Mastic None Detected
Beige Mastic None Detected
Peel 'n' Stick Floor Tile with
Adhesive
30-FT2-97 Unit 134B - North Room, NE Area
Grey Floor Tile Peel and Stick
None Detected
Tan Mastic
30-FT2-98 Unit 134B - SW Room, NE Area
Grey Floor Tile Peel and Stick
Tan Mastic
30-FT2-99 Unit 134B - North Room, West-Central Area
Grey Floor Tile Peel and Stick
Tan Mastic
12" x 12" Green, Tan Floor
Tile with Tan Mastic
31-FT2-100 Unit 134B - North Room, NE Area
Tan Floor Tile
None Detected
Tan Mastic
31-FT2-101 Unit 134B - North Room, SE-Central Area
Tan Floor Tile
Grey Leveling Compound
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
12" x 12" Green, Tan Floor
Tile with Tan Mastic 31-FT2-102 Unit 134B - North Room, West-Central Area
Green Floor Tile
None Detected
Tan Mastic
6" x 6" Green, Red Floor
Tile with Tan Mastic
32-FT2-103
Unit 134B - South Hallway, near North
Restroom
Red Floor Tile
None Detected
Tan Mastic
32-FT2-104
Unit 134B - South Hallway, near North
Restroom
Green Floor Tile
Tan Mastic
32-FT2-105
Unit 134B - South Hallway, near North
Restroom
Red Floor Tile
Tan Mastic
12" x 12" Tan Floor Tile with Mastic
33-FT2-106 Unit 128 - NE Room, near Door
Tan Floor Tile
None Detected
Black Mastic
33-FT2-107 Unit 128 - Kitchen, NE Area
Tan Floor Tile
Tan Mastic
33-FT2-108 Unit 130A - West Restroom
Tan Floor Tile
Tan Mastic
Faux-CFT Sheet Flooring with Paper Backing
34-FC1-109 Unit 130B - West Restroom Tan Sheet Flooring 25% Chrysotile
34-FC1-110 Unit 130B - West Restroom Tan Sheet Flooring 25% Chrysotile
34-FC1-111 Unit 130B - South Restroom
Tan Sheet Flooring 25% Chrysotile
Yellow Mastic None Detected
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
35 Tan Carpet Adhesive
35-MG7-112 Unit 136 - South Area Yellow Mastic with Grey Fibrous
Material
None Detected 35-MG7-113 Unit 136 - South Area Yellow Mastic with Grey Fibrous
Material
35-MG7-114 Unit 136 - South Area Yellow Mastic
36 Tan Carpet Adhesive
36-MG7-115 Unit 134A - North Room, North Area Yellow Mastic
None Detected 36-MG7-116 Unit 134A - North Room, North Area Yellow Mastic
36-MG7-117 Unit 134A - North Room, North Area Yellow Mastic
Tan Carpet Adhesive with
Paper
37-MG7-118 Unit 134A - Hallway, Central Area
Red Carpet
None Detected
Yellow Mastic
Brown Insulation
Brown Paper
37-MG7-119 Unit 134A - Hallway, Central Area
Red Carpet
Yellow Mastic
Brown Insulation
Brown Paper
37-MG7-120 Unit 134A - Hallway, Central Area
Red Carpet
Yellow Mastic
Brown Insulation
Brown Paper
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
38 Tan Carpet Adhesive
38-MG7-121 Unit 134B - North Room, SE Area Yellow Mastic
None Detected 38-MG7-122 Unit 134B - SE Room, East-Central Area Yellow Mastic
38-MG7-123 Unit 134B - North Room, NE Area Yellow Mastic
39 Tan Carpet Adhesive
39-MG7-124 Unit 130B - North Room, Central Area Yellow Mastic
None Detected 39-MG7-125 Unit 130B - WNW Room, Central Area Yellow Mastic
39-MG7-126 Unit 130B - SE Room Yellow Mastic
40 Residual Black Mastic
40-MG5-127
Unit 128 - North Room, near NE Overhead
Door Black Mastic
None Detected 40-MG5-128 Unit 128 - North Room, Central Area Black Mastic
40-MG5-129 Unit 130A - South Area Black Mastic
Grey/Light Grey/Blue with Black and White
Flecks Epoxy Flooring
41-FC2-130 Unit 132 - NE-Central Area Grey Flooring Epoxy None Detected
41-FC2-131 Unit 132 - West-Central Area
Grey Flooring Epoxy None Detected
Black Mastic 2% Chrysotile
41-FC2-132 Unit 132 - SE Area
Grey Flooring Epoxy None Detected
Black Mastic 2% Chrysotile
42 Epoxy Flooring
42-FC2-133 Unit 134B - North Restroom Grey/White Flooring Epoxy
None Detected 42-FC2-134 Unit 134B - South Restroom Grey/White Flooring Epoxy
42-FC2-135 Unit 134B - South Restroom Grey/White Flooring Epoxy
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
Pink, Grey Leveling
Compound
43-FC6-136 Unit 134B - North Room, NW Area Pink/Grey Leveling Compound
None Detected
43-FC6-137 Unit 134B - North Room, SE-Central Area Pink/Grey Leveling Compound
43-FC6-138 Unit 134B - North Room, SW Area Pink/Grey Leveling Compound
43-FC6-139 Unit 134B - North Room, West-Central Area Pink/Grey Leveling Compound
43-FC6-140 Unit 134B - North Room, West-Central Area Pink/Grey Leveling Compound
44 White Leveling Compound
44-FC6-141 Unit 134B - North Room, NE-Central Area
White Leveling Compound
None Detected
Yellow Mastic
44-FC6-142 Unit 134B - North Room, NE-Central Area
White Leveling Compound
Yellow Mastic
44-FC6-143 Unit 134B - North Room, NE Area
White Leveling Compound
Yellow Mastic
Pink-White Leveling
Compound
45-FC6-144 Unit 134B - SW Room, NW Area
White Leveling Compound
None Detected
Yellow Mastic
45-FC6-145 Unit 134B - SW Room, NW Area
White Leveling Compound
Yellow Mastic
45-FC6-146 Unit 134B - SW Room, NW Area
White Leveling Compound
Yellow Mastic
46 Concrete Slab
46-CP5-147 Unit 140 - Stockroom, East Area Grey Concrete
None Detected
46-CP5-148 Unit 138 - Open Room, Central Area Grey Concrete
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
46 Concrete Slab 46-CP5-149 Unit 132 - NW Area, at Door to Unit 134A Grey Concrete None Detected
47 Door Caulk
47-CA2-150 Unit 130B - Door to South Exterior
White Caulk
None Detected
Tan Cementitious Material
47-CA2-151 Unit 130B - Door to South Exterior
White Caulk
Tan Cementitious Material
47-CA2-152 Unit 130B - Door to South Exterior
White Caulk
Tan Cementitious Material
48 Black Wall Mastic
48-MG5-153 Unit 140 - South Breakroom, West Wall Black Mastic 3% Chrysotile
48-MG5-154 Unit 140 - South Breakroom, West Wall Black Mastic 3% Chrysotile
48-MG5-155 Unit 140 - South Breakroom, West Wall Black Mastic 3% Chrysotile
49 Grey/Green Wall Mastic
49-MG5-156 Unit 140 - Salesfloor, SW Area, East Wall Grey Mastic
None Detected 49-MG5-157 Unit 140 - Salesfloor, SW Area, East Wall Grey Mastic
49-MG5-158 Unit 140 - Salesfloor, SW Area, East Wall Grey Mastic
50 Black Wall Mastic
50-MG5-159 Unit 140 - Salesfloor, SW Area, East Wall
Black Mastic
None Detected
Yellow Mastic
50-MG5-160 Unit 140 - Salesfloor, SW Area, East Wall
Black Mastic
Yellow Mastic
50-MG5-161 Unit 140 - Salesfloor, SW Area, East Wall
Black Mastic
Yellow Mastic
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
51 Brown Drywall Mastic
51-MG5-162 Unit 132 - West Wall, South Area Brown Mastic
None Detected 51-MG5-163 Unit 132 - West Wall, South Area Brown Mastic
51-MG5-164 Unit 132 - West Wall, South Area Brown Mastic
52 Dark Tan FRP Mastic
52-MG5-165 Unit 138 - SE Restroom Tan Mastic
None Detected 52-MG5-166 Unit 138 - SE Restroom Tan Mastic
52-MG5-167 Unit 138 - SE Restroom Tan Mastic
53 Dark Tan FRP Mastic
53-MG5-168
Unit 134B - North Room, East Wall, South
Area Tan Mastic
None Detected 53-MG5-169 Unit 134B - North Room, North Wall, West
Area Tan Mastic
53-MG5-170 Unit 134B - North Room, East Wall, North Area Tan Mastic
1" x 1" Faux-Stone
Ceramic Table-Top Tile with Grout and Adhesive
54-MA5-171 Unit 132 - SE Area, Table-Top, West Side
Grey Ceramic Tile
None Detected
White Mortar
Grey Mortar
54-MA5-172 Unit 132 - SE Area, Table-Top, South End
Grey Ceramic Tile
White Mortar
Grey Mortar
54-MA5-173 Unit 132 - SE Area, Table-Top, East Side
Grey Ceramic Tile
Grey Mortar
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
55 Fiberglass Pipe Insulation
55-PI4-174 Unit 130A - South Area, near Water Heater
Yellow Insulation
None Detected
Silver/Beige Wrap
55-PI4-175 Unit 130A - South Area, near Water Heater
Yellow Insulation
Silver/Beige Wrap
55-PI4-176 Unit 130A - Restroom
Yellow Insulation
Silver/Beige Wrap
56 Fluted-Stone Siding Mortar
56-MA3-177 Unit 128 - East Exterior, Siding Light Brown Mortar
None Detected 56-MA3-178 Unit 140 - West Exterior, Siding Light Brown Mortar
56-MA3-179 Unit 134A - North Exterior, Column Grey Mortar
57 Concrete Block Mortar
57-MA2-180 Unit 134A - North Perimeter Wall, near Door Light Brown Mortar
None Detected 57-MA2-181 Unit 134B - North Perimeter Wall, near West
Door Light Brown Mortar
57-MA2-182 Unit 128 - North Perimeter Wall, near Door Light Brown Mortar
58 Concrete Block Mortar
58-MA2-183 Unit 140 - East Exterior Grey Mortar
None Detected 58-MA2-184 Unit 140 - SW Room, West Wall Light Brown Mortar
58-MA2-185 Unit 140 - Stockroom, East Wall Grey Mortar
Drywall with Joint
Compound
59-WB5-186 Unit 128 - North Exterior, Awning Soffit
White Drywall with Brown Paper
None Detected
White Joint Compound
59-WB5-187 Unit 134A - North Exterior, Awning Soffit
White Drywall with Brown Paper
White Joint Compound
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
Drywall with Joint
Compound 59-WB5-188 Unit 138 - North Exterior, Awning Soffit
White Drywall with Brown Paper
None Detected
White Joint Compound
Dark Brown Expansion
Joint
60-MS5-189 Unit 128 - NE Exterior Black Expansion Joint
None Detected 60-MS5-190 Unit 138 - North Exterior Black Expansion Joint
60-MS5-191 Unit 138 - North Exterior Black Expansion Joint
61 Black Expansion Joint
61-MS5-192 Unit 128 - East Exterior, at Loading Bay Door Black Expansion Joint Tar
None Detected 61-MS5-193 Unit 128 - East Exterior, at Loading Bay Door Black Expansion Joint Tar
61-MS5-194 Unit 128 - East Exterior, at Loading Bay Door Black Expansion Joint Tar
62 Stone Wall Finish
62-MA6-195 Unit 128 - East Exterior Light Brown Cementitious
Material
None Detected 62-MA6-196 Unit 140 - West Exterior Light Brown Cementitious
Material
62-MA6-197 Unit 140 - North Exterior Light Brown Cementitious
Material
63 Roofing Material
63-RF5-198
Roof - East Area, on East AHU, over Unit
Black Roofing Material 20% Chrysotile
63-RF5-199
Roof - East Area, on East AHU, over Unit
Black Roofing Material 15% Chrysotile
63-RF5-200
Roof - East Area, on East AHU, over Unit
Black Roofing Material 20% Chrysotile
64 Roofing Material 64-RF5-201 Roof - East Area, over Unit 128
White/Black Roofing Membrane
None Detected
Brown/Black Insulation
Yellow Insulation
Black/Silver Roofing Material
Black Roofing Material
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
64 Roofing Material
64-RF5-202 Roof - Central Area, over Unit 138
White/Black Roofing Membrane
None Detected
Brown/Black Insulation
Yellow Insulation
Black Roofing Material #1
Black Roofing Material #2
64-RF5-203 Roof - West Area, over Unit 140
White/Black Roofing Membrane
Yellow Insulation
Black Roofing Material #1
Black Roofing Material #2
Black Roofing Material #3
65 Flashing Sealant
65-RF1-204
Roof - NE Corner, Breezeway Wall, over
Unit 128
White Sealant None Detected
Black Tar 8% Chrysotile
65-RF1-205
Roof - East Perimeter Wall, South Area, over Unit 128
Grey Sealant None Detected
Black Tar 8% Chrysotile
65-RF1-206
Roof - Over Unit 140, South-Central Area, on Exhaust
White Sealant None Detected
Black Tar 7% Chrysotile
66 Tar Sealant
66-RF1-207
Roof - Over Unit 140, East-Central Area, on Pipe Black/White Tar 6% Chrysotile
66-RF1-208
Roof - SW-Central Area, on Pipe, over Unit
Black/White Tar 7% Chrysotile
66-RF1-209
Roof - Central Area, on Pipe, over Unit
Black/White Tar None Detected
Material Description
Sample
Number Sample Location Sample Layer Description Lab Results
67 Foamboard Paper
67-RF2-210 Roof - Along West Perimeter, over Unit 140 Grey Paper
None Detected 67-RF2-211 Roof - Along West Perimeter, over Unit 140 Grey Paper
67-RF2-212 Roof - Along West Perimeter, over Unit 140 Grey Paper
68 Asphaltic Shingle
68-RF3-213
Roof - Wall between Units 138 and 140, East
Side Brown/Black Roofing Shingle
None Detected 68-RF3-214 Roof - Wall between Units 138 and 140, East
Side Brown/Black Roofing Shingle
68-RF3-215
Roof - Wall between Units 138 and 140, East
Side Brown/Black Roofing Shingle
Asbestos-containing materials in BOLD.
Italics - Materials containing 1% or less asbestos
Appendix C
Asbestos Laboratory Analytical Results
Approved by:
Approved Signatory Frank Ehrenfeld
Report for:
Ryan Slanczka Terracon Consultants- Lenexa 15620 W. 113th St Lenexa, KS 66219
Regarding:
Eurofins Built Environment Testing East, LLC Project: 02237230.03.2 - 128-140 S Clairborne Rd
EML ID: 4128787
All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. The results relate only to the samples as received and tested. The results include an inherent uncertainty of measurement associated with estimating percentages by polarized light microscopy. Measurement uncertainty data for sample results with >1% asbestos concentration can be provided when requested.
Eurofins Built Environment Testing East, LLC ("the Company"), a member of the Eurofins Built Environment Testing group of companies, shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results. In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor.
Dates of Analysis:
Asbestos PLM (Layer %): 07-08-2025
Service SOPs: Asbestos PLM (Layer %) (EPA 40CFR App E to Sub E of Part 763 & EPA METHOD 600/R-93-116, SOP EB-AS-S- 1267) NVLAP Lab Code 101165-0
EMLab ID: 4128787, Page 1 of 39Eurofins Built Environment Testing East, LLC
Eurofins Built Environment Testing East, LLC 9000 Commerce Parkway, Suite B, Mount Laurel, NJ 08054
(856) 231-9449 www.eurofinsus.com/Built Client: Terracon Consultants- Lenexa C/O: Ryan Slanczka Re: 02237230.03.2 - 128-140 S Clairborne Rd
Date of Receipt: 06-30-2025 Date of Report: 07-08-2025
Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM) Appx E Sub E 40 CFR 763 / EPA 600/R-93/116
Sample ID # Lab-ID version Sample Description Asbestos
Constituents Non-Asbestos Constituents Comment
01-WB5-01. Drywall with Joint Compound; Unit 140 - Salesfloor, SW Area, East Wall 20617326-1
Layer 1 White Drywall with Brown Paper Homogeneity:Good
Not Detected 85% Non-Fibrous Material 15% Cellulose
A
Layer 2
Homogeneity:Good
Not Detected 100% Non-Fibrous Material A
Composite Asbestos ND A
01-WB5-02. Drywall with Joint Compound; Unit 140 - Stockroom, North Wall 20617327-1
Layer 1 White Drywall with Brown Paper Homogeneity:Good
Not Detected 85% Non-Fibrous Material
Homogeneity:Good
Not Detected 100% Non-Fibrous Material A
Composite Asbestos ND A
01-WB5-03. Drywall with Joint Compound; Unit 140 - Salesfloor, SW Area, West Wall 20617328-1
Layer 1 White Drywall with Brown Paper Homogeneity:Good
Not Detected 85% Non-Fibrous Material
B
Homogeneity:Good
2% Chrysotile 98% Non-Fibrous Material B
Layer 3
Homogeneity:Good
Not Detected 100% Cellulose B
Composite Asbestos < 1% B
01-WB5-04. Drywall with Joint Compound; Unit 138 - East Wall 20617329-1
Layer 1 White Drywall with Brown Paper Homogeneity:Good
Not Detected 85% Non-Fibrous Material
B
Comments: A)Composite content provided does not follow the guidelines set forth by NVLAP. This analysis was performed by following the NESHAP guidelines. B) Composite asbestos content provided is only for Drywall/Joint compound. Composite content provided does not follow the guidelines set forth by NVLAP.
This analysis was performed by following the NESHAP guidelines.
EMLab ID: 4128787, Page 2 of 39Eurofins Built Environment Testing East, LLC
The total percentage of sample components shown may be greater than 100% when some components are detected at <1%.
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers of that type were detected.
When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
(856) 231-9449 www.eurofinsus.com/Built Client: Terracon Consultants- Lenexa C/O: Ryan Slanczka Re: 02237230.03.2 - 128-140 S Clairborne Rd
Date of Receipt: 06-30-2025 Date of Report: 07-08-2025
Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM) Appx E Sub E 40 CFR 763 / EPA 600/R-93/116
Sample ID # Lab-ID version Sample Description Asbestos
Constituents Non-Asbestos Constituents Comment
01-WB5-04. Drywall with Joint Compound; Unit 138 - East Wall 20617329-1(cont.)
Layer 2 White Joint Compound
Not Detected 100% Non-Fibrous Material A
Homogeneity:Good
Not Detected 100% Cellulose A
Composite Asbestos ND A
01-WB5-05. Drywall with Joint Compound; Unit 132 - West Wall, Central…