26-8672_Supplemental_Info_-_Geotechnical_Report.pdf
PDF 2 MB Posted
- Attached to
- Collier Senior Center Expansion Project
- Solicitation number
- 26-8672
- Issued by
- Collier County, Florida
About this file
This is a Geotechnical Report prepared by UES (University Engineering Services) for Collier County's Hardening & Senior Center expansion project located at 4741 Golden Gate Parkway in Naples, Florida. The report documents subsurface exploration and engineering evaluation conducted in June 2024 to assess soil conditions and provide foundation design recommendations for a proposed one-story building expansion. Four Standard Penetration Test (SPT) borings were advanced to approximately 25 feet below ground surface to characterize soil properties and evaluate their impact on proposed construction. The investigation determined that subsurface conditions generally consist of very loose to medium dense sands, very soft to soft silts with weathered limestone fragments, and soft to hard limestone layers encountered at variable depths between 2 and 13 feet below ground surface. Groundwater was encountered at approximately 4 feet 1 inch below existing ground surface and will fluctuate seasonally. The project assumes maximum loading conditions of 100 kips for individual column footings and 7 kips per linear foot for continuous wall footings, with nominal fill placement of 1-2 feet required to reach finished grades.
Based on the geotechnical investigation, UES recommends that foundations be designed using an allowable net soil contact pressure of 2,500 pounds per square foot (psf) with shallow foundations embedded a minimum of 18 inches below final grade. Recommended site preparation includes proof rolling of surficial sands to 95 percent Modified Proctor compaction density, placement of structural fill in 12-inch lifts compacted to 95 percent Modified Proctor, and probing of limestone surfaces for voids prior to footing placement. Expected total settlement is less than 1 inch with differential settlement less than 0.5 inch between adjacent columns or within 20 feet horizontal distance. Excavation into the hard limestone and rock layers encountered across the site will likely present difficulty, particularly in confined spaces such as utility trenches, and may require pneumatic chisels or dynamic removal methods. UES recommends retention of the firm for construction phase inspection and monitoring services to verify adequacy of earthwork operations and confirm proper implementation of geotechnical design recommendations throughout the project.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Florida’s Leading Engineering Source
Report of Geotechnical Exploration
Proposed Collier County Hardening & Senior Center
4741 Golden Gate Parkway
Naples, Collier County, Florida
June 25, 2024 UES Project No.: 0530.2400086.0000
Prepared For:
Harvard Jolly, Inc.
1639 Hendry Street
Fort Myers, FL 33901 Attention: Mr. Thomas A. Mayo
Phone: (239) 275-7774
Prepared By:
UES
201 Waldo Avenue North Lehigh Acres, Florida 33971
Phone: (239) 489-2443 www.teamues.com http://www.teamues.com/
201 Waldo Avenue North • Lehigh Acres, Florida 33971 • (239) 489-2443 • (239) 489-3438 (fax) www.teamUES.com
OFFICES THROUGHOUT FLORIDA
June 25, 2024
Mr. Thomas A. Mayo Harvard Jolly, Inc.
1639 Hendry Street Fort Myers, FL 33901 Phone: (239) 275-7774 Email: t.mayo@harvardjolly.com
Site: Proposed Collier County Hardening & Senior Center
4741 Golden Gate Parkway Naples, Collier County, Florida UES Project No. 0530.2400086.0000
Dear Mr. Mayo:
UES has completed the subsurface exploration and geotechnical engineering evaluation for the above-referenced project in accordance with the geotechnical and engineering service agreement for this project. The scope of services was completed in accordance with UES’s Geotechnical Engineering Proposal (0530.0623.00020) planned in conjunction with and authorized by you.
EXECUTIVE SUMMARY
The purpose of this subsurface exploration was to classify the nature of the subsurface soils and general geomorphic conditions and evaluate their impact upon the proposed construction. This report contains the results of the subsurface exploration at the site and UES’s engineering interpretations of these, with respect to the project characteristics described to UES including providing recommendations for site preparation and the design of the foundation system.
UES understands that the project will consist of the construction of a Collier County Hardening & Senior Center building located at 4741 Golden Gate Parkway in Naples, Collier County, Florida.
UES understands that the proposed structure will be a stand alone one-story building expansion to the existing building. UES was provided with a site plan prepared by Harvard Jolly PBK dated March 28th, 2024, depicting the proposed building construction. Specific loading conditions were not available at the time of this report, but for the purposes of evaluating the bearing capacity and settlement values, UES has assumed that the maximum loading conditions will be on the order of 100 kips for individual column footings and 7 kips per lineal foot (klf) for continuous wall footings. UES has assumed a nominal amount (1-2 feet) of fill will be required to raise the site from current elevations to finished elevations. The recommendations provided herein are based upon the above considerations. If the project description has been revised, please inform UES so that UES may review the recommendations with respect to any modifications. No site or project facilities/improvements, other than those described herein, should be designed using the soil information presented in this report. Moreover, UES will not be responsible for the performance of any site improvements so designed and constructed.
A total of four (4) Standard Penetration Test (SPT) borings advanced to depths of approximately 25 feet below ground surface (BGS) were completed for this study.
mailto:t.mayo@harvardjolly.com
Proposed Collier County Hardening & Senior Center - 4741 Golden Gate Parkway Geotechnical Report Naples, Collier County, Florida June 25, 2024 UES Project No. 0530.2400086.0000 Page 2 of 10
This document has been digitally signed and sealed by Carlos Mercado on the date adjacent to the seal.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
The subsurface soil conditions encountered at this site generally consist of very loose to medium dense sands (SP) with (if any) some limestone fragments and a trace of shell fragments, very soft to soft silts (ML) with (if any) varying amounts of weathered limestone fragments, soft weathered limestone (WLS) and hard limestone (LS) to the boring termination depths. Please refer to
“Appendix D: Record of Test Borings” for a detailed account of each boring.
Soft weathered to hard limestone was encountered across the site at variable depths, thickness, and hardness. Hard rock (which may contain boulders or lenses of hard rock) was encountered at all of our test boring locations approximately from 2 feet to 13 feet below the ground surface.
Difficulty will likely be encountered excavating into or these layers particularly in a confined space such as utility trenches.
Based on the four soil borings and knowledge of the project at the time of this report, the subsurface soil conditions at the project site are generally favorable for the support of the proposed structures on shallow foundations with maximum loading conditions on the order of 100 kips for individual column footings 7 kips per linear foot (klf) for continuous wall footings. A maximum allowable bearing pressure of 2,500 psf may be used for foundation design. Based on the projected loads, expected settlement of the structure is less than 1 inch total and less than ½ inch differential between adjacent columns or a horizontal distance of 20 feet.
UES appreciates the opportunity to be of service to you on this project and looks forward to a continued association. Please do not hesitate to contact UES if you have any questions or comments, or if UES may further assist you as your plans proceed.
Respectfully Submitted, UES
Registry Number 4930
Vineetha Garikapati, M.S., E.I Geotechnical Project Engineer
Carlos A. Mercado, P.E. No. 71707 State of Florida Principal Engineer
UES Project No. 0530.2400086.0000 Page 3 of 10
TABLE OF CONTENTS
1.0 INTRODUCTION
1.1 Scope of Services
1.2 Project Description
2.0 OBSERVATIONS
2.1 Site Inspection
2.2 Field Exploration
2.3 Visual Classification
2.4 Geomorphic Conditions
2.5 Hydrogeological Conditions
3.0 ENGINEERING EVALUATION AND RECOMMENDATIONS
3.1 General
3.2 Site Preparation
3.3 Design of Footings
3.4 Ground Floor Slabs
4.0 EXCAVATION CONSIDERATIONS
5.0 CONSTRUCTION RELATED SERVICES
6.0 REPORT LIMITATIONS
7.0 BASIS FOR RECOMMENDATIONS
Appendix A - Vicinity Map Appendix B - Test Location Plan Appendix C - Notes Related to Borings Appendix D - Record of Test Borings Appendix E - Discussion of Soil Groups
UES Project No. 0530.2400086.0000 Page 4 of 10
1.0 INTRODUCTION
1.1 Scope of Services
The objective of the geotechnical services was to collect subsurface data for the subject project, summarize the test results, and discuss any apparent site conditions that may have geotechnical significance for the proposed structure construction. The scope of the services was limited to the following:
1. Conduct four Standard Penetration Test (SPT) borings to determine the nature and condition of the subsurface soils and prepare record logs of these soil borings depicting the subsurface soil conditions encountered during the field exploration.
2. Review each soil sample obtained during the field exploration for classification and additional testing, if necessary.
3. Evaluate the existing soil conditions found during the exploration with respect to foundation support for the proposed structure.
4. Prepare this report to document the results of the field exploration, engineering analysis, and foundation design recommendations.
1.2 Project Description
UES understands that the project will consist of the construction of a Collier County Hardening & Senior Center building located at 4741 Golden Gate Parkway in Naples, Collier County, Florida.
UES understands that the proposed structure will be a stand alone one-story building expansion to the existing building. UES was provided with a site plan prepared by Harvard Jolly PBK dated March 28th, 2024, depicting the proposed building construction. Specific loading conditions were not available at the time of this report, but for the purposes of evaluating the bearing capacity and settlement values, UES has assumed that the maximum loading conditions will be on the order of 100 kips for individual column footings and 7 kips per lineal foot (klf) for continuous wall footings. UES has assumed a nominal amount (1-2 feet) of fill will be required to raise the site from current elevations to finished elevations. The recommendations provided herein are based upon the above considerations. If the project description has been revised, please inform UES so that UES may review the recommendations with respect to any modifications. No site or project facilities/improvements, other than those described herein, should be designed using the soil information presented in this report. Moreover, UES will not be responsible for the performance of any site improvements so designed and constructed.
2.0 OBSERVATIONS
2.1 Site Inspection
The recovered samples were not evaluated, either visually or analytically, for chemical composition or environmental hazards. UES would be pleased to perform these services for an additional fee, if required.
UES Project No. 0530.2400086.0000 Page 5 of 10
2.2 Field Exploration
This field exploration consisted of four Standard Penetration Test (SPT) borings advanced to depths of approximately 25 feet below the existing ground surface (BGS). The locations of the borings performed are illustrated in “Appendix B: Test Location Plan". The Standard Penetration Test (SPT) boring method was used as the investigative tool within the borings. SPT tests were performed in substantial accordance with ASTM Procedure D-1586, “Penetration Test and Split- Barrel Sampling of Soils”. This test procedure consists of driving a 1.4-inch I.D. split-tube sampler into the soil profile using a 140-pound hammer falling 30 inches. The number of blows per foot for the second and third 6-inch increments is an indication of soil strength.
The soil samples recovered from the soil borings were visually classified and their stratification is illustrated in “Appendix D: Record of Test Borings". It should be noted that soil conditions might vary between the strata interfaces shown on the logs. The soil boring data reflects information from a specific test location only. The boring depths were selected based on UES’s knowledge of vicinity soils and to include the zone of soil likely to be stressed by the proposed construction.
UES located the test borings by using the provided site plan, measuring from existing on-site landmarks shown on an aerial photograph, and by using handheld GPS devices. Horizontal and vertical survey control was not provided for the boring locations. The indicated test locations on the boring location plan should be considered approximate and accurate to the degree implied by the methodologies used to locate the test locations in the field. GPS coordinates can be provided upon request.
2.3 Visual Classification
Soil samples recovered from the field exploration were returned to UES’s laboratory where they were visually classified in general accordance with ASTM D-2488. Samples were evaluated to obtain an accurate understanding of the soil properties and site geomorphic conditions. After performing a review of the recovered site soils no laboratory testing was deemed necessary. Bag samples of the soil encountered during the field exploration will be held in UES’s laboratory for your inspection for 45 days and then discarded unless UES is notified otherwise in writing.
2.4 Geomorphic Conditions
Boring logs derived from the field exploration are presented in “Appendix D: Record of Test Borings.” The boring logs depict the observed soils in graphic detail. The Standard Penetration Test borings indicate the penetration resistance, or N-values, logged during the drilling and sampling activities. The classifications and descriptions shown on the logs are generally based upon visual characterizations of the recovered soil samples.
All soil samples reviewed have been depicted and classified in general accordance with the Unified Soil Classification System, modified as necessary to describe typical southwest Florida conditions. See “Appendix E: Discussion of Soil Groups", for a detailed description of various soil groups.
UES Project No. 0530.2400086.0000 Page 6 of 10
The subsurface soil conditions encountered at this site generally consist of very loose to medium dense sands (SP) with (if any) some limestone fragments and a trace of shell fragments, very soft to soft silts (ML) with (if any) varying amounts of weathered limestone fragments, soft weathered limestone (WLS) and hard limestone (LS) to the boring termination depths. Please refer to
“Appendix D: Record of Test Borings” for a detailed account of each boring.
2.5 Hydrogeological Conditions
On the dates of the initial field exploration, the groundwater table was encountered at depths of approximately 4 feet 1 inch below the existing ground surface. The groundwater table will fluctuate seasonally depending upon local rainfall and other site specific and/or local influences such as tidal events. Brief ponding of stormwater may occur across the site after heavy rains.
Horizontal and vertical survey control was not provided for the boring locations. Ground surface elevations at the boring locations would be beneficial to help UES identify any anomalies in our measured and estimated seasonal high groundwater levels, as well as improve the usefulness of the groundwater information during the civil engineering design of the site. UES will not be responsible for the performance of any site improvements designed and constructed based on the reported soil and groundwater depths without horizontal and vertical survey control.
Based on the rock layer encountered in all of the test boring locations performed at the subject site, there is potential for perched water tables to exist, the design team should take this into consideration when designing site drainage systems and others systems they may be affected by perched water tables.
No additional investigation was included in the scope of work in relation to the wet seasonal high groundwater table or any existing well fields in the vicinity. Well fields may influence water table levels and cause significant fluctuations. If a more comprehensive water table analysis is necessary, please contact UES for additional guidance.
3.0 ENGINEERING EVALUATION AND RECOMMENDATIONS
3.1 General
A foundation system for any structure must be designed to resist bearing capacity failures, have settlements that are tolerable, and resist the environmental forces that the foundation may be subjected to over the life of the structure. The soil bearing capacity is the soil’s ability to support loads without plunging into the soil profile. Bearing capacity failures are analogous to shear failures in structural design and are usually sudden and catastrophic.
The amount of settlement that a structure may tolerate is dependent on several factors including uniformity of settlement, time rate of settlement, structural dimensions and properties of the materials. Generally, total or uniform settlement does not damage a structure but may affect drainage and utility connections. These can generally tolerate movements of several inches for building construction. In contrast, differential settlement affects a structure’s frame and is limited by the structural flexibility.
UES Project No. 0530.2400086.0000 Page 7 of 10
Compaction of the surface soils is recommended to increase the soil bearing capacity and minimize foundation settlement. The following are the recommendations for overall site preparation and foundation design that UES feel best suited for the proposed construction and existing soil conditions.
UES notes that the applicability of geotechnical recommendations is very dependent upon project characteristics, specifically (1) improvement locations, (2) grade alterations, (3) and actual applied structural loads. For that reason, UES must be provided with the preliminary and final site and grading plans, as well as structural design loads, to validate all recommendations provided in this report. Without performing this review, UES’s recommendations should not be relied upon for final design or construction of any site improvements.
3.2 Site Preparation
UES recommends the following compaction requirements for this project:
➢ Proof Roll ..................................................................... 95% of a Modified Proctor
➢ Building Pad Fill ............................................................ 95% of a Modified Proctor
➢ Footings ....................................................................... 95% of a Modified Proctor
The compaction percentages presented above are based upon the maximum dry density as determined by a “modified proctor” test (ASTM D-1557). All density tests should be performed to a depth of 12 inches below the tested surface unless noted otherwise. All density tests should be performed using the nuclear method (ASTM D-6938) or the sand cone method (ASTM D-1556).
The recommendations for the preparation of the site for the use of shallow foundation systems are presented below. This approach to improving and maintaining the site soils has been found to be successful on projects with similar soil conditions.
1. Initial site preparation should consist of clearing, stripping, and de-grubbing of trees, and vegetation and associated root systems to a depth of their vertical reach. This should be done within and to 5 feet outside the perimeter of the proposed building footprint (including exterior isolated columns).
2. Following site stripping and prior the placement of any fill, areas of surficial sand (not exposed limestone) should be compacted (“proof rolled”) and tested. UES recommends using a steel drum vibratory roller with sufficient static weight and vibratory impact energy to achieve the required compaction. Density tests should be performed on the proof rolled surface at a frequency of not less than one test per 2,500 square feet, or a minimum of four (4) tests, whichever is greater. Areas of exposed intact limestone shall be visually confirmed by the project geotechnical engineer prior to fill placement, in lieu of proof rolling.
UES Project No. 0530.2400086.0000 Page 8 of 10
3. Fill material may then be placed in the building pad as required. The fill material should be inorganic (classified as SP, SW, GP, GW, SP-SM, SW-SM, GW-GM, GP-GM) containing not more than 5 percent (by weight) organic materials. Fill materials with silt-size soil fines in excess of 12% should not be used. Fill should be placed in lifts with a maximum lift thickness not exceeding 12 inches. Each lift should be compacted and tested prior to the placement of the next lift. Density tests should be performed within the fill at a frequency of not less than one test per 2,500 square feet per lift in the building areas, or a minimum of four
(4) tests per lift, whichever is greater.
4. For any footings bearing on a limestone formation, the bottom of all footing excavation shall be examined by the engineer / geologist or his representative to determine the condition of the limestone. The limestone shall be probed for voids and loose pockets of sand. Such areas shall be cleaned to depth of 3 times the greatest horizontal dimension and backfilled with lean concrete.
5. For footings placed on structural fill or compacted native granular soils, the bottom of all footings shall be tested for compaction and examined by the engineer / geologist or his representative to determine if the soil is free of organic and/or deleterious material. Density tests should be performed at a frequency of not less than one (1) density test per each isolated column footing and one (1) test per each fifty (50) lineal feet of wall footings.
6. The contractor should take into account the final contours and grades as established by the plan when executing his backfilling and compaction operations.
Using vibratory compaction equipment at this site may disturb adjacent structures. UES recommends that you monitor nearby structures before and during proof-compaction operations.
A representative of UES can monitor the vibration disturbance of adjacent structures. A proposal for vibration monitoring during compaction operations can be supplied upon request.
3.3 Design of Footings
Foundation soils prepared in accordance with the above recommendations should be suitable for supporting the proposed structure on an economical and conventionally designed shallow foundation system. The foundations should be designed for an allowable net soil contact pressure of 2,500 pounds per square foot (psf) or less.
Shallow foundations should be embedded a minimum of 18 inches below final grade. This embedment shall be measured from the lowest adjacent grade. Isolated column footings should be at least 24 inches in width and continuous strip footings should have a width of at least 18 inches regardless of contact pressure.
Based on the boring information and the maximum loading conditions (100 kips for individual column footings and 7 kips per linear foot (klf) for continuous wall footings), expected settlement of the structure is less than 1 inch total and less than ½ inch differential between adjacent columns or a horizontal distance of 20 feet. Because foundation soils are mostly coarse-grained, the majority of settlement will occur during construction as the load is being applied. All footings and columns should be structurally separated from the floor slab, as they will be loaded differently and at different times, unless a monolithic mat foundation is designed.
UES Project No. 0530.2400086.0000 Page 9 of 10
3.4 Ground Floor Slabs
The ground floor slabs may be supported directly on the existing grade or on granular fill following the foundation site preparation and fill placement procedures outlined in this report. For purposes of design, a coefficient of subgrade modulus 150 pounds per cubic inch may be used. The ground floor slab should be structurally separated from all walls and columns to allow for differential vertical movement.
Excessive moisture vapor transmission through floor slabs-on-grade can result in damage to floor coverings as well as other deleterious effects. An appropriate moisture vapor retarder should be placed beneath the floor slab to reduce moisture vapor from entering the building through the slab. The retarder should be installed in general accordance with applicable ASTM procedures including sealing around pipe penetrations and at the edges of foundations.
4.0 EXCAVATION CONSIDERATIONS
Soft weathered to hard limestone was encountered across the site at variable depths, thickness, and hardness. Hard rock (which may contain boulders or lenses of hard rock) was encountered at all of our test boring locations approximately from 2 feet to 13 feet below the ground surface.
Difficulty will likely be encountered excavating into or these layers particularly in a confined space such as utility trenches.
In similar occurrences, soft limestone has been removed using large excavators. However, the hard limestone, cobbles and boulders will likely require the use of pneumatic chisels or other dynamic methods to remove and should be expected along some sections of utility excavations and the excavations of the pump station and retention ponds.
UES recommends that the contract documents stipulate that the site contractor is solely responsible for selecting their equipment appropriately for these anticipated site conditions without recourse for a change order after the project has been awarded.
5.0 CONSTRUCTION RELATED SERVICES
UES recommends the owner retain UES to provide inspection services during the site preparation procedures for confirmation of the adequacy of the earthwork operations. Field tests and observations include verification of foundation and/or pavement subgrades by monitoring earthwork operations and performing quality assurance tests of the placement of compacted structural fill courses.
The geotechnical engineering design does not end with the advertisement of the construction documents. The design is an ongoing process throughout construction. Because of UES’s familiarity with the site conditions and the intent of the engineering design, UES is most qualified to address site problems or construction changes which may arise during construction in a timely and cost-effective manner.
UES Project No. 0530.2400086.0000 Page 10 of 10
The monitoring and inspection of construction procedures and the supervision of the implementation of the recommendations given herein shall be made by UES. Otherwise, the retained firm shall study this report, perform additional tests as they deem necessary, and submit their own recommendations or assume full responsibility for the outlined recommendations in their entirety.
6.0 REPORT LIMITATIONS
This consulting report has been prepared for the exclusive use of the current project owners and other members of the design team for the proposed Collier County Hardening & Senior Center in Naples, Collier County, Florida. This report has been prepared in accordance with generally accepted local geotechnical engineering practices; no other warranty is expressed or implied.
The evaluation submitted in this report is based in part upon the data collected during a field exploration. However, the nature and extent of variations throughout the subsurface profile may not become evident until the time of construction. If variations then appear evident, it may be necessary to reevaluate information and professional opinions as provided in this report. In the event changes are made in the nature, design, or locations of the proposed structure, the evaluation and opinions contained in this report shall not be considered valid unless the changes are reviewed, and conclusions modified or verified in writing by UES. UES is not responsible for damage caused by soil improvement and/or construction activity vibrations related to this project.
UES is also not responsible for damage concerning drainage or moisture related issues for the proposed or nearby structures.
UES should be provided the opportunity to review the final foundation design drawings and specifications to determine whether UES’s recommendations have been properly interpreted, communicated and implemented. If UES is not afforded the opportunity to participate in construction related aspects of foundation installation as recommended in this report or any report addendum, UES will accept no responsibility for the interpretation of UES’s recommendations made in this report or on a report addendum for foundation performance.
7.0 BASIS FOR RECOMMENDATIONS
The analysis and recommendations submitted in this report are based on the data obtained from the tests performed at the locations indicated on the attached figure in Appendix B. This report does not reflect any variations, which may occur between borings. While the borings are representative of the subsurface conditions at their respective locations and for their vertical reaches, local variations characteristic of the subsurface soils of the region are anticipated and may be encountered. The delineation between soil types shown on the soil logs is approximate and the description represents UES’s interpretation of the subsurface conditions at the designated boring locations on the particular date drilled.
Any third-party reliance on UES’s geotechnical report or parts thereof is strictly prohibited without the expressed written consent of UES. The methodology (ASTM D-1586) used in performing the borings and for determining penetration resistance is specific to the sampling tools utilized and does not reflect the ease or difficulty of advancing other tools or materials.
Appendix A - Vicinity Map
VICINITY MAP
SOURCE: GOOGLE EARTH PRO©
Drawn By:
JR
Checked By: Date:
AJD
Project No.: Approved By:
Adam Dornacker, P.E.
06/19/2024
Collier County Hardening & Senior Center
4741 Golden Gate Parkway, Naples, Collier County, FL
0530.2400086.0000
Project Site
© 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping
MiamiMiamiMiamiMiamiMiamiMiamiMiamiMiamiMiami
TallahasseeTallahasseeTallahasseeTallahasseeTallahasseeTallahasseeTallahasseeTallahasseeTallahassee
TampaTampaTampaTampaTampaTampaTampaTampaTampa
Jack sonvilleJack sonvilleJack sonvilleJack sonvilleJack sonvilleJack sonvilleJack sonvilleJack sonvilleJack sonville
FLOR IDA
© 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping
Site Location Naples, FL
Appendix B - Test Location Plan
TEST LOCATION PLAN
Boring and test locations are an approximation.
Drawn By: JR Checked By: Date:
AJD
Project No.: Approved By:
Adam Dornacker, P.E.
Collier County Hardening & Senior Center
4741 Golden Gate Parkway, Naples, Collier County, FL
06/19/2024
0530.2400086.0000
© 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping
MiamiMiamiMiamiMiamiMiamiMiamiMiamiMiamiMiami
TallahasseeTallahasseeTallahasseeTallahasseeTallahasseeTallahasseeTallahasseeTallahasseeTallahassee
TampaTampaTampaTampaTampaTampaTampaTampaTampa
Jack sonvilleJack sonvilleJack sonvilleJack sonvilleJack sonvilleJack sonvilleJack sonvilleJack sonvilleJack sonville
FLOR IDA
© 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping
TEST LOCATION PLAN
Boring and test locations are an approximation.
Drawn By: JR Checked By: Date:
AJD
Project No.: Approved By:
Adam Dornacker, P.E.
Collier County Hardening & Senior Center
4741 Golden Gate Parkway, Naples, Collier County, FL
06/19/2024
0530.2400086.0000
© 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping
MiamiMiamiMiamiMiamiMiamiMiamiMiamiMiamiMiami
TallahasseeTallahasseeTallahasseeTallahasseeTallahasseeTallahasseeTallahasseeTallahasseeTallahassee
TampaTampaTampaTampaTampaTampaTampaTampaTampa
Jack sonvilleJack sonvilleJack sonvilleJack sonvilleJack sonvilleJack sonvilleJack sonvilleJack sonvilleJack sonville
FLOR IDA
© 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping © 1993 DeL orme Mapping
Appendix C - Notes Related to Borings
NOTES RELATED TO
RECORDS OF TEST BORING AND
GENERALIZED SUBSURFACE PROFILE
1. Groundwater level was encountered and recorded (if shown) following the completion of the soil test boring on the date indicated. Fluctuations in groundwater levels are common; consult report text for a discussion.
2. The boring location was identified and located in the field based on measured and estimated distances from existing site features.
3. The borehole was backfilled to site grade following boring completion, patched with asphalt cold patch mix when pavement was encountered.
4. The Record of Test Boring represents our interpretation of field conditions based on engineering examination of the soil samples.
5. The Record of Test Boring is subject to the limitations, conclusions, and recommendations presented in the report text.
6. The Standard Penetration Test (SPT) was performed in accordance ASTM Procedure D-1586. SPT testing procedure consists of driving a 1.4-inch I.D. split-tube sampler into the soil profile using a 140-pound hammer falling 30 inches.
7. On the Record of Test Boring listed as “Blow Counts”, the N-value is the sum of the SPT hammer blows required to drive the split-tube sampler through the second and third 6-inch increment of the sampling layer, and is an indication of soil strength.
8. Shown on the Record of Test Boring an SPT N-value expressed as 50/2” is descriptive of the fact that 50 hammer blows were required to drive the split-spoon sampler a distance of approximately 2 inches.
9. The soil/rock strata interfaces shown on the Records of Test Boring are approximate and may vary from those in the field. The soil/rock conditions shown on the Records of Test Boring refer to conditions at the specific location tested; soil/rock conditions may vary between test locations.
10.Relative density and consistency for sands/gravels, silts/clays, and limestone are described as follows:
Cohesionless Soils Silts and Clays Limestone
Safety SPT (N-Value)
Auto SPT (N-Value)
Relative Density
Safety SPT (N-Value)
Auto SPT (N-Value)
Consistency SPT (N-Value) Relative Density
0 – 4 0 – 3 Very Loose 0 – 2 0 – 1 Very Soft 0 – 50 Soft 5 – 10 4 – 8 Loose 3 – 5 2 – 4 Soft 51 – 50 for 0” Hard 11 – 30 9 – 24 Medium Dense 6 – 7 5 – 6 Firm 31 – 50 25 – 40 Dense 8 – 15 7 – 12 Stiff Over 50 Over 40 Very Dense 16 – 30 13 – 24 Very Stiff
Over 30 Over 24 Hard
11. Definition of descriptive terms of modifiers for silts/clays/shells/gravels are described as follows:
Percentage of Modifier Material First Qualifier Second Qualifier
0 – 5 (No mention) (No mention) 5 – 12 Slightly + Modifier + y With Trace
12 – 30 Modifier + y With Some 30 – 50 Very + Modifier + y And
12. Descriptive characteristics for organic content percentages are described as follows:
Percentage of Organic Material Descriptor
0 – 2.5 (No mention)
2.5 – 5 With a Trace of Organics 5 – 20 Organic
20 – 75 Highly Organic 75 – 100 Peat
Appendix D - Record of Test Borings
SOIL PROFILES SOIL PROFILE LEGEND SOIL LEGEND
B-X = BORING NUMBER
SOIL TYPE X
N = SPT TEST
VALUE
GROUND WATER
INDICATES PRACTICAL
REFUSAL TO BORING
EQUIPMENT
= INDICATES GRADUAL TRANSITION
IN SOIL TYPES
NOTES:
LEVEL
S O
IL
S
Y M
B O
L
N - STANDARD PENETRATION RESISTANCE TEST
(SPT) VALUE. NUMBERS TO THE RIGHT OF
BORINGS INDICATE SPT VALUE FOR 12-INCHES
OF PENETRATION (UNLESS OTHERWISE NOTED).
WOH - BORING INTERVAL ADVANCED UNDER
WEIGHT OF HAMMER.
WOR - BORING INTERVAL ADVANCED UNDER
WEIGHT OF ROD.
LFC - LOSS OF DRILLING FLUID CIRCULATION.
WLS - WEATHERED LIMESTONE
RECORD OF TEST BORINGS
D E
P T
H I
N F
E E
T
Client: Harvard Jolly, Inc.
Project:
Collier County Hardening & Senior Center 4741 Golden Gate Parkway, Naples, Collier County, Florida
Date: 06/18/2024 Project No: 0530.2400086.0000
B-02B- 01
N-AUTO
B-04
Approved By: AJD
Drawn By: JR
Drilled By: LS
RIG: CME 45
SOIL CLASSIFICATION
CORRELATION OF N - VALUES WITH RELATIVE
DENSITY AND CONSISTENCY
CORRELATION OF N - VALUES WITH
HARDNESS DESCRIPTION
COHESIONLESS SOIL SILTS AND CLAYS LIMEROCK
N - VALUE
(AUTO)
N - VALUE
(AUTO)
N - VALUE
RELATIVE DENSITY
CONSISTENCY RELATIVE DENSITY
0 - 3 0 - 1 0 - 50VERY LOOSE VERY SOFT SOFT
4 - 8 2 - 4LOOSE SOFT
9 - 24 5 - 6
51 - 50 FOR 0"
MEDIUM DENSE FIRM
HARD
25 - 40 7 - 12DENSE STIFF
OVER 40 13 - 24VERY DENSE
6 - 7
VERY STIFF
OVER 24
8 - 15
HARD
16 - 30
APPROXIMATE
FINES
CONTENT
MODIFIERS
5% TO 12%
12% TO 25%
26% TO 49%
SLIGHTLY SILTY OR SLIGHTLY CLAYEY
SILTY OR CLAYEY
VERY SILTY OR VERY CLAYEY
APPROXIMATE
SHELL
CONTENT
MODIFIERS
0% TO 5%
5% TO 12%
NO MENTION
SLIGHTLY SHELLY
APPROXIMATE
ORGANIC CONTENT MODIFIERS
2.5% TO 5%
5% TO 20%
20% TO 75%
WITH A TRACE
WITH ORGANICS
HIGHLY ORGANIC
75% TO 100% PEAT
13% TO 30%
31% TO 50%
SHELLY
VERY SHELLY
DEFINITION OF DESCRIPTIVE TERMS OF MODIFIERS FOR SILTS/CLAYS/SHELLS/GRAVELS ARE DESCRIBED AS FOLLOWS:
PERCENTAGE OF MODIFIER MATERIAL
5 - 12 12 - 30 30 - 50
FIRST QUALIFIER
SLIGHTLY + MODIFIER + Y
MODIFIER + Y
VERY + MODIFIER + Y
SECOND QUALIFIER
WITH A LITTLE
WITH SOME
AND
N - VALUE
(SAFETY)
0 - 4 5 - 10 11 - 30 31 - 50
OVER 50
N - VALUE
(SAFETY)
0 - 2 3 - 5
OVER 30
0% TO 2.5% NO MENTION
With
WLS
Slightly Shelly
With WLS
1 1
UES
201 Waldo Ave. N.
Lehigh Acres, Florida 33971 239-489-2443 www.teamues.com
B-03
With Some
WLS
With Some Limestone Fragments
Some WLS
Brown, Tan, SAND (SP)
Very Loose to Medium Dense
Light Gray, SILT (ML)
Very Soft to Soft
Gray, WEATHERED LIMESTONE (WLS)
Soft3
Brown, LIMESTONE (LS)
Hard
06/10/2024 06/12/2024 06/10/2024 06/10/2024
N-AUTO N-AUTO N-AUTO
50/1"
50/2"
50/2"
50/4"
50/5"
WOH
WOH
5 NO RECOVERY4
With WLS
With Some
WLS
50/2" 50/4" 50/5"
50/2" 50/4" 50/5"
50/4" 50/5"
Appendix E - Discussion of Soil Groups
DISCUSSION OF SOIL GROUPS
COARSE GRAINED SOILS
GW and SW GROUPS. These groups comprise well-graded gravelly and sandy soils having little or no plastic fines (less than 5 percent passing the No. 200 sieve). The presence of the fines must not noticeably change the strength characteristics of the coarse-grained fraction and must not interface with it's free-draining characteristics.
GP and SP GROUPS. Poorly graded gravels and sands containing little of no plastic fines (less than 5 percent passing the No. 200 sieve) are classed in GP and SP groups.
The materials may be called uniform gravels, uniform sands or non-uniform mixtures of very coarse material and very fine sands, with intermediate sizes lacking (sometimes called skip-graded, gap-graded or step-graded). This last group often results from borrow pit excavation in which gravel and sand layers are mixed.
GM and SM GROUPS. In general, the GM and SM groups comprise gravels or sands with fines (more than 12 percent passing the No. 200 sieve) having low or no plasticity.
The plasticity index and liquid limit of soils in the group should plot below the "A" line on the plasticity chart. The gradation of the material is not considered significant and both well and poorly graded materials are included.
GC and SC GROUPS. In general, the GC and SC groups comprise gravelly or sandy soils with fines (more than 12 percent passing the No. 200 sieve), which have a fairly high plasticity. The liquid limit and plasticity index should plot above the "A” line on the plasticity chart.
FINE GRAINED SOILS
ML and MH GROUPS. In these groups, the symbol M has been used to designate predominantly silty material. The symbols L and H represent low and high liquid limits, respectively, and an arbitrary dividing line between the two is set at a liquid limit of 50.
The soils in the ML and MH groups are sandy silts, clayey silts or inorganic silts with relatively low plasticity. Also included are loess type soils and rock flours.
CL and CH GROUPS. In these groups the symbol C stands for clay, with L and H denoting low or high liquid limits, with the dividing line again set at a liquid limit of 50.
The soils are primarily inorganic clays. Low plasticity clays are classified as CL and are usually lean clays, sandy clays or silty clays. The medium and high plasticity clays are classified as CH. These include the fat clays, gumbo clays and some volcanic clays.
OL and OH GROUPS. The soil in the OL and OH groups are characterized by the presence of organic odor or color, hence the symbol O. Organic silts and clays are classified in these groups. The materials have a plasticity range that corresponds with the ML and MH groups.
HIGHLY ORGANIC SOILS
The highly organic soils are usually very soft and compressible and have undesirable construction characteristics. Particles of leaves, grasses, branches, or other fibrous vegetable matter are common components of these soils. They are not subdivided and are classified into one group with the symbol PT. Peat humus and swamp soils with a highly organic texture are typical soils of the group.