26-8672_Exhibit_-_Lenel_Card_Access_Requirements.pdf

PDF 1 MB Posted

Attached to
Collier Senior Center Expansion Project
Solicitation number
26-8672
Issued by
Collier County, Florida

About this file

This document is a technical specification exhibit for card access requirements and guidelines issued by Collier County for the Collier Senior Center Expansion Project (IFB 26-8672). The exhibit establishes mandatory equipment specifications for Lenel-based access control systems, including controllers, card reader interface panels, HID card readers, door contacts, electrified locks, and request-for-exit mechanisms. All installations must utilize Lenel LNL-M4420 controllers (supporting up to two doors each), Lenel LNL-1320-S3 dual card reader interface panels for installations exceeding two doors, HID readers (standard models 40TKS-00-0000 or 40KTKS-00-0000, or space-constrained model 20TKS-00-0000), GE Security Interlogix 1078C-G recessed door contacts, and HES 1600 or HES 9600 electrified door locks with Schlage L909X mortise locks. Request-for-exit functionality must be either embedded in electrified door locks or provided via Bosch DS150i PIR motion sensors; exit buttons and mag locks are prohibited without prior Collier County approval. The specification also addresses wiring requirements, power supply configurations, alarm control options, wave-to-open door sensors, and system configuration protocols, including TLS encryption for controllers and RS-485 line termination at specified ports.

The specification mandates that controllers be configured with IP addresses, gateways, and subnets provided by Brevard County (BCC) Facilities but configured by the vendor, with reader numbers and addresses supplied by BCC but terminated and labeled by the vendor. Power supplies must be AL600ULXB units (12/24VDC dual output preferred with 20 percent extra amperage) hardwired from dedicated circuits, with sufficient battery backup (typically 2-12VDC/7AH batteries) and AC/battery failure supervision. The exhibit requires compliance with specific equipment models and prohibits substitutions without Collier County approval, establishing strict technical requirements to ensure system consistency and interoperability across the Senior Center expansion project's access control infrastructure.

View the file

Other files

File Type Posted
26-8672_FPP_-_HUD_R2.9.25.26.pdf PDF
26-8672_-_Bid_Schedule_R7.xlsx XLSX spreadsheet
Addendum_9_EOR_NARRATIVE_09.25.2026.pdf PDF
26-8672_-_Exhibit_M_-_Senior_Center_Expansion_-_Construction_Plans_REV4.pdf PDF
26-8672_-_Exhibit_L_-_Scope_of_Work_Revised_09252026.pdf PDF
26-8672_-_Exhibit_J_-_Senior_Center_-_Specifications_REV5.pdf PDF
26-8672_Pre-Bid_and_Site-Visit_Sign-in_Sheet.pdf PDF
26-8672_Exhibit_-_GC_Staging_and_Parking_Maps.pdf PDF
26-8672_Exhibit_-_Avigilon_Camera_List.xlsx XLSX spreadsheet
26-8672_Addendum_3_EOR_Narrative_08.24.2026.pdf PDF
26-8672_-_SolicitationR1.pdf PDF
26-8672_Supplemental_Info_-_Geotechnical_Report.pdf PDF
26-8672_-_Solicitation_07.14.26.pdf PDF
26-8672_-_Bid_Schedule_R3.xlsx XLSX spreadsheet
Construction_Services_Agreement_2025_Template_ver_3_with_Exhibits.pdf PDF
26-8672_-_Exhibit_K_-_Site_Development_Plan_Amendment_(SDPA).pdf PDF
26-8672_FPP.pdf PDF
PO_Terms_and_Conditions_Rev.3.pdf PDF
26-8672_-_Exhibit_L_-_Scope_of_Work.pdf PDF
26-8672_-_Exhibit_J_-_Senior_Center_-_Specifications.pdf PDF
26-8672_-_Exhibit_N_-_EHS_Contractor_Requirements_Master_2021_rev.pdf PDF
26-8672_-_Exhibit_M_-_Senior_Center_Expansion_-_Construction_Plans.pdf PDF
Construction_Bid_Instructions_Version_1.pdf PDF
26-8672_-_Authorization_to_Advertise_-_2026_07-08.pdf PDF
Show all 24

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

06/18/2026

Collier County Card Access Requirements and Guidelines:

o Lenel LNL-M4420 Controllers – Required (each LNL-M4420 can support up to 2 doors) o Lenel LNL-1320-S3 Dual card reader Interface panels – Required if more than 2 Doors (each LNL-1320-S3 can support 2 doors) o HID Readers:

40TKS-00-0000 or 40KTKS-00-0000 (K for keyboard) – Required.

20TKS-00-0000 for space Constrained mounting o Recessed Door Contacts: GE Security Interlogix 1078C-G Recessed Steel Door Contact or equivalent o For Chain Link Fence Doors, use: GL1 Electromechanical Gate Lock: SKU: GL1-FLM By Securitron o For Door Strikes or Electrified Door Locks use

HES 1600

L909X Schlage Electrified Mortise Door locks

Heavy duty Electrified hinges Similar to Ives 180 continuous electrified hinge

NOTE: HES 9600 is okay also Equivalents need the approval of Collier County o REX (request for exit) RX embedded in Electrified Door Locks Or PIR - Bosch DS150i Request-to-Exit PIR Detector Motion Sensor -

DC 12/24V - Light Gray o Should not be any Exit buttons (i.e. no Mag Locks)

But if so, Request Collier County Approval first to use o Alarm Control TS-14 or TS-15 space constrained mounting

GUIDE for GENERAL CARD ACCESS WIRING

There should be ran in a singular combo cable following wires:

4 wire OSDP rated cable - 22 Gauge 2 Wires for Door Contact – 22 Gauge 4 Wires for Request for Exit – 22 Gauge 2 Wires for Lock power – 18 Gauge

All Lenel installations shall use the following equipment:

Lenel LNL-M4420 (Controller)

Lenel LNL-1320-S3 (Dual Card Reader Interface Panels)

HID Card Readers o Standard: 40TKS-00-0000 or 40KTKS-00-0000 (K for keyboard) o Space Constrained Mounting: 20TKS-00-0000

GE Security Recessed Door Contacts o Interlogix 1078C-G Recessed Steel Door Contact or equivalent

Door Strikes/Electrified Door Locks o HES 1600 or HES 9600 o Schlage L909X

Request for Exit (REX) o REX embedded in Electrified Door

Or o PIR - Bosch DS150i Request-to-Exit PIR Detector Motion Sensor - DC 12/24V - Light Gray

Refrain from using Exit Buttons (i.e., no Mag Locks) o If needed, Request Collier County Approval first to use o Alarm Control TS-14 or TS-15 (Space Constrained Mounting)

Wave-to-Open Door Sensors (where applicable) o Camden CM-332/42SW or equivalent

Typical setup for enclosure

T1M1CK1 – Trove2 and/or Trove3 models can be substituted for larger installation projects.

Install rocker and tamper switch and hardwire power supply).

Ensure ‘supervision’ with AC Failure and battery failure.

Install a sufficient number of batteries (typically 2-12VDC/7AH) for requirements to each power supply.

LNL-M4420 (or 1320/S2)

IP, gateway, and subnet will be provided by BCC Facilities but configured by vendor.

Address and Reader numbers will be provided by BCC Facilities but terminated and labeled by vendor.

M4420 should be configured with TLS encryption.

Terminate RS-485 line at Port 2.

J7 jumper should be set appropriately based on input voltage.

Inputs should be reserved for door contact, PIR, or automatic openers.

*LNL-1100/1200-S3 is preferred model if additional inputs are required.

AL600ULXB (12/24VDC dual output is preferred, provision 20% extra amperage) Power supply needs to be hardwired from nearest or existing dedicated circuit available.

PDS8CB –

ACM8CB (or ACM4CB)

*In scope where existing access control is being removed, FACP should be terminated to ACM8CB.

VR6 -