This document is a UST (Underground Storage Tank) Regulatory Inspection Requirements chart detailing mandatory inspection and maintenance activities. The chart specifies various regulatory requirements, their inspection frequencies, and responsible parties, primarily categorized into monthly, annually, and three-year intervals. Key requirements include monthly tasks like manual tank gauging, interstitial monitoring sensor status checks, release detection equipment walkthrough inspections, and spill bucket inspections, which are primarily performed by Operations & Maintenance (O&M) personnel.
Longer-interval requirements include three-year inspections for corrosion protection, piping tightness testing, overfill protection, and sump tightness testing, which are typically conducted by a UST Contractor. Additionally, the chart indicates some annual requirements such as registration/delivery certificate verification by GSA, handheld release detection equipment inspection, and release detection equipment testing. Other notable requirements include maintaining records of debris/water removal within 96 hours and conducting operator training every three years. The document serves as a comprehensive guide for maintaining regulatory compliance and ensuring the proper monitoring and maintenance of underground storage tank systems.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UST Regulatory Inspection Requirements Regulatory Requirement Frequency Date Due Performed by
Registration/Delive ry Certificate
Annually GSA
Corrosion Protection 3 year inspection
UST
Contractor
Manual Tank Gauge (stick)
Monthly O&M
Interstitial Monitoring Sensor Status
Monthly O&M
Release Detection Equipment walkthrough Inspection
Monthly O&M
Inspect handheld release detection equipment (stick) walkthrough
Annually O&M
Test Release Detection Equipment for Proper Operation
Annually UST Contractor
Piping Tightness Testing
3 years UST Contractor
Spill bucket inspection Monthly O&M
Spill Bucket & 3 years UST
Sump Tightness Testing
Contractor
Annual Walkthrough log for all containment sumps
Annually &M
Records showing removal of debris/water removed
96 hours O&M
Overfill Protection Inspection
3 years UST Contractor
Operator Training 3 years O&M