2025.06.19-_Exist_Warehouse_to_Parks_Rec_-_Structural_Permit_Set_SS.pdf
PDF 2 MB Posted
- Attached to
- Michigan Avenue Warehouse Renovation
- Solicitation number
- ITB 25-098
- Issued by
- Lee County, Fruitville CDP, Florida
About this file
These structural engineering documents are for the Warehouse Conversion to Clerk of Court Records project for the City of Fort Myers, Florida, located at 2200 Second Street. The project involves converting an existing warehouse into a new facility for the Clerk of Court Records, with structural modifications to both the north and south buildings. The documents, prepared by RTM Engineering Consultants and dated June 19, 2025, are permit documents designed to guide the renovation, which includes modifications to foundations, wall openings, canopy framing, and roof structures.
The structural plans detail comprehensive retrofitting strategies, including reinforcing existing concrete and CMU walls, creating new wall openings, installing new HSS beams and columns, and modifying roof and canopy framing. The design incorporates specific engineering specifications such as using 4000 PSI concrete, ASTM-compliant materials, and following the 2023 Florida Building Code. The plans specify wind load requirements of 160 MPH, use of mechanical anchors, and detailed connection methods between new and existing structural elements. The project appears to be fully funded and prepared for permit submission, with a focus on maintaining structural integrity while adapting the existing warehouse for its new governmental records storage purpose.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STANDARD ABBREVIATIONS
AB ANCHOR BOLT
ACI AMERICAN CONCRETE INSTITUTE
AFF ABOVE FINISH FLOOR
ALT ALTERNATE
ARCH ARCHITECT
ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS
ASD ALLOWABLE STRESS DESIGN
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
AWS AMERICAN WELDING SOCIETY
@ AT
BLDG BUILDING
BLK BLOCKING
BOT BOTTOM
BP BASE PLATE
BRG BEARING
BTWN BETWEEN
CANT CANTILEVER
CG CENTER OF GRAVITY
CIP CAST IN PLACE
CJ CONTROL JOINT
CL CENTERLINE
CLR CLEAR, CLEARANCE
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONT CONTINUOUS
CTR CENTER
DEG DEGREES
DIA DIAMETER
DL DEAD LOAD
DN DOWN
DTL DETAIL
DWG DRAWING
DWL DOWEL
(E) EXISTING
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
ELEV ELEVATOR
EQ EQUAL
EW EACH WAY
f’c CONCRETE STRENGTH
FBC FLORIDA BUILDING CODE
FIN FINISH
FND FOUNDATION
FTG FOOTING
Fy YIELD STRENGTH OF STEEL
GA GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
HORIZ HORIZONTAL
K KIPS
KLF KIPS PER LINEAR FOOT
KSF KIPS PER SQUARE FOOT
KSI KIPS PER SQUARE INCH
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LRFD LOAD AND RESISTANCE FACTOR DESIGN
Lr ROOF LIVE LOAD
LSH LONG SIDE HORIZONTAL
LSL LONG SLOTTED
LSV LONG SIDE VERTICAL
LW LIGHTWEIGHT
MAX MAXIMUM
MECH MECHANICAL
MEP MECHANICAL, ELECTRICAL AND PLUMBING
MEZZ MEZZANINE
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
NDS NATIONAL DESIGN SPECIFICATION FOR
WOOD
NOM NOMINAL
NTS NOT TO SCALE
OC ON CENTER
OPP OPPOSITE
OWJ OPEN WEB JOIST
PCF POUNDS PER CUBIC FOOT
PCI PRECAST CONCRETE INSTITUTE
PL PLATE
PLF POUNDS PER LINEAR FOOT
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED, POST-TENSION
REF REFERENCE
REINF REINFORCEMENT
REQD REQUIRED
REV REVISION
SDI STEEL DECK INSTITUTE
SF SQUARE FOOT
SIM SIMILAR
SOG SLAB ON GRADE
SPEC SPECIFICATION
SS STAINLESS STEEL
SSL SHORT SLOTTED
STD STANDARD
T&B TOP AND BOTTOM
T/REFERENCE TOP OF REFERENCE
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
W/ WITH
W/O WITHOUT
WWF WELDED WIRE FABRIC
A101
SIM
CONCRETE TILT PANEL
STRUCTURAL MASONRY WALL
DETAIL SECTION NUMBER
STEP IN WALL/BEAM
ON SHEET REFERENCE
STEP IN SLAB ELEVATION
SLOPE IN SLAB
EBX EMBED TAG
W21x44 [22] <1 1/4"> 33K
UNFACTORED REACTION
CAMBER @ MIDSPAN
# OF 3/4" Ø x 4 1/2" HS
BEAM SIZE
SECTION MARK
SYMBOL DESCRIPTION
LEGEND
CONCRETE/PRECAST COLUMN
TAG - THROUGH
CONCRETE/PRECAST COLUMN
TAG - ABOVE
XX
XX
CONCRETE/PRECAST COLUMN
TAG - BELOW
XX
SPAN DIRECTION
SYMBOL DESCRIPTION
FOOTING STEP SYMBOL
MOMENT CONNECTION
REQUIRED
UP DOWN
STRUCTURAL WOOD WALL
METAL STUD WALL
EARTH FILL
EARTH UNDISTURBED
CAST IN PLACE CONCRETE
PRECAST CONCRETE
SOUTH BUILDING NORTH BUILDING
EXISTING ROOF EXISTING ROOF
CONDENSER
UNIT
PLATFORM
CONDENSER UNIT
PLATFORM
NEW STRUCTURE
NEW STRUCTURE
NEW STRUCTURE
S4.1
S4.1
SEE ARCH.
S E
E A
R C
H
SEE ARCH.
EX. SKYLIGHTS TO BE
REMOVED
ROOF TO BE REFRAMED
(TYP.)
EX. SKYLIGHTS TO BE REMOVED
ROOF TO BE REFRAMED
(TYP.)
S5.0
S5.0
TYP.
TYP.
engineering consultants 12573 New Brittany Blvd. | Fort Myers, FL 33907
T: 239.210.5090 : www.rtmassociates.com
PROJECT NO:
DATE:
PHASE:
ISSUED FOR
SEAL:
GRACE HEBERT CURTIS ARCHITECTS, LLC
SHEET NUMBER
© THIS SET OF DOCUMENTS INCLUSIVE OF
DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT
BE COPIED, SCANNED, NOR ELECTRONICALLY
DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT
THE EXPRESSED WRITTEN CONSENT OF GRACE
HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,
ELECTRONIC PLAN SERVICE (INTERNET PLAN
SERVICE), NOR REPRODUCTION COMPANY SHALL BE
PERMITTED TO POST THESE DOCUMENTS WITHOUT
THE EXPRESSED WRITTEN CONSENT OF THE
ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.
COA: 31254Project Number: 24335
/2
/2
:3
:0
A
M
A u to d e s k D o c s
/W a re h o u s e C o n v e rt t o
P a rk s
R e c D e p a rt m e n t/
E x is t W a re h o u s e t o P a rk s
R e c
N o rt h
S o u th b u id in g
S
T R
R
.r v t
S1.0
GENERAL NOTES
40-24105
W A
R E
H O
U S
E C
O N
V E
R S
IO
N
T O
C L
E R
K O
F C
O U
R T
R E
C O
R D
S C
IT
Y
O F
F O
R T
M Y
E R
S
06/19/2025
PERMIT DOCUMENTS
S
E C
O N
D S
T R
E E
T F
O R
T M
Y E
R S
F
L
GENERAL STRUCTURAL NOTES
GENERAL: DETAILS AND SECTIONS SHOWN ON THE DRAWINGS ARE TYPICAL AND APPLY TO SIMILAR SITUATIONS ELSEWHERE, EXCEPT AS OTHERWISE INDICATED. ADAPT REQUIREMENTS OF DETAILS, SECTIONS, PLANS, AND NOTES AT LOCATIONS WHERE CONDITIONS ARE SIMILAR.
CENTER ALL FOOTINGS AND PIERS UNDER COLUMNS ABOVE UNLESS SPECIFICALLY DIMENSIONED OTHERWISE.
STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, AND SITE DRAWINGS. CONSULT THESE DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN ON STRUCTURAL DRAWINGS.
CONTRACTOR SHALL LOCATE ALL BURIED UTILITIES PRIOR TO EXCAVATION FOR BUILDING FOUNDATIONS. THE STRUCTURAL ENGINEER SHALL BE NOTIFIED OF
POTENTIAL CONFLICTS BETWEEN FOUNDATIONS AND BURIED UTILITIES.
CODE REQUIREMENTS: THE BUILDING STRUCTURE IS DESIGNED IN ACCORDANCE WITH THE 2023 8th EDITION OF THE FLORIDA BUILDING CODE. FOLLOW ALL APPLICABLE PROVISIONS FOR ALL PHASES OF CONSTRUCTION. ADDITIONS ARE IN COMPLIANCE WITH THE 2023 EDITION OF THE FLORIDA EXISTING BUILDING
CODE.
DESIGN CRITERIA: DESIGN WAS BASED ON STRENGTH AND DEFLECTION CRITERIA OF THE 2023 FLORIDA BUILDING CODE. IN ADDITION TO THE DEAD LOADS, THE FOLLOWING LOADS AND ALLOWABLES WERE USED FOR DESIGN, WITH LIVE LOADS REDUCED PER THE 2023 FBC:
SUPERIMPOSED DEAD LOADS:
FLOORS: 20 PSF
CANOPY 20 PSF 300 POUND CONCENTRATED
INCLUDES AN ALLOWANCE OF 5 PSF AND A 250 LB POINT LOAD FOR WATER FILLED SPRINKLER PIPING.
CANOPY: 20 PSF
RAIN LOAD:
RAIN 20 PSF
RAINFALL INTENSITY 5.0 IN/HR
WIND SPEED (ASCE 7-22) 160 MPH (124 MPH ALLOWABLE)
RISK CATEGORY II
EXPOSURE D
INTERNAL PRESSURE COEFF +/- 0.18 ENCLOSED
ROOF TOP EQUIPMENT PRESSURES: HORIZONTAL 160 PSF/UPLIFT 126 PSF (ULTIMATE)
OPENINGS LOCATED WITHIN 30FT OF GRADE SHALL BE PROTECTED FROM WIND BORNE DEBRIS PER MISSILE LEVEL D OF ASTM E1996.
OPENINGS LOCATED ABOVE 30FT OF GRADE SHALL BE PROTECTED FROM WIND BORNE DEBRIS PER MISSILE LEVEL A OF ASTM E1996.
FOUNDATIONS: FOUNDATIONS ARE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,500 PSF ON COMPACTED FILL. BEFORE CONSTRUCTION COMMENCES, SOIL BEARING CAPACITY SHALL BE VERIFIED BY A SUBSURFACE INVESTIGATION, AS WELL AS FIELD AND LABORATORY TESTS PERFORMED BY A CERTIFIED TESTING LABORATORY, WHOSE REPORT SHALL INCLUDE ANALYSIS AND RECOMMENDATIONS FOR SITE PREPARATION IN ORDER TO BEAR THE FOUNDATION LOADS. ABOVE REPORT SHALL BE SUBMITTED TO THE STRUCTURAL ENGINEER FOR REVIEW
BEFORE FOUNDATION CONSTRUCTION BEGINS.
SUBMITTALS: SHOP DRAWINGS SHALL BE SUBMITTED TO THE ARCHITECT PRIOR TO FABRICATION AND CONSTRUCTION REGARDING ALL STRUCTURAL ITEMS
INCLUDING THE FOLLOWING:
1. CONCRETE MIX DESIGNS
2. CONCRETE AND MASONRY REINFORCING
3. STRUCTURAL STEEL
4. ROOF METAL DECK
SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMITTAL TO THE ARCHITECT/ENGINEER. DRAWINGS SUBMITTED WITHOUT REVIEW
WILL BE RETURNED UNCHECKED.
IF THE SHOP DRAWINGS DIFFER FROM OR ADD TO THE DESIGN OF THE STRUCTURAL DRAWINGS, THEY SHALL BEAR THE SEAL AND SIGNATURE OF A STRUCTURAL ENGINEER REGISTERED IN THE STATE OF PROJECT LOCATION. ANY CHANGES TO THE STRUCTURAL DRAWINGS SHALL BE SUBMITTED TO THE
ARCHITECT AND ARE SUBJECT TO THE REVIEW AND ACCEPTANCE OF THE ENGINEER.
DESIGN DRAWINGS, SHOP DRAWINGS, AND CALCULATIONS FOR THE DESIGN AND FABRICATION OF ITEMS THAT ARE DESIGNED BY OTHERS, INCLUDING:
1. STRUCTURAL STEEL CONNECTIONS,
2. PREENGINEERED STAIRS,
3. MECHANICAL EQUIPMENT STANDS.
SHALL BEAR THE SEAL AND SIGNATURE OF A STRUCTURAL ENGINEER REGISTERED IN THE STATE OF PROJECT LOCATION, AND SHALL BE SUBMITTED TO THE ARCHITECT PRIOR TO FABRICATION. CALCULATIONS SHALL BE INCLUDED FOR ALL CONNECTIONS TO THE STRUCTURE, CONSIDERING LOCALIZED EFFECTS ON THE STRUCTURAL ELEMENTS INDUCED BY THE CONNECTION LOADS. DESIGN SHALL BE BASED ON THE REQUIREMENTS OF THE 2023 FBC.
SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGN INTENT OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC.
CONTRACTOR SHALL NOT BE RELIEVED FROM RESPONSIBILITY FOR ERRORS OR OMISSIONS IN SHOP DRAWINGS OR MIX DESIGNS BY THE ENGINEER’S
REVIEW.
CONCRETE: REINFORCED CONCRETE CONSTRUCTION SHALL CONFORM TO THE FBC AND ACI 318 "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE". CONCRETE STRENGTHS SHALL BE VERIFIED BY STANDARD 28-DAY CYLINDER TESTS PER ASTM C39, AND SHALL BE AS FOLLOWS:
f’c USE
3000 PSI FOUNDATIONS/SLAB ON GRADE
4000 PSI ALL USES, U.N.O.
CEMENT SHALL CONFORM TO ASTM C150, TYPE 1. FLY ASH CONFORMING TO ASTM C618, TYPE F OR TYPE C, MAY BE USED TO REPLACE UP TO 20% OF THE CEMENT CONTENT, PROVIDED THAT THE MIX STRENGTH IS SUBSTANTIATED BY TEST DATA. COARSE AGGREGATE SHALL CONFORM TO ASTM C33 WITH A MAXIMUM SIZE OF 3/4". FINE AGGREGATE SHALL BE CLEAN, DURABLE, NATURAL SAND CONFORMING TO ASTM C33.
A WATER-REDUCING ADMIXTURE, IF USED, SHALL CONFORM TO ASTM C494 AND USED IN STRICT ACCORDANCE WITH THE MANUFACTURER’S RECOMMENDATIONS, SHALL BE INCORPORATED IN CONCRETE DESIGN MIXES. A HIGH-RANGE WATER-REDUCING ADMIXTURE CONFORMING TO ASTM C494, TYPE F OR G, MAY BE USED IN CONCRETE MIXES, PROVIDING THAT THE SLUMP DOES NOT EXCEED 8”.
SLEEVES, OPENINGS, CONDUIT, AND OTHER EMBEDDED ITEMS NOT SHOWN ON THE STRUCTURAL DRAWINGS SHALL BE APPROVED BY THE STRUCTURAL ENGINEER BEFORE POURING. NO SLEEVE, OPENING, OR INSERT MAY BE PLACED IN BEAMS, JOISTS, OR COLUMNS UNLESS APPROVED BY THE ENGINEER.
CONDUITS EMBEDDED IN SLABS SHALL NOT BE LARGER IN OUTSIDE DIMENSION THAN ONE THIRD OF THE THICKNESS OF THE SLAB AND SHALL NOT BE SPACED
CLOSER THAN THREE DIAMETERS ON CENTER.
PROVIDE 3/4” CHAMFERS ON ALL EXPOSED CONCRETE EDGES, UNLESS NOTED OTHERWISE. WHERE INDICATED OR REQUIRED, SLOPE CONCRETE SLABS TO
DRAINS SHOWN ON PLUMBING AND/OR ARCHITECTURAL DRAWINGS.
ALL CONCRETE SHALL BE CURED IMMEDIATELY AFTER FINISHING OPERATIONS.
REINFORCING STEEL: REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 60, FOR DEFORMED BAR AND ASTM A1064 FOR SMOOTH WELDED WIRE FABRIC (WWF), UNLESS OTHERWISE NOTED. REINFORCING STEEL TO BE WELDED SHALL CONFORM TO ASTM A706. REINFORCING STEEL SHALL
BE SECURELY TIED IN PLACE WITH #16 ANNEALED IRON WIRE..
ALL DETAILING AND ACCESSORIES SHALL CONFORM TO ACI DETAILING MANUAL SP-66. PROVIDE CHAIRS, SPACERS, BOLSTERS, AND ITEMS IN CONTACT WITH FORMS WITH HOT-DIP GALVANIZED LEGS OR PLASTIC LEGS. ACCURATELY POSITION, SUPPORT, AND SECURE REINFORCEMENT AGAINST DISPLACEMENT BY FORMWORK CONSTRUCTION OR CONCRETE PLACEMENT OPERATIONS. "WET-STICKING" OF REINFORCING IS PROHIBITED.
REQUIRED CONCRETE COVER FOR REINFORCING STEEL (UNLESS NOTED OTHERWISE):
FOOTINGS 3" BOTTOM AND SIDES, 2" TOP
SLABS 3/4"
WALLS 1-1/2”
LAP SPLICE CONTINUOUS VERTICAL OR HORIZONTAL BARS IN CONCRETE MEMBERS IN ACCORDANCE WITH ACI 318, LATEST EDITION, FOR CLASS "B" TENSION LAP SPLICES. DO NOT SPLICE CONTINUOUS TOP BARS IN BEAMS AT ENDS OF CLEAR SPANS. DO NOT SPLICE CONTINUOUS BOTTOM BARS IN BEAMS IN CLEAR SPANS BETWEEN SUPPORTS. SHOW ALL SPLICES ON SHOP DRAWINGS. SPLICE LOCATIONS AND METHODS SUBJECT TO APPROVAL OF STRUCTURAL
ENGINEER.
AT SLAB RE-ENTRANT CORNERS, PROVIDE (2) #5 X 4’-0” DIAGONAL BARS. AT SLAB AND WALL OPENINGS PROVIDE A MINIMUM OF (2) #5 BARS ALL FOUR SIDES AND DIAGONALLY; EXTEND THESE BARS A LAP DISTANCE OR A MINIMUM OF 24” PAST THE OPENING OR HOOK BARS IF DISCONTINUOUS.
DOWEL ALL WALLS AND COLUMNS TO FOOTINGS WITH BAR SIZE AND SPACING TO MATCH VERTICAL REINFORCING UNLESS OTHERWISE SHOWN.
SLABS ON GRADE: PREPARE SUBGRADE AS PER THE RECOMMENDATIONS OUTLINED IN THE GEOTECHNICAL REPORT. CHAIR WIRE FABRIC DURING CONCRETE PLACEMENT TO INSURE PROPER POSITION IN SLAB. USE VAPOR BARRIER UNDER ALL ENCLOSED INTERIOR SPACES, PER ARCHITECTURAL DRAWINGS.
PLACE CRACK CONTROL JOINTS AS SHOWN ON PLAN OR AT 12 FEET MAXIMUM FOR 4” SLAB. JOINT SPACING SHALL NOT EXCEED A 1.5 TO 1 WIDTH TO LENGTH RATIO. CONTRACTOR SHALL SUBMIT A CONTROL JOINT LAYOUT FOR ENGINEER’S AND ARCHITECT’S REVIEW PRIOR TO CONCRETE PLACEMENT. LOCATE CONTROL JOINTS AT COLUMN LINES AND RE-ENTRANT CORNERS TYPICAL. PROVIDE (1) #5 X 4’-0” DIAGONAL BARS AT SLAB RE-ENTRANT CORNERS.
FOR 4” THICK SLABS ON GRADE, PROVIDE 6X6 W1.4XW1.4 WELDED WIRE FABRIC OR 1.5 POUNDS PER CUBIC YARD OF MICRO SYNTHETIC FIBERS (FRC
MONO-150 OR EQUAL), UNLESS NOTED OTHERWISE.
CONCRETE ACCESSORIES: HEADED SHEAR STUDS SHALL BE NELSON HEADED ANCHORS WITH FLUXED ENDS OR APPROVED EQUAL. DEFORMED BAR ANCHORS (DBA) SHALL BE NELSON, TYPE D2L, OR APPROVED. STUDS AND DBA SHALL BE AUTOMATICALLY END WELDED WITH THE MANUFACTURER'S STANDARD EQUIPMENT IN ACCORDANCE WITH THEIR RECOMMENDATIONS. HAND WELDING NOT PERMITTED.
PERMANENTLY EXPOSED EMBEDDED PLATES AND ANGLES SHALL BE HOT-DIPPED GALVANIZED AFTER FABRICATION. ACCURATELY POSITION, SUPPORT, AND SECURE EMBEDDED ITEMS AGAINST DISPLACEMENT BY FORMWORK CONSTRUCTION OR CONCRETE PLACEMENT OPERATIONS. SECURELY ATTACH EMBEDDED ITEMS TO FORMWORK PRIOR TO START OF CONCRETE PLACEMENT. “WET-STICKING" OF EMBEDDED ITEMS IS PROHIBITED. NO LOADS OR WELDS SHALL BE PLACED ON EMBEDDED PLATES OR ANGLES FOR A MINIMUM OF 7 DAYS AFTER CASTING
WHERE NEW CONCRETE IS PLACED AGAINST EXISTING CONCRETE, THE EXISTING CONCRETE SURFACE SHOULD BE CLEANED AND ROUGHENED TO A MINIMUM
1/4” AMPLITUDE
MECHANICAL ANCHORS: MECHANICAL ANCHORS SHALL HAVE THE ICC ES EVALUATION REPORT INDICATING CONFORMANCE WITH CURRENT APPLICABLE ICC ES ACCEPTANCE CRITERIA. MECHANICAL ANCHORS SHALL BE EXPANSION TYPE OR SCREW TYPE AS NOTED ON THE DRAWINGS.
UNLESS OTHERWISE NOTED, PROVIDE CARBON STEEL ANCHORS, ZINC PLATED IN ACCORDANCE WITH ASTM B633 OR HOT-DIPPED GALVANIZED ACCORDING TO ASTM A153. PERMANENTLY EXPOSED ANCHORS SHALL BE STAINLESS STEEL. USE 316 STAINLESS STEEL FOR MECHANICAL EQUIPMENT AND FOR ALUMINUM
AND FIBERGLASS STRUCTURES AND ASSEMBLIES.
ACCEPTABLE MECHANICAL ANCHORS FOR ANCHORAGE TO CONCRETE SHALL BE AS FOLLOWS, OR AS NOTED ON THE DRAWINGS:
1. HILTI KWIK HUS EZ AND KWIK HUS EZ-I SCREW ANCHORS PER ICC ESR-3027
2. POWERS WEDGE BOLT SCREW ANCHOR PER ICC ESR-2526
3. SIMPSON TITEN HD SCREW ANCHOR PER ICC ESR-2713
MINIMUM EMBEDMENT FOR CONCRETE ANCHORS SHALL BE AS FOLLOWS, OR AS NOTED ON THE DRAWINGS:
1. 1/2” DIAMETER – 3 3/4” EMBEDMENT
2. 5/8” DIAMETER – 5” EMBEDMENT
3. 3/4" DIAMETER – 5 3/4” EMBEDMENT
FOR ANCHORAGE TO SOLID GROUTED CMU PROVIDE ONE OF THE FOLLOWING ANCHORS, OR AS NOTED ON THE DRAWINGS:
1. HILTI KWIK HUS EZ AND KWIK HUS EZ-I SCREW ANCHORS PER ICC ESR-3056
2. POWERS WEDGE BOLT SCREW ANCHOR PER ICC ESR-1678
3. SIMPSON TITEN HD SCREW ANCHOR PER ICC ESR-1056
MINIMUM EMBEDMENT FOR SOLID GROUTED CMU ANCHORS SHALL BE AS FOLLOWS, OR AS NOTED ON THE DRAWINGS: ANCHORS NOT ALLOWED WITHIN 1 1/2"
OF HEAD JOINTS
1. 1/2” DIAMETER – 3 3/4” EMBEDMENT
2. 5/8” DIAMETER – 5” EMBEDMENT
3. 3/4" DIAMETER – 5 3/4” EMBEDMENT
IDENTIFY POSITION OF REINFORCING STEEL AND OTHER EMBEDDED ITEMS PRIOR TO DRILLING HOLES FOR ANCHORS. EXERCISE CARE IN CORING OR DRILLING TO AVOID DAMAGING EXISTING REINFORCING OR EMBEDDED ITEMS. NOTIFY THE ENGINEER IF REINFORCING STEEL OR OTHER EMBEDDED ITEMS
ARE ENCOUNTERED DURING DRILLING.
MASONRY WALLS: MASONRY UNITS SHALL MEET ASTM C90, TYPE 2. ASSEMBLIES SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF f’m= 1500. MORTAR SHALL BE TYPE "M" OR "S" AND MEET ASTM C270. GROUT SHALL BE 2000 PSI MINIMUM COMPRESSIVE STRENGTH AND MEET ASTM C476. GROUT SHALL CONSIST OF A MIXTURE OF CEMENTITIOUS MATERIALS AND AGGREGATE TO WHICH SUFFICIENT WATER HAS BEEN ADDED TO CAUSE THE MIXTURE TO FLOW WITHOUT SEGREGATION OF THE CONSTITUENTS. ALL CELLS CONTAINING VERTICAL BARS, BOND BEAMS, AND ALL CELLS BELOW GRADE SHALL BE FILLED
WITH GROUT. MAXIMUM HEIGHT OF GROUT POUR ALLOWED IS 4'-0" UNLESS CLEAN-OUT OPENING IS PROVIDED AT BOTTOM OF CELLS TO BE FILLED. LOCATE
CLEAN-OUT OPENINGS IN AREAS NOT EXPOSED TO VIEW.
UNLESS NOTED OTHERWISE EIGHT INCH MASONRY WALLS SHALL BE PARTIALLY REINFORCED MASONRY WALL CONSTRUCTION WITH #5 AT 48 INCH O.C. IN GROUT FILLED CELLS. ADD (1) #5 REINFORCING BAR EACH SIDE OF OPENINGS EXCEEDING 3 FEET.
PROVIDE REINFORCING BARS AT CORNERS, INTERSECTIONS, AND EACH SIDE OF OPENINGS. PROVIDE (2) REINFORCING BARS EACH SIDE OF OPENINGS OVER 4 FEET WIDE, AND AS SHOWN ON THE PLANS. PROVIDE HOOKED DOWELS INTO FOOTINGS AND STRUCTURE ABOVE AND/OR BELOW TO PROVIDE CONTINUITY.
PROVIDE 9 GAGE GALVANIZED HORIZONTAL JOINT REINFORCING (DUR-O-WAL OR ENGINEER-APPROVED EQUAL) AT 16” O.C. REINFORCING LAPS TO BE 48 BAR
DIAMETERS.
DO NOT PLACE CONDUITS, PIPES, ETC., IN CELLS WITH VERTICAL REINFORCING. DO NOT RUN CONDUITS, PIPES, ETC., HORIZONTALLY IN CMU WALLS PARALLEL TO LENGTH OF WALL. WHERE MASONRY WALLS ABUT CONCRETE COLUMNS TO BE PLACED PRIOR TO ERECTION OF MASONRY WALLS, PROVIDE DOVETAIL SLOTS BETWEEN COLUMN AND WALLS AND GROUT THE CMU CELL CONTAINING THE DOVETAIL ANCHORS. OTHERWISE, EXTEND CMU HORIZONTAL
JOINT REINFORCING THROUGH CONCRETE COLUMN.
CONTROL JOINTS SHALL BE PROVIDED IN ALL CONCRETE MASONRY CONSTRUCTION AT LOCATIONS INDICATED ON THE ARCHITECTURAL DRAWINGS.
HORIZONTAL WALL REINFORCING SHALL BE STOPPED EACH SIDE OF CONTROL JOINTS. SEE ARCHITECTURAL DRAWINGS FOR SEALANT REQUIREMENTS AT
CONTROL JOINTS.
USE METAL LATH OR WIRE SCREEN FOR CAVITY CAPS. SHEET METAL, FELT, BUILDING PAPER, OR LIKE MATERIALS ARE PROHIBITED.
STRUCTURAL STEEL: STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING:
W-SHAPES ASTM A992 GRADE 50.
CHANNELS, PLATES AND ANGLES ASTM A36.
RECTANGULAR AND SQUARE TUBES ASTM A500 GRADE C (Fy = 50KSI).
DESIGN, FABRICATION AND ERECTION SHALL BE IN ACCORDANCE WITH THE "AISC SPECIFICATION FOR THE DESIGN, FABRICATION AND ERECTION OF
STRUCTURAL STEEL FOR BUILDINGS".
BOLTS SHALL CONFORM TO THE ASTM SPECIFICATION FOR A325 OR A490, HIGH STRENGTH BOLTS.
WELDING SHALL CONFORM TO THE AWS CODES FOR ARC AND GAS WELDING IN BUILDING CONSTRUCTION. WELDS SHALL BE MADE USING E70XX ELECTRODES AND SHALL BE 3/16” MINIMUM UNLESS OTHERWISE NOTED. WELDING SHALL BE BY AWS CERTIFIED WELDERS. PREQUALIFIED WELDING PROCEDURES ARE TO BE USED, UNLESS AWS QUALIFICATION IS SUBMITTED TO THE ENGINEER PRIOR TO FABRICATION.
STEEL TO RECEIVE ONE SHOP COAT AND ONE FIELD TOUCH UP COAT OF APPROVED PAINT, EXCEPT WHERE GALVANIZING IS INDICATED ON THE DRAWINGS.
ALL BOLTED CONNECTIONS SHALL CONSIST OF MINIMUM 3/4 INCH DIAMETER ASTM A325 HIGH STRENGTH BOLTS. BEAM CONNECTIONS SHALL BE DESIGNED BY THE FABRICATOR FOR THE REACTIONS SHOWN ON THE PLANS. IF NOT SHOWN, THE FABRICATOR SHALL DESIGN THE BEAM CONNECTIONS TO SUPPORT AN END REACTION OF 1/2 THE ALLOWABLE UNIFORM LOAD CAPACITY WITH A MINIMUM OF 2 BOLTS.
STEEL STUDS AND RUNNER TRACK MEMBERS SHALL CONFORM TO ASTM A653 GRADE C (MINIMUM YIELD POINT 40,000 PSI) WITH HOT DIPPED GALVANIZED
COATING CONFORMING TO ASTM A525 (CLASS G90).
ALL FRAMING MEMBERS SHALL BE CUT SQUARELY. MEMBERS SHALL BE HELD FIRMLY IN PLACE UNTIL PROPERLY JOINED. JOINING OF MEMBERS SHALL BE MADE WITH SELF-DRILLING SCREWS OR WELDING. WIRE TYING OF FRAMING MEMBERS SHALL NOT BE PERMITTED. ATTACHMENT OF MATERIALS TO FRAMING
MEMBERS SHALL BE MADE WITH SELF DRILLING SCREWS.
STUDS SHALL SIT SQUARELY IN THE TOP AND BOTTOM RUNNER TRACKS WITH FIRM ABUTMENT AGAINST TRACK WELDS. STUDS SHALL BE PLUMB AND
SECURELY FASTENED TO THE FLANGES OF BOTH TOP AND BOTTOM RUNNER TRACKS.
SUBMIT COMPLETE SHOP DRAWINGS AND DESIGN CALCULATIONS, PREPARED, SIGNED, AND SEALED BY A PROFESSIONAL ENGINEER LICENSED IN THE STATE
OF FLORIDA, SUBSTANTIATING ALL STRENGTH AND SERVICEABILITY CRITERIA.
SCALE: 1" = 20'-0"
KEY PLAN1 N.T.S.
NO. DESCRIPTION DATE
06/23/2025
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND
SEALED USING A DIGITAL SIGNATURE.
PRINTED COPIES OF THIS DOCUMENT ARE NOT
CONSIDERED SIGNED AND SEALED AND THE
SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC
COPIES.
UP
DN
(E) COLUMN TO
REMAIN, TYP.
(E) COLUMN TO
REMAIN, TYP.
(E) WALL TO
REMAIN, TYP. (E) WALL TO
REMAIN, TYP.
(E) OPENING TO
REMAIN, TYP.
F W
F W
F20W
F20W
F W
6" CONCRETE
SLAB ON GRADE
W/ 6X6
W2.9XW2.9 WWF TYP.
6" CONCRETE
SLAB ON GRADE
W/ 6X6
W2.9XW2.9 WWF TYP.
4" CONCRETE
SLAB ON GRADE
W/ 6X6
W1.4XW1.4 WWF
6" CONCRETE
SLAB ON GRADE
W/ 6X6
W2.9XW2.9 WWF TYP.
S4.0
S4.1
N-4N-4
N-3N-3
N-A
N-A
N-B
N-B
N-C
N-C
N-D
N-D N-5
N-5 N-E
N-E
N-F
N-F
N-G
N-G
20' - 0" 18' - 10" 1' - 2" 20' - 0" 20' - 0" 20' - 0"
1' - 2" 7' - 0 5/8" 6' - 5 3/8" 8' - 9" 5' - 0" 12' - 9" 20' - 0"
/8
(E) RAMP TO
REMAIN, TYP.
(E) WALL TO
REMAIN, TYP.
S4.1
RAMP GEOMETRY -
SEE ARCH DWGS
(TYPICAL.)
FOUNDATION PLAN NOTES:
1. REFER TO ARCHITECTURAL DRAWINGS FOR VAPOR BARRIER REQUIREMENTS, SLOPES, STEPS, AND DRAIN LOCATIONS IN FLOOR SLABS.
2. REFER TO GEOTECHNICAL RECOMMENDATIONS FOR SUBGRADE COMPACTION AND DRAINAGE REQUIREMENTS.
3. DO NOT SCALE DRAWINGS. VERIFY/COORDINATE ALL DIMENSIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS BEFORE COMMENCING CONSTRUCTION. NOTIFY THE STRUCTURAL ENGINEER AND ARCHITECT OF RECORD OF ANY DISCREPANCIES BEFORE PROCEEDING WITH CONSTRUCTION.
4. CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS PRIOR TO COMMENCING CONSTRUCTION. NOTIFY THE ENGINEER OF
RECORD OF ANY DISCREPANCIES.
5. VERIFY/COORDINATE THE LOCATION OF ALL UNDERGROUND PIPING WITH THE FOUNDATION.
6. VERIFY/COORDINATE EDGE OF SLAB DETAILS AT EXTERIOR DOORS, SILL HEIGHTS AND DETAILS OF WALL OPENINGS WITH ARCHITECTURAL DRAWINGS.
7. FX INDICATES FOOTING TYPE, REFER TO FOOTING SCHEDULE ON THIS SHEET. TOP OF FOOTING ELEVATION SHALL BE AT LEAST -1'-4" BELOW ADJCAENT
FINISHED GRADE, UNLESS NOTED OTHERWISE.
8. INDICATES 8" CMU WALLS W/ #5 VERTICALS AT 48" OC MAX, AND AT CORNERS, INTERSECTIONS AND BOTH SIDES OF OPENINGS, UNLESS
NOTED OTHERWISE.
(E) COLUMN TO
REMAIN, TYP.
(E) WALL TO
REMAIN, TYP.
(E) WALL TO
REMAIN, TYP.
NEW CMU INFILL
F20WF20W
F W
F20W
F W
F W
6" CONCRETE
SLAB ON GRADE
W/ 6X6
W1.4XW1.4 WWF
4" CONCRETE
SLAB ON GRADE
W/ 6X6
W1.4XW1.4 WWF
S4.0
S4.1
6" CONCRETE
SLAB ON GRADE
W/ 6X6
W2.9XW2.9 WWF TYP.
6" CONCRETE
SLAB ON GRADE
W/ 6X6
W1.4XW1.4 WWF
S-1S-1
S-A
S-A
S-B
S-B
S-C
S-C
S-D
S-D
S-2 S-2
16' - 8" 7' - 0" 5' - 0"
35' - 2" 30' - 0" 34' - 0"
'-0
12' - 0" 7' - 0" 29' - 6"
NEW WINDOW OPENING
IN EXISTING WALLNEW DOOR OPENING
IN EXISTING WALL
NEW WINDOW OPENING
IN EXISTING WALL
17' - 0" 5' - 11" 13' - 4" 24' - 0" 4' - 11" 3' - 9" 8' - 0"
MC1
F20W
F W
RAMP GEOMETRY -
SEE ARCH DWGS
(TYP.)
PLANTER WALL -
SEE ARCH. DWGS
S-A
S-A
S-B
S-B
S-C
S-C
S-5S-5
F W
F W
F30W
S4.1
S4.1
(E) WALL TO
REMAIN, TYP.(E) COLUMN TO
REMAIN, TYP.
NEW DOOR OPENING
IN EXISTING WALL
6" CONCRETE
SLAB ON GRADE
W/ 6X6
W2.9XW2.9 WWF TYP.
(E) SLAB TO
REMAIN, TYP.
(E ) C
O
L (E) CO
L
BASE PL 1/2"X12"X16" FOR
(4) 3/4" TITEN HD SCREWS
(TYP.)
S4.0
(E) FOOTING TO
REMAIN, TYP.
(E) FOOTING TO
REMAIN, TYP.
(E) FOOTING TO
REMAIN, TYP.
6" CONCRETE
SLAB ON GRADE
W/ 6X6
W2.9XW2.9 WWF TYP.
6" CONCRETE
SLAB ON GRADE
W/ 6X6
W2.9XW2.9 WWF TYP.
GS SHALL PRICE FOR MEASURES
THAT WOULD ALLOW TO VERIFY
IN FIELD IF THE EXISTING BASE IS
SUITABLE TO INSTALL NEW
COLUMNS IN THE LOCATION OF
DEMOLISHED COLUMNS.
RAMP GEOMETRY -
SEE ARCH DWGS
(TYPICAL.)
DRILL & EPOXY #5 x 2'-0" DOWEL W/
6" EMBED - TYP TOP & BOTTOM
AT EACH NEW VERT.
EXISTING CMU WALL
#5 VERT IN GROUT FILLED CELL EA
SIDE OF OPENING AND @ 32" OC
EXISTING FOOTING OR
WINDOW SILL
DRILL AND EPOXY #3 x 9" @ 16" OC
W' 3" EMBED OR BRICK TIE @ 16" OC
#5 VERT IN GROUTED
FILLED CELL EACH SIDE
OF OPENING, DRILL &
EPOXY LAP BAR 30" LAP,
6" EMBED MIN USE HILTI
HIT HY 150 OR SIMPSON
EPOXY TIE SET EPOXY
INTO EXISTING TIE
BEAM
EXISTING
MASONRY WALL
OPENING
NEW PRECAST
CONCRETE LINTEL
8" BEARING
engineering consultants 12573 New Brittany Blvd. | Fort Myers, FL 33907
T: 239.210.5090 : www.rtmassociates.com
PROJECT NO:
DATE:
PHASE:
ISSUED FOR
SEAL:
GRACE HEBERT CURTIS ARCHITECTS, LLC
SHEET NUMBER
© THIS SET OF DOCUMENTS INCLUSIVE OF
DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT
BE COPIED, SCANNED, NOR ELECTRONICALLY
DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT
THE EXPRESSED WRITTEN CONSENT OF GRACE
HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,
ELECTRONIC PLAN SERVICE (INTERNET PLAN
SERVICE), NOR REPRODUCTION COMPANY SHALL BE
PERMITTED TO POST THESE DOCUMENTS WITHOUT
THE EXPRESSED WRITTEN CONSENT OF THE
ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.
COA: 31254Project Number: 24335
/2
/2
:3
:0
A
M
A u to d e s k D o c s
/W a re h o u s e C o n v e rt t o
P a rk s
R e c D e p a rt m e n t/
E x is t W a re h o u s e t o P a rk s
R e c
N o rt h
S o u th b u id in g
S
T R
R
.r v t
S2.0
PARTIAL FOUNDATION
PLANS
40-24105
W A
R E
H O
U S
E C
O N
V E
R S
IO
N
T O
C L
E R
K O
F C
O U
R T
R E
C O
R D
S C
IT
Y
O F
F O
R T
M Y
E R
S
06/19/2025
PERMIT DOCUMENTS
S
E C
O N
D S
T R
E E
T F
O R
T M
Y E
R S
F
L
SCALE: 3/16" = 1'-0"
FOUNDATION PLAN - NORTH BUILDING
WALL FOUNDATION SCHEDULE NORTH BLDG
MARK WIDTH THICKNESS REINFORCEMENT COMMENTS
F20W 2' - 0" 1' - 0" (3) #5 CONT. BOT -
F30W 3' - 0" 1' - 0" (4) #5 CONT. BOT -
SCALE: 3/16" = 1'-0"
FOUNDATION PLAN - SOUTH BUILDING
SCALE: 3/16" = 1'-0"
FOUNDATION PLAN - SOUTH BUILDING
WALL FOUNDATION SCHEDULE SOUTH BLDG
MARK WIDTH THICKNESS REINFORCEMENT COMMENTS
F20W 2' - 0" 1' - 0" (3) #5 CONT. BOT -
F30W 3' - 0" 1' - 0" (4) #5 CONT. BOT -
F40W-R 4' - 0 3/8" 1' - 0" (5) #5 CONT. BOT & #4 @ 12"
OC TRANSVERSE T&B
RETAINING WALL FOOTING
SCALE: 3/4" = 1'-0"
CMU INFILL DETAIL1 SCALE: 3/4" = 1'-0"
NEW OPENING IN CMU WALL2
NO. DESCRIPTION DATE
06/23/2025
N-4N-4
N-3N-3
N-A
N-A
N-B
N-B
N-C
N-C
N-D
N-D N-5
N-5 N-E
N-E
N-F
N-F
N-G
N-G
6' - 5" 6' - 10" 19' - 8 3/8"
ALUMINUM CANOPY BY
OTHERS. (TYP.)
W.O. BELOW
5' - 0"
HSS6X6X3/8
EX. DOOR JAMB MEMBER AND GIRT
BEAM AT NEW HANGER ATTACHEMENT
TO BE TO BE REINFORCED W/ L6X6X3/8.
3/16 WELDS.
GRIND EX. MEMBERS AS REQUIRED.
S5.0
(N) C8X11.5 B18'-0" EXT.
(N) C8X11.5 B18'-0" INT.
S5.0
STRUCTURAL PLAN NOTES
1. REFER TO ARCHITECTURAL DRAWINGS FOR SLOPES, STEPS, AND DRAIN LOCATIONS IN FLOOR SLABS.
2. BX INDICATES CONCRETE BEAM TYPE, REFER TO CONCRETE BEAM SCHEDULE ON THIS SHEET.
3. TX'-X" INDICATES TOP OF BEAM ELEVATION, 11'-10" UNLESS NOTED OTHERWISE.
S-1S-1
S-A
S-A
S-B
S-B
S-C
S-C
S-D
S-D
S-2 S-2
ALUMINUM CANOPY
DESIGNED BY OTHERS
(TYP.)MC1
VIF
17' - 0"
W.O. BELOW
5' - 11"
VIF
1' - 1"
W.O. BELOW
24' - 0"
VIF
4' - 11" 3' - 9"
W.O. BELOW
8' - 0"
W.O. BELOW
8' - 0" 6' - 3"
(N) C8X11.5 B17'-4" INT.(N) C8X11.5 B17'-4" INT.(N) C12X30 B17'-4" INT.(N) C8X11.5 B17'-4" INT.
(N) HSS12X4X1/4 (FLAT) T20'-6"
(E) METAL WALL
TO REMAIN, TYP.
S5.0
(E ) C
O L
(E ) C
O L
(E ) C
O L
(E ) C
O L.
(E ) C
O L.
(N) HSS12X4X1/4 (FLAT) T20'-6" (N) HSS12X4X1/4 (FLAT) T20'-6"
WELD TO EX.
COLUMN USING
L6X6X3/8 T&B
TYP.
H S
S X
X
/4
(N) C8X11.5 B17'-4" EXT.
(N) C8X11.5 B17'-4" EXT. (N) C8X11.5 B17'-4" EXT. (N) C8X11.5 B17'-4" EXT.
S5.0
S5.0
S-A
S-A
S-B
S-B
S-C
S-C
S-5S-5
EXISTING CANOPY TO BE
DEMOLISHED & NEW ALUMINUM
CANOPY DESIGNED BY OTHERS
3' - 4 1/2"
W.O. BELOW
2' - 10"
S5.0
(E ) C
O L
(E ) C
O L
(N) HSS12X6X1/4 B/12' - 0"EX. TIE BEAM
EX. TIE BEAM
TOP ELEVATION TO MATCH
TOP OF, TIE BEAM VIF.
ATTACH HSS TO EX. WALL
USING
3/8"x4"x12" x 6" WIDE
BENT PL @ 32" OC.
WELDED TO HSS AND
BOLTED TO CMU USING (2)
3/4" TITEN HD SCREWS (TYP.)
(N
HSS12
X6X
3/
(E) WALL ABOVE SHORE,
CUT AND RECONNECT
13' - 4"
CONNECT BOTH HSS
POSTS W 3/8"x4"x12" x
6" WIDE BENT PL @ 32"
OC WELDED TO WEBS
(TYP.)
(N) HSS 8X6X1/4 FLAT
EL. VIF.(N
HSS12
X6X
3/ engineering consultants 12573 New Brittany Blvd. | Fort Myers, FL 33907
T: 239.210.5090 : www.rtmassociates.com
PROJECT NO:
DATE:
PHASE:
ISSUED FOR
SEAL:
GRACE HEBERT CURTIS ARCHITECTS, LLC
SHEET NUMBER
© THIS SET OF DOCUMENTS INCLUSIVE OF
DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT
BE COPIED, SCANNED, NOR ELECTRONICALLY
DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT
THE EXPRESSED WRITTEN CONSENT OF GRACE
HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,
ELECTRONIC PLAN SERVICE (INTERNET PLAN
SERVICE), NOR REPRODUCTION COMPANY SHALL BE
PERMITTED TO POST THESE DOCUMENTS WITHOUT
THE EXPRESSED WRITTEN CONSENT OF THE
ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.
COA: 31254Project Number: 24335
/2
/2
:3
:0
A
M
A u to d e s k D o c s
/W a re h o u s e C o n v e rt t o
P a rk s
R e c D e p a rt m e n t/
E x is t W a re h o u s e t o P a rk s
R e c
N o rt h
S o u th b u id in g
S
T R
R
.r v t
S3.0
PARTIAL STRUCTURAL
PLANS
40-24105
W A
R E
H O
U S
E C
O N
V E
R S
IO
N
T O
C L
E R
K O
F C
O U
R T
R E
C O
R D
S C
IT
Y
O F
F O
R T
M Y
E R
S
06/19/2025
PERMIT DOCUMENTS
S
E C
O N
D S
T R
E E
T F
O R
T M
Y E
R S
F
L
SCALE: 3/16" = 1'-0"
CANOPY FRAMING PLAN - NORTH BUILDING1
SCALE: 3/16" = 1'-0"
CANOPY FRAMING PLAN - SOUTH BUILDING2 SCALE: 3/16" = 1'-0"
CANOPY FRAMING PLAN - SOUTH BUILDING3
N-4N-4
N-3N-3
N-A
N-A
N-B
N-B
N-C
N-C
N-D
N-D N-5
N-5
S
-4
O C
S
-4
O C
S-1S-1
S-A
S-A
S-B
S-B
S-C
S-C
S-D
S-D
S-2 S-2
S-3S-3
S-4 S-4
S-5S-5
ALUMINUM CANOPY BY
OTHERS. (TYP.)
ALUMINUM CANOPY BY
OTHERS. (TYP.)
ALUMINUM CANOPY BY
OTHERS. (TYP.) ALUMINUM CANOPY BY
OTHERS. (TYP.)
MC1
17' - 0"
W.O. BELOW
5' - 11"
1' - 1"
W.O. BELOW
24' - 0" 4' - 11" 3' - 9"
W.O. BELOW
8' - 0"
W.O. BELOW
8' - 0" 6' - 3"
(N) C8X11.5 B/ 17'-4" (N) C8X11.5 B/ 17'-4" (N) C12X30 B/ 17'-4" (N) C8X11.5 B/ 17'-4"
HSS 12X4X1/4 FLAT T/ 20'-6"
(E) METAL WALL
TO REMAIN, TYP.
S5.0
(E ) C
O L
(E ) C
O L
(E ) C
O L
(E ) C
O L.
(E ) C
O L.
HSS 12X4X1/4 FLAT T/ 20'-6" HSS 12X4X1/4 FLAT T/ 20'-6"
WELD TO EX.
COLUMN USING
L6X6X3/8 T&B
TYP.H
S
S X
X
/4
(2
S
-4
S
-4
O C
800S162-43 @ 16" OC
(2) 1000S162-43
800S162-43
800S162-43
S
-4
O C
1000S162-43 @ 16" OC
800S162-43 @ 16" OC
S
-4
S
-4
S
-4
S
-4
S
-4
O C
1000S162-43 @ 16" OC
800S162-43 @ 16" OC
(2
S
-4
S
-4
O C
S
-4
O C
S5.0
FLOOR FRAMING PLAN NOTES
1. REFER TO ARCHITECTURAL DRAWINGS FOR SLOPES, STEPS, AND DRAIN LOCATIONS IN FLOOR SLABS.
4. TX'-X" INDICATES TOP OF BEAM ELEVATION, [X'-X"] UNLESS NOTED OTHERWISE.
3. INDICATES 4" METAL STUD WALLS W/ 16" STUD SPACING.
engineering consultants 12573 New Brittany Blvd. | Fort Myers, FL 33907
T: 239.210.5090 : www.rtmassociates.com
PROJECT NO:
DATE:
PHASE:
ISSUED FOR
SEAL:
GRACE HEBERT CURTIS ARCHITECTS, LLC
SHEET NUMBER
© THIS SET OF DOCUMENTS INCLUSIVE OF
DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT
BE COPIED, SCANNED, NOR ELECTRONICALLY
DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT
THE EXPRESSED WRITTEN CONSENT OF GRACE
HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,
ELECTRONIC PLAN SERVICE (INTERNET PLAN
SERVICE), NOR REPRODUCTION COMPANY SHALL BE
PERMITTED TO POST THESE DOCUMENTS WITHOUT
THE EXPRESSED WRITTEN CONSENT OF THE
ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.
COA: 31254Project Number: 24335
/2
/2
:3
:0
A
M
A u to d e s k D o c s
/W a re h o u s e C o n v e rt t o
P a rk s
R e c D e p a rt m e n t/
E x is t W a re h o u s e t o P a rk s
R e c
N o rt h
S o u th b u id in g
S
T R
R
.r v t
S3.1
CEILING FRAMING
40-24105
W A
R E
H O
U S
E C
O N
V E
R S
IO
N
T O
C L
E R
K O
F C
O U
R T
R E
C O
R D
S C
IT
Y
O F
F O
R T
M Y
E R
S
06/19/2025
PERMIT DOCUMENTS
S
E C
O N
D S
T R
E E
T F
O R
T M
Y E
R S
F
L
SCALE: 3/16" = 1'-0"
CEILING FRAMING PLAN - NORTH BUILDING1
SCALE: 3/16" = 1'-0"
CEILING FRAMING PLAN - SOUTH BUILDING2
KEYED JOINT
CONSTRUCTION JOINT
CONTROL JOINT
POSITION
REINFORCEMENT IN
CENTER OF SLAB
SUBGRADE PER
GEOTECHNICAL
RECOMMENDATIONS
T H
IC
K
N E
S S
/4
S
L A
B
VAPOR BARRIER
PER ARCH
S L A
B T
H
IC
K N
E S
S
SAW CUT JOINT POSITION
REINFORCEMENT IN
CENTER OF SLAB
SUBGRADE PER
GEOTECHNICAL
RECOMMENDATIONS
VAPOR BARRIER
PER ARCH
#4 @ 16" OC
EPOXIED INTO EX.
SLAB W/ 6" MIN.
EMBED. EX. SLAB TO
REMAIN
SUBGRADE PER
GEOTECHNICAL
RECOMMENDATIONS
POSITION
REINFORCEMENT IN
CENTER OF SLAB
RECESS PER
ARCH. DWGS
1' - 0" MIN.
V .I .F
OVERLAP
1' - 0" MIN.
EXIST. VAPOR
BARRIER TO
SALVAGE AND
OVERLAP W/ NEW
SLAB ON GRADE
PER PLAN
#4 @ 16" OC
(2) #5 CONT
1' - 0"
#4 NOSING BAR
TYP
#3 @ 18" OC EACH WAY
SEE ARCH DWGS FOR
STAIR LAYOUT
6"
1' - 0"
FINISH GRADE
1' - 0"
SLAB ON GRADE
PER PLAN
TYPE-1
TYPE-2
TYPE-3
/- T Y
P
STUD OR
JOIST
#10 SCREWS @ 12" O.C.
TYP. @ TOP AND BOTTOM
BUILT-UP BEAM PER
PLAN
CONT. CLOSURE METAL
TRACK @ TOP AND
BOTTOM (SIZE AND GAGE
MATCH TO STUDS)
#10 SCREWS @ 12"
O.C. TYP. @ TOP
AND BOTTOM
BUILT-UP BEAM
PER PLAN
BUILT-UP BEAM
PER PLAN
#10 SCREWS @ 12" O.C.
TYP. @ TOP AND BOTTOM
(STAGGERED 6")
NOTE:-
MEMBER SHOWN AS
HORIZONTAL BEAMS, HOWEVER,
THIS DETAIL ALSO APPLIES TO
VERTICAL POST.
CFS STUD WALL PER
PLAN
EXTERIOR SIDE
INTERIOR SIDE 1 3/4" LONG STRONG-DRIVE PPSD #10 SCREWS @
12" O.C. FOR SHEATHING-TO-CFS OR EQ.
CFS STUD AS
PER PLAN
FINISHES AS PER ARCH.
FINISHES AS PER ARCH.
FINISHES AS PER
ARCH.
FINISHES AS PER
ARCH. EXISTING BEAM
OPENING
1/4
L4X4X1/4 x 12" LG
BOLTED TO EX. TIE
BEAM USING (2) 3/4"
ANCHORS W/ 4" MIN
EMBED.
L4X4X1/4 (TYP.)
WELDED TOGETHER
EX. TIE BEAM
1/4
TYP.
SCALE: NOT TO SCALE
RAMP AT SLAB ON GRADE3 SCALE: 3/4" = 1'-0"
CAST IN PLACE STAIR ON GRADE4SCALE: NOT TO SCALE
TYPICAL SLAB ON GRADE JOINTS1 SCALE: NOT TO SCALE
TYPICAL NEW AND EXISTING SLAB INTERFACE2
engineering consultants 12573 New Brittany Blvd. | Fort Myers, FL 33907
T: 239.210.5090 : www.rtmassociates.com
PROJECT NO:
DATE:
PHASE:
ISSUED FOR
SEAL:
GRACE HEBERT CURTIS ARCHITECTS, LLC
SHEET NUMBER
© THIS SET OF DOCUMENTS INCLUSIVE OF
DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT
BE COPIED, SCANNED, NOR ELECTRONICALLY
DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT
THE EXPRESSED WRITTEN CONSENT OF GRACE
HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,
ELECTRONIC PLAN SERVICE (INTERNET PLAN
SERVICE), NOR REPRODUCTION COMPANY SHALL BE
PERMITTED TO POST THESE DOCUMENTS WITHOUT
THE EXPRESSED WRITTEN CONSENT OF THE
ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.
COA: 31254Project Number: 24335
/2
/2
:3
:0
A
M
A u to d e s k D o c s
/W a re h o u s e C o n v e rt t o
P a rk s
R e c D e p a rt m e n t/
E x is t W a re h o u s e t o P a rk s
R e c
N o rt h
S o u th b u id in g
S
T R
R
.r v t
S4.0
TYPICAL DETAILS
40-24105
W A
R E
H O
U S
E C
O N
V E
R S
IO
N
T O
C L
E R
K O
F C
O U
R T
R E
C O
R D
S C
IT
Y
O F
F O
R T
M Y
E R
S
06/19/2025
PERMIT DOCUMENTS
S
E C
O N
D S
T R
E E
T F
O R
T M
Y E
R S
F
L
SCALE: 6" = 1'-0"
TYPICAL BUILT-UP MEMBER CONFIGURATIONS6
SCALE: 6" = 1'-0"
EXTERIOR WALL SECTION IN PLAN5
SCALE: 6" = 1'-0"
TYP. DETAIL @ CORNER7 SCALE: 3/4" = 1'-0"
EXISTING STEEL PROFILE WALL OPENING DETAIL8
CONCRETE FOOTING
PER PLAN
GROUT CMU SOLID
BELOW GRADE
SLAB ON GRADE
PER PLAN
#4x2'-0" HOOKED BAR @ 18" OC
TYP.
(1) #5 CONT.
TYP.
8" CMU WALL W/ #5 VERTS
@ 48" OC MAX
8" CMU WALL W/ #5 VERTS
@ 48" OC MAX
EXISTING CONCRETE
FOOTING
EXISTING CMU WALL
SLAB ON GRADE
PER PLAN
#4x2'-0" HOOKED BAR @ 18" OC
TYP.
CONCRETE
FOOTING PER PLAN
1' - 6"
#4x2'-0" HOOKED BAR @ 18" OC
TYP.
DRILL AND EPOXY #5
DOWEL W/ 6" EMBED
MATCH WALL
REINFORCING.
B
A R
D
IA
L A
P
CONCRETE FOOTING
PER PLAN
SLAB ON GRADE
PER PLAN
#4x2'-0" HOOKED BAR @ 18" OC
TYP.
(1) #5 CONT.
TYP.
8" CMU WALL W/ #5 VERTS
@ 48" OC MAX
GROUT CMU SOLID
BELOW GRADE
8" CMU WALL W/ #5 VERTS
@ 48" OC MAX
EXISTING CONCRETE
FOOTING
EXISTING CMU WALL
SLAB ON GRADE
PER PLAN
#4x2'-0" HOOKED BAR @ 18" OC
TYP.
CONCRETE
FOOTING PER PLAN
1' - 6"
#4x2'-0" HOOKED BAR @ 18" OC
TYP.
DRILL AND EPOXY #5
DOWEL W/ 6" EMBED
MATCH WALL
REINFORCING.
B
A R
D
IA
L A
P
SEE ARCH.
CONCRETE FOOTING
PER PLAN
(1) COURSE BOND BEAM
W/ (1) #5 CONT
CMU WALL FULLY GROUTED
W/ #5 VERTS @ 24" OC
CONCRETE SLAB ON
GRADE PER PLAN
FINISH GRADE
1' - 0"
D
IA
O
F R
E B
A R
GROUT CMU SOLID
BELOW GRADE
8" CMU WALL W/ #5 VERTS
@ 24" OC MAX
EPOXIED INTO FTG. BELOW
W/ 6" EMBED
EXISTING CONCRETE
FOOTING
EXISTING CMU WALL
SLAB ON GRADE
PER PLAN
#4x2'-0" HOOKED BAR
@ 18" OC TYP.
GROUT CMU SOLID
BELOW GRADE
8" CMU WALL W/ #5 VERTS
@ 48" OC MAX
EXISTING CONCRETE
FOOTING
EXISTING CMU WALL
ALIGN
#4x2'-0" HOOKED BAR @ 18" OC
TYP.
CONCRETE
FOOTING PER PLAN
1' - 6"
#4x2'-0" HOOKED BAR @ 18" OC
TYP.
DRILL AND EPOXY #5
DOWEL W/ 6" EMBED
MATCH WALL
REINFORCING.
B
A R
D
IA
L A
P
SLAB ON GRADE
PER PLANSEE ARCH.
(5) #4 CONT. TYP. 1
#4 @ 16" OC
DOWELS EPOXIED
INTO EXISTING SLAB
(TYP.)
PROVIDE MIN. 12" WIDE
OVERLAP OF NEW & OLD
VAPOUR BARRIER (TYP.)
MEP LINES - SEE MEP
DWGS.
MAX.
2' - 0"
NEW VAPOUR BARRIER -
SEE ARCH, 10 MIL MIN.
M A
X
#4 @ 12" OC
EXISTING SLAB ON GRADE
VAPOUR BARRIER - VIF
ALIGN (TYP.)
SLOPE AS REQUIRED
(5) #4 CONT. TYP. 1
#4 @ 16" OC
DOWELS EPOXIED
INTO EXISTING SLAB
(TYP.)
PROVIDE MIN. 12" WIDE
OVERLAP OF NEW & OLD
VAPOUR BARRIER (TYP.)
2' - 0"
NEW VAPOUR BARRIER -
SEE ARCH, 10 MIL MIN.
M A
X
#4 @ 12" OC
EXISTING SLAB ON GRADE
VAPOUR BARRIER - VIF
ALIGN (TYP.)
SLOPE AS REQUIRED
HSS POST AND BASE PLATE
DESIGNED BY STAIR
MANUFACTURER
BASE PLATE DESIGNED BY
OTHERS ATT'D TO NEW
FOUNDATION USING (4) 3/4"
TITEN HD SCREWS W/ 6"
MIN. EMBED.
engineering consultants 12573 New Brittany Blvd. | Fort Myers, FL 33907
T: 239.210.5090 : www.rtmassociates.com
PROJECT NO:
DATE:
PHASE:
ISSUED FOR
SEAL:
GRACE HEBERT CURTIS ARCHITECTS, LLC
SHEET NUMBER
© THIS SET OF DOCUMENTS INCLUSIVE OF
DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT
BE COPIED, SCANNED, NOR ELECTRONICALLY
DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT
THE EXPRESSED WRITTEN CONSENT OF GRACE
HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,
ELECTRONIC PLAN SERVICE (INTERNET PLAN
SERVICE), NOR REPRODUCTION COMPANY SHALL BE
PERMITTED TO POST THESE DOCUMENTS WITHOUT
THE EXPRESSED WRITTEN CONSENT OF THE
ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.
COA: 31254Project Number: 24335
/2
/2
:3
:0
A
M
A u to d e s k D o c s
/W a re h o u s e C o n v e rt t o
P a rk s
R e c D e p a rt m e n t/
E x is t W a re h o u s e t o P a rk s
R e c
N o rt h
S o u th b u id in g
S
T R
R
.r v t
S4.1
FOUNDATION DETAILS
40-24105
W A
R E
H O
U S
E C
O N
V E
R S
IO
N
T O
C L
E R
K O
F C
O U
R T
R E
C O
R D
S C
IT
Y
O F
F O
R T
M Y
E R
S
06/19/2025
PERMIT DOCUMENTS
S
E C
O N
D S
T R
E E
T F
O R
T M
Y E
R S
F
L
SCALE: 3/4" = 1'-0"
SECTION THRU RAMP4SCALE: 3/4" = 1'-0"
SECTION THRU RAMP2 SCALE: 3/4" = 1'-0"
SECTION THRU RAMP3
SCALE: 3/4" = 1'-0"
CMU RETAINING WALL5
SCALE: 3/4" = 1'-0"
SECTION THRU RAMP1
SCALE: 3/4" = 1'-0"
SECTION AT CONDENSER UNIT PLATFORM6 SCALE: 3/4" = 1'-0"
TYPICAL TRENCH DETAIL AT EXISTING SOG7 SCALE: 3/4" = 1'-0"
TYPICAL TRENCH DETAIL AT EXISTING SOG Copy 18
(E) OPENING TO REMAIN
(N) HSS BEAM PER PLAN
CANOPY FRAMING BY
OTHERS
CONNECT NEW ALUMINUM
CANOPY TO NEW HSS AS
REQUIRED
NEW EXTERIOR WALL PROFILE
TO MATCH EXISTING - SEE
ARCH. DWGS
CONNECT TO HSS AS REQUIRED
SEE ARCH DWGS FOR DETAILS
COLUMN BEYOND
(E) WALL PER PLAN
L4X4X1/4 T&B
(E) BEAM V.I.F.
BENT PL 1/2"X12"X12"
x 16" LG BOTH SIDES
FOR 3/4" THREADED
RODS IN LONG-
SLOTTED HOLES
(VERTICAL)
VIF
1/4
TYP.
(N) COILING DOOR NOT
SHOWN FOR CLARITY -
SEE ARCH. DWGS
CLCL
(E) CMU WALL PER PLAN
NEW OPENING PER
PLAN
T.O. WALL
VIF
CHANNEL PER PLAN
(E) METAL WALL
PER PLAN
HSS BEAM PER
PLAN
L4x4x1/4 x 12" LG @32"
OC W/ (2) 1/2" TITEN
HD , 4" EMBED. T&B
T.O. BM
VIF
1/4
TYP.
L4X4X1/4 x 12" LG TO EXISTING
TIE BEAM USING 1/2" DIA. MECH
ANCHORS @ 24" OC.
PLACEMENT TO COORDINTAE
W/ ARCH DRAWINGS
ATTACHMENT TO EX.
STRUCTURE DESIGNED BY
OTHERS
ALUMINUM CANOPY DESIGNED
BY OTHERS
V.I.F
T.O. NEW OPENINGS
DRY PACK SOLID
CONNECTION PER 8/S5.0
EXISTING
CMU WALL V.I.F
1/2" X12"X12" PL
ATTACHED TO EX. CMU
WALL USING (4) 1/2"
TITEN HD SCREWS W/
4" MIN EMBED
HSS BEAM PER PLAN
FILL CELLS W/ GROUT
1/4
1/4
L4X4X1/4 B.S.
1/4
3 SIDES SHEAR CONNECTION BY
FABRICATOR
HSS BEAM PER PLAN
EX. STEEL COL
V.I.F.
5/8
L6X4X1/4 T&B
1"
EXISTING
COLUMN V.I.F
HSS BEAM PER PLAN
1/4
TYP.
5/16
TYP.
L6X4X1/4
W/ 2" MIN OVERLAP
ON EA. FL OF EX.
COLUMN TO ALLOW
WELDING
EXISTING
COLUMN V.I.F
HSS BEAM PER PLAN
1/4
3 SIDES
1/4
3 SIDES
1/4
3 SIDES
TYP.
L4X4X1/4 x 12" LG AT
TOP & BOTT. OF HSS
BEAM
L4X4X1/4 x 12" LG AT
TOP & BOTT. OF HSS
BEAM
HSS BEAM PER PLAN
NEW ROOF DECKING TO
MATCH EX. OR BETTER
EX. ROOF METAL DECK
V.I.F.
GRIND GALVANIZATION OF EXISTING PURLINS
AS REQUIRED TO ALLOW FOR PROPER
WELDING, PAINT BACK AS REQUIRED.
NEW L5X5 OR L6X6 CROSS MEMBERS SPANNED
BETWEEN NEW SUB-GIRDERS TO PROVIDE
SUPPORT FOR BOTH EX. AND NEW METAL DECK
W/ MIN. 2" BEARING. E.S.
PROVIDE FASTENERS FROM METAL DECK TO
NEW FRAMING BELOW TO MATCH EXIST.
FASTENING PATTERN AND SIZE.
NEW SUB-GIRDER: L6X6 @
4'-0" MAX SPACING AND AT
OPENING SHORT EDGES
LOWER IT TO CLEAR LIP OF
EX. PURLIN
3/16
TYP.
EX. PURLIN
V.I.F.
PROVIDE 3/8"x4"x6" SHEAR
TUBS AS REQUIRED
COORD. W/ ARCH. DWGS
NEW WALL OPENING
MIN. JAMB
1' - 4"
MIN. JAMB
1' - 4"
6" 8" 8" 1' - 6" 1' - 4" 8" 6"
NOTE: CMU BETWEEN CHANNELS AND AT JAMBS MUST BE
SOLID GROUTED. CHANNELS MUST BE INSTALLED
BEFORE CMU IS REMOVED.
CHANNEL PER PLAN W/ 3/4" DIA.
TITEN HD EA. SIDE
EX. MASONRY PROPOSED JAMBS TO BE FULLY FROUTED
EXISTING CONCRETE BEAM
OR MASONRY ABOVE NEW
OPENING
STEEL CHANNEL
W/ 3/4" O THRU
BOLTS
MIN.
1' - 0" engineering consultants 12573 New Brittany Blvd. | Fort Myers, FL 33907
T: 239.210.5090 : www.rtmassociates.com
PROJECT NO:
DATE:
PHASE:
ISSUED FOR
SEAL:
GRACE HEBERT CURTIS ARCHITECTS, LLC
SHEET NUMBER
© THIS SET OF DOCUMENTS INCLUSIVE OF
DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT
BE COPIED, SCANNED, NOR ELECTRONICALLY
DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT
THE EXPRESSED WRITTEN CONSENT OF GRACE
HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,
ELECTRONIC PLAN SERVICE (INTERNET PLAN
SERVICE), NOR REPRODUCTION COMPANY SHALL BE
PERMITTED TO POST THESE DOCUMENTS WITHOUT
THE EXPRESSED WRITTEN CONSENT OF THE
ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.
COA: 31254Project Number: 24335
/2
/2
:3
:0
A
M
A u to d e s k D o c s
/W a re h o u s e C o n v e rt t o
P a rk s
R e c D e p a rt m e n t/
E x is t W a re h o u s e t o P a rk s
R e c
N o rt h
S o u th b u id in g
S
T R
R
.r v t
S5.0
FRAMING DETAILS
40-24105
W A
R E
H O
U S
E C
O N
V E
R S
IO
N
T O
C L
E R
K O
F C
O U
R T
R E
C O
R D
S C
IT
Y
O F
F O
R T
M Y
E R
S
06/19/2025
PERMIT DOCUMENTS
S
E C
O N
D S
T R
E E
T F
O R
T M
Y E
R S
F
L
SCALE: 3/4" = 1'-0"
CANOPY DETAIL1 SCALE: 3/4" = 1'-0"
CANOPY DETAIL2 SCALE: NOT TO SCALE
HSS BEAM TO EXISTING CMU WALL CONNECTION3 SCALE: NOT TO SCALE
HSS BEAM TO EXISTING COLUMN4
SCALE: NOT TO SCALE
HSS BEAM TO CONNECTS AT WEB ON EXISTING COLUMN5 SCALE: NOT TO SCALE
HSS BEAM TO EXISTING COLUMN DETAILS6 SCALE: 3/4" = 1'-0"
TYP. EXISTING ROOF INFILL DETAIL AT FORMER SKYLIGHT7
NO. DESCRIPTION DATE
SCALE: NOT TO SCALE
NEW OPENING IN CMU WALL8
| Sheets |
| S1.0 - GENERAL NOTES |
| S2.0 - PARTIAL FOUNDATION PLANS |
| S3.0 - PARTIAL STRUCTURAL PLANS |
| S3.1 - CEILING FRAMING |
| S4.0 - TYPICAL DETAILS |
| S4.1 - FOUNDATION DETAILS |
| S5.0 - FRAMING DETAILS |
| 2025-06-23T08:54:58-0400 | |
| Esra Persellin |
File details come from the government source that posted it. Updated .