2024-118_-_CoFM_Warehouse_-_Combined_Electrical.pdf
PDF 4 MB Posted
- Attached to
- Michigan Avenue Warehouse Renovation
- Solicitation number
- ITB 25-098
- Issued by
- Lee County, Fruitville CDP, Florida
About this file
This is an electrical design set of construction documents for the Warehouse Convert to Parks & Rec Department project located at 2801 Michigan Avenue in Fort Myers, Florida, prepared by Grace Hebert Curtis Architects and Matern Professional Engineering for the City of Fort Myers. The project involves converting an existing warehouse into a Parks and Recreation Department facility, with comprehensive electrical design documents dated June 19, 2025, for permit submission. The electrical documents include detailed plans for power systems, lighting, fire alarm systems, site electrical infrastructure, and mechanical equipment feeders across two building sections (North and South), with specific focus on renovating the existing electrical infrastructure to support the new facility's operational requirements.
The electrical design includes a 208V, 3-phase, 4-wire service with an 800A main distribution panel (MDP), two branch panels (SBLP1 and SBLP2) for the South Building, and two branch panels (NBLP1 and NBLP2) for the North Building. The project incorporates LED lighting fixtures, emergency backup lighting, occupancy sensors, and comprehensive systems including fire alarm, access control, and security infrastructure. The electrical design provides for various building spaces including warehouses, offices, conference rooms, restrooms, mechanical rooms, and exterior site lighting. The design also includes provisions for future expansion, surge protection, grounding systems, and compliance with the 2020 National Electrical Code, ensuring a modern, efficient electrical system for the Parks and Recreation Department's new facility.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LIGHT FIXTURE SCHEDULE
TYPE DESCRIPTION BASIS OF DESIGN EQUAL EQUAL VOLTS
A2
RECESSED 2X2' LED
FLAT PANEL
METALUX:
22CGTS-L3C3
DAYBRITE:
2SBP2035L8DS-2-UNV-DIM
ELITE:
22 FPL1 LED 2000/3000/400L-
DIM10-MVOLT-35K/40K/50K-85
4000 LUMENS
4000K 33W
A2E
RECESSED 2X2' LED
FLAT PANEL,
EMERGENCY BATTERY
PACK
METALUX:
22CGTS-L3C3-EL14W
DAYBRITE:
2SBP2035L8DS-2-UNV-
DIM-FPEMLED10RM
ELITE:
22 FPL1 LED 2000/3000/400L-
DIM10-MVOLT-35K/40K/50K-85-
0-EMG-LED-20W
4000 LUMENS
4000K 33W
B1 HIGH BAY LED
METALUX:
SPHB-24-SE-M-UNV-L750-CD
DAYBRITE:
FCY-1525L-8CST-UNV-DIM
ELITE:
CB2-CPA-24000/27000/30000L-
DIM10-MVOLT-MD-
30K/35K/40K/50K-85
24000 LUMENS
4000K 159W
B1E
HIGH BAY LED,
EMERGENCY BATTERY
PACK
METALUX:
SPHB-24-SE-M-UNV-L750-
EL20WHV-CD
DAYBRITE:
FCY-1525L-8CST-UNV-DIM-EM
ELITE:
CB2-CPA-24000/27000/30000L-
DIM10-MVOLT-MD-
30K/35K/40K/50K-85-
EMG-LED-G4-120-347V-CP-25W-HV
24000 LUMENS
4000K 159W
B2
4' DIRECT/INDIRECT
LINEAR PENDENT
AXIS:
TB2DILED-300-1000-80-40-S0-
4-FINISH-UNV-DP-1-CA(#)
FINELITE:
HP2-P-ID-4’-S-TL-840-F-F-96LG-
VOLT-SC-FC-1%-faxxx-C4-
FE-SW
ELITE:
OLS-D1-LED-2-S-D1000L-U500L-1C-
DIM10-MVOLT-40K-85-FINISH
5600 LUMENS
4000K 43W
B2E
4' DIRECT/INDIRECT
LINEAR PENDENT,
EMERGENCY BATTERY
PACK
AXIS:
TB2DILED-300-1000-80-40-S0-
5-FINISH-UNV-DP-1-CA(#)-B
FINELITE:
HP2-P-ID-4’-S-TL-840-F-F-96LG-
VOLT-SC-FC-1%-faxxx-C4-
FE-SW-LGD10W
ELITE:
OLS-D1-LED-2-S-D1000L-U500L-1C-
DIM10-MVOLT-40K-85-FINISH-
0-EMG-LED-10W
5600 LUMENS
4000K 43W
C1
4' LED INDUSTRIAL
STRIP, WET LOCATION
LISTED
METALUX:
4SNX-33SL-LW-UNV-L840-CD-1-U
DAYBRITE:
FSS-4-30L-840-UNV-DIM
ELITE:
4-OC4-LED-
3000/4000/5000L-DIM10-MVOLT-
35K/40K/50K-85
3000 LUMENS
4000K 22W
D1
4" RECESSED LED
DOWNLIGHT
HALO COMMERICAL:
HC420D010-HM405258400
-41MDWF
LIGHTOLIER:
M4R-DL-25-9CS-M-WH-Z10U
ELITE:
HH4-1000/1500/2000L-DIM10-
MVOLT-27/30/35/40/50K-
HH4501-W-WH-MWD-90+
2000 LUMENS
4000K 20W
EM
INDOOR EMERGENCY
BATTERY FIXTURE
SURE-LITES:
APEL SERIES
BEGHELLI:
PEH1
COMPASS:
CU2
120 LED
W1
TYPE FOUR WALL
PACK, WET LOCATION
RAYON LIGHTING:
T652LEDB-20W-UNV-40K-T4-BZ-EM
GARDCO:
GWS-A02-740-T4M-UNV-BZ
BEACON:
VPW2-48L-20-4K7-4F-UNV-DBS
2600 LUMENS
4000K 20W
W1E
TYPE FOUR WALL
PACK, WET LOCATION
WITH BACK UP
BATTERY.
RAYON LIGHTING:
T652LEDB-20W-UNV-40K-T4-BZ-EM
GARDCO:
GWS-A02-740-T4M-UNV-EM-BZ
BEACON:
VPW2-48L-20-4K7-4F-UNV-DBS
2600 LUMENS
4000K 20W
W2
TYPE TWO WALL PACK,
WET LOCATION
RAYON LIGHTING:
T652LEDB-10W-UNV-40K-T2-BZ
GARDCO:
GWS-A01-740-T2M-UNV-BZ
BEACON:
VPW2-48L-15-4K7-2-UNV-DBS
1900 LUMENS
4000K 10W
W2E
TYPE TWO WALL PACK,
WET LOCATION WITH
BACK UP BATTERY.
RAYON LIGHTING:
T652LEDB-10W-UNV-40K-T2-BZ-EM
GARDCO:
GWS-A01-740-T2M-UNV-EM-BZ
BEACON:
VPW2-48L-15-4K7-2-UNV-DBS-E
1900 LUMENS
4000K 10W
X1
EXIT SIGN, RED
LETTERS, BATTERY
BACK-UP
SURE-LITES:
APX7RG
BEGHELLI:
EPX-SA
COMPASS:
CERG
120 LED
SL1
POLE MOUNTED LED
SITE FIXTURE, TYPE V
FORWARD THROW
DISTRIBUTION WITH
SENSOR FOR DIMMING
MOTION, 25' DIRECT
BURIAL CONCRETE
POLE
MCGRAW EDISON:
GALN-SA1B-840-U-T4FT-
FINISH-HSS-WLS4BK
GARDCO:
OPF-S-PO2-840-T4M-AR1-UNV-BL50-
L2-BK
BEACON:
VP-1-160L-35-4K8-4F-UNV-MAF-
FINISH-SHLD-1-HSS-90-B-
FINISH-NXWS-40F
3500 LUMENS
4000K 44W
SL2
POLE MOUNTED LED
SITE FIXTURE, TYPE V
FORWARD THROW
DISTRIBUTION WITH
SENSOR FOR DIMMING
MOTION, 15' DIRECT
BURIAL CONCRETE
POLE
MCGRAW EDISON:
GALN-SA1B-840-U-T4FT-
FINISH-HSS-WLS2BK
GARDCO:
OPF-S-PO2-840-T4M-AR1-UNV-BL50-
L2-BK
BEACON:
VP-1-160L-35-4K8-4F-UNV-MAF-
FINISH-SHLD-1-HSS-90-B-FINISH-
NXWS-16F
3500 LUMENS
4000K 44W
SL3
POLE MOUNTED LED
SITE FIXTURE, 90 SPILL
LIGHT ELIMINATOR ON
RIGHT SIDE WITH
SENSOR FOR DIMMING
MOTION, 15' DIRECT
BURIAL CONCRETE
POLE
MCGRAW EDISON:
GALN-SA1B-840-U-SLR-
FINISH-HSS-WLS2BK
INTENSE:
GTM-L6-35-DIM-FINISH-FF
BEACON:
VP-1-160L-35-4K8-4F-UNV-MAF-
FINISH-SHLD-1-HSS-90-B-FINISH-
NXWS-16F
4400 LUMENS
3500K 45W
LIGHTING FIXTURE SCHEDULE GENERAL NOTES:
(1) CONTRACTOR SHALL CAREFULLY COORDINATE THE LIGHTING FIXTURE TRIM TYPES WITH THE TYPE OF CEILING WHERE THE LIGHTING FIXTURES ARE TO BE INSTALLED. MODIFY FIXTURE CATALOG NUMBER AS REQUIRED TO COORDINATE FIXTURE WITH CEILING.
(2) CONTRACTOR, AT HIS OPTION, MAY USE A U.L. LISTED FLEXIBLE WIRING SYSTEM FOR LIGHTING FIXTURE BRANCH CIRCUITRY ABOVE ACCESSIBLE LAY-IN CEILINGS.
ALL HOMERUNS, CONNECTIONS TO LIGHT SWITCHES, AND BRANCH CIRCUITRY FOR ALL OTHER CEILING CONDITIONS SHALL BE IN A CONVENTIONAL RACEWAY SYSTEM
PER SPECIFICATIONS.
(3) WHEN FIXTURE MODEL NUMBER DIFFERS FROM FIXTURE DESCRIPTION, CONTRACTOR IS TO SUBMIT RFI REQUESTING CLARIFICATION PRIOR TO BID, PRIOR TO SHOP DRAWING SUBMITTAL AND PRIOR TO ORDERING OF FIXTURE. WHERE CONTRACTOR DOES NOT REQUEST CLARIFICATION PRIOR TO BID, CONTRACTOR SHALL PROVIDE THE MOST EXPENSIVE OPTION BETWEEN A FIXTURE THAT MATCHES THE DESCRIPTION AND A FIXTURE THAT MATCHES THE MODEL NUMBER. AFTER BID, CONTRACTOR SHALL SUBMIT RFI REQUESTING CLARIFICATION SO PROPER FIXTURE GETS SUBMITTED, PROVIDED AND INSTALLED.
TYPICAL INDICATING DEVICES
TYPICAL INITIATING DEVICES
TYPICAL CONTROL RELAYS
1ST FLOOR
SOUTH BUILDING FIRE ALARM RISER DIAGRAM
NTS
LOCAL FACP
FIRE ALARM
CONTROL PANEL
DEDICATED TELEPHONE CONNECTION
FOR THIRD PARTY NOTIFICATION
SPRINKLER FLOW & TAMPER
SWITCHES
PROVIDE BATTERY
CALCULATION OF NEW DEVICES
DIALER
F F
F
F
R R FS TS
FIRE ALARM
TERMINAL
CABINET
SITE SPRINKLER FLOW & TAMPER
SWITCHES FS TS
FA-NEW
PROVIDE SURGE ON ALL INCOMING
EXTERRIOR COPPER CABLES
F
F
F
AR
TYPICAL INDICATING DEVICES
TYPICAL INITIATING DEVICES
TYPICAL CONTROL RELAYS
1ST FLOOR
NORTH BUILDING FIRE ALARM RISER DIAGRAM
NTS
SPRINKLER FLOW & TAMPER
SWITCHES
PROVIDE BATTERY
CALCULATION OF NEW DEVICES
F F
F
F
R
FS TS
FA-NEW
F
F
F
2ND FLOOR
CONNECT TO FIRE ALARM VIA
LOCKABLE 20A CB.
CONNECT TO FIRE ALARM VIA
LOCKABLE 20A CB.
FIRE ALARM
TERMINAL
CABINET
LOCAL FACP
FIRE ALARM
CONTROL PANEL
DEDICATED TELEPHONE CONNECTION
FOR THIRD PARTY NOTIFICATION
DIALER
TYPICAL INDICATING DEVICES
TYPICAL INITIATING DEVICES
F
F
F
TYPICAL CONTROL RELAYS RRAR
CONNECT TO FIRE ALARM VIA
LOCKABLE 20A CB. ELECTRICAL SHEET INDEX
SHEET NUMBER SHEET NAME
E001 GENERAL NOTES, LEGEND, ABBREVIATIONS & SHEET INDEX
E001-2 GENERAL NOTES, LEGEND, ABBREVIATIONS & SHEET INDEX
E002 ELECTRICAL SYMBOL LEGEND
E003 ELECTRICAL SYMBOL LEGEND
E010 ELECTRICAL SITE PLAN - POWER AND SYSTEMS
E041 ELECTRICAL SITE PLAN - LIGHTING
E042-N ELECTRICAL SITE PLAN - PHOTOMETERICS
E042-S ELECTRICAL SITE PLAN - PHOTOMETERICS
ED111-N POWER & SYSTEMS - 1ST AND 2ND FLOOR DEMOLITION PLANS - NORTH
BUILDING
ED111-S POWER & SYSTEMS - 1ST FLOOR DEMOLITION PLAN - SOUTH BUILDING
ED411-N LIGHTING - 1ST AND 2ND FLOOR DEMOLITION PLANS - NORTH BUILDING
ED411-S LIGHTING - 1ST FLOOR DEMOLITION PLAN - SOUTH BUILDING
E111-N POWER - 1ST AND 2ND FLOOR PLANS - NORTH BUILDING
E111-S POWER - 1ST FLOOR PLAN - SOUTH BUILDING
E111-S-2 POWER - 1ST FLOOR PLAN - SOUTH BUILDING
E112 ELECTRICAL ROOF PLANS
E311-N SYSTEMS - 1ST AND 2ND FLOOR PLANS - NORTH BUILDING
E311-S SYSTEMS - 1ST FLOOR PLAN - SOUTH BUILDING
E311-S-2 SYSTEMS - 1ST FLOOR PLAN - SOUTH BUILDING
E411-N LIGHTING - 1ST AND 2ND FLOOR PLANS - NORTH BUILDING
E411-S LIGHTING - 1ST FLOOR PLAN - SOUTH BUILDING
E411-S-2 LIGHTING - 1ST FLOOR PLAN - SOUTH BUILDING
E501 ELECTRICAL RISER DIAGRAMS
E501-2 ELECTRICAL RISER DIAGRAMS
E601 ELECTRICAL PANEL SCHEDULES
E601-2 ELECTRICAL PANEL SCHEDULES
E602 ELECTRICAL PANEL SCHEDULES
E701 MECHANICAL FEEDER SCHEDULES
E901 ELECTRICAL DETAILS
A - AMERAGE
A/C - AIR CONDITIONING
A.C. - ALTERNATING CURRENT
A/E - ARCHITECT/ENGINEER (OR ENGINEER
WHEN ARCHITECT NOT APPLICABLE)
AFD - ADJUSTABLE FREQUENCY DRIVE
AFF - ABOVE FINISHED FLOOR
AFG - ABOVE FINISHED GRADE
AHU - AIR HANDLER UNIT
AIC - AMPS INTERRUPTING CAPACITY
AL - ALUMINUM
ALT - ALTERNATE
ANSI - AMERICAN NATIONAL STANDARDS INSTITUTE
AWG - AMERICAN WIRE GAUGE
B.C. - BARE COPPER
BLDG - BUILDING
BRKR - BREAKER
C. - CONDUIT
C.B. - CIRCUIT BREAKER
CD. - CANDELA
CKT. - CIRCUIT
C/L - CENTER LINE
CLG. - CEILING
COMP. - COMPRESSOR
CONN. - CONNECTION
COND. - CONDENSER
CONT. - CONTINUOUS
C.R.I. - COLOR RENDERING INDEX
C.T. - CURRENT TRANSFORMER
CU. - COPPER
C.U. - COMPRESSOR CONDENSER UNIT
CW - COLD WATER
D - DEMO
D.B. - DIRECT BURIAL
D.W. - DIRECT CURRENT
C. - DISCONNECT
DPST - DOUBLE POLE SINGLE THROW
DWG - DRAWING
EC - ELECTRICAL CONTRACTOR
(OR GENERAL CONTRACTOR)
DN. - ELEVATOR
EMT - ELECTRIC METALLIC TUBING
EPA - ENVIRONMENTAL PROTECTION AGENCY
EQUIP. - EQUIPMENT
EST - ESTIMATE
ETR - EXISTING TO REMAIN
FAAP - FIRE ALARM ANNUNCIATOR PANEL
FACP - FIRE ALARM CONTROL PANEL
FATC - FIRE ALARM TERMINAL CABINET
FCCP - FIRE ALARM COMMAND CENTER PANEL
FLA - FULL LOAD AMPERES
FT. - FEET
FLR - FLOOR
F.C. - FOOTCANDLES
G - GROUND FAULT CIRCUIT INTERRUPTER
GAL. - GALLON
GALV. - GALVANIZED
GPH - GALLONS PER HOUR
GPM - GALLONS PER MINUTE
GFI - GROUND FAULT INTERRUPTING
GRS - GALVANIZED RIGID STEEL CONDUIT
GND. - GROUND
HTG - HEATERS
HT - HEIGHT
HZ - HERTZ (CYCLES)
H.P.F. - HIGH POWER FACTOR
HP. - HORSEPOWER
HR. - HOUR
H.S. - HEAT STRIP
IMC - INTERMEDIATE METALLIC CONDUIT
IN. - INCHES
J.B. - JUNCTION BOX
KVA - KILOVOLT AMPERE
KW - KILOWATTS
KWH - KILOWATT HOUR
K - KELVIN
L.L.D. - LAMP LUMEN DEPRECIATION
LED - LIGHT EMITTING DIODE
LIU - LIGHT INTERFACE UNIT
LT. - LIGHT
LTG. - LIGHTING
LTS. - LIGHTS
L.P.F. - LOW POWER FACTOR
M.C.B. - MAIN CIRCUIT BREAKER
M.L.O. - MAIN LUGS ONLY
MAINT. - MAINTENANCE
MH. - METAL HALIDE
MFG. - MANUFACTURER
MCM - THOUSAND CIRCULAR MILS
MOCP - MINIMUM OVERCURRENT
PROTECTION
MIN - MINIMUM
MCP - MOTOR CIRCUIT PROTECTOR
MTD - MOUNTED
N. - NEUTRAL
NEC - NATIONAL ELECTRIC CODE
NEMA - NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NFPA - NATIONAL FIRE PROTECTION ASSOCIATION
N.P.T. - NATIONAL PIPE THREAD
NF - NON FUSED
N.C. - NORMALLY CLOSED
N.O. - NORMALLY OPEN
NIC. - NOT IN CONTRACT
NO. - NUMBER
O.L. - OVERLOAD
% - PERCENT
∅ - PHASE
P. - POLE
P.T. - POTENTIAL TRANSFORMER
PB - PULLBOX
PNL - PANEL
PR - PAIR
PRI. - PRIMARY
R - REMOVED
RECEP - RECEPTACLE
REL - RELOCATE
RPM - REVOLUTIONS PER MINUTE
R.S. - RAPID START
SCA - SHORT CIRCUIT AMPS
SEC. - SECONDARY
S/N - SOLID NEUTRAL
SPST - SINGLE POLE SINGLE THROW
SF - SQUARE FOOT
SW. - SWITCH
SWBD - SWITCHBOARD
SYS. - SYSTEM
THHN - THWN NYLON JACKETED WIRE
TTB - TELEPHONE TERMINAL BOARD
TTC - TELEPHONE TERMINAL CABINET
TV - TELEVISION
TVTC - TELEVISION TERMINAL CABINET
TVEC - TELEVISION EQUIP. CABINET
TYP - TYPICAL TEMP. - TEMPERATURE
U.L. - UNDERWRITERS' LABORATORIES
VFD - VARIABLE FREQUENCY DRIVE
VHF - VERY HIGH FREQUENCY
VHO - VERY HIGH OUTPUT
V - VOLT
VA - VOLT AMPERES
VOL. - VOLUME
W - WIRE
W.G. - WIRE GUARD
W.P. - WEATHERPROOF
XFMR - TRANSFORMER
Y - WYE
YD. - YARD
YR. - YEAR
3R - RAINPROOF
4X - STAINLESS STEEL DUSTIGHT,
WATERTIGHT
ELECTRICAL ABBREVIATIONS
MPE JOB #:
ENG. BUS. No. EB-0005096
CERT. OF AUTH. No. 5096
PHONE (239) 332-1187
12437 Brantley Commons Fort Myers, FL 33907
SCOTT LA IN
No 69099P R
STATE OF
E
O F
E S
S
ION A L E N
G
IN
E E
R
NSECIL
F L O R I DA
PROJECT NO:
DATE:
PHASE:
ISSUED FOR
SEAL:
GRACE HEBERT CURTIS ARCHITECTS, LLC
SHEET NUMBER
© THIS SET OF DOCUMENTS INCLUSIVE OF
DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT
BE COPIED, SCANNED, NOR ELECTRONICALLY
DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT
THE EXPRESSED WRITTEN CONSENT OF GRACE
HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,
ELECTRONIC PLAN SERVICE (INTERNET PLAN
SERVICE), NOR REPRODUCTION COMPANY SHALL BE
PERMITTED TO POST THESE DOCUMENTS WITHOUT
THE EXPRESSED WRITTEN CONSENT OF THE
ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.
2024-118
/1
/2
:3
:2
P
M
A u to d e s k D o c s /W a re h o u s e
C o n v e rt t o P a rk s
R e c D e p a rt m e n t/
-1
E le c tr ic a l M o d e l_
O p ti o n O n e
R e v it
B
IM
.r v t
E001
GENERAL NOTES, LEGEND,
ABBREVIATIONS & SHEET
INDEX
40-24105
W A
R E
H O
U S
E C
O N
V E
R T
T O
P A
R K
S
R E
C D
E P
T
C
IT
Y O
F F
O R
T M
Y E
R S
06/19/2025
PERMIT DOCUMENTS
M
IC
H
IG
A
N A
V E
N U
E F
O R
T M
Y E
R S
F
L O
R
ID
A
1. NO MULTI-WIRE BRANCH CIRCUITS ARE TO BE USED. EACH CIRCUIT IS TO HAVE SEPARATE INDIVIDUAL NEUTRAL.
2. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 0-100 FEET, ARE TO HAVE #12 MINIMUM BRANCH CIRCUIT WIRING
THROUGHOUT CIRCUIT. (CONDUIT SIZE PER SPECIFICATION AND NEC).
3. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 101-125 FEET, ARE TO HAVE #10 MINIMUM BRANCH CIRCUIT WIRING HOMERUN (3/4"C.) FROM PANEL CIRCUIT BREAKER TO FIRST DEVICE AND #12 BRANCH CIRCUIT WIRING THROUGHOUT THE REMAINDER OF THE CIRCUIT. (CONDUIT SIZE PER SPECIFICATION AND NEC). NOT LESS THAN THE FIRST 75 FEET OF COMBINED HOMERUN AND BRANCH CIRCUIT TO BE MINIMUM #10 WIRE (3/4"C).
4. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 126-160 FEET, ARE TO HAVE #10 MINIMUM BRANCH CIRCUIT
WIRING THROUGHOUT CIRCUIT (3/4”C).\
5. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 161-205 FEET, ARE TO HAVE #8 MINIMUM BRANCH CIRCUIT WIRING HOMERUN (1"C.) FROM PANEL CIRCUIT BREAKER TO FIRST DEVICE AND #10 BRANCH CIRCUIT WIRING THROUGHOUT THE REMAINDER OF THE CIRCUIT (3/4"C.). NOT LESS THAN THE FIRST 125 FEET OF COMBINED HOMERUN AND BRANCH
CIRCUIT TO BE MINIMUM #8 WIRE (1"C.)
6. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 206-230 FEET, ARE TO HAVE #8 MINIMUM BRANCH CIRCUIT WIRING
THROUGHOUT CIRCUIT (1"C.).
7. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 231-250 FEET, ARE TO HAVE #6 MINIMUM BRANCH CIRCUIT WIRING HOMERUN (1-1/4"C.) FROM PANEL CIRCUIT BREAKER TO FIRST DEVICE AND #10 BRANCH CIRCUIT WIRING THROUGHOUT THE REMAINDER OF THE CIRCUIT (3/4"C.). NOT LESS THAN THE FIRST 175 FEET OF COMBINED HOMERUN AND
BRANCH CIRCUIT TO BE MINIMUM #6 WIRE (1-1/4"C.).
8. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 251-325 FEET, ARE TO HAVE #6 MINIMUM BRANCH CIRCUIT WIRING HOMERUN (1-1/4"C.) FROM PANEL CIRCUIT BREAKER TO FIRST DEVICE AND #8 BRANCH CIRCUIT WIRING THROUGHOUT THE REMAINDER OF THE CIRCUIT (1"C.). NOT LESS THAN THE FIRST 250 FEET OF COMBINED HOMERUN AND
BRANCH CIRCUIT TO BE MINIMUM #6 WIRE (1-1/4"C.).
9. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 326-370 FEET FROM THE PANEL, ARE TO HAVE #6 MINIMUM
BRANCH CIRCUIT WIRING THROUGHOUT CIRCUIT (1-1/4"C.).
10. 120 VOLT BRANCH CIRCUITS SERVING RECEPTACLES FOR COMPUTER WORKSTATIONS (IE OUTLETS WITH 'C' DESIGNATION) SHALL HAVE MINIMUM CONDUCTOR SIZE OF #10. #10 MINIMUM CONDUCTOR SIZE SHALL BE INCREASED IF
REQUIRED TO COMPLY WITH GENERAL NOTES ABOVE.
11. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF FIXTURES.
12. COORDINATE EXACT LOCATION OF LIGHTING FIXTURES IN ALL MECH. ROOMS, AND SPACES WITH NO CEILING (EXPOSED STRUCTURE AREAS), SPACES, ETC., WITH DUCTWORK INSTALLER PRIOR TO ROUGH-IN. LOCATE BELOW
DUCTWORK (8'-0" A.F.F. MINIMUM) CENTERED IN ROOM AS MUCH AS FEASIBLE.
13. COORDINATE EXACT INSTALLATION REQUIREMENTS OF OUTLETS IN MILLWORK WITH ARCHITECTURAL DRAWINGS AND ACCEPTED MILLWORK SHOP DRAWINGS.
14. VERIFY EXACT LOCATION OF ALL MECH. EQUIP. INCLUDING WALL SWITCHES, T'STATS, ETC. WITH MECH. CONTRACTOR AND MECH. DRAWINGS.
15. REFER TO MECHANICAL EQUIPMENT SCHEDULE, FOR RESPECTIVE CONDUIT/CONDUCTORS, DISCONNECTS, MISC. EQUIPMENT REQUIRED FOR ALL MECHANICAL AND PLUMBING EQUIPMENT. REFER TO PANEL SCHEDULES FOR
CIRCUITS NUMBERS OF CIRCUITS FOR MECHANICAL AND PLUMBING EQUIPMENT.
16. VISIT AND CAREFULLY EXAMINE THOSE PORTIONS OF THE BUILDING AND SITE AFFECTED BY THIS WORK BEFORE SUBMITTING PROPOSALS, SO AS TO BECOME FAMILIAR WITH EXISTING CONDITIONS AND DIFFICULTIES THAT WILL AFFECT EXECUTION OF THE WORK. SUBMISSION OF A PROPOSAL WILL BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE AND LATER CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE OF
DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED.
17. READ SPECIFICATIONS.
18. SEE RISER DIAGRAMS AND BUILDING PLANS.
19. ALL EMPTY CONDUITS ARE TO HAVE PULL-STRINGS PROVIDED IN THEM.
20. EXISTING CONDITIONS AND UTILITIES INDICATED ARE TAKEN FROM EXISTING CONSTRUCTION DOCUMENTS, VARIOUS SURVEYS, AND FIELD INVESTIGATIONS. IT IS TO BE UNDERSTOOD THAT UNFORESEEN CONDITIONS PROBABLY EXIST AND NEW WORK MAY NOT BE FIELD LOCATED EXACTLY AS SHOWN ON THE DRAWINGS. COOPERATION WITH OTHER TRADES IN ROUTING AND/OR BURIAL DEPTHS AS DETERMINED DURING CONSTRUCTION AND AS DIRECTED BY THE ARCHITECT/ENGINEER MAY BE NECESSARY AND IT IS INTENDED THAT SUCH DEVIATIONS SHALL BE CONSIDERED A PART OF THIS CONTRACT. IT IS ALSO UNDERSTOOD THAT THE PLANS ARE NOT COMPLETELY TO SCALE. THIS CONTRACTOR IS TO FIELD VERIFY DIMENSIONS OF ALL SITE UTILITIES, ETC., PRIOR TO BID AND INCLUDE ANY DEVIATIONS IN THE CONTRACT.
21. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO LOCATE ALL EXISTING UTILITIES WHETHER SHOWN ON PLANS OR NOT AND TO PROTECT THEM FROM DAMAGE. THE CONTRACTOR SHALL BEAR ALL EXPENSE FOR REPAIR OR REPLACEMENT OF UTILITIES OR OTHER PROPERTY DAMAGED BY OPERATIONS IN CONJUNCTION WITH THE COMPLETION OF THIS WORK. THE CONTRACTOR SHALL LOCATE ALL UTILITIES (BOTH KNOWN AND UNKNOWN) IN AREA OF WORK PRIOR TO EXCAVATION WITH THE USE OF ELECTRONIC LOCATOR/TRACER DEVICES AND EQUIPMENT SUITABLE FOR SUCH USE. REFLECT LOCATED UTILITIES ON AS-BUILT DOCUMENTS.
22. REMOVE EXISTING POWER, LIGHTING, SYSTEMS, MATERIAL AND EQUIPMENT WHICH ARE MADE OBSOLETE OR WHICH INTERFERE WITH THE CONSTRUCTION OF THE PROJECT.
23. REINSTALL ANY SUCH POWER, LIGHTING, SYSTEMS, MATERIALS AND EQUIPMENT WHICH ARE REQUIRED TO REMAIN ACTIVE FOR THE FACILITY TO BE FULLY FUNCTIONAL.
24. REMOVE ALL EXISTING ELECTRICAL IN AREAS OF REMODELING UNLESS SPECIFICALLY NOTED OTHERWISE, OR UNLESS REQUIRED FOR CONTINUITY OF CIRCUITS IN AREAS NOT IN REMODEL AREA.
25. ALL EXISTING ELECTRICAL IS NOT SHOWN. IT IS THE CONTRACTORS RESPONSIBILITY TO BECOME FAMILIAR WITH ALL EXISTING CONDITIONS PRIOR TO BID, AND INCLUDE IN HIS BID THE REMOVAL OF ALL ELECTRICAL EQUIPMENT, WIRE, CONDUIT, DEVICES, FIXTURES, ETC. THAT IS NOT BEING REUSED, BACK TO ITS SOURCE.
26. ALL RECEPTACLES, DEVICES AND EQUIPMENT NOT SHOWN, AND IN AREAS OUTSIDE OF REMODELING SHALL REMAIN ACTIVE UNLESS OTHERWISE NOTED. FURNISH AND INSTALL ACCESSIBLE JUNCTION BOXES AND REWORK EXISTING CIRCUITS AS REQUIRED TO MAINTAIN CIRCUIT CONTINUITY TO RECEPTACLES, DEVICES AND EQUIPMENT REMAINING.
27. ALL CONDUIT TO BE CONCEALED UNLESS IMPOSSIBLE DUE TO EXISTING CONDITIONS (I.E. EXPOSED CEILINGS, BUILDING EXTERIOR WALL RUNS, IMPOSSIBLE UNDERGROUND RUNS). CONCEAL ALL CONDUITS ABOVE CEILINGS OR IN
WALL/COUNTERS.
28. ALL NEW DEVICES TO BE FLUSH MOUNTED UNLESS SPECIFICALLY NOTED OTHERWISE.
GENERAL NOTES:
CODE REFERENCE:
NATIONAL ELECTRICAL CODE: 2020
NO. DESCRIPTION DATE
LIGHT FIXTURE SCHEDULE
TYPE DESCRIPTION BASIS OF DESIGN EQUAL EQUAL VOLTS
A2
RECESSED 2X2' LED
FLAT PANEL
METALUX:
22CGTS-L3C3
DAYBRITE:
2SBP2035L8DS-2-UNV-DIM
ELITE:
22 FPL1 LED 2000/3000/400L-
DIM10-MVOLT-35K/40K/50K-85
4000 LUMENS
4000K 33W
A2E
RECESSED 2X2' LED
FLAT PANEL,
EMERGENCY BATTERY
PACK
METALUX:
22CGTS-L3C3-EL14W
DAYBRITE:
2SBP2035L8DS-2-UNV-
DIM-FPEMLED10RM
ELITE:
22 FPL1 LED 2000/3000/400L-
DIM10-MVOLT-35K/40K/50K-85-
0-EMG-LED-20W
4000 LUMENS
4000K 33W
B1 HIGH BAY LED
METALUX:
SPHB-24-SE-M-UNV-L750-CD
DAYBRITE:
FCY-1525L-8CST-UNV-DIM
ELITE:
CB2-CPA-24000/27000/30000L-
DIM10-MVOLT-MD-
30K/35K/40K/50K-85
24000 LUMENS
4000K 159W
B1E
HIGH BAY LED,
EMERGENCY BATTERY
PACK
METALUX:
SPHB-24-SE-M-UNV-L750-
EL20WHV-CD
DAYBRITE:
FCY-1525L-8CST-UNV-DIM-EM
ELITE:
CB2-CPA-24000/27000/30000L-
DIM10-MVOLT-MD-
30K/35K/40K/50K-85-
EMG-LED-G4-120-347V-CP-25W-HV
24000 LUMENS
4000K 159W
C1
4' LED INDUSTRIAL
STRIP, WET LOCATION
LISTED
METALUX:
4SNX-33SL-LW-UNV-L840-CD-1-U
DAYBRITE:
FSS-4-30L-840-UNV-DIM
ELITE:
4-OC4-LED-
3000/4000/5000L-DIM10-MVOLT-
35K/40K/50K-85
3000 LUMENS
4000K 22W
D1
4" RECESSED LED
DOWNLIGHT
HALO COMMERICAL:
HC420D010-HM405258400
-41MDWF
LIGHTOLIER:
M4R-DL-25-9CS-M-WH-Z10U
ELITE:
HH4-1000/1500/2000L-DIM10-
MVOLT-27/30/35/40/50K-
HH4501-W-WH-MWD-90+
2000 LUMENS
4000K 20W
EM
INDOOR EMERGENCY
BATTERY FIXTURE
SURE-LITES:
APEL SERIES
BEGHELLI:
PEH1
COMPASS:
CU2
120 LED
W1
TYPE FOUR WALL
PACK, WET LOCATION
RAYON LIGHTING:
T652LEDB-20W-UNV-40K-T4-BZ-EM
GARDCO:
GWS-A02-740-T4M-UNV-BZ
BEACON:
VPW2-48L-20-4K7-4F-UNV-DBS
2600 LUMENS
4000K 20W
W1E
TYPE FOUR WALL
PACK, WET LOCATION
WITH BACK UP
BATTERY.
RAYON LIGHTING:
T652LEDB-20W-UNV-40K-T4-BZ-EM
GARDCO:
GWS-A02-740-T4M-UNV-EM-BZ
BEACON:
VPW2-48L-20-4K7-4F-UNV-DBS
2600 LUMENS
4000K 20W
W2
TYPE TWO WALL PACK,
WET LOCATION
RAYON LIGHTING:
T652LEDB-10W-UNV-40K-T2-BZ
GARDCO:
GWS-A01-740-T2M-UNV-BZ
BEACON:
VPW2-48L-15-4K7-2-UNV-DBS
1900 LUMENS
4000K 10W
W2E
TYPE TWO WALL PACK,
WET LOCATION WITH
BACK UP BATTERY.
RAYON LIGHTING:
T652LEDB-10W-UNV-40K-T2-BZ-EM
GARDCO:
GWS-A01-740-T2M-UNV-EM-BZ
BEACON:
VPW2-48L-15-4K7-2-UNV-DBS-E
1900 LUMENS
4000K 10W
X1
EXIT SIGN, RED
LETTERS, BATTERY
BACK-UP
SURE-LITES:
APX7RG
BEGHELLI:
EPX-SA
COMPASS:
CERG
120 LED
SL1
POLE MOUNTED LED
SITE FIXTURE, TYPE V
FORWARD THROW
DISTRIBUTION WITH
SENSOR FOR DIMMING
MOTION, 25' DIRECT
BURIAL CONCRETE
POLE
MCGRAW EDISON:
GALN-SA1B-840-U-T4FT-
FINISH-HSS-WLS4BK
GARDCO:
OPF-S-PO2-840-T4M-AR1-UNV-BL50-
L2-BK
BEACON:
VP-1-160L-35-4K8-4F-UNV-MAF-
FINISH-SHLD-1-HSS-90-B-
FINISH-NXWS-40F
3500 LUMENS
4000K 44W
SL2
POLE MOUNTED LED
SITE FIXTURE, TYPE V
FORWARD THROW
DISTRIBUTION WITH
SENSOR FOR DIMMING
MOTION, 15' DIRECT
BURIAL CONCRETE
POLE
MCGRAW EDISON:
GALN-SA1B-840-U-T4FT-
FINISH-HSS-WLS2BK
GARDCO:
OPF-S-PO2-840-T4M-AR1-UNV-BL50-
L2-BK
BEACON:
VP-1-160L-35-4K8-4F-UNV-MAF-
FINISH-SHLD-1-HSS-90-B-FINISH-
NXWS-16F
3500 LUMENS
4000K 44W
SL3
POLE MOUNTED LED
SITE FIXTURE, 90 SPILL
LIGHT ELIMINATOR ON
RIGHT SIDE WITH
SENSOR FOR DIMMING
MOTION, 15' DIRECT
BURIAL CONCRETE
POLE
MCGRAW EDISON:
GALN-SA1B-840-U-SLR-
FINISH-HSS-WLS2BK
INTENSE:
GTM-L6-35-DIM-FINISH-FF
BEACON:
VP-1-160L-35-4K8-4F-UNV-MAF-
FINISH-SHLD-1-HSS-90-B-FINISH-
NXWS-16F
4400 LUMENS
3500K 45W
LIGHTING FIXTURE SCHEDULE GENERAL NOTES:
(1) CONTRACTOR SHALL CAREFULLY COORDINATE THE LIGHTING FIXTURE TRIM TYPES WITH THE TYPE OF CEILING WHERE THE LIGHTING FIXTURES ARE TO BE INSTALLED. MODIFY FIXTURE CATALOG NUMBER AS REQUIRED TO COORDINATE FIXTURE WITH CEILING.
(2) CONTRACTOR, AT HIS OPTION, MAY USE A U.L. LISTED FLEXIBLE WIRING SYSTEM FOR LIGHTING FIXTURE BRANCH CIRCUITRY ABOVE ACCESSIBLE LAY-IN CEILINGS.
ALL HOMERUNS, CONNECTIONS TO LIGHT SWITCHES, AND BRANCH CIRCUITRY FOR ALL OTHER CEILING CONDITIONS SHALL BE IN A CONVENTIONAL RACEWAY SYSTEM
PER SPECIFICATIONS.
(3) WHEN FIXTURE MODEL NUMBER DIFFERS FROM FIXTURE DESCRIPTION, CONTRACTOR IS TO SUBMIT RFI REQUESTING CLARIFICATION PRIOR TO BID, PRIOR TO SHOP DRAWING SUBMITTAL AND PRIOR TO ORDERING OF FIXTURE. WHERE CONTRACTOR DOES NOT REQUEST CLARIFICATION PRIOR TO BID, CONTRACTOR SHALL PROVIDE THE MOST EXPENSIVE OPTION BETWEEN A FIXTURE THAT MATCHES THE DESCRIPTION AND A FIXTURE THAT MATCHES THE MODEL NUMBER. AFTER BID, CONTRACTOR SHALL SUBMIT RFI REQUESTING CLARIFICATION SO PROPER FIXTURE GETS SUBMITTED, PROVIDED AND INSTALLED.
TYPICAL INDICATING DEVICES
TYPICAL INITIATING DEVICES
TYPICAL CONTROL RELAYS
1ST FLOOR
SOUTH BUILDING FIRE ALARM RISER DIAGRAM
NTS
LOCAL FACP
FIRE ALARM
CONTROL PANEL
DEDICATED TELEPHONE CONNECTION
FOR THIRD PARTY NOTIFICATION
SPRINKLER FLOW & TAMPER
SWITCHES
PROVIDE BATTERY
CALCULATION OF NEW DEVICES
DIALER
F F
F
F
R R FS TS
FIRE ALARM
TERMINAL
CABINET
SITE SPRINKLER FLOW & TAMPER
SWITCHES FS TS
FA-NEW
PROVIDE SURGE ON ALL INCOMING
EXTERRIOR COPPER CABLES
F
F
F
AR
TYPICAL INDICATING DEVICES
TYPICAL INITIATING DEVICES
TYPICAL CONTROL RELAYS
1ST FLOOR
NORTH BUILDING FIRE ALARM RISER DIAGRAM
NTS
SPRINKLER FLOW & TAMPER
SWITCHES
PROVIDE BATTERY
CALCULATION OF NEW DEVICES
F F
F
F
R
FS TS
FA-NEW
F
F
F
2ND FLOOR
CONNECT TO FIRE ALARM VIA
LOCKABLE 20A CB.
CONNECT TO FIRE ALARM VIA
LOCKABLE 20A CB.
FIRE ALARM
TERMINAL
CABINET
LOCAL FACP
FIRE ALARM
CONTROL PANEL
DEDICATED TELEPHONE CONNECTION
FOR THIRD PARTY NOTIFICATION
DIALER
TYPICAL INDICATING DEVICES
TYPICAL INITIATING DEVICES
F
F
F
TYPICAL CONTROL RELAYS RRAR
CONNECT TO FIRE ALARM VIA
LOCKABLE 20A CB.
A - AMERAGE
A/C - AIR CONDITIONING
A.C. - ALTERNATING CURRENT
A/E - ARCHITECT/ENGINEER (OR ENGINEER
WHEN ARCHITECT NOT APPLICABLE)
AFD - ADJUSTABLE FREQUENCY DRIVE
AFF - ABOVE FINISHED FLOOR
AFG - ABOVE FINISHED GRADE
AHU - AIR HANDLER UNIT
AIC - AMPS INTERRUPTING CAPACITY
AL - ALUMINUM
ALT - ALTERNATE
ANSI - AMERICAN NATIONAL STANDARDS INSTITUTE
AWG - AMERICAN WIRE GAUGE
B.C. - BARE COPPER
BLDG - BUILDING
BRKR - BREAKER
C. - CONDUIT
C.B. - CIRCUIT BREAKER
CD. - CANDELA
CKT. - CIRCUIT
C/L - CENTER LINE
CLG. - CEILING
COMP. - COMPRESSOR
CONN. - CONNECTION
COND. - CONDENSER
CONT. - CONTINUOUS
C.R.I. - COLOR RENDERING INDEX
C.T. - CURRENT TRANSFORMER
CU. - COPPER
C.U. - COMPRESSOR CONDENSER UNIT
CW - COLD WATER
D - DEMO
D.B. - DIRECT BURIAL
D.W. - DIRECT CURRENT
C. - DISCONNECT
DPST - DOUBLE POLE SINGLE THROW
DWG - DRAWING
EC - ELECTRICAL CONTRACTOR
(OR GENERAL CONTRACTOR)
DN. - ELEVATOR
EMT - ELECTRIC METALLIC TUBING
EPA - ENVIRONMENTAL PROTECTION AGENCY
EQUIP. - EQUIPMENT
EST - ESTIMATE
ETR - EXISTING TO REMAIN
FAAP - FIRE ALARM ANNUNCIATOR PANEL
FACP - FIRE ALARM CONTROL PANEL
FATC - FIRE ALARM TERMINAL CABINET
FCCP - FIRE ALARM COMMAND CENTER PANEL
FLA - FULL LOAD AMPERES
FT. - FEET
FLR - FLOOR
F.C. - FOOTCANDLES
G - GROUND FAULT CIRCUIT INTERRUPTER
GAL. - GALLON
GALV. - GALVANIZED
GPH - GALLONS PER HOUR
GPM - GALLONS PER MINUTE
GFI - GROUND FAULT INTERRUPTING
GRS - GALVANIZED RIGID STEEL CONDUIT
GND. - GROUND
HTG - HEATERS
HT - HEIGHT
HZ - HERTZ (CYCLES)
H.P.F. - HIGH POWER FACTOR
HP. - HORSEPOWER
HR. - HOUR
H.S. - HEAT STRIP
IMC - INTERMEDIATE METALLIC CONDUIT
IN. - INCHES
J.B. - JUNCTION BOX
KVA - KILOVOLT AMPERE
KW - KILOWATTS
KWH - KILOWATT HOUR
K - KELVIN
L.L.D. - LAMP LUMEN DEPRECIATION
LED - LIGHT EMITTING DIODE
LIU - LIGHT INTERFACE UNIT
LT. - LIGHT
LTG. - LIGHTING
LTS. - LIGHTS
L.P.F. - LOW POWER FACTOR
M.C.B. - MAIN CIRCUIT BREAKER
M.L.O. - MAIN LUGS ONLY
MAINT. - MAINTENANCE
MH. - METAL HALIDE
MFG. - MANUFACTURER
MCM - THOUSAND CIRCULAR MILS
MOCP - MINIMUM OVERCURRENT
PROTECTION
MIN - MINIMUM
MCP - MOTOR CIRCUIT PROTECTOR
MTD - MOUNTED
N. - NEUTRAL
NEC - NATIONAL ELECTRIC CODE
NEMA - NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NFPA - NATIONAL FIRE PROTECTION ASSOCIATION
N.P.T. - NATIONAL PIPE THREAD
NF - NON FUSED
N.C. - NORMALLY CLOSED
N.O. - NORMALLY OPEN
NIC. - NOT IN CONTRACT
NO. - NUMBER
O.L. - OVERLOAD
% - PERCENT
∅ - PHASE
P. - POLE
P.T. - POTENTIAL TRANSFORMER
PB - PULLBOX
PNL - PANEL
PR - PAIR
PRI. - PRIMARY
R - REMOVED
RECEP - RECEPTACLE
REL - RELOCATE
RPM - REVOLUTIONS PER MINUTE
R.S. - RAPID START
SCA - SHORT CIRCUIT AMPS
SEC. - SECONDARY
S/N - SOLID NEUTRAL
SPST - SINGLE POLE SINGLE THROW
SF - SQUARE FOOT
SW. - SWITCH
SWBD - SWITCHBOARD
SYS. - SYSTEM
THHN - THWN NYLON JACKETED WIRE
TTB - TELEPHONE TERMINAL BOARD
TTC - TELEPHONE TERMINAL CABINET
TV - TELEVISION
TVTC - TELEVISION TERMINAL CABINET
TVEC - TELEVISION EQUIP. CABINET
TYP - TYPICAL TEMP. - TEMPERATURE
U.L. - UNDERWRITERS' LABORATORIES
VFD - VARIABLE FREQUENCY DRIVE
VHF - VERY HIGH FREQUENCY
VHO - VERY HIGH OUTPUT
V - VOLT
VA - VOLT AMPERES
VOL. - VOLUME
W - WIRE
W.G. - WIRE GUARD
W.P. - WEATHERPROOF
XFMR - TRANSFORMER
Y - WYE
YD. - YARD
YR. - YEAR
3R - RAINPROOF
4X - STAINLESS STEEL DUSTIGHT,
WATERTIGHT
ELECTRICAL ABBREVIATIONS
MPE JOB #:
ENG. BUS. No. EB-0005096
CERT. OF AUTH. No. 5096
PHONE (239) 332-1187
12437 Brantley Commons Fort Myers, FL 33907
SCOTT LA IN
No 69099P R
STATE OF
E
O F
E S
S
ION A L E N
G
IN
E E
R
NSECIL
F L O R I DA
PROJECT NO:
DATE:
PHASE:
ISSUED FOR
SEAL:
GRACE HEBERT CURTIS ARCHITECTS, LLC
SHEET NUMBER
© THIS SET OF DOCUMENTS INCLUSIVE OF
DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT
BE COPIED, SCANNED, NOR ELECTRONICALLY
DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT
THE EXPRESSED WRITTEN CONSENT OF GRACE
HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,
ELECTRONIC PLAN SERVICE (INTERNET PLAN
SERVICE), NOR REPRODUCTION COMPANY SHALL BE
PERMITTED TO POST THESE DOCUMENTS WITHOUT
THE EXPRESSED WRITTEN CONSENT OF THE
ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.
2024-118
/1
/2
:3
:5
P
M
A u to d e s k D o c s /W a re h o u s e C o n v e rt t o
P a rk s
R e c D e p a rt m e n t/
-1
E le c tr ic a l M o d e l_
O p ti o n T w o
R e v it
B
IM
.r v t
E001-2
GENERAL NOTES, LEGEND,
ABBREVIATIONS & SHEET
INDEX
40-24105
W A
R E
H O
U S
E C
O N
V E
R T
T O
P A
R K
S
R E
C D
E P
T
C
IT
Y O
F F
O R
T M
Y E
R S
06/19/2025
PERMIT DOCUMENTS
M
IC
H
IG
A
N A
V E
N U
E F
O R
T M
Y E
R S
F
L O
R
ID
A
1. NO MULTI-WIRE BRANCH CIRCUITS ARE TO BE USED. EACH CIRCUIT IS TO HAVE SEPARATE INDIVIDUAL NEUTRAL.
2. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 0-100 FEET, ARE TO HAVE #12 MINIMUM BRANCH CIRCUIT WIRING
THROUGHOUT CIRCUIT. (CONDUIT SIZE PER SPECIFICATION AND NEC).
3. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 101-125 FEET, ARE TO HAVE #10 MINIMUM BRANCH CIRCUIT WIRING HOMERUN (3/4"C.) FROM PANEL CIRCUIT BREAKER TO FIRST DEVICE AND #12 BRANCH CIRCUIT WIRING THROUGHOUT THE REMAINDER OF THE CIRCUIT. (CONDUIT SIZE PER SPECIFICATION AND NEC). NOT LESS THAN THE FIRST 75 FEET OF COMBINED HOMERUN AND BRANCH CIRCUIT TO BE MINIMUM #10 WIRE (3/4"C).
4. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 126-160 FEET, ARE TO HAVE #10 MINIMUM BRANCH CIRCUIT
WIRING THROUGHOUT CIRCUIT (3/4”C).\
5. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 161-205 FEET, ARE TO HAVE #8 MINIMUM BRANCH CIRCUIT WIRING HOMERUN (1"C.) FROM PANEL CIRCUIT BREAKER TO FIRST DEVICE AND #10 BRANCH CIRCUIT WIRING THROUGHOUT THE REMAINDER OF THE CIRCUIT (3/4"C.). NOT LESS THAN THE FIRST 125 FEET OF COMBINED HOMERUN AND BRANCH
CIRCUIT TO BE MINIMUM #8 WIRE (1"C.)
6. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 206-230 FEET, ARE TO HAVE #8 MINIMUM BRANCH CIRCUIT WIRING
THROUGHOUT CIRCUIT (1"C.).
7. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 231-250 FEET, ARE TO HAVE #6 MINIMUM BRANCH CIRCUIT WIRING HOMERUN (1-1/4"C.) FROM PANEL CIRCUIT BREAKER TO FIRST DEVICE AND #10 BRANCH CIRCUIT WIRING THROUGHOUT THE REMAINDER OF THE CIRCUIT (3/4"C.). NOT LESS THAN THE FIRST 175 FEET OF COMBINED HOMERUN AND
BRANCH CIRCUIT TO BE MINIMUM #6 WIRE (1-1/4"C.).
8. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 251-325 FEET, ARE TO HAVE #6 MINIMUM BRANCH CIRCUIT WIRING HOMERUN (1-1/4"C.) FROM PANEL CIRCUIT BREAKER TO FIRST DEVICE AND #8 BRANCH CIRCUIT WIRING THROUGHOUT THE REMAINDER OF THE CIRCUIT (1"C.). NOT LESS THAN THE FIRST 250 FEET OF COMBINED HOMERUN AND
BRANCH CIRCUIT TO BE MINIMUM #6 WIRE (1-1/4"C.).
9. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 326-370 FEET FROM THE PANEL, ARE TO HAVE #6 MINIMUM
BRANCH CIRCUIT WIRING THROUGHOUT CIRCUIT (1-1/4"C.).
10. 120 VOLT BRANCH CIRCUITS SERVING RECEPTACLES FOR COMPUTER WORKSTATIONS (IE OUTLETS WITH 'C' DESIGNATION) SHALL HAVE MINIMUM CONDUCTOR SIZE OF #10. #10 MINIMUM CONDUCTOR SIZE SHALL BE INCREASED IF
REQUIRED TO COMPLY WITH GENERAL NOTES ABOVE.
11. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF FIXTURES.
12. COORDINATE EXACT LOCATION OF LIGHTING FIXTURES IN ALL MECH. ROOMS, AND SPACES WITH NO CEILING (EXPOSED STRUCTURE AREAS), SPACES, ETC., WITH DUCTWORK INSTALLER PRIOR TO ROUGH-IN. LOCATE BELOW
DUCTWORK (8'-0" A.F.F. MINIMUM) CENTERED IN ROOM AS MUCH AS FEASIBLE.
13. COORDINATE EXACT INSTALLATION REQUIREMENTS OF OUTLETS IN MILLWORK WITH ARCHITECTURAL DRAWINGS AND ACCEPTED MILLWORK SHOP DRAWINGS.
14. VERIFY EXACT LOCATION OF ALL MECH. EQUIP. INCLUDING WALL SWITCHES, T'STATS, ETC. WITH MECH. CONTRACTOR AND MECH. DRAWINGS.
15. REFER TO MECHANICAL EQUIPMENT SCHEDULE, FOR RESPECTIVE CONDUIT/CONDUCTORS, DISCONNECTS, MISC. EQUIPMENT REQUIRED FOR ALL MECHANICAL AND PLUMBING EQUIPMENT. REFER TO PANEL SCHEDULES FOR
CIRCUITS NUMBERS OF CIRCUITS FOR MECHANICAL AND PLUMBING EQUIPMENT.
16. VISIT AND CAREFULLY EXAMINE THOSE PORTIONS OF THE BUILDING AND SITE AFFECTED BY THIS WORK BEFORE SUBMITTING PROPOSALS, SO AS TO BECOME FAMILIAR WITH EXISTING CONDITIONS AND DIFFICULTIES THAT WILL AFFECT EXECUTION OF THE WORK. SUBMISSION OF A PROPOSAL WILL BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE AND LATER CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE OF
DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED.
17. READ SPECIFICATIONS.
18. SEE RISER DIAGRAMS AND BUILDING PLANS.
19. ALL EMPTY CONDUITS ARE TO HAVE PULL-STRINGS PROVIDED IN THEM.
20. EXISTING CONDITIONS AND UTILITIES INDICATED ARE TAKEN FROM EXISTING CONSTRUCTION DOCUMENTS, VARIOUS SURVEYS, AND FIELD INVESTIGATIONS. IT IS TO BE UNDERSTOOD THAT UNFORESEEN CONDITIONS PROBABLY EXIST AND NEW WORK MAY NOT BE FIELD LOCATED EXACTLY AS SHOWN ON THE DRAWINGS. COOPERATION WITH OTHER TRADES IN ROUTING AND/OR BURIAL DEPTHS AS DETERMINED DURING CONSTRUCTION AND AS DIRECTED BY THE ARCHITECT/ENGINEER MAY BE NECESSARY AND IT IS INTENDED THAT SUCH DEVIATIONS SHALL BE CONSIDERED A PART OF THIS CONTRACT. IT IS ALSO UNDERSTOOD THAT THE PLANS ARE NOT COMPLETELY TO SCALE. THIS CONTRACTOR IS TO FIELD VERIFY DIMENSIONS OF ALL SITE UTILITIES, ETC., PRIOR TO BID AND INCLUDE ANY DEVIATIONS IN THE CONTRACT.
21. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO LOCATE ALL EXISTING UTILITIES WHETHER SHOWN ON PLANS OR NOT AND TO PROTECT THEM FROM DAMAGE. THE CONTRACTOR SHALL BEAR ALL EXPENSE FOR REPAIR OR REPLACEMENT OF UTILITIES OR OTHER PROPERTY DAMAGED BY OPERATIONS IN CONJUNCTION WITH THE COMPLETION OF THIS WORK. THE CONTRACTOR SHALL LOCATE ALL UTILITIES (BOTH KNOWN AND UNKNOWN) IN AREA OF WORK PRIOR TO EXCAVATION WITH THE USE OF ELECTRONIC LOCATOR/TRACER DEVICES AND EQUIPMENT SUITABLE FOR SUCH USE. REFLECT LOCATED UTILITIES ON AS-BUILT DOCUMENTS.
22. REMOVE EXISTING POWER, LIGHTING, SYSTEMS, MATERIAL AND EQUIPMENT WHICH ARE MADE OBSOLETE OR WHICH INTERFERE WITH THE CONSTRUCTION OF THE PROJECT.
23. REINSTALL ANY SUCH POWER, LIGHTING, SYSTEMS, MATERIALS AND EQUIPMENT WHICH ARE REQUIRED TO REMAIN ACTIVE FOR THE FACILITY TO BE FULLY FUNCTIONAL.
24. REMOVE ALL EXISTING ELECTRICAL IN AREAS OF REMODELING UNLESS SPECIFICALLY NOTED OTHERWISE, OR UNLESS REQUIRED FOR CONTINUITY OF CIRCUITS IN AREAS NOT IN REMODEL AREA.
25. ALL EXISTING ELECTRICAL IS NOT SHOWN. IT IS THE CONTRACTORS RESPONSIBILITY TO BECOME FAMILIAR WITH ALL EXISTING CONDITIONS PRIOR TO BID, AND INCLUDE IN HIS BID THE REMOVAL OF ALL ELECTRICAL EQUIPMENT, WIRE, CONDUIT, DEVICES, FIXTURES, ETC. THAT IS NOT BEING REUSED, BACK TO ITS SOURCE.
26. ALL RECEPTACLES, DEVICES AND EQUIPMENT NOT SHOWN, AND IN AREAS OUTSIDE OF REMODELING SHALL REMAIN ACTIVE UNLESS OTHERWISE NOTED. FURNISH AND INSTALL ACCESSIBLE JUNCTION BOXES AND REWORK EXISTING CIRCUITS AS REQUIRED TO MAINTAIN CIRCUIT CONTINUITY TO RECEPTACLES, DEVICES AND EQUIPMENT REMAINING.
27. ALL CONDUIT TO BE CONCEALED UNLESS IMPOSSIBLE DUE TO EXISTING CONDITIONS (I.E. EXPOSED CEILINGS, BUILDING EXTERIOR WALL RUNS, IMPOSSIBLE UNDERGROUND RUNS). CONCEAL ALL CONDUITS ABOVE CEILINGS OR IN
WALL/COUNTERS.
28. ALL NEW DEVICES TO BE FLUSH MOUNTED UNLESS SPECIFICALLY NOTED OTHERWISE.
GENERAL NOTES:
CODE REFERENCE:
NATIONAL ELECTRICAL CODE: 2020
CEILING OUTLET BOX AND FLUORESCENT OR LED FIXTURE
WALL OUTLET BOX AND FLUORESCENT OR LED FIXTURE
SEE FIXTURE SCHEDULE
SEE FIXTURE SCHEDULE
d d
SYMBOL LEGEND
SYMBOL DESCRIPTION DESIGN SELECTION APPROVED SUBSTITUTION APPROVED SUBSTITUTION REMARKS
OUTLET BOX AND FLUORESCENT OR LED LIGHT
FIXTURE ON EMERGENCY SYSTEM BRANCH
CIRCUIT (LIFE SAFETY BRANCH)
SEE FIXTURE SCHEDULE d
OUTLET BOX AND FLUORESCENT OR LED IN COVE OR
MILLWORK. COORDINATE WITH ARCHITECTURAL PLANS
SEE FIXTURE SCHEDULE d
SYMBOL LEGEND
SYMBOL DESCRIPTION DESIGN SELECTION APPROVED SUBSTITUTION APPROVED SUBSTITUTION REMARKS
ELECTRICAL SYMBOL LEGEND
NOTES:
1. ALL DEVICES TO BE GREY WITH SMOOTH METAL #302 S.S. PLATES UNLESS OTHERWISE NOTED.
2. DASHED ITEM DENOTES "EXISTING".
3. "R" BY DEVICE DENOTES EXISTING TO BE REMOVED COMPLETELY.
4. "H" BY DEVICE DENOTES DEVICE TO BE MOUNTED HORIZONTALLY.
5. MOUNT SWITCHES AT 48" AFF TO TOP, SEE ARCHITECTURAL ELEVATIONS.
6. SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
7. ALL ITEMS NOTED ON THE LEGENDS DO NOT NECESSARILY APPEAR ON PLANS.
REMARKS:
a. U.L. LISTED FOR WET LOCATION IN CLOSED POSITION.
b. SUPPORT OUTLET BOX FROM STRUCTURE WITH (1) 3/8" ALL THREADS MINIMUM. BOXES LARGER THAN 25 SQUARE INCHES SHALL BE
SUPPORTED WITH (2) 3/8" ALL THREADS MINIMUM.
c. U.L. LISTED FOR WET LOCATION IN OPEN POSITION WITH ATTACHMENT PLUG INSERTED.
d. JUNCTION/OUTLET BOX SHALL BE SIZED AS REQUIRED FOR CONDUCTOR/DEVICE FILL PER N.E.C.
e. THREADED CONDUIT HUBS SHALL BE SIZED AND CONFIGURED AS REQUIRED FOR APPLICATION.
f. IF WITHIN 30 MILES OF THE COAST LINE, COPPER FREE CAST ALUMINUM OUTLET BOXES SHALL BE USED FOR EXTERIOR
APPLICATIONS.
g. PROVIDE KINDORF MTG. RACK FOR FREE STANDING APPLICATIONS. KINDORF SHALL BE PVC COATED FOR EXTERIOR APPLICATIONS.
ALL CUT ENDS ARE TO BE SEALED.
h. WHEN SURFACE JUNCTION BOX SYMBOL IS COMBINED WITH DEVICE SYMBOL, PROVIDE APPROPRIATE SURFACE PLATE FOR OUTLET
APPLICATION.
i. MAINTAIN WORKING CLEARANCES IN STRICT ACCORDANCE WITH N.E.C. CORRDINATE EXACT LOCATION OF EQUIPMENT WITH ALL DISCIPLINES (I.E. STRUCTURAA, HVAC, PLUMBING, FIRE PROTECTION, KITCHEN, MILLWORK, ETC.) PRIOR TO ROUTH-IN TO MAINTAIN
CLEARANCES.
j. OUTLET BOX SHALL BE SIZED PER SYSTEM INSTALLER REQUIREMENTS.
k. COORDINATE THE TELEPONE/DATA/SYSTEMS DEVICE, WIRE, CABLE, ETC. WITH THE TELE/DATA/SYSTEMS SPECIFICATIONS, DRAWINGS AND/OR SYMBOL LEGENDS..
l. PROVIDE CONDUIT AS CALLED FOR ON SYSTEMS PLANS/SYMBOL LEGENDS.
S
S
S
S
CEILING OUTLET BOX AND HID, FLUORESCENT, LED OR
INCANDESCENT FIXTURE
WALL OUTLET BOX AND HID, FLUORESCENT, LED OR
INCANDESCENT FIXTURE
CEILING OUTLET BOX AND LIGHT FIXTURE ON EMERGENCY
SYSTEM BRANCH CIRCUIT
WALL OUTLET BOX AND HID, FLUORESCENT, LED OR
INCANDESCENT FIXTURE ON EMERGENCY SYSTEM
BRANCH CIRCUIT
WALL OUTLET BOX AND EMERGENCY BATTERY UNIT
EQUIPMENT LIGHT FIXTURE, TRIANGLES IDENTIFY NUMBER
OF FIXTURE HEADS. WALL MTD.
CEILING OUTLET BOX AND EXIT SIGN LIGHT
FIXTURE ON EMERGENCY SYSTEM BRANCH
CIRCUIT (LIFE SAFETY BRANCH) SHADING
INDICATES NUMBER OF FACES AND ORIENTATION
WALL OUTLET BOX AND EXIT SIGN LIGHT FIXTURE
ON EMERGENCY SYSTEM BRANCH CIRCUIT (LIFE
SAFETY BRANCH)
POLE WITH MOUNTING ARM AND CUT-OFF LIGHT FIXTURE.
BOXES INDICATE NUMBER OF FIXTURES AND ORIENTATION
WALL OUTLET BOX AND 20 AMP SINGLE POLE SWITCH ('a'
INDICATES SWITCH-LEG)
WALL OUTLET BOX AND 20 AMP DOUBLE POLE SWITCH
WALL OUTLET BOX AND 20 AMP THREE-WAY SWITCH
WALL OUTLET BOX AND 20 AMP FOUR-WAY SWITCH
SEE FIXTURE SCHEDULE
SEE FIXTURE SCHEDULE
SEE FIXTURE SCHEDULE
SEE FIXTURE SCHEDULE
SEE FIXTURE SCHEDULE
SEE FIXTURE SCHEDULE
SEE FIXTURE SCHEDULE
SEE FIXTURE SCHEDULE
P&S #PS20AC1 HUBBELL #HBL1221 LEVITON #1221-2
P&S #PS20AC2
d d d d d d d d d d d
HUBBELL #HBL1222 LEVITON #1222-2
P&S #PS20AC3 HUBBELL #HBL1223 LEVITON #1223-2
P&S #PS20AC4 HUBBELL #HBL1224 LEVITON #1224-2
a
REMOTE DRIVER AS CALLED FOR ON
DRAWINGS OR IN
SPECIFICATIONS.
RD
S
S
S
D
D
OUTLET BOX AND 20 AMP, 1P MANUAL MOTOR CONTROLLER
WITHOUT OVERLOADS. RATED 1 HP @ 120V, 2 HP @ 277V.
OUTLET BOX AND 20 AMP, 2P MANUAL MOTOR CONTROLLER
WITHOUT OVERLOADS. RATED 2 HP @ 240V.
OUTLET BOX AND 30 AMP, 3P MANUAL MOTOR CONTROLLER
WITHOUT OVERLOADS. RATED 7.5 HP @ 240V, 10 HP @ 480V.
WALL OUTLET BOX AND DIMMER SWITCH, AS NOTED ON
PLANS
WALL OUTLET BOX AND THREE-WAY DIMMER SWITCH AS
NOTED ON PLANS
P&S #PS20AC1/7801P HUBBELL #HBL1221/LOCK
BRACKET
d
P&S #PS20AC2/7801P HUBBELL #HBL1222/LOCK
BRACKET
d
P&S #7803MD/7801P HUBBELL #HBL7810D/LOCK
BRACKET
LEVITON #MS303-DS/LOCK
BRACKET
d
LUTRON d
LUTRON d
M
2M
M3
S
AUTOMATIC WALL SWITCH, DUAL TECHNOLOGY (PIR)
PASSIVE INFRARED AND ULTRASONIC, DIP SWITCH
PROGRAMMING, AUTOMATIC OR MANUAL OPERATION.
RATED: 800 WATTS @ 120V, 1200 WATTS @ 277V.
WATTSTOPPER
DW-100
d
OS
SENSOR SWITCH, INC. GREENGATE
0-10 VOLT DIMMING WALL SWITCH OCCUPANCY SENSOR,
DUAL TECHNOLOGY, PASSIVE INFRARED (PIR) AND
ULTRASONIC, DIP SWITCH PROGRAMMING, MANUAL ON-
AUTO OFF OPERATION. RATED 1000 WATTS AT 120V, 1200
WATTS AT 277V.
WATT STOPPER CAT#
DW-311
d
D OS
LEVITON #1221-2/LOCK
BRACKET
LEVITON #1222-2/LOCK
BRACKET
S WALL OUTLET BOX AND 20 AMP SINGLE POLE KEY SWITCH dP&S #PS20AC1-L HUBBELL #HBL1221L LEVITON #1221-2L
K
S
S
WALL OUTLET BOX AND 20 AMP THREE-WAY KEY SWITCH
WALL OUTLET BOX AND 20 AMP
FOUR-WAY KEY SWITCH
d d
P&S #PS20AC3-L HUBBELL #HBL1223L LEVITON #1223-2L
P&S #PS20AC4-L HUBBELL #HBL1224L LEVITON #1224-2L
3K
4K
S
S
FLUSH WALL OUTLET BOX AND 20 AMP
SINGLE POLE SWITCH, WITH DIE CAST
WEATHERPROOF COVER
FLUSH WALL OUTLET BOX AND 20 AMP SINGLE POLE SWITCH,
WITH LOCKING STAINLESS STEEL WEATHERPROOF COVER.
MOUNT OUTLET BOX HORIZONTALLY.
DEVICE: P&S #PS20AC1
PLATE: P&S #CA1-G
DEVICE: HUBBELL #HBL1221
PLATE: P&S #CA1-G
DEVICE: LEVITON #1221-2 a, d
DEVICE: P&S #20AC1
PLATE: P&S #WPH-1L
DEVICE: HUBBELL #HBL1221
PLATE: P&S #WPH-1L
DEVICE: LEVITON #1221-2 a, d
WP
WPL
S
CAST IRON ZINC PLATED SURFACE MTD. OUTLET BOX AND 20
AMP SINGLE POLE SWITCH, WITH COPPER FREE CAST
ALUMINUM WEATHERPROOF COVER
DEVICE: P&S #PS20AC1
BOX AND PLATE:
APPLETON #FS/FD/FSK-WT2
DEVICE: HUBBELL
#HBL1221 BOX AND PLATE:
APPLETON #FS/FD/FSK-WT2
DEVICE: LEVITON #1221-2 a, d, e, f, g
WP
S
WALL OUTLET BOX AND 6 HOUR MECHANICAL TIME SWITCH
WITH HOLD, RATED 20 AMPS @ 120V, 10 AMPS @ 277V
TORK #
A506HH
INTERMATIC #
FF6HH
ST
d
CEILING MOUNTED (PIR) PASSIVE INFRARED AND
ULTRASONIC OCCUPANCY SENSOR. OMNI DIRECTIONAL 360
DEGREE PIR COVERAGE. PROVIDE MATCHING POWER
PACK.
CEILING MOUNTED LOW VOLTAGE PHOTOSENSOR
COMPATIBLE WITH 0 - 10 VDC ELECTRONIC DIMMING
BALLASTS AND LED DRIVERS THAT DIMS FIXTURES AS
DAYLIGHT INCREASES. 20 TO 60 FOOT CANDLE ADJUSTABLE
SET POINT PROGRAMMABLE VIA WIRELESS PROGRAMMER.
WALL OR CEILING MOUNTED (PIR) PASSIVE INFRARED AND
ULTRASONIC OCCUPANCY SENSOR. PROVIDE MATCHING
POWER PACK.
WATTSTOPPER
DT-305
d
WATTSTOPPER
LS-301
d
WATTSTOPPER
DT-205
d
DT-305
OS
LS-301
PS
OS
DT-205
SENSOR SWITCH, INC. GREENGATE
SENSOR SWITCH,
INC.
GREENGATE
SENSOR SWITCH, INC. GREENGATE
OCCUPANCY SENSOR SYSTEM POWER PACK(S) AS REQUIRED
FOR LOADS AND ZONES. REFER TO SPECIFICATIONS AND
DETAILS. N = NORMAL BRANCH, Q = EQUIPMENT BRANCH
WATTSTOPPER d P
SENSOR SWITCH,
INC.
GREENGATE
* = N or Q
WALL OUTLET BOX AND 20 AMP
SINGLE RECEPTACLE
WALL OUTLET BOX AND 20 AMP
DUPLEX RECEPTACLE
TWO GANG WALL OUTLET BOX AND TWO
20 AMP DUPLEX RECEPTACLES
WALL OUTLET BOX AND 20 AMP DUPLEX RECEPTACLE
MOUNTED ABOVE COUNTER. COORDINATE WITH
ARCHITECTURAL PLANS
P&S #5361 HUBBELL #HBL5361 LEVITON #5351 d
P&S #PS5362 HUBBELL #HBL5352 LEVITON #5362 d
(2)-P&S #PS5362 (2)-HUBBELL #HBL5352 (2)-LEVITON #5362 d
P&S #PS5362 HUBBELL #HBL5352 LEVITON #5362 d
DIGITAL CEILING MOUNTED (PIR) PASSIVE INFRARED AND
ULTRASONIC OCCUPANCY SENSOR. OMNI DIRECTIONAL 360
DEGREE PIR COVERAGE. PROVIDE MATCHING
CONTROLLER.
WATTSTOPPER
LMDC-100
d
LMDC-100
OS
SENSOR SWITCH, INC. GREENGATE
DIGITAL LIGHTING SYSTEM ON\OFF ROOM CONTROLLER(S)
AS REQUIRED FOR SENSORS, LOADS AND ZONES. REFER TO
SPECIFICATIONS AND DETAILS.
WATTSTOPPER d
RC
SENSOR SWITCH,
INC.
GREENGATE
DIGITAL WALL OR CEILING MOUNTED (PIR) PASSIVE
INFRARED AND ULTRASONIC OCCUPANCY SENSOR. PROVIDE
MATCHING CONTROLLER.
WATTSTOPPER
LMDX-100
d
OS
LMDX-100 SENSOR SWITCH,
INC.
GREENGATE
DRC
WATT STOPPER dDIGITAL LIGHTING SYSTEM DIMMING ROOM CONTROLLER(S)
AS REQUIRED FOR SENSORS, LOADS AND ZONES.
CONTROLLER(S) TO PROVIDE 0 - 10 VOLT DIMMING OUTPUT
FOR EACH ON/OFF RELAY. REFER TO SPECIFICATIONS AND
DETAILS.
SENSOR SWITCH GREENGATE
WALL OUTLET BOX AND 20 AMP DUPLEX RECEPTACLE
MOUNTED ABOVE COUNTER. COORDINATE WITH
ARCHITECTURAL PLANS
P&S #PS5362 HUBBELL #HBL5352 LEVITON #5362 d
WALL OUTLET BOX AND 20 AMP RED DUPLEX RECEPTACLE
CONNECTED TO EMERGENCY SYSTEM BRANCH CIRCUIT
P&S #5362-RED HUBBELL #HBL5352-RED LEVITON #5362-RED d
TWO GANG WALL OUTLET BOX AND TWO 20 AMP RED
DUPLEX RECEPTACLE CONNECTED TO EMERGENCY SYSTEM
BRANCH CIRCUIT
(2)-P&S #5362-RED (2)-HUBBELL #HBL5352-RED (2)-LEVITON #5362-RED d
TV
WALL OUTLET BOX AND 20 AMP DUPLEX RECEPTACLE FOR
TELEVISION, MOUNT ADJACENT TO TELEVISION OUTLET AT
84"AFF UNLESS OTHERWISE NOTED.
P&S #PS5362 HUBBELL #HBL5352 LEVITON #5362 d
G
WALL OUTLET BOX AND 20 AMP SELF-TESTING GFI DUPLEX
RECEPTACLE
P&S #2097TRWRGRY HUBBELL #GF5362SGGY LEVITON #G5362-WTG d
CLG
EWC
TWO GANG CEILING OUTLET BOX AND TWO 20 AMP DUPLEX
RECEPTACLES
WALL OUTLET BOX AND 20 AMP SELF-TESTING GFI DUPLEX
RECEPTACLE FOR ELECTRIC WATER COOLER, COORDINATE
WITH EWC INSTALLER FOR MOUNTING REQUIREMENTS.
(2)-P&S #5362 (2)-HUBBELL #HBL5352 (2)-LEVITON #5362 b, d
P&S #2097TRWRGRY HUBBELL #GF5362SGGY LEVITON #G5362-WTG d
CLG
CLG
CEILING OUTLET BOX AND 20 AMP SINGLE RECEPTACLE
CEILING OUTLET BOX AND 20 AMP DUPLEX RECEPTACLE
P&S #5361 HUBBELL #HBL5361 LEVITON #5351 b, d
P&S #5362 HUBBELL #HBL5352 LEVITON #5362 b, d
WPG FLUSH WALL OUTLET BOX AND 20 AMP WEATHER RESISTANT
SELF-TESTING GFCI DUPLEX RECEPTACLE WITH CAST
ALUMINUM WEATHER PROOF IN USE COVER
P&S #2097TRWRGRY WITH
THOMAS & BETTS #CKMGV
OR INTERMATIC
#WP1010MC
HUBBELL #GF5362SGGY WITH
THOMAS & BETTS #CKMGV OR
HUBBELL #WP26M COVER
LEVITON #G5362-WTG WITH
THOMAS & BETTS #CKMGV
OR INTERMATIC
#WP1010MC
a, d
WPL
FLUSH WALL OUTLET BOX AND 20 AMP WEATHER
RESISTANT SELF-TESTING GFCI DUPLEX RECEPTACLE WITH
LOCKING STAINLESS STEEL WEATHER PROOF IN USE
COVER. PROVIDE LOCK WITH COVER. ALL LOCKS SHALL BE
SET TO THE SAME KEY
P&S #2097TRWRGRY WITH
THOMAS & BETTS #CKMGV
OR INTERMATIC #WP1010MC
HUBBELL #GF5362SGGY WITH
THOMAS & BETTS #CKMGV OR
HUBBELL #WP26M COVER
LEVITTON #G5362-WTG WITH
THOMAS & BETTS #CKMGV
OR INTERMATIC #WP1010MC
a, d
WPG CAST IRON PLATED SURFACE MTD. OUTLET BOX AND 20 AMP
WEATHER RESISTANT SELF-TESTING GFCI DUPLEX
RECEPTACLE WITH CAST ALUMINUM WEATHERPROOF IN USE
COVER
P&S #2097TRWRGRY WITH
APPLETON #FS-ID AND
THOMAS & BETTS #CKMGV
OR INTERMATIC #WP1010MC
HUBBELL #GF5362SGGY
APPLETON
#FS-ID AND HUBBELL #WP26M
COVER
LEVITTON #G5362-WTG
APPLETON #FS-ID AND
THOMAS & BETTS #CKMGV
OR INTERMATIC
#WP1010MC
a, c, d, e f, g
WALL OUTLET BOX AND SPECIAL PURPOSE RECEPTACLE AS
NOTED ON PLANS
P&S HUBBELL LEVITON d
(IG)
(C)
(IG)
(C)
HUBBELL #B-2436/S-3625/
SB3083 WITH HUBBELL #HBL5352
WALL OUTLET BOX AND RECESSED 15 AMP
CLOCK RECEPTACLE STAINLESS STEEL
CAST IRON FULLY ADJUSTABLE FLOOR OUTLET BOX AND 20
AMP DUPLEX RECEPTACLE WITH CARPET FLANGE
CAST IRON FULLY ADJUSTABLE TWO GANG FLOOR OUTLET
BOX WITH TWO (2) RECEPTACLES AND CARPET FLANGE.
(PROVIDE SPECIAL RECEPTACLES, I.E. ISOLATED GROUND
OR BLACK COMPUTER TYPE WHERE NOTED)
CAST IRON FULY ADJUSTABLE TWO GANG FLOOR OUTLET
BOX WITH 20 AMP DUPLEX RECEPTACLE, ONE PDS
(VOICE/DATA) OUTLET AND CARPET FLANGE (PROVIDE
SPECIAL RECEPTACLES, I.E. ISOLATED GROUND OR BLACK
COMPUTER TYPE WHERE NOTED)
POWER POLE WITH 20 AMP DUPLEX RECEPTACLE AS NOTED
ON PLANS.
HANGING DUPLEX RECEPTACLE. SEE DETAILS.
HANGING QUAD RECEPTACLE. SEE DETAILS
2 HR. FIRE RATED FLUSH POKE-THRU WITH INTEGRAL
15 AMP DUPLEX RECEPTACLE AND TWO COMMUNICATIONS
PORTS. DIE CAST ALUMINUM FLANGE WITH BRASS FINISH
FLUSH WALL JUNCTION BOX AND BLANK PLATE
JUNCTION BOX AND BLANK PLATE ABOVE CEILING
SURFACE JUNCTION BOX AND BLANK PLATE, WALL MTD. OR
MTD. TO CEILING/STRUCTURE AS INDICATED
SURFACE MTD. WEATHERPROOF JUNCTION BOX AND COVER,
AS NOTED ON PLANS
PUSHBUTTON, AS NOTED, MOUNTED AT 48" TO TOP
MOTOR CONNECTION, AS NOTED
P&S #S3733-55
WALKER 880 CSI/828P/817C
WITH P&S #PS5362
STEEL CITY #641/P-64-DU/
P64-CP WITH LEVITON #5362
d
WALKER 880 CS2/(2)828P/
827C WITH (2) P&S #PS5362
HUBBELL #B-4233/(2)S-3625/
SB3084 WITH (2) HUBBELL
#HBL5352
STEEL CITY #642 WITH
(2)P-64-DU/P64-2G-CP
WITH (2) LEVITON #5362
d
WALKER 880 CS2/828P/829
CK-1/827C WITH P&S #PS5362
HUBBELL #B-4233/S-3625/
S-2625/SB3084 WITH HUBBELL
#HBL5352
STEEL CITY #642/P-64-
3/4-2/P64-DU/P64-
2G-CP WITH LEVITON #5362
d, j, k, l d d, j, k
WIREMOLD #RC7ATCBS WALKER #1570-A-BRS STEEL CITY #PT-700-A-BRS d, j
STEEL CITY RACO d
STEEL CITY RACO b, d
STEEL CITY RACO b, d, g, h
HOFFMAN d, g, h d i
WP
RELAY, AS NOTED
CONTROL AND/OR POWER CONNECTION ON EQUIPMENT
TIME CLOCK, 2-POLE, RESERVE SPRING, 24 HR. WITH
CONTACTS AND COIL VOLTAGE AS REQUIRED FOR CIRCUITS
(UNLESS OTHERWISE NOTED)
PHOTO CELL
METER, AS NOTED
i
TORK
(SEE DETAIL)
PARAGON
(SEE DETAIL)
INTERMATIC
(SEE DETAIL)
i
TORK (SEE DETAIL) PARAGON (SEE DETAIL) INTERMATIC (SEE DETAIL)
R
C
EMERGENCY RELAY, AS NOTED
ER
BAS
BUILDING AUTOMATION SYSTEM CONTROL PANEL. PROVIDE
20 AMP, 120 VOLT DEDICATED CIRCUIT, WITH 3#12 MIN.
CONDUCTORS IN 1/2 INCH CONDUIT TO NEAREST NORMAL
POWER PANEL. WHERE CIRCUIT IS NOT PROVIDED OR
NOTED, USE 20 AMP, 1 P CIRCUIT BREAKER MARKED SPARE
IN PANEL SCHEDULE.
BUSBAR
MAGNETIC MOTOR STARTER, MOTOR CONTROLLER OR
CONTACTOR, AS NOTED
SQUARE "D" G.E. SIEMENS g, i
DISCONNECT SWITCH, SIZE AS NOTED SQUARE "D" G.E. SIEMENS g, i
AFD
STARTER/DISCONNECT SWITCH, SIZE AS NOTED
ADJUSTABLE FREQUENCY DRIVE W/DISC. SW. FURNISHED BY
DIVISION 15
SQUARE "D" G.E. SIEMENS g, i i
120/208V BRANCH CIRCUIT PANELBOARD SURFACE MOUNTED
120/208V BRANCH CIRCUIT PANELBOARD FLUSH MOUNTED
277/480V BRANCH CIRCUIT PANELBOARD SURFACE MOUNTED
277/480V BRANCH CIRCUIT PANELBOARD FLUSH MOUNTED
SQUARE "D" G.E. SIEMENS i
SQUARE "D" G.E. SIEMENS
SQUARE "D" G.E. SIEMENS
SQUARE "D" G.E. SIEMENS
i i i
INTEGRATED FACILITIES SWITCHBOARD (IFS) - 2 SECTION
INTEGRATED FACILITIES SWITCHBOARD (IFS) - 3 SECTION
SQUARE "D" G.E. SIEMENS
SQUARE "D" G.E. SIEMENS
T O
RUSSELECTRIC ASCO
TRANSFORMER
AUTOMATIC TRANSFER SWITCH
SYSTEMS PANEL - SURFACE MOUNTED
SYSTEMS PANEL - FLUSH MOUNTED
SQUARE "D" G.E. SIEMENS i i
SEE SYSTEMS LEGEND/SPECS i, j
SEE SYSTEMS LEGEND/SPECS i, j
LIGHTING CONTROL OR DIMMER PANEL - SURFACE MOUNTED
LIGHTING CONTROL OR DIMMER PANEL - FLUSH MOUNTED
BRANCH CIRCUIT CONDUIT CONCEALED ABOVE CEILING OR IN
WALL. SLASH MARKS INDICATE NUMBER OF CONDUCTORS
(GROUND WIRE NOT SHOWN). TWO CONDUCTORS PLUS
GROUND REQUIRED (UNLESS OTHERWISE NOTED OR MARKED)
E
BRANCH CIRCUIT CONDUIT CONCEALED BELOW SLAB OR
UNDERGROUND
EMERGENCY SYSTEM BRANCH CIRCUIT CONDUIT,
CONCEALED (LIFE SAFETY BRANCH)
C LEGALLY REQUIRED STANDBY SYSTEM BRANCH CIRCUIT
CONDUIT, CONCEALED (CRITICAL BRANCH)
X SECURITY BRANCH CIRCUIT CONDUIT, CONCEALED
G
CONDUIT SEAL-OFF FITTING
GROUND WIRE, CONCEALED
GROUND OR GROUND ROD AS NOTED
CROUSE HINDS APPLETON e
Q OPTIONAL STANDBY SYSTEM BRANCH CIRCUIT CONDUIT,
CONCEALED (EQUIPMENT BRANCH)
DC DIRECT CURRENT EMERGENCY SYSTEM WIRE AND CONDUIT,
CONCEALED
CW
UPS
CONTROL WIRING AND CONDUIT, CONCEALED
UNINTERUPTABLE POWER SYSTEM BRANCH CIRCUIT WITH
ISOLATED GROUND ON EMERGENCY SYSTEM (LIFE SAFETY
BRANCH)
HOME RUN WIRING. ONE CIRCUIT PER ARROW HEAD
CONDUIT CAPPED OFF
CONDUIT CONTINUED
CONDUIT RUN UP
CONDUIT RUN DOWN
(IG)
(C)
CAST IRON FULY ADJUSTABLE THREE GANG…