2024-118_-_CoFM_Warehouse_-_Combined_Electrical.pdf

PDF 4 MB Posted

Attached to
Michigan Avenue Warehouse Renovation
Solicitation number
ITB 25-098
Issued by
Lee County, Fruitville CDP, Florida

About this file

This is an electrical design set of construction documents for the Warehouse Convert to Parks & Rec Department project located at 2801 Michigan Avenue in Fort Myers, Florida, prepared by Grace Hebert Curtis Architects and Matern Professional Engineering for the City of Fort Myers. The project involves converting an existing warehouse into a Parks and Recreation Department facility, with comprehensive electrical design documents dated June 19, 2025, for permit submission. The electrical documents include detailed plans for power systems, lighting, fire alarm systems, site electrical infrastructure, and mechanical equipment feeders across two building sections (North and South), with specific focus on renovating the existing electrical infrastructure to support the new facility's operational requirements.

The electrical design includes a 208V, 3-phase, 4-wire service with an 800A main distribution panel (MDP), two branch panels (SBLP1 and SBLP2) for the South Building, and two branch panels (NBLP1 and NBLP2) for the North Building. The project incorporates LED lighting fixtures, emergency backup lighting, occupancy sensors, and comprehensive systems including fire alarm, access control, and security infrastructure. The electrical design provides for various building spaces including warehouses, offices, conference rooms, restrooms, mechanical rooms, and exterior site lighting. The design also includes provisions for future expansion, surge protection, grounding systems, and compliance with the 2020 National Electrical Code, ensuring a modern, efficient electrical system for the Parks and Recreation Department's new facility.

View the file

Other files

File Type Posted
Michigan_Avenue_Warehouse_Renovation_(Addendum_#19_Revision).pdf PDF
Michigan_Avenue_Warehouse_Renovation_(Addendum_#10_Revision).pdf PDF
DIVISION_22_-_PLUMBING.pdf PDF
CFM_Parks_and_Rec_-_Landscape_Plans_-_South_Parcel.pdf PDF
DIVISIONS_27_&_28_-_SECURITY_&_COMMS.pdf PDF
CoFM_Warehouse_Conversion_Parks_and_Records_Dept_Arch_Spec_Binder.pdf PDF
CFM_Parks_and_Rec_-_Civil_Plans_-_North_Parcel.pdf PDF
2024-118_-_Combined_Plumbing_-_S&S.pdf PDF
2024-118_-_Combined_Mechanical_-_S&S.pdf PDF
20250619_-_Warehouse_Convert_to_Parks_&_Rec_Department_100%_CD_KMW.pdf PDF
CFM_Parks_and_Rec_-_Tech_Specifications.pdf PDF
2025.06.19-_Exist_Warehouse_to_Parks_Rec_-_Structural_Permit_Set_SS.pdf PDF
DIVISON_26_-_ELECTRICAL.pdf PDF
DIVISON_21_-_FIRE_PROTECTION.pdf PDF
CFM_Parks_and_Rec_-_Civil_Plans_-_South_Parcel.pdf PDF
2024-118_-_Combined_Fire_Protection_-_S&S.pdf PDF
CFM_Parks_and_Rec_-_Landscape_Plans_-_North_Parcel.pdf PDF
DIVISION_23_-_HVAC.pdf PDF
SRF_SupplementaryConditions_EM_Contract_(August_2022).pdf PDF
SRF_SupplementaryConditions_Construction_Contract_(August_2022).pdf PDF
FHWA-1273_(10_23)_.pdf PDF
Notice_of_Award.docx DOCX document
2_CFR_Part_200_app_II_(up_to_date_as_of_4-28-2025).pdf PDF
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LIGHT FIXTURE SCHEDULE

TYPE DESCRIPTION BASIS OF DESIGN EQUAL EQUAL VOLTS

A2

RECESSED 2X2' LED

FLAT PANEL

METALUX:

22CGTS-L3C3

DAYBRITE:

2SBP2035L8DS-2-UNV-DIM

ELITE:

22 FPL1 LED 2000/3000/400L-

DIM10-MVOLT-35K/40K/50K-85

4000 LUMENS

4000K 33W

A2E

RECESSED 2X2' LED

FLAT PANEL,

EMERGENCY BATTERY

PACK

METALUX:

22CGTS-L3C3-EL14W

DAYBRITE:

2SBP2035L8DS-2-UNV-

DIM-FPEMLED10RM

ELITE:

22 FPL1 LED 2000/3000/400L-

DIM10-MVOLT-35K/40K/50K-85-

0-EMG-LED-20W

4000 LUMENS

4000K 33W

B1 HIGH BAY LED

METALUX:

SPHB-24-SE-M-UNV-L750-CD

DAYBRITE:

FCY-1525L-8CST-UNV-DIM

ELITE:

CB2-CPA-24000/27000/30000L-

DIM10-MVOLT-MD-

30K/35K/40K/50K-85

24000 LUMENS

4000K 159W

B1E

HIGH BAY LED,

EMERGENCY BATTERY

PACK

METALUX:

SPHB-24-SE-M-UNV-L750-

EL20WHV-CD

DAYBRITE:

FCY-1525L-8CST-UNV-DIM-EM

ELITE:

CB2-CPA-24000/27000/30000L-

DIM10-MVOLT-MD-

30K/35K/40K/50K-85-

EMG-LED-G4-120-347V-CP-25W-HV

24000 LUMENS

4000K 159W

B2

4' DIRECT/INDIRECT

LINEAR PENDENT

AXIS:

TB2DILED-300-1000-80-40-S0-

4-FINISH-UNV-DP-1-CA(#)

FINELITE:

HP2-P-ID-4’-S-TL-840-F-F-96LG-

VOLT-SC-FC-1%-faxxx-C4-

FE-SW

ELITE:

OLS-D1-LED-2-S-D1000L-U500L-1C-

DIM10-MVOLT-40K-85-FINISH

5600 LUMENS

4000K 43W

B2E

4' DIRECT/INDIRECT

LINEAR PENDENT,

EMERGENCY BATTERY

PACK

AXIS:

TB2DILED-300-1000-80-40-S0-

5-FINISH-UNV-DP-1-CA(#)-B

FINELITE:

HP2-P-ID-4’-S-TL-840-F-F-96LG-

VOLT-SC-FC-1%-faxxx-C4-

FE-SW-LGD10W

ELITE:

OLS-D1-LED-2-S-D1000L-U500L-1C-

DIM10-MVOLT-40K-85-FINISH-

0-EMG-LED-10W

5600 LUMENS

4000K 43W

C1

4' LED INDUSTRIAL

STRIP, WET LOCATION

LISTED

METALUX:

4SNX-33SL-LW-UNV-L840-CD-1-U

DAYBRITE:

FSS-4-30L-840-UNV-DIM

ELITE:

4-OC4-LED-

3000/4000/5000L-DIM10-MVOLT-

35K/40K/50K-85

3000 LUMENS

4000K 22W

D1

4" RECESSED LED

DOWNLIGHT

HALO COMMERICAL:

HC420D010-HM405258400

-41MDWF

LIGHTOLIER:

M4R-DL-25-9CS-M-WH-Z10U

ELITE:

HH4-1000/1500/2000L-DIM10-

MVOLT-27/30/35/40/50K-

HH4501-W-WH-MWD-90+

2000 LUMENS

4000K 20W

EM

INDOOR EMERGENCY

BATTERY FIXTURE

SURE-LITES:

APEL SERIES

BEGHELLI:

PEH1

COMPASS:

CU2

120 LED

W1

TYPE FOUR WALL

PACK, WET LOCATION

RAYON LIGHTING:

T652LEDB-20W-UNV-40K-T4-BZ-EM

GARDCO:

GWS-A02-740-T4M-UNV-BZ

BEACON:

VPW2-48L-20-4K7-4F-UNV-DBS

2600 LUMENS

4000K 20W

W1E

TYPE FOUR WALL

PACK, WET LOCATION

WITH BACK UP

BATTERY.

RAYON LIGHTING:

T652LEDB-20W-UNV-40K-T4-BZ-EM

GARDCO:

GWS-A02-740-T4M-UNV-EM-BZ

BEACON:

VPW2-48L-20-4K7-4F-UNV-DBS

2600 LUMENS

4000K 20W

W2

TYPE TWO WALL PACK,

WET LOCATION

RAYON LIGHTING:

T652LEDB-10W-UNV-40K-T2-BZ

GARDCO:

GWS-A01-740-T2M-UNV-BZ

BEACON:

VPW2-48L-15-4K7-2-UNV-DBS

1900 LUMENS

4000K 10W

W2E

TYPE TWO WALL PACK,

WET LOCATION WITH

BACK UP BATTERY.

RAYON LIGHTING:

T652LEDB-10W-UNV-40K-T2-BZ-EM

GARDCO:

GWS-A01-740-T2M-UNV-EM-BZ

BEACON:

VPW2-48L-15-4K7-2-UNV-DBS-E

1900 LUMENS

4000K 10W

X1

EXIT SIGN, RED

LETTERS, BATTERY

BACK-UP

SURE-LITES:

APX7RG

BEGHELLI:

EPX-SA

COMPASS:

CERG

120 LED

SL1

POLE MOUNTED LED

SITE FIXTURE, TYPE V

FORWARD THROW

DISTRIBUTION WITH

SENSOR FOR DIMMING

MOTION, 25' DIRECT

BURIAL CONCRETE

POLE

MCGRAW EDISON:

GALN-SA1B-840-U-T4FT-

FINISH-HSS-WLS4BK

GARDCO:

OPF-S-PO2-840-T4M-AR1-UNV-BL50-

L2-BK

BEACON:

VP-1-160L-35-4K8-4F-UNV-MAF-

FINISH-SHLD-1-HSS-90-B-

FINISH-NXWS-40F

3500 LUMENS

4000K 44W

SL2

POLE MOUNTED LED

SITE FIXTURE, TYPE V

FORWARD THROW

DISTRIBUTION WITH

SENSOR FOR DIMMING

MOTION, 15' DIRECT

BURIAL CONCRETE

POLE

MCGRAW EDISON:

GALN-SA1B-840-U-T4FT-

FINISH-HSS-WLS2BK

GARDCO:

OPF-S-PO2-840-T4M-AR1-UNV-BL50-

L2-BK

BEACON:

VP-1-160L-35-4K8-4F-UNV-MAF-

FINISH-SHLD-1-HSS-90-B-FINISH-

NXWS-16F

3500 LUMENS

4000K 44W

SL3

POLE MOUNTED LED

SITE FIXTURE, 90 SPILL

LIGHT ELIMINATOR ON

RIGHT SIDE WITH

SENSOR FOR DIMMING

MOTION, 15' DIRECT

BURIAL CONCRETE

POLE

MCGRAW EDISON:

GALN-SA1B-840-U-SLR-

FINISH-HSS-WLS2BK

INTENSE:

GTM-L6-35-DIM-FINISH-FF

BEACON:

VP-1-160L-35-4K8-4F-UNV-MAF-

FINISH-SHLD-1-HSS-90-B-FINISH-

NXWS-16F

4400 LUMENS

3500K 45W

LIGHTING FIXTURE SCHEDULE GENERAL NOTES:

(1) CONTRACTOR SHALL CAREFULLY COORDINATE THE LIGHTING FIXTURE TRIM TYPES WITH THE TYPE OF CEILING WHERE THE LIGHTING FIXTURES ARE TO BE INSTALLED. MODIFY FIXTURE CATALOG NUMBER AS REQUIRED TO COORDINATE FIXTURE WITH CEILING.

(2) CONTRACTOR, AT HIS OPTION, MAY USE A U.L. LISTED FLEXIBLE WIRING SYSTEM FOR LIGHTING FIXTURE BRANCH CIRCUITRY ABOVE ACCESSIBLE LAY-IN CEILINGS.

ALL HOMERUNS, CONNECTIONS TO LIGHT SWITCHES, AND BRANCH CIRCUITRY FOR ALL OTHER CEILING CONDITIONS SHALL BE IN A CONVENTIONAL RACEWAY SYSTEM

PER SPECIFICATIONS.

(3) WHEN FIXTURE MODEL NUMBER DIFFERS FROM FIXTURE DESCRIPTION, CONTRACTOR IS TO SUBMIT RFI REQUESTING CLARIFICATION PRIOR TO BID, PRIOR TO SHOP DRAWING SUBMITTAL AND PRIOR TO ORDERING OF FIXTURE. WHERE CONTRACTOR DOES NOT REQUEST CLARIFICATION PRIOR TO BID, CONTRACTOR SHALL PROVIDE THE MOST EXPENSIVE OPTION BETWEEN A FIXTURE THAT MATCHES THE DESCRIPTION AND A FIXTURE THAT MATCHES THE MODEL NUMBER. AFTER BID, CONTRACTOR SHALL SUBMIT RFI REQUESTING CLARIFICATION SO PROPER FIXTURE GETS SUBMITTED, PROVIDED AND INSTALLED.

TYPICAL INDICATING DEVICES

TYPICAL INITIATING DEVICES

TYPICAL CONTROL RELAYS

1ST FLOOR

SOUTH BUILDING FIRE ALARM RISER DIAGRAM

NTS

LOCAL FACP

FIRE ALARM

CONTROL PANEL

DEDICATED TELEPHONE CONNECTION

FOR THIRD PARTY NOTIFICATION

SPRINKLER FLOW & TAMPER

SWITCHES

PROVIDE BATTERY

CALCULATION OF NEW DEVICES

DIALER

F F

F

F

R R FS TS

FIRE ALARM

TERMINAL

CABINET

SITE SPRINKLER FLOW & TAMPER

SWITCHES FS TS

FA-NEW

PROVIDE SURGE ON ALL INCOMING

EXTERRIOR COPPER CABLES

F

F

F

AR

TYPICAL INDICATING DEVICES

TYPICAL INITIATING DEVICES

TYPICAL CONTROL RELAYS

1ST FLOOR

NORTH BUILDING FIRE ALARM RISER DIAGRAM

NTS

SPRINKLER FLOW & TAMPER

SWITCHES

PROVIDE BATTERY

CALCULATION OF NEW DEVICES

F F

F

F

R

FS TS

FA-NEW

F

F

F

2ND FLOOR

CONNECT TO FIRE ALARM VIA

LOCKABLE 20A CB.

CONNECT TO FIRE ALARM VIA

LOCKABLE 20A CB.

FIRE ALARM

TERMINAL

CABINET

LOCAL FACP

FIRE ALARM

CONTROL PANEL

DEDICATED TELEPHONE CONNECTION

FOR THIRD PARTY NOTIFICATION

DIALER

TYPICAL INDICATING DEVICES

TYPICAL INITIATING DEVICES

F

F

F

TYPICAL CONTROL RELAYS RRAR

CONNECT TO FIRE ALARM VIA

LOCKABLE 20A CB. ELECTRICAL SHEET INDEX

SHEET NUMBER SHEET NAME

E001 GENERAL NOTES, LEGEND, ABBREVIATIONS & SHEET INDEX

E001-2 GENERAL NOTES, LEGEND, ABBREVIATIONS & SHEET INDEX

E002 ELECTRICAL SYMBOL LEGEND

E003 ELECTRICAL SYMBOL LEGEND

E010 ELECTRICAL SITE PLAN - POWER AND SYSTEMS

E041 ELECTRICAL SITE PLAN - LIGHTING

E042-N ELECTRICAL SITE PLAN - PHOTOMETERICS

E042-S ELECTRICAL SITE PLAN - PHOTOMETERICS

ED111-N POWER & SYSTEMS - 1ST AND 2ND FLOOR DEMOLITION PLANS - NORTH

BUILDING

ED111-S POWER & SYSTEMS - 1ST FLOOR DEMOLITION PLAN - SOUTH BUILDING

ED411-N LIGHTING - 1ST AND 2ND FLOOR DEMOLITION PLANS - NORTH BUILDING

ED411-S LIGHTING - 1ST FLOOR DEMOLITION PLAN - SOUTH BUILDING

E111-N POWER - 1ST AND 2ND FLOOR PLANS - NORTH BUILDING

E111-S POWER - 1ST FLOOR PLAN - SOUTH BUILDING

E111-S-2 POWER - 1ST FLOOR PLAN - SOUTH BUILDING

E112 ELECTRICAL ROOF PLANS

E311-N SYSTEMS - 1ST AND 2ND FLOOR PLANS - NORTH BUILDING

E311-S SYSTEMS - 1ST FLOOR PLAN - SOUTH BUILDING

E311-S-2 SYSTEMS - 1ST FLOOR PLAN - SOUTH BUILDING

E411-N LIGHTING - 1ST AND 2ND FLOOR PLANS - NORTH BUILDING

E411-S LIGHTING - 1ST FLOOR PLAN - SOUTH BUILDING

E411-S-2 LIGHTING - 1ST FLOOR PLAN - SOUTH BUILDING

E501 ELECTRICAL RISER DIAGRAMS

E501-2 ELECTRICAL RISER DIAGRAMS

E601 ELECTRICAL PANEL SCHEDULES

E601-2 ELECTRICAL PANEL SCHEDULES

E602 ELECTRICAL PANEL SCHEDULES

E701 MECHANICAL FEEDER SCHEDULES

E901 ELECTRICAL DETAILS

A - AMERAGE

A/C - AIR CONDITIONING

A.C. - ALTERNATING CURRENT

A/E - ARCHITECT/ENGINEER (OR ENGINEER

WHEN ARCHITECT NOT APPLICABLE)

AFD - ADJUSTABLE FREQUENCY DRIVE

AFF - ABOVE FINISHED FLOOR

AFG - ABOVE FINISHED GRADE

AHU - AIR HANDLER UNIT

AIC - AMPS INTERRUPTING CAPACITY

AL - ALUMINUM

ALT - ALTERNATE

ANSI - AMERICAN NATIONAL STANDARDS INSTITUTE

AWG - AMERICAN WIRE GAUGE

B.C. - BARE COPPER

BLDG - BUILDING

BRKR - BREAKER

C. - CONDUIT

C.B. - CIRCUIT BREAKER

CD. - CANDELA

CKT. - CIRCUIT

C/L - CENTER LINE

CLG. - CEILING

COMP. - COMPRESSOR

CONN. - CONNECTION

COND. - CONDENSER

CONT. - CONTINUOUS

C.R.I. - COLOR RENDERING INDEX

C.T. - CURRENT TRANSFORMER

CU. - COPPER

C.U. - COMPRESSOR CONDENSER UNIT

CW - COLD WATER

D - DEMO

D.B. - DIRECT BURIAL

D.W. - DIRECT CURRENT

C. - DISCONNECT

DPST - DOUBLE POLE SINGLE THROW

DWG - DRAWING

EC - ELECTRICAL CONTRACTOR

(OR GENERAL CONTRACTOR)

DN. - ELEVATOR

EMT - ELECTRIC METALLIC TUBING

EPA - ENVIRONMENTAL PROTECTION AGENCY

EQUIP. - EQUIPMENT

EST - ESTIMATE

ETR - EXISTING TO REMAIN

FAAP - FIRE ALARM ANNUNCIATOR PANEL

FACP - FIRE ALARM CONTROL PANEL

FATC - FIRE ALARM TERMINAL CABINET

FCCP - FIRE ALARM COMMAND CENTER PANEL

FLA - FULL LOAD AMPERES

FT. - FEET

FLR - FLOOR

F.C. - FOOTCANDLES

G - GROUND FAULT CIRCUIT INTERRUPTER

GAL. - GALLON

GALV. - GALVANIZED

GPH - GALLONS PER HOUR

GPM - GALLONS PER MINUTE

GFI - GROUND FAULT INTERRUPTING

GRS - GALVANIZED RIGID STEEL CONDUIT

GND. - GROUND

HTG - HEATERS

HT - HEIGHT

HZ - HERTZ (CYCLES)

H.P.F. - HIGH POWER FACTOR

HP. - HORSEPOWER

HR. - HOUR

H.S. - HEAT STRIP

IMC - INTERMEDIATE METALLIC CONDUIT

IN. - INCHES

J.B. - JUNCTION BOX

KVA - KILOVOLT AMPERE

KW - KILOWATTS

KWH - KILOWATT HOUR

K - KELVIN

L.L.D. - LAMP LUMEN DEPRECIATION

LED - LIGHT EMITTING DIODE

LIU - LIGHT INTERFACE UNIT

LT. - LIGHT

LTG. - LIGHTING

LTS. - LIGHTS

L.P.F. - LOW POWER FACTOR

M.C.B. - MAIN CIRCUIT BREAKER

M.L.O. - MAIN LUGS ONLY

MAINT. - MAINTENANCE

MH. - METAL HALIDE

MFG. - MANUFACTURER

MCM - THOUSAND CIRCULAR MILS

MOCP - MINIMUM OVERCURRENT

PROTECTION

MIN - MINIMUM

MCP - MOTOR CIRCUIT PROTECTOR

MTD - MOUNTED

N. - NEUTRAL

NEC - NATIONAL ELECTRIC CODE

NEMA - NATIONAL ELECTRICAL MANUFACTURERS

ASSOCIATION

NFPA - NATIONAL FIRE PROTECTION ASSOCIATION

N.P.T. - NATIONAL PIPE THREAD

NF - NON FUSED

N.C. - NORMALLY CLOSED

N.O. - NORMALLY OPEN

NIC. - NOT IN CONTRACT

NO. - NUMBER

O.L. - OVERLOAD

% - PERCENT

∅ - PHASE

P. - POLE

P.T. - POTENTIAL TRANSFORMER

PB - PULLBOX

PNL - PANEL

PR - PAIR

PRI. - PRIMARY

R - REMOVED

RECEP - RECEPTACLE

REL - RELOCATE

RPM - REVOLUTIONS PER MINUTE

R.S. - RAPID START

SCA - SHORT CIRCUIT AMPS

SEC. - SECONDARY

S/N - SOLID NEUTRAL

SPST - SINGLE POLE SINGLE THROW

SF - SQUARE FOOT

SW. - SWITCH

SWBD - SWITCHBOARD

SYS. - SYSTEM

THHN - THWN NYLON JACKETED WIRE

TTB - TELEPHONE TERMINAL BOARD

TTC - TELEPHONE TERMINAL CABINET

TV - TELEVISION

TVTC - TELEVISION TERMINAL CABINET

TVEC - TELEVISION EQUIP. CABINET

TYP - TYPICAL TEMP. - TEMPERATURE

U.L. - UNDERWRITERS' LABORATORIES

VFD - VARIABLE FREQUENCY DRIVE

VHF - VERY HIGH FREQUENCY

VHO - VERY HIGH OUTPUT

V - VOLT

VA - VOLT AMPERES

VOL. - VOLUME

W - WIRE

W.G. - WIRE GUARD

W.P. - WEATHERPROOF

XFMR - TRANSFORMER

Y - WYE

YD. - YARD

YR. - YEAR

3R - RAINPROOF

4X - STAINLESS STEEL DUSTIGHT,

WATERTIGHT

ELECTRICAL ABBREVIATIONS

MPE JOB #:

ENG. BUS. No. EB-0005096

CERT. OF AUTH. No. 5096

PHONE (239) 332-1187

12437 Brantley Commons Fort Myers, FL 33907

SCOTT LA IN

No 69099P R

STATE OF

E

O F

E S

S

ION A L E N

G

IN

E E

R

NSECIL

F L O R I DA

PROJECT NO:

DATE:

PHASE:

ISSUED FOR

SEAL:

GRACE HEBERT CURTIS ARCHITECTS, LLC

SHEET NUMBER

© THIS SET OF DOCUMENTS INCLUSIVE OF

DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT

BE COPIED, SCANNED, NOR ELECTRONICALLY

DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT

THE EXPRESSED WRITTEN CONSENT OF GRACE

HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,

ELECTRONIC PLAN SERVICE (INTERNET PLAN

SERVICE), NOR REPRODUCTION COMPANY SHALL BE

PERMITTED TO POST THESE DOCUMENTS WITHOUT

THE EXPRESSED WRITTEN CONSENT OF THE

ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.

2024-118

/1

/2

:3

:2

P

M

A u to d e s k D o c s /W a re h o u s e

C o n v e rt t o P a rk s

R e c D e p a rt m e n t/

-1

E le c tr ic a l M o d e l_

O p ti o n O n e

R e v it

B

IM

.r v t

E001

GENERAL NOTES, LEGEND,

ABBREVIATIONS & SHEET

INDEX

40-24105

W A

R E

H O

U S

E C

O N

V E

R T

T O

P A

R K

S

R E

C D

E P

T

C

IT

Y O

F F

O R

T M

Y E

R S

06/19/2025

PERMIT DOCUMENTS

M

IC

H

IG

A

N A

V E

N U

E F

O R

T M

Y E

R S

F

L O

R

ID

A

1. NO MULTI-WIRE BRANCH CIRCUITS ARE TO BE USED. EACH CIRCUIT IS TO HAVE SEPARATE INDIVIDUAL NEUTRAL.

2. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 0-100 FEET, ARE TO HAVE #12 MINIMUM BRANCH CIRCUIT WIRING

THROUGHOUT CIRCUIT. (CONDUIT SIZE PER SPECIFICATION AND NEC).

3. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 101-125 FEET, ARE TO HAVE #10 MINIMUM BRANCH CIRCUIT WIRING HOMERUN (3/4"C.) FROM PANEL CIRCUIT BREAKER TO FIRST DEVICE AND #12 BRANCH CIRCUIT WIRING THROUGHOUT THE REMAINDER OF THE CIRCUIT. (CONDUIT SIZE PER SPECIFICATION AND NEC). NOT LESS THAN THE FIRST 75 FEET OF COMBINED HOMERUN AND BRANCH CIRCUIT TO BE MINIMUM #10 WIRE (3/4"C).

4. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 126-160 FEET, ARE TO HAVE #10 MINIMUM BRANCH CIRCUIT

WIRING THROUGHOUT CIRCUIT (3/4”C).\

5. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 161-205 FEET, ARE TO HAVE #8 MINIMUM BRANCH CIRCUIT WIRING HOMERUN (1"C.) FROM PANEL CIRCUIT BREAKER TO FIRST DEVICE AND #10 BRANCH CIRCUIT WIRING THROUGHOUT THE REMAINDER OF THE CIRCUIT (3/4"C.). NOT LESS THAN THE FIRST 125 FEET OF COMBINED HOMERUN AND BRANCH

CIRCUIT TO BE MINIMUM #8 WIRE (1"C.)

6. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 206-230 FEET, ARE TO HAVE #8 MINIMUM BRANCH CIRCUIT WIRING

THROUGHOUT CIRCUIT (1"C.).

7. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 231-250 FEET, ARE TO HAVE #6 MINIMUM BRANCH CIRCUIT WIRING HOMERUN (1-1/4"C.) FROM PANEL CIRCUIT BREAKER TO FIRST DEVICE AND #10 BRANCH CIRCUIT WIRING THROUGHOUT THE REMAINDER OF THE CIRCUIT (3/4"C.). NOT LESS THAN THE FIRST 175 FEET OF COMBINED HOMERUN AND

BRANCH CIRCUIT TO BE MINIMUM #6 WIRE (1-1/4"C.).

8. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 251-325 FEET, ARE TO HAVE #6 MINIMUM BRANCH CIRCUIT WIRING HOMERUN (1-1/4"C.) FROM PANEL CIRCUIT BREAKER TO FIRST DEVICE AND #8 BRANCH CIRCUIT WIRING THROUGHOUT THE REMAINDER OF THE CIRCUIT (1"C.). NOT LESS THAN THE FIRST 250 FEET OF COMBINED HOMERUN AND

BRANCH CIRCUIT TO BE MINIMUM #6 WIRE (1-1/4"C.).

9. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 326-370 FEET FROM THE PANEL, ARE TO HAVE #6 MINIMUM

BRANCH CIRCUIT WIRING THROUGHOUT CIRCUIT (1-1/4"C.).

10. 120 VOLT BRANCH CIRCUITS SERVING RECEPTACLES FOR COMPUTER WORKSTATIONS (IE OUTLETS WITH 'C' DESIGNATION) SHALL HAVE MINIMUM CONDUCTOR SIZE OF #10. #10 MINIMUM CONDUCTOR SIZE SHALL BE INCREASED IF

REQUIRED TO COMPLY WITH GENERAL NOTES ABOVE.

11. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF FIXTURES.

12. COORDINATE EXACT LOCATION OF LIGHTING FIXTURES IN ALL MECH. ROOMS, AND SPACES WITH NO CEILING (EXPOSED STRUCTURE AREAS), SPACES, ETC., WITH DUCTWORK INSTALLER PRIOR TO ROUGH-IN. LOCATE BELOW

DUCTWORK (8'-0" A.F.F. MINIMUM) CENTERED IN ROOM AS MUCH AS FEASIBLE.

13. COORDINATE EXACT INSTALLATION REQUIREMENTS OF OUTLETS IN MILLWORK WITH ARCHITECTURAL DRAWINGS AND ACCEPTED MILLWORK SHOP DRAWINGS.

14. VERIFY EXACT LOCATION OF ALL MECH. EQUIP. INCLUDING WALL SWITCHES, T'STATS, ETC. WITH MECH. CONTRACTOR AND MECH. DRAWINGS.

15. REFER TO MECHANICAL EQUIPMENT SCHEDULE, FOR RESPECTIVE CONDUIT/CONDUCTORS, DISCONNECTS, MISC. EQUIPMENT REQUIRED FOR ALL MECHANICAL AND PLUMBING EQUIPMENT. REFER TO PANEL SCHEDULES FOR

CIRCUITS NUMBERS OF CIRCUITS FOR MECHANICAL AND PLUMBING EQUIPMENT.

16. VISIT AND CAREFULLY EXAMINE THOSE PORTIONS OF THE BUILDING AND SITE AFFECTED BY THIS WORK BEFORE SUBMITTING PROPOSALS, SO AS TO BECOME FAMILIAR WITH EXISTING CONDITIONS AND DIFFICULTIES THAT WILL AFFECT EXECUTION OF THE WORK. SUBMISSION OF A PROPOSAL WILL BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE AND LATER CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE OF

DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED.

17. READ SPECIFICATIONS.

18. SEE RISER DIAGRAMS AND BUILDING PLANS.

19. ALL EMPTY CONDUITS ARE TO HAVE PULL-STRINGS PROVIDED IN THEM.

20. EXISTING CONDITIONS AND UTILITIES INDICATED ARE TAKEN FROM EXISTING CONSTRUCTION DOCUMENTS, VARIOUS SURVEYS, AND FIELD INVESTIGATIONS. IT IS TO BE UNDERSTOOD THAT UNFORESEEN CONDITIONS PROBABLY EXIST AND NEW WORK MAY NOT BE FIELD LOCATED EXACTLY AS SHOWN ON THE DRAWINGS. COOPERATION WITH OTHER TRADES IN ROUTING AND/OR BURIAL DEPTHS AS DETERMINED DURING CONSTRUCTION AND AS DIRECTED BY THE ARCHITECT/ENGINEER MAY BE NECESSARY AND IT IS INTENDED THAT SUCH DEVIATIONS SHALL BE CONSIDERED A PART OF THIS CONTRACT. IT IS ALSO UNDERSTOOD THAT THE PLANS ARE NOT COMPLETELY TO SCALE. THIS CONTRACTOR IS TO FIELD VERIFY DIMENSIONS OF ALL SITE UTILITIES, ETC., PRIOR TO BID AND INCLUDE ANY DEVIATIONS IN THE CONTRACT.

21. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO LOCATE ALL EXISTING UTILITIES WHETHER SHOWN ON PLANS OR NOT AND TO PROTECT THEM FROM DAMAGE. THE CONTRACTOR SHALL BEAR ALL EXPENSE FOR REPAIR OR REPLACEMENT OF UTILITIES OR OTHER PROPERTY DAMAGED BY OPERATIONS IN CONJUNCTION WITH THE COMPLETION OF THIS WORK. THE CONTRACTOR SHALL LOCATE ALL UTILITIES (BOTH KNOWN AND UNKNOWN) IN AREA OF WORK PRIOR TO EXCAVATION WITH THE USE OF ELECTRONIC LOCATOR/TRACER DEVICES AND EQUIPMENT SUITABLE FOR SUCH USE. REFLECT LOCATED UTILITIES ON AS-BUILT DOCUMENTS.

22. REMOVE EXISTING POWER, LIGHTING, SYSTEMS, MATERIAL AND EQUIPMENT WHICH ARE MADE OBSOLETE OR WHICH INTERFERE WITH THE CONSTRUCTION OF THE PROJECT.

23. REINSTALL ANY SUCH POWER, LIGHTING, SYSTEMS, MATERIALS AND EQUIPMENT WHICH ARE REQUIRED TO REMAIN ACTIVE FOR THE FACILITY TO BE FULLY FUNCTIONAL.

24. REMOVE ALL EXISTING ELECTRICAL IN AREAS OF REMODELING UNLESS SPECIFICALLY NOTED OTHERWISE, OR UNLESS REQUIRED FOR CONTINUITY OF CIRCUITS IN AREAS NOT IN REMODEL AREA.

25. ALL EXISTING ELECTRICAL IS NOT SHOWN. IT IS THE CONTRACTORS RESPONSIBILITY TO BECOME FAMILIAR WITH ALL EXISTING CONDITIONS PRIOR TO BID, AND INCLUDE IN HIS BID THE REMOVAL OF ALL ELECTRICAL EQUIPMENT, WIRE, CONDUIT, DEVICES, FIXTURES, ETC. THAT IS NOT BEING REUSED, BACK TO ITS SOURCE.

26. ALL RECEPTACLES, DEVICES AND EQUIPMENT NOT SHOWN, AND IN AREAS OUTSIDE OF REMODELING SHALL REMAIN ACTIVE UNLESS OTHERWISE NOTED. FURNISH AND INSTALL ACCESSIBLE JUNCTION BOXES AND REWORK EXISTING CIRCUITS AS REQUIRED TO MAINTAIN CIRCUIT CONTINUITY TO RECEPTACLES, DEVICES AND EQUIPMENT REMAINING.

27. ALL CONDUIT TO BE CONCEALED UNLESS IMPOSSIBLE DUE TO EXISTING CONDITIONS (I.E. EXPOSED CEILINGS, BUILDING EXTERIOR WALL RUNS, IMPOSSIBLE UNDERGROUND RUNS). CONCEAL ALL CONDUITS ABOVE CEILINGS OR IN

WALL/COUNTERS.

28. ALL NEW DEVICES TO BE FLUSH MOUNTED UNLESS SPECIFICALLY NOTED OTHERWISE.

GENERAL NOTES:

CODE REFERENCE:

NATIONAL ELECTRICAL CODE: 2020

NO. DESCRIPTION DATE

LIGHT FIXTURE SCHEDULE

TYPE DESCRIPTION BASIS OF DESIGN EQUAL EQUAL VOLTS

A2

RECESSED 2X2' LED

FLAT PANEL

METALUX:

22CGTS-L3C3

DAYBRITE:

2SBP2035L8DS-2-UNV-DIM

ELITE:

22 FPL1 LED 2000/3000/400L-

DIM10-MVOLT-35K/40K/50K-85

4000 LUMENS

4000K 33W

A2E

RECESSED 2X2' LED

FLAT PANEL,

EMERGENCY BATTERY

PACK

METALUX:

22CGTS-L3C3-EL14W

DAYBRITE:

2SBP2035L8DS-2-UNV-

DIM-FPEMLED10RM

ELITE:

22 FPL1 LED 2000/3000/400L-

DIM10-MVOLT-35K/40K/50K-85-

0-EMG-LED-20W

4000 LUMENS

4000K 33W

B1 HIGH BAY LED

METALUX:

SPHB-24-SE-M-UNV-L750-CD

DAYBRITE:

FCY-1525L-8CST-UNV-DIM

ELITE:

CB2-CPA-24000/27000/30000L-

DIM10-MVOLT-MD-

30K/35K/40K/50K-85

24000 LUMENS

4000K 159W

B1E

HIGH BAY LED,

EMERGENCY BATTERY

PACK

METALUX:

SPHB-24-SE-M-UNV-L750-

EL20WHV-CD

DAYBRITE:

FCY-1525L-8CST-UNV-DIM-EM

ELITE:

CB2-CPA-24000/27000/30000L-

DIM10-MVOLT-MD-

30K/35K/40K/50K-85-

EMG-LED-G4-120-347V-CP-25W-HV

24000 LUMENS

4000K 159W

C1

4' LED INDUSTRIAL

STRIP, WET LOCATION

LISTED

METALUX:

4SNX-33SL-LW-UNV-L840-CD-1-U

DAYBRITE:

FSS-4-30L-840-UNV-DIM

ELITE:

4-OC4-LED-

3000/4000/5000L-DIM10-MVOLT-

35K/40K/50K-85

3000 LUMENS

4000K 22W

D1

4" RECESSED LED

DOWNLIGHT

HALO COMMERICAL:

HC420D010-HM405258400

-41MDWF

LIGHTOLIER:

M4R-DL-25-9CS-M-WH-Z10U

ELITE:

HH4-1000/1500/2000L-DIM10-

MVOLT-27/30/35/40/50K-

HH4501-W-WH-MWD-90+

2000 LUMENS

4000K 20W

EM

INDOOR EMERGENCY

BATTERY FIXTURE

SURE-LITES:

APEL SERIES

BEGHELLI:

PEH1

COMPASS:

CU2

120 LED

W1

TYPE FOUR WALL

PACK, WET LOCATION

RAYON LIGHTING:

T652LEDB-20W-UNV-40K-T4-BZ-EM

GARDCO:

GWS-A02-740-T4M-UNV-BZ

BEACON:

VPW2-48L-20-4K7-4F-UNV-DBS

2600 LUMENS

4000K 20W

W1E

TYPE FOUR WALL

PACK, WET LOCATION

WITH BACK UP

BATTERY.

RAYON LIGHTING:

T652LEDB-20W-UNV-40K-T4-BZ-EM

GARDCO:

GWS-A02-740-T4M-UNV-EM-BZ

BEACON:

VPW2-48L-20-4K7-4F-UNV-DBS

2600 LUMENS

4000K 20W

W2

TYPE TWO WALL PACK,

WET LOCATION

RAYON LIGHTING:

T652LEDB-10W-UNV-40K-T2-BZ

GARDCO:

GWS-A01-740-T2M-UNV-BZ

BEACON:

VPW2-48L-15-4K7-2-UNV-DBS

1900 LUMENS

4000K 10W

W2E

TYPE TWO WALL PACK,

WET LOCATION WITH

BACK UP BATTERY.

RAYON LIGHTING:

T652LEDB-10W-UNV-40K-T2-BZ-EM

GARDCO:

GWS-A01-740-T2M-UNV-EM-BZ

BEACON:

VPW2-48L-15-4K7-2-UNV-DBS-E

1900 LUMENS

4000K 10W

X1

EXIT SIGN, RED

LETTERS, BATTERY

BACK-UP

SURE-LITES:

APX7RG

BEGHELLI:

EPX-SA

COMPASS:

CERG

120 LED

SL1

POLE MOUNTED LED

SITE FIXTURE, TYPE V

FORWARD THROW

DISTRIBUTION WITH

SENSOR FOR DIMMING

MOTION, 25' DIRECT

BURIAL CONCRETE

POLE

MCGRAW EDISON:

GALN-SA1B-840-U-T4FT-

FINISH-HSS-WLS4BK

GARDCO:

OPF-S-PO2-840-T4M-AR1-UNV-BL50-

L2-BK

BEACON:

VP-1-160L-35-4K8-4F-UNV-MAF-

FINISH-SHLD-1-HSS-90-B-

FINISH-NXWS-40F

3500 LUMENS

4000K 44W

SL2

POLE MOUNTED LED

SITE FIXTURE, TYPE V

FORWARD THROW

DISTRIBUTION WITH

SENSOR FOR DIMMING

MOTION, 15' DIRECT

BURIAL CONCRETE

POLE

MCGRAW EDISON:

GALN-SA1B-840-U-T4FT-

FINISH-HSS-WLS2BK

GARDCO:

OPF-S-PO2-840-T4M-AR1-UNV-BL50-

L2-BK

BEACON:

VP-1-160L-35-4K8-4F-UNV-MAF-

FINISH-SHLD-1-HSS-90-B-FINISH-

NXWS-16F

3500 LUMENS

4000K 44W

SL3

POLE MOUNTED LED

SITE FIXTURE, 90 SPILL

LIGHT ELIMINATOR ON

RIGHT SIDE WITH

SENSOR FOR DIMMING

MOTION, 15' DIRECT

BURIAL CONCRETE

POLE

MCGRAW EDISON:

GALN-SA1B-840-U-SLR-

FINISH-HSS-WLS2BK

INTENSE:

GTM-L6-35-DIM-FINISH-FF

BEACON:

VP-1-160L-35-4K8-4F-UNV-MAF-

FINISH-SHLD-1-HSS-90-B-FINISH-

NXWS-16F

4400 LUMENS

3500K 45W

LIGHTING FIXTURE SCHEDULE GENERAL NOTES:

(1) CONTRACTOR SHALL CAREFULLY COORDINATE THE LIGHTING FIXTURE TRIM TYPES WITH THE TYPE OF CEILING WHERE THE LIGHTING FIXTURES ARE TO BE INSTALLED. MODIFY FIXTURE CATALOG NUMBER AS REQUIRED TO COORDINATE FIXTURE WITH CEILING.

(2) CONTRACTOR, AT HIS OPTION, MAY USE A U.L. LISTED FLEXIBLE WIRING SYSTEM FOR LIGHTING FIXTURE BRANCH CIRCUITRY ABOVE ACCESSIBLE LAY-IN CEILINGS.

ALL HOMERUNS, CONNECTIONS TO LIGHT SWITCHES, AND BRANCH CIRCUITRY FOR ALL OTHER CEILING CONDITIONS SHALL BE IN A CONVENTIONAL RACEWAY SYSTEM

PER SPECIFICATIONS.

(3) WHEN FIXTURE MODEL NUMBER DIFFERS FROM FIXTURE DESCRIPTION, CONTRACTOR IS TO SUBMIT RFI REQUESTING CLARIFICATION PRIOR TO BID, PRIOR TO SHOP DRAWING SUBMITTAL AND PRIOR TO ORDERING OF FIXTURE. WHERE CONTRACTOR DOES NOT REQUEST CLARIFICATION PRIOR TO BID, CONTRACTOR SHALL PROVIDE THE MOST EXPENSIVE OPTION BETWEEN A FIXTURE THAT MATCHES THE DESCRIPTION AND A FIXTURE THAT MATCHES THE MODEL NUMBER. AFTER BID, CONTRACTOR SHALL SUBMIT RFI REQUESTING CLARIFICATION SO PROPER FIXTURE GETS SUBMITTED, PROVIDED AND INSTALLED.

TYPICAL INDICATING DEVICES

TYPICAL INITIATING DEVICES

TYPICAL CONTROL RELAYS

1ST FLOOR

SOUTH BUILDING FIRE ALARM RISER DIAGRAM

NTS

LOCAL FACP

FIRE ALARM

CONTROL PANEL

DEDICATED TELEPHONE CONNECTION

FOR THIRD PARTY NOTIFICATION

SPRINKLER FLOW & TAMPER

SWITCHES

PROVIDE BATTERY

CALCULATION OF NEW DEVICES

DIALER

F F

F

F

R R FS TS

FIRE ALARM

TERMINAL

CABINET

SITE SPRINKLER FLOW & TAMPER

SWITCHES FS TS

FA-NEW

PROVIDE SURGE ON ALL INCOMING

EXTERRIOR COPPER CABLES

F

F

F

AR

TYPICAL INDICATING DEVICES

TYPICAL INITIATING DEVICES

TYPICAL CONTROL RELAYS

1ST FLOOR

NORTH BUILDING FIRE ALARM RISER DIAGRAM

NTS

SPRINKLER FLOW & TAMPER

SWITCHES

PROVIDE BATTERY

CALCULATION OF NEW DEVICES

F F

F

F

R

FS TS

FA-NEW

F

F

F

2ND FLOOR

CONNECT TO FIRE ALARM VIA

LOCKABLE 20A CB.

CONNECT TO FIRE ALARM VIA

LOCKABLE 20A CB.

FIRE ALARM

TERMINAL

CABINET

LOCAL FACP

FIRE ALARM

CONTROL PANEL

DEDICATED TELEPHONE CONNECTION

FOR THIRD PARTY NOTIFICATION

DIALER

TYPICAL INDICATING DEVICES

TYPICAL INITIATING DEVICES

F

F

F

TYPICAL CONTROL RELAYS RRAR

CONNECT TO FIRE ALARM VIA

LOCKABLE 20A CB.

A - AMERAGE

A/C - AIR CONDITIONING

A.C. - ALTERNATING CURRENT

A/E - ARCHITECT/ENGINEER (OR ENGINEER

WHEN ARCHITECT NOT APPLICABLE)

AFD - ADJUSTABLE FREQUENCY DRIVE

AFF - ABOVE FINISHED FLOOR

AFG - ABOVE FINISHED GRADE

AHU - AIR HANDLER UNIT

AIC - AMPS INTERRUPTING CAPACITY

AL - ALUMINUM

ALT - ALTERNATE

ANSI - AMERICAN NATIONAL STANDARDS INSTITUTE

AWG - AMERICAN WIRE GAUGE

B.C. - BARE COPPER

BLDG - BUILDING

BRKR - BREAKER

C. - CONDUIT

C.B. - CIRCUIT BREAKER

CD. - CANDELA

CKT. - CIRCUIT

C/L - CENTER LINE

CLG. - CEILING

COMP. - COMPRESSOR

CONN. - CONNECTION

COND. - CONDENSER

CONT. - CONTINUOUS

C.R.I. - COLOR RENDERING INDEX

C.T. - CURRENT TRANSFORMER

CU. - COPPER

C.U. - COMPRESSOR CONDENSER UNIT

CW - COLD WATER

D - DEMO

D.B. - DIRECT BURIAL

D.W. - DIRECT CURRENT

C. - DISCONNECT

DPST - DOUBLE POLE SINGLE THROW

DWG - DRAWING

EC - ELECTRICAL CONTRACTOR

(OR GENERAL CONTRACTOR)

DN. - ELEVATOR

EMT - ELECTRIC METALLIC TUBING

EPA - ENVIRONMENTAL PROTECTION AGENCY

EQUIP. - EQUIPMENT

EST - ESTIMATE

ETR - EXISTING TO REMAIN

FAAP - FIRE ALARM ANNUNCIATOR PANEL

FACP - FIRE ALARM CONTROL PANEL

FATC - FIRE ALARM TERMINAL CABINET

FCCP - FIRE ALARM COMMAND CENTER PANEL

FLA - FULL LOAD AMPERES

FT. - FEET

FLR - FLOOR

F.C. - FOOTCANDLES

G - GROUND FAULT CIRCUIT INTERRUPTER

GAL. - GALLON

GALV. - GALVANIZED

GPH - GALLONS PER HOUR

GPM - GALLONS PER MINUTE

GFI - GROUND FAULT INTERRUPTING

GRS - GALVANIZED RIGID STEEL CONDUIT

GND. - GROUND

HTG - HEATERS

HT - HEIGHT

HZ - HERTZ (CYCLES)

H.P.F. - HIGH POWER FACTOR

HP. - HORSEPOWER

HR. - HOUR

H.S. - HEAT STRIP

IMC - INTERMEDIATE METALLIC CONDUIT

IN. - INCHES

J.B. - JUNCTION BOX

KVA - KILOVOLT AMPERE

KW - KILOWATTS

KWH - KILOWATT HOUR

K - KELVIN

L.L.D. - LAMP LUMEN DEPRECIATION

LED - LIGHT EMITTING DIODE

LIU - LIGHT INTERFACE UNIT

LT. - LIGHT

LTG. - LIGHTING

LTS. - LIGHTS

L.P.F. - LOW POWER FACTOR

M.C.B. - MAIN CIRCUIT BREAKER

M.L.O. - MAIN LUGS ONLY

MAINT. - MAINTENANCE

MH. - METAL HALIDE

MFG. - MANUFACTURER

MCM - THOUSAND CIRCULAR MILS

MOCP - MINIMUM OVERCURRENT

PROTECTION

MIN - MINIMUM

MCP - MOTOR CIRCUIT PROTECTOR

MTD - MOUNTED

N. - NEUTRAL

NEC - NATIONAL ELECTRIC CODE

NEMA - NATIONAL ELECTRICAL MANUFACTURERS

ASSOCIATION

NFPA - NATIONAL FIRE PROTECTION ASSOCIATION

N.P.T. - NATIONAL PIPE THREAD

NF - NON FUSED

N.C. - NORMALLY CLOSED

N.O. - NORMALLY OPEN

NIC. - NOT IN CONTRACT

NO. - NUMBER

O.L. - OVERLOAD

% - PERCENT

∅ - PHASE

P. - POLE

P.T. - POTENTIAL TRANSFORMER

PB - PULLBOX

PNL - PANEL

PR - PAIR

PRI. - PRIMARY

R - REMOVED

RECEP - RECEPTACLE

REL - RELOCATE

RPM - REVOLUTIONS PER MINUTE

R.S. - RAPID START

SCA - SHORT CIRCUIT AMPS

SEC. - SECONDARY

S/N - SOLID NEUTRAL

SPST - SINGLE POLE SINGLE THROW

SF - SQUARE FOOT

SW. - SWITCH

SWBD - SWITCHBOARD

SYS. - SYSTEM

THHN - THWN NYLON JACKETED WIRE

TTB - TELEPHONE TERMINAL BOARD

TTC - TELEPHONE TERMINAL CABINET

TV - TELEVISION

TVTC - TELEVISION TERMINAL CABINET

TVEC - TELEVISION EQUIP. CABINET

TYP - TYPICAL TEMP. - TEMPERATURE

U.L. - UNDERWRITERS' LABORATORIES

VFD - VARIABLE FREQUENCY DRIVE

VHF - VERY HIGH FREQUENCY

VHO - VERY HIGH OUTPUT

V - VOLT

VA - VOLT AMPERES

VOL. - VOLUME

W - WIRE

W.G. - WIRE GUARD

W.P. - WEATHERPROOF

XFMR - TRANSFORMER

Y - WYE

YD. - YARD

YR. - YEAR

3R - RAINPROOF

4X - STAINLESS STEEL DUSTIGHT,

WATERTIGHT

ELECTRICAL ABBREVIATIONS

MPE JOB #:

ENG. BUS. No. EB-0005096

CERT. OF AUTH. No. 5096

PHONE (239) 332-1187

12437 Brantley Commons Fort Myers, FL 33907

SCOTT LA IN

No 69099P R

STATE OF

E

O F

E S

S

ION A L E N

G

IN

E E

R

NSECIL

F L O R I DA

PROJECT NO:

DATE:

PHASE:

ISSUED FOR

SEAL:

GRACE HEBERT CURTIS ARCHITECTS, LLC

SHEET NUMBER

© THIS SET OF DOCUMENTS INCLUSIVE OF

DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT

BE COPIED, SCANNED, NOR ELECTRONICALLY

DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT

THE EXPRESSED WRITTEN CONSENT OF GRACE

HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,

ELECTRONIC PLAN SERVICE (INTERNET PLAN

SERVICE), NOR REPRODUCTION COMPANY SHALL BE

PERMITTED TO POST THESE DOCUMENTS WITHOUT

THE EXPRESSED WRITTEN CONSENT OF THE

ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.

2024-118

/1

/2

:3

:5

P

M

A u to d e s k D o c s /W a re h o u s e C o n v e rt t o

P a rk s

R e c D e p a rt m e n t/

-1

E le c tr ic a l M o d e l_

O p ti o n T w o

R e v it

B

IM

.r v t

E001-2

GENERAL NOTES, LEGEND,

ABBREVIATIONS & SHEET

INDEX

40-24105

W A

R E

H O

U S

E C

O N

V E

R T

T O

P A

R K

S

R E

C D

E P

T

C

IT

Y O

F F

O R

T M

Y E

R S

06/19/2025

PERMIT DOCUMENTS

M

IC

H

IG

A

N A

V E

N U

E F

O R

T M

Y E

R S

F

L O

R

ID

A

1. NO MULTI-WIRE BRANCH CIRCUITS ARE TO BE USED. EACH CIRCUIT IS TO HAVE SEPARATE INDIVIDUAL NEUTRAL.

2. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 0-100 FEET, ARE TO HAVE #12 MINIMUM BRANCH CIRCUIT WIRING

THROUGHOUT CIRCUIT. (CONDUIT SIZE PER SPECIFICATION AND NEC).

3. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 101-125 FEET, ARE TO HAVE #10 MINIMUM BRANCH CIRCUIT WIRING HOMERUN (3/4"C.) FROM PANEL CIRCUIT BREAKER TO FIRST DEVICE AND #12 BRANCH CIRCUIT WIRING THROUGHOUT THE REMAINDER OF THE CIRCUIT. (CONDUIT SIZE PER SPECIFICATION AND NEC). NOT LESS THAN THE FIRST 75 FEET OF COMBINED HOMERUN AND BRANCH CIRCUIT TO BE MINIMUM #10 WIRE (3/4"C).

4. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 126-160 FEET, ARE TO HAVE #10 MINIMUM BRANCH CIRCUIT

WIRING THROUGHOUT CIRCUIT (3/4”C).\

5. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 161-205 FEET, ARE TO HAVE #8 MINIMUM BRANCH CIRCUIT WIRING HOMERUN (1"C.) FROM PANEL CIRCUIT BREAKER TO FIRST DEVICE AND #10 BRANCH CIRCUIT WIRING THROUGHOUT THE REMAINDER OF THE CIRCUIT (3/4"C.). NOT LESS THAN THE FIRST 125 FEET OF COMBINED HOMERUN AND BRANCH

CIRCUIT TO BE MINIMUM #8 WIRE (1"C.)

6. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 206-230 FEET, ARE TO HAVE #8 MINIMUM BRANCH CIRCUIT WIRING

THROUGHOUT CIRCUIT (1"C.).

7. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 231-250 FEET, ARE TO HAVE #6 MINIMUM BRANCH CIRCUIT WIRING HOMERUN (1-1/4"C.) FROM PANEL CIRCUIT BREAKER TO FIRST DEVICE AND #10 BRANCH CIRCUIT WIRING THROUGHOUT THE REMAINDER OF THE CIRCUIT (3/4"C.). NOT LESS THAN THE FIRST 175 FEET OF COMBINED HOMERUN AND

BRANCH CIRCUIT TO BE MINIMUM #6 WIRE (1-1/4"C.).

8. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 251-325 FEET, ARE TO HAVE #6 MINIMUM BRANCH CIRCUIT WIRING HOMERUN (1-1/4"C.) FROM PANEL CIRCUIT BREAKER TO FIRST DEVICE AND #8 BRANCH CIRCUIT WIRING THROUGHOUT THE REMAINDER OF THE CIRCUIT (1"C.). NOT LESS THAN THE FIRST 250 FEET OF COMBINED HOMERUN AND

BRANCH CIRCUIT TO BE MINIMUM #6 WIRE (1-1/4"C.).

9. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUIT CONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TO ANY DEVICE ON THE CIRCUIT IS 326-370 FEET FROM THE PANEL, ARE TO HAVE #6 MINIMUM

BRANCH CIRCUIT WIRING THROUGHOUT CIRCUIT (1-1/4"C.).

10. 120 VOLT BRANCH CIRCUITS SERVING RECEPTACLES FOR COMPUTER WORKSTATIONS (IE OUTLETS WITH 'C' DESIGNATION) SHALL HAVE MINIMUM CONDUCTOR SIZE OF #10. #10 MINIMUM CONDUCTOR SIZE SHALL BE INCREASED IF

REQUIRED TO COMPLY WITH GENERAL NOTES ABOVE.

11. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF FIXTURES.

12. COORDINATE EXACT LOCATION OF LIGHTING FIXTURES IN ALL MECH. ROOMS, AND SPACES WITH NO CEILING (EXPOSED STRUCTURE AREAS), SPACES, ETC., WITH DUCTWORK INSTALLER PRIOR TO ROUGH-IN. LOCATE BELOW

DUCTWORK (8'-0" A.F.F. MINIMUM) CENTERED IN ROOM AS MUCH AS FEASIBLE.

13. COORDINATE EXACT INSTALLATION REQUIREMENTS OF OUTLETS IN MILLWORK WITH ARCHITECTURAL DRAWINGS AND ACCEPTED MILLWORK SHOP DRAWINGS.

14. VERIFY EXACT LOCATION OF ALL MECH. EQUIP. INCLUDING WALL SWITCHES, T'STATS, ETC. WITH MECH. CONTRACTOR AND MECH. DRAWINGS.

15. REFER TO MECHANICAL EQUIPMENT SCHEDULE, FOR RESPECTIVE CONDUIT/CONDUCTORS, DISCONNECTS, MISC. EQUIPMENT REQUIRED FOR ALL MECHANICAL AND PLUMBING EQUIPMENT. REFER TO PANEL SCHEDULES FOR

CIRCUITS NUMBERS OF CIRCUITS FOR MECHANICAL AND PLUMBING EQUIPMENT.

16. VISIT AND CAREFULLY EXAMINE THOSE PORTIONS OF THE BUILDING AND SITE AFFECTED BY THIS WORK BEFORE SUBMITTING PROPOSALS, SO AS TO BECOME FAMILIAR WITH EXISTING CONDITIONS AND DIFFICULTIES THAT WILL AFFECT EXECUTION OF THE WORK. SUBMISSION OF A PROPOSAL WILL BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE AND LATER CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE OF

DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED.

17. READ SPECIFICATIONS.

18. SEE RISER DIAGRAMS AND BUILDING PLANS.

19. ALL EMPTY CONDUITS ARE TO HAVE PULL-STRINGS PROVIDED IN THEM.

20. EXISTING CONDITIONS AND UTILITIES INDICATED ARE TAKEN FROM EXISTING CONSTRUCTION DOCUMENTS, VARIOUS SURVEYS, AND FIELD INVESTIGATIONS. IT IS TO BE UNDERSTOOD THAT UNFORESEEN CONDITIONS PROBABLY EXIST AND NEW WORK MAY NOT BE FIELD LOCATED EXACTLY AS SHOWN ON THE DRAWINGS. COOPERATION WITH OTHER TRADES IN ROUTING AND/OR BURIAL DEPTHS AS DETERMINED DURING CONSTRUCTION AND AS DIRECTED BY THE ARCHITECT/ENGINEER MAY BE NECESSARY AND IT IS INTENDED THAT SUCH DEVIATIONS SHALL BE CONSIDERED A PART OF THIS CONTRACT. IT IS ALSO UNDERSTOOD THAT THE PLANS ARE NOT COMPLETELY TO SCALE. THIS CONTRACTOR IS TO FIELD VERIFY DIMENSIONS OF ALL SITE UTILITIES, ETC., PRIOR TO BID AND INCLUDE ANY DEVIATIONS IN THE CONTRACT.

21. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO LOCATE ALL EXISTING UTILITIES WHETHER SHOWN ON PLANS OR NOT AND TO PROTECT THEM FROM DAMAGE. THE CONTRACTOR SHALL BEAR ALL EXPENSE FOR REPAIR OR REPLACEMENT OF UTILITIES OR OTHER PROPERTY DAMAGED BY OPERATIONS IN CONJUNCTION WITH THE COMPLETION OF THIS WORK. THE CONTRACTOR SHALL LOCATE ALL UTILITIES (BOTH KNOWN AND UNKNOWN) IN AREA OF WORK PRIOR TO EXCAVATION WITH THE USE OF ELECTRONIC LOCATOR/TRACER DEVICES AND EQUIPMENT SUITABLE FOR SUCH USE. REFLECT LOCATED UTILITIES ON AS-BUILT DOCUMENTS.

22. REMOVE EXISTING POWER, LIGHTING, SYSTEMS, MATERIAL AND EQUIPMENT WHICH ARE MADE OBSOLETE OR WHICH INTERFERE WITH THE CONSTRUCTION OF THE PROJECT.

23. REINSTALL ANY SUCH POWER, LIGHTING, SYSTEMS, MATERIALS AND EQUIPMENT WHICH ARE REQUIRED TO REMAIN ACTIVE FOR THE FACILITY TO BE FULLY FUNCTIONAL.

24. REMOVE ALL EXISTING ELECTRICAL IN AREAS OF REMODELING UNLESS SPECIFICALLY NOTED OTHERWISE, OR UNLESS REQUIRED FOR CONTINUITY OF CIRCUITS IN AREAS NOT IN REMODEL AREA.

25. ALL EXISTING ELECTRICAL IS NOT SHOWN. IT IS THE CONTRACTORS RESPONSIBILITY TO BECOME FAMILIAR WITH ALL EXISTING CONDITIONS PRIOR TO BID, AND INCLUDE IN HIS BID THE REMOVAL OF ALL ELECTRICAL EQUIPMENT, WIRE, CONDUIT, DEVICES, FIXTURES, ETC. THAT IS NOT BEING REUSED, BACK TO ITS SOURCE.

26. ALL RECEPTACLES, DEVICES AND EQUIPMENT NOT SHOWN, AND IN AREAS OUTSIDE OF REMODELING SHALL REMAIN ACTIVE UNLESS OTHERWISE NOTED. FURNISH AND INSTALL ACCESSIBLE JUNCTION BOXES AND REWORK EXISTING CIRCUITS AS REQUIRED TO MAINTAIN CIRCUIT CONTINUITY TO RECEPTACLES, DEVICES AND EQUIPMENT REMAINING.

27. ALL CONDUIT TO BE CONCEALED UNLESS IMPOSSIBLE DUE TO EXISTING CONDITIONS (I.E. EXPOSED CEILINGS, BUILDING EXTERIOR WALL RUNS, IMPOSSIBLE UNDERGROUND RUNS). CONCEAL ALL CONDUITS ABOVE CEILINGS OR IN

WALL/COUNTERS.

28. ALL NEW DEVICES TO BE FLUSH MOUNTED UNLESS SPECIFICALLY NOTED OTHERWISE.

GENERAL NOTES:

CODE REFERENCE:

NATIONAL ELECTRICAL CODE: 2020

CEILING OUTLET BOX AND FLUORESCENT OR LED FIXTURE

WALL OUTLET BOX AND FLUORESCENT OR LED FIXTURE

SEE FIXTURE SCHEDULE

SEE FIXTURE SCHEDULE

d d

SYMBOL LEGEND

SYMBOL DESCRIPTION DESIGN SELECTION APPROVED SUBSTITUTION APPROVED SUBSTITUTION REMARKS

OUTLET BOX AND FLUORESCENT OR LED LIGHT

FIXTURE ON EMERGENCY SYSTEM BRANCH

CIRCUIT (LIFE SAFETY BRANCH)

SEE FIXTURE SCHEDULE d

OUTLET BOX AND FLUORESCENT OR LED IN COVE OR

MILLWORK. COORDINATE WITH ARCHITECTURAL PLANS

SEE FIXTURE SCHEDULE d

SYMBOL LEGEND

SYMBOL DESCRIPTION DESIGN SELECTION APPROVED SUBSTITUTION APPROVED SUBSTITUTION REMARKS

ELECTRICAL SYMBOL LEGEND

NOTES:

1. ALL DEVICES TO BE GREY WITH SMOOTH METAL #302 S.S. PLATES UNLESS OTHERWISE NOTED.

2. DASHED ITEM DENOTES "EXISTING".

3. "R" BY DEVICE DENOTES EXISTING TO BE REMOVED COMPLETELY.

4. "H" BY DEVICE DENOTES DEVICE TO BE MOUNTED HORIZONTALLY.

5. MOUNT SWITCHES AT 48" AFF TO TOP, SEE ARCHITECTURAL ELEVATIONS.

6. SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

7. ALL ITEMS NOTED ON THE LEGENDS DO NOT NECESSARILY APPEAR ON PLANS.

REMARKS:

a. U.L. LISTED FOR WET LOCATION IN CLOSED POSITION.

b. SUPPORT OUTLET BOX FROM STRUCTURE WITH (1) 3/8" ALL THREADS MINIMUM. BOXES LARGER THAN 25 SQUARE INCHES SHALL BE

SUPPORTED WITH (2) 3/8" ALL THREADS MINIMUM.

c. U.L. LISTED FOR WET LOCATION IN OPEN POSITION WITH ATTACHMENT PLUG INSERTED.

d. JUNCTION/OUTLET BOX SHALL BE SIZED AS REQUIRED FOR CONDUCTOR/DEVICE FILL PER N.E.C.

e. THREADED CONDUIT HUBS SHALL BE SIZED AND CONFIGURED AS REQUIRED FOR APPLICATION.

f. IF WITHIN 30 MILES OF THE COAST LINE, COPPER FREE CAST ALUMINUM OUTLET BOXES SHALL BE USED FOR EXTERIOR

APPLICATIONS.

g. PROVIDE KINDORF MTG. RACK FOR FREE STANDING APPLICATIONS. KINDORF SHALL BE PVC COATED FOR EXTERIOR APPLICATIONS.

ALL CUT ENDS ARE TO BE SEALED.

h. WHEN SURFACE JUNCTION BOX SYMBOL IS COMBINED WITH DEVICE SYMBOL, PROVIDE APPROPRIATE SURFACE PLATE FOR OUTLET

APPLICATION.

i. MAINTAIN WORKING CLEARANCES IN STRICT ACCORDANCE WITH N.E.C. CORRDINATE EXACT LOCATION OF EQUIPMENT WITH ALL DISCIPLINES (I.E. STRUCTURAA, HVAC, PLUMBING, FIRE PROTECTION, KITCHEN, MILLWORK, ETC.) PRIOR TO ROUTH-IN TO MAINTAIN

CLEARANCES.

j. OUTLET BOX SHALL BE SIZED PER SYSTEM INSTALLER REQUIREMENTS.

k. COORDINATE THE TELEPONE/DATA/SYSTEMS DEVICE, WIRE, CABLE, ETC. WITH THE TELE/DATA/SYSTEMS SPECIFICATIONS, DRAWINGS AND/OR SYMBOL LEGENDS..

l. PROVIDE CONDUIT AS CALLED FOR ON SYSTEMS PLANS/SYMBOL LEGENDS.

S

S

S

S

CEILING OUTLET BOX AND HID, FLUORESCENT, LED OR

INCANDESCENT FIXTURE

WALL OUTLET BOX AND HID, FLUORESCENT, LED OR

INCANDESCENT FIXTURE

CEILING OUTLET BOX AND LIGHT FIXTURE ON EMERGENCY

SYSTEM BRANCH CIRCUIT

WALL OUTLET BOX AND HID, FLUORESCENT, LED OR

INCANDESCENT FIXTURE ON EMERGENCY SYSTEM

BRANCH CIRCUIT

WALL OUTLET BOX AND EMERGENCY BATTERY UNIT

EQUIPMENT LIGHT FIXTURE, TRIANGLES IDENTIFY NUMBER

OF FIXTURE HEADS. WALL MTD.

CEILING OUTLET BOX AND EXIT SIGN LIGHT

FIXTURE ON EMERGENCY SYSTEM BRANCH

CIRCUIT (LIFE SAFETY BRANCH) SHADING

INDICATES NUMBER OF FACES AND ORIENTATION

WALL OUTLET BOX AND EXIT SIGN LIGHT FIXTURE

ON EMERGENCY SYSTEM BRANCH CIRCUIT (LIFE

SAFETY BRANCH)

POLE WITH MOUNTING ARM AND CUT-OFF LIGHT FIXTURE.

BOXES INDICATE NUMBER OF FIXTURES AND ORIENTATION

WALL OUTLET BOX AND 20 AMP SINGLE POLE SWITCH ('a'

INDICATES SWITCH-LEG)

WALL OUTLET BOX AND 20 AMP DOUBLE POLE SWITCH

WALL OUTLET BOX AND 20 AMP THREE-WAY SWITCH

WALL OUTLET BOX AND 20 AMP FOUR-WAY SWITCH

SEE FIXTURE SCHEDULE

SEE FIXTURE SCHEDULE

SEE FIXTURE SCHEDULE

SEE FIXTURE SCHEDULE

SEE FIXTURE SCHEDULE

SEE FIXTURE SCHEDULE

SEE FIXTURE SCHEDULE

SEE FIXTURE SCHEDULE

P&S #PS20AC1 HUBBELL #HBL1221 LEVITON #1221-2

P&S #PS20AC2

d d d d d d d d d d d

HUBBELL #HBL1222 LEVITON #1222-2

P&S #PS20AC3 HUBBELL #HBL1223 LEVITON #1223-2

P&S #PS20AC4 HUBBELL #HBL1224 LEVITON #1224-2

a

REMOTE DRIVER AS CALLED FOR ON

DRAWINGS OR IN

SPECIFICATIONS.

RD

S

S

S

D

D

OUTLET BOX AND 20 AMP, 1P MANUAL MOTOR CONTROLLER

WITHOUT OVERLOADS. RATED 1 HP @ 120V, 2 HP @ 277V.

OUTLET BOX AND 20 AMP, 2P MANUAL MOTOR CONTROLLER

WITHOUT OVERLOADS. RATED 2 HP @ 240V.

OUTLET BOX AND 30 AMP, 3P MANUAL MOTOR CONTROLLER

WITHOUT OVERLOADS. RATED 7.5 HP @ 240V, 10 HP @ 480V.

WALL OUTLET BOX AND DIMMER SWITCH, AS NOTED ON

PLANS

WALL OUTLET BOX AND THREE-WAY DIMMER SWITCH AS

NOTED ON PLANS

P&S #PS20AC1/7801P HUBBELL #HBL1221/LOCK

BRACKET

d

P&S #PS20AC2/7801P HUBBELL #HBL1222/LOCK

BRACKET

d

P&S #7803MD/7801P HUBBELL #HBL7810D/LOCK

BRACKET

LEVITON #MS303-DS/LOCK

BRACKET

d

LUTRON d

LUTRON d

M

2M

M3

S

AUTOMATIC WALL SWITCH, DUAL TECHNOLOGY (PIR)

PASSIVE INFRARED AND ULTRASONIC, DIP SWITCH

PROGRAMMING, AUTOMATIC OR MANUAL OPERATION.

RATED: 800 WATTS @ 120V, 1200 WATTS @ 277V.

WATTSTOPPER

DW-100

d

OS

SENSOR SWITCH, INC. GREENGATE

0-10 VOLT DIMMING WALL SWITCH OCCUPANCY SENSOR,

DUAL TECHNOLOGY, PASSIVE INFRARED (PIR) AND

ULTRASONIC, DIP SWITCH PROGRAMMING, MANUAL ON-

AUTO OFF OPERATION. RATED 1000 WATTS AT 120V, 1200

WATTS AT 277V.

WATT STOPPER CAT#

DW-311

d

D OS

LEVITON #1221-2/LOCK

BRACKET

LEVITON #1222-2/LOCK

BRACKET

S WALL OUTLET BOX AND 20 AMP SINGLE POLE KEY SWITCH dP&S #PS20AC1-L HUBBELL #HBL1221L LEVITON #1221-2L

K

S

S

WALL OUTLET BOX AND 20 AMP THREE-WAY KEY SWITCH

WALL OUTLET BOX AND 20 AMP

FOUR-WAY KEY SWITCH

d d

P&S #PS20AC3-L HUBBELL #HBL1223L LEVITON #1223-2L

P&S #PS20AC4-L HUBBELL #HBL1224L LEVITON #1224-2L

3K

4K

S

S

FLUSH WALL OUTLET BOX AND 20 AMP

SINGLE POLE SWITCH, WITH DIE CAST

WEATHERPROOF COVER

FLUSH WALL OUTLET BOX AND 20 AMP SINGLE POLE SWITCH,

WITH LOCKING STAINLESS STEEL WEATHERPROOF COVER.

MOUNT OUTLET BOX HORIZONTALLY.

DEVICE: P&S #PS20AC1

PLATE: P&S #CA1-G

DEVICE: HUBBELL #HBL1221

PLATE: P&S #CA1-G

DEVICE: LEVITON #1221-2 a, d

DEVICE: P&S #20AC1

PLATE: P&S #WPH-1L

DEVICE: HUBBELL #HBL1221

PLATE: P&S #WPH-1L

DEVICE: LEVITON #1221-2 a, d

WP

WPL

S

CAST IRON ZINC PLATED SURFACE MTD. OUTLET BOX AND 20

AMP SINGLE POLE SWITCH, WITH COPPER FREE CAST

ALUMINUM WEATHERPROOF COVER

DEVICE: P&S #PS20AC1

BOX AND PLATE:

APPLETON #FS/FD/FSK-WT2

DEVICE: HUBBELL

#HBL1221 BOX AND PLATE:

APPLETON #FS/FD/FSK-WT2

DEVICE: LEVITON #1221-2 a, d, e, f, g

WP

S

WALL OUTLET BOX AND 6 HOUR MECHANICAL TIME SWITCH

WITH HOLD, RATED 20 AMPS @ 120V, 10 AMPS @ 277V

TORK #

A506HH

INTERMATIC #

FF6HH

ST

d

CEILING MOUNTED (PIR) PASSIVE INFRARED AND

ULTRASONIC OCCUPANCY SENSOR. OMNI DIRECTIONAL 360

DEGREE PIR COVERAGE. PROVIDE MATCHING POWER

PACK.

CEILING MOUNTED LOW VOLTAGE PHOTOSENSOR

COMPATIBLE WITH 0 - 10 VDC ELECTRONIC DIMMING

BALLASTS AND LED DRIVERS THAT DIMS FIXTURES AS

DAYLIGHT INCREASES. 20 TO 60 FOOT CANDLE ADJUSTABLE

SET POINT PROGRAMMABLE VIA WIRELESS PROGRAMMER.

WALL OR CEILING MOUNTED (PIR) PASSIVE INFRARED AND

ULTRASONIC OCCUPANCY SENSOR. PROVIDE MATCHING

POWER PACK.

WATTSTOPPER

DT-305

d

WATTSTOPPER

LS-301

d

WATTSTOPPER

DT-205

d

DT-305

OS

LS-301

PS

OS

DT-205

SENSOR SWITCH, INC. GREENGATE

SENSOR SWITCH,

INC.

GREENGATE

SENSOR SWITCH, INC. GREENGATE

OCCUPANCY SENSOR SYSTEM POWER PACK(S) AS REQUIRED

FOR LOADS AND ZONES. REFER TO SPECIFICATIONS AND

DETAILS. N = NORMAL BRANCH, Q = EQUIPMENT BRANCH

WATTSTOPPER d P

SENSOR SWITCH,

INC.

GREENGATE

* = N or Q

WALL OUTLET BOX AND 20 AMP

SINGLE RECEPTACLE

WALL OUTLET BOX AND 20 AMP

DUPLEX RECEPTACLE

TWO GANG WALL OUTLET BOX AND TWO

20 AMP DUPLEX RECEPTACLES

WALL OUTLET BOX AND 20 AMP DUPLEX RECEPTACLE

MOUNTED ABOVE COUNTER. COORDINATE WITH

ARCHITECTURAL PLANS

P&S #5361 HUBBELL #HBL5361 LEVITON #5351 d

P&S #PS5362 HUBBELL #HBL5352 LEVITON #5362 d

(2)-P&S #PS5362 (2)-HUBBELL #HBL5352 (2)-LEVITON #5362 d

P&S #PS5362 HUBBELL #HBL5352 LEVITON #5362 d

DIGITAL CEILING MOUNTED (PIR) PASSIVE INFRARED AND

ULTRASONIC OCCUPANCY SENSOR. OMNI DIRECTIONAL 360

DEGREE PIR COVERAGE. PROVIDE MATCHING

CONTROLLER.

WATTSTOPPER

LMDC-100

d

LMDC-100

OS

SENSOR SWITCH, INC. GREENGATE

DIGITAL LIGHTING SYSTEM ON\OFF ROOM CONTROLLER(S)

AS REQUIRED FOR SENSORS, LOADS AND ZONES. REFER TO

SPECIFICATIONS AND DETAILS.

WATTSTOPPER d

RC

SENSOR SWITCH,

INC.

GREENGATE

DIGITAL WALL OR CEILING MOUNTED (PIR) PASSIVE

INFRARED AND ULTRASONIC OCCUPANCY SENSOR. PROVIDE

MATCHING CONTROLLER.

WATTSTOPPER

LMDX-100

d

OS

LMDX-100 SENSOR SWITCH,

INC.

GREENGATE

DRC

WATT STOPPER dDIGITAL LIGHTING SYSTEM DIMMING ROOM CONTROLLER(S)

AS REQUIRED FOR SENSORS, LOADS AND ZONES.

CONTROLLER(S) TO PROVIDE 0 - 10 VOLT DIMMING OUTPUT

FOR EACH ON/OFF RELAY. REFER TO SPECIFICATIONS AND

DETAILS.

SENSOR SWITCH GREENGATE

WALL OUTLET BOX AND 20 AMP DUPLEX RECEPTACLE

MOUNTED ABOVE COUNTER. COORDINATE WITH

ARCHITECTURAL PLANS

P&S #PS5362 HUBBELL #HBL5352 LEVITON #5362 d

WALL OUTLET BOX AND 20 AMP RED DUPLEX RECEPTACLE

CONNECTED TO EMERGENCY SYSTEM BRANCH CIRCUIT

P&S #5362-RED HUBBELL #HBL5352-RED LEVITON #5362-RED d

TWO GANG WALL OUTLET BOX AND TWO 20 AMP RED

DUPLEX RECEPTACLE CONNECTED TO EMERGENCY SYSTEM

BRANCH CIRCUIT

(2)-P&S #5362-RED (2)-HUBBELL #HBL5352-RED (2)-LEVITON #5362-RED d

TV

WALL OUTLET BOX AND 20 AMP DUPLEX RECEPTACLE FOR

TELEVISION, MOUNT ADJACENT TO TELEVISION OUTLET AT

84"AFF UNLESS OTHERWISE NOTED.

P&S #PS5362 HUBBELL #HBL5352 LEVITON #5362 d

G

WALL OUTLET BOX AND 20 AMP SELF-TESTING GFI DUPLEX

RECEPTACLE

P&S #2097TRWRGRY HUBBELL #GF5362SGGY LEVITON #G5362-WTG d

CLG

EWC

TWO GANG CEILING OUTLET BOX AND TWO 20 AMP DUPLEX

RECEPTACLES

WALL OUTLET BOX AND 20 AMP SELF-TESTING GFI DUPLEX

RECEPTACLE FOR ELECTRIC WATER COOLER, COORDINATE

WITH EWC INSTALLER FOR MOUNTING REQUIREMENTS.

(2)-P&S #5362 (2)-HUBBELL #HBL5352 (2)-LEVITON #5362 b, d

P&S #2097TRWRGRY HUBBELL #GF5362SGGY LEVITON #G5362-WTG d

CLG

CLG

CEILING OUTLET BOX AND 20 AMP SINGLE RECEPTACLE

CEILING OUTLET BOX AND 20 AMP DUPLEX RECEPTACLE

P&S #5361 HUBBELL #HBL5361 LEVITON #5351 b, d

P&S #5362 HUBBELL #HBL5352 LEVITON #5362 b, d

WPG FLUSH WALL OUTLET BOX AND 20 AMP WEATHER RESISTANT

SELF-TESTING GFCI DUPLEX RECEPTACLE WITH CAST

ALUMINUM WEATHER PROOF IN USE COVER

P&S #2097TRWRGRY WITH

THOMAS & BETTS #CKMGV

OR INTERMATIC

#WP1010MC

HUBBELL #GF5362SGGY WITH

THOMAS & BETTS #CKMGV OR

HUBBELL #WP26M COVER

LEVITON #G5362-WTG WITH

THOMAS & BETTS #CKMGV

OR INTERMATIC

#WP1010MC

a, d

WPL

FLUSH WALL OUTLET BOX AND 20 AMP WEATHER

RESISTANT SELF-TESTING GFCI DUPLEX RECEPTACLE WITH

LOCKING STAINLESS STEEL WEATHER PROOF IN USE

COVER. PROVIDE LOCK WITH COVER. ALL LOCKS SHALL BE

SET TO THE SAME KEY

P&S #2097TRWRGRY WITH

THOMAS & BETTS #CKMGV

OR INTERMATIC #WP1010MC

HUBBELL #GF5362SGGY WITH

THOMAS & BETTS #CKMGV OR

HUBBELL #WP26M COVER

LEVITTON #G5362-WTG WITH

THOMAS & BETTS #CKMGV

OR INTERMATIC #WP1010MC

a, d

WPG CAST IRON PLATED SURFACE MTD. OUTLET BOX AND 20 AMP

WEATHER RESISTANT SELF-TESTING GFCI DUPLEX

RECEPTACLE WITH CAST ALUMINUM WEATHERPROOF IN USE

COVER

P&S #2097TRWRGRY WITH

APPLETON #FS-ID AND

THOMAS & BETTS #CKMGV

OR INTERMATIC #WP1010MC

HUBBELL #GF5362SGGY

APPLETON

#FS-ID AND HUBBELL #WP26M

COVER

LEVITTON #G5362-WTG

APPLETON #FS-ID AND

THOMAS & BETTS #CKMGV

OR INTERMATIC

#WP1010MC

a, c, d, e f, g

WALL OUTLET BOX AND SPECIAL PURPOSE RECEPTACLE AS

NOTED ON PLANS

P&S HUBBELL LEVITON d

(IG)

(C)

(IG)

(C)

HUBBELL #B-2436/S-3625/

SB3083 WITH HUBBELL #HBL5352

WALL OUTLET BOX AND RECESSED 15 AMP

CLOCK RECEPTACLE STAINLESS STEEL

CAST IRON FULLY ADJUSTABLE FLOOR OUTLET BOX AND 20

AMP DUPLEX RECEPTACLE WITH CARPET FLANGE

CAST IRON FULLY ADJUSTABLE TWO GANG FLOOR OUTLET

BOX WITH TWO (2) RECEPTACLES AND CARPET FLANGE.

(PROVIDE SPECIAL RECEPTACLES, I.E. ISOLATED GROUND

OR BLACK COMPUTER TYPE WHERE NOTED)

CAST IRON FULY ADJUSTABLE TWO GANG FLOOR OUTLET

BOX WITH 20 AMP DUPLEX RECEPTACLE, ONE PDS

(VOICE/DATA) OUTLET AND CARPET FLANGE (PROVIDE

SPECIAL RECEPTACLES, I.E. ISOLATED GROUND OR BLACK

COMPUTER TYPE WHERE NOTED)

POWER POLE WITH 20 AMP DUPLEX RECEPTACLE AS NOTED

ON PLANS.

HANGING DUPLEX RECEPTACLE. SEE DETAILS.

HANGING QUAD RECEPTACLE. SEE DETAILS

2 HR. FIRE RATED FLUSH POKE-THRU WITH INTEGRAL

15 AMP DUPLEX RECEPTACLE AND TWO COMMUNICATIONS

PORTS. DIE CAST ALUMINUM FLANGE WITH BRASS FINISH

FLUSH WALL JUNCTION BOX AND BLANK PLATE

JUNCTION BOX AND BLANK PLATE ABOVE CEILING

SURFACE JUNCTION BOX AND BLANK PLATE, WALL MTD. OR

MTD. TO CEILING/STRUCTURE AS INDICATED

SURFACE MTD. WEATHERPROOF JUNCTION BOX AND COVER,

AS NOTED ON PLANS

PUSHBUTTON, AS NOTED, MOUNTED AT 48" TO TOP

MOTOR CONNECTION, AS NOTED

P&S #S3733-55

WALKER 880 CSI/828P/817C

WITH P&S #PS5362

STEEL CITY #641/P-64-DU/

P64-CP WITH LEVITON #5362

d

WALKER 880 CS2/(2)828P/

827C WITH (2) P&S #PS5362

HUBBELL #B-4233/(2)S-3625/

SB3084 WITH (2) HUBBELL

#HBL5352

STEEL CITY #642 WITH

(2)P-64-DU/P64-2G-CP

WITH (2) LEVITON #5362

d

WALKER 880 CS2/828P/829

CK-1/827C WITH P&S #PS5362

HUBBELL #B-4233/S-3625/

S-2625/SB3084 WITH HUBBELL

#HBL5352

STEEL CITY #642/P-64-

3/4-2/P64-DU/P64-

2G-CP WITH LEVITON #5362

d, j, k, l d d, j, k

WIREMOLD #RC7ATCBS WALKER #1570-A-BRS STEEL CITY #PT-700-A-BRS d, j

STEEL CITY RACO d

STEEL CITY RACO b, d

STEEL CITY RACO b, d, g, h

HOFFMAN d, g, h d i

WP

RELAY, AS NOTED

CONTROL AND/OR POWER CONNECTION ON EQUIPMENT

TIME CLOCK, 2-POLE, RESERVE SPRING, 24 HR. WITH

CONTACTS AND COIL VOLTAGE AS REQUIRED FOR CIRCUITS

(UNLESS OTHERWISE NOTED)

PHOTO CELL

METER, AS NOTED

i

TORK

(SEE DETAIL)

PARAGON

(SEE DETAIL)

INTERMATIC

(SEE DETAIL)

i

TORK (SEE DETAIL) PARAGON (SEE DETAIL) INTERMATIC (SEE DETAIL)

R

C

EMERGENCY RELAY, AS NOTED

ER

BAS

BUILDING AUTOMATION SYSTEM CONTROL PANEL. PROVIDE

20 AMP, 120 VOLT DEDICATED CIRCUIT, WITH 3#12 MIN.

CONDUCTORS IN 1/2 INCH CONDUIT TO NEAREST NORMAL

POWER PANEL. WHERE CIRCUIT IS NOT PROVIDED OR

NOTED, USE 20 AMP, 1 P CIRCUIT BREAKER MARKED SPARE

IN PANEL SCHEDULE.

BUSBAR

MAGNETIC MOTOR STARTER, MOTOR CONTROLLER OR

CONTACTOR, AS NOTED

SQUARE "D" G.E. SIEMENS g, i

DISCONNECT SWITCH, SIZE AS NOTED SQUARE "D" G.E. SIEMENS g, i

AFD

STARTER/DISCONNECT SWITCH, SIZE AS NOTED

ADJUSTABLE FREQUENCY DRIVE W/DISC. SW. FURNISHED BY

DIVISION 15

SQUARE "D" G.E. SIEMENS g, i i

120/208V BRANCH CIRCUIT PANELBOARD SURFACE MOUNTED

120/208V BRANCH CIRCUIT PANELBOARD FLUSH MOUNTED

277/480V BRANCH CIRCUIT PANELBOARD SURFACE MOUNTED

277/480V BRANCH CIRCUIT PANELBOARD FLUSH MOUNTED

SQUARE "D" G.E. SIEMENS i

SQUARE "D" G.E. SIEMENS

SQUARE "D" G.E. SIEMENS

SQUARE "D" G.E. SIEMENS

i i i

INTEGRATED FACILITIES SWITCHBOARD (IFS) - 2 SECTION

INTEGRATED FACILITIES SWITCHBOARD (IFS) - 3 SECTION

SQUARE "D" G.E. SIEMENS

SQUARE "D" G.E. SIEMENS

T O

RUSSELECTRIC ASCO

TRANSFORMER

AUTOMATIC TRANSFER SWITCH

SYSTEMS PANEL - SURFACE MOUNTED

SYSTEMS PANEL - FLUSH MOUNTED

SQUARE "D" G.E. SIEMENS i i

SEE SYSTEMS LEGEND/SPECS i, j

SEE SYSTEMS LEGEND/SPECS i, j

LIGHTING CONTROL OR DIMMER PANEL - SURFACE MOUNTED

LIGHTING CONTROL OR DIMMER PANEL - FLUSH MOUNTED

BRANCH CIRCUIT CONDUIT CONCEALED ABOVE CEILING OR IN

WALL. SLASH MARKS INDICATE NUMBER OF CONDUCTORS

(GROUND WIRE NOT SHOWN). TWO CONDUCTORS PLUS

GROUND REQUIRED (UNLESS OTHERWISE NOTED OR MARKED)

E

BRANCH CIRCUIT CONDUIT CONCEALED BELOW SLAB OR

UNDERGROUND

EMERGENCY SYSTEM BRANCH CIRCUIT CONDUIT,

CONCEALED (LIFE SAFETY BRANCH)

C LEGALLY REQUIRED STANDBY SYSTEM BRANCH CIRCUIT

CONDUIT, CONCEALED (CRITICAL BRANCH)

X SECURITY BRANCH CIRCUIT CONDUIT, CONCEALED

G

CONDUIT SEAL-OFF FITTING

GROUND WIRE, CONCEALED

GROUND OR GROUND ROD AS NOTED

CROUSE HINDS APPLETON e

Q OPTIONAL STANDBY SYSTEM BRANCH CIRCUIT CONDUIT,

CONCEALED (EQUIPMENT BRANCH)

DC DIRECT CURRENT EMERGENCY SYSTEM WIRE AND CONDUIT,

CONCEALED

CW

UPS

CONTROL WIRING AND CONDUIT, CONCEALED

UNINTERUPTABLE POWER SYSTEM BRANCH CIRCUIT WITH

ISOLATED GROUND ON EMERGENCY SYSTEM (LIFE SAFETY

BRANCH)

HOME RUN WIRING. ONE CIRCUIT PER ARROW HEAD

CONDUIT CAPPED OFF

CONDUIT CONTINUED

CONDUIT RUN UP

CONDUIT RUN DOWN

(IG)

(C)

CAST IRON FULY ADJUSTABLE THREE GANG…