2024-118_-_Combined_Mechanical_-_S&S.pdf

PDF 6 MB Posted

Attached to
Michigan Avenue Warehouse Renovation
Solicitation number
ITB 25-098
Issued by
Lee County, Fruitville CDP, Florida

About this file

These mechanical design documents are for a Warehouse Conversion to Parks & Recreation Department project located at 2801 Michihan Avenue in Fort Myers, Florida, prepared by Grace Hebert Curtis Architects and Matern Professional Engineering (MPE). The project involves renovating mechanical systems for two buildings (North and South), with a total combined renovated area of approximately 14,574 square feet. The mechanical plans detail the replacement of existing HVAC equipment, including air handling units (AHU-N-1, AHU-S-1), condensing units, blower coil units, exhaust fans, and variable air volume (VAV) terminal boxes. The project is designed under the 2023 8th Edition Florida Building Code and Florida Fire Prevention Code, with mechanical systems complying with ASHRAE standards 62.1-2019 and 90.1-2019.

The mechanical systems are designed with energy efficiency and comfort in mind, utilizing electronically commutated motors (ECM), MERV 13 filtration, and building automation system (BAS) controls. The North Building is being designed primarily for records storage, while the South Building will serve multiple office and public spaces. The equipment specifications include Trane and Mitsubishi units with specific performance characteristics, such as cooling capacities ranging from 18,000 to 240,000 BTU and SEER ratings up to 20.2. The project includes provisions for ventilation, humidity control, and energy optimization routines, with systems capable of occupancy-based operation, optimal start functionality, and comprehensive alarm and notification systems.

View the file

Other files

File Type Posted
Michigan_Avenue_Warehouse_Renovation_(Addendum_#19_Revision).pdf PDF
Michigan_Avenue_Warehouse_Renovation_(Addendum_#10_Revision).pdf PDF
DIVISION_22_-_PLUMBING.pdf PDF
CFM_Parks_and_Rec_-_Landscape_Plans_-_South_Parcel.pdf PDF
DIVISIONS_27_&_28_-_SECURITY_&_COMMS.pdf PDF
CoFM_Warehouse_Conversion_Parks_and_Records_Dept_Arch_Spec_Binder.pdf PDF
CFM_Parks_and_Rec_-_Civil_Plans_-_North_Parcel.pdf PDF
2024-118_-_Combined_Plumbing_-_S&S.pdf PDF
2024-118_-_CoFM_Warehouse_-_Combined_Electrical.pdf PDF
20250619_-_Warehouse_Convert_to_Parks_&_Rec_Department_100%_CD_KMW.pdf PDF
CFM_Parks_and_Rec_-_Tech_Specifications.pdf PDF
2025.06.19-_Exist_Warehouse_to_Parks_Rec_-_Structural_Permit_Set_SS.pdf PDF
DIVISON_26_-_ELECTRICAL.pdf PDF
DIVISON_21_-_FIRE_PROTECTION.pdf PDF
CFM_Parks_and_Rec_-_Civil_Plans_-_South_Parcel.pdf PDF
2024-118_-_Combined_Fire_Protection_-_S&S.pdf PDF
CFM_Parks_and_Rec_-_Landscape_Plans_-_North_Parcel.pdf PDF
DIVISION_23_-_HVAC.pdf PDF
SRF_SupplementaryConditions_EM_Contract_(August_2022).pdf PDF
SRF_SupplementaryConditions_Construction_Contract_(August_2022).pdf PDF
FHWA-1273_(10_23)_.pdf PDF
Notice_of_Award.docx DOCX document
2_CFR_Part_200_app_II_(up_to_date_as_of_4-28-2025).pdf PDF
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT DESIGN CONDITIONS - SOUTH BUILDING

TEMPERATURE CONDITIONS BUILDING LOAD CONDITIONS

OUTDOOR INTERNAL LOADS

DRY BULB

(F)

WET

BULB (F)

COMMENTS QUANTITY UNITS COMMENTS

SUMMER 95 78 (0.40% mean coincided db/wb) PEOPLE N/A PEOPLE BASED ON FURNITURE LAYOUTS

SUMMER NA NA

(0.40% wetbulb used for Cooling

Tower Selection)

LIGHTING VARIES W/SF BASED ON FBC TABLE C405.3.2(2)

WINTER 40 X (99.6% db) EQUIPMENT VARIES W

BASED ON FURNITURE LAYOUT

AND ASHRAE FUNDAMENTALS

DAILY RANGE X VENTILATION AIR VARIES

CFM/SQFT &

CFM/PERSON

BASED ON ASHRAE 90.1

LOCATION BASED ON ASHRAE WEATHER

DATA FOR:

FORT MYERS, FL FLOOR AREA 7,080 SF RENOVATED AREA

INDOOR EXTERNAL LOADS

DRY BULB

(F)

RH % COMMENTS

"U"

FACTOR

SHADING

COEF.

COMMENTS

COOLING 75 60 WALL VARIES X EXISTING

HEATING 68 60 ROOF VARIES X EXISTING

GLAZING VARIES VARIES EXISTING

VENTILATION DETERMINATION IS BASED ON OCCUPANCY PER ASHRAE STD. 62.1-2019

ENVELOPE AND EQUIPMENT EFFICIENCIES ARE BASED ON ASHRAE STD. 90.1-2019 & THE 2023 8th EDITION FLORIDA BUILDING CODE - ENERGY CONSERVATION

THIS PROJECT IS DESIGNED UNDER THE 2023 8th EDITION FLORIDA BUILDING CODE & 2023 8th EDITION OF THE FLORIDA FIRE PREVENTION CODE

PROJECT DESIGN CONDITIONS - NORTH BUILDING

TEMPERATURE CONDITIONS BUILDING LOAD CONDITIONS

OUTDOOR INTERNAL LOADS

DRY BULB

(F)

WET

BULB (F)

COMMENTS QUANTITY UNITS COMMENTS

SUMMER 95 78 (0.40% mean coincided db/wb) PEOPLE N/A PEOPLE BASED ON FURNITURE LAYOUTS

SUMMER NA NA

(0.40% wetbulb used for Cooling

Tower Selection)

LIGHTING VARIES W/SF BASED ON FBC TABLE C405.3.2(2)

WINTER 40 X (99.6% db) EQUIPMENT VARIES W

BASED ON FURNITURE LAYOUT

AND ASHRAE FUNDAMENTALS

DAILY RANGE X VENTILATION AIR VARIES

CFM/SQFT &

CFM/PERSON

BASED ON ASHRAE 90.1

LOCATION BASED ON ASHRAE WEATHER

DATA FOR:

FORT MYERS, FL FLOOR AREA 7,494 SF RENOVATED AREA

INDOOR EXTERNAL LOADS

DRY BULB

(F)

RH % COMMENTS

"U"

FACTOR

SHADING

COEF.

COMMENTS

COOLING 78 60 RECORDS STORAGE WALL VARIES X EXISTING

COOLING 75 60 SECOND FLOOR ROOF VARIES X EXISTING

COOLING 75 60 PRINT ROOM GLAZING VARIES X EXISTING

HEATING 68 60 PRINT ROOM

VENTILATION DETERMINATION IS BASED ON OCCUPANCY PER ASHRAE STD. 62.1-2019

ENVELOPE AND EQUIPMENT EFFICIENCIES ARE BASED ON ASHRAE STD. 90.1-2019 & THE 2023 8th EDITION FLORIDA BUILDING CODE - ENERGY CONSERVATION

THIS PROJECT IS DESIGNED UNDER THE 2023 8th EDITION FLORIDA BUILDING CODE & 2023 8th EDITION OF THE FLORIDA FIRE PREVENTION CODE

TRANSFER AIR OPENINGTAO

WALL CLEANOUTWCO

TD TRENCH DRAIN

VOLUME DAMPERVD

SAF SUPPLY AIR FAN

REQUIREDREQ'D

PRESS PRESSURE

INSUL INSULATION

HORIZ HORIZONTAL

H20 WATER

EXISTINGEXIST

CONCRETE MASONARY UNITCMU

CONTINUATIONCONT

COMBINATIONCOMB

BRAKE HORSEPOWERBHP

ACCESS PANELAP

AUXILLIARYAUX

AUTOMATICAUTO

ARCHITECTURALARCH

WMS

RAF

SAN

UH

SA

RA

RM

RPM

SAU

SP

SPEC

TDH

TEMP

PSIG

PVC

RH

VAV

W

W/

W/O

WB

WC

WG

WP

RHC

RV

HW HOT WATER

PRIMARY CHILLED WATER PUMP

BOD BOTTOM OF DUCT

D

EF

AHU

OA

FDPR

APPROX

AFF

AD

CHR

CHS

DRAIN LINE

EXHAUST FAN

AIR HANDLING UNIT

OUTSIDE AIR

FIRE DAMPER

APPROXIMATELY

ABOVE FINISHED FLOOR

ACCESS DOOR

CHILLED WATER RETURN

CHILLED WATER SUPPLY

AC

FCU

COLD WATER (CITY)

BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNITS PER HOUR

CFM

CUH CABINET UNIT HEATER

DG

EAT

EVAP

EWT

EH

LAT LEAVING AIR TEMPERTURE

LB/HR

LWT

MBH

NIC

NTS

NC

NO

CW

BTU

A

BLDG

CC

CD

CH

CHWP

CLG

CO

COMPR

COND

CU FT

CU IN

DB

DHW

DIAM

DN

DWG

DX

EDH

EL

ELEC

EQ

EWB

EXP

°F

FA

FBP

FLA

FPI

FPS

FV

GA

GAL

GPH

GPM

HT

HC

HD

HP

HR

HZ

IN

KW

LBS

LDB

LIN FT

LWB

MAX

MB

MC

MIN

NO.

OD

OV

PD

PHC

PSI

AMPERES

BUILDING

COOLING COIL

CONDENSATE DRAIN

CHILLER

CHILLED WATER PUMP

CEILING

CLEAN-OUT

CONDENSATE OR CONDENSER

CUBIC FEET

CUBIC INCHES

COMPRESSOR

DRY BULB

DOMESTIC HOT WATER

DIAMETER

DOWN

DRAWING

DIRECT EXPANSION

ELECTRIC DUCT HEATER

ELEVATION

ELECTRICAL

EQUAL

ENTERING WET BULB TEMPERATURE

EXPANSION

DEGREES FAHRENHEIT

FREE AREA (SQ. FT.) 0R FACE AREA

FIELD BUILT PLENUM

FULL LOAD AMPERES

FINS PER INCH

FEET PER SECOND

FACE VELOCITY

GAUGE

GALLONS

GALLONS PER HOUR

GALLONS PER MINUTE

HEIGHT

HEATING COIL

HEAD

HORSEPOWER OR HEAT PUMP

HOUR

FREQUENCY (HERTZ)

INCH OR INCHES

KILOWATT

POUNDS

LEAVING DRY BULB TEMPERATURE

LINEAR FEET

LEAVING WET BULB

MAXIMUM

MIXING BOX

MECHANICAL CONTRACTOR

MINIMUM

NUMBER

OUTSIDE DIAMETER

OUTLET VELOCITY

PRESSURE DROP

PREHEAT COIL

POUNDS PER SQUARE INCH

FPM FEET PER MINUTE

WIRE MESH SCREEN

RETURN AIR FAN

SANITARY

UNIT HEATER

SUPPLY AIR

RETURN AIR

*REFRIGERANT HOT GAS DISCHARGE

*REFRIGERANT LIQUID LINE

*REFRIGERANT SUCTION LINE

ROOM

REVOLUTIONS PER MINUTE

SOUND ATTENUATION UNIT

STATIC PRESSURE

SPECIFICATION

TOTAL DYNAMIC HEAD

TEMPERATURE

TYPICAL

PSI GAUGE

POLYVINYL CHLORIDE

RELATIVE HUMIDITY

VARIABLE AIR VOLUME UNIT

WATT

WITH

WITHOUT

WET BULB

WATER COLUMN

WATER GAUGE

WORKING PRESSURE

REHEAT COIL

RELIEF VALVE

PSIA PSI ABSOLUTE

HB HOSE BIBB

F FIRE SPRINKLER PIPING PCHWP

FD FLOOR DRAIN

S/FDPR COMBINED SMOKE AND FIRE DAMPER

SDPR SMOKE DAMPER

FCO FLOOR CLEANOUT

FTB FAN POWERED TERMINAL BOX

SGCHS SECONDARY GLYCOL CHILLED WATER SUPPLY

SGCHR SECONDARY GLYCOL CHILLED WATER RETURN

AIR CONDITIONING

CUBIC FEET PER MINUTE

DOOR GRILLE

ENTERING AIR TEMPERATURE

ELECTRIC HEATER

EVAPORATOR

ENTERING WATER TEMPERATURE

FAN COIL UNIT

POUNDS PER HOUR

LEAVING WATER TEMPERATURE

BTUH, THOUSANDS

NORMALLY CLOSED

NOT IN CONTRACT

NOT TO SCALE

NORMALLY OPEN

RHG

RLL

RSL

AIR SEPARATORAS

BUILDING AUTOMATION SYSTEMBAS

CWR CONDENSER WATER RETURN

CWS CONDENSER WATER SUPPLY

CWP CONDENSER WATER PUMP

CONN CONNECTION

CU CONDENSING UNIT

EA EXHAUST AIR

EDB ENTERING DRY BULB TEMPERATURE

ET EXPANSION TANK

FLEX FLEXIBLE

ID INSIDE DIAMETER

MCA MAXIMUM CIRCUIT AMPS

MOCP MAXIMUM OVERCURRENT PROTECTION

LRA LOCK ROTOR AMPS

RLA RATED LOAD AMPS

PLUMBING CONTRACTORPC

RELIEF FANRF

SCHWP SECONDARY CHILLED WATER PUMP

UG UNDERGROUND

ZD ZONE DAMPER

MECHANICAL ABBREVIATIONS

TYP

CHILLED WATER SUPPLY (ABOVE GRADE)

CHILLED WATER RETURN (ABOVE GRADE)

CONDENSATE DRAIN (ABOVE GRADE)

CONDENSATE DRAIN (BELOW GRADE)

CHILLED WATER RETURN (BELOW GRADE)

CHILLED WATER SUPPLY (BELOW GRADE)

CHEMICAL FEED PIPING

FLEXIBLE ROUND DUCT

CONDENSER WATER SUPPLY (ABOVE GRADE)

CONDENSER WATER RETURN (ABOVE GRADE)

CONDENSER WATER RETURN (BELOW GRADE)

CONDENSER WATER SUPPLY (BELOW GRADE)

CD

CF

CD-UG

CHR

CHS

CHR-UG

CHS-UG

GENERAL LEGEND

CWR

CWS

CWR-UG

CWS-UG

PITCH PIPE DOWN IN DIRECTION OF ARROW

SOLENOID VALVE

PIPE UP

PIPE DOWN

PIPE SECTION-RETURN

PIPE SECTION-SUPPLY

FLOW ARROW

PIPE ANCHOR

A

PIPE GUIDE

G

EXPANSION JOINT

GATE VALVE

GLOBE VALVE

STRAINER, Y-TYPE AND BLOW-OFF VALVE

CONTROL VALVE (2-WAY, 3-WAY)

CAPPED LINE

PIPE CONTINUATION

BALL VALVE

CHECK VALVE, HORIZONTAL SWING

EJ

FLEXIBLE CONNECTOR

BALANCING COCK

BC

BUTTERFLY VALVE, TAPPED LUG WAFER

MANUAL AIR VENT

MAV

PRESSURE GAUGE TAPPING (WATER)

NEEDLE VALVE

S

AUTOMATIC AIR VENT

AAV

TEMPERATURE & PRESSURE TAP (PETE'S PLUG)

PP

SHUT -OFF VALVE & PRESSURE TAPPTV

PTW

PRESSURE GAUGE W/BALL VALVE (WATER)PG

SHUT -OFF VALVE & PRESSURE TAPSV

CHECK VALVE, VERTICAL SPRING LOADED

PIPE REDUCTION4"

THERMOMETER

T

THERMOMETER WELL

TW

6"

SHEET WHERE SECTION APPEARS

SECTION DESIGNATION

M101

PIPE DESIGNATIONS

UC

CFM

DOOR UNDERCUT TAG

G-1

(2)

AIRFLOW (CFM)

DIFFUSER TYPE (REFER

TO SCHEDULE AND

SPECIFICATIONS)

TYPICAL FIXTURE

COUNT

DIFFUSER TAG}

DUCT TAKE-OFF W/ VOLUME DAMPER

(CONICAL, RECTANGULAR)

CEILING AIR DEVICE - SUPPLY

(SHADED AREA DENOTES BLANKED

OFF PANEL)

CEILING AIR DEVICE - RETURN

RECTANGULAR ELBOW WITH

TURNING VANES

SIDE WALL RETURN AIR DEVICE

SIDE WALL SUPPLY AIR DEVICE

POINT OF CONNECTION

POINT OF DISCONNECTION

ACCESS DOOR IN DUCT

CEILING AIR DEVICE - EXHAUST

DOWN DUCT STATIC PRESSURE SENSOR

SPACE CARBON DIOXIDE SENSOR

REMOTE TEMPERATURE SENSOR

SPACE HUMIDITY SENSOR

SMOKE DETECTOR

MOTORIZED DAMPER

MOTORIZED VALVE

SPACE TEMPERATURE SENSOR

HUMIDISTAT

AIR FLOW MEASURING STATION

FLOW METER

BACKDRAFT DAMPER

COMBINATION - FIRE/SMOKE DAMPER

SMOKE DAMPER

VOLUME DAMPER

MECHANICAL THERMOSTAT

M

FM

FIRE DAMPER

DOUBLE WALL DUCT

CO2

T

T

H

H

B B

D

SP

C F

M

S

S

M

T

SD

DEMOLITION REGION

GENERAL:

1. REFER TO THE DIVISION 23 SPECIFICATIONS.

2. THE CONTRACTOR SHALL DEMONSTRATE EACH HVAC SYSTEMS PERFORMANCE IN THE PRESENCE OF THE ENGINEER AND THE OWNER'S PROJECT MANAGER. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COST OF ANY ADDITIONAL SYSTEM TEST REQUIRED IF IN THE OPINION OF THE ENGINEER AND

THE OWNER'S PROJECT MANAGER THE SYSTEMS DO NOT PERFORM AS SPECIFIED.

3. VISIT AND CAREFULLY EXAMINE THOSE PORTIONS OF THE BUILDING AND SITE AFFECTED BY THIS WORK BEFORE SUBMITTING PROPOSALS, SO AS TO BECOME FAMILIAR WITH EXISTING CONDITIONS AND DIFFICULTIES THAT WILL AFFECT EXECUTION OF THE WORK. SUBMISSION OF A PROPOSAL WILL BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE AND LATER CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE OF DIFFICULTIES ENCOUNTERED WILL NOT BE

RECOGNIZED.

4. ALL GRILLES, REGISTERS OR DIFFUSERS SHOWN IN THE CEILING SHALL BE 24x24 UNLESS OTHERWISE

NOTED.

5. PROVIDE A VOLUME DAMPER AT EVERY LOW PRESSURE BRANCH DUCT AND AS SHOWN ON THE

DOCUMENTS FOR ALL DUCTWORK SYSTEMS. ALL DAMPERS MAY NOT BE SHOWN ON THE DOCUMENTS

FOR CLARITY.

6. FULLY COORDINATE ALL CEILING MOUNTED AIR DISTRIBUTION DEVICES WITH ARCHITECTURAL CEILING

GRID.

7. VERIFY EXACT LOCATION OF ALL ELECTRICAL EQUIPMENT INCLUDING WALL SWITCHES, FIRE ALARM

DEVICES, ETC. WITH ELECTRICAL CONTRACTOR AND ELECTRICAL DRAWINGS.

8. ALL DUCT SIZES INDICATED ON THE DOCUMENTS ARE NET FREE AREA DIMENSIONS.

9. UNFORESEEN CONDITIONS MAY EXIST AND WORK MAY NOT BE FIELD LOCATED EXACTLY AS SHOWN

ON THE DRAWINGS. COOPERATION WITH OTHER TRADES IN ROUTING AS DETERMINED DURING

CONSTRUCTION AND AS DIRECTED BY THE ARCHITECT/ENGINEER MAY BE NECESSARY. IT IS INTENDED THAT SUCH DEVIATIONS SHALL BE CONSIDERED AS PART OF THIS CONTRACT. SUCH DEVIATIONS MAY NOT BE CONSIDERED AS PART OF THIS CONTRACT WHEN PROPERLY DOCUMENTED IN WRITING. THE PLANS ARE NOT COMPLETELY TO SCALE. THIS CONTRACTOR IS TO FIELD VERIFY DIMENSIONS OF ALL

SITE UTILITIES, ETC., PRIOR TO BID AND INCLUDE ANY DEVIATIONS IN THE CONTRACT.

10. ALL DUCT IS TO BE CONCEALED ABOVE CEILING OR IN NEW WALLS, UNLESS SPECIFICALLY NOTED AS

EXPOSED OR SURFACE MOUNTED.

11. WORK SHALL BE PERFORMED IN STRICT COMPLIANCE WITH THE ESTABLISHED WORK SCHEDULE

BEING SET FORTH BY THE OWNER. COORDINATE ALL WORK WITH GENERAL CONTRACTOR. THIS

CONTRACTOR SHALL FURNISH ADEQUATE FORCES, CONSTRUCTION PLANT AND EQUIPMENT, AND

SHALL WORK SUCH HOURS, INCLUDING NIGHT SHIFTS, OVERTIME OPERATIONS, SUNDAYS AND

HOLIDAYS IN ACCORDANCE WITH THE OWNER'S OPERATIONAL SCHEDULE AS LISTED IN DIVISION 1 OF THE SPECIFICATIONS. IF THE CONTRACTOR DOES NOT MAINTAIN THE CONSTRUCTION SCHEDULE

BECAUSE OF INADEQUATE FORCES, SUPERVISION OR ANY OTHER REASON UNDER THE

CONTRACTOR'S CONTROL, THE OWNER MAY REQUIRE THE CONTRACTOR TO INCREASE THE NUMBER OF SHIFTS AND/OR OVERTIME OPERATIONS, DAY OF WORK AND/OR THE AMOUNT OF CONSTRUCTION PLANT, AT NO ADDITIONAL COST TO THE OWNER UNDER THIS CONTRACT. FAILURE TO MAINTAIN THE

CONSTRUCTION SCHEDULE DUE TO OWNER'S OPERATIONAL INTERFERENCES, WHICH WERE NOT

IDENTIFIED IN OR PRIOR TO THE PRE-BID CONFERENCE, SHALL NOT BE THE CONTRACTOR'S LIABILITY.

12. ALL CONCRETE, WALL PATCHING, CEILING REPAIR, FENCE WORK AND OTHER GENERAL

CONSTRUCTION WORK REQUIRED FOR INSTALLING MECHANICAL/PLUMBING OR FIRE PROTECTION

SYSTEMS SHALL BE PROVIDED BY MECHANICAL CONTRACTOR AND FULLY COORDINATED WITH

GENERAL CONTRACTOR USING THE APPROPRIATE CONSTRUCTION TRADES.

13. ALL MATERIALS AND EQUIPMENT SHALL BE NEW AND SHALL BE UL LISTED WHERE APPLICABLE.

14. DUCTWORK SHALL NOT BE SUPPORTED BY THE CEILING SUSPENSION SYSTEM. COORDINATE

LOCATIONS OF GRILLES, DIFFUSERS AND LOUVERS WITH ELECTRICAL, ARCHITECTURAL AND

PLUMBING WORK.

15. IN GENERAL, PLANS AND DIAGRAMS ARE SCHEMATIC ONLY AND SHOULD NOT BE SCALED.

CONTRACTOR SHALL COORDINATE ALL PLUMBING, HEATING AND ELECTRICAL WORK AT THE SITE, SO

AS NOT TO CONFLICT IN LOCATION WITH OTHER WORK UNDER THE CONTRACT.

16. ANY CONFLICT WITH DOORS, WINDOWS, CABINETS OR ANY OTHER EQUIPMENT SHALL BE BROUGHT TO

THE ATTENTION OF THE ARCHITECT/ENGINEER.

17. THE MECHANICAL CONTRACTOR IS DIRECTED TO COMPLY WITH DIVISION 26 OF THE CONTRACT

SPECIFICATIONS REFERRING TO MOTORS, STARTERS, ETC.

18. WHENEVER A REFERENCE IS MADE TO A STANDARD, INSTALLATION AND MATERIALS SHALL COMPLY WITH THE LATEST PUBLISHED EDITION AT THE TIME THE PROJECT IS BID UNLESS OTHERWISE

SPECIFIED.

19. ALL MATERIAL STORED ON SITE SHALL BE PROPERLY PROTECTED FROM INJURY OR DETERIORATION.

MATERIAL SHALL NOT BE STORED IN CONTACT WITH THE GROUND OR FLOOR. ALL DUCTWORK AND EQUIPMENT STORED SHALL BE SEALED AT ANY OPENING TO PREVENT ANY DEBRIS OR DIRT ENTERING THE INSIDE OF THE DUCTWORK AND EQUIPMENT. IF DEBRIS OR DIRT IS FOUND INSIDE THE DUCTWORK DURING ANY INSPECTION, THE CONTRACTOR WILL BE RESPONSIBLE FOR ALL COSTS INCURRED TO

CLEAN THE DUCTWORK TO THE SATISFACTION OF THE OWNER AND ENGINEER.

20. ALL SUPPLY AIR DUCT BENDS FROM THE VERTICAL TO THE HORIZONTAL AND ANGLED TURNS OF DUCTWORK SHALL HAVE LONG RADIUS ELBOWS. TURNING VANES WILL ONLY BE ACCEPTED WHERE

SHOWN ON THE DOCUMENTS.

21. VOLUME DAMPERS SHALL BE INSTALLED IN ALL BRANCH DUCTS LEADING FROM MAIN TRUNK LINES.

22. ALL EXTERNAL FIBROUS GLASS WRAPPED INSULATION JOINTS, SEAMS AND CONNECTIONS SHALL BE

CONSTRUCTED WITH FAB AND STAPLES AND THEN SEALED WITH MASTIC. HEAT AND PRESSURE

SENSITIVE TAPE ARE NOT ACCEPTABLE AS A FINAL CLOSURE.

23. DUCTWORK SHALL BE SHEET METAL, EXTERNALLY WRAPPED UNLESS OTHERWISE NOTED, MIN. 26 GA.

AND CONSTRUCTED IN STRICT ACCORDANCE WITH SMACNA STANDARDS.

24. CONTRACTOR SHALL COORDINATE WORK WITH ALL OTHER TRADES.

25. MECHANICAL CONTRACTOR TO TEST AND BALANCE HVAC SYSTEMS TO PROVIDE MAXIMUM

PERFORMANCE WITH REGARDS TO CFM, TEMPERATURE AND STATIC PRESSURE. REFER TO

SPECIFICATIONS FOR TEST AND BALANCE REQUIREMENTS.

26. ALL INSULATION USED FOR DUCTWORK SHALL BE INSTALLED THICKNESS RECOMMENDED BY THE ASHRAE GUIDE AND DATA BOOKS. INSULATION MATERIAL SHALL MEET NFPA 90A REQUIREMENTS AND SHALL HAVE COMPOSITE FIRE AND SMOKE HAZARD RATING AS TESTED IN ACCORDANCE WITH NFPA 225 OR UL 723 NOT EXCEEDING FLAME SPREAD OF MORE THAN 25 AND SMOKE DEVELOPED 50. REFER

TO SPECIFICATIONS.

28. ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE 8th EDITION (2023), FLORIDA BUILDING CODE 8th EDITION (2023) PLUMBING, FLORIDA BUILDING CODE 8th EDITION (2023) MECHANICAL, FLORIDA FIRE PREVENTION CODE 8th EDITION (2023), FLORIDA BUILDING CODE 8th

EDITION (2023) ENERGY CONSERVATION & STANDARDS AS REFERENCED IN DIVISION 1 AND

THROUGHOUT THE SPECIFICATIONS.

29. NOT ALL ABBREVIATIONS, OR LEGEND ITEMS SHOWN ARE APPLICABLE TO THIS PROJECT.

30. ALL DRAWINGS ARE DIAGRAMMATIC IN NATURE.

31. REFER TO CONTROLS GENERAL NOTES.

32. SEE SPECIFICATION SECTION 01 91 13 FOR COMISSIONING REQUIREMENTS.

33. PROVIDE ALUMINUM JACKET ON ALL EXPOSED AND OR VISIBLE PIPING.

34. ENERGY CODE COMPLIANCE EXEMPTION

THE AIR CONDITIONG SYSTEM FOR THE NORTH BUILDING ON THIS PROJECT IS BEING DESIGNED FOR STORAGE AND NOT FOR THERMAL COMFORT. THIS REQUIRES THE PROJECT TO CLAIM EXEMPTION

FROM THE FLORIDA BUILDING CODE 8TH EDITION (2023) - ENERGY CONSERVATION.

MECHANICAL GENERAL NOTES

MPE JOB #:

ENG. BUS. No. EB-0005096

CERT. OF AUTH. No. 5096

PHONE (239) 332-1187

12437 Brantley Commons Fort Myers, FL 33907

TO

D GRIFF

No 67083P R

STATE OF

E

O F

E S

S

ION A L E N

G

IN

E E

R

NSECIL

F L O R I DA

THK

D I

K. Todd Griffith No.67083

PROJECT NO:

DATE:

PHASE:

ISSUED FOR

SEAL:

GRACE HEBERT CURTIS ARCHITECTS, LLC

SHEET NUMBER

© THIS SET OF DOCUMENTS INCLUSIVE OF

DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT

BE COPIED, SCANNED, NOR ELECTRONICALLY

DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT

THE EXPRESSED WRITTEN CONSENT OF GRACE

HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,

ELECTRONIC PLAN SERVICE (INTERNET PLAN

SERVICE), NOR REPRODUCTION COMPANY SHALL BE

PERMITTED TO POST THESE DOCUMENTS WITHOUT

THE EXPRESSED WRITTEN CONSENT OF THE

ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.

2024-118

/1

/2

:4

:4

P

M

A u to d e s k D o c s /W a re h o u s e

C o n v e rt t o P a rk s

R e c D e p a rt m e n t/

-1

M e c h a n ic a l M o d e l_

O p ti o n O n e

R e v it

B

IM

.r v t

M001

GENERAL NOTES, LEGEND,

ABBREVIATIONS & SHEET

INDEX

40-24105

W A

R E

H O

U S

E C

O N

V E

R T

T O

P A

R K

S

R E

C D

E P

T

C

IT

Y O

F F

O R

T M

Y E

R S

06/19/2025

PERMIT DOCUMENTS

M

IC

H

IH

A

N A

V E

N U

E F

O R

T M

Y E

R S

F

L O

R

ID

A

DEMOLITION GENERAL NOTES

1. REFER TO “MECHANICAL GENERAL NOTES” ON DRAWING. THEY ARE APPLICABLE TO ALL WORK DESCRIBED ON EVERY MECHANICAL DRAWING.

2. ALL HEX NOTES NOT NECESSARILY USED ON ALL SHEETS.

3. ALL UNUSED SLAB PENETRATIONS SHALL BE PROPERLY SEALED TO MATCH EXISTING.

4. ALL UNUSED ROOF AND EXTERIOR PENETRATIONS SHALL BE PROPERLY CAPPED AND SEALED WATER TIGHT.

5. ALL EXISTING MECHANICAL EQUIPMENT, DUCTWORK, PIPING AND ACCESSORIES ARE SCHEDULED TO REMAIN UNLESS NOTED OTHERWISE. NOT ALL EXISTING

WORK MAY BE SHOWN FOR DRAWING CLARITY.

6. MAINTAIN CONTINUITY OF ALL SYSTEMS FOR BUILDING OPERATIONAL HOURS DURING CONSTRUCTION. COORDINATE WITH GC AND OWNERS SCHEDULE.

7. PRIOR TO COMMENCEMENT OF WORK, CONTRACTOR SHALL PRE-TEST ALL AIR FLOW DEVICES ON THIS FLOOR, INCLUDING DIFFUSERS/GRILLES.TEST RESULTS SHALL BE PRESENTED TO ENGINEER FOR REVIEW PRIOR TO ANY MODIFICATIONS BEING MADE TO THE SYSTEMS.

8. IT IS A REQUIREMENT THAT EACH SPACE IN THIS FACILITY, DURING OCCUPIED HOURS, SHALL HAVE CONTINUOUS HEATING AND/OR COOLING THROUGHOUT THE DURATION OF CONSTRUCTION AND THAT TEMPERATURES SHALL BE MAINTAINED FOR EACH SPACE PER OWNER'S REQUIREMENTS. IF THE CONTRACTOR BELIEVES THAT TEMPORARY HEATING AND/OR COOLING METHODS WILL BE NECESSARY TO MEET THIS REQUIREMENT, THEN CONTRACTOR SHALL INCLUDE THIS AS A SEPARATE COST LINE ITEM WITH THEIR BID, INCLUDING THE DURATION REQUIRED FOR TEMPORARY EQUIPMENT. OMISSION OF THIS LINE ITEM CONSTITUTES CONTRACTOR'S ABILITY TO COMPLY WITH PROJECT REQUIREMENTS WITHOUT THE NEED FOR TEMPORARY HEATING AND/OR COOLING.

9. ALL EQUIPMENT SHALL BE REMOVED IN A CAREFULLY PLANNED MANNER. ALL CEILING-HUNG EQUIPMENT SHALL BE REMOVED BY PROVIDING SUPPORT FROM

BELOW. NO DROPPING OF EXISTING EQUIPMENT ONTO THE FLOOR SLAB WILL BE ALLOWED.

10. REMOVE CONTROL WIRING ASSOCIATED WITH EQUIPMENT BEING REMOVED; COORDINATE WITH ELECTRICAL CONTRACTOR AS REQUIRED. THE REMOVAL OF CONTROL APPARATUS SHALL NOT INTERFERE WITH NORMAL OPERATION OF REMAINING EQUIPMENT OR SYSTEMS.

11. NOT ALL HVAC EQUIPMENT, DUCTWORK, PIPING AND/OR OTHER PIPING SYSTEMS ARE SHOWN ON THESE DEMOLITION DRAWINGS. CONTRACTOR SHALL IDENTIFY

ALL AFFECTED DUCTS AND PIPES PRIOR TO DEMOLITION.

12. SIZES OF PIPING AND DUCTWORK TO BE REMOVED AND/OR REMAIN MAY NOT HAVE BEEN INDICATED. CONTRACTOR SHALL SURVEY EXISTING SPACE, VERIFY SIZES AND INCLUDE IN SCOPE OF WORK. DISCREPANCIES DISCOVERED BETWEEN FIELD CONDITIONS AND CONSTRUCTION DOCUMENTS SHALL BE REPORTED TO

ENGINEER PROMPTLY.

13. PROVIDE TEMPORARY SHEETMETAL CAP ON ALL OPEN END DUCTWORK THAT IS TO REMAIN FUNCTIONAL DURING THE PROJECT.

14. ALL SERVICES PASSING THROUGH DEMOLITION CONTRACT AREA SERVING OTHER AREAS SHALL REMAIN AND SHALL BE PROTECTED UNLESS OTHERWISE NOTED.

15. THE CONTRACTOR SHALL OBTAIN THE PERMISSION OF THE OWNER'S REPRESENTATIVE AND COORDINATE WITH OTHER TRADES PRIOR TO COMMENCEMENT OF

DEMOLITION OF THE EXISTING INSTALLATIONS.

16. THE CONTRACTOR SHALL PROVIDE FOR SAFE CONDUCT OF THE WORK, PROTECTION OF PROPERTY, AND COORDINATION WITH OTHER WORK IN PROGRESS. THE

SPREAD OF DUST AND FLYING PARTICLES SHALL BE MINIMIZED.

17. EXISTING CONSTRUCTION TO REMAIN SHALL BE PROTECTED FROM DAMAGE. WORK DAMAGED BY THE CONTRACTOR SHALL BE REPAIRED TO MATCH EXISTING

WORK.

18. WHEN INDICATED, THE CONTRACTOR SHALL REMOVE SPECIFIC EQUIPMENT IN A CAREFUL MANNER SO AS TO MAINTAIN THE EQUIPMENT IN PROPER OPERATING ORDER. THIS EQUIPMENT WILL BE TURNED OVER TO THE OWNER AND TRANSPORTED TO A STORAGE AREA AS DIRECTED BY THE OWNER AND FURTHER

DESCRIBED HEREIN.

19. MATERIAL DEMOLISHED UNDER THIS SECTION AND NOT TO BE RETAINED BY THE OWNER SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE

PROMPTLY REMOVED AND DISPOSED OF OFF THE SITE.

20. DEBRIS AND RUBBISH SHALL NOT ACCUMULATE ON THE SITE, AND SHALL BE DISPOSED OF PERIODICALLY BY THE CONTRACTOR.

21. ALL NECESSARY PRECAUTIONS SHALL BE TAKEN BY THE CONTRACTOR TO PREVENT SPILLAGE DURING REMOVAL ACTIVITIES. PAVEMENT AND AREAS ADJACENT TO THE DEMOLITION AREAS SHALL BE KEPT CLEAN AND FREE FROM MUD, DIRT AND DEBRIS AT ALL TIMES.

22. EXISTING UTILITIES AND MECHANICAL SYSTEMS INCLUDING RELATED EQUIPMENT SHALL BE DISCONNECTED BY THE CONTRACTOR TO THE EXTENT SHOWN ON THE CONTRACT DRAWINGS OR SPECIFIED AND AS REQUIRED TO PERFORM THE WORK IN ACCORDANCE WITH DIVISION 23 OF THE SPECIFICATIONS.

23. THE CONTRACTOR SHALL EXERCISE CARE DURING THE PROGRESS OF THE WORK UNDER THIS SECTION SO AS NOT TO DAMAGE OR DISPLACE THE WORK OF THE OTHER TRADES PERFORMED UNDER OTHER SECTIONS. HE SHALL COORDINATE WORK UNDER THIS SECTION WITH WORK UNDER OTHER SECTIONS, AS NECESSARY

FOR THE PROPER EXECUTION OF THE ENTIRE WORK.

24. WHEN THE CONTRACT DOCUMENTS INDICATE THE REMOVAL OF EXISTING EQUIPMENT TO BE TEMPORARILY STORED AND TO BE RE-USED, THE CONTRACTOR SHALL PROVIDE ADEQUATE PROTECTION FOR THE STORED EQUIPMENT INCLUDING THE PROPER CAPPING OF SEVERAL PIPE CONNECTIONS, PROTECTION OF POWER AND

CONTROL WIRING AND DEVICES, AND DRAINING OF COILS TO PREVENT FREEZING DAMAGE.

25. EQUIPMENT WHICH CONTAINS REFRIGERANTS SHALL BE PUMPED DOWN PRIOR TO DEMOLITION. THE REFRIGERANT SHALL BE PROPERLY CONTAINED AND

DISPOSED OF IN ACCORDANCE WITH THE ACCEPTED LOCAL PROCEDURES.

26. PRE-DEMOLITION PHOTOGRAPHS SHALL BE TAKEN SHOWING EXISTING CONDITIONS OF ADJOINING CONSTRUCTION AND SITE IMPROVEMENTS, INCLUDING FINISHED SURFACES THAT MIGHT BE MISCONSTRUED AS DAMAGE CAUSED BY SELECTIVE DEMOLITION OPERATIONS. PHOTOGRAPH ITEMS REQUESTED TO BE SALVAGE BY

THE OWNER. SUBMIT ALL PHOTOGRAPHIC DOCUMENTATION BEFORE THE START OF DEMOLITION.

27. PRE-DEMOLITION CONFERENCE: CONDUCT CONFERENCE AT PROJECT SITE WITH THE OWNER TO INSPECT AND DISCUSS CONDITION OF CONSTRUCTION TO BE SELECTIVELY DEMOLISHED, REVIEW AREAS WHERE EXISTING CONSTRUCTION IS TO REMAIN AND REQUIRES PROTECTION, REVIEW LIST OF ITEMS TO BE

SALVAGED AND DELIVERED TO THE OWNER.

28. REFER TO SPECIFICATIONS.

NO. DESCRIPTION DATE

MECHANICAL SHEET INDEX

SHEET NUMBER SHEET NAME

M001 GENERAL NOTES, LEGEND, ABBREVIATIONS & SHEET INDEX

MD101-N 1ST AND 2ND FLOOR DEMOLITION PLANS - NORTH BUILDING - MECHANICAL

MD101-S 1ST FLOOR DEMOLITION PLAN - SOUTH BUILDING - MECHANICAL

M101-N 1ST AND 2ND FLOOR PLANS - NORTH BUILDING - MECHANICAL

M101-S 1ST FLOOR PLAN - SOUTH BUILDING - MECHANICAL

M101-S-2 1ST FLOOR PLAN - SOUTH BUILDING - MECHANICAL - ALTERNATE

M201 SECTION VIEWS - MECHANICAL

M502 CONTROLS - MECHANICAL

M503 CONTROLS - MECHANICAL

M504 CONTROLS - MECHANICAL

M601 SCHEDULES - MECHANICAL

M601-2 SCHEDULES - MECHANICAL - ALTERNATE

M901 DETAILS - MECHANICAL

M902 DETAILS - MECHANICAL

M903 DETAILS - MECHANICAL

DN

DN

GENERAL/DEMOLITION GENERAL NOTES:

1. REFER TO GENERAL/DEMOLITION GENERAL NOTES

FOR THIS DISCIPLINE. SEE SHEET M001.

2. REFER TO SPECIFICATIONS.

3. ALL HEX NOTES NOT NECESSARILY USED ON ALL

SHEETS.

MPE JOB #:

ENG. BUS. No. EB-0005096

CERT. OF AUTH. No. 5096

PHONE (239) 332-1187

12437 Brantley Commons Fort Myers, FL 33907

TO

D GRIFF

No 67083P R

STATE OF

E

O F

E S

S

ION A L E N

G

IN

E E

R

NSECIL

F L O R I DA

THK

D I

K. Todd Griffith No.67083

HEX NOTES:

PROJECT NO:

DATE:

PHASE:

ISSUED FOR

SEAL:

GRACE HEBERT CURTIS ARCHITECTS, LLC

SHEET NUMBER

© THIS SET OF DOCUMENTS INCLUSIVE OF

DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT

BE COPIED, SCANNED, NOR ELECTRONICALLY

DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT

THE EXPRESSED WRITTEN CONSENT OF GRACE

HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,

ELECTRONIC PLAN SERVICE (INTERNET PLAN

SERVICE), NOR REPRODUCTION COMPANY SHALL BE

PERMITTED TO POST THESE DOCUMENTS WITHOUT

THE EXPRESSED WRITTEN CONSENT OF THE

ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.

2024-118

/1

/2

:3

:1

P

M

A u to d e s k D o c s /W a re h o u s e

C o n v e rt t o P a rk s

R e c D e p a rt m e n t/

-1

M e c h a n ic a l M o d e l_

O p ti o n O n e

R e v it

B

IM

.r v t

MD101-N

1ST AND 2ND FLOOR

DEMOLITION PLANS -

NORTH BUILDING -

MECHANICAL

40-24105

W A

R E

H O

U S

E C

O N

V E

R T

T O

P A

R K

S

R E

C D

E P

T

C

IT

Y O

F F

O R

T M

Y E

R S

06/19/2025

PERMIT DOCUMENTS

M

IC

H

IH

A

N A

V E

N U

E F

O R

T M

Y E

R S

F

L O

R

ID

A

1/4" = 1'-0"1 FIRST FLOOR DEMOLITION PLAN - NORTH BUILDING

1/4" = 1'-0"2 SECOND FLOOR DEMOLITION PLAN - NORTH BUILDING

1 CONTRACTOR SHALL REMOVE ALL EXISTING HVAC

EQUIPMENT AND ALL ASSOCIATED PIPING,

CONTROLS AND DUCTWORK WITHIN DEMOLITION

REGION.

NO. DESCRIPTION DATE

GENERAL/DEMOLITION GENERAL NOTES:

1. REFER TO GENERAL/DEMOLITION GENERAL NOTES

FOR THIS DISCIPLINE. SEE SHEET M001.

2. REFER TO SPECIFICATIONS.

3. ALL HEX NOTES NOT NECESSARILY USED ON ALL

SHEETS.

MPE JOB #:

ENG. BUS. No. EB-0005096

CERT. OF AUTH. No. 5096

PHONE (239) 332-1187

12437 Brantley Commons Fort Myers, FL 33907

TO

D GRIFF

No 67083P R

STATE OF

E

O F

E S

S

ION A L E N

G

IN

E E

R

NSECIL

F L O R I DA

THK

D I

K. Todd Griffith No.67083

HEX NOTES:

PROJECT NO:

DATE:

PHASE:

ISSUED FOR

SEAL:

GRACE HEBERT CURTIS ARCHITECTS, LLC

SHEET NUMBER

© THIS SET OF DOCUMENTS INCLUSIVE OF

DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT

BE COPIED, SCANNED, NOR ELECTRONICALLY

DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT

THE EXPRESSED WRITTEN CONSENT OF GRACE

HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,

ELECTRONIC PLAN SERVICE (INTERNET PLAN

SERVICE), NOR REPRODUCTION COMPANY SHALL BE

PERMITTED TO POST THESE DOCUMENTS WITHOUT

THE EXPRESSED WRITTEN CONSENT OF THE

ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.

2024-118

/1

/2

:3

:1

P

M

A u to d e s k D o c s /W a re h o u s e

C o n v e rt t o P a rk s

R e c D e p a rt m e n t/

-1

M e c h a n ic a l M o d e l_

O p ti o n O n e

R e v it

B

IM

.r v t

MD101-S

1ST FLOOR DEMOLITION

PLAN - SOUTH BUILDING -

MECHANICAL

40-24105

W A

R E

H O

U S

E C

O N

V E

R T

T O

P A

R K

S

R E

C D

E P

T

C

IT

Y O

F F

O R

T M

Y E

R S

06/19/2025

PERMIT DOCUMENTS

M

IC

H

IH

A

N A

V E

N U

E F

O R

T M

Y E

R S

F

L O

R

ID

A

1/4" = 1'-0"1 FIRST FLOOR DEMOLITION PLAN - SOUTH BUILDING

1 CONTRACTOR SHALL REMOVE ALL EXISTING HVAC

EQUIPMENT AND ALL ASSOCIATED PIPING,

CONTROLS AND DUCTWORK. WITHIN DEMOLITION

REGION

DN

M SD

MM C

F

M

SD

M

C

(TYP.16)

A

TH

HT

"x

S A

"x

S A

"x

S A

"x

S A

24"x20" SA 26"x20" SA

"x

S A

"x

S A

"x

S A

"x

S A

20"x20" SA20"x16" SA18"x14" SA14"x14" SA

B

A

(TYP.2)

EF-N-1

6"ø EALV-N-2

CU-N-2CU-N-3

4 5

CU-N-1

DISC.

FOR CU-N-1

DISC.

FOR CU-N-3

DISC.

FOR CU-N-2

D

EF-N-2

8"ø EA

"ø

E A

FORKLIFT CHARGING

STATION

OFFICES/ MULTI-USE

PRINT ROOM

STAGING AREA

RECORDS STORAGE

CUSTODIAL

UNISEX R.R.

T H

14"x10" OA

"x

O A

12"x10" OA

40"x24" RA

"x

S A

BCU-N-2

"x

S A

BCU-N-3

D

C

4" CONCRETE PAD

4" CONCRETE PAD

4" CONCRETE PAD

DISC.

FOR AHU-N-1

DISC.

FOR BCU-N-2

M201

LV-N-1

DISC.

FOR BCU-N-3

EDH-N-2

10"x10" SA

"x

R A

"x

S A

M201

M201

AHU-N-1

"x

O A

SD

MPE JOB #:

ENG. BUS. No. EB-0005096

CERT. OF AUTH. No. 5096

PHONE (239) 332-1187

12437 Brantley Commons Fort Myers, FL 33907

TO

D GRIFF

No 67083P R

STATE OF

E

O F

E S

S

ION A L E N

G

IN

E E

R

NSECIL

F L O R I DA

THK

D I

K. Todd Griffith No.67083

HEX NOTES:

PROJECT NO:

DATE:

PHASE:

ISSUED FOR

SEAL:

GRACE HEBERT CURTIS ARCHITECTS, LLC

SHEET NUMBER

© THIS SET OF DOCUMENTS INCLUSIVE OF

DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT

BE COPIED, SCANNED, NOR ELECTRONICALLY

DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT

THE EXPRESSED WRITTEN CONSENT OF GRACE

HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,

ELECTRONIC PLAN SERVICE (INTERNET PLAN

SERVICE), NOR REPRODUCTION COMPANY SHALL BE

PERMITTED TO POST THESE DOCUMENTS WITHOUT

THE EXPRESSED WRITTEN CONSENT OF THE

ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.

2024-118

/1

/2

:4

:5

P

M

A u to d e s k D o c s /W a re h o u s e

C o n v e rt t o P a rk s

R e c D e p a rt m e n t/

-1

M e c h a n ic a l M o d e l_

O p ti o n O n e

R e v it

B

IM

.r v t

M101-N

1ST AND 2ND FLOOR

PLANS - NORTH BUILDING -

MECHANICAL

40-24105

W A

R E

H O

U S

E C

O N

V E

R T

T O

P A

R K

S

R E

C D

E P

T

C

IT

Y O

F F

O R

T M

Y E

R S

06/19/2025

PERMIT DOCUMENTS

M

IC

H

IH

A

N A

V E

N U

E F

O R

T M

Y E

R S

F

L O

R

ID

A

1/4" = 1'-0"1 FIRST FLOOR NORTH BUILDING

1/4" = 1'-0"2 SECOND FLOOR NORTH BUILDING

1 CONTRACTOR TO ROUTE 1" INSULATED

CONDENSATE PIPING TO NEAREST HUB DRAIN.

2 CONTRACTOR TO COORDINATE EXISTING

PENETRATION IN EXTERIOR WALL WITH NEW

LOUVER (LV-N-1) PRIOR TO PURCAHSE.

3 PROVIDE MAGNETIC CONTACT SWITCH. INTERLOCK

MAGNETIC CONTACT SWITCH WITH AHU-N-1.

MAGNETIC CONTACT SWITCH WILL SHUT AHU-N-1

OFF AFTER 5 MINUTES OF THE ROLL UP DOOR

BEING OPENED.

4 SPACE HUMIDITY SENSOR ASSOCIATED WITH

AHU-N-1. TERMINATE SENSOR AT AHU-N-1

CONTROLLER.

5 SPACE TEMPERATURE SENSOR ASSOCIATED WITH

AHU-N-1. TERMINATE SENSOR AT AHU-N-1

CONTROLLER.

6 SPACE HUMIDITY SENSOR ASSOCIATED WITH

BCU-N-2. TERMINATE SENSOR AT BCU-N-2

CONTROLLER.

7 SPACE TEMPERATURE SENSOR ASSOCIATED WITH

BCU-N-2. TERMINATE SENSOR AT BCU-N-2

CONTROLLER.

8 SPACE TEMPERATURE SENSOR ASSOCIATED WITH

BCU-N-3. TERMINATE SENSOR AT BCU-N-3

CONTROLLER.

9 SPACE HUMIDITY SENSOR ASSOCIATED WITH

BCU-N-3. TERMINATE SENSOR AT BCU-N-3

CONTROLLER.

10 CONTRACTOR TO PROVIDE PRICE 30" X 30" HEAVY

DUTY GYM GRILLE (3285 CFM) (MODEL #: 95FH).

11 CONTRACTOR TO INSTALL CONDENSING UNIT 1'

ABOVE FLOOD ELEVATION.

12 SEE CONTINUATION ON SECOND FLOOR

MECHANICAL PLAN

13 SEE CONTINUATION ON FIRST FLOOR MECHANICAL

PLAN.

GENERAL NOTES:

1. REFER TO GENERAL NOTES FOR THIS DISCIPLINE.

2. REFER TO SPECIFICATIONS.

3. ALL HEX NOTES NOT NECESSARILY USED ON ALL

SHEETS.

4. SEE SECTION VIEW MECHANICAL ROOM PLANS FOR

MORE DETAIL.

5. ALL AIR HANDLING SYSTEMS WILL UTILIZE A FULLY

DUCTED RETURN AIR SYSTEM.

6. PROVIDE A VOLUME DAMPER ON ALL BRANCH

DUCTWORK AND ANY RUNOUT TO A DIFFUSER,

WHETHER SHOWN ON DRAWINGS OR NOT.

7. ALL VOLUME DAMPERS INSTALLED ABOVE GYPSUM

BOARD CEILING SHALL HAVE REMOTELY OPERATED

DAMPER.ALL OUTSIDE AIR LOUVERS SHALL BE

PROVIDED WITH 1/4" X 1/4" REMOVABLE BIRD SCREEN

AND REMOVABLE FILTERS IN A FILTER RACK. THIS

SHALL BE INSTALLED IN A CHANNEL AND SHALL BE

EASILY REMOVED. SCREWED BIRD SCREEN TO THE

LOUVER IS NOT ACCEPTABLE.

8. PROVIDE VOLUME DAMPERS ON EACH BATHROOM

EXHAUST GRILLE.

9. REFER TO MANUFACTURER'S RECOMMENDATIONS

FOR ALL REFRIGERANT PIPE SIZES ACCORDING TO

FINAL LENGTH OF RUN.

10. ALL RETURN GRILLES LOCATIONS MUST BE

INSTALLED AT OR FARTHER THAN LOCATIONS

SHOWN, OR FARTHER THAN BRANCH RUNOUT TO

ELIMINATE NOISE TRANSMISSION.

11. ALL LOUVER PLENUMS SHALL SLOPE BACK TOWARDS

THE LOUVER ON THE EXTERIOR WALL. FINAL SIZE,

HEIGHT, COLOR AND LOCATION OF THE LOUVERS

SHOULD BE COORDINATED WITH THE

ARCHITECTURAL ELEVATIONS AND GENERAL

CONTRACTOR, PRIOR TO ORDERING LOUVERS.

12. FULLY COORDINATE WITH THE ARCHITECTURAL

REFLECTED CEILING PLANS FOR DIFFUSER

LOCATIONS PRIOR TO INSTALLATION.

13. CONTRACTOR SHALL COORDINATE VAV ELECTRICAL

CLEARANCES. INCLUDING LOW VOLTAGE, WITH ALL

CEILING MOUNTED EQUIPMENT IN SHOP DRAWINGS,

WHICH INCLUDES BUT IS NOT LIMITED TO LIGHTING,

PROJECTORS, SYSTEMS DEVICES, AND FIRE

SPRINKLERS. CLEARANCES SHALL BE SIZED AND

COORDINATED AS REQUIRED BASED ON THE

AWARDED MANUFACTURER VAV BOX

REQUIREMENTS. LIGHTS AND EQUIPMENT BELOW THE

VAV CLEARANCE, IN THE CEILING ARE NOT

ACCEPTABLE.

14. REFER TO ARCHITECTURAL DRAWINGS FOR

MOUNTING HEIGHT AND COLOR OF ALL LINEAR

DIFFUSERS.

DN

C F

M

M

A

(TYP.2)

A

(TYP.2)

T

T

T T H

T

T

T

T

T

B

B

B

B

B

"x

E A

6"x6" EA

A

A

A

A

A

A

"x

S A

12"x10" SA

"x

S A

8"ø SA

"x

S A

8"ø SA

"x

S A

"x

S A

8"x8" SA

8"x8" SA

"x

S A

"x

S A

8"x6" SA

8"x8" SA 10"x8" SA 1 "x

"x

S A

8"x8" SA

"ø

S A

10"ø SA

10"x10" SA14"x14" SA

"x

S A

"x

S A

"x

S A

8"ø SA

12"x10" 8"ø SA

4" CONCRETE PAD

BAS

DISC.

FOR AHU-S-1

LV-S-4

LV-S-1

VAV-S-1-6

VAV-S-1-7

VAV-S-1-3

VAV-S-1-5

VAV-S-1-8

VAV-S-1-1

VAV-S-1-2

VAV-S-1-4

A

A

A

A

CF-1

VAV-S-1-9

EF-S-1

32"x30" RA

"x

R A

14"x12" RA

"x

R A

"x

R A

"x

R A

"x

R A

"x

R A

12"x12" RA "x

R A

M201

T

T

MSCU-S-1

4" CONCRETE PAD

EF-S-2 LV-S-2

44"x44" EA

LV-S-3

T

12"x12" SA10"x10" SA

26"x20" SA

/4

"ø C

D

MSAC-S-1

VAV-S-10

D

D 270C

B

B

B

B

B

B

A

C

B

"ø

S A

14"x12" EA

"x

S A

10"x10" SA

"x

" R

A

"ø

S A

CU-S-1

14"x12" OA

AHU-S-1

4" CONCRETE PAD

"x

S A

10"ø SA

8"ø SA

5"ø SA

"ø

S A

"ø

S A

8"ø SA

"x

S A

"ø

S A

10"ø SA

"ø

S A

H/O/A

DISC.

FOR CU-S-1

DISC.

FOR MSCU-S-1

A

CUSTODIAL

SMALL CONFERENCE

ROOM

CUBICLE 1

CUBICLE 2

471 SF

MAINTENANCE &

REPAIRS AREA

948 SF

EQUIPMENT TOOL'S

CAGES

MECH. ROOM

ELECTRICAL ROOM

126 MDF ROOM

CLOSET

LARGE CONFERENCE

ROOM

EXECUTIVE OFFICE

CUBICLE 5

CUBICLE 4

SENIOR ASSIST.

PUBLIC

MEN'S RESTROOM

WOMEN'S RESTROOM

LOUNGE ROOM

OFF. SUPPLIES

SPECIAL EVENTS

STORAGE/ MULTI-USE

WORK ROOM

CUBICLE 3

CUBICLE 8

CUBICLE 9

CUBICLE 7

CUBICLE 12

CUBICLE 11

CUBICLE 10

CUBICLE 13

CUBICLE 6

OPEN SPACE

2016 SF

PARKS & REC

WAREHOUSE

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

"x

S A

"x

S A

"x

S A

6"ø SA

"x

S A

"x

E A

C

C

6"x6" SA

C

C

C

C

C

C

C

C

C

16"x14" RA

D

GENERAL NOTES:

1. REFER TO GENERAL NOTES FOR THIS DISCIPLINE.

2. REFER TO SPECIFICATIONS.

3. ALL HEX NOTES NOT NECESSARILY USED ON ALL

SHEETS.

4. SEE SECTION VIEW MECHANICAL ROOM PLANS FOR

MORE DETAIL.

5. ALL AIR HANDLING SYSTEMS WILL UTILIZE A FULLY

DUCTED RETURN AIR SYSTEM.

6. PROVIDE A VOLUME DAMPER ON ALL BRANCH

DUCTWORK AND ANY RUNOUT TO A DIFFUSER,

WHETHER SHOWN ON DRAWINGS OR NOT.

7. ALL VOLUME DAMPERS INSTALLED ABOVE GYPSUM

BOARD CEILING SHALL HAVE REMOTELY OPERATED

DAMPER.ALL OUTSIDE AIR LOUVERS SHALL BE

PROVIDED WITH 1/4" X 1/4" REMOVABLE BIRD SCREEN

AND REMOVABLE FILTERS IN A FILTER RACK. THIS

SHALL BE INSTALLED IN A CHANNEL AND SHALL BE

EASILY REMOVED. SCREWED BIRD SCREEN TO THE

LOUVER IS NOT ACCEPTABLE.

8. PROVIDE VOLUME DAMPERS ON EACH BATHROOM

EXHAUST GRILLE.

9. REFER TO MANUFACTURER'S RECOMMENDATIONS

FOR ALL REFRIGERANT PIPE SIZES ACCORDING TO

FINAL LENGTH OF RUN.

10. ALL RETURN GRILLES LOCATIONS MUST BE

INSTALLED AT OR FARTHER THAN LOCATIONS

SHOWN, OR FARTHER THAN BRANCH RUNOUT TO

ELIMINATE NOISE TRANSMISSION.

11. ALL LOUVER PLENUMS SHALL SLOPE BACK TOWARDS

THE LOUVER ON THE EXTERIOR WALL. FINAL SIZE,

HEIGHT, COLOR AND LOCATION OF THE LOUVERS

SHOULD BE COORDINATED WITH THE

ARCHITECTURAL ELEVATIONS AND GENERAL

CONTRACTOR, PRIOR TO ORDERING LOUVERS.

12. FULLY COORDINATE WITH THE ARCHITECTURAL

REFLECTED CEILING PLANS FOR DIFFUSER

LOCATIONS PRIOR TO INSTALLATION.

13. CONTRACTOR SHALL COORDINATE VAV ELECTRICAL

CLEARANCES. INCLUDING LOW VOLTAGE, WITH ALL

CEILING MOUNTED EQUIPMENT IN SHOP DRAWINGS,

WHICH INCLUDES BUT IS NOT LIMITED TO LIGHTING,

PROJECTORS, SYSTEMS DEVICES, AND FIRE

SPRINKLERS. CLEARANCES SHALL BE SIZED AND

COORDINATED AS REQUIRED BASED ON THE

AWARDED MANUFACTURER VAV BOX

REQUIREMENTS. LIGHTS AND EQUIPMENT BELOW THE

VAV CLEARANCE, IN THE CEILING ARE NOT

ACCEPTABLE.

14. REFER TO ARCHITECTURAL DRAWINGS FOR

MOUNTING HEIGHT AND COLOR OF ALL LINEAR

DIFFUSERS.

MPE JOB #:

ENG. BUS. No. EB-0005096

CERT. OF AUTH. No. 5096

PHONE (239) 332-1187

12437 Brantley Commons Fort Myers, FL 33907

TO

D GRIFF

No 67083P R

STATE OF

E

O F

E S

S

ION A L E N

G

IN

E E

R

NSECIL

F L O R I DA

THK

D I

K. Todd Griffith No.67083

HEX NOTES:

PROJECT NO:

DATE:

PHASE:

ISSUED FOR

SEAL:

GRACE HEBERT CURTIS ARCHITECTS, LLC

SHEET NUMBER

© THIS SET OF DOCUMENTS INCLUSIVE OF

DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT

BE COPIED, SCANNED, NOR ELECTRONICALLY

DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT

THE EXPRESSED WRITTEN CONSENT OF GRACE

HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,

ELECTRONIC PLAN SERVICE (INTERNET PLAN

SERVICE), NOR REPRODUCTION COMPANY SHALL BE

PERMITTED TO POST THESE DOCUMENTS WITHOUT

THE EXPRESSED WRITTEN CONSENT OF THE

ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.

2024-118

/1

/2

:3

:0

P

M

A u to d e s k D o c s /W a re h o u s e

C o n v e rt t o P a rk s

R e c D e p a rt m e n t/

-1

M e c h a n ic a l M o d e l_

O p ti o n O n e

R e v it

B

IM

.r v t

M101-S

1ST FLOOR PLAN - SOUTH

BUILDING - MECHANICAL

40-24105

W A

R E

H O

U S

E C

O N

V E

R T

T O

P A

R K

S

R E

C D

E P

T

C

IT

Y O

F F

O R

T M

Y E

R S

06/19/2025

PERMIT DOCUMENTS

M

IC

H

IH

A

N A

V E

N U

E F

O R

T M

Y E

R S

F

L O

R

ID

A

1/4" = 1'-0"1 FIRST FLOOR SOUTH BUILDING

1 CONTRACTOR TO ROUTE 1" INSULATED

CONDENSATE PIPING TO NEAREST HUB DRAIN.

2 CONTRACTOR TO COORDINATE EXISTING

PENETRATION IN EXTERIOR WALL WITH NEW

LOUVER (LV-S-4) PRIOR TO PURCAHSE.

3 CONTRACTOR TO PROVIDE FACTORY CONTROLLER

FOR CF-1.

4 SPACE HUMIDITY SENSOR ASSOCIATED WITH

AHU-S-1. TERMINATE SENSOR AT AHU-S-1

CONTROLLER.

5 CONTRACTOR TO INSTALL CONDENSING UNIT 1'

ABOVE FLOOD ELEVATION

6 CONTRACTOR TO COORDINATE EXISTING

PENETRATION IN EXTERIOR WALL WITH NEW

LOUVER (LV-S-1) PRIOR TO PURCAHSE.

7 CONTRACTOR TO PROVIDE ACCESS DOOR FOR

FANS ON RIGHT SIDE OF AIR HANDLER

8 PROVIDE STANDALONE TEMPERATURE SENSOR

FOR MONITORING PURPOSES.

9 CONTRACTOR TO ROUTE INSULATED 1"

CONDENSATE LINE TO NEAREST HUB DRAIN.

DN

C F

M

M

A

A

(TYP.2)

A

(TYP.2)

T

T

T T H

T

T

T

T

T

B

B

B

B

B

B

B

"x

E A

"x

E A

"x

E A

6"x6" EA

8"x8" EA

8"x8" EA

A

A

A

A

A

A

"x

S A

12"x10" SA

"x

S A

8"ø SA

"x

S A

8"ø SA

"x

S A

"x

S A

8"ø SA

6"ø SA

8"x8" SA

"ø

S A

"ø

S A

6"ø SA

8"ø SA 10"x8" SA 1 "x

"x

S A

6"ø SA

6"ø SA

"ø

S A

10"ø SA

10"x10" SA14"x14" SA

"ø

S A

"x

S A

"ø

S A

"x

S A

16"x16" S A

"x

S A 8"ø SA

8"ø SA

8"ø SA

"ø

S A

6"ø SA6"ø SA

"x

S A

8"ø SA

8"ø SA

8"ø SA

12"x10" 8"ø SA

4" CONCRETE PAD

BAS

DISC.

FOR AHU-S-1

LV-S-4

LV-S-1

VAV-S-1-6

VAV-S-1-7

VAV-S-1-3

VAV-S-1-5

VAV-S-1-8

VAV-S-1-1

VAV-S-1-2

VAV-S-1-4

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

CF-1

VAV-S-1-9

EF-S-1

32"x30" RA

"x

R A

34"x20" RA20"x16" RA14"x12" RA

"x

R A

"x

R A

"x

R A

"x

R A

"x

R A

"x

R A

"x

R A

"x

R A

16"x14" RA "x

R A

10"x10" RA

M201

EQUIPMENT TOOLS

CAGES

OFFICE 3

OFFICE 4

1123 OFFICE 5

OFFICE 6

OFFICE 7

229 SF

SMALL CONFERENCE

ROOM

LOUNGE ROOM

357 SF

LARGE CONFERENCE

ROOM

950 SF

SPECIAL EVENT

STORAGE/ MULTI-USE

WORK ROOM

MEN'S RESTROOM

CUSTODIAL

411 SF

PUBLIC

WOMEN'S RESTROOM

CUBICLE 6

238 SF

WOMEN'S BATHROOM

MEN'S BATHROOM

OFFICE 6

MDF ROOM

OPEN SPACE

OFF. SUPPLIES

CUBICLE 4

CUBICLE 5

MAINTENANCE &

REPAIRS AREA

CUSTODIAL

156 SF

MECH. ROOM

84 SF

ELECTRIAL ROOM

PARKS & REC

WAREHOUSE

CLOSET

EXECUTIVE OFFICE

CUBICLE 3

CUBICLE 2

SENIOR ASSIST.

CUSTODIAL

OFFICE 1

OFFICE 2

T

T

MSCU-S-1

4" CONCRETE PAD

EF-S-2 LV-S-2

44"x44" EA

LV-S-3

TA

A

A

10"ø SA

12"x12" SA10"ø SA

26"x20" SA

/4

"ø C

D

MSAC-S-1

VAV-S-10

D

D 270C

B

B

B 725 B

B

B

B

B

B

B 100B

B

A

C

B

6"ø SA

6"ø SA

"ø

S A

20"x12" EA

"x

S A

10"x10" SA

"x

" R

A

"ø

S A

B

"ø

S A

CU-S-1

B

B

B

"x

R A

10"x8" RA 10"x8"

14"x12" OA

AHU-S-1

4" CONCRETE PAD

"x

S A

12"ø SA

8"ø SA

5"ø SA

"ø

S A

"ø

S A

8"ø SA

"x

S A

"ø

S A

10"ø SA

"ø

S A

H/O/A

DISC.

FOR CU-S-1

DISC.

FOR MSCU-S-1

A

GENERAL NOTES:

1. REFER TO GENERAL NOTES FOR THIS DISCIPLINE.

2. REFER TO SPECIFICATIONS.

3. ALL HEX NOTES NOT NECESSARILY USED ON ALL

SHEETS.

4. SEE SECTION VIEW MECHANICAL ROOM PLANS FOR

MORE DETAIL.

5. ALL AIR HANDLING SYSTEMS WILL UTILIZE A FULLY

DUCTED RETURN AIR SYSTEM.

6. PROVIDE A VOLUME DAMPER ON ALL BRANCH

DUCTWORK AND ANY RUNOUT TO A DIFFUSER,

WHETHER SHOWN ON DRAWINGS OR NOT.

7. ALL VOLUME DAMPERS INSTALLED ABOVE GYPSUM

BOARD CEILING SHALL HAVE REMOTELY OPERATED

DAMPER.ALL OUTSIDE AIR LOUVERS SHALL BE

PROVIDED WITH 1/4" X 1/4" REMOVABLE BIRD SCREEN

AND REMOVABLE FILTERS IN A FILTER RACK. THIS

SHALL BE INSTALLED IN A CHANNEL AND SHALL BE

EASILY REMOVED. SCREWED BIRD SCREEN TO THE

LOUVER IS NOT ACCEPTABLE.

8. PROVIDE VOLUME DAMPERS ON EACH BATHROOM

EXHAUST GRILLE.

9. REFER TO MANUFACTURER'S RECOMMENDATIONS

FOR ALL REFRIGERANT PIPE SIZES ACCORDING TO

FINAL LENGTH OF RUN.

10. ALL RETURN GRILLES LOCATIONS MUST BE

INSTALLED AT OR FARTHER THAN LOCATIONS

SHOWN, OR FARTHER THAN BRANCH RUNOUT TO

ELIMINATE NOISE TRANSMISSION.

11. ALL LOUVER PLENUMS SHALL SLOPE BACK TOWARDS

THE LOUVER ON THE EXTERIOR WALL. FINAL SIZE,

HEIGHT, COLOR AND LOCATION OF THE LOUVERS

SHOULD BE COORDINATED WITH THE

ARCHITECTURAL ELEVATIONS AND GENERAL

CONTRACTOR, PRIOR TO ORDERING LOUVERS.

12. FULLY COORDINATE WITH THE ARCHITECTURAL

REFLECTED CEILING PLANS FOR DIFFUSER

LOCATIONS PRIOR TO INSTALLATION.

13. CONTRACTOR SHALL COORDINATE VAV ELECTRICAL

CLEARANCES. INCLUDING LOW VOLTAGE, WITH ALL

CEILING MOUNTED EQUIPMENT IN SHOP DRAWINGS,

WHICH INCLUDES BUT IS NOT LIMITED TO LIGHTING,

PROJECTORS, SYSTEMS DEVICES, AND FIRE

SPRINKLERS. CLEARANCES SHALL BE SIZED AND

COORDINATED AS REQUIRED BASED ON THE

AWARDED MANUFACTURER VAV BOX

REQUIREMENTS. LIGHTS AND EQUIPMENT BELOW THE

VAV CLEARANCE, IN THE CEILING ARE NOT

ACCEPTABLE.

14. REFER TO ARCHITECTURAL DRAWINGS FOR

MOUNTING HEIGHT AND COLOR OF ALL LINEAR

DIFFUSERS.

MPE JOB #:

ENG. BUS. No. EB-0005096

CERT. OF AUTH. No. 5096

PHONE (239) 332-1187

12437 Brantley Commons Fort Myers, FL 33907

TO

D GRIFF

No 67083P R

STATE OF

E

O F

E S

S

ION A L E N

G

IN

E E

R

NSECIL

F L O R I DA

THK

D I

K. Todd Griffith No.67083

HEX NOTES:

PROJECT NO:

DATE:

PHASE:

ISSUED FOR

SEAL:

GRACE HEBERT CURTIS ARCHITECTS, LLC

SHEET NUMBER

© THIS SET OF DOCUMENTS INCLUSIVE OF

DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT

BE COPIED, SCANNED, NOR ELECTRONICALLY

DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT

THE EXPRESSED WRITTEN CONSENT OF GRACE

HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,

ELECTRONIC PLAN SERVICE (INTERNET PLAN

SERVICE), NOR REPRODUCTION COMPANY SHALL BE

PERMITTED TO POST THESE DOCUMENTS WITHOUT

THE EXPRESSED WRITTEN CONSENT OF THE

ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.

2024-118

/1

/2

:1

:4

P

M

A u to d e s k D o c s /W a re h o u s e C o n v e rt t o P a rk s

R e c D e p a rt m e n t/

-1

M e c h a n ic a l M o d e l_

O p ti o n T w o

R e v it

B

IM

.r v t

M101-S-2

1ST FLOOR PLAN - SOUTH

BUILDING - MECHANICAL -

ALTERNATE

40-24105

W A

R E

H O

U S

E C

O N

V E

R T

T O

P A

R K

S

R E

C D

E P

T

C

IT

Y O

F F

O R

T M

Y E

R S

06/19/2025

PERMIT DOCUMENTS

M

IC

H

IH

A

N A

V E

N U

E F

O R

T M

Y E

R S

F

L O

R

ID

A

1/4" = 1'-0"1 FIRST FLOOR SOUTH BUILDING

1 CONTRACTOR TO ROUTE 1" INSULATED

CONDENSATE PIPING TO NEAREST HUB DRAIN.

2 CONTRACTOR TO COORDINATE EXISTING

PENETRATION IN EXTERIOR WALL WITH NEW

LOUVER (LV-S-4) PRIOR TO PURCAHSE.

3 CONTRACTOR TO PROVIDE FACTORY CONTROLLER

FOR CF-1.

4 SPACE HUMIDITY SENSOR ASSOCIATED WITH

AHU-S-1. TERMINATE SENSOR AT AHU-S-1

CONTROLLER.

5 CONTRACTOR TO INSTALL CONDENSING UNIT 1'

ABOVE FLOOD ELEVATION

6 CONTRACTOR TO COORDINATE EXISTING

PENETRATION IN EXTERIOR WALL WITH NEW

LOUVER (LV-S-1) PRIOR TO PURCAHSE.

7 CONTRACTOR TO PROVIDE ACCESS DOOR FOR

FANS ON RIGHT SIDE OF AIR HANDLER

8 PROVIDE STANDALONE TEMPERATURE SENSOR

FOR MONITORING PURPOSES.

9 CONTRACTOR TO ROUTE INSULATED 1"

DN

C F

M

M

A

A

(TYP.2)

A

(TYP.2)

T

T

T T H

T

T

T

T

T

B

B

B

B

B

B

B

"x

E A

"x

E A

"x

E A

6"x6" EA

8"x8" EA

8"x8" EA

A

A

A

A

A

A

"x

S A

12"x10" SA

"x

S A

8"ø SA

"x

S A

8"ø SA

"x

S A

"x

S A

8"ø SA

6"ø SA

8"x8" SA

"ø

S A

"ø

S A

6"ø SA

8"ø SA 10"x8" SA 1 "x

"x

S A

6"ø SA

6"ø SA

"ø

S A

10"ø SA

10"x10" SA14"x14" SA

"ø

S A

"x

S A

"ø

S A

"x

S A

16"x16" S A

"x

S A 8"ø SA

8"ø SA

8"ø SA

"ø

S A

6"ø SA6"ø SA

"x

S A

8"ø SA

8"ø SA

8"ø SA

12"x10" 8"ø SA

4" CONCRETE PAD

BAS

DISC.

FOR AHU-S-1

LV-S-4

LV-S-1

VAV-S-1-6

VAV-S-1-7

VAV-S-1-3

VAV-S-1-5

VAV-S-1-8

VAV-S-1-1

VAV-S-1-2

VAV-S-1-4

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

CF-1

VAV-S-1-9

EF-S-1

32"x30" RA

"x

R A

34"x20" RA20"x16" RA14"x12" RA

"x

R A

"x

R A

"x

R A

"x

R A

"x

R A

"x

R A

"x

R A

"x

R A

16"x14" RA "x

R A

10"x10" RA

M201

EQUIPMENT TOOLS

CAGES

OFFICE 3

OFFICE 4

1123 OFFICE 5

OFFICE 6

OFFICE 7

229 SF

SMALL CONFERENCE

ROOM

LOUNGE ROOM

357 SF

LARGE CONFERENCE

ROOM

950 SF

SPECIAL EVENT

STORAGE/ MULTI-USE

WORK ROOM

MEN'S RESTROOM

CUSTODIAL

411 SF

PUBLIC

WOMEN'S RESTROOM

CUBICLE 6

238 SF

WOMEN'S BATHROOM

MEN'S BATHROOM

OFFICE 6

MDF ROOM

OPEN SPACE

OFF. SUPPLIES

CUBICLE 4

CUBICLE 5

MAINTENANCE &

REPAIRS AREA

CUSTODIAL

156 SF

MECH. ROOM

84 SF

ELECTRIAL ROOM

PARKS & REC

WAREHOUSE

CLOSET

EXECUTIVE OFFICE

CUBICLE 3

CUBICLE 2

SENIOR ASSIST.

CUSTODIAL

OFFICE 1

OFFICE 2

T

T

MSCU-S-1

4" CONCRETE PAD

EF-S-2 LV-S-2

44"x44" EA

LV-S-3

TA

A

A

10"ø SA

12"x12" SA10"ø SA

26"x20" SA

/4

"ø C

D

MSAC-S-1

VAV-S-10

D

D 270C

B

B

B 725 B

B

B

B

B

B

B 100B

B

A

C

B

6"ø SA

6"ø SA

"ø

S A

20"x12" EA

"x

S A

10"x10" SA

"x

" R

A

"ø

S A

B

"ø

S A

CU-S-1

B

B

B

"x

R A

10"x8" RA 10"x8"

14"x12" OA

AHU-S-1

4" CONCRETE PAD

"x

S A

12"ø SA

8"ø SA

5"ø SA

"ø

S A

"ø

S A

8"ø SA

"x

S A

"ø

S A

10"ø SA

"ø

S A

H/O/A

DISC.

FOR CU-S-1

DISC.

FOR MSCU-S-1

A

GENERAL NOTES:

1. REFER TO GENERAL NOTES FOR THIS DISCIPLINE.

2. REFER TO SPECIFICATIONS.

3. ALL HEX NOTES NOT NECESSARILY USED ON ALL

SHEETS.

4. SEE SECTION VIEW MECHANICAL ROOM PLANS FOR

MORE DETAIL.

5. ALL AIR HANDLING SYSTEMS WILL UTILIZE A FULLY

DUCTED RETURN AIR SYSTEM.

6. PROVIDE A VOLUME DAMPER ON ALL BRANCH

DUCTWORK AND ANY RUNOUT TO A DIFFUSER,

WHETHER SHOWN ON DRAWINGS OR NOT.

7. ALL VOLUME DAMPERS INSTALLED ABOVE GYPSUM

BOARD CEILING SHALL HAVE REMOTELY OPERATED

DAMPER.ALL OUTSIDE AIR LOUVERS SHALL BE

PROVIDED WITH 1/4" X 1/4" REMOVABLE BIRD SCREEN

AND REMOVABLE FILTERS IN A FILTER RACK. THIS

SHALL BE INSTALLED IN A CHANNEL AND SHALL BE

EASILY REMOVED. SCREWED BIRD SCREEN TO THE

LOUVER IS NOT ACCEPTABLE.

8. PROVIDE VOLUME DAMPERS ON EACH BATHROOM

EXHAUST GRILLE.

9. REFER TO MANUFACTURER'S RECOMMENDATIONS

FOR ALL REFRIGERANT PIPE SIZES ACCORDING TO

FINAL LENGTH OF RUN.

10. ALL RETURN GRILLES LOCATIONS MUST BE

INSTALLED AT OR FARTHER THAN LOCATIONS

SHOWN, OR FARTHER THAN BRANCH RUNOUT TO

ELIMINATE NOISE TRANSMISSION.

11. ALL LOUVER PLENUMS SHALL SLOPE BACK TOWARDS

THE LOUVER ON THE EXTERIOR WALL. FINAL SIZE,

HEIGHT, COLOR AND LOCATION OF THE LOUVERS

SHOULD BE COORDINATED WITH THE

ARCHITECTURAL ELEVATIONS AND GENERAL

CONTRACTOR, PRIOR TO ORDERING LOUVERS.

12. FULLY COORDINATE WITH THE ARCHITECTURAL

REFLECTED CEILING PLANS FOR DIFFUSER

LOCATIONS PRIOR TO INSTALLATION.

13. CONTRACTOR SHALL COORDINATE VAV ELECTRICAL

CLEARANCES. INCLUDING LOW VOLTAGE, WITH ALL

CEILING MOUNTED EQUIPMENT IN SHOP DRAWINGS,

WHICH INCLUDES BUT IS NOT LIMITED TO LIGHTING,

PROJECTORS, SYSTEMS DEVICES, AND FIRE

SPRINKLERS. CLEARANCES SHALL BE SIZED AND

COORDINATED AS REQUIRED BASED ON THE

AWARDED MANUFACTURER VAV BOX

REQUIREMENTS. LIGHTS AND EQUIPMENT BELOW THE

VAV CLEARANCE, IN THE CEILING ARE NOT

ACCEPTABLE.

14. REFER TO ARCHITECTURAL DRAWINGS FOR

MOUNTING HEIGHT AND COLOR OF ALL LINEAR

DIFFUSERS.

MPE JOB #:

ENG. BUS. No. EB-0005096

CERT. OF AUTH. No. 5096

PHONE (239) 332-1187

12437 Brantley Commons Fort Myers, FL 33907

TO

D GRIFF

No 67083P R

STATE OF

E

O F

E S

S

ION A L E N

G

IN

E E

R

NSECIL

F L O R I DA

THK

D I

K. Todd Griffith No.67083

HEX NOTES:

PROJECT NO:

DATE:

PHASE:

ISSUED FOR

SEAL:

GRACE HEBERT CURTIS ARCHITECTS, LLC

SHEET NUMBER

© THIS SET OF DOCUMENTS INCLUSIVE OF

DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT

BE COPIED, SCANNED, NOR ELECTRONICALLY

DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT

THE EXPRESSED WRITTEN CONSENT OF GRACE

HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,

ELECTRONIC PLAN SERVICE (INTERNET PLAN

SERVICE), NOR REPRODUCTION COMPANY SHALL BE

PERMITTED TO POST THESE DOCUMENTS WITHOUT

THE EXPRESSED WRITTEN CONSENT OF THE

ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.

2024-118

/1

/2

:0

:1

P

M

A u to d e s k D o c s /W a re h o u s e C o n v e rt t o P a rk s

R e c D e p a rt m e n t/

-1

M e c h a n ic a l M o d e l_

O p ti o n T w o

R e v it

B

IM

.r v t

M101-S-2

1ST FLOOR PLAN - SOUTH

BUILDING - MECHANICAL -

ALTERNATE

40-24105

W A

R E

H O

U S

E C

O N

V E

R T

T O

P A

R K

S

R E

C D

E P

T

C

IT

Y O

F F

O R

T M

Y E

R S

06/19/2025

PERMIT DOCUMENTS

M

IC

H

IH

A

N A

V E

N U

E F

O R

T M

Y E

R S

F

L O

R

ID

A

1/4" = 1'-0"1 FIRST FLOOR SOUTH BUILDING

1 CONTRACTOR TO ROUTE 1" INSULATED

CONDENSATE PIPING TO NEAREST HUB DRAIN.

2 CONTRACTOR TO COORDINATE EXISTING

PENETRATION IN EXTERIOR WALL WITH NEW

LOUVER (LV-S-4) PRIOR TO PURCAHSE.

3 CONTRACTOR TO PROVIDE FACTORY CONTROLLER

FOR CF-1.

4 SPACE HUMIDITY SENSOR ASSOCIATED WITH

AHU-S-1. TERMINATE SENSOR AT AHU-S-1

CONTROLLER.

5 CONTRACTOR TO INSTALL CONDENSING UNIT 1'

ABOVE FLOOD ELEVATION

6 CONTRACTOR TO COORDINATE EXISTING

PENETRATION IN EXTERIOR WALL WITH NEW

LOUVER (LV-S-1) PRIOR TO PURCAHSE.

7 CONTRACTOR TO PROVIDE ACCESS DOOR FOR

FANS ON RIGHT SIDE OF AIR HANDLER

8 PROVIDE STANDALONE TEMPERATURE SENSOR

FOR MONITORING PURPOSES.

9 CONTRACTOR TO ROUTE INSULATED 1"

BUILDING AUTOMATION SYSTEM & CONTROLS GENERAL NOTES

GENERAL NOTES

1. REFER TO SPECIFICATION SECTION 23 09 23.

2. REFER TO SPECIFICATION SECTION 23 09 93.

3. REFER TO SPECIFICATION SECTION 23 05 93.

4. REFER TO SPECIFICATION SECTION 23 08 00.

5. REFER TO THE DIVISION 23 SPECIFICATIONS.

6. REFER TO THE DIVISION 26 SPECIFICATIONS.

7. REFER TO NEC.

8. REFER TO PROJECT GENERAL NOTES.

9. CONTROL DRAWINGS ARE NOT TO SCALE.

10. CONTROL FLOW DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE

NOT MEANT TO REPRESENT THE PHYSICAL CONFIGURATIONS OR

DIMENSIONS OF THE REFERENCED EQUIPMENT.

11. CONTROL FLOW SHAPES ARE DIAGRAMMATIC IN NATURE AND ARE NOT

MEANT TO REPRESENT THE PHYSICAL CONFIGURATIONS, DIMENSIONS,

MODELS, TYPES, GENERATIONS, OR MANUFACTURERS OF THE

REFERENCED DEVICES.

12. THE CONTROL POINTS INDICATED IN THESE DRAWINGS ARE

REPRESENTATIVE OF THE MINIMUM SUCH POINTS REQUIRED TO

ACHIEVE THE INTENDED SEQUENCE OF OPERATION AND SYSTEM

MONITORING FUNCTIONALITY. CONTROL SCHEMES EMPLOYING FEWER

POINTS IN CONCERT WITH SHARED VALUES, COMMUNICATED VALUES,

OR CALCULATED VALUES IN LIEU OF INDICATED POINT COUNT SHALL

NOT BE ACCEPTABLE.

13. THE CONTROL HARDWARE AND END DEVICES INDICATED IN THESE

DRAWINGS ARE REPRESENTATIVE OF THE MINIMUM SUCH DEVICES

REQUIRED TO ACHIEVE THE INTENDED SEQUENCE OF OPERATION AND

SYSTEM MONITORING FUNCTIONALITY. CONTROL SCHEMES EMPLOYING

FEWER DEVICES IN CONCERT WITH SHARED VALUES, COMMUNICATED

VALUES, OR CALCULATED VALUES IN LIEU OF INDICATED DEVICE

QUANTITY SHALL NOT BE ACCEPTABLE.

14. CONTROLS HARDWARE AND END DEVICES INSTALLED BY OR PROVIDED

BY HVAC EQUIPMENT MANUFACTURER ARE SUBJECT TO THE SAME

SPECIFICATIONS AND REQUIREMENTS AS THOSE INSTALLED BY OR

PROVIDED BY THE BAS CONTRACTOR.

15. ANY INDIVIDUAL SYSTEM, AS DEFINED BY CONTROLS FLOW DIAGRAMS,

CONTROLLED OR MONITORED BY THE BAS COMPRISED OF THREE OR

GREATER CONTROLS POINTS, COMBINATION OF INPUTS AND OUTPUTS,

SHALL BE EQUIPPED WITH A DEDICATED CONTROLLER WITHIN THE BAS

ARCHITECTURE.

16. WHERE PERIPHERAL SYSTEMS ARE CONTROLLED OR MONITORED VIA

THE USE OF AUXILIARY POINT TERMINATIONS ON CONTROLLERS NOT

DEDICATED TO SAID SYSTEMS, BAS CONTRACTOR SHALL PROVIDE A

SCHEDULE OF SUCH SYSTEMS INDICATING THE CONTROLS POINTS IN

QUESTION, THE LOCATION OF THE ASSOCIATED CONTROLLER, AND THE

INDIVIDUAL POINT TERMINATION DESIGNATIONS. THIS INFORMATION

SHALL BE DISPLAYED ON THE BAS GRAPHICAL INTERFACE FOR

REFERENCE PURPOSES.

17. SYSTEM ALARMS AND NOTIFICATIONS SHALL BE IDENTIFIED WITH

SPECIFIC UNIT TAGS, BUILDING NUMBERS, ROOM NUMBERS, OR OTHER

SITE SPECIFIC IDENTIFYING CRITERIA, VIA THE BAS INTERFACE, SUCH

THAT SYSTEM OPERATORS CAN ASSOCIATE ANY ALARM WITH THE

SPECIFIC PIECE OF EQUIPMENT IT IS RELATED TO.

18. BAS FLOOR PLAN GRAPHICS SHALL INCLUDE SITE SPECIFIC BUILDING

NUMBERS OR NAMES, ROOM NUMBERS OR NAMES, GENERAL AREA

DESIGNATIONS, AND EQUIPMENT TAGS SUCH THAT SYSTEM

OPERATORS CAN ASSOCIATE OCCUPANT COMMUNICATIONS WITH THE

SPECIFIC PIECE OF EQUIPMENT SERVING THE LOCATION IN QUESTION.

19. BAS GRAPHICS TEXT SHALL BE ARRANGED IN A LOGICAL MANNER AND

CONFIGURED TO COINCIDE WITH THE GRAPHICAL DESIGN AND COLOR

SCHEME SUCH THAT TEXT IS CLEAR & LEGIBLE AND ITS PLACEMENT

DOES NOT RESULT IN EXCESSIVE OVERLAP WITH BACKGROUND

IMAGES.

20. SPACE SENSORS MOUNTED ON EXTERIOR WALLS SHALL BE

THERMALLY INSULATED FROM THE SURFACE TO WHICH THEY ARE

MOUNTED.

21. BAS CONTROLLERS SHALL BE PROGRAMMED WITH A DEFAULT

OPERATIONAL STATE TO BE ACTIVATED IN THE EVENT OF SYSTEM

COMMUNICATION FAILURE IN ACCORDANCE WITH THE SEQUENCE OF

OPERATION OF THE ASSOCIATED SYSTEM. IF NO DEFAULT STATE IS

SPECIFIED, IT SHALL BE ASSUMED THAT THE SYSTEM IS INTENDED TO

OPERATE IN OCCUPIED MODE DURING COMMUNICATION FAILURE.

22. CONTROLS HARDWARE AND END DEVICES EQUIPPED WITH LOCAL

DISPLAYS SHALL BE MOUNTED SUCH THAT THE LOCAL DISPLAY IS FREE

OF OBSTRUCTIONS AND IS LEGIBLE FROM A HEIGHT OF FIVE FEET

ABOVE THE FLOOR.

23. FOR THE PURPOSE OF CONTROL VALVE SELECTION, A NOMINAL

PRESSURE DROP OF BETWEEN 3 TO 4 PSI SHALL BE USED TO

CALCULATE THE TARGET FLOW COEFFICIENT (Cv) OF THE SELECTED

VALVE.

24. CONTROL VALVE SIZE (DIAMETER) SHALL NOT BE MORE THAN TWO

STANDARD PIPE SIZES (DIAMETERS) SMALLER THAN THE INCOMING

PIPE SIZE (DIAMETER).

25. TWO POSITION CONTROL VALVES USED FOR ISOLATION PURPOSES

SHALL BE OF THE SAME SIZE (DIAMETER) AS THE INCOMING PIPE.

26. CONTROL VALVES SHALL BE SELECTED TO FACILITATE SUFFICIENT

CONTROLLABILITY RELATIVE TO THE CONTROLLED LOAD WITH AT

LEAST 75% OF THE TOTAL VALVE STROKE AVAILABLE AT NOMINAL

SYSTEM PRESSURE.

27. CONTROL VALVES AND ACTUATORS SHALL BE SELECTED WITH

SUFFICIENT CLOSE OFF PRESSURE TO FACILITATE FULL VALVE

CLOSURE AT MAXIMUM SYSTEM PRESSURE.

28. FOR SYSTEMS EMPLOYING FLOATING POINT ACTUATORS, THE BAS

SHALL BE PROGRAMMED TO EXECUTE A PERIODIC…

This is the start of the file's text. The full file is on GovTribe.