About this file
This document is a comprehensive set of mechanical engineering design and construction drawings for the Warehouse Convert to Parks & Rec Department project for the City of Fort Myers, Florida, located at 2801 Michigan Avenue. The project involves mechanical system renovations for two buildings (North and South), with a total renovation area of approximately 14,574 square feet. The mechanical design is based on the 2023 8th Edition Florida Building Code, Florida Fire Prevention Code, and ASHRAE standards. The project includes the installation of multiple air handling units (AHU-N-1, AHU-S-1), blower coil units, condensing units, exhaust fans, and variable air volume (VAV) terminal units with and without electric heating coils.
The mechanical systems are designed to provide heating, ventilation, and air conditioning (HVAC) for various spaces including offices, conference rooms, restrooms, storage areas, and a warehouse. The design incorporates energy-efficient components such as electronically commutated motors (ECM), MERV 13 filters, and building automation system (BAS) controls. The system includes features like demand control ventilation, optimal start capabilities, and humidity monitoring. The project appears to be funded by the City of Fort Myers and is scheduled for permit documents as of June 19, 2025, with the mechanical design prepared by Matern Professional Engineering, located in Fort Myers, Florida.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT DESIGN CONDITIONS - SOUTH BUILDING
TEMPERATURE CONDITIONS BUILDING LOAD CONDITIONS
OUTDOOR INTERNAL LOADS
DRY BULB
(F)
WET
BULB (F)
COMMENTS QUANTITY UNITS COMMENTS
SUMMER 95 78 (0.40% mean coincided db/wb) PEOPLE N/A PEOPLE BASED ON FURNITURE LAYOUTS
SUMMER NA NA
(0.40% wetbulb used for Cooling
Tower Selection)
LIGHTING VARIES W/SF BASED ON FBC TABLE C405.3.2(2)
WINTER 40 X (99.6% db) EQUIPMENT VARIES W
BASED ON FURNITURE LAYOUT
AND ASHRAE FUNDAMENTALS
DAILY RANGE X VENTILATION AIR VARIES
CFM/SQFT &
CFM/PERSON
BASED ON ASHRAE 90.1
LOCATION BASED ON ASHRAE WEATHER
DATA FOR:
FORT MYERS, FL FLOOR AREA 7,080 SF RENOVATED AREA
INDOOR EXTERNAL LOADS
DRY BULB
(F)
RH % COMMENTS
"U"
FACTOR
SHADING
COEF.
COMMENTS
COOLING 75 60 WALL VARIES X EXISTING
HEATING 68 60 ROOF VARIES X EXISTING
GLAZING VARIES VARIES EXISTING
VENTILATION DETERMINATION IS BASED ON OCCUPANCY PER ASHRAE STD. 62.1-2019
ENVELOPE AND EQUIPMENT EFFICIENCIES ARE BASED ON ASHRAE STD. 90.1-2019 & THE 2023 8th EDITION FLORIDA BUILDING CODE - ENERGY CONSERVATION
THIS PROJECT IS DESIGNED UNDER THE 2023 8th EDITION FLORIDA BUILDING CODE & 2023 8th EDITION OF THE FLORIDA FIRE PREVENTION CODE
PROJECT DESIGN CONDITIONS - NORTH BUILDING
TEMPERATURE CONDITIONS BUILDING LOAD CONDITIONS
OUTDOOR INTERNAL LOADS
DRY BULB
(F)
WET
BULB (F)
COMMENTS QUANTITY UNITS COMMENTS
SUMMER 95 78 (0.40% mean coincided db/wb) PEOPLE N/A PEOPLE BASED ON FURNITURE LAYOUTS
SUMMER NA NA
(0.40% wetbulb used for Cooling
Tower Selection)
LIGHTING VARIES W/SF BASED ON FBC TABLE C405.3.2(2)
WINTER 40 X (99.6% db) EQUIPMENT VARIES W
BASED ON FURNITURE LAYOUT
AND ASHRAE FUNDAMENTALS
DAILY RANGE X VENTILATION AIR VARIES
CFM/SQFT &
CFM/PERSON
BASED ON ASHRAE 90.1
LOCATION BASED ON ASHRAE WEATHER
DATA FOR:
FORT MYERS, FL FLOOR AREA 7,494 SF RENOVATED AREA
INDOOR EXTERNAL LOADS
DRY BULB
(F)
RH % COMMENTS
"U"
FACTOR
SHADING
COEF.
COMMENTS
COOLING 78 60 RECORDS STORAGE WALL VARIES X EXISTING
COOLING 75 60 SECOND FLOOR ROOF VARIES X EXISTING
COOLING 75 60 PRINT ROOM GLAZING VARIES X EXISTING
HEATING 68 60 PRINT ROOM
VENTILATION DETERMINATION IS BASED ON OCCUPANCY PER ASHRAE STD. 62.1-2019
ENVELOPE AND EQUIPMENT EFFICIENCIES ARE BASED ON ASHRAE STD. 90.1-2019 & THE 2023 8th EDITION FLORIDA BUILDING CODE - ENERGY CONSERVATION
THIS PROJECT IS DESIGNED UNDER THE 2023 8th EDITION FLORIDA BUILDING CODE & 2023 8th EDITION OF THE FLORIDA FIRE PREVENTION CODE
TRANSFER AIR OPENINGTAO
WALL CLEANOUTWCO
TD TRENCH DRAIN
VOLUME DAMPERVD
SAF SUPPLY AIR FAN
REQUIREDREQ'D
PRESS PRESSURE
INSUL INSULATION
HORIZ HORIZONTAL
H20 WATER
EXISTINGEXIST
CONCRETE MASONARY UNITCMU
CONTINUATIONCONT
COMBINATIONCOMB
BRAKE HORSEPOWERBHP
ACCESS PANELAP
AUXILLIARYAUX
AUTOMATICAUTO
ARCHITECTURALARCH
WMS
RAF
SAN
UH
SA
RA
RM
RPM
SAU
SP
SPEC
TDH
TEMP
PSIG
PVC
RH
VAV
W
W/
W/O
WB
WC
WG
WP
RHC
RV
HW HOT WATER
PRIMARY CHILLED WATER PUMP
BOD BOTTOM OF DUCT
D
EF
AHU
OA
FDPR
APPROX
AFF
AD
CHR
CHS
DRAIN LINE
EXHAUST FAN
AIR HANDLING UNIT
OUTSIDE AIR
FIRE DAMPER
APPROXIMATELY
ABOVE FINISHED FLOOR
ACCESS DOOR
CHILLED WATER RETURN
CHILLED WATER SUPPLY
AC
FCU
COLD WATER (CITY)
BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNITS PER HOUR
CFM
CUH CABINET UNIT HEATER
DG
EAT
EVAP
EWT
EH
LAT LEAVING AIR TEMPERTURE
LB/HR
LWT
MBH
NIC
NTS
NC
NO
CW
BTU
A
BLDG
CC
CD
CH
CHWP
CLG
CO
COMPR
COND
CU FT
CU IN
DB
DHW
DIAM
DN
DWG
DX
EDH
EL
ELEC
EQ
EWB
EXP
°F
FA
FBP
FLA
FPI
FPS
FV
GA
GAL
GPH
GPM
HT
HC
HD
HP
HR
HZ
IN
KW
LBS
LDB
LIN FT
LWB
MAX
MB
MC
MIN
NO.
OD
OV
PD
PHC
PSI
AMPERES
BUILDING
COOLING COIL
CONDENSATE DRAIN
CHILLER
CHILLED WATER PUMP
CEILING
CLEAN-OUT
CONDENSATE OR CONDENSER
CUBIC FEET
CUBIC INCHES
COMPRESSOR
DRY BULB
DOMESTIC HOT WATER
DIAMETER
DOWN
DRAWING
DIRECT EXPANSION
ELECTRIC DUCT HEATER
ELEVATION
ELECTRICAL
EQUAL
ENTERING WET BULB TEMPERATURE
EXPANSION
DEGREES FAHRENHEIT
FREE AREA (SQ. FT.) 0R FACE AREA
FIELD BUILT PLENUM
FULL LOAD AMPERES
FINS PER INCH
FEET PER SECOND
FACE VELOCITY
GAUGE
GALLONS
GALLONS PER HOUR
GALLONS PER MINUTE
HEIGHT
HEATING COIL
HEAD
HORSEPOWER OR HEAT PUMP
HOUR
FREQUENCY (HERTZ)
INCH OR INCHES
KILOWATT
POUNDS
LEAVING DRY BULB TEMPERATURE
LINEAR FEET
LEAVING WET BULB
MAXIMUM
MIXING BOX
MECHANICAL CONTRACTOR
MINIMUM
NUMBER
OUTSIDE DIAMETER
OUTLET VELOCITY
PRESSURE DROP
PREHEAT COIL
POUNDS PER SQUARE INCH
FPM FEET PER MINUTE
WIRE MESH SCREEN
RETURN AIR FAN
SANITARY
UNIT HEATER
SUPPLY AIR
RETURN AIR
*REFRIGERANT HOT GAS DISCHARGE
*REFRIGERANT LIQUID LINE
*REFRIGERANT SUCTION LINE
ROOM
REVOLUTIONS PER MINUTE
SOUND ATTENUATION UNIT
STATIC PRESSURE
SPECIFICATION
TOTAL DYNAMIC HEAD
TEMPERATURE
TYPICAL
PSI GAUGE
POLYVINYL CHLORIDE
RELATIVE HUMIDITY
VARIABLE AIR VOLUME UNIT
WATT
WITH
WITHOUT
WET BULB
WATER COLUMN
WATER GAUGE
WORKING PRESSURE
REHEAT COIL
RELIEF VALVE
PSIA PSI ABSOLUTE
HB HOSE BIBB
F FIRE SPRINKLER PIPING PCHWP
FD FLOOR DRAIN
S/FDPR COMBINED SMOKE AND FIRE DAMPER
SDPR SMOKE DAMPER
FCO FLOOR CLEANOUT
FTB FAN POWERED TERMINAL BOX
SGCHS SECONDARY GLYCOL CHILLED WATER SUPPLY
SGCHR SECONDARY GLYCOL CHILLED WATER RETURN
AIR CONDITIONING
CUBIC FEET PER MINUTE
DOOR GRILLE
ENTERING AIR TEMPERATURE
ELECTRIC HEATER
EVAPORATOR
ENTERING WATER TEMPERATURE
FAN COIL UNIT
POUNDS PER HOUR
LEAVING WATER TEMPERATURE
BTUH, THOUSANDS
NORMALLY CLOSED
NOT IN CONTRACT
NOT TO SCALE
NORMALLY OPEN
RHG
RLL
RSL
AIR SEPARATORAS
BUILDING AUTOMATION SYSTEMBAS
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
CWP CONDENSER WATER PUMP
CONN CONNECTION
CU CONDENSING UNIT
EA EXHAUST AIR
EDB ENTERING DRY BULB TEMPERATURE
ET EXPANSION TANK
FLEX FLEXIBLE
ID INSIDE DIAMETER
MCA MAXIMUM CIRCUIT AMPS
MOCP MAXIMUM OVERCURRENT PROTECTION
LRA LOCK ROTOR AMPS
RLA RATED LOAD AMPS
PLUMBING CONTRACTORPC
RELIEF FANRF
SCHWP SECONDARY CHILLED WATER PUMP
UG UNDERGROUND
ZD ZONE DAMPER
MECHANICAL ABBREVIATIONS
TYP
CHILLED WATER SUPPLY (ABOVE GRADE)
CHILLED WATER RETURN (ABOVE GRADE)
CONDENSATE DRAIN (ABOVE GRADE)
CONDENSATE DRAIN (BELOW GRADE)
CHILLED WATER RETURN (BELOW GRADE)
CHILLED WATER SUPPLY (BELOW GRADE)
CHEMICAL FEED PIPING
FLEXIBLE ROUND DUCT
CONDENSER WATER SUPPLY (ABOVE GRADE)
CONDENSER WATER RETURN (ABOVE GRADE)
CONDENSER WATER RETURN (BELOW GRADE)
CONDENSER WATER SUPPLY (BELOW GRADE)
CD
CF
CD-UG
CHR
CHS
CHR-UG
CHS-UG
GENERAL LEGEND
CWR
CWS
CWR-UG
CWS-UG
PITCH PIPE DOWN IN DIRECTION OF ARROW
SOLENOID VALVE
PIPE UP
PIPE DOWN
PIPE SECTION-RETURN
PIPE SECTION-SUPPLY
FLOW ARROW
PIPE ANCHOR
A
PIPE GUIDE
G
EXPANSION JOINT
GATE VALVE
GLOBE VALVE
STRAINER, Y-TYPE AND BLOW-OFF VALVE
CONTROL VALVE (2-WAY, 3-WAY)
CAPPED LINE
PIPE CONTINUATION
BALL VALVE
CHECK VALVE, HORIZONTAL SWING
EJ
FLEXIBLE CONNECTOR
BALANCING COCK
BC
BUTTERFLY VALVE, TAPPED LUG WAFER
MANUAL AIR VENT
MAV
PRESSURE GAUGE TAPPING (WATER)
NEEDLE VALVE
S
AUTOMATIC AIR VENT
AAV
TEMPERATURE & PRESSURE TAP (PETE'S PLUG)
PP
SHUT -OFF VALVE & PRESSURE TAPPTV
PTW
PRESSURE GAUGE W/BALL VALVE (WATER)PG
SHUT -OFF VALVE & PRESSURE TAPSV
CHECK VALVE, VERTICAL SPRING LOADED
PIPE REDUCTION4"
THERMOMETER
T
THERMOMETER WELL
TW
6"
SHEET WHERE SECTION APPEARS
SECTION DESIGNATION
M101
PIPE DESIGNATIONS
UC
CFM
DOOR UNDERCUT TAG
G-1
(2)
AIRFLOW (CFM)
DIFFUSER TYPE (REFER
TO SCHEDULE AND
SPECIFICATIONS)
TYPICAL FIXTURE
COUNT
DIFFUSER TAG}
DUCT TAKE-OFF W/ VOLUME DAMPER
(CONICAL, RECTANGULAR)
CEILING AIR DEVICE - SUPPLY
(SHADED AREA DENOTES BLANKED
OFF PANEL)
CEILING AIR DEVICE - RETURN
RECTANGULAR ELBOW WITH
TURNING VANES
SIDE WALL RETURN AIR DEVICE
SIDE WALL SUPPLY AIR DEVICE
POINT OF CONNECTION
POINT OF DISCONNECTION
ACCESS DOOR IN DUCT
CEILING AIR DEVICE - EXHAUST
DOWN DUCT STATIC PRESSURE SENSOR
SPACE CARBON DIOXIDE SENSOR
REMOTE TEMPERATURE SENSOR
SPACE HUMIDITY SENSOR
SMOKE DETECTOR
MOTORIZED DAMPER
MOTORIZED VALVE
SPACE TEMPERATURE SENSOR
HUMIDISTAT
AIR FLOW MEASURING STATION
FLOW METER
BACKDRAFT DAMPER
COMBINATION - FIRE/SMOKE DAMPER
SMOKE DAMPER
VOLUME DAMPER
MECHANICAL THERMOSTAT
M
FM
FIRE DAMPER
DOUBLE WALL DUCT
CO2
T
T
H
H
B B
D
SP
C F
M
S
S
M
T
SD
DEMOLITION REGION
GENERAL:
1. REFER TO THE DIVISION 23 SPECIFICATIONS.
2. THE CONTRACTOR SHALL DEMONSTRATE EACH HVAC SYSTEMS PERFORMANCE IN THE PRESENCE OF THE ENGINEER AND THE OWNER'S PROJECT MANAGER. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COST OF ANY ADDITIONAL SYSTEM TEST REQUIRED IF IN THE OPINION OF THE ENGINEER AND
THE OWNER'S PROJECT MANAGER THE SYSTEMS DO NOT PERFORM AS SPECIFIED.
3. VISIT AND CAREFULLY EXAMINE THOSE PORTIONS OF THE BUILDING AND SITE AFFECTED BY THIS WORK BEFORE SUBMITTING PROPOSALS, SO AS TO BECOME FAMILIAR WITH EXISTING CONDITIONS AND DIFFICULTIES THAT WILL AFFECT EXECUTION OF THE WORK. SUBMISSION OF A PROPOSAL WILL BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE AND LATER CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE OF DIFFICULTIES ENCOUNTERED WILL NOT BE
RECOGNIZED.
4. ALL GRILLES, REGISTERS OR DIFFUSERS SHOWN IN THE CEILING SHALL BE 24x24 UNLESS OTHERWISE
NOTED.
5. PROVIDE A VOLUME DAMPER AT EVERY LOW PRESSURE BRANCH DUCT AND AS SHOWN ON THE
DOCUMENTS FOR ALL DUCTWORK SYSTEMS. ALL DAMPERS MAY NOT BE SHOWN ON THE DOCUMENTS
FOR CLARITY.
6. FULLY COORDINATE ALL CEILING MOUNTED AIR DISTRIBUTION DEVICES WITH ARCHITECTURAL CEILING
GRID.
7. VERIFY EXACT LOCATION OF ALL ELECTRICAL EQUIPMENT INCLUDING WALL SWITCHES, FIRE ALARM
DEVICES, ETC. WITH ELECTRICAL CONTRACTOR AND ELECTRICAL DRAWINGS.
8. ALL DUCT SIZES INDICATED ON THE DOCUMENTS ARE NET FREE AREA DIMENSIONS.
9. UNFORESEEN CONDITIONS MAY EXIST AND WORK MAY NOT BE FIELD LOCATED EXACTLY AS SHOWN
ON THE DRAWINGS. COOPERATION WITH OTHER TRADES IN ROUTING AS DETERMINED DURING
CONSTRUCTION AND AS DIRECTED BY THE ARCHITECT/ENGINEER MAY BE NECESSARY. IT IS INTENDED THAT SUCH DEVIATIONS SHALL BE CONSIDERED AS PART OF THIS CONTRACT. SUCH DEVIATIONS MAY NOT BE CONSIDERED AS PART OF THIS CONTRACT WHEN PROPERLY DOCUMENTED IN WRITING. THE PLANS ARE NOT COMPLETELY TO SCALE. THIS CONTRACTOR IS TO FIELD VERIFY DIMENSIONS OF ALL
SITE UTILITIES, ETC., PRIOR TO BID AND INCLUDE ANY DEVIATIONS IN THE CONTRACT.
10. ALL DUCT IS TO BE CONCEALED ABOVE CEILING OR IN NEW WALLS, UNLESS SPECIFICALLY NOTED AS
EXPOSED OR SURFACE MOUNTED.
11. WORK SHALL BE PERFORMED IN STRICT COMPLIANCE WITH THE ESTABLISHED WORK SCHEDULE
BEING SET FORTH BY THE OWNER. COORDINATE ALL WORK WITH GENERAL CONTRACTOR. THIS
CONTRACTOR SHALL FURNISH ADEQUATE FORCES, CONSTRUCTION PLANT AND EQUIPMENT, AND
SHALL WORK SUCH HOURS, INCLUDING NIGHT SHIFTS, OVERTIME OPERATIONS, SUNDAYS AND
HOLIDAYS IN ACCORDANCE WITH THE OWNER'S OPERATIONAL SCHEDULE AS LISTED IN DIVISION 1 OF THE SPECIFICATIONS. IF THE CONTRACTOR DOES NOT MAINTAIN THE CONSTRUCTION SCHEDULE
BECAUSE OF INADEQUATE FORCES, SUPERVISION OR ANY OTHER REASON UNDER THE
CONTRACTOR'S CONTROL, THE OWNER MAY REQUIRE THE CONTRACTOR TO INCREASE THE NUMBER OF SHIFTS AND/OR OVERTIME OPERATIONS, DAY OF WORK AND/OR THE AMOUNT OF CONSTRUCTION PLANT, AT NO ADDITIONAL COST TO THE OWNER UNDER THIS CONTRACT. FAILURE TO MAINTAIN THE
CONSTRUCTION SCHEDULE DUE TO OWNER'S OPERATIONAL INTERFERENCES, WHICH WERE NOT
IDENTIFIED IN OR PRIOR TO THE PRE-BID CONFERENCE, SHALL NOT BE THE CONTRACTOR'S LIABILITY.
12. ALL CONCRETE, WALL PATCHING, CEILING REPAIR, FENCE WORK AND OTHER GENERAL
CONSTRUCTION WORK REQUIRED FOR INSTALLING MECHANICAL/PLUMBING OR FIRE PROTECTION
SYSTEMS SHALL BE PROVIDED BY MECHANICAL CONTRACTOR AND FULLY COORDINATED WITH
GENERAL CONTRACTOR USING THE APPROPRIATE CONSTRUCTION TRADES.
13. ALL MATERIALS AND EQUIPMENT SHALL BE NEW AND SHALL BE UL LISTED WHERE APPLICABLE.
14. DUCTWORK SHALL NOT BE SUPPORTED BY THE CEILING SUSPENSION SYSTEM. COORDINATE
LOCATIONS OF GRILLES, DIFFUSERS AND LOUVERS WITH ELECTRICAL, ARCHITECTURAL AND
PLUMBING WORK.
15. IN GENERAL, PLANS AND DIAGRAMS ARE SCHEMATIC ONLY AND SHOULD NOT BE SCALED.
CONTRACTOR SHALL COORDINATE ALL PLUMBING, HEATING AND ELECTRICAL WORK AT THE SITE, SO
AS NOT TO CONFLICT IN LOCATION WITH OTHER WORK UNDER THE CONTRACT.
16. ANY CONFLICT WITH DOORS, WINDOWS, CABINETS OR ANY OTHER EQUIPMENT SHALL BE BROUGHT TO
THE ATTENTION OF THE ARCHITECT/ENGINEER.
17. THE MECHANICAL CONTRACTOR IS DIRECTED TO COMPLY WITH DIVISION 26 OF THE CONTRACT
SPECIFICATIONS REFERRING TO MOTORS, STARTERS, ETC.
18. WHENEVER A REFERENCE IS MADE TO A STANDARD, INSTALLATION AND MATERIALS SHALL COMPLY WITH THE LATEST PUBLISHED EDITION AT THE TIME THE PROJECT IS BID UNLESS OTHERWISE
SPECIFIED.
19. ALL MATERIAL STORED ON SITE SHALL BE PROPERLY PROTECTED FROM INJURY OR DETERIORATION.
MATERIAL SHALL NOT BE STORED IN CONTACT WITH THE GROUND OR FLOOR. ALL DUCTWORK AND EQUIPMENT STORED SHALL BE SEALED AT ANY OPENING TO PREVENT ANY DEBRIS OR DIRT ENTERING THE INSIDE OF THE DUCTWORK AND EQUIPMENT. IF DEBRIS OR DIRT IS FOUND INSIDE THE DUCTWORK DURING ANY INSPECTION, THE CONTRACTOR WILL BE RESPONSIBLE FOR ALL COSTS INCURRED TO
CLEAN THE DUCTWORK TO THE SATISFACTION OF THE OWNER AND ENGINEER.
20. ALL SUPPLY AIR DUCT BENDS FROM THE VERTICAL TO THE HORIZONTAL AND ANGLED TURNS OF DUCTWORK SHALL HAVE LONG RADIUS ELBOWS. TURNING VANES WILL ONLY BE ACCEPTED WHERE
SHOWN ON THE DOCUMENTS.
21. VOLUME DAMPERS SHALL BE INSTALLED IN ALL BRANCH DUCTS LEADING FROM MAIN TRUNK LINES.
22. ALL EXTERNAL FIBROUS GLASS WRAPPED INSULATION JOINTS, SEAMS AND CONNECTIONS SHALL BE
CONSTRUCTED WITH FAB AND STAPLES AND THEN SEALED WITH MASTIC. HEAT AND PRESSURE
SENSITIVE TAPE ARE NOT ACCEPTABLE AS A FINAL CLOSURE.
23. DUCTWORK SHALL BE SHEET METAL, EXTERNALLY WRAPPED UNLESS OTHERWISE NOTED, MIN. 26 GA.
AND CONSTRUCTED IN STRICT ACCORDANCE WITH SMACNA STANDARDS.
24. CONTRACTOR SHALL COORDINATE WORK WITH ALL OTHER TRADES.
25. MECHANICAL CONTRACTOR TO TEST AND BALANCE HVAC SYSTEMS TO PROVIDE MAXIMUM
PERFORMANCE WITH REGARDS TO CFM, TEMPERATURE AND STATIC PRESSURE. REFER TO
SPECIFICATIONS FOR TEST AND BALANCE REQUIREMENTS.
26. ALL INSULATION USED FOR DUCTWORK SHALL BE INSTALLED THICKNESS RECOMMENDED BY THE ASHRAE GUIDE AND DATA BOOKS. INSULATION MATERIAL SHALL MEET NFPA 90A REQUIREMENTS AND SHALL HAVE COMPOSITE FIRE AND SMOKE HAZARD RATING AS TESTED IN ACCORDANCE WITH NFPA 225 OR UL 723 NOT EXCEEDING FLAME SPREAD OF MORE THAN 25 AND SMOKE DEVELOPED 50. REFER
TO SPECIFICATIONS.
28. ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE 8th EDITION (2023), FLORIDA BUILDING CODE 8th EDITION (2023) PLUMBING, FLORIDA BUILDING CODE 8th EDITION (2023) MECHANICAL, FLORIDA FIRE PREVENTION CODE 8th EDITION (2023), FLORIDA BUILDING CODE 8th
EDITION (2023) ENERGY CONSERVATION & STANDARDS AS REFERENCED IN DIVISION 1 AND
THROUGHOUT THE SPECIFICATIONS.
29. NOT ALL ABBREVIATIONS, OR LEGEND ITEMS SHOWN ARE APPLICABLE TO THIS PROJECT.
30. ALL DRAWINGS ARE DIAGRAMMATIC IN NATURE.
31. REFER TO CONTROLS GENERAL NOTES.
32. SEE SPECIFICATION SECTION 01 91 13 FOR COMISSIONING REQUIREMENTS.
33. PROVIDE ALUMINUM JACKET ON ALL EXPOSED AND OR VISIBLE PIPING.
34. ENERGY CODE COMPLIANCE EXEMPTION
THE AIR CONDITIONG SYSTEM FOR THE NORTH BUILDING ON THIS PROJECT IS BEING DESIGNED FOR STORAGE AND NOT FOR THERMAL COMFORT. THIS REQUIRES THE PROJECT TO CLAIM EXEMPTION
FROM THE FLORIDA BUILDING CODE 8TH EDITION (2023) - ENERGY CONSERVATION.
MECHANICAL GENERAL NOTES
MPE JOB #:
ENG. BUS. No. EB-0005096
CERT. OF AUTH. No. 5096
PHONE (239) 332-1187
12437 Brantley Commons Fort Myers, FL 33907
TO
D GRIFF
No 67083P R
STATE OF
E
O F
E S
S
ION A L E N
G
IN
E E
R
NSECIL
F L O R I DA
THK
D I
K. Todd Griffith No.67083
PROJECT NO:
DATE:
PHASE:
ISSUED FOR
SEAL:
GRACE HEBERT CURTIS ARCHITECTS, LLC
SHEET NUMBER
© THIS SET OF DOCUMENTS INCLUSIVE OF
DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT
BE COPIED, SCANNED, NOR ELECTRONICALLY
DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT
THE EXPRESSED WRITTEN CONSENT OF GRACE
HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,
ELECTRONIC PLAN SERVICE (INTERNET PLAN
SERVICE), NOR REPRODUCTION COMPANY SHALL BE
PERMITTED TO POST THESE DOCUMENTS WITHOUT
THE EXPRESSED WRITTEN CONSENT OF THE
ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.
2024-118
/1
/2
:4
:4
P
M
A u to d e s k D o c s /W a re h o u s e
C o n v e rt t o P a rk s
R e c D e p a rt m e n t/
-1
M e c h a n ic a l M o d e l_
O p ti o n O n e
R e v it
B
IM
.r v t
M001
GENERAL NOTES, LEGEND,
ABBREVIATIONS & SHEET
INDEX
40-24105
W A
R E
H O
U S
E C
O N
V E
R T
T O
P A
R K
S
R E
C D
E P
T
C
IT
Y O
F F
O R
T M
Y E
R S
06/19/2025
PERMIT DOCUMENTS
M
IC
H
IH
A
N A
V E
N U
E F
O R
T M
Y E
R S
F
L O
R
ID
A
DEMOLITION GENERAL NOTES
1. REFER TO “MECHANICAL GENERAL NOTES” ON DRAWING. THEY ARE APPLICABLE TO ALL WORK DESCRIBED ON EVERY MECHANICAL DRAWING.
2. ALL HEX NOTES NOT NECESSARILY USED ON ALL SHEETS.
3. ALL UNUSED SLAB PENETRATIONS SHALL BE PROPERLY SEALED TO MATCH EXISTING.
4. ALL UNUSED ROOF AND EXTERIOR PENETRATIONS SHALL BE PROPERLY CAPPED AND SEALED WATER TIGHT.
5. ALL EXISTING MECHANICAL EQUIPMENT, DUCTWORK, PIPING AND ACCESSORIES ARE SCHEDULED TO REMAIN UNLESS NOTED OTHERWISE. NOT ALL EXISTING
WORK MAY BE SHOWN FOR DRAWING CLARITY.
6. MAINTAIN CONTINUITY OF ALL SYSTEMS FOR BUILDING OPERATIONAL HOURS DURING CONSTRUCTION. COORDINATE WITH GC AND OWNERS SCHEDULE.
7. PRIOR TO COMMENCEMENT OF WORK, CONTRACTOR SHALL PRE-TEST ALL AIR FLOW DEVICES ON THIS FLOOR, INCLUDING DIFFUSERS/GRILLES.TEST RESULTS SHALL BE PRESENTED TO ENGINEER FOR REVIEW PRIOR TO ANY MODIFICATIONS BEING MADE TO THE SYSTEMS.
8. IT IS A REQUIREMENT THAT EACH SPACE IN THIS FACILITY, DURING OCCUPIED HOURS, SHALL HAVE CONTINUOUS HEATING AND/OR COOLING THROUGHOUT THE DURATION OF CONSTRUCTION AND THAT TEMPERATURES SHALL BE MAINTAINED FOR EACH SPACE PER OWNER'S REQUIREMENTS. IF THE CONTRACTOR BELIEVES THAT TEMPORARY HEATING AND/OR COOLING METHODS WILL BE NECESSARY TO MEET THIS REQUIREMENT, THEN CONTRACTOR SHALL INCLUDE THIS AS A SEPARATE COST LINE ITEM WITH THEIR BID, INCLUDING THE DURATION REQUIRED FOR TEMPORARY EQUIPMENT. OMISSION OF THIS LINE ITEM CONSTITUTES CONTRACTOR'S ABILITY TO COMPLY WITH PROJECT REQUIREMENTS WITHOUT THE NEED FOR TEMPORARY HEATING AND/OR COOLING.
9. ALL EQUIPMENT SHALL BE REMOVED IN A CAREFULLY PLANNED MANNER. ALL CEILING-HUNG EQUIPMENT SHALL BE REMOVED BY PROVIDING SUPPORT FROM
BELOW. NO DROPPING OF EXISTING EQUIPMENT ONTO THE FLOOR SLAB WILL BE ALLOWED.
10. REMOVE CONTROL WIRING ASSOCIATED WITH EQUIPMENT BEING REMOVED; COORDINATE WITH ELECTRICAL CONTRACTOR AS REQUIRED. THE REMOVAL OF CONTROL APPARATUS SHALL NOT INTERFERE WITH NORMAL OPERATION OF REMAINING EQUIPMENT OR SYSTEMS.
11. NOT ALL HVAC EQUIPMENT, DUCTWORK, PIPING AND/OR OTHER PIPING SYSTEMS ARE SHOWN ON THESE DEMOLITION DRAWINGS. CONTRACTOR SHALL IDENTIFY
ALL AFFECTED DUCTS AND PIPES PRIOR TO DEMOLITION.
12. SIZES OF PIPING AND DUCTWORK TO BE REMOVED AND/OR REMAIN MAY NOT HAVE BEEN INDICATED. CONTRACTOR SHALL SURVEY EXISTING SPACE, VERIFY SIZES AND INCLUDE IN SCOPE OF WORK. DISCREPANCIES DISCOVERED BETWEEN FIELD CONDITIONS AND CONSTRUCTION DOCUMENTS SHALL BE REPORTED TO
ENGINEER PROMPTLY.
13. PROVIDE TEMPORARY SHEETMETAL CAP ON ALL OPEN END DUCTWORK THAT IS TO REMAIN FUNCTIONAL DURING THE PROJECT.
14. ALL SERVICES PASSING THROUGH DEMOLITION CONTRACT AREA SERVING OTHER AREAS SHALL REMAIN AND SHALL BE PROTECTED UNLESS OTHERWISE NOTED.
15. THE CONTRACTOR SHALL OBTAIN THE PERMISSION OF THE OWNER'S REPRESENTATIVE AND COORDINATE WITH OTHER TRADES PRIOR TO COMMENCEMENT OF
DEMOLITION OF THE EXISTING INSTALLATIONS.
16. THE CONTRACTOR SHALL PROVIDE FOR SAFE CONDUCT OF THE WORK, PROTECTION OF PROPERTY, AND COORDINATION WITH OTHER WORK IN PROGRESS. THE
SPREAD OF DUST AND FLYING PARTICLES SHALL BE MINIMIZED.
17. EXISTING CONSTRUCTION TO REMAIN SHALL BE PROTECTED FROM DAMAGE. WORK DAMAGED BY THE CONTRACTOR SHALL BE REPAIRED TO MATCH EXISTING
WORK.
18. WHEN INDICATED, THE CONTRACTOR SHALL REMOVE SPECIFIC EQUIPMENT IN A CAREFUL MANNER SO AS TO MAINTAIN THE EQUIPMENT IN PROPER OPERATING ORDER. THIS EQUIPMENT WILL BE TURNED OVER TO THE OWNER AND TRANSPORTED TO A STORAGE AREA AS DIRECTED BY THE OWNER AND FURTHER
DESCRIBED HEREIN.
19. MATERIAL DEMOLISHED UNDER THIS SECTION AND NOT TO BE RETAINED BY THE OWNER SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE
PROMPTLY REMOVED AND DISPOSED OF OFF THE SITE.
20. DEBRIS AND RUBBISH SHALL NOT ACCUMULATE ON THE SITE, AND SHALL BE DISPOSED OF PERIODICALLY BY THE CONTRACTOR.
21. ALL NECESSARY PRECAUTIONS SHALL BE TAKEN BY THE CONTRACTOR TO PREVENT SPILLAGE DURING REMOVAL ACTIVITIES. PAVEMENT AND AREAS ADJACENT TO THE DEMOLITION AREAS SHALL BE KEPT CLEAN AND FREE FROM MUD, DIRT AND DEBRIS AT ALL TIMES.
22. EXISTING UTILITIES AND MECHANICAL SYSTEMS INCLUDING RELATED EQUIPMENT SHALL BE DISCONNECTED BY THE CONTRACTOR TO THE EXTENT SHOWN ON THE CONTRACT DRAWINGS OR SPECIFIED AND AS REQUIRED TO PERFORM THE WORK IN ACCORDANCE WITH DIVISION 23 OF THE SPECIFICATIONS.
23. THE CONTRACTOR SHALL EXERCISE CARE DURING THE PROGRESS OF THE WORK UNDER THIS SECTION SO AS NOT TO DAMAGE OR DISPLACE THE WORK OF THE OTHER TRADES PERFORMED UNDER OTHER SECTIONS. HE SHALL COORDINATE WORK UNDER THIS SECTION WITH WORK UNDER OTHER SECTIONS, AS NECESSARY
FOR THE PROPER EXECUTION OF THE ENTIRE WORK.
24. WHEN THE CONTRACT DOCUMENTS INDICATE THE REMOVAL OF EXISTING EQUIPMENT TO BE TEMPORARILY STORED AND TO BE RE-USED, THE CONTRACTOR SHALL PROVIDE ADEQUATE PROTECTION FOR THE STORED EQUIPMENT INCLUDING THE PROPER CAPPING OF SEVERAL PIPE CONNECTIONS, PROTECTION OF POWER AND
CONTROL WIRING AND DEVICES, AND DRAINING OF COILS TO PREVENT FREEZING DAMAGE.
25. EQUIPMENT WHICH CONTAINS REFRIGERANTS SHALL BE PUMPED DOWN PRIOR TO DEMOLITION. THE REFRIGERANT SHALL BE PROPERLY CONTAINED AND
DISPOSED OF IN ACCORDANCE WITH THE ACCEPTED LOCAL PROCEDURES.
26. PRE-DEMOLITION PHOTOGRAPHS SHALL BE TAKEN SHOWING EXISTING CONDITIONS OF ADJOINING CONSTRUCTION AND SITE IMPROVEMENTS, INCLUDING FINISHED SURFACES THAT MIGHT BE MISCONSTRUED AS DAMAGE CAUSED BY SELECTIVE DEMOLITION OPERATIONS. PHOTOGRAPH ITEMS REQUESTED TO BE SALVAGE BY
THE OWNER. SUBMIT ALL PHOTOGRAPHIC DOCUMENTATION BEFORE THE START OF DEMOLITION.
27. PRE-DEMOLITION CONFERENCE: CONDUCT CONFERENCE AT PROJECT SITE WITH THE OWNER TO INSPECT AND DISCUSS CONDITION OF CONSTRUCTION TO BE SELECTIVELY DEMOLISHED, REVIEW AREAS WHERE EXISTING CONSTRUCTION IS TO REMAIN AND REQUIRES PROTECTION, REVIEW LIST OF ITEMS TO BE
SALVAGED AND DELIVERED TO THE OWNER.
28. REFER TO SPECIFICATIONS.
NO. DESCRIPTION DATE
MECHANICAL SHEET INDEX
SHEET NUMBER SHEET NAME
M001 GENERAL NOTES, LEGEND, ABBREVIATIONS & SHEET INDEX
MD101-N 1ST AND 2ND FLOOR DEMOLITION PLANS - NORTH BUILDING - MECHANICAL
MD101-S 1ST FLOOR DEMOLITION PLAN - SOUTH BUILDING - MECHANICAL
M101-N 1ST AND 2ND FLOOR PLANS - NORTH BUILDING - MECHANICAL
M101-S 1ST FLOOR PLAN - SOUTH BUILDING - MECHANICAL
M101-S-2 1ST FLOOR PLAN - SOUTH BUILDING - MECHANICAL - ALTERNATE
M201 SECTION VIEWS - MECHANICAL
M502 CONTROLS - MECHANICAL
M503 CONTROLS - MECHANICAL
M504 CONTROLS - MECHANICAL
M601 SCHEDULES - MECHANICAL
M601-2 SCHEDULES - MECHANICAL - ALTERNATE
M901 DETAILS - MECHANICAL
M902 DETAILS - MECHANICAL
M903 DETAILS - MECHANICAL
DN
DN
GENERAL/DEMOLITION GENERAL NOTES:
1. REFER TO GENERAL/DEMOLITION GENERAL NOTES
FOR THIS DISCIPLINE. SEE SHEET M001.
2. REFER TO SPECIFICATIONS.
3. ALL HEX NOTES NOT NECESSARILY USED ON ALL
SHEETS.
MPE JOB #:
ENG. BUS. No. EB-0005096
CERT. OF AUTH. No. 5096
PHONE (239) 332-1187
12437 Brantley Commons Fort Myers, FL 33907
TO
D GRIFF
No 67083P R
STATE OF
E
O F
E S
S
ION A L E N
G
IN
E E
R
NSECIL
F L O R I DA
THK
D I
K. Todd Griffith No.67083
HEX NOTES:
PROJECT NO:
DATE:
PHASE:
ISSUED FOR
SEAL:
GRACE HEBERT CURTIS ARCHITECTS, LLC
SHEET NUMBER
© THIS SET OF DOCUMENTS INCLUSIVE OF
DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT
BE COPIED, SCANNED, NOR ELECTRONICALLY
DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT
THE EXPRESSED WRITTEN CONSENT OF GRACE
HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,
ELECTRONIC PLAN SERVICE (INTERNET PLAN
SERVICE), NOR REPRODUCTION COMPANY SHALL BE
PERMITTED TO POST THESE DOCUMENTS WITHOUT
THE EXPRESSED WRITTEN CONSENT OF THE
ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.
2024-118
/1
/2
:3
:1
P
M
A u to d e s k D o c s /W a re h o u s e
C o n v e rt t o P a rk s
R e c D e p a rt m e n t/
-1
M e c h a n ic a l M o d e l_
O p ti o n O n e
R e v it
B
IM
.r v t
MD101-N
1ST AND 2ND FLOOR
DEMOLITION PLANS -
NORTH BUILDING -
MECHANICAL
40-24105
W A
R E
H O
U S
E C
O N
V E
R T
T O
P A
R K
S
R E
C D
E P
T
C
IT
Y O
F F
O R
T M
Y E
R S
06/19/2025
PERMIT DOCUMENTS
M
IC
H
IH
A
N A
V E
N U
E F
O R
T M
Y E
R S
F
L O
R
ID
A
1/4" = 1'-0"1 FIRST FLOOR DEMOLITION PLAN - NORTH BUILDING
1/4" = 1'-0"2 SECOND FLOOR DEMOLITION PLAN - NORTH BUILDING
1 CONTRACTOR SHALL REMOVE ALL EXISTING HVAC
EQUIPMENT AND ALL ASSOCIATED PIPING,
CONTROLS AND DUCTWORK WITHIN DEMOLITION
REGION.
NO. DESCRIPTION DATE
GENERAL/DEMOLITION GENERAL NOTES:
1. REFER TO GENERAL/DEMOLITION GENERAL NOTES
FOR THIS DISCIPLINE. SEE SHEET M001.
2. REFER TO SPECIFICATIONS.
3. ALL HEX NOTES NOT NECESSARILY USED ON ALL
SHEETS.
MPE JOB #:
ENG. BUS. No. EB-0005096
CERT. OF AUTH. No. 5096
PHONE (239) 332-1187
12437 Brantley Commons Fort Myers, FL 33907
TO
D GRIFF
No 67083P R
STATE OF
E
O F
E S
S
ION A L E N
G
IN
E E
R
NSECIL
F L O R I DA
THK
D I
K. Todd Griffith No.67083
HEX NOTES:
PROJECT NO:
DATE:
PHASE:
ISSUED FOR
SEAL:
GRACE HEBERT CURTIS ARCHITECTS, LLC
SHEET NUMBER
© THIS SET OF DOCUMENTS INCLUSIVE OF
DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT
BE COPIED, SCANNED, NOR ELECTRONICALLY
DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT
THE EXPRESSED WRITTEN CONSENT OF GRACE
HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,
ELECTRONIC PLAN SERVICE (INTERNET PLAN
SERVICE), NOR REPRODUCTION COMPANY SHALL BE
PERMITTED TO POST THESE DOCUMENTS WITHOUT
THE EXPRESSED WRITTEN CONSENT OF THE
ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.
2024-118
/1
/2
:3
:1
P
M
A u to d e s k D o c s /W a re h o u s e
C o n v e rt t o P a rk s
R e c D e p a rt m e n t/
-1
M e c h a n ic a l M o d e l_
O p ti o n O n e
R e v it
B
IM
.r v t
MD101-S
1ST FLOOR DEMOLITION
PLAN - SOUTH BUILDING -
MECHANICAL
40-24105
W A
R E
H O
U S
E C
O N
V E
R T
T O
P A
R K
S
R E
C D
E P
T
C
IT
Y O
F F
O R
T M
Y E
R S
06/19/2025
PERMIT DOCUMENTS
M
IC
H
IH
A
N A
V E
N U
E F
O R
T M
Y E
R S
F
L O
R
ID
A
1/4" = 1'-0"1 FIRST FLOOR DEMOLITION PLAN - SOUTH BUILDING
1 CONTRACTOR SHALL REMOVE ALL EXISTING HVAC
EQUIPMENT AND ALL ASSOCIATED PIPING,
CONTROLS AND DUCTWORK. WITHIN DEMOLITION
REGION
DN
M SD
MM C
F
M
SD
M
C
(TYP.16)
A
TH
HT
"x
S A
"x
S A
"x
S A
"x
S A
24"x20" SA 26"x20" SA
"x
S A
"x
S A
"x
S A
"x
S A
20"x20" SA20"x16" SA18"x14" SA14"x14" SA
B
A
(TYP.2)
EF-N-1
6"ø EALV-N-2
CU-N-2CU-N-3
4 5
CU-N-1
DISC.
FOR CU-N-1
DISC.
FOR CU-N-3
DISC.
FOR CU-N-2
D
EF-N-2
8"ø EA
"ø
E A
FORKLIFT CHARGING
STATION
OFFICES/ MULTI-USE
PRINT ROOM
STAGING AREA
RECORDS STORAGE
CUSTODIAL
UNISEX R.R.
T H
14"x10" OA
"x
O A
12"x10" OA
40"x24" RA
"x
S A
BCU-N-2
"x
S A
BCU-N-3
D
C
4" CONCRETE PAD
4" CONCRETE PAD
4" CONCRETE PAD
DISC.
FOR AHU-N-1
DISC.
FOR BCU-N-2
M201
LV-N-1
DISC.
FOR BCU-N-3
EDH-N-2
10"x10" SA
"x
R A
"x
S A
M201
M201
AHU-N-1
"x
O A
SD
MPE JOB #:
ENG. BUS. No. EB-0005096
CERT. OF AUTH. No. 5096
PHONE (239) 332-1187
12437 Brantley Commons Fort Myers, FL 33907
TO
D GRIFF
No 67083P R
STATE OF
E
O F
E S
S
ION A L E N
G
IN
E E
R
NSECIL
F L O R I DA
THK
D I
K. Todd Griffith No.67083
HEX NOTES:
PROJECT NO:
DATE:
PHASE:
ISSUED FOR
SEAL:
GRACE HEBERT CURTIS ARCHITECTS, LLC
SHEET NUMBER
© THIS SET OF DOCUMENTS INCLUSIVE OF
DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT
BE COPIED, SCANNED, NOR ELECTRONICALLY
DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT
THE EXPRESSED WRITTEN CONSENT OF GRACE
HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,
ELECTRONIC PLAN SERVICE (INTERNET PLAN
SERVICE), NOR REPRODUCTION COMPANY SHALL BE
PERMITTED TO POST THESE DOCUMENTS WITHOUT
THE EXPRESSED WRITTEN CONSENT OF THE
ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.
2024-118
/1
/2
:4
:5
P
M
A u to d e s k D o c s /W a re h o u s e
C o n v e rt t o P a rk s
R e c D e p a rt m e n t/
-1
M e c h a n ic a l M o d e l_
O p ti o n O n e
R e v it
B
IM
.r v t
M101-N
1ST AND 2ND FLOOR
PLANS - NORTH BUILDING -
MECHANICAL
40-24105
W A
R E
H O
U S
E C
O N
V E
R T
T O
P A
R K
S
R E
C D
E P
T
C
IT
Y O
F F
O R
T M
Y E
R S
06/19/2025
PERMIT DOCUMENTS
M
IC
H
IH
A
N A
V E
N U
E F
O R
T M
Y E
R S
F
L O
R
ID
A
1/4" = 1'-0"1 FIRST FLOOR NORTH BUILDING
1/4" = 1'-0"2 SECOND FLOOR NORTH BUILDING
1 CONTRACTOR TO ROUTE 1" INSULATED
CONDENSATE PIPING TO NEAREST HUB DRAIN.
2 CONTRACTOR TO COORDINATE EXISTING
PENETRATION IN EXTERIOR WALL WITH NEW
LOUVER (LV-N-1) PRIOR TO PURCAHSE.
3 PROVIDE MAGNETIC CONTACT SWITCH. INTERLOCK
MAGNETIC CONTACT SWITCH WITH AHU-N-1.
MAGNETIC CONTACT SWITCH WILL SHUT AHU-N-1
OFF AFTER 5 MINUTES OF THE ROLL UP DOOR
BEING OPENED.
4 SPACE HUMIDITY SENSOR ASSOCIATED WITH
AHU-N-1. TERMINATE SENSOR AT AHU-N-1
CONTROLLER.
5 SPACE TEMPERATURE SENSOR ASSOCIATED WITH
AHU-N-1. TERMINATE SENSOR AT AHU-N-1
CONTROLLER.
6 SPACE HUMIDITY SENSOR ASSOCIATED WITH
BCU-N-2. TERMINATE SENSOR AT BCU-N-2
CONTROLLER.
7 SPACE TEMPERATURE SENSOR ASSOCIATED WITH
BCU-N-2. TERMINATE SENSOR AT BCU-N-2
CONTROLLER.
8 SPACE TEMPERATURE SENSOR ASSOCIATED WITH
BCU-N-3. TERMINATE SENSOR AT BCU-N-3
CONTROLLER.
9 SPACE HUMIDITY SENSOR ASSOCIATED WITH
BCU-N-3. TERMINATE SENSOR AT BCU-N-3
CONTROLLER.
10 CONTRACTOR TO PROVIDE PRICE 30" X 30" HEAVY
DUTY GYM GRILLE (3285 CFM) (MODEL #: 95FH).
11 CONTRACTOR TO INSTALL CONDENSING UNIT 1'
ABOVE FLOOD ELEVATION.
12 SEE CONTINUATION ON SECOND FLOOR
MECHANICAL PLAN
13 SEE CONTINUATION ON FIRST FLOOR MECHANICAL
PLAN.
GENERAL NOTES:
1. REFER TO GENERAL NOTES FOR THIS DISCIPLINE.
2. REFER TO SPECIFICATIONS.
3. ALL HEX NOTES NOT NECESSARILY USED ON ALL
SHEETS.
4. SEE SECTION VIEW MECHANICAL ROOM PLANS FOR
MORE DETAIL.
5. ALL AIR HANDLING SYSTEMS WILL UTILIZE A FULLY
DUCTED RETURN AIR SYSTEM.
6. PROVIDE A VOLUME DAMPER ON ALL BRANCH
DUCTWORK AND ANY RUNOUT TO A DIFFUSER,
WHETHER SHOWN ON DRAWINGS OR NOT.
7. ALL VOLUME DAMPERS INSTALLED ABOVE GYPSUM
BOARD CEILING SHALL HAVE REMOTELY OPERATED
DAMPER.ALL OUTSIDE AIR LOUVERS SHALL BE
PROVIDED WITH 1/4" X 1/4" REMOVABLE BIRD SCREEN
AND REMOVABLE FILTERS IN A FILTER RACK. THIS
SHALL BE INSTALLED IN A CHANNEL AND SHALL BE
EASILY REMOVED. SCREWED BIRD SCREEN TO THE
LOUVER IS NOT ACCEPTABLE.
8. PROVIDE VOLUME DAMPERS ON EACH BATHROOM
EXHAUST GRILLE.
9. REFER TO MANUFACTURER'S RECOMMENDATIONS
FOR ALL REFRIGERANT PIPE SIZES ACCORDING TO
FINAL LENGTH OF RUN.
10. ALL RETURN GRILLES LOCATIONS MUST BE
INSTALLED AT OR FARTHER THAN LOCATIONS
SHOWN, OR FARTHER THAN BRANCH RUNOUT TO
ELIMINATE NOISE TRANSMISSION.
11. ALL LOUVER PLENUMS SHALL SLOPE BACK TOWARDS
THE LOUVER ON THE EXTERIOR WALL. FINAL SIZE,
HEIGHT, COLOR AND LOCATION OF THE LOUVERS
SHOULD BE COORDINATED WITH THE
ARCHITECTURAL ELEVATIONS AND GENERAL
CONTRACTOR, PRIOR TO ORDERING LOUVERS.
12. FULLY COORDINATE WITH THE ARCHITECTURAL
REFLECTED CEILING PLANS FOR DIFFUSER
LOCATIONS PRIOR TO INSTALLATION.
13. CONTRACTOR SHALL COORDINATE VAV ELECTRICAL
CLEARANCES. INCLUDING LOW VOLTAGE, WITH ALL
CEILING MOUNTED EQUIPMENT IN SHOP DRAWINGS,
WHICH INCLUDES BUT IS NOT LIMITED TO LIGHTING,
PROJECTORS, SYSTEMS DEVICES, AND FIRE
SPRINKLERS. CLEARANCES SHALL BE SIZED AND
COORDINATED AS REQUIRED BASED ON THE
AWARDED MANUFACTURER VAV BOX
REQUIREMENTS. LIGHTS AND EQUIPMENT BELOW THE
VAV CLEARANCE, IN THE CEILING ARE NOT
ACCEPTABLE.
14. REFER TO ARCHITECTURAL DRAWINGS FOR
MOUNTING HEIGHT AND COLOR OF ALL LINEAR
DIFFUSERS.
DN
C F
M
M
A
(TYP.2)
A
(TYP.2)
T
T
T T H
T
T
T
T
T
B
B
B
B
B
"x
E A
6"x6" EA
A
A
A
A
A
A
"x
S A
12"x10" SA
"x
S A
8"ø SA
"x
S A
8"ø SA
"x
S A
"x
S A
8"x8" SA
8"x8" SA
"x
S A
"x
S A
8"x6" SA
8"x8" SA 10"x8" SA 1 "x
"x
S A
8"x8" SA
"ø
S A
10"ø SA
10"x10" SA14"x14" SA
"x
S A
"x
S A
"x
S A
8"ø SA
12"x10" 8"ø SA
4" CONCRETE PAD
BAS
DISC.
FOR AHU-S-1
LV-S-4
LV-S-1
VAV-S-1-6
VAV-S-1-7
VAV-S-1-3
VAV-S-1-5
VAV-S-1-8
VAV-S-1-1
VAV-S-1-2
VAV-S-1-4
A
A
A
A
CF-1
VAV-S-1-9
EF-S-1
32"x30" RA
"x
R A
14"x12" RA
"x
R A
"x
R A
"x
R A
"x
R A
"x
R A
12"x12" RA "x
R A
M201
T
T
MSCU-S-1
4" CONCRETE PAD
EF-S-2 LV-S-2
44"x44" EA
LV-S-3
T
12"x12" SA10"x10" SA
26"x20" SA
/4
"ø C
D
MSAC-S-1
VAV-S-10
D
D 270C
B
B
B
B
B
B
A
C
B
"ø
S A
14"x12" EA
"x
S A
10"x10" SA
"x
" R
A
"ø
S A
CU-S-1
14"x12" OA
AHU-S-1
4" CONCRETE PAD
"x
S A
10"ø SA
8"ø SA
5"ø SA
"ø
S A
"ø
S A
8"ø SA
"x
S A
"ø
S A
10"ø SA
"ø
S A
H/O/A
DISC.
FOR CU-S-1
DISC.
FOR MSCU-S-1
A
CUSTODIAL
SMALL CONFERENCE
ROOM
CUBICLE 1
CUBICLE 2
471 SF
MAINTENANCE &
REPAIRS AREA
948 SF
EQUIPMENT TOOL'S
CAGES
MECH. ROOM
ELECTRICAL ROOM
126 MDF ROOM
CLOSET
LARGE CONFERENCE
ROOM
EXECUTIVE OFFICE
CUBICLE 5
CUBICLE 4
SENIOR ASSIST.
PUBLIC
MEN'S RESTROOM
WOMEN'S RESTROOM
LOUNGE ROOM
OFF. SUPPLIES
SPECIAL EVENTS
STORAGE/ MULTI-USE
WORK ROOM
CUBICLE 3
CUBICLE 8
CUBICLE 9
CUBICLE 7
CUBICLE 12
CUBICLE 11
CUBICLE 10
CUBICLE 13
CUBICLE 6
OPEN SPACE
2016 SF
PARKS & REC
WAREHOUSE
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
"x
S A
"x
S A
"x
S A
6"ø SA
"x
S A
"x
E A
C
C
6"x6" SA
C
C
C
C
C
C
C
C
C
16"x14" RA
D
GENERAL NOTES:
1. REFER TO GENERAL NOTES FOR THIS DISCIPLINE.
2. REFER TO SPECIFICATIONS.
3. ALL HEX NOTES NOT NECESSARILY USED ON ALL
SHEETS.
4. SEE SECTION VIEW MECHANICAL ROOM PLANS FOR
MORE DETAIL.
5. ALL AIR HANDLING SYSTEMS WILL UTILIZE A FULLY
DUCTED RETURN AIR SYSTEM.
6. PROVIDE A VOLUME DAMPER ON ALL BRANCH
DUCTWORK AND ANY RUNOUT TO A DIFFUSER,
WHETHER SHOWN ON DRAWINGS OR NOT.
7. ALL VOLUME DAMPERS INSTALLED ABOVE GYPSUM
BOARD CEILING SHALL HAVE REMOTELY OPERATED
DAMPER.ALL OUTSIDE AIR LOUVERS SHALL BE
PROVIDED WITH 1/4" X 1/4" REMOVABLE BIRD SCREEN
AND REMOVABLE FILTERS IN A FILTER RACK. THIS
SHALL BE INSTALLED IN A CHANNEL AND SHALL BE
EASILY REMOVED. SCREWED BIRD SCREEN TO THE
LOUVER IS NOT ACCEPTABLE.
8. PROVIDE VOLUME DAMPERS ON EACH BATHROOM
EXHAUST GRILLE.
9. REFER TO MANUFACTURER'S RECOMMENDATIONS
FOR ALL REFRIGERANT PIPE SIZES ACCORDING TO
FINAL LENGTH OF RUN.
10. ALL RETURN GRILLES LOCATIONS MUST BE
INSTALLED AT OR FARTHER THAN LOCATIONS
SHOWN, OR FARTHER THAN BRANCH RUNOUT TO
ELIMINATE NOISE TRANSMISSION.
11. ALL LOUVER PLENUMS SHALL SLOPE BACK TOWARDS
THE LOUVER ON THE EXTERIOR WALL. FINAL SIZE,
HEIGHT, COLOR AND LOCATION OF THE LOUVERS
SHOULD BE COORDINATED WITH THE
ARCHITECTURAL ELEVATIONS AND GENERAL
CONTRACTOR, PRIOR TO ORDERING LOUVERS.
12. FULLY COORDINATE WITH THE ARCHITECTURAL
REFLECTED CEILING PLANS FOR DIFFUSER
LOCATIONS PRIOR TO INSTALLATION.
13. CONTRACTOR SHALL COORDINATE VAV ELECTRICAL
CLEARANCES. INCLUDING LOW VOLTAGE, WITH ALL
CEILING MOUNTED EQUIPMENT IN SHOP DRAWINGS,
WHICH INCLUDES BUT IS NOT LIMITED TO LIGHTING,
PROJECTORS, SYSTEMS DEVICES, AND FIRE
SPRINKLERS. CLEARANCES SHALL BE SIZED AND
COORDINATED AS REQUIRED BASED ON THE
AWARDED MANUFACTURER VAV BOX
REQUIREMENTS. LIGHTS AND EQUIPMENT BELOW THE
VAV CLEARANCE, IN THE CEILING ARE NOT
ACCEPTABLE.
14. REFER TO ARCHITECTURAL DRAWINGS FOR
MOUNTING HEIGHT AND COLOR OF ALL LINEAR
DIFFUSERS.
MPE JOB #:
ENG. BUS. No. EB-0005096
CERT. OF AUTH. No. 5096
PHONE (239) 332-1187
12437 Brantley Commons Fort Myers, FL 33907
TO
D GRIFF
No 67083P R
STATE OF
E
O F
E S
S
ION A L E N
G
IN
E E
R
NSECIL
F L O R I DA
THK
D I
K. Todd Griffith No.67083
HEX NOTES:
PROJECT NO:
DATE:
PHASE:
ISSUED FOR
SEAL:
GRACE HEBERT CURTIS ARCHITECTS, LLC
SHEET NUMBER
© THIS SET OF DOCUMENTS INCLUSIVE OF
DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT
BE COPIED, SCANNED, NOR ELECTRONICALLY
DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT
THE EXPRESSED WRITTEN CONSENT OF GRACE
HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,
ELECTRONIC PLAN SERVICE (INTERNET PLAN
SERVICE), NOR REPRODUCTION COMPANY SHALL BE
PERMITTED TO POST THESE DOCUMENTS WITHOUT
THE EXPRESSED WRITTEN CONSENT OF THE
ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.
2024-118
/1
/2
:3
:0
P
M
A u to d e s k D o c s /W a re h o u s e
C o n v e rt t o P a rk s
R e c D e p a rt m e n t/
-1
M e c h a n ic a l M o d e l_
O p ti o n O n e
R e v it
B
IM
.r v t
M101-S
1ST FLOOR PLAN - SOUTH
BUILDING - MECHANICAL
40-24105
W A
R E
H O
U S
E C
O N
V E
R T
T O
P A
R K
S
R E
C D
E P
T
C
IT
Y O
F F
O R
T M
Y E
R S
06/19/2025
PERMIT DOCUMENTS
M
IC
H
IH
A
N A
V E
N U
E F
O R
T M
Y E
R S
F
L O
R
ID
A
1/4" = 1'-0"1 FIRST FLOOR SOUTH BUILDING
1 CONTRACTOR TO ROUTE 1" INSULATED
CONDENSATE PIPING TO NEAREST HUB DRAIN.
2 CONTRACTOR TO COORDINATE EXISTING
PENETRATION IN EXTERIOR WALL WITH NEW
LOUVER (LV-S-4) PRIOR TO PURCAHSE.
3 CONTRACTOR TO PROVIDE FACTORY CONTROLLER
FOR CF-1.
4 SPACE HUMIDITY SENSOR ASSOCIATED WITH
AHU-S-1. TERMINATE SENSOR AT AHU-S-1
CONTROLLER.
5 CONTRACTOR TO INSTALL CONDENSING UNIT 1'
ABOVE FLOOD ELEVATION
6 CONTRACTOR TO COORDINATE EXISTING
PENETRATION IN EXTERIOR WALL WITH NEW
LOUVER (LV-S-1) PRIOR TO PURCAHSE.
7 CONTRACTOR TO PROVIDE ACCESS DOOR FOR
FANS ON RIGHT SIDE OF AIR HANDLER
8 PROVIDE STANDALONE TEMPERATURE SENSOR
FOR MONITORING PURPOSES.
9 CONTRACTOR TO ROUTE INSULATED 1"
CONDENSATE LINE TO NEAREST HUB DRAIN.
DN
C F
M
M
A
A
(TYP.2)
A
(TYP.2)
T
T
T T H
T
T
T
T
T
B
B
B
B
B
B
B
"x
E A
"x
E A
"x
E A
6"x6" EA
8"x8" EA
8"x8" EA
A
A
A
A
A
A
"x
S A
12"x10" SA
"x
S A
8"ø SA
"x
S A
8"ø SA
"x
S A
"x
S A
8"ø SA
6"ø SA
8"x8" SA
"ø
S A
"ø
S A
6"ø SA
8"ø SA 10"x8" SA 1 "x
"x
S A
6"ø SA
6"ø SA
"ø
S A
10"ø SA
10"x10" SA14"x14" SA
"ø
S A
"x
S A
"ø
S A
"x
S A
16"x16" S A
"x
S A 8"ø SA
8"ø SA
8"ø SA
"ø
S A
6"ø SA6"ø SA
"x
S A
8"ø SA
8"ø SA
8"ø SA
12"x10" 8"ø SA
4" CONCRETE PAD
BAS
DISC.
FOR AHU-S-1
LV-S-4
LV-S-1
VAV-S-1-6
VAV-S-1-7
VAV-S-1-3
VAV-S-1-5
VAV-S-1-8
VAV-S-1-1
VAV-S-1-2
VAV-S-1-4
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
CF-1
VAV-S-1-9
EF-S-1
32"x30" RA
"x
R A
34"x20" RA20"x16" RA14"x12" RA
"x
R A
"x
R A
"x
R A
"x
R A
"x
R A
"x
R A
"x
R A
"x
R A
16"x14" RA "x
R A
10"x10" RA
M201
EQUIPMENT TOOLS
CAGES
OFFICE 3
OFFICE 4
1123 OFFICE 5
OFFICE 6
OFFICE 7
229 SF
SMALL CONFERENCE
ROOM
LOUNGE ROOM
357 SF
LARGE CONFERENCE
ROOM
950 SF
SPECIAL EVENT
STORAGE/ MULTI-USE
WORK ROOM
MEN'S RESTROOM
CUSTODIAL
411 SF
PUBLIC
WOMEN'S RESTROOM
CUBICLE 6
238 SF
WOMEN'S BATHROOM
MEN'S BATHROOM
OFFICE 6
MDF ROOM
OPEN SPACE
OFF. SUPPLIES
CUBICLE 4
CUBICLE 5
MAINTENANCE &
REPAIRS AREA
CUSTODIAL
156 SF
MECH. ROOM
84 SF
ELECTRIAL ROOM
PARKS & REC
WAREHOUSE
CLOSET
EXECUTIVE OFFICE
CUBICLE 3
CUBICLE 2
SENIOR ASSIST.
CUSTODIAL
OFFICE 1
OFFICE 2
T
T
MSCU-S-1
4" CONCRETE PAD
EF-S-2 LV-S-2
44"x44" EA
LV-S-3
TA
A
A
10"ø SA
12"x12" SA10"ø SA
26"x20" SA
/4
"ø C
D
MSAC-S-1
VAV-S-10
D
D 270C
B
B
B 725 B
B
B
B
B
B
B 100B
B
A
C
B
6"ø SA
6"ø SA
"ø
S A
20"x12" EA
"x
S A
10"x10" SA
"x
" R
A
"ø
S A
B
"ø
S A
CU-S-1
B
B
B
"x
R A
10"x8" RA 10"x8"
14"x12" OA
AHU-S-1
4" CONCRETE PAD
"x
S A
12"ø SA
8"ø SA
5"ø SA
"ø
S A
"ø
S A
8"ø SA
"x
S A
"ø
S A
10"ø SA
"ø
S A
H/O/A
DISC.
FOR CU-S-1
DISC.
FOR MSCU-S-1
A
GENERAL NOTES:
1. REFER TO GENERAL NOTES FOR THIS DISCIPLINE.
2. REFER TO SPECIFICATIONS.
3. ALL HEX NOTES NOT NECESSARILY USED ON ALL
SHEETS.
4. SEE SECTION VIEW MECHANICAL ROOM PLANS FOR
MORE DETAIL.
5. ALL AIR HANDLING SYSTEMS WILL UTILIZE A FULLY
DUCTED RETURN AIR SYSTEM.
6. PROVIDE A VOLUME DAMPER ON ALL BRANCH
DUCTWORK AND ANY RUNOUT TO A DIFFUSER,
WHETHER SHOWN ON DRAWINGS OR NOT.
7. ALL VOLUME DAMPERS INSTALLED ABOVE GYPSUM
BOARD CEILING SHALL HAVE REMOTELY OPERATED
DAMPER.ALL OUTSIDE AIR LOUVERS SHALL BE
PROVIDED WITH 1/4" X 1/4" REMOVABLE BIRD SCREEN
AND REMOVABLE FILTERS IN A FILTER RACK. THIS
SHALL BE INSTALLED IN A CHANNEL AND SHALL BE
EASILY REMOVED. SCREWED BIRD SCREEN TO THE
LOUVER IS NOT ACCEPTABLE.
8. PROVIDE VOLUME DAMPERS ON EACH BATHROOM
EXHAUST GRILLE.
9. REFER TO MANUFACTURER'S RECOMMENDATIONS
FOR ALL REFRIGERANT PIPE SIZES ACCORDING TO
FINAL LENGTH OF RUN.
10. ALL RETURN GRILLES LOCATIONS MUST BE
INSTALLED AT OR FARTHER THAN LOCATIONS
SHOWN, OR FARTHER THAN BRANCH RUNOUT TO
ELIMINATE NOISE TRANSMISSION.
11. ALL LOUVER PLENUMS SHALL SLOPE BACK TOWARDS
THE LOUVER ON THE EXTERIOR WALL. FINAL SIZE,
HEIGHT, COLOR AND LOCATION OF THE LOUVERS
SHOULD BE COORDINATED WITH THE
ARCHITECTURAL ELEVATIONS AND GENERAL
CONTRACTOR, PRIOR TO ORDERING LOUVERS.
12. FULLY COORDINATE WITH THE ARCHITECTURAL
REFLECTED CEILING PLANS FOR DIFFUSER
LOCATIONS PRIOR TO INSTALLATION.
13. CONTRACTOR SHALL COORDINATE VAV ELECTRICAL
CLEARANCES. INCLUDING LOW VOLTAGE, WITH ALL
CEILING MOUNTED EQUIPMENT IN SHOP DRAWINGS,
WHICH INCLUDES BUT IS NOT LIMITED TO LIGHTING,
PROJECTORS, SYSTEMS DEVICES, AND FIRE
SPRINKLERS. CLEARANCES SHALL BE SIZED AND
COORDINATED AS REQUIRED BASED ON THE
AWARDED MANUFACTURER VAV BOX
REQUIREMENTS. LIGHTS AND EQUIPMENT BELOW THE
VAV CLEARANCE, IN THE CEILING ARE NOT
ACCEPTABLE.
14. REFER TO ARCHITECTURAL DRAWINGS FOR
MOUNTING HEIGHT AND COLOR OF ALL LINEAR
DIFFUSERS.
MPE JOB #:
ENG. BUS. No. EB-0005096
CERT. OF AUTH. No. 5096
PHONE (239) 332-1187
12437 Brantley Commons Fort Myers, FL 33907
TO
D GRIFF
No 67083P R
STATE OF
E
O F
E S
S
ION A L E N
G
IN
E E
R
NSECIL
F L O R I DA
THK
D I
K. Todd Griffith No.67083
HEX NOTES:
PROJECT NO:
DATE:
PHASE:
ISSUED FOR
SEAL:
GRACE HEBERT CURTIS ARCHITECTS, LLC
SHEET NUMBER
© THIS SET OF DOCUMENTS INCLUSIVE OF
DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT
BE COPIED, SCANNED, NOR ELECTRONICALLY
DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT
THE EXPRESSED WRITTEN CONSENT OF GRACE
HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,
ELECTRONIC PLAN SERVICE (INTERNET PLAN
SERVICE), NOR REPRODUCTION COMPANY SHALL BE
PERMITTED TO POST THESE DOCUMENTS WITHOUT
THE EXPRESSED WRITTEN CONSENT OF THE
ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.
2024-118
/1
/2
:1
:4
P
M
A u to d e s k D o c s /W a re h o u s e C o n v e rt t o P a rk s
R e c D e p a rt m e n t/
-1
M e c h a n ic a l M o d e l_
O p ti o n T w o
R e v it
B
IM
.r v t
M101-S-2
1ST FLOOR PLAN - SOUTH
BUILDING - MECHANICAL -
ALTERNATE
40-24105
W A
R E
H O
U S
E C
O N
V E
R T
T O
P A
R K
S
R E
C D
E P
T
C
IT
Y O
F F
O R
T M
Y E
R S
06/19/2025
PERMIT DOCUMENTS
M
IC
H
IH
A
N A
V E
N U
E F
O R
T M
Y E
R S
F
L O
R
ID
A
1/4" = 1'-0"1 FIRST FLOOR SOUTH BUILDING
1 CONTRACTOR TO ROUTE 1" INSULATED
CONDENSATE PIPING TO NEAREST HUB DRAIN.
2 CONTRACTOR TO COORDINATE EXISTING
PENETRATION IN EXTERIOR WALL WITH NEW
LOUVER (LV-S-4) PRIOR TO PURCAHSE.
3 CONTRACTOR TO PROVIDE FACTORY CONTROLLER
FOR CF-1.
4 SPACE HUMIDITY SENSOR ASSOCIATED WITH
AHU-S-1. TERMINATE SENSOR AT AHU-S-1
CONTROLLER.
5 CONTRACTOR TO INSTALL CONDENSING UNIT 1'
ABOVE FLOOD ELEVATION
6 CONTRACTOR TO COORDINATE EXISTING
PENETRATION IN EXTERIOR WALL WITH NEW
LOUVER (LV-S-1) PRIOR TO PURCAHSE.
7 CONTRACTOR TO PROVIDE ACCESS DOOR FOR
FANS ON RIGHT SIDE OF AIR HANDLER
8 PROVIDE STANDALONE TEMPERATURE SENSOR
FOR MONITORING PURPOSES.
9 CONTRACTOR TO ROUTE INSULATED 1"
DN
C F
M
M
A
A
(TYP.2)
A
(TYP.2)
T
T
T T H
T
T
T
T
T
B
B
B
B
B
B
B
"x
E A
"x
E A
"x
E A
6"x6" EA
8"x8" EA
8"x8" EA
A
A
A
A
A
A
"x
S A
12"x10" SA
"x
S A
8"ø SA
"x
S A
8"ø SA
"x
S A
"x
S A
8"ø SA
6"ø SA
8"x8" SA
"ø
S A
"ø
S A
6"ø SA
8"ø SA 10"x8" SA 1 "x
"x
S A
6"ø SA
6"ø SA
"ø
S A
10"ø SA
10"x10" SA14"x14" SA
"ø
S A
"x
S A
"ø
S A
"x
S A
16"x16" S A
"x
S A 8"ø SA
8"ø SA
8"ø SA
"ø
S A
6"ø SA6"ø SA
"x
S A
8"ø SA
8"ø SA
8"ø SA
12"x10" 8"ø SA
4" CONCRETE PAD
BAS
DISC.
FOR AHU-S-1
LV-S-4
LV-S-1
VAV-S-1-6
VAV-S-1-7
VAV-S-1-3
VAV-S-1-5
VAV-S-1-8
VAV-S-1-1
VAV-S-1-2
VAV-S-1-4
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
CF-1
VAV-S-1-9
EF-S-1
32"x30" RA
"x
R A
34"x20" RA20"x16" RA14"x12" RA
"x
R A
"x
R A
"x
R A
"x
R A
"x
R A
"x
R A
"x
R A
"x
R A
16"x14" RA "x
R A
10"x10" RA
M201
EQUIPMENT TOOLS
CAGES
OFFICE 3
OFFICE 4
1123 OFFICE 5
OFFICE 6
OFFICE 7
229 SF
SMALL CONFERENCE
ROOM
LOUNGE ROOM
357 SF
LARGE CONFERENCE
ROOM
950 SF
SPECIAL EVENT
STORAGE/ MULTI-USE
WORK ROOM
MEN'S RESTROOM
CUSTODIAL
411 SF
PUBLIC
WOMEN'S RESTROOM
CUBICLE 6
238 SF
WOMEN'S BATHROOM
MEN'S BATHROOM
OFFICE 6
MDF ROOM
OPEN SPACE
OFF. SUPPLIES
CUBICLE 4
CUBICLE 5
MAINTENANCE &
REPAIRS AREA
CUSTODIAL
156 SF
MECH. ROOM
84 SF
ELECTRIAL ROOM
PARKS & REC
WAREHOUSE
CLOSET
EXECUTIVE OFFICE
CUBICLE 3
CUBICLE 2
SENIOR ASSIST.
CUSTODIAL
OFFICE 1
OFFICE 2
T
T
MSCU-S-1
4" CONCRETE PAD
EF-S-2 LV-S-2
44"x44" EA
LV-S-3
TA
A
A
10"ø SA
12"x12" SA10"ø SA
26"x20" SA
/4
"ø C
D
MSAC-S-1
VAV-S-10
D
D 270C
B
B
B 725 B
B
B
B
B
B
B 100B
B
A
C
B
6"ø SA
6"ø SA
"ø
S A
20"x12" EA
"x
S A
10"x10" SA
"x
" R
A
"ø
S A
B
"ø
S A
CU-S-1
B
B
B
"x
R A
10"x8" RA 10"x8"
14"x12" OA
AHU-S-1
4" CONCRETE PAD
"x
S A
12"ø SA
8"ø SA
5"ø SA
"ø
S A
"ø
S A
8"ø SA
"x
S A
"ø
S A
10"ø SA
"ø
S A
H/O/A
DISC.
FOR CU-S-1
DISC.
FOR MSCU-S-1
A
GENERAL NOTES:
1. REFER TO GENERAL NOTES FOR THIS DISCIPLINE.
2. REFER TO SPECIFICATIONS.
3. ALL HEX NOTES NOT NECESSARILY USED ON ALL
SHEETS.
4. SEE SECTION VIEW MECHANICAL ROOM PLANS FOR
MORE DETAIL.
5. ALL AIR HANDLING SYSTEMS WILL UTILIZE A FULLY
DUCTED RETURN AIR SYSTEM.
6. PROVIDE A VOLUME DAMPER ON ALL BRANCH
DUCTWORK AND ANY RUNOUT TO A DIFFUSER,
WHETHER SHOWN ON DRAWINGS OR NOT.
7. ALL VOLUME DAMPERS INSTALLED ABOVE GYPSUM
BOARD CEILING SHALL HAVE REMOTELY OPERATED
DAMPER.ALL OUTSIDE AIR LOUVERS SHALL BE
PROVIDED WITH 1/4" X 1/4" REMOVABLE BIRD SCREEN
AND REMOVABLE FILTERS IN A FILTER RACK. THIS
SHALL BE INSTALLED IN A CHANNEL AND SHALL BE
EASILY REMOVED. SCREWED BIRD SCREEN TO THE
LOUVER IS NOT ACCEPTABLE.
8. PROVIDE VOLUME DAMPERS ON EACH BATHROOM
EXHAUST GRILLE.
9. REFER TO MANUFACTURER'S RECOMMENDATIONS
FOR ALL REFRIGERANT PIPE SIZES ACCORDING TO
FINAL LENGTH OF RUN.
10. ALL RETURN GRILLES LOCATIONS MUST BE
INSTALLED AT OR FARTHER THAN LOCATIONS
SHOWN, OR FARTHER THAN BRANCH RUNOUT TO
ELIMINATE NOISE TRANSMISSION.
11. ALL LOUVER PLENUMS SHALL SLOPE BACK TOWARDS
THE LOUVER ON THE EXTERIOR WALL. FINAL SIZE,
HEIGHT, COLOR AND LOCATION OF THE LOUVERS
SHOULD BE COORDINATED WITH THE
ARCHITECTURAL ELEVATIONS AND GENERAL
CONTRACTOR, PRIOR TO ORDERING LOUVERS.
12. FULLY COORDINATE WITH THE ARCHITECTURAL
REFLECTED CEILING PLANS FOR DIFFUSER
LOCATIONS PRIOR TO INSTALLATION.
13. CONTRACTOR SHALL COORDINATE VAV ELECTRICAL
CLEARANCES. INCLUDING LOW VOLTAGE, WITH ALL
CEILING MOUNTED EQUIPMENT IN SHOP DRAWINGS,
WHICH INCLUDES BUT IS NOT LIMITED TO LIGHTING,
PROJECTORS, SYSTEMS DEVICES, AND FIRE
SPRINKLERS. CLEARANCES SHALL BE SIZED AND
COORDINATED AS REQUIRED BASED ON THE
AWARDED MANUFACTURER VAV BOX
REQUIREMENTS. LIGHTS AND EQUIPMENT BELOW THE
VAV CLEARANCE, IN THE CEILING ARE NOT
ACCEPTABLE.
14. REFER TO ARCHITECTURAL DRAWINGS FOR
MOUNTING HEIGHT AND COLOR OF ALL LINEAR
DIFFUSERS.
MPE JOB #:
ENG. BUS. No. EB-0005096
CERT. OF AUTH. No. 5096
PHONE (239) 332-1187
12437 Brantley Commons Fort Myers, FL 33907
TO
D GRIFF
No 67083P R
STATE OF
E
O F
E S
S
ION A L E N
G
IN
E E
R
NSECIL
F L O R I DA
THK
D I
K. Todd Griffith No.67083
HEX NOTES:
PROJECT NO:
DATE:
PHASE:
ISSUED FOR
SEAL:
GRACE HEBERT CURTIS ARCHITECTS, LLC
SHEET NUMBER
© THIS SET OF DOCUMENTS INCLUSIVE OF
DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT
BE COPIED, SCANNED, NOR ELECTRONICALLY
DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT
THE EXPRESSED WRITTEN CONSENT OF GRACE
HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,
ELECTRONIC PLAN SERVICE (INTERNET PLAN
SERVICE), NOR REPRODUCTION COMPANY SHALL BE
PERMITTED TO POST THESE DOCUMENTS WITHOUT
THE EXPRESSED WRITTEN CONSENT OF THE
ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.
2024-118
/1
/2
:0
:1
P
M
A u to d e s k D o c s /W a re h o u s e C o n v e rt t o P a rk s
R e c D e p a rt m e n t/
-1
M e c h a n ic a l M o d e l_
O p ti o n T w o
R e v it
B
IM
.r v t
M101-S-2
1ST FLOOR PLAN - SOUTH
BUILDING - MECHANICAL -
ALTERNATE
40-24105
W A
R E
H O
U S
E C
O N
V E
R T
T O
P A
R K
S
R E
C D
E P
T
C
IT
Y O
F F
O R
T M
Y E
R S
06/19/2025
PERMIT DOCUMENTS
M
IC
H
IH
A
N A
V E
N U
E F
O R
T M
Y E
R S
F
L O
R
ID
A
1/4" = 1'-0"1 FIRST FLOOR SOUTH BUILDING
1 CONTRACTOR TO ROUTE 1" INSULATED
CONDENSATE PIPING TO NEAREST HUB DRAIN.
2 CONTRACTOR TO COORDINATE EXISTING
PENETRATION IN EXTERIOR WALL WITH NEW
LOUVER (LV-S-4) PRIOR TO PURCAHSE.
3 CONTRACTOR TO PROVIDE FACTORY CONTROLLER
FOR CF-1.
4 SPACE HUMIDITY SENSOR ASSOCIATED WITH
AHU-S-1. TERMINATE SENSOR AT AHU-S-1
CONTROLLER.
5 CONTRACTOR TO INSTALL CONDENSING UNIT 1'
ABOVE FLOOD ELEVATION
6 CONTRACTOR TO COORDINATE EXISTING
PENETRATION IN EXTERIOR WALL WITH NEW
LOUVER (LV-S-1) PRIOR TO PURCAHSE.
7 CONTRACTOR TO PROVIDE ACCESS DOOR FOR
FANS ON RIGHT SIDE OF AIR HANDLER
8 PROVIDE STANDALONE TEMPERATURE SENSOR
FOR MONITORING PURPOSES.
9 CONTRACTOR TO ROUTE INSULATED 1"
BUILDING AUTOMATION SYSTEM & CONTROLS GENERAL NOTES
GENERAL NOTES
1. REFER TO SPECIFICATION SECTION 23 09 23.
2. REFER TO SPECIFICATION SECTION 23 09 93.
3. REFER TO SPECIFICATION SECTION 23 05 93.
4. REFER TO SPECIFICATION SECTION 23 08 00.
5. REFER TO THE DIVISION 23 SPECIFICATIONS.
6. REFER TO THE DIVISION 26 SPECIFICATIONS.
7. REFER TO NEC.
8. REFER TO PROJECT GENERAL NOTES.
9. CONTROL DRAWINGS ARE NOT TO SCALE.
10. CONTROL FLOW DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE
NOT MEANT TO REPRESENT THE PHYSICAL CONFIGURATIONS OR
DIMENSIONS OF THE REFERENCED EQUIPMENT.
11. CONTROL FLOW SHAPES ARE DIAGRAMMATIC IN NATURE AND ARE NOT
MEANT TO REPRESENT THE PHYSICAL CONFIGURATIONS, DIMENSIONS,
MODELS, TYPES, GENERATIONS, OR MANUFACTURERS OF THE
REFERENCED DEVICES.
12. THE CONTROL POINTS INDICATED IN THESE DRAWINGS ARE
REPRESENTATIVE OF THE MINIMUM SUCH POINTS REQUIRED TO
ACHIEVE THE INTENDED SEQUENCE OF OPERATION AND SYSTEM
MONITORING FUNCTIONALITY. CONTROL SCHEMES EMPLOYING FEWER
POINTS IN CONCERT WITH SHARED VALUES, COMMUNICATED VALUES,
OR CALCULATED VALUES IN LIEU OF INDICATED POINT COUNT SHALL
NOT BE ACCEPTABLE.
13. THE CONTROL HARDWARE AND END DEVICES INDICATED IN THESE
DRAWINGS ARE REPRESENTATIVE OF THE MINIMUM SUCH DEVICES
REQUIRED TO ACHIEVE THE INTENDED SEQUENCE OF OPERATION AND
SYSTEM MONITORING FUNCTIONALITY. CONTROL SCHEMES EMPLOYING
FEWER DEVICES IN CONCERT WITH SHARED VALUES, COMMUNICATED
VALUES, OR CALCULATED VALUES IN LIEU OF INDICATED DEVICE
QUANTITY SHALL NOT BE ACCEPTABLE.
14. CONTROLS HARDWARE AND END DEVICES INSTALLED BY OR PROVIDED
BY HVAC EQUIPMENT MANUFACTURER ARE SUBJECT TO THE SAME
SPECIFICATIONS AND REQUIREMENTS AS THOSE INSTALLED BY OR
PROVIDED BY THE BAS CONTRACTOR.
15. ANY INDIVIDUAL SYSTEM, AS DEFINED BY CONTROLS FLOW DIAGRAMS,
CONTROLLED OR MONITORED BY THE BAS COMPRISED OF THREE OR
GREATER CONTROLS POINTS, COMBINATION OF INPUTS AND OUTPUTS,
SHALL BE EQUIPPED WITH A DEDICATED CONTROLLER WITHIN THE BAS
ARCHITECTURE.
16. WHERE PERIPHERAL SYSTEMS ARE CONTROLLED OR MONITORED VIA
THE USE OF AUXILIARY POINT TERMINATIONS ON CONTROLLERS NOT
DEDICATED TO SAID SYSTEMS, BAS CONTRACTOR SHALL PROVIDE A
SCHEDULE OF SUCH SYSTEMS INDICATING THE CONTROLS POINTS IN
QUESTION, THE LOCATION OF THE ASSOCIATED CONTROLLER, AND THE
INDIVIDUAL POINT TERMINATION DESIGNATIONS. THIS INFORMATION
SHALL BE DISPLAYED ON THE BAS GRAPHICAL INTERFACE FOR
REFERENCE PURPOSES.
17. SYSTEM ALARMS AND NOTIFICATIONS SHALL BE IDENTIFIED WITH
SPECIFIC UNIT TAGS, BUILDING NUMBERS, ROOM NUMBERS, OR OTHER
SITE SPECIFIC IDENTIFYING CRITERIA, VIA THE BAS INTERFACE, SUCH
THAT SYSTEM OPERATORS CAN ASSOCIATE ANY ALARM WITH THE
SPECIFIC PIECE OF EQUIPMENT IT IS RELATED TO.
18. BAS FLOOR PLAN GRAPHICS SHALL INCLUDE SITE SPECIFIC BUILDING
NUMBERS OR NAMES, ROOM NUMBERS OR NAMES, GENERAL AREA
DESIGNATIONS, AND EQUIPMENT TAGS SUCH THAT SYSTEM
OPERATORS CAN ASSOCIATE OCCUPANT COMMUNICATIONS WITH THE
SPECIFIC PIECE OF EQUIPMENT SERVING THE LOCATION IN QUESTION.
19. BAS GRAPHICS TEXT SHALL BE ARRANGED IN A LOGICAL MANNER AND
CONFIGURED TO COINCIDE WITH THE GRAPHICAL DESIGN AND COLOR
SCHEME SUCH THAT TEXT IS CLEAR & LEGIBLE AND ITS PLACEMENT
DOES NOT RESULT IN EXCESSIVE OVERLAP WITH BACKGROUND
IMAGES.
20. SPACE SENSORS MOUNTED ON EXTERIOR WALLS SHALL BE
THERMALLY INSULATED FROM THE SURFACE TO WHICH THEY ARE
MOUNTED.
21. BAS CONTROLLERS SHALL BE PROGRAMMED WITH A DEFAULT
OPERATIONAL STATE TO BE ACTIVATED IN THE EVENT OF SYSTEM
COMMUNICATION FAILURE IN ACCORDANCE WITH THE SEQUENCE OF
OPERATION OF THE ASSOCIATED SYSTEM. IF NO DEFAULT STATE IS
SPECIFIED, IT SHALL BE ASSUMED THAT THE SYSTEM IS INTENDED TO
OPERATE IN OCCUPIED MODE DURING COMMUNICATION FAILURE.
22. CONTROLS HARDWARE AND END DEVICES EQUIPPED WITH LOCAL
DISPLAYS SHALL BE MOUNTED SUCH THAT THE LOCAL DISPLAY IS FREE
OF OBSTRUCTIONS AND IS LEGIBLE FROM A HEIGHT OF FIVE FEET
ABOVE THE FLOOR.
23. FOR THE PURPOSE OF CONTROL VALVE SELECTION, A NOMINAL
PRESSURE DROP OF BETWEEN 3 TO 4 PSI SHALL BE USED TO
CALCULATE THE TARGET FLOW COEFFICIENT (Cv) OF THE SELECTED
VALVE.
24. CONTROL VALVE SIZE (DIAMETER) SHALL NOT BE MORE THAN TWO
STANDARD PIPE SIZES (DIAMETERS) SMALLER THAN THE INCOMING
PIPE SIZE (DIAMETER).
25. TWO POSITION CONTROL VALVES USED FOR ISOLATION PURPOSES
SHALL BE OF THE SAME SIZE (DIAMETER) AS THE INCOMING PIPE.
26. CONTROL VALVES SHALL BE SELECTED TO FACILITATE SUFFICIENT
CONTROLLABILITY RELATIVE TO THE CONTROLLED LOAD WITH AT
LEAST 75% OF THE TOTAL VALVE STROKE AVAILABLE AT NOMINAL
SYSTEM PRESSURE.
27. CONTROL VALVES AND ACTUATORS SHALL BE SELECTED WITH
SUFFICIENT CLOSE OFF PRESSURE TO FACILITATE FULL VALVE
CLOSURE AT MAXIMUM SYSTEM PRESSURE.
28. FOR SYSTEMS EMPLOYING FLOATING POINT ACTUATORS, THE BAS
SHALL BE PROGRAMMED TO EXECUTE A PERIODIC…