2024-118_-_Combined_Fire_Protection_-_S&S.pdf
PDF 1 MB Posted
- Attached to
- Michigan Avenue Warehouse Renovation
- Solicitation number
- ITB 25-098
- Issued by
- Lee County, Fruitville CDP, Florida
About this file
These documents are fire protection design plans for a warehouse conversion project for the City of Fort Myers Parks & Recreation Department, involving the renovation of existing warehouse buildings located at 2801 Michigan Avenue in Fort Myers, Florida. The project involves providing a wet sprinkler system for two buildings: a North Building of approximately XX,XXX square feet and a South Building of approximately XX,XXX square feet. The fire protection system design is prepared by Matern Engineering and follows multiple codes and standards including NFPA 13, Florida Building Code, Florida Fire Prevention Code, and local Lee County ordinances. The sprinkler system will be a hydraulically designed automatic wet pipe fire sprinkler system, with careful consideration for ceiling grid, architectural features, equipment locations, and maintaining appropriate clearances and coverage.
The system design includes specific hydraulic calculations for system demand, with estimated requirements ranging from 280 GPM for office areas to 640 GPM for record storage areas. The design specifies different occupancy classifications with corresponding sprinkler spacing and density requirements, including Light Hazard (0.10 GPM/sq ft), Ordinary Hazard Group I (0.15 GPM/sq ft), and provisions for storage areas. All devices and equipment will be U.L. listed and F.M. approved, with an existing 8" fire main supplying the system. The project includes revising existing branch piping, providing sprinkler coverage in all areas, and ensuring compliance with fire protection standards, including requirements for spare sprinklers, hanger specifications, and water flow device installations.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
XXX
XX PSI
XX PSI
XXX GPM
XXX
XXX
FIRE SPRINKLER SPARE CABINET
WATER FLOW DEVICE
TRAPEZE HANGER DETAIL
NOT TO SCALE9
HANGER DETAIL
W/ HEAD GUARDSPRINKLER
SPRINKLER
2 3
W/ HEAD GUARD
SPRINKLER
UPRIGHT SPRINKLERRECESSED PENDENT UPRIGHT PENDENT SPRINKLER SIDEWALL
HYDRAULIC-SYSTEM
THIS BUILDING IS PROTECTED
BY A HYDRAULICALLY DESIGNED
AUTOMATIC SPRINKLER SYSTEM
LOCATION
NO. OF SPRINKLERS
BASIS OF DESIGN
SYSTEM DEMAND
1. DENSITY
2. DESIGNED AREA OF DISCHARGE
1. GPM DISCHARGE
2. RESIDUAL PRESSURE AT THE
BASE OF THE RISER
GPM SQ FT
SQ FT
GPM
PSI
HYDRAULIC SYSTEM SIGN DETAIL
NOT TO SCALE
RATED PIPE PENETRATION - GYPSUM BOARD WALLS
NOT TO SCALE12
17.4.2* MAXIMUM DISTANCE BETWEEN HANGERS.
17.4.2.1 THE MAXIMUM DISTANCE BETWEEN HANGERS SHALL NOT EXCEED THAT SPECIFIED IN TABLE
17.4.2.1(A) OR TABLE 17.4.2.1(B), EXCEPT WHERE THE PROVISIONS OF 17.4.4 APPLY.
TABLE 9.2.2.1 MAXIMUM DISTANCE BETWEEN HANGERS
(FT-IN)
Nominal Pipe Size (in.) 3/4
N/ASteel pipe except threaded lightwall
12-0
1 1/4 1 1/2
15-0
2 2 1/2 3 43 1/2
12-0 15-0 15-0 15-0 15-0 15-0
17.2.1HANGER RODS.
17.2.1.1 UNLESS THE REQUIREMENTS OF 17.2.1.2 ARE MET,
HANGER ROD SIZE SHALL BE THE SAME AS THAT APPROVED FOR
USE WITH THE HANGER ASSEMBLY, AND THE SIZE OF RODS SHALL
NOT BE LESS THAN THAT GIVEN IN TABLE 17.2.1.1.
Diameter of Rod
Pipe Size
Up to and including 4 in.
5 in., 6 in., and 8 in.
10 in
17.2.2.10 MINIMUM BOLT SIZE FOR CONCRETE.
17.2.2.10.1 THE SIZE OF A BOLT USED WITH A HANGER AND
INSTALLED THROUGH CONCRETE SHALL NOT BE LESS THAN
SPECIFIED IN TABLE 17.2.2.10.1.
Size of Bolt
Pipe Size
Up to and including 4 in.
5 in. to 8 in.
10 in.
Table 17.2.1.1 Hanger Rod Sizes
Table 17.2.2.10.1 Minimum Bolt Size for Concrete
12 in.
DISTANCE BETWEEN HANGERS
HANGER SPACING DETAIL
NOT TO SCALE11
12 in
5 6 8
15-0 15-0 15-0
61G15-32.003
1 DESIGN CRITERIA:
THE NATURE AND SCOPE OF THE WORK IS: THE PROJECT IS TO PROVIDE A WET SPRINKLER FOR EXISTING WAREHOUSE BUILDINGS.
NORTH BUILDING AT XX,XXX SQUARE FEET.
SOUTH BUILDING AT XX,XXX SQUARE FEET.
SPRINKLER SYSTEM LAYOUT SHALL BE SUBMITTED BY A STATE OF FLORIDA LICENSED FIRE PROTECTION CONTRACTOR. THE BUILDING HAS AN EXISTING WET
PIPE SPRINKLER SYSTEM. THE CONTRACTOR SHALL PROVIDE A REVISED LAYOUT OF THE EXISTING SPRINKLER SYSTEM. AUTOMATIC WET PIPE FIRE
SPRINKLER SYSTEM SHALL BE APPLICABLE TO ALL CODES SET FORTH BY THE AUTHORITY HAVING JURISDICTION. DISCHARGE FROM INDIVIDUAL HEADS IN
THE HYDRAULICALLY MOST REMOTE/DEMANDING AREA SHALL BE HYDRAULICALLY CALCULATED TO AN ACCEPTABLE MARGIN OF SAFETY OF NOT LESS THAN 5
PSI. FIRE SPRINKLER SYSTEM SHALL INCLUDE MATERIALS, ACCESSORIES, AND EQUIPMENT INSIDE AND OUTSIDE THE BUILDING TO PROVIDE A COMPLETE AND
READY FOR USE SPRINKLER SYSTEM. LAYOUT AND PROVIDE EACH SYSTEM TO GIVE FULL CONSIDERATION TO BLIND SPACES, PIPING, ELECTRICAL
EQUIPMENT, DUCTS, HVAC EQUIPMENT, ACCESS SPACE NEEDED FOR MAINTENANCE OF EQUIPMENT AND OTHER CONSTRUCTION AND EQUIPMENT IN
ACCORDANCE WITH DETAILED WORKING DRAWINGS TO BE SUBMITTED FOR APPROVAL. LOCATE SPRINKLER HEADS IN A CONSISTENT PATTERN WITH CEILING
GRID, LIGHTS, DIFFUSER, REGISTERS, GRILLES AND ARCHITECTURAL FEATURES. DEVICES AND EQUIPMENT FOR FIRE PROTECTION SERVICES SHALL BE U.L.
LISTED AND F.M. APPROVED FOR USE IN WET PIPE
SYSTEM.
THE AUTOMATIC FIRE SUPPRESSION SYSTEM SHALL BE TESTED IN ACCORDANCE WITH NFPA 13, CHAPTER 25 AND NFPA 25.
UNDER GROUND FIRE SERVICE MAINS SHALL BE TESTED IN ACCORDANCE WITH NFPA 25.
5 PER STRUCTURAL SHEETS DESIGNED SUPERIMPOSED ROOF LOADS INCLUDING FIRE PROTECTION LOADS ARE:
LIVE = XX PSF AND SUPERIMPOSED DEAD LOAD = XX PSF
REFER TO STRUCTURAL SHEETS FOR COMPLETE PROJECT INFORMATION
61G15-32.004
4A FOR "POINT OF SERVICE" PER F.S. 633 REFER TO SHEET FXXX.
4B INSTALLATION SHALL BE IN ACCORDANCE WITH NFPA 13, FIRE PREVENTION CODE, STATE AND LOCAL AUTHORITIES.
4C REFER TO HYDRAULIC DESIGN DATA LEGEND ON FLOOR PLANS.
4D REFER TO 61G15-32.003 COMPLIANCE NOTE #1 AND HYDRAULIC DESIGN DATA LEGEND ON FLOOR PLANS.
4E BUILDING SPRINKLER SYSTEM IS SUPPLIED BY A X" FIRE MAIN 1'-0" ABOVE FINISHED FLOOR TO X" WATER MAIN ON SITE. THE 8" WATER MAIN IS CIRCULATING AND CONNECTS TO OFF-SITE EXISTING 10" WATER MAIN EAST OF PROJECT SITE AND TO OFF-SITE EXISTING X" MAIN NORTH SIDE COUNTY PROPERTY.
4G ALL VALVES CONTROLLING WATER SUPPLY SHALL HAVE A RED TAMPER PROOF COVER WHICH WILL ACTIVATE AN ALARM OR
TROUBLE SIGNAL WHEN ADJUSTED.
4H UTILITY PURVEYOR IS NOT AWARE OF MICROBIOLOGICAL CONTAMINANTS WHICH MAY CAUSE MICROBIAL INDUCED CORROSION IN
THEIR SYSTEM.
4I FIRE MAIN IS PROVIDED WITH WILKENS 450DA N-STYLE DOUBLE CHECK DETECTOR ASSEMBLY WITH AN ALLOWABLE PRESSURE DROP
OF 12 PSI.
4J ALL YARD AND INTERIOR FIRE PROTECTION COMPONENTS SHALL BE NEW U.L. LISTED AND FM APPROVED.
PROJECT NAME: WAREHOUSE CONVERT TO PARKS & REC DEPARTMENTPROJECT LOCATION: FORT MYERS, FLORIDA
61G15-32 COMPLIANCE NOTES
4F FLOW TEST DATE
STATIC GAUGE PRESSURE
RESIDUAL GAUGE PRESSURE
FLOW RATE
SOURCE OF INFORMATION:
FLOW HYDRANT
SPARE SPRINKLERS
NOT TO SCALE
WHICH IS MAINTAINED BELOW
WITH 19 GAUGE SHEET
22 GAUGE SHEET METAL
CABINET BOX SHALL BE
PAINT WITH RED ENAMEL
INSIDE AND OUT AND
LABEL
METAL COVER
MOUNT IN A SECURE AREA
95° F AMBIENT
SPRINKLER WRENCH
ACTUATOR COLLAR
1/2" CONDUIT HOLE
SADDLE LOCATOR
VANE
RESET SPRING
MOUNTING PLATE
COVER TAMPER SWITCH
DUAL SWITCH
NOT TO SCALE
ACTUATOR LEVER
PNEUMATIC RETARD DEVICE
RETARD ADJUSTMENT DIAL
WASHERS
VANE GASKET
SADDLE O-RING
SADDLE GASKET
TORSION SPRING
- NORMAL SET POSITION -
FLOW
WATER
SADDLE
U-BOLT
FACILITIES HAVING UNDER 300 SPRINKLERS - NO FEWER THAN 6 SPARE SPRINKLERS IN STOCK FACILITIES HAVING 300 - 1000 SPRINKLERS - NO FEWER THAN 12 SPARE SPRINKLERS IN STOCK FACILITIES HAVING OVER 1000 SPRINKLERS - NO FEWER THAN 24 SPARE SPRINKLERS IN STOCK
LOCATE IN CUSTODIAL EQUIPMENT STORAGE 01-141
BAR JOIST
TOP BEAM CLAMP
SWIVEL HANGER RING
PIPE (SPECIFY
SIZE & LENGTH)
ALL-THREAD ROD
(LENGTHS VARY)
SWIVEL HANGER RING
NOT TO SCALE
PIPE
THREADED
ROD
W/LOCK NUT
C-CLAMP (STANDARD THROAT)
SWIVEL RING
ADJUSTABLE
STEEL I-BEAM OR
BAR JOIST
JOIST TO CENTER LINE
TOP OF BEAM OR BAR
OF PIPE
NOT TO SCALE NOT TO SCALE NOT TO SCALE NOT TO SCALE NOT TO SCALE
F
LO
W
F
LO
W
SIDEWALL
LU C701AUL
TOP HSW-1
RELIABLE
RASCO
PROJECT INFORMATION
NOTE:
HYDRAULIC SYSTEM PLATE SHALL BE LOCATED AS TO BE
HIGHLY VISIBLE ON EACH SYSTEM RISER.
4K A FIRE PUMP IS NOT REQUIRED BASED ON THE FLOW TEST PROVIDED AND THE DEMANDS OF THE BUILDING.
4M
4L FIRE WATER STORAGE TANK IS NOT REQUIRED. REFER TO ESTIMATED DEMAND BELOW.
ESTIMATE OF SYSTEM DEMAND: Q (GPM)
Q = DENSITY X REMOTE AREA X OVERAGE FACTOR + HOSE STREAM = MINIMUM GPM
OVERAGE FACTOR:
LIGHT HAZARD: 1.2
ORDINARY HAZARD: 1.3
EXTRA HAZARD: 1.4
RECORD STORA
DENSITY: ORDINARY HAZARD .20
REMOTE AREA: 1,500 SQ.FT.
OVERAGE FACTOR: 1.3
Q = .20 X 1,500 SQ.FT. X 1.3 (OH-1) + 250 = 640 GPM
OFFICE AREA
DENSITY: LIGHT HAZARD .10
REMOTE AREA: 1,500 SQ.FT.
OVERAGE FACTOR: 1.2
Q = .10 X 1,500 SQ.FT. X 1.2 (LH) + 100 = 280 GPM
THE ABOVE LOCATION IS BASED ON A REMOTE ARE OF 1,500 SQ.FT.. CONTRACTOR HAS THE OPTION TO
REDUCED THE REMOTE ARE IN ACCORDANCE WITH NFPA 13, 11.2.3.2.3.1.
THIS BUILDING HAS NO SPECIALIZED OCCUPANCIES OR AREAS, STORAGE OVER 12' OR STORAGE OF PLASTICS, RUBBER OR SIMILAR PRODUCTS AS NOTED
IN NFPA 13 FIGURE A.23.1(B).
SECTION A-A
A
A
4B 3 4A
1A
4A 4B
1B
SYSTEM NO. W-L-5001
F RATINGS-1 AND 2 HR (SEE ITEM 1)
T RATINGS-3/4, 1 AND 1-1/2 HR (SEE ITEM 3)
L RATING AT AMBIENT - 2 CFM PER SQ FT
L RATING AT 400 F - LESS THAN 1 CFM PER SQ FT
REFER HYDRAULIC DESIGN DATA BELOW AND ON FLOOR PLAN SHEETS FOR HAZARD CLASSIFICATIONS AND REQUIRED DENSITIES.
LIGHT HAZARD OCCUPANCY CLASSIFICATION:
MAXIMUM SPRINKLER SPACING 225 SQ. FT. PER SPRINKLER,
DENSITY GPM/SQ. FT. = 0.10 GPM OVER 1,500 SQ. FT.
HOSE STREAM = 100 GPM / DURATION 30 MINUTES
˃CLASS III, BACK-TO-BACK, 10' TO ≤ 12' STORAGE HIEGHT CLASSIFICATION:
MAXIMUM SPRINKLER SPACING 130 SQ. FT. PER SPRINKLER,
DENSITY GPM/SQ. FT. = OH-2 DESIGN CURVE OVER 1,500 SQ. FT.
HOSE STREAM = 250 GPM / DURATION 90 MINUTES
EXTRA HAZARD GROUP I OCCUPANCY CLASSIFICATION:
MAXIMUM SPRINKLER SPACING 100 SQ. FT. PER SPRINKLER,
DENSITY GPM/SQ. FT. = 0.30 GPM OVER 2,500 SQ. FT.
HOSE STREAM = 500 GPM / DURATION 90-120 MINUTES
ORDINARY HAZARD GROUP I OCCUPANCY CLASSIFICATION:
MAXIMUM SPRINKLER SPACING 130 SQ. FT. PER SPRINKLER,
DENSITY GPM/SQ. FT. = 0.15 GPM/SQ.FT. OVER 1,500 SQ. FT.
HOSE STREAM = 250 GPM / DURATION 60-90 MINUTES
17.4.3.2* MINIMUM NUMBER OF HANGERS.
17.4.3.2.1 UNLESS THE REQUIREMENTS OF 17.4.3.2.2 THROUGH 17.4.3.2.5 ARE MET, THERE SHALL BE NOT LESS THAN ONE HANGER FOR EACH SECTION
OF PIPE.
17.4.3.2.2* UNLESS THE REQUIREMENTS OF 17.4.3.2.3 ARE MET, WHERE SPRINKLERS ARE SPACED LESS THAN 6 FT (1.8 M) APART, HANGERS SPACED UP
TO A MAXIMUM OF 12 FT (3.7 M) SHALL BE PERMITTED.
17.4.3.2.3 FOR WELDED OR MECHANICAL OUTLETS ON A CONTINUOUS SECTION OF PIPE, HANGER SPACING SHALL BE ACCORDING TO TABLE 17.4.2.1(A)
OR TABLE 17.4.2.1(B).
17.4.3.2.4* STARTER LENGTHS LESS THAN 6 FT (1.8 M) SHALL NOT REQUIRE A HANGER, UNLESS ON THE END LINE OF A SIDEFEED SYSTEM OR WHERE AN
INTERMEDIATE CROSS MAIN HANGER HAS BEEN OMITTED.
17.4.3.2.5* A SINGLE SECTION OF PIPE SHALL NOT REQUIRE A HANGER WHEN THE CUMULATIVE DISTANCE BETWEEN HANGERS ON THE BRANCH LINE
DOES NOT EXCEED THE SPACING REQUIRED BY TABLE 17.4.2.1(A) AND TABLE 17.4.2.1(B).
17.4.3.3 CLEARANCE TO HANGERS. THE DISTANCE BETWEEN A HANGER AND THE CENTERLINE OF AN UPRIGHT SPRINKLER SHALL NOT BE LESS
THAN 3 IN. (75 MM)..
in.
3/8
1/2 mm
5/8 16 in.
3/8
1/2 mm
5/8 16
3/4 20
3/4 20
1. REFER TO SPECIFICATIONS FOR THIS DISCIPLINE.
2. WORKING PLANS SHALL BE SUBMITTED FOR APPROVAL TO THE
AUTHORITY HAVING JURISDICTION BEFORE ANY EQUIPMENT IS
INSTALLED.
3. PENDENT SPRINKLERS SHALL BE INSTALLED IN ALL AREAS WITH
LAY-IN CEILINGS, SPRINKLER SHALL BE LOCATED IN CENTER TILE.
WHEN 2'x4' TILES ARE INSTALLED, TREAT TILE AS 2'x2' AND INSTALL
CENTER OF TILE.
4. SPRINKLER HEADS IN AREAS WITH NO CEILING (NO TILES OR
GYPSUM BOARD) SHALL BE AN UPRIGHT SPRINKLER.
5. CONTRACTOR TO COORDINATE WORK WITH ALL OTHER TRADES.
CONTRACTOR TO COORDINATE FIRE PROTECTION EQUIPMENT
LOCATIONS TO AVOID LIGHTS, AIR DIFFUSERS.
6. CONTRACT SHALL COORDINATE PIPING WITH EQUIPMENT WITHIN
CEILING SPACE NEEDING ACCESS FOR MAINTENANCE.
7. HEAD GUARDS SHALL BE INSTALLED ON SPRINKLERS IN AREAS
WHERE THERE IS A CHANCE OF DAMAGE DUE TO EQUIPMENT.
8. ALL MATERIALS AND EQUIPMENT SHALL BE NEW AND SHALL BE UL
LISTED AND FM APPROVED WHERE APPLICABLE.
9. All SPRINKLER HEADS TO BE INSTALLED PERPENDICULAR TO
CEILING.
10. CONTRACTOR SHALL PROTECT ALL SURFACES DURING
INSTALLATION AND TESTING OF SYSTEMS.
11. UNFORESEEN CONDITIONS MAY EXIST. COOPERATION WITH OTHER
TRADES IN ROUTING AND/OR BURIAL DEPTHS AS DETERMINED
DURING CONSTRUCTION AND AS DIRECTED BY THE ARCHITECT MAY
BE NECESSARY. IT IS INTENDED THAT SUCH DEVIATIONS SHALL BE
CONSIDERED AS PART OF THIS CONTRACT. THE PLANS ARE NOT
COMPLETELY TO SCALE. THIS CONTRACTOR IS TO FIELD VERIFY
DIMENSIONS OF ALL SITE UTILITIES, ETC., PRIOR TO BID AND
INCLUDE ANY DEVIATIONS IN THE CONTRACT.
12. THE CONTRACTOR SHALL PROVIDE ALL MATERIAL, LABOR,
TRUCKING, HOISTING, ENGINEERING, SCAFFOLDING, POWER HOOK
UPS, PROTECTION, SHOP DRAWINGS, TAXES, LAYOUT, EQUIPMENT,
SUPERVISION, INSURANCE, ETC. NECESSARY FOR THE FURNISHING
AND INSTALLATION OF ALL SPECIFIED AND RELATED WORK IN
ACCORDANCE WITH THE CONTACT DRAWINGS AND SPECIFICATIONS.
13. CONTRACTOR SHALL GIVE ALL NECESSARY NOTICES, APPLY FOR
ALL PERMITS, AND PAY ALL GOVERNMENTAL TAXES, FEES AND
SUBMIT ALL NECESSARY PLANS, ALL DOCUMENTS AND OBTAIN ALL
NECESSARY APPROVALS FROM ALL DEPARTMENTS HAVING
JURISDICTION. OBTAIN ALL REQUIRED CERTIFICATIONS OF
INSPECTION FOR HIS/HER WORK AND DELIVER SAME TO THE OWNER
BEFORE REQUEST FOR ACCEPTANCE AND FINAL PAYMENT FOR THE
WORK.
14. WORK SHALL BE PERFORMED, IN STRICT COMPLIANCE WITH THE
ESTABLISHED WORK SCHEDULE BEING SET FORTH BY OWNER.
COORDINATE ALL WORK WITH GENERAL CONTRACTOR. THIS
CONTRACTOR SHALL FURNISH ADEQUATE FORCES, CONSTRUCTION
PLANT AND EQUIPMENT, AND SHALL WORK SUCH HOURS, INCLUDING
NIGHT SHIFTS, OVERTIME OPERATIONS, SUNDAYS AND HOLIDAYS IN
ACCORDANCE WITH THE OWNER'S OPERATIONAL SCHEDULE AS
LISTED IN DIVISION 1 OF THE SPECIFICATIONS. IF THE CONTRACTOR
DOES NOT MAINTAIN THE CONSTRUCTION SCHEDULE BECAUSE OF
INADEQUATE FORCES, SUPERVISION OR ANY OTHER REASON
UNDER THE CONTRACTOR'S CONTROL, THE OWNER MAY REQUIRE
THE CONTRACTOR TO INCREASE THE NUMBER OF SHIFTS AND/OR
OVERTIME OPERATIONS, DAY OF WORK AND/OR THE AMOUNT OF
CONSTRUCTION PLANT, AT NO ADDITIONAL COST TO THE OWNER
UNDER THIS CONTRACT.
15. ALL VALVES CONTROLLING WATER SUPPLY SHALL BE EQUIPPED
WITH TAMPER SWITCHES .
16. CONTRACTOR SHALL PROVIDE AUXILIARY DRAINS AS REQUIRED
PER NFPA 13, 8.15.2.5.2.3.
3. PIPE COVERING*--NOM 1 OR 2 IN. THICK HOLLOW CYLINDRICAL HEAVY DENSITY (MIN 3.5 PCF) GLASS FIBER UNITS JACKETED ON THE OUTSIDE WITH AN ALL SERVICE JACKET. LONGITUDINAL JOINTS SEALED WITH METAL FASTENERS OR FACTORY-APPLIED SELF-SEALING LAP TAPE. TRANSVERSE JOINTS SEALED WITH METAL FASTENERS OR WITH BUTT STRIP TAPE SUPPLIED WITH THE PRODUCT. WHEN NOM 1 IN. THICK PIPE COVERING IS USED, THE ANNULAR SPACE BETWEEN THE PIPE COVERING AND THE CIRCULAR CUTOUT IN THE GYPSUM WALLBOARD LAYERS ON EACH SIDE OF THE WALL SHALL BE MIN 1/4 IN. TO MAX 3/8 IN. WHEN NOM 2 IN. THICK PIPE COVERING IS USED, THE ANNULAR SPACE BETWEEN THE PIPE COVERING AND THE CIRCULAR CUTOUT IN THE GYPSUM WALLBOARD LAYERS ON EACH SIDE OF THE WALL SHALL BE MIN 1/2 IN. TO MAX 3/4 IN. SEE PIPE AND EQUIPMENT COVERING MATERIALS (BRGU) CATEGORY IN BUILDING MATERIALS DIRECTORY FOR NAMES OF MANUFACTURERS. ANY PIPE COVERING MATERIAL MEETING THE ABOVE SPECIFICATIONS AND BEARING THE UL CLASSIFICATION MARKING WITH A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE DEVELOPED INDEX OF 50 OR LESS MAY BE USED. THE HOURLY T RATING OF THE FIRESTOP SYSTEM IS 3/4 HR WHEN NOM 1 IN. THICK PIPE COVERING IS USED.
THE HOURLY T RATING OF THE FIRESTOP SYSTEM IS 1 HR AND 1-1/2 HR WHEN NOM 2 IN. THICK PIPE COVERING IS USED WITH
1 HR AND 2 HR FIRE RATED WALLS, RESPECTIVELY.
4. FIRESTOP SYSTEM--INSTALLED SYMMETRICALLY ON BOTH SIDES OF WALL ASSEMBLY. THE DETAILS OF THE FIRESTOP
SYSTEM SHALL BE AS FOLLOWS:
A. FILL, VOID OR CAVITY MATERIALS*--WRAP STRIP--NOM 1/4 IN. THICK INTUMESCENT ELASTOMERIC MATERIAL FACED ON ONE SIDE WITH ALUMINUM FOIL, SUPPLIED IN 2 IN. WIDE STRIPS. NOM 2 IN. WIDE STRIP TIGHTLY WRAPPED AROUND PIPE COVERING (FOIL SIDE OUT) WITH SEAM BUTTED. WRAP STRIP LAYER SECURELY BOUND WITH STEEL WIRE OR ALUMINUM FOIL TAPE AND SLID INTO ANNULAR SPACE APPROX 1-1/4 IN. SUCH THAT APPROX 3/4 IN. OF THE WRAP STRIP WIDTH PROTRUDES FROM THE WALL SURFACE. ONE LAYER OF WRAP STRIP IS REQUIRED WHEN NOM 1 IN. THICK PIPE COVERING IS USED. TWO
LAYERS OF WRAP STRIP ARE REQUIRED WHEN NOM 2 IN. THICK PIPE COVERING S USED.
MINNESOTA MINING & MFG. CO.--FS-195+
B. FILL, VOID OR CAVITY MATERIALS*--CAULK--MIN 1/4 IN. DIAM CONTINUOUS BEAD APPLIED TO THE WRAP STRIP/WALL INTERFACE AND TO THE EXPOSED EDGE OF THE WRAP STRIP LAYER APPROX 3/4 IN. FROM THE WALL SURFACE.
MINNESOTA MINING & MFG. CO.--CP 25WB+.
*BEARING THE UL CLASSIFICATION MARKING
1. WALL ASSEMBLY--THE 1 OR 2 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION DESIGN IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:
A. STUDS--WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. LUMBER SPACED 16 IN. OC WITH NOM 2 BY 4 IN. LUMBER END PLATES AND CROSS BRACES. STEEL
STUDS TO BE MIN 3-5/8 IN. WIDE BY 1-3/8 IN. DEEP CHANNELS SPACED MAX 24 IN. OC.
B. WALLBOARD, GYPSUM*--NOM 5/8 IN. THICK, 4 FT WIDE WITH SQUARE OR TAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF OPENING IS 14-1/2 IN FOR
WOOD STUD WALLS AND 18 IN. FOR STEEL STUD WALLS.
THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS 1 HR WHEN INSTALLED IN A 1 HR FIRE RATED WALL AND 2 HR WHEN
INSTALLED IN A 2 HR FIRE RATED WALL.
2. THROUGH PENETRANTS--ONE METALLIC PIPE OR TUBING TO BE CENTERED WITHIN THE FIRESTOP SYSTEM. PIPE OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC
PIPES OR TUBING MAY BE USED:
A. STEEL PIPE--NOM 12 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. COPPER TUBING--NOM 6 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.
C. COPPER PIPE--NOM 6 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
1. STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEM - NFPA 13, 2019 EDITION
2. STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE SYSTEM - NFPA 14, 2019 EDITION
3. FLORIDA ADMINISTRATIVE CODE 61G15-32.003 AND 61G15-32.004.
4. FLORIDA BUILDING CODE 8TH EDITION (2023)
5. FLORIDA FIRE PREVENTION CODE 8TH EDITION (2023)
6. FIRE CODE - NFPA 1, 2021 EDITION WITH FLORIDA AMENDMENTS
7. LIFE SAFETY CODE - NFPA 101, 2021 EDITION
8. NATIONAL ELECTRICAL CODE - NFPA 70, 2020 EDITION
9. NATIONAL FIRE ALARM AND SIGNALING CODE - 72, 2019 EDITION
10. LEE COUNTY ORDINANCES
11. STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES - NFPA 24, 2019 EDITION
12. STANDARD FOR THE INSPECTION, TESTING AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS - NFPA 25, 2020
- SHEET INDEX - FIRE -
Sheet Number Sheet Name
F001 GENERAL NOTES AND LEGENDS - FIRE PROTECTION
F101-N FIRE PROTECTION - 1ST AND 2ND FLOOR PLANS - NORTH BUILDING
F101-S FIRE PROTECTION - 1ST FLOOR PLAN - SOUTH BUILDING
F101-S-2 FIRE PROTECTION - 1ST FLOOR PLAN - SOUTH BUILDING - ALTERNATE
MPE JOB #:
ENG. BUS. No. EB-0005096
CERT. OF AUTH. No. 5096
PHONE (239) 332-1187
12437 Brantley Commons Fort Myers, FL 33907
TO
D GRIFF
No 67083P R
STATE OF
E
O F
E S
S
ION A L E N
G
IN
E E
R
NSECIL
F L O R I DA
THK
D I
PROJECT NO:
DATE:
PHASE:
ISSUED FOR
SEAL:
GRACE HEBERT CURTIS ARCHITECTS, LLC
SHEET NUMBER
© THIS SET OF DOCUMENTS INCLUSIVE OF
DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT
BE COPIED, SCANNED, NOR ELECTRONICALLY
DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT
THE EXPRESSED WRITTEN CONSENT OF GRACE
HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,
ELECTRONIC PLAN SERVICE (INTERNET PLAN
SERVICE), NOR REPRODUCTION COMPANY SHALL BE
PERMITTED TO POST THESE DOCUMENTS WITHOUT
THE EXPRESSED WRITTEN CONSENT OF THE
ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.
2024-118
/2
/2
:2
:1
P
M
A u to d e s k D o c s /W a re h o u s e
C o n v e rt t o
P a rk s
R e c D e p a rt m e n t/
-1
P lu m b in g M o d e l_
O p ti o n O n e
R e v it
B
IM
.r v t
F001
GENERAL NOTES AND
LEGENDS - FIRE
PROTECTION
40-24105
W A
R E
H O
U S
E C
O N
V E
R T
T O
P A
R K
S
R E
C D
E P
T
C
IT
Y O
F F
O R
T M
Y E
R S
06/19/2025
PERMIT DOCUMENTS
M
IC
H
IH
A
N A
V E
N U
E F
O R
T M
Y E
R S
F
L O
R
ID
A
NO. DESCRIPTION DATE
8 125
7 9 10 115
GENERAL NOTES
1) REFER TO GENERAL NOTES FOR THIS DISCIPLINE.
2) REFER TO SPECIFICATIONS.
3) ALL SPRINKLERS ARE TO BE CENTER OF TILE UNLESS NOTED
OTHERWISE (2' X 2' TILES).
4) ALL PIPING 2" OR LARGER TO BE SCHEDULE 10 PIPE UNLESS
NOTED OTHERWISE.
5) ALL 1-1/2" OR SMALLER TO BE SCHEDULE 40 PIPE UNLESS
NOTED OTHERWISE.
6) ALL ARM OVERS ARE TO BE 1" SCHEDULE 40 PIPE UNLESS
NOTED OTHERWISE.
7) IT IS THE RESPONSIBILITY OF THE SPRINKLER CONTRACTOR
TO COORDINATE HIS WORK WITH ALL OTHER TRADES, AS
WELL AS THE ARCHITECTURAL AND STRUCTURAL FEATURES
OF THE BUILDING.
8) PROVIDE SPRINKLER COVERAGE ABOVE CEILING IN AREAS
NOT MEETING UNSPRINKLERED CONCEALED SPACE
REQUIREMENTS OF NFPA 13, 8.14.1.2.
9) PROVIDE AUXILIARY DRAIN IN PIPING WHERE AN EXCESS OF
5 GALLONS OF WATER IS TRAPPED, NFPA 13, 8.15.2.5.3.3.
COORDINATE DISCHARGE LOCATION WITH ARCHITECT.
10) CONTRACTOR SHALL CREATE A FULL SET OF COORDINATION
DRAWINGS WITH ALL DISCIPLINES PRIOR TO INSTALLATION
OF SPRINKLER SYSTEM TO INSURE AVAILABLE SPACE FOR
ALL DISCIPLINE COMPONENTS.
11) PROPOSED PIPE ROUTING IS SHOWN AS NEEDED FOR
COORDINATION. FINAL ROUTING OF PIPING SHALL BE
PROVIDED ON CONTRACTOR SHOP DRAWINGS.
MPE JOB #:
ENG. BUS. No. EB-0005096
CERT. OF AUTH. No. 5096
PHONE (239) 332-1187
12437 Brantley Commons Fort Myers, FL 33907
TO
D GRIFF
No 67083P R
STATE OF
E
O F
E S
S
ION A L E N
G
IN
E E
R
NSECIL
F L O R I DA
THK
D I
PROJECT NO:
DATE:
PHASE:
ISSUED FOR
SEAL:
GRACE HEBERT CURTIS ARCHITECTS, LLC
SHEET NUMBER
© THIS SET OF DOCUMENTS INCLUSIVE OF
DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT
BE COPIED, SCANNED, NOR ELECTRONICALLY
DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT
THE EXPRESSED WRITTEN CONSENT OF GRACE
HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,
ELECTRONIC PLAN SERVICE (INTERNET PLAN
SERVICE), NOR REPRODUCTION COMPANY SHALL BE
PERMITTED TO POST THESE DOCUMENTS WITHOUT
THE EXPRESSED WRITTEN CONSENT OF THE
ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.
2024-118
/2
/2
:2
:1
P
M
A u to d e s k D o c s /W a re h o u s e
C o n v e rt t o
P a rk s
R e c D e p a rt m e n t/
-1
P lu m b in g M o d e l_
O p ti o n O n e
R e v it
B
IM
.r v t
F101-N
FIRE PROTECTION - 1ST
AND 2ND FLOOR PLANS -
NORTH BUILDING
40-24105
W A
R E
H O
U S
E C
O N
V E
R T
T O
P A
R K
S
R E
C D
E P
T
C
IT
Y O
F F
O R
T M
Y E
R S
06/19/2025
PERMIT DOCUMENTS
M
IC
H
IH
A
N A
V E
N U
E F
O R
T M
Y E
R S
F
L O
R
ID
A
1/4" = 1'-0"1 FIRST FLOOR NORTH BUILDING
1/4" = 1'-0"2 SECOND FLOOR NORTH BUILDING
DIAMOND NOTES
1 EXISTING 8” SUPPLY MAIN FROM EXISTING BACKFLOW PREVENTER.
2 EXISTING 8” FIRE RISER AND SUPPLY MAIN.
3 EXISTING 2" MAIN DRAIN PIPING THROUGH EXTERIOR WALL.
4 REMOVE EXISTING PIPING TO HOSE RACK AND ASSOCIATED PIPING
BACK TO FITTING AT MAIN DRAIN PIPING AND PLUG FITTING.
5 CONTRACTOR SHALL REVISE BRANCH PIPING AS REQUIRED TO
ACCOMMODATE RENOVATION OF WAREHOUSE.
6 LIGHT HAZARD OCCUPANCY CLASSIFICATION:
MAXIMUM SPRINKLER SPACING 225 SQ. FT. PER SPRINKLER,
DENSITY GPM/SQ. FT. = 0.10 GPM OVER 1,500 SQ. FT.
HOSE STREAM = 100 GPM / DURATION 30 MINUTES
7 ORDINARY HAZARD GROUP I OCCUPANCY CLASSIFICATION:
MAXIMUM SPRINKLER SPACING 130 SQ. FT. PER SPRINKLER,
DENSITY GPM/SQ. FT. = 0.15 GPM OVER 1,500 SQ. FT.
HOSE STREAM = 250 GPM / DURATION 60-90 MINUTES
8 CLASS III, BACK-TO-BACK, ˃10’ TO ≤ 12’ STORAGE HIEGHT
CLASSIFICATION:
MAXIMUM SPRINKLER SPACING 130 SQ. FT. PER SPRINKLER,
DENSITY GPM/SQ. FT. = OH-2 DESIGN CURVE OVER 1,500 SQ. FT.
HOSE STREAM = 250 GPM / DURATION 90 MINUTES
9 PROVIDE INTERMEDIATE TEMPERATURE (200°) SPRINKLER.
10 CONTRACTOR SHALL COORDINATE PIPE ROUTING WITH
ELECTRICAL PANEL LOCATIONS OR SYSTEMS COMPONENTS. NO
PIPING SHALL BE ROUTED ABOVE ELECTRICAL PANELS OR
SYSTEMS COMPONENTS.
11 PROVIDE SPRINKLER BELOW DUCTWORK IN ACCORDANCE WITH
NFPA 13, 8.6.5.5.
12 EXISTING STAIR IS PROVIDED WITH SPRINKLER BELOW STAIR TO
REMAIN.
5 5
5 5
5 5 5 5
6 8 9
6 9
5 3 7 5
MPE JOB #:
ENG. BUS. No. EB-0005096
CERT. OF AUTH. No. 5096
PHONE (239) 332-1187
12437 Brantley Commons Fort Myers, FL 33907
TO
D GRIFF
No 67083P R
STATE OF
E
O F
E S
S
ION A L E N
G
IN
E E
R
NSECIL
F L O R I DA
THK
D I
PROJECT NO:
DATE:
PHASE:
ISSUED FOR
SEAL:
GRACE HEBERT CURTIS ARCHITECTS, LLC
SHEET NUMBER
© THIS SET OF DOCUMENTS INCLUSIVE OF
DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT
BE COPIED, SCANNED, NOR ELECTRONICALLY
DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT
THE EXPRESSED WRITTEN CONSENT OF GRACE
HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,
ELECTRONIC PLAN SERVICE (INTERNET PLAN
SERVICE), NOR REPRODUCTION COMPANY SHALL BE
PERMITTED TO POST THESE DOCUMENTS WITHOUT
THE EXPRESSED WRITTEN CONSENT OF THE
ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.
2024-118
/2
/2
:2
:1
P
M
A u to d e s k D o c s /W a re h o u s e
C o n v e rt t o
P a rk s
R e c D e p a rt m e n t/
-1
P lu m b in g M o d e l_
O p ti o n O n e
R e v it
B
IM
.r v t
F101-S
FIRE PROTECTION - 1ST
FLOOR PLAN - SOUTH
BUILDING
40-24105
W A
R E
H O
U S
E C
O N
V E
R T
T O
P A
R K
S
R E
C D
E P
T
C
IT
Y O
F F
O R
T M
Y E
R S
06/19/2025
PERMIT DOCUMENTS
M
IC
H
IH
A
N A
V E
N U
E F
O R
T M
Y E
R S
F
L O
R
ID
A
1/4" = 1'-0"1 FIRST FLOOR SOUTH BUILDING
GENERAL NOTES
1) REFER TO GENERAL NOTES FOR THIS DISCIPLINE.
2) REFER TO SPECIFICATIONS.
3) ALL SPRINKLERS ARE TO BE CENTER OF TILE UNLESS NOTED
OTHERWISE (2' X 2' TILES).
4) ALL PIPING 2" OR LARGER TO BE SCHEDULE 10 PIPE UNLESS
NOTED OTHERWISE.
5) ALL 1-1/2" OR SMALLER TO BE SCHEDULE 40 PIPE UNLESS
NOTED OTHERWISE.
6) ALL ARM OVERS ARE TO BE 1" SCHEDULE 40 PIPE UNLESS
NOTED OTHERWISE.
7) IT IS THE RESPONSIBILITY OF THE SPRINKLER CONTRACTOR
TO COORDINATE HIS WORK WITH ALL OTHER TRADES, AS
WELL AS THE ARCHITECTURAL AND STRUCTURAL FEATURES
OF THE BUILDING.
8) PROVIDE SPRINKLER COVERAGE ABOVE CEILING IN AREAS
NOT MEETING UNSPRINKLERED CONCEALED SPACE
REQUIREMENTS OF NFPA 13, 8.14.1.2.
9) PROVIDE AUXILIARY DRAIN IN PIPING WHERE AN EXCESS OF
5 GALLONS OF WATER IS TRAPPED, NFPA 13, 8.15.2.5.3.3.
COORDINATE DISCHARGE LOCATION WITH ARCHITECT.
10) CONTRACTOR SHALL CREATE A FULL SET OF COORDINATION
DRAWINGS WITH ALL DISCIPLINES PRIOR TO INSTALLATION
OF SPRINKLER SYSTEM TO INSURE AVAILABLE SPACE FOR
ALL DISCIPLINE COMPONENTS.
11) PROPOSED PIPE ROUTING IS SHOWN AS NEEDED FOR
COORDINATION. FINAL ROUTING OF PIPING SHALL BE
PROVIDED ON CONTRACTOR SHOP DRAWINGS.
DIAMOND NOTES
1 EXISTING SUPPLY MAIN FROM EXISTING BACKFLOW PREVENTER.
2 EXISTING FIRE RISER TO REMAIN.
3 CONTRACTOR SHALL REVISE BRANCH PIPING AS REQUIRED TO
ACCOMMODATE RENOVATION OF WAREHOUSE.
4 PROVIDE SPRINKLER CABINET AT FIRE RISER LOCATION.
5 LIGHT HAZARD OCCUPANCY CLASSIFICATION:
MAXIMUM SPRINKLER SPACING 225 SQ. FT. PER SPRINKLER,
DENSITY GPM/SQ. FT. = 0.10 GPM OVER 1,500 SQ. FT.
HOSE STREAM = 100 GPM / DURATION 30 MINUTES
6 ORDINARY HAZARD GROUP I OCCUPANCY CLASSIFICATION:
MAXIMUM SPRINKLER SPACING 130 SQ. FT. PER SPRINKLER,
DENSITY GPM/SQ. FT. = 0.15 GPM OVER 1,500 SQ. FT.
HOSE STREAM = 250 GPM / DURATION 60-90 MINUTES
7 CLASS III, BACK-TO-BACK, ˃10’ TO ≤ 12’ STORAGE HIEGHT
CLASSIFICATION:
MAXIMUM SPRINKLER SPACING 130 SQ. FT. PER SPRINKLER,
DENSITY GPM/SQ. FT. = OH-2 DESIGN CURVE OVER 1,500 SQ. FT.
HOSE STREAM = 250 GPM / DURATION 90 MINUTES
8 PROVIDE INTERMEDIATE TEMPERATURE (200°) SPRINKLER.
9 CONTRACTOR SHALL COORDINATE PIPE ROUTING WITH
ELECTRICAL PANEL LOCATIONS OR SYSTEMS COMPONENTS. NO
PIPING SHALL BE ROUTED ABOVE ELECTRICAL PANELS OR
SYSTEMS COMPONENTS.
10 PROVIDE SPRINKLER BELOW DUCTWORK IN ACCORDANCE WITH
NFPA 13, 8.6.5.5.
S
5 5
5 5
5 5 5 5
6 8 9
6 9
OFFICE 3
OFFICE 4
OFFICE 5
OFFICE 6
OFFICE 7
SMALL CONFERENCE
ROOM
LOUNGE ROOM
LARGE CONFERENCE
ROOM
SPECIAL EVENT
STORAGE/ MULTI-USE
WORK ROOM
MEN'S RESTROOM
CUSTODIAL
PUBLIC
WOMEN'S RESTROOM
CUBICLE 6
WOMEN'S BATHROOM
MEN'S BATHROOM
OFFICE 6
MDF ROOM
OPEN SPACE
EQUIPMENT TOOLS
CAGES
OFF. SUPPLIES
CUBICLE 4
CUBICLE 5
MAINTENANCE &
REPAIRS AREA
CUSTODIAL
MECH. ROOM
ELECTRIAL ROOM
PARKS & REC
WAREHOUSE
CLOSET
EXECUTIVE OFFICE
CUBICLE 3
CUBICLE 2
SENIOR ASSIST.
OFFICE 1
OFFICE 2
CUSTODIAL
MPE JOB #:
ENG. BUS. No. EB-0005096
CERT. OF AUTH. No. 5096
PHONE (239) 332-1187
12437 Brantley Commons Fort Myers, FL 33907
TO
D GRIFF
No 67083P R
STATE OF
E
O F
E S
S
ION A L E N
G
IN
E E
R
NSECIL
F L O R I DA
THK
D I
PROJECT NO:
DATE:
PHASE:
ISSUED FOR
SEAL:
GRACE HEBERT CURTIS ARCHITECTS, LLC
SHEET NUMBER
© THIS SET OF DOCUMENTS INCLUSIVE OF
DRAWINGS,SPECIFICATIONS, AND ADDENDA MAY NOT
BE COPIED, SCANNED, NOR ELECTRONICALLY
DISTRIBUTED OR USED FOR CONSTRUCTION WITHOUT
THE EXPRESSED WRITTEN CONSENT OF GRACE
HEBERT CURTIS ARCHITECTS, LLC. NO PLAN ROOM,
ELECTRONIC PLAN SERVICE (INTERNET PLAN
SERVICE), NOR REPRODUCTION COMPANY SHALL BE
PERMITTED TO POST THESE DOCUMENTS WITHOUT
THE EXPRESSED WRITTEN CONSENT OF THE
ARCHITECT, GRACE HEBERT CURTIS ARCHITECTS, LLC.
2024-118
/2
/2
:2
:0
P
M
A u to d e s k D o c s /W a re h o u s e
C o n v e rt t o
P a rk s
R e c D e p a rt m e n t/
-1
P lu m b in g M o d e l_ O p ti o n
T w o
R e v it
B
IM
.r v t
F101-S-2
FIRE PROTECTION - 1ST
FLOOR PLAN - SOUTH
BUILDING - ALTERNATE
40-24105
W A
R E
H O
U S
E C
O N
V E
R T
T O
P A
R K
S
R E
C D
E P
T
C
IT
Y O
F F
O R
T M
Y E
R S
06/19/2025
PERMIT DOCUMENTS
M
IC
H
IH
A
N A
V E
N U
E F
O R
T M
Y E
R S
F
L O
R
ID
A
1/4" = 1'-0"1 FIRST FLOOR SOUTH BUILDING
GENERAL NOTES
1) REFER TO GENERAL NOTES FOR THIS DISCIPLINE.
2) REFER TO SPECIFICATIONS.
3) ALL SPRINKLERS ARE TO BE CENTER OF TILE UNLESS NOTED
OTHERWISE (2' X 2' TILES).
4) ALL PIPING 2" OR LARGER TO BE SCHEDULE 10 PIPE UNLESS
NOTED OTHERWISE.
5) ALL 1-1/2" OR SMALLER TO BE SCHEDULE 40 PIPE UNLESS
NOTED OTHERWISE.
6) ALL ARM OVERS ARE TO BE 1" SCHEDULE 40 PIPE UNLESS
NOTED OTHERWISE.
7) IT IS THE RESPONSIBILITY OF THE SPRINKLER CONTRACTOR
TO COORDINATE HIS WORK WITH ALL OTHER TRADES, AS
WELL AS THE ARCHITECTURAL AND STRUCTURAL FEATURES
OF THE BUILDING.
8) PROVIDE SPRINKLER COVERAGE ABOVE CEILING IN AREAS
NOT MEETING UNSPRINKLERED CONCEALED SPACE
REQUIREMENTS OF NFPA 13, 8.14.1.2.
9) PROVIDE AUXILIARY DRAIN IN PIPING WHERE AN EXCESS OF
5 GALLONS OF WATER IS TRAPPED, NFPA 13, 8.15.2.5.3.3.
COORDINATE DISCHARGE LOCATION WITH ARCHITECT.
10) CONTRACTOR SHALL CREATE A FULL SET OF COORDINATION
DRAWINGS WITH ALL DISCIPLINES PRIOR TO INSTALLATION
OF SPRINKLER SYSTEM TO INSURE AVAILABLE SPACE FOR
ALL DISCIPLINE COMPONENTS.
11) PROPOSED PIPE ROUTING IS SHOWN AS NEEDED FOR
COORDINATION. FINAL ROUTING OF PIPING SHALL BE
PROVIDED ON CONTRACTOR SHOP DRAWINGS.
DIAMOND NOTES
1 EXISTING SUPPLY MAIN FROM EXISTING BACKFLOW PREVENTER.
2 EXISTING FIRE RISER TO REMAIN.
3 CONTRACTOR SHALL REVISE BRANCH PIPING AS REQUIRED TO
ACCOMMODATE RENOVATION OF WAREHOUSE.
4 PROVIDE SPRINKLER CABINET AT FIRE RISER LOCATION.
5 LIGHT HAZARD OCCUPANCY CLASSIFICATION:
MAXIMUM SPRINKLER SPACING 225 SQ. FT. PER SPRINKLER,
DENSITY GPM/SQ. FT. = 0.10 GPM OVER 1,500 SQ. FT.
HOSE STREAM = 100 GPM / DURATION 30 MINUTES
6 ORDINARY HAZARD GROUP I OCCUPANCY CLASSIFICATION:
MAXIMUM SPRINKLER SPACING 130 SQ. FT. PER SPRINKLER,
DENSITY GPM/SQ. FT. = 0.15 GPM OVER 1,500 SQ. FT.
HOSE STREAM = 250 GPM / DURATION 60-90 MINUTES
7 CLASS III, BACK-TO-BACK, ˃10’ TO ≤ 12’ STORAGE HIEGHT
CLASSIFICATION:
MAXIMUM SPRINKLER SPACING 130 SQ. FT. PER SPRINKLER,
DENSITY GPM/SQ. FT. = OH-2 DESIGN CURVE OVER 1,500 SQ. FT.
HOSE STREAM = 250 GPM / DURATION 90 MINUTES
8 PROVIDE INTERMEDIATE TEMPERATURE (200°) SPRINKLER.
9 CONTRACTOR SHALL COORDINATE PIPE ROUTING WITH
ELECTRICAL PANEL LOCATIONS OR SYSTEMS COMPONENTS. NO
PIPING SHALL BE ROUTED ABOVE ELECTRICAL PANELS OR
SYSTEMS COMPONENTS.
10 PROVIDE SPRINKLER BELOW DUCTWORK IN ACCORDANCE WITH
NFPA 13, 8.6.5.5.
| 2024-118 - Plumbing Model_Option One - Revit 2024 - BIM360 - Sheet - F001 - GENERAL NOTES AND LEGENDS - FIRE PROTECTION |
| 2024-118 - Plumbing Model_Option One - Revit 2024 - BIM360 - Sheet - F101-N - FIRE PROTECTION - 1ST AND 2ND FLOOR PLANS - NORTH BUILDING |
| 2024-118 - Plumbing Model_Option One - Revit 2024 - BIM360 - Sheet - F101-S - FIRE PROTECTION - 1ST FLOOR PLAN - SOUTH BUILDING |
| 2024-118 - Plumbing Model_Option Two - Revit 2024 - BIM360 - Sheet - F101-S-2 - FIRE PROTECTION - 1ST FLOOR PLAN - SOUTH BUILDING - ALTERNATE |
| 2025-06-20T15:27:09-0400 | |
| Kevin T Griffith | |
| This item has been digitally signed and sealed by K. Todd Griffith using a digital signature. Printed copies of this document are not considered signed and sealed and the SHA authentication code must be verified on any copies. |
File details come from the government source that posted it. Updated .