20220818 Mitchell SP South TS Replace SPEC 2 of 2.pdf
PDF 3 MB Posted
- Solicitation number
- RFQ 171 220000000521 4
- Issued by
- Wexford County, Burt CDP, Michigan
About this file
This is a comprehensive bidding and contract document for the Mitchell State Park South Toilet Shower Building Replacement project in Wexford County, Michigan, issued by the Department of Technology, Management and Budget (DTMB) State Facilities Administration. The project involves the complete replacement of a toilet and shower facility building, including site clearing, excavation, utility installation (water distribution, sanitary sewers, and storm sewers), concrete work, asphalt paving, roofing, interior finishes, electrical systems, mechanical systems, and plumbing fixtures. The project file number is 751/22029.JAN with official request number 125. Bids were due by 11/9/2022, and the contract must be awarded by the same date. The scope includes demolition of existing structures, site preparation with soil erosion and sedimentation control, installation of building systems, and site restoration. All work must comply with Michigan Department of Natural Resources regulations, including restrictions on weekend and holiday work without written permission and prohibition of work during September without authorization.
Pricing is based on prevailing wage rates established by the State of Michigan Wage and Hour Division, with rates varying by trade classification (carpenter, electrician, laborer, operating engineer, etc.) and including base hourly wages, overtime provisions, and fringe benefits. The contract requires compliance with all federal, state, and local codes, including OSHA standards, Michigan State Construction Code, and the International Mechanical and Plumbing Codes. The contractor must obtain all necessary permits and is responsible for hazardous materials management, asbestos abatement if required, and waste management including recycling and salvage. A Soil Erosion and Sedimentation Control Implementation Plan must be submitted for approval before earthwork begins. The project is funded by state resources through DTMB, and the contractor must provide comprehensive operating and maintenance manuals, as-built drawings, and one year of warranty coverage on all installed systems and materials.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Mitchell State Park File No. 751/22029.JAN South Toilet Shower Building Replacement Unit No. 5126
Bituminous Dampproofing 07.11.13 - 1 of 2
SECTION 07 11 13
BITUMINOUS DAMPPROOFING
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Bituminous dampproofing.
1.02 RELATED SECTIONS
A. Division 31 - Earthwork.
1.03 REFERENCES
A. ASTM D 41 - Standard Specification for Asphalt Primer Used in Roofing, Dampproofing, and Waterproofing; 2005.
B. ASTM D 449 - Standard Specification for Asphalt Used in Dampproofing and Waterproofing;
2003.
C. ASTM D 2822 - Standard Specification for Asphalt Roof Cement; 1991 (Reapproved 1997).
D. NRCA ML104 - The NRCA Roofing and Waterproofing; National Roofing Contractors Association; Fifth Edition.
1.04 SUBMITTALS
A. See Division 1 for submittal procedures.
B. Product Data: Provide properties of primer, bitumen, and mastics.
C. Manufacturer's Installation Instructions: Indicate special procedures and perimeter conditions requiring special attention.
1.05 QUALITY ASSURANCE
A. Perform work in accordance with NRCA Roofing and Waterproofing Manual.
B. Installer Qualifications: Company specializing in performing the work of this section with minimum three years experience.
1.06 ENVIRONMENTAL REQUIREMENTS
A. Maintain ambient temperatures above 40 degrees F for 24 hours before and during application until dampproofing has cured.
PART 2 PRODUCTS
2.01 MANUFACTURERS
A. W.R. Meadows, Inc; Product Spray-Mastic: www.wrmeadows.com.
B. Other Acceptable Manufacturers:
1. Karnak Chemical Corp; Product 83AF Fibered Dampproofing: www.karnakcorp.com.
2. Mar-Flex Systems, Inc; Product Cavity Wall and Foundation Coating: www.mar-flex.com.
3. Substitutions: See Section 01 60 00 - Product Requirements.
2.02 MATERIALS
Bituminous Dampproofing 07.11.13 - 2 of 2
A. Bitumen: ASTM D 449, Type I, asphalt, asbestos-free.
B. Primer: ASTM D 41, compatible with substrate.
C. Sealing Mastic: Asphalt roof cement, ASTM D 2822, Type I.
PART 3 EXECUTION
3.01 EXAMINATION
A. Verify existing conditions before starting work.
B. Verify substrate surfaces are durable, free of matter detrimental to adhesion or application of dampproofing system.
C. Verify items which penetrate surfaces to receive dampproofing are securely installed.
3.02 PREPARATION
A. Protect adjacent surfaces not designated to receive dampproofing.
B. Clean and prepare surfaces to receive dampproofing in accordance with manufacturer's instructions.
C. Do not apply dampproofing to surfaces unacceptable to manufacturer.
D. Apply mastic to seal penetrations, small cracks, or minor honeycomb in substrate.
3.03 APPLICATION
A. Prime surfaces in accordance with manufacturer's instructions.
B. Apply bitumen by spray application and in accordance with manufacturer's written instructions.
C. Apply bitumen at a temperature limited by equiviscous temperature (EVT) plus or minus 25 degrees F; do not exceed finish blowing temperature for four hours.
D. Apply from 2 inches below finish grade elevation down to top of footings.
E. Seal items projecting through dampproofing surface with mastic. Seal watertight.
F. Immediately backfill against dampproofing to protect from damage.
3.04 SCHEDULE
A. Foundation Wall: Unexcavated or backfilled both sides (locations without basement or pipe trench): Two coatings of asphalt dampproofing.
END OF SECTION 07 11 13
Dampproofing & Waterproofing 07 11 50 - 1 of 2
SECTION 07 11 50
DAMPPROOFING & WATERPROOFING
PART 1 - GENERAL
1.1 SUMMARY
A. This section includes cold fluid applied (CFA) dampproofing.
B. This section includes application of cold fluid applied (CFA) waterproofing.
1.2 RELATED SECTIONS
A. 04 81 00 Unit Masonry Assemblies
1.3 SUBMITTALS
A. Product Data: For each product indicated.
PART 2 - PRODUCTS
2.1 MONOLITHIC DAMPPROOFING
A. Odor Elimination: For interior and concealed-in-wall uses other than exterior face of inner wythe of cavity walls, provide dampproofing material warranted by manufacturer to be substantially odor free after drying for 24 hours under normal conditions.
B. Cold Fluid Applied (CFA) Dampproofing: For intended purpose as shown on the drawings use products from one of the following manufacturers:
1. Basis of design is Perm-A-Barrier from Grace Construction Products:
a. Owens Corning; Trumbull Division.
b. Henry
c. Grace Construction Products
d. Sonneborn, Div. of ChemRex, Inc.
e. W.R. Meadows
C. Block filler and Primer: as recommended by manufacturer.
PART 3 - EXECUTION
3.1 APPLICATION, GENERAL
A. Clean substrates of projections and substances detrimental to work; fill voids, seal joints, and apply bond breakers if any, as recommended by prime material manufacturer.
Dampproofing & Waterproofing 07 11 50 - 2 of 2
B. Apply dampproofing to masonry and foundation walls from finished-grade line to top of wall.
Damproofing to be used in areas with-out basements. At basement areas, use waterproofing only.
1. Extend 12 inches (300 mm) onto intersecting walls and footings, but do not extend onto surfaces exposed to view when Project is completed.
2. Install flashings and corner protection stripping at internal and external corners, changes in plane, construction joints, cracks, and where shown as "reinforced," by embedding an 8-inch- (200-mm-) wide strip of asphalt-coated glass fabric in a heavy coat of dampproofing. Dampproofing coat required for embedding fabric is in addition to other coats required.
C. Apply dampproofing to provide continuous plane of protection on exterior face of inner wythe of exterior masonry cavity walls.
D. Apply dampproofing to provide continuous plane of protection on cavity face of above grade, exterior walls.
E. Apply waterproofing to masonry and foundation walls below finished-grade line to footing, extend over top of footing, and down a minimum of 6 inches (150 mm) over outside face of footing. At basement areas, use waterproofing only.
3.2 INSTALLATION OF PROTECTION COURSE
A. Where indicated, install protection course over completed-and-cured waterproofing. Comply with waterproofing material manufacturer's written recommendations for attaching protection course. Support protection course with spot application of trowel-grade mastic where not otherwise indicated.
3.3 SCHEDULE
A. Dampproofing: Apply at exterior face of inner wythe of exterior masonry cavity walls.
B. Waterproofing: Apply at exterior side of below grade foundations walls in locations of excavated below grade space within building (such as basement or pipe trench).
END OF SECTION 07 11 50
Self-Adhering Sheet Waterproofing 07.13.26 - 1 of 3
SECTION 07 13 26
SELF-ADHERING SHEET WATERPROOFING
A. Self-adhering membrane as a roof membrane and coping underlayment.
1.02 RELATED SECTIONS
A. Section 06 10 00 – Rough Carpentry: Wood nailers and curbs.
B. Section 07 62 00 – Sheet Metal Flashing and Trim
A. D412 Standard Test Methods for Vulcanized Rubber and Elastomeric Tension
B. D461 Standard Test Methods for Felt
C. D903 Test Methods for Peel or Stripping Strength of Adhesive Bonds
D. D1970 Standard Specification for Self-Adhering Polymer Modified Bituminous Sheet Materials
Used as Steep Roofing Underlayment for Ice Dam Protection
E. D3767 Standard Practice for Rubber—Measurement of Dimensions
F. E96 Standard Test Methods for Water Vapor Transmission
G. Architectural Sheet Metal Manual (SMACNA) - Sheet Metal and Air Conditioning Contractor's
National Association; 2003.
H. UL (RMSD) - Roofing Materials and Systems Directory; Underwriters Laboratories Inc.; current edition.
1.04 SUBMITTALS
A. See Division 1 for submittal procedures.
B. Product Data: Provide data indicating membrane materials..
C. Shop Drawings: Indicate joint or termination detail conditions and conditions of interface with other materials.
D. Manufacturer's Installation Instructions: Indicate membrane seaming precautions and perimeter conditions requiring special attention.
E. Manufacturer's Certificate: Certify that products meet or exceed specified requirements.
F. Manufacturer's Field Reports: Indicate procedures followed, ambient temperatures, humidity, wind velocity during application, and supplementary instructions given.
G. Warranty: Submit manufacturer warranty and ensure forms have been completed in Owner's name and registered with manufacturer.
1.05 QUALITY ASSURANCE
Self-Adhering Sheet Waterproofing 07.13.26 - 2 of 3
A. Perform work in accordance with NRCA Roofing and Waterproofing Manual and manufacturer's instructions.
B. Manufacturer Qualifications: Company specializing in manufacturing the products specified in this section with minimum three years of documented experience.
C. Applicator Qualifications: Company specializing in performing the work of this section with minimum three years experience and approved by manufacturer.
1.06 DELIVERY, STORAGE, AND PROTECTION
A. Deliver products in manufacturer's original containers, dry, undamaged, with seals and labels intact.
B. Store products in weather protected environment, clear of ground and moisture.
C. Protect foam insulation from direct exposure to sunlight.
1.07 PROJECT CONDITIONS
A. Coordinate the work with installation of associated counterflashings and roof materials installed by other sections as the work of this section proceeds.
1.08 ENVIRONMENTAL REQUIREMENTS
A. Do not apply membrane during unsuitable weather.
B. Do not apply roofing membrane when ambient temperature is below 40 degrees F or above 90 degrees F.
C. Do not apply roofing membrane to damp or frozen deck surface or when precipitation is expected or occurring.
D. Do not expose materials vulnerable to water or sun damage in quantities greater than can be weatherproofed the same day.
1.09 WARRANTY
A. See Division 1 for Closeout Submittals and warranty requirements.
B. Correct defective Work within a one year period after Date of Substantial Completion.
A. Self-adhering membrane materials:
1. W.R. Grace & Co.: www.graceconstruction.com.
2. Substitutions: See Section 01 16 00 – Product Requirements
2.02 ROOFING MEMBRANE AND ASSOCIATED MATERIALS
A. Membrane: A cold-applied, self-adhering membrane composed of a high density, cross laminated polyethylene film coated on one side with a layer of rubberized asphalt adhesive.
An embossed, slip resistant surface is provided on the polyethylene. The membrane is interwound with a disposable silicone coated release sheet. Membrane shall conform to the physical properties as listed in the chart below:
Property Value Test Method
Self-Adhering Sheet Waterproofing 07.13.26 - 3 of 3
Color Gray-black Thickness, membrane 40 mil (1.02 mm) ASTM D3767 procedure A Tensile strength, membrane 250 psi (1720 kN/m2) ASTM D412 (Die C modified) Elongation, membrane 250% ASTM D412 (Die C modified) Low temperature flexibility Unaffected @ -20°F (-29°C) ASTM D1970 Adhesion to plywood 3.0 lbs/in. width (525 N/m) ASTM D903 Permeance (max) 0.05 Perms (2.9 ng/m2s Pa) ASTM E96 Material weight installed (max) 0.3 lb/ft2 (1.3 kg/m2) ASTM D461
2.03 ACCESSORIES
A. Perm-A-Barrier®WB Primer.
A. Verify that surfaces and site conditions are ready to receive work.
B. Verify deck is supported and secure.
C. Verify deck is clean and smooth, flat, free of depressions, waves, or projections, properly sloped and suitable for installation of roof system.
D. Verify deck surfaces are dry and free of snow or ice.
E. Verify that roof openings, curbs, and penetrations through roof are solidly set, and nailing strips are in place.
A. Install the membrane directly on a clean, dry, continuous structural deck. Some suitable deck materials include plywood, wood composition, wood plank, metal, concrete, or gypsum sheathing. Remove dust, dirt, loose nails, and old roofing materials. Protrusions from the deck area must be removed. Decks shall have no voids, damaged, or unsupported areas. Repair deck areas before installing the membrane.
B. Prime concrete, masonry surfaces and DensDeck® with Perm-A-BarrierWB Primer at a rate of
250–350 ft2/gal (6–8 m2/L). Prime wood composition and gypsum sheathing with Perm-A BarrierWB Primer if adhesion is found to be marginal. (Refer to Technical Letter 12, Use on Oriented Strand Board (OSB) Roof Sheathing.) Apply at same rate.
C. Priming is not required for other suitable surfaces provided that they are clean and dry.
3.03 MEMBRANE INSTALLATION
A. Install in strict accordance with manufacturer’s printed application procedures, precautions, and limitations.
3.04 FIELD QUALITY CONTROL
A. See Division 1 - Quality Requirements, for general requirements for field quality control and inspection.
3.05 PROTECTION OF FINISHED WORK
A. Protect installed roofing and flashings from construction operations.
B. Where traffic must continue over finished roof membrane, protect surfaces using durable materials.
3.06 SCHEDULE
A. As required in manufacturers standard installation details.
END OF SECTION 07 13 26
Board and Batt Insulation 07.21.00 - 1 of 4
SECTION 07 21 00
BOARD AND BATT INSULATION
A. Board insulation at perimeter foundation wall and underside of floor slabs.
B. Cavity Wall Insulation.
C. Batt insulation in exterior wall construction.
D. Batt insulation for filling perimeter window and door shim spaces and crevices in exterior wall and roof.
A. Section 04 21 00 – Veneer Masonry Units.
B. Section 04 72 00 – Cast Stone
C. Section 04 80 10 - Unit Masonry Assemblies.
A. ASTM C 578 - Standard Specification for Rigid, Cellular Polystyrene Thermal Insulation; 2004a.
B. ASTM C 665 - Standard Specification for Mineral-Fiber Blanket Thermal Insulation for Light Frame Construction and Manufactured Housing; 2001.
C. ASTM E 84 - Standard Test Method for Surface Burning Characteristics of Building Materials;
2005.
D. ASTM E 136 - Standard Test Method for Behavior of Materials in a Vertical Tube Furnace At
750 Degrees C; 2004.
1.04 SUBMITTALS
A. See Section 01 30 00 - Administrative Requirements, for submittal procedures.
B. Product Data: Provide data on product characteristics.
C. Manufacturer's Installation Instructions: Include information on special environmental conditions required for installation and installation techniques.
D. Manufacturer's Certificate: Certify that products meet or exceed specified requirements.
1.05 ENVIRONMENTAL REQUIREMENTS
A. Do not install insulation adhesives when temperature or weather conditions are detrimental to successful installation.
1.06 SEQUENCING
A. Sequence work to ensure fireproofing and firestop materials are in place before beginning work of this section.
2.01 BOARD INSULATION MATERIALS
Board and Batt Insulation 07.21.00 - 2 of 4
A. Extruded Polystyrene Board Insulation: ASTM C 578, Type IV; Extruded polystyrene board with natural skin surfaces; with the following characteristics:
1. Board Size: 48 x 96 inch.
2. Board Thickness: 2 inches.
3. Board Edges: Square.
4. Board Density: 1.6 lb/cu ft.
5. Water Absorption, maximum: 0.1 percent, volume.
6. Manufacturers:
a. Dow Chemical Co.; Product StyroFoam SE: www.dow.com.
b. Owens Corning Corp: www.owenscorning.com.
c. Pactiv Building Products: www.pactiv.com/green-guard/.
7. Substitutions: See Section 01 60 00 - Product Requirements.
2.02 CAVITY WALL INSULATION
A. Polyisocyanurate Board Insulation with Facers Both Sides: Rigid cellular foam, complying with ASTM C1289; Type I, aluminum foil both faces; Class 2, glass fiber-reinforced core.
1. Basis of Design:
a. Dow Chemical Company; THERMAX XARMOR™ ci: www.dowbuildingsolutions.com.
2. Flame Spread Index (FSI): Class A - 0 to 25, when tested in accordance with ASTM E84.
3. Smoke Developed Index (SDI): 450 or less, when tested in accordance with ASTM E84.
4. Front Facer: 4.0 mil gray acrylic coated embossed aluminum.
5. Back Facer: 1.25 mil embossed aluminum.
6. Board Size: 48 by 96 inch
7. Board Thickness: per drawings
8. Board Edges: Shiplap on 1.5” and thicker boards.
9. Substitutions: See Section 01 60 00 - Product Requirements.
2.02 BATT INSULATION MATERIALS
A. Batt Insulation: ASTM C 665; preformed glass fiber batt; friction fit, conforming to the following:
1. Surface Burning Characteristics: Flame spread index of 25 or less; smoke developed index of 450 or less, when tested in accordance with ASTM E 84.
2. Combustibility: Non-combustible when tested in accordance with ASTM E 136, except for facing, if any.
3. Provide insulation made without formaldehyde.
4. Thickness: As indicated on the drawings.
B. Sound Attenuation Blankets: ASTM C 665, Type I. Lightweight, unfaced fiber glass, conforming to the following:
1. Surface Burning Characteristics: Fire Hazard Classification (FHC) of 25/50 when tested in accordance with ASTM E-84.
2. Combustibility: Non-combustible.
3. Provide insulation made without formaldehyde.
4. Thickness: As indicated on the drawings.
C. Manufacturers:
1. CertainTeed Corporation: www.certainteed.com
2. Johns Manville Corporation: www.jm.com
3. Owens Corning Corp: www.owenscorning.com
D. Substitutions: See Section 01 60 00 - Product Requirements.
2.03 ACCESSORIES
A. Sheet Vapor Retarder: Clear polyethylene film, 4 mil thick.
B. Tape: Polyester self-adhering type, mesh reinforced, 2 inch wide.
Board and Batt Insulation 07.21.00 - 3 of 4
C. Insulation Fasteners: Impaling clip of unfinished steel with washer retainer and clips, to be adhered to surface to receive insulation, length to suit insulation thickness and substrate, capable of securely and rigidly fastening insulation in place.
D. Wire Mesh: Galvanized steel, knitted wire mesh.
E. Adhesive: Type recommended by insulation manufacturer for application.
A. Verify that substrate, adjacent materials, and insulation materials are dry and that substrates are ready to receive insulation and adhesive.
B. Verify substrate surfaces are flat, free of honeycomb, fins, irregularities, or materials or substances that may impede adhesive bond.
3.02 BOARD INSTALLATION AT FOUNDATION PERIMETER
A. Apply adhesive to back of boards:
1. Three continuous beads per board length.
2. Full bed 1/8 inch thick.
B. Install boards horizontally on foundation perimeter.
1. Place boards to maximize adhesive contact.
2. Butt edges and ends tightly to adjacent boards and to protrusions.
C. Extend boards over expansion joints, unbonded to foundation on one side of joint.
D. Cut and fit insulation tightly to protrusions or interruptions to the insulation plane.
3.03 BOARD INSTALLATION UNDER CONCRETE SLABS
A. Place insulation under slabs on grade after base for slab has been compacted.
B. Cut and fit insulation tightly to protrusions or interruptions to the insulation plane.
C. Prevent insulation from being displaced or damaged while placing vapor retarder and placing slab.
3.04 BATT INSTALLATION
A. Install insulation and vapor retarder in accordance with manufacturer's instructions.
B. Install in exterior wall spaces without gaps or voids. Do not compress insulation.
C. Trim insulation neatly to fit spaces. Insulate miscellaneous gaps and voids.
D. Fit insulation tightly in cavities and tightly to exterior side of mechanical and electrical services within the plane of the insulation.
E. Retain insulation batts in place with wire mesh secured to framing members.
F. Tape seal butt ends, lapped flanges, and tears or cuts in membrane.
G. At metal framing, place vapor retarder on warm side of insulation; lap and seal sheet retarder joints over member face.
H. Tape seal tears or cuts in vapor retarder.
Board and Batt Insulation 07.21.00 - 4 of 4
I. Extend vapor retarder tightly to full perimeter of adjacent window and door frames and other items interrupting the plane of the membrane. Tape seal in place.
A. Do not permit installed insulation to be damaged prior to its concealment.
3.06 SITE ENVIRONMENTAL PROCEDURES
A. Waste Management:
1. Coordinate with product manufacturer for take-back program if available. Set aside scrap to be returned to manufacturer for recycling.
END OF SECTION 07 21 00
Cornerstone Architects Weather Barrier 07.25.00 - 1 of 2
SECTION 07 25 00
WEATHER BARRIER
1.01 Summary
A. Includes but not limited to:
1. Furnish and install air barrier/weather resistant barrier over exterior of wall sheathing at all locations regardless of whether or not indicated on drawings to protect exterior sheathing and interior walls.
1.02 References:
A. American Society for Testing and Materials B. Technical Association of the Pulp and Paper Industry C. American Association of Textile Chemists and Colorists
1.03 Submittals
A. General: Submit each item in this Article according to the conditions of the Contract and
Division I Specifications Sections.
B. Product Data: Submit product specifications, technical data and installation instructions of manufacturer equaling or exceeding those specified.
1.04 Quality Assurance
A. Qualifications:
1. Installer with successful experience in the installation of air barrier/secondary weather resistant barriers.
B. Install job mock-up using specified air barrier/secondary weather resistant barrier with system of fastening and taping seams as per manufacturer’s instructions. Obtain architect’s approval of system for appearance and workmanship standard.
2.01 Manufacturers
A. Acceptable Manufacturer:
1. Grace (GCP Applied Technologies)
2. Prosocco
3. DuPont Weatherization Systems (www.tyvek.com).
4. Or Approved Equal
B. Substitutions: See Section 01 60 00 - Product Requirements
2.02 Materials
A. For locations where application will be concealed prior to manufacturer limit of UV exposure, Basis of Design: Grace VYCOR enV
1. Performance Characteristics
a. Per Grace Vycor enV Specifications
2. Sealing Tape/Fasteners
a. Per Grace Vycor enV Specifications
B. For rainscreen assemblies where application will be subject to long term UV exposure, Cornerstone Architects Weather Barrier 07.25.00 - 2 of 2
Basis of Design: Cat 5 Rain Screen from Prosocco
1. Performance Characteristics
a. Per Prosocco Cat 5 Rain Screen Specifications
2. Sealing Tape/Fasteners
a. Per Prosocco Cat 5 Rain Screen Specifications
C. Substitutions: See Section 01 60 00 - Product Requirements.
PART 3 - EXECUTION
3.01 Installation
A. Install Air Barrier over exterior side of exterior wall sheathing.
1 Install Air Barrier after sheathing is installed and before windows and doors are installed.
Install lower level barrier prior to upper layers to ensure proper shingling of layers.
2 Overlap Air Barrier at corners of building by a minimum of 12 inches.
3 Overlap Air Barrier vertical seams by a minimum of 6 inches.
4 Ensure barrier is plum and level with foundation, and unroll extending Air Barrier over window and door openings.
5 Attach Air Barrier to wood, insulated sheathing board or exterior gypsum with plastic cap nails every 12” to 18” on vertical stud line with wood stud framing, and screws with washers to metal stud framing. When attaching to masonry, use adhesive recommended by manufacturer.
6 Prepare window and door rough openings as follows:
a. Prepare each window rough opening by cutting a modified “I” pattern in the Air Barrier.
1. Horizontally cut Air Barrier along bottom of header.
2. Vertically cut Air Barrier down the center of window openings from the top of the window opening down to 2/3 of the way to the bottom of the window openings.
3. Diagonally cut Air Barrier from the bottom of the vertical cut to the left and right corners of opening.
4. Fold side and bottom flaps into window opening and fasten every 6 inches. Trim off excess.
b. Prepare each rough door opening by cutting a standard “I” pattern in the Air Barrier.
1. Horizontally cut Air Barrier along bottom of door frame header and along top of sill.
2. Vertically cut Air Barrier down the center of door openings from the top of the door opening (header) down to the bottom of the door opening (sill).
3. Fold side flaps inside around door openings and fasten every 6 inches. Trim off excess.
7 Tape all horizontal and vertical seam of Air Barrier with manufacturer recommended seam tape.
8 Seal all tears and cuts in Air Barrier with manufacturer recommended tear and cut tape.
END OF SECTION 07 25 00
Under-Slab Vapor Barrier 07.30.00 - 1 of 3
SECTION 07 30 00
UNDER-SLAB VAPOR BARRIER
PART 1 – GENERAL
1.1 SUMMARY
A. Products supplied under this section:
1. Vapor barrier and installation accessories for installation under concrete slabs.
B. Related sections:
1. Section 03 30 00 Cast-in-Place Concrete
2. Section 07 26 00 Vapor Retarders
1.2 REFERENCES
A. American Society for Testing and Materials (ASTM):
1. ASTM E1745- 11Standard Specification for Plastic Water Vapor Retarders Used in Contact with Soil or Granular Fill Under Concrete Slabs.
2. ASTM E1643- 11Selection, Design, Installation, and Inspection of Water Vapor
Retarders Used in Contact with Earth or Granular Fill Under Concrete Slabs.
B. Technical Reference - American Concrete Institute (ACI):
1. ACI 302.2R-06 Guide for Concrete Slabs that Receive Moisture-Sensitive
Flooring Materials.
2. ACI 302.1R-15 Guide to Concrete Floor and Slab Construction.
1.3 SUBMITTALS
A. Quality control/assurance:
1. Summary of test results per paragraph 9.3 of ASTM E1745.
2. Manufacturer’s samples and literature.
3. Manufacturer’s installation instructions for placement, seaming, penetration prevention and repair, and perimeter seal per ASTM E1643.
4. All mandatory ASTM E1745 testing must be performed on a single production roll per ASTM E1745 Section 8.1.
PART 2 – PRODUCTS
2.1 MATERIALS
A. Vapor barrier shall have all of the following qualities:
1. Maintain permeance of less than 0.01 Perms [grains/(ft2 · hr · inHg)] as tested in accordance with mandatory conditioning tests per ASTM E1745 Section 7.1 (7.1.1-7.1.5).
2. Other performance criteria:
a. Strength: ASTM E1745 Class A.
b. Thickness: 15 mils minimum
3. Provide third party documentation that all testing was performed on a single production roll per ASTM E1745 Section 8.1
B. Provide vapor barrier products by one of the Following:
Under-Slab Vapor Barrier 07.30.00 - 2 of 3
1. Basis of Design: Stego Wrap Vapor Barrier (15-mil) by Stego Industries LLC.,
(877) 464-7834 www.stegoindustries.com.
2. Grace PrePrufe Pre-Applied Sheet Membrane Waterproofing by GCP Applied Technologies Inc., https://gcpat.com/en
3. Substitutions: See Section 01 60 00 - Product Requirements
2.2 ACCESSORIES
A. Seams:
1. Stego Tape by Stego Industries LLC, (877) 464-7834 www.stegoindustries.com.
B. Sealing Penetrations of Vapor barrier:
1. Stego Mastic by Stego Industries LLC, (877) 464-7834 www.stegoindustries.com.
2. Stego Tape by Stego Industries LLC, (877) 464-7834 www.stegoindustries.com.
C. Perimeter/edge seal:
1. Stego Crete Claw by Stego Industries LLC, (877) 464-7834 www.stegoindustries.com.
2. Stego Term Bar by Stego Industries LLC, (877) 464-7834 www.stegoindustries.com.
3. StegoTack Tape (double-sided sealant tape) by Stego Industries LLC, (877) 464-
7834 www.stegoindustries.com.
D. Penetration Prevention:
1. Beast Foot by Stego Industries LLC, (877) 464-7834 www.stegoindustries.com.
E. Vapor Barrier-Safe Screed System
1. Beast Screed by Stego Industries, LLC, (877) 464-7834 www.stegoindustries.com.
PART 3 – EXECUTION
3.1 PREPARATION
A. The installer shall examine conditions of substrates and other conditions under which this work is to be performed and notify the Contractor, in writing, of circumstances detrimental to the proper completion of the work. Do not proceed with work until unsatisfactory conditions are corrected.
B. Ensure that subsoil is reviewed by Architect or Geotechnical Engineer.
1. Level and compact base material.
3.2 INSTALLATION
A. Install vapor barrier in accordance ASTM E1643.
1. Unroll vapor barrier with the longest dimension parallel with the direction of the concrete placement and face laps away from the expected direction of the placement whenever possible.
2. Extend vapor barrier to the perimeter of the slab. If practicable, terminate it at the top of the slab, otherwise (a) at a point acceptable to the structural engineer or
(b) where obstructed by impediments, such as dowels, waterstops, or any other site condition requiring early termination of the vapor barrier. At the point of termination, seal vapor barrier to the foundation wall, grade beam or slab itself.
Under-Slab Vapor Barrier 07.30.00 - 3 of 3
a. Seal vapor barrier to the entire slab perimeter using Stego Crete Claw, per manufacturer's instructions.
b. Seal vapor barrier to the entire perimeter wall or footing/grade beam with double sided StegoTack Tape, or both Stego Term Bar and StegoTack Tape, per manufacturer’s instructions. Ensure the concrete is clean and dry prior to adhering tape.
3. Overlap joints 6 inches and seal with manufacturer’s seam tape.
4. Apply seam tape/Crete Claw to a clean and dry vapor barrier.
5. Seal all penetrations (including pipes) per manufacturer’s instructions.
6. For interior forming applications, avoid the use of non-permanent stakes driven through vapor barrier. Use blunt-end and/or threaded nail stakes (screed pad posts) and insert them into Beast Foot. Ensure Beast Foot’s peel-and-stick adhesive base is fully adhered to the vapor barrier
7. If non-permanent stakes must be driven through vapor retarder, repair as recommended by vapor retarder manufacturer.
8. Use reinforcing bar supports with base sections that eliminate or minimize the potential for puncture of the vapor barrier.
9. Repair damaged areas with vapor barrier material of similar (or better) permeance, puncture and tensile.
10. For vapor barrier-safe concrete screeding applications, install Beast Screed (vapor barrier-safe screed system) per manufacturer’s instructions prior to placing concrete.
3.3 PROTECTION
A. Protect membrane in accordance with manufacturer’s recommendations until placement of concrete. Inspect for damage just prior to placement of concrete and make repairs in accordance with manufacturer’s recommendations.
END OF SECTION
Asphalt Shingles 07 31 00 - 1
SECTION 07 31 00
ASPHALT SHINGLES
PART 1
A Asphalt roofing shingles.
B Leak barrier and roof deck protection.
C Metal flashing associated with shingle roofing.
D Attic ventilation.
1.02 RELATED SECTIONS
A Section 06 10 00 - Rough Carpentry: Framing, wood decking, and roof sheathing.
B Section 07 62 00 - Flashing and Sheet Metal: Sheet metal flashing not associated with shingle roofing; gutters and downspouts.
1.03 REFERENCES American Society for Testing and Materials (ASTM) - Annual Book of ASTM Standards
1. ASTM A 653/A 653M - Standard Specification for Steel Sheet, Zinc Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process.
2. ASTM B 209 - Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate.
3. ASTM B 370 - Standard Specification for Copper Sheet and Strip for Building Construction.
4. ASTM D 2218 – Impact Resistance of Prepared Roof Covering Materials.
5. ASTM D 3018 - Standard Specification for Class A Asphalt Shingles Surfaced with Mineral Granules.
6. ASTM D 3161 - Standard Test Method for Wind-Resistance of Asphalt Shingles (Fan-Induced Method).
7. ASTM D 3462 – Standard Specification for Asphalt Shingles Made From Glass Felt and Surfaced with Mineral Granules.
8. ASTM D 4586 - Standard Specification for Asphalt Roof Cement, Asbestos-Free.
9. ASTM D 7158 - Standard Test Method for Wind-Resistance of Sealed Asphalt Shingles (Uplift Force/Uplift Resistance Method).
B Underwriters Laboratories (UL) - Roofing Systems and Materials Guide (TGFU R1306)
1. UL 790 - Tests for Fire Resistance of Roof Covering Materials.
2. UL 997 - Wind Resistance of Prepared Roof Covering Materials.
C Asphalt Roofing Manufacturers Association (ARMA)
D National Roofing Contractors Association (NRCA)
E U.S. Green Building Council (USGBC)
F ENERGY STAR
G Cool Roof Rating Council (CRRC)
1.04 DEFINITIONS
Asphalt Shingles 07 31 00 - 2
A Roofing Terminology: Refer to ASTM D1079 and the glossary of the National Roofing Contractors Association (NRCA) Roofing and Waterproofing Manual for definitions of roofing terms related to this section.
1.05 SUBMITTALS
A Submit copies of GAF product data sheets, detail drawings and samples for each type of roofing product.
1.06 QUALITY ASSURANCE
A Manufacturer Qualifications: Provide all primary roofing products, including shingles, underlayment, leak barrier, and ventilation, by a single manufacturer. Basis of Design for Self-Adhering Sheet Waterproofing is Grace Ice and Water Shield.
B Installer Qualifications: Installer must be approved for installation of all roofing products to be installed under this section.
1.07 REGULATORY REQUIREMENTS
A Provide a roofing system achieving an Underwriters Laboratories (UL) Class A fire classification.
B Install all roofing products in accordance with all federal, state and local building codes.
C All work shall be performed in a manner consistent with current OSHA guidelines.
1.08 PREINSTALLATION MEETING
A General: For this project, a pre-installation meeting is required.
B Timing: The meeting shall take place at the start of the roofing installation, no more than 2 weeks into the roofing project.
C Attendees: Meeting to be called for by manufacturer’s certified contractor. Meeting’s mandatory attendees shall include the certified contractor and the manufacturer’s representative. Non-mandatory attendees shall include the owner’s representative, architect or engineer’s representative, and the general contractor’s representative.
D Topics: Certified contractor and manufacturer’s representative shall review all pertinent requirements for the project, including but not limited to, scheduling, weather considerations, project duration, and requirements for the specified warranty.
1.09 DELIVERY, STORAGE, AND HANDLING
A Store all products in manufacturer's unopened, labeled packaging until they are ready for installation.
B Store products in a covered, ventilated area, at temperature not more than 110 degrees F (43 degrees C); do not store near steam pipes, radiators, or in direct sunlight.
C Store bundles on a flat surface. Maximum stacking height shall not exceed GAF’s recommendations. Store all rolls on end.
D Store and dispose of solvent-based materials in accordance with all federal, state and local regulations.
1.10 WEATHER CONDITIONS
A Proceed with work only when existing and forecasted weather conditions will permit work to be performed in accordance with GAF’s recommendations
1.11 WARRANTY
B Provide to the owner a GAF Materials Corporation Weather Stopper® System Plus Ltd Warranty, or approved equal.
Asphalt Shingles 07 31 00 - 3
A Basis of Design Manufacturer: GAF Materials Corporation , 1361 Alps Rd. Wayne NJ 07470. Tel: 1-973-628-3000.
B Approved Manufacturers:
1. CertainTeed, Valley Forge, Pennsylvania. 800-233-8990.
2. Tamko Building Products, Joplin, Missouri. 800-641-4691.
C Requests for substitutions will be considered in accordance with provisions of Section 01 60 00.
2.02 SHINGLES – Basis of Design
A Heavyweight, triple layer, granule surfaced, self sealing asphalt shingle with a strong fiberglass reinforced Micro Weave® core and StainGuard® protection, which prevents pronounced discoloration from blue-green algae through formulation/unique blends of granules. Dovetail cut tabs and bold shadow lines provide a slate appearance with a 7 ½” exposure. UL 790 Class A rated with UL 997 Wind Resistance Label; ASTM D 7158, Class H; ASTM D 3161, Type 1; ASTM D 3018, Type 1; ASTM D 3462; CSA 123.5-98; Dade County Approved, Florida Building Code Approved, Texas Dept of Insurance Approved, ICC Report Approval. Glenwood® Lifetime Designer Shingles, by GAF.
1. Color: As selected by Architect from manufacturers’ full range.
2.03 HIP AND RIDGE SHINGLES
A Distinctive vented hip and ridge cap shingle complementing the color of selected roof shingle. Each bundle covers approx. 20 lineal feet (6.10m) with a 9 ¼ inch (235mm) exposure. Vented RidgeCrest™ Venting Ridge Cap Shingles by GAF.
2.04 STARTER STRIP
A Self sealing starter shingle designed for all roof shingles. Each bundle covers approx.
120 lineal feet (36.58m). ProStart™ Starter Strip by GAF.
2.05 LEAK BARRIER
A Ice and Water Shield: Provide an ice and water shield membrane. Products of W.R.
Grace Company, or approved equal, are to be utilized in accordance with the Manufacturers recommended installation procedures. Overlap each row a minimum of 4”. Provide two layers of ice and water shield in locations as required to accommodate existing roof conditions.
2.06 SHINGLE UNDERLAYMENT
A Premium, water repellant, breather type non-asphaltic underlayment. UV stabilized polypropylene construction. Meets or exceeds ASTM D226 and D4869. Approved by Dade Country, Florida Building Code, and ICC. Each roll contains approximately 10 squares (1003 sq. ft.) of material and is 54 in. x 223 ft. Deck-Armor™ Premium Breathable Roof Deck Protection, by GAF®.
2.07 ROOFING CEMENT
A Asphalt Plastic Roofing Cement meeting the requirements of ASTM D 4586, Type I or
II.
2.08 VENTILATION
Asphalt Shingles 07 31 00 - 4
A Rigde Vent: Plastic ridge ventilator designed to allow the passage of hot air from attics while prohibiting snow infiltration. For use in conjunction with eave/ soffit intake ventilation products. Provide Net Free Ventilation Area per lineal foot as indicated on drawings. Provide ridge vent as recommended by manufacturer equal to Coravent V- 600T. Provide shingle-over installation as recommended by roof manufacturer.
B Sidewall Vent: Plastic ventilator designed to allow the passage of air into attic spaces to facilitate exhaust of hot air. For use in conjunction with eave/soffit intake ventilation products. Provides Net Free Ventilation Area per lineal foot as indicated on drawings.
Provide Coravent S-400 Strip Vent or equal.
2.09 ROOF ACCESSORIES
A Exterior acrylic rust resistant aerosol roof accessory paint. Each 6 oz can is available in boxes of 6 and in a wide variety of colors to compliment the roof. Roof Accessory Paint by Shingle Manufacturer.
B Nails: Standard round wire, zinc-coated steel or aluminum; 10 to 12 gauge, smooth, barbed or deformed shank, with heads 3/8 inch (9mm) to 7/16 inch (11mm) in diameter.
Length must be sufficient to penetrate into solid wood at least 3/4 inch (19mm) or through plywood or oriented strand board by at least 1/8 inch (3.18mm).
2.10 WARRANTY
A Provide manufactures standard lifetime warranty.
A Do not begin installation until the roof deck has been properly prepared.
B If roof deck preparation is the responsibility of another installer, notify the architect or building owner of unsatisfactory preparation before proceeding.
3.02 PREPARATION Remove existing roofing down to the roof deck at area shown on plans.
A At existing roof locations, inspect for damage and / or remaining life of shingles.
Notify architect, building owner, and construction manager of recommendation for existing roof singles.
B After initial inspection of existing roofs and after all necessary parties have been consulted and agree to move forward with a new roof, remove all existing roofing down to the roof deck. If necessary parties do not agree to move forward with new roofing at existing roof locations, protect all shingles in place so that damage does not occur during the construction process.
C Verify that the deck is dry, sound, clean and smooth. It shall be free of any depressions, waves, and projections. Cover with sheet metal, all holes over 1 inch (25mm) in diameter, cracks over 1/2 inch (12mm) in width, loose knots and excessively resinous areas.
D Replace damaged deck with new materials.
E Clean deck surfaces thoroughly prior to installation of eaves protection membrane and underlayment.
F Provide for air tranfser between attic space of existing roof and new roof by cutting in openings. Existing and new attic space to act as one space for ventilation. See drawings.
3.03 SUBSTRATE INSTALLATION
A The structural roof deck shown in the plans shall be smooth and level and free of water or debris before the nail base insulation is installed. Apply vapor retarder if required.
Asphalt Shingles 07 31 00 - 5
B Installation shall follow the GAF written installation instructions.
C Fasten with ThermaCal® Fasteners to the supporting roof deck shown in the plans.
D Protect nail base insulation work from exposure to moisture damage and deterioration, primarily by prompt installation of the roofing, sheet metal and waterproofing work.
3.04 INSTALLATION OF UNDERLAYMENTS General:
1. Install using methods recommended by Shingle Manufacterer, in accordance with local building codes. When local codes and application instructions are in conflict, the more stringent requirements shall take precedence.
B Eaves:
1. Install eaves edge metal flashing tight with fascia boards; lap joints 2 inches and seal with plastic cement or high quality urethane sealant; nail at the top of the flange.
2. Install ice and water shield/GAF leak barrier up the slope from eaves edge a full 36 inches or to at least 24 inches beyond the interior “warm wall”. Lap ends 6 inches (152mm) and bond.
C Valleys:
1. Install eaves protection membrane at least 36 (914mm) inches wide and centered on the valley. Lap ends 6 inches (152mm) and seal.
2. Where valleys are indicated to be "open valleys", install metal flashing over leak barrier before roof deck protection is installed; DO NOT nail through the flashing.
Secure the flashing by nailing at 18 inches on center just beyond edge of flashing so that nail heads hold down the edge.
D Hips and Ridges:
1. Install leak barrier along entire lengths. If ridge vents are to be installed, position the leak barrier so that the ridge slots will not be covered.
E Roof Deck:
1. Install one layer of roof deck protection over the entire area not protected by leak barrier at the eaves or valley. Install sheets horizontally so water sheds and nail in place.
2. On roofs sloped at more than 4 in 12, lap horizontal edges at least 2 inches and at least 2 inches over eaves protection membrane.
3. On roofs sloped between 2 in 12 and 4 in 12, lap horizontal edges at least 19 inches and at least 19 inches over eaves protection membrane. Apply one layer of leak barrier over entire roof.
4. Lap ends at least 4 inches. Stagger end laps of each layer at least 36 inches.
5. Lap roof deck protection over leak barrier in valley at least 6 inches.
F Penetrations:
1. Vent pipes: Install a 24 inch square piece of eaves protection membrane lapping over roof deck underlayment; seal tightly to pipe.
2. Vertical walls: Install eaves protection membrane extending at least 6 inches up the wall and 12 inches on to the roof surface. Lap the membrane over the roof deck underlayment.
3. Rake Edges: Install metal edge flashing over eaves protection membrane and roof
Asphalt Shingles 07 31 00 - 6 deck underlayment; set tight to rake boards; lap joints at least 2 inches and seal with plastic cement; secure with nails.
3.05 INSTALLATION OF SHINGLES
A General:
1. Install in accordance with Shingle Manufacturer's instructions and local building codes. When local codes and application instructions are in conflict, the more stringent requirements shall take precedence.
2. Minimize breakage of shingles by avoiding dropping bundles on edge, by separating shingles carefully (not by "breaking" over ridge or bundles), and by taking extra precautions in temperatures below 40 degrees F (4 degrees C).
3. Handle carefully in hot weather to avoid scuffing the surfacing, or damaging the shingle edges.
B Placement and Nailing: For maximum wind resistance along rakes & eaves, install any starter strip containing sealant or cement shingles to underlayment and each other in a 4" (102mm) width of asphalt plastic roof cement.
2. Secure with 4, 5, or 6 nails per shingle per Shingle Manufacterer’s instructions or local codes.
3. Placement of nails varies based on the type of shingle specified. Consult the application instructions for the specified shingle for details.
4. Nails must be driven flush with the shingle surface. Do not overdrive or under drive the nails.
5. Shingle offset varies based on the type of shingle specified. Consult the application instructions for the specified shingle for details.
C Placement and Nailing:
1. Beginning with the starter strip, trim shingles so that they “nest” within the shingle located beneath it. This procedure will yield a first course that is typically 3” (76mm) to 4” (102mm) rather than a fully exposed shingle.
2. For maximum wind resistance along rakes, install any starter strip containing sealant or cement shingles to underlayment and each other in a 4" (102mm) width of asphalt plastic roof cement.
3. Laterally, offset the new shingles from the existing keyways, to avoid waves or depressions caused by excessive dips in the roofing materials.
4. Using the bottom of the tab on existing shingles, align subsequent courses.
5. *Note: DO NOT install standard sized shingles (5” exposure) over metric (5 5/8” exposure) shingles, as it will overexpose the shingles and reveal the nails. Use standard alignment methods to assure proper shingle placement.
6. Secure with 4, 5, or 6 nails per shingle per Shingle Manufacterer’s instructions or local codes.
7. Placement of nails varies based on the type of shingle specified. Consult the application instructions for the specified shingle for details.
8. Nails must be driven flush with the shingle surface. Do not overdrive or under drive the nails.
9. Shingle offset varies based on the type of shingle specified. Consult the application instructions for the specified shingle for details.
D Valleys: Install valleys using the "open valley" method:
Asphalt Shingles 07 31 00 - 7 a Snap diverging chalk lines on the metal flashing, starting at 3 inches (76mm) each side of top of valley, spreading at 1/8 inch per foot (9mm per meter) to the eaves.
b Run shingles to chalk line.
c Trim last shingle in each course to match the chalk line; do not trim shingles to less than 12 inches (305mm) wide.
d Apply a 2 inch (51mm) wide strip of plastic cement under ends of shingles, sealing them to the metal flashing.
E Penetrations
1. All Penetrations are to be flashed according to GAF, ARMA and NRCA application instructions and construction details.
3.06 INSTALLATION OF ATTIC VENTILATION
A General
1. Ventilation must meet or exceed current F.H.A., H.U.D. and local code requirements.
B Ridge / Soffit and hip ventilation
1. Install ridge vent along the entire length of ridges:
2. Cut continuous vent slots through the sheathing, stopping 6 inches from each end of the ridge.
3. On roofs without ridge board, make a slot 1 inch wide, on either side of the peak (2 inch overall).
4. On roofs with ridge board, make two slots 1-3/4 inches wide, one on each side of the peak (3 ½ inch overall).
5. Install ridge vent material along the full length of the ridge, including uncut areas.
6. Butt ends of ridge vent material and join using roofing cement.
7. Install eaves vents in sufficient quantity to equal or exceed the ridge vent area.
3.07 PROTECTION
A Protect installed products from foot traffic until completion of the project.
B Any roof areas that are not completed by the end of the workday are to be protected from moisture and contaminants.
Standing Seam Metal Roof Panels 07 41 13 - Page 1 of 8
SECTION 07 41 13
STANDING SEAM METAL ROOF PANELS
PART 1 - GENERAL
1.1 SECTION INCLUDES
A. Standing seam metal roof panels, with related metal trim and accessories.
1.2 RELATED REQUIREMENTS
A. Division 06 Section "Sheathing" for sheathing substrate for metal roof panels.
B. Division 07 Section “Board and Batt Insulation”.
C. Division 07 Section "Air Barriers" for air barriers within roof assembly and adjacent to roof assembly.
D. Division 07 Section "Sheet Metal Flashing and Trim" for formed sheet metal copings, flashings, reglets, and roof drainage items in addition to items specified in this Section.
E. Division 07 Section "Joint Sealants" for field-applied joint sealants.
1.3 REFERENCES
A. American Architectural Manufacturer's Association (AAMA): www.aamanet.org:
1. AAMA 621 - Voluntary Specifications for High Performance Organic Coatings on Coil Coated Architectural Hot Dipped Galvanized (HDG) & Zinc-Aluminum Coated Steel Substrates.
2. AAMA 809.2 - Voluntary Specification Non-Drying Sealants.
B. American Society of Civil Engineers (ASCE): www.asce.org/codes-standards:
1. ASCE 7 - Minimum Design Loads for Buildings and Other Structures.
C. ASTM International (ASTM): www.astm.org:
1. ASTM A 653 - Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy- Coated (Galvannealed) by the Hot-Dip Process.
2. ASTM A 755 - Specification for Steel Sheet, Metallic Coated by the Hot-Dip Process and Prepainted by the Coil-Coating Process for Exterior Exposed Building Products.
3. ASTM A 792/A 792M - Standard Specification for Steel Sheet, 55 % Aluminum-Zinc Alloy-Coated by the Hot-Dip Process.
4. ASTM A 980 - Standard Specification for Steel, Sheet, Carbon, Ultra High Strength Cold Rolled.
5. ASTM C 645 - Specification for Nonstructural Steel Framing Members.
6. ASTM C 920 - Specification for Elastomeric Joint Sealants.
7. ASTM D 226 - Standard Specification for Asphalt-Saturated Organic Felt Used in Roofing and Waterproofing.
8. ASTM D 2244 - Test Method for Calculation of Color Differences from Instrumentally
Measured Color Coordinates.
9. ASTM D 4214 - Test Methods for Evaluating Degree of Chalking of Exterior Paint Films.
Standing Seam Metal Roof Panels 07 41 13 - Page 2 of 8
10. ASTM E 1592 - Standard Test Method for Structural Performance of Sheet Metal Roof and Siding Systems by Uniform Static Air Pressure Difference.
11. ASTM E 1980 - Practice for Calculating Solar Reflectance Index of Horizontal and Low- Sloped Opaque Surfaces.
D. Underwriters Laboratories, Inc. (UL): www.ul.com:
1. UL 580 - Tests for Uplift Resistance of Roof Assemblies
1.4 ADMINISTRATIVE REQUIREMENTS
A. Preinstallation Meeting: Prior to erection of framing, conduct preinstallation meeting at site attended by Owner, Architect, manufacturer's technical representative, inspection agency and related trade contractors.
1. Coordinate building framing in relation to metal panel system.
2. Coordinate openings and penetrations of metal panel system.
3. Coordinate work of Division 07 Sections "Roof Specialties" and "Roof Accessories" and openings and penetrations and manufacturer's accessories with installation of metal panels.
1.5 QUALITY ASSURANCE
A. Manufacturer/Source: Provide metal roof panel assembly and accessories from a single manufacturer providing fixed-base roll forming, and accredited under IAS AC 472 Part B.
B. Manufacturer Qualifications: Approved manufacturer listed in this Section with minimum five…