1502000 J Facility Investment ver 2.4.doc

DOC document 266 KB Posted

Attached to
Above Ground / Underground Storage Tank Services, NAVAL STATION NEWPORT, NEWPORT RI
Solicitation number
N4008521B2500
Issued by

View the file

Other files

File Type Posted
Revised ELINs- AST-UST 12.14.20.xlsx XLSX spreadsheet
Revised AST UST Inventory 12 14 20.xlsx XLSX spreadsheet
Amendment 4 N4008521B2500 REVISED INVENTORY AND ELINS and RFI Questions and Answeres.pdf PDF
Amendment 3 N4008521B2500 Attachment Revision- Bid Due date extension- clarification.pdf PDF
RFI ELINs - AST-UST.xlsx XLSX spreadsheet
Revised 1502000 C UST-AST SOW (FFP).docx DOCX document
Revised UST-AST Tank Inventory 12-11-20.xlsx XLSX spreadsheet
Amendment 2 N4008521B2500 BID OPENING INFORMATION.pdf PDF
NSNTanksMapbook_20201104 FINAL.pdf PDF
Amendment 1 N4008521B2500 Add Attachment Tank Mapbook.pdf PDF
Current NSN Tank Inventory 21 April 2020.xlsx XLSX spreadsheet
0200000 F Management and Administration v2.8 (track changes).docx DOCX document
PAP AST UST.doc DOC document
1502000 FAP Facility Investment ver 2.5.doc DOC document
1502000 C UST-AST SOW (FFP) w EM comments.docx DOCX document
1502000 J Facility Investment ver 2.4 F.doc DOC document
Wage Determination.pdf PDF
Solicitation AST-UST Services Contract Naval Station Newport N4008521R2516.pdf PDF
ELINs - AST-UST Completed.xlsx XLSX spreadsheet
0200000 J Management and Administration v2.6 (track changes).docx DOCX document
0200000 C Management and Administration v2.9 (track changes).docx DOCX document
0100000 C General Information.docx DOCX document
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SECTION J

DOCUMENTS, EXHIBITS, AND OTHER ATTACHMENTS

TABLE OF CONTENTS

ATTACHMENT NUMBER
ATTACHMENT TITLE
J-1502000-01
Definitions and Acronyms
J-1502000-02
References and Technical Documents
J-1502000-03
Facilities Property Inventory
J-1502000-04
Site Maps
J-1502000-05
Historical Service Order Workload

ATTACHMENT J-1502000-01

DEFINITIONS AND ACRONYMS

DEFINITION
DESCRIPTION
CRANE, CATEGORY 1
Portal cranes, Hammerhead cranes, Locomotive cranes, Derricks, Floating cranes (YD), Tower cranes, Container cranes, Mobile cranes (except those indicated as category 4), including truck, cruiser, crawler, warehouse/industrial cranes, and cranes used for dragline, pile driving, clamshell, magnet, bucket work, and Aircraft crash cranes.
CRANE, CATEGORY 2 & 3
Cranes with rated capacities of 20,000 pounds or greater are category 2. Examples are Over head traveling cranes, Gantry cranes (rail mounted), Wall cranes, Jib cranes, Pillar cranes, Pillar jib cranes, Monorails and associated hoists, Fixed hoists, including chain falls. Pedestal mounted commercial boom assemblies (fixed length, telescoping, and articulating types) attached to stake trucks, trailers, flatbeds, or railcars, or stationary mounted to piers, etc., with OEM rated capacities less than 2,000 pounds.
CRANE, CATEGORY 4
Commercial truck mounted cranes, Truck mounted articulating boom cranes, Pedestal mounted commercial boom assemblies (fixed length, telescoping, and articulating types) attached to stake trucks, trailers, flatbeds, or railcars, or stationary mounted to piers, etc., with OEM rated capacities of 2,000 pounds and greater. Commercial truck mounted cranes and truck mounted articulating boom cranes with OEM capacities of 2,000 pounds and greater require a licensed operator even if the cranes are down rated below 2,000 pounds capacity for administrative purposes.
EQUIPMENT, COLLATERAL
Encompasses built-in and large substantially affixed equipment/property that is normally acquired and installed as part of a facility project.
EQUIPMENT, INSTALLED
Encompasses building-type equipment, built-in equipment, and large, substantially affixed equipment/property, and is normally acquired and installed as part of a facility project. Installed equipment is normally required to make a facility useful and operable. Removing such equipment would impair the usefulness, safety, or environment of the facility or the facility restoration work required after its removal, is substantial.
EQUIPMENT, PERSONAL PROPERTY
Personal property equipment includes all equipment other than collateral equipment. Such equipment, when acquired and used in a facility or a test apparatus, can be severed and removed aster erection or installation without substantial loss of value or damage thereto or to the premises where installed.
FACILITIES LIFE CYCLE
A facilities life cycle is divided into four stages, requirements (planning and design), acquisition (construction and acceptance), stewardship (operations, maintenance and repair), and disposal.
FACILITIES MAINTENANCE MANAGEMENT
The planning, prioritizing, organizing, controlling, reporting, evaluating, and adjusting of facilities maintenance operations to support the CNO/NAVFAC facilities policy and objectives and satisfy customers’ facility needs. Defined by the International Facility Management Association as “the practice of coordinating the physical workplace with the people and work of the organization.”
Integrated Maintenance Program (IMP)
IMP is a recurring state-of-the-art, reliability-centered inspection, testing, maintenance and repair program that determines best practices for managing the functions and consequences of failures of facilities equipment and system components. IMP encompasses accepted commercial practices, including reactive, preventive, predictive and proactive maintenance, into one optimal program. The IMP approach gives the Contractor full responsibility to maintain systems and equipment and perform repairs whenever necessary to ensure equipment and systems are operational and remain in a constant state of readiness. Service calls will not be issued for accomplishment of repairs on systems and equipment maintained under IMP.
LIFE-CYCLE COSTS
A form of economic analysis that considers the total cost of owning, operating, and maintaining a building or system over its useful life.
MAINTENANCE, PREVENTIVE
Maintenance designed to increase the availability of the facilities/equipment by reducing the number of unexpected breakdowns or service interruptions. It is any planned maintenance activity that improves equipment life and avoid any unplanned maintenance requirements.
MANAGEMENT INFORMATION SYSTEMS-MAINTENANCE
A computerized system that will provide sufficient information for management to evaluate differences between budgets and actual costs and evaluate performance.
REPAIR
Repair is the restoration of facilities or equipment to such a condition that it may be effectively utilized for its designated purposes by overhaul, reconstruction, or replacement of constituent parts or materials which have deteriorated by action of the elements or usage, and which have not been corrected through maintenance. This term also applies to replacement of the entire unit or system if beyond economical repair. The intent of repair is to have the equipment at normal working condition.
REPLACEMENT
Replacement, as a distinct work element, is confined to a program of planned replacement of a facility or its components. It may be further limited to major components such as air conditioning compressors, furnaces or hot water heaters. Replacement is performed when the equipment has reached the end of its useful life; when it no longer can perform due to degradation of its internal components and repair is no longer cost effective. Included under the replacement would be the major rebuilding of any component, since rebuilding also restores performance.
RESTORATION
Restoration of real property to such a condition that it can be used for its intended purpose. Includes repair or replacement work to restore facilities damaged by inadequate sustainment, excessive age, natural disaster, fire, accident or other causes.
SUSTAINMENT
Maintenance and repair activities necessary to keep a typical inventory of facilities in “normal working condition”. Sustainment includes regularly scheduled maintenance as well as cyclical major repairs or replacement of components that occur periodically over the expected service life of the facilities.
SERVICE ORDER
Any work required to return a facility, system, equipment or component to normal working condition. Service orders are minor facility problem requests or requests for other non-recurring work that is too small to be planned and estimated.

The purpose of a service order is to provide the Government with a means of issuing work up to a defined liability limit for requirements occurring outside of the specified recurring work. The Government may utilize service orders to accomplish any work up to the respective liability limit based on the service order classification.

SERVICE ORDER CYCLE
Count down starts when the customer is notified that the work has been accepted to be accomplished to the time when the work chit is turned in by the craftsmen as complete is one complete cycle period for a service order.
SERVICE ORDER, EMERGENCY
Emergency is defined as any facility deficiency that immediately compromises the mission or life, health and safety. Always includes, but is not limited to, failure of any utility, fire protection, environmental control, or security alarm systems.
SERVICE ORDER, URGENT
Urgent is defined as any deficiency that does not immediately endanger personnel or property, but extended delays of repairs could result in damage to Government property, or soon affect the security, health, or well-being of personnel or the continued operation of a service or system.
SERVICE ORDER, ROUTINE
Routine is defined as any work requirement within the defined LOL that does not qualify as emergency or urgent.
WEIGHT HANDLING EQUIPMENT (WHE)
Weight handling equipment consists of cranes (e.g., portal cranes, jib cranes), rigging gear (e.g., slings, shackles), and associated equipment (e.g., portable hoists, dynamometers). For purposes of this technical sub-annex, WHE does not include mobile or transportable truck, crawler, and railway mounted locomotive cranes covered in 1700000 BSVE.

ATTACHMENT J-1502000-01

DEFINITIONS AND ACRONYMS

Acronym
Title
BPVC
Boiler and Pressure Vessel Code
HVAC
Heating, Ventilation, and Air Conditioning
RPIE
Real Property Inventory Equipment
SCADA
Supervisory Control And Data Acquisition
SRM
Sustainment, Restoration and Modernization
UFC
Unified Facilities Criteria
UPV
Unfired Pressure Vessel
VTE
Vertical Transportation Equipment

ATTACHMENT J-1502000-02

REFERENCES AND TECHNICAL DOCUMENTS

Reference
Title
General Laws of Rhode Island
Chapters 23, 42 and 46
OPNAVINST
5090.1C

DEM-OWM-UST08-07

State of Rhode Island
Oil Pollution Control Regulations

AST regulation #2

RIDEM UST
250-140-25 Part 1-Rule 1.10.U
NFPA
Fire Codes; i.

NFPA 30

ii.

NFPA 30A

iii.

NFPA 31

iv.

NFPA 37

v.

NFPA 70

vi.

NFPA 77

vii.

NFPA 110

viii.

NFPA 704

Applicable Standards
i.

API 653

ii.

STI SP001

Federal Standards
i.

40 CFR 280

ii.

40 CFR 112

iii.

29 CFR 1910.06

iv.

29 CFR 1910.106

State Regulations
i.

250-RICR-140-25-1

ii.

250-RICR-140-25-2

iii.

250-RICR-140-30-1

iv.

250-RICR-150-05-3

v.

250-RICR-120-05-11

ATTACHMENT J-1502000-03

FACILITY PROPERTY INVENTORY

Tank Management Program Active USTs

Bldg #
TNO Tank #
Location
Capacity
Product Stored
Tank Type
Usage
Date Tank Installed
Tank Age
1286
75
1286CP gas station
20,000
Premium gas
DW FRP
Product Dispenser
1/1/1991
29
1286
76
1286CP gas station
20,000
Super gas
DW FRP
Product Dispenser
1/1/1991
29
1286
77
1286CP gas station
20,000
Regular gas
DW FRP
Product Dispenser
1/1/1991
29
1285
79
1286CP gas station
2,500
No. 2 Fuel Oil
DW FRP
Heating System Supply
1/1/1990
30
A9
80
PW Trans A9 CC
4,000
Diesel
DW FRP
Product Dispenser
1/1/1991
29
23A
103
23NH
4,000
Diesel
DW FRP
Emergency Generator Supply
1/1/1996
24
988
105
988 MEL
2,500
Diesel
DW FRP
Emergency Generator Supply
10/1/1995
24
1250
106
1250CP NEX
3,000
No. 2 Fuel Oil
DW FRP
Heating System Supply
8/23/1999
20
1181
113
1181 MEL
1,000
Diesel
DW FRP
Emergency Generator Supply
10/1/1995
24
987MEL
115
987 MEL
1,000
Diesel
DW FRP
Emergency Generator Supply
10/1/1995
24
820
116
820 MEL
1,000
Diesel
DW FRP
Emergency Generator Supply
10/1/1995
24
315A
117
315 CP
1,000
Diesel
DW FRP
Emergency Generator Supply
10/1/1995
24
361A
118
361 CP
1,000
Diesel
DW FRP
Emergency Generator Supply
10/1/1995
24
170A
119
170 CHI
1,000
Diesel
DW FRP
Emergency Generator Supply
10/1/1995
24
448
120
448 FA
1,000
Diesel
DW FRP
Emergency Generator Supply
10/1/1995
24
694
122
694 MID SLS
1,000
Diesel
DW FRP
Emergency Generator Supply
10/1/1995
24
158A
124
158 CHI
1,000
Diesel
DW FRP
Emergency Generator Supply
10/1/1995
24
75A
125
75 CC Stillwater Basin
2,500
Diesel
DW FRP
Emergency Generator Supply
10/1/1995
24
338A
126
338 CP
2,500
Diesel
DW FRP
Emergency Generator Supply
10/1/1995
24
68
127
68 NH
2,500
Diesel
DW FRP
Emergency Generator Supply
10/1/1995
24
1900
129
1900 CP Post Office
1,000
No.2 Fuel Oil
DW FRP
Heating System Supply
1/1/1995
25
1901
130
1901 CP Package Store
1,000
No.2 Fuel Oil
DW FRP
Heating System Supply
1/1/1995
25
1903
131
1903 CP Laundry
2,500
No.2 Fuel Oil
DW FRP
Heating System Supply
1/1/1995
25
403
135
403 CP Buttercup
2,500
No.2 Fuel Oil
DW FRP
Heating System Supply
1/1/1994
26
1112
137
1112 CP Mardet
3,000
No.2 Fuel Oil
DW FRP
Heating System Supply
1/1/1995
25
1312
142
1312 CP BEQ
10,000
No.2 Fuel Oil
DW FRP
Heating System Supply
1/1/1996
24
1312
144
1312 CP BEQ
10,000
No.2 Fuel Oil
DW FRP
Heating System Supply
1/1/1996
24
7
145
7 CC Boiler Plant
35,000
No.2 Fuel Oil
DW FRP
Heating System Supply
1/1/1996
24
7
146
7 CC Boiler Plant
35,000
No.2 Fuel Oil
DW FRP
Heating System Supply
1/1/1997
23
7
148
7 CC Boiler Plant
1,000
Diesel
DW FRP
Emergency Generator Supply
1/1/1997
23
447
150
447 CP BEQ, Eadie Hall
2,500
No. 2 Fuel Oil
DW FRP
Heating System Supply
1/1/1998
22
7
145C
7 CC Boiler Plant
30,000
No.4 Fuel Oil
DW FRP
Heating System Supply
1/1/2002
18
7
145D
7 CC Boiler Plant
30,000
No.4 Fuel Oil
DW FRP
Heating System Supply
1/1/2002
18
7
145E
7 CC Boiler Plant
35,000
No.2 Fuel Oil
DW FRP
Heating System Supply
1/1/2005
15
7
145F
7 CC Boiler Plant
35,000
No.2 Fuel Oil
DW FRP
Heating System Supply
1/1/2005
15

Tank Management Program Active ASTs

Bldg #
TNO Tank #
Location
Capacity
Product Stored
Tank Type
Usage
Date Installed
Tank Age
27
B27
Bldg 27 CHI
150
Diesel

unk

27
R165
CHI Bldg 27, McCarthy Hall
10,000
Diesel
Double wall, steel
3/7/2005
15
27
R166
CHI NWC, Bldg 27, McCarthy
10,000
No. 2 Fuel Oil
Double wall, steel
Heating System Supply
1/1/2005
15
95
95
CHI, Bldg 95
310
Cooking Oil
Double wall, steel
Cooking
6/1/2006
13
991
B991
Bldg 991 CHI
70
Diesel
1/1/2015
5
1688
1688
NGIS CHI Bldg 1688
372
Diesel
Double wall, steel
Emergency Generator Supply
2/1/2017
3
158A
158A DT
CHI, Bldg 158A
115
Diesel
Generator Day Tank
1/1/1995
25
170A
170A DT
CHI, Bldg 170A, U207
56
Diesel
Generator Day Tank
1/1/1995
25
1A
1A GEN
CHI, Bldg 1A
278
Diesel
Emergency Generator Supply
1/1/2012
8
Gate 1
R164
Bldg 1386, guard shack
188
Diesel
Double wall, steel
Emergency Generator Supply
8/1/2005
14
7
R168
CC Bldg 7, boiler plant U195
281,386
No. 4 Fuel Oil
Steel
1/1/2007
13
7
R169
CC Bldg 7, boiler plant U196
281,386
No. 4 Fuel Oil
Steel
1/1/2007
13
48
315
A48, Coddington Cove
2,500
Diesel
Steel, concrete dike
Emergency Generator Supply
1/1/1997
23
48
315DT
CC, Coddington Cove, Bldg 48
350
Diesel
Double wall, steel
Emergency Generator Supply
1/1/1997
23
68
R152
CC Pier 2, Bldg 68
1,500
No. 2 Fuel Oil
Double wall, steel
Heating System Supply
8/1/2004
15
68
R153
CC Pier 2, Bldg 68
1,500
No. 2 Fuel Oil
Double wall, steel
Heating System Supply
8/1/2004
15
76
R167
CC, Bldg 76 CC Phone Exchng
225
Diesel
Single wall steel
Emergency Generator Supply
unk
1373
R170
Bldg 1373, Codd. Cove
1,250
Diesel
Double wall, steel
Emergency Generator Supply
1/3/2006
14
74C
74C
Coddington Cove, bldg 74C
500
Diesel
Steel single wall w basin
Emergency Generator Supply
6/1/2016
3
74C
74C DT
CC Coddington Cove, bldg 74C
115
Diesel
Single wall steel w basin
Generator Day Tank
unk
75A
75A DT
NUWC Stillwater Basin, bldg 75A
150
Diesel
Single wall steel w basin
Generator Day Tank
unk
A63
R151
A-63, Coddington Cove
500
Diesel
Double wall, steel
1/1/2004
16
A9
A9-1
Coddington Cove, bldg A9
300
Used Oil
Double wall, steel
Used Oil Storage
6/1/2016
3
Gate 17
R171
Coddington Cove, Gate 17, U192
275
Diesel
Double wall, steel
Emergency Generator Supply
1/1/2007
13
S245
R170B
Coddington Cove, S245
240
Diesel
Double wall, steel
Emergency Generator Supply
1/1/2010
10
U194
R168A
Coddington Cove, U194
160
Diesel
Double wall, steel
Emergency Generator Supply
1/1/2008
12
1163
R172
Coddington Pt. Bldg 1163
217
Diesel
Double wall, steel
Emergency Generator Supply
4/1/2016
4
291
R155
CP, NAPS, 291 Kollmeyer St
1,000
No. 2 Fuel Oil
Double wall, steel
Heating System Supply
8/1/2004
15
292
132
CP, Coddington Pt, Bldg 292
900
Diesel
Double wall, steel
Emergency Generator Supply
1/1/2011
9
292
R156
CP, 292 Capodanno Dr
3,000
No. 2 Fuel Oil
Double wall, steel
Heating System Supply
9/1/2004
15
302
R180
CP, NAPS gym, bldg 302
300
No. 2 Fuel Oil
Double wall, steel
Heating System Supply
7/11/2011
8
305
322
CP Bldg 305CP, Thrift Shop
275
No. 2 Fuel Oil
unlisted
Heating System Supply
unk
399
399
CP, Coddington Pt, Bldg 399
1,074
Diesel
Double wall, steel
Emergency Generator Supply
6/1/2016
3
440
323
440CP, Perry Hall
700
Diesel
Double wall, steel
1/1/2011
9
440
R158
CP, 440 Meyerkord Av.
660
No. 2 Fuel Oil
Double wall, steel
Heating System Supply
7/1/2004
15
678
335
Bldg 678, Coddington Pt
275
No. 2 Fuel Oil
Steel, concrete dike
Heating System Supply
1/1/1997
23
678
336
Bldg 678, Coddington Pt
275
No. 2 Fuel Oil
Steel, concrete dike
Heating System Supply
1/1/1997
23
688
R159
688 Rochambeau St.
660
No. 2 Fuel Oil
Double wall, steel
Heating System Supply
8/1/2004
15
690
R179
Coddington Point, Bldg 690
700
Diesel
Double wall, steel
1/1/2011
9
690
R160
690 Peary St, HQ
330
No. 2 Fuel Oil
Double wall, steel
Heating System Supply
7/1/2004
15
1260
1260-1
Bldg 1260, Family Serv.
275
No. 2 Fuel Oil
Double wall plastic in steel
10/1/2015
4
1260
1260-2
Bldg 1260, Family Serv.
275
No. 2 Fuel Oil
Double wall plastic in steel
10/1/2015
4
1260
1260-3
Bldg 1260, Family Serv.
275
No. 2 Fuel Oil
Double wall plastic in steel
10/1/2015
4
1269
R161
1269 Elliot Street
500
No. 2 Fuel Oil
Double wall, steel
Heating System Supply
8/1/2004
15
1285
329
CP Auto Hobby
300
Waste Oil
Double wall, steel
Used Oil Storage
1/1/1999
21
1312
1312 DT
Coddington Pt, Bldg 1312
75
Diesel
Single wall steel, steel berm
Generator Day Tank
1/1/2013
7
1356
1356
Coddington Pt, Bldg 1356
2,000
No. 2 Fuel Oil
Double wall, steel
Emergency Generator Supply
6/1/2016
3
1356
1356-DT
Coddington Pt, Bldg 1356
100
No. 2 Fuel Oil
Double wall, steel
Generator Day Tank
6/1/2016
3
1357
R177
OTC Combat Pool, 1357
1,000
No. 2 Fuel Oil
Double wall, steel
Heating System Supply
12/1/2008
11
1372
1372 DT
Coddington Pt, Bldg 1372 U197
100
No. 2 Fuel Oil
Steel single wall w basin
Generator Day Tank
6/1/2016
3
1372
R163
1372 Meyerkord Ave. U196
6,000
No. 2 Fuel Oil
Double wall, steel
Emergency Generator Supply
1/1/2008
12
1372
R173
Coddington Pt, Bldg 1372
200
Diesel
Double wall, steel
Emergency Generator Supply
1/1/2008
12
1801
R162
1801 Vaughn Ave, gym
660
No. 2 Fuel Oil
Double wall, steel
Emergency Generator Supply
8/1/2004
15
315A
315A DT
Coddington Point, bldg 315A
56
Diesel
Single wall steel, steel berm
Generator Day Tank
1/1/1995
25
338A
338A DT
CP Coddington Point, bldg 338A
150
Diesel
Single wall steel, steel berm
Generator Day Tank
unk
361A
361A DT
CP Coddington Point, bldg 361A
150
Diesel
Single wall steel, steel berm
Generator Day Tank
unk
Gate 2
R174
Coddington Point, Gate 2
240
Diesel
Double wall, steel
Emergency Generator Supply
1/1/2004
16
W 36
334
Bldg W36CP (bldg K61?)
3,000
No. 2 Fuel Oil
Steel
Heating System Supply
10/1/1999
20
W34
13
W-34
2,000
No. 2 Fuel Oil
Steel,steel dike, w/o rainshield
Heating System Supply
1/1/1998
22
448
448 DT
FA Fort Adams, Bldg 448, U201
56
Diesel
Single wall steel, steel berm
Heating System Supply
unk
1289
332
1289FA
275
Diesel
Steel, concrete dike
Water Pump Supply
1/1/1988
32
1289
333
1289FA
275
Diesel
Steel, concrete dike
Water Pump Supply
1/1/1988
32
62
62 GEN
Bldg 62, Melville
300
Diesel
Double wall, steel
Emergency Generator Supply
6/1/2016
3
58
58
Melville Bldg 58
300
Diesel
Double wall, steel
Emergency Generator Supply
6/1/2016
3
820
820 DT
Bldg 820, Melville
56
Diesel
Single wall, steel berm
Generator Day Tank
unk
987
987 DT
Bldg 987, Melville
56
Diesel
Single wall, steel berm
Generator Day Tank
unk
988
988 DT
Bldg 988B, Melville
56
Diesel
Single wall steel, steel berm
Generator Day Tank
unk
1181
1181 DT
Melville Bldg 1181, near DLA fuel dispene
56
Diesel
Single wall steel, steel berm
Generator Day Tank
unk
U30
U-30
Mellville, U-30
366
Diesel
Double wall steel
Emergency Generator Supply
6/1/2016
3
694
694 DT
Bldg 694, Midway
115
Diesel
Single wall steel, steel berm
Generator Day Tank
unk
43
43-1
NH, Naval Hospital, Bldg 43
275
No. 2 Fuel Oil
Single wall steel w basin
Heating System Supply
6/1/2016
3
43
43-2
NH, Naval Hospital, Bldg 43
275
No. 2 Fuel Oil
Single wall steel w basin
Heating System Supply
6/1/2016
3
44
44 GEN
NH, Naval Hospital, Bldg 44
449
Diesel
Double wall, steel
Emergency Generator Supply
1/1/2013
7
68
68 DT
NH Naval Hospital, Bldg 68
115
Diesel
Single wall steel, steel berm
Generator Day Tank
unk
1271
326
Bldg 1271 Naval Hosp
275
Diesel
Single wall steel, concrete berm
Fire Pump Supply
1/1/1972
48
1271
327
Bldg 1271 Naval Hosp
275
Diesel
Single wall steel, concrete berm
Fire Pump Supply
1/1/1972
48
1271
328
Bldg 1271 Naval Hosp
275
Diesel
Single wall steel, concrete berm
Fire Pump Supply
1/1/1972
48
23A
23A DT
Naval Hospital, bldg 23A
159
Diesel
Double wall steel
Generator Day Tank
6/1/2016
3
A6
302
Bldg 6, Naval Hospital
275
Diesel
Steel, concrete dike
Emergency Generator Supply
1/1/1982
38
A6
303
Bldg 6, Naval Hospital
275
Diesel
Steel, concrete dike
Emergency Generator Supply
1/1/1982
38
Gate 23
Gate 23
NUWC Gate 23
348
Diesel
TBD
Emergency Generator Supply
TBD
80
B-80-1
NUWC, Bldg 80
78
Diesel
Double wall steel
Emergency Generator Supply
unk
104
104
NUWC Bldg 104
597
Diesel
Double wall steel
Emergency Generator Supply
1/1/2006
14
105
105
NUWC building 105
348
Diesel

Emergency Generator Supply

106
106
NUWC Bldg 106
266
Diesel
Double wall steel
Emergency Generator Supply
1/1/2003
17
111
111
NUWC Bldg 111
411
Diesel
Double wall steel
Emergency Generator Supply
1/1/2002
18
990
990
NUWC Bldg 990
266
Diesel
Double wall steel
Emergency Generator Supply
1/1/2003
17
1171
1171
NUWC Bldg 1171
348
Diesel
TBD
Emergency Generator Supply
TBD
1176
1176-1
NUWC Bldg 1176
1,200
Isopar M
Double wall, steel
1/1/2011
9
1176
1176-2
NUWC Bldg 1176
800
Iospar L
Double wall, steel
1/1/2011
9
1176
1176-3
NUWC Bldg 1176
8,000
Norpar 12
Double wall, steel
1/1/2011
9
1176
1176-4
NUWC Bldg 1176
8,000
Isopar L
Double wall, steel
1/1/2011
9
1176
1176-5
NUWC Bldg 1176
4,000
Used Isopar
Double wall, steel
1/1/2011
9
1176
1176-6
NUWC Bldg 1176
800
Norpar 12
Double wall, steel
1/1/2011
9
1258
1258
NUWC building 1258
350
Diesel

Emergency Generator Supply

1259
B-1259-1
NUWC Bldg 1259
150
Diesel
Single wall steel, concrete berm

unk

1259
B-1259-2
NUWC Bldg 1259
275
Diesel
Single wall steel, concrete berm

unk

1319
B-1319
NUWC Bldg 1319
295
Diesel
Single wall steel, steel berm
Fire Pump Supply
unk
1320
B-1320
NUWC Bldg 1320
130
Diesel
Single wall steel, concrete berm
Fire Pump Supply
unk
1346
1346
NUWC, Bldg 1346
472
Diesel
Double wall, steel
Emergency Generator Supply
6/1/2016
3
1349
B-1349
NUWC Bldg 1349
275
Diesel
Double wall steel
Emergency Generator Supply
unk
1350
B-1350
NUWC Bldg 1350
275
Diesel
Double wall steel
Emergency Generator Supply
unk

Tank Management Program Active AST Groundwater Monitoring Wells

7
R168, R169
North
Must have water level recorded, and any presence of oil noted once each calendar month
7
R168, R169
South
Must have water level recorded, and any presence of oil noted once each calendar month
7
R168, R169
West
Must have water level recorded, and any presence of oil noted once each calendar month

ATTACHMENT J-1502000-04

SITE MAPS

Please see separate PDF attachments for area Maps

ATTACHMENT J-1502000-05

HISTORICAL SERVICE ORDER WORKLOAD

Labor Categories
Emergency Service Orders (received during Government regular working hours)
Routine Service Orders
Number of Calls
Avg. Hrs. to Complete
Number of Calls
Number of Calls

AST/UST

Total Service Orders

File details come from the government source that posted it. Updated .