1501000 J Facility Management.pdf
PDF 578 KB Posted
- Attached to
- Regional HVAC&R Hampton Roads, Virginia
- Solicitation number
- N4008522R2506
About this file
This solicitation seeks proposals for a facility support indefinite delivery/indefinite quantity contract to provide heating, ventilation, air conditioning and refrigeration repair and maintenance services in the Hampton Roads, Virginia area. Services include facility investment sustainment, restoration and modernization work as well as facilities management infrastructure condition assessment program support. Facility investment work involves building systems, ceiling and exhaust fans, compressed air systems, chemical feeders, exhaust systems, heaters and heat transfer units, HVAC systems including variable frequency and speed drives. Facilities management support includes condition assessment reporting. The contract term is one year with four one-year options and has a total estimated value over $2,000,000. Proposals are due February 10, 2022 and will be evaluated for technical approach, experience, safety, and past performance. The North American Industry Classification System code is 811310 and the size standard is $8 million. This is a competitive small business total set-aside issued by the Naval Facilities Engineering Command Mid-Atlantic.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 22R2506 Amendment 0005.pdf | ||
| 22R2506 Amendment 0004.pdf | ||
| J-0200000-21 (Amendment 0003- SIte Visit Log).pdf | ||
| 22R2506 Amendment 0003.pdf | ||
| 22R2506 Amendment 0002.pdf | ||
| 22R2506 Amendment 0001.pdf | ||
| 22R2506 Amendment 0001.pdf | ||
| J-0200000-20 (Amendment 0001) NCTAMS Site Visit Incoming Visitor Log.xlsx | XLSX spreadsheet | |
| J-15020000-07 HVAC IMP Inventory.xlsx | XLSX spreadsheet | |
| 0200000 J Management and Administration.pdf | ||
| J-0200000-07 ASSET INFORMATION.xlsx | XLSX spreadsheet | |
| J-0200000-15 ELINS.xlsx | XLSX spreadsheet | |
| 1502000 J Facility Investment.pdf | ||
| J-15020000-08 HVAC Seasonal Startup-Shutdown.xlsx | XLSX spreadsheet | |
| J-0200000-06 SERVICE PROVIDER INFORMATION.xlsx | XLSX spreadsheet | |
| J-15020000-05 HVAC PM Inventory.xlsx | XLSX spreadsheet | |
| N4008522R2506 Regional HVAC.pdf |
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION J – 1501000
Facility Management
ATTACHMENT NUMBER ATTACHMENT TITLE
J-1501000-01 Definitions and Acronyms
J-1501000-02 References and Technical Documents
J-1501000-03 Meter Group Descriptions and Direct Condition Rating Guidance
J-1501000-04 General Direct Condition Rating Guidance
ATTACHMENT J-1501000-01
DEFINITIONS AND ACRONYMS
TERM DEFINITION
CONDITION BASED
MAINTENANCE
MANAGEMENT
A maintenance philosophy that encompasses a condition management cycle that is sustained throughout the entire life-cycle of a facility and its constituent component sections, or assets.
FACILITIES LIFE CYCLE A facilities life cycle is divided into four stages, requirements (planning and design), acquisition (construction and acceptance), stewardship
(operations, maintenance and repair), and disposal.
INFRASTRUCTURE
CONDITION ASSESSMENT
PROGRAM
A foundational component of Condition Based Maintenance Management
(CBMM). ICAP comprises three of the four CBMM quadrants: Inventory, Assessment, and Analysis.
FACILITIES MAINTENANCE
MANAGEMENT
The planning, prioritizing, organizing, controlling, reporting, evaluating, and adjusting of facilities maintenance operations to support the
CNO/NAVFAC facilities policy and objectives and satisfy customers’ facility needs. Defined by the International Facility Management
Association as “the practice of coordinating the physical workplace with the people and work of the organization.”
LIFE-CYCLE COSTS A form of economic analysis that considers the total cost of owning, operating, and maintaining a building or system over its useful life.
REAL PROPERTY Land and improvements to land (i.e., facilities). It includes equipment affixed and built into the facility as an integral part of the facility (such as heating systems), but not movable equipment (e.g., plant equipment, industrial equipment, buoys).
RESTORATION Restoration of real property to such a condition that it can be used for its intended purpose. Includes repair or replacement work to restore facilities damaged by inadequate sustainment, excessive age, natural disaster, fire, accident or other causes.
SUSTAINMENT Maintenance and repair activities necessary to keep a typical inventory of facilities in “normal working condition”. Sustainment includes regularly scheduled maintenance as well as cyclical major repairs or replacement of components that occur periodically over the expected service life of the facilities.
UNIFORMAT
CLASSIFICATION
A standard classification of building components established by the
National Institute of Standards and Technology.
Acronym Title
BFR Basic Facility Requirements
CBMM Condition Based Maintenance Management
ICAP Infrastructure Condition Assessment Program
IMP Integrated Maintenance Program
MDI Mission Dependency Index
MILCON Military Construction
PM Preventive Maintenance
POAM Plan of Action and Milestones
RSIP Regional Shore Infrastructure Plan
ATTACHMENT J-1501000-02
REFERENCES AND TECHNICAL DOCUMENTS
Reference Title
NAVFAC P-78 Real Property Inventory Procedures Manual
OPNAVINST 11011.10 Utilization of Navy Real Property
SECNAVINST 11011.47 Acquisition, Management, and Disposal of Real Property and Real Property
Interests by the Department of the Navy
ATTACHMENT J-1501000-03
METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE
D3030130 - Chiller, Reciprocating, Water Cooled
Meter & Description Direct Condition Rating Guidance Condition
CR-5140 - Record the condition of the
Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational
AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional
RED: Unacceptable Noise, Vibration, or overheating from compressor, significant damage, and/or operationally impaired
CR-5155 - Record the condition of the
Condenser
GREEN: Minimal corrosion or fouling of the condenser/coils, no damage
AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
RED: Significant damage, corrosion or fouling of the condenser/coils, no damage, operationally impaired
CR-5200 - Record the condition of the Controls
GREEN: Controls function properly
AMBER: Controls need calibrating
RED: Controls are damaged and/or not operational
CR-5295 - Record the
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured
AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
RED: Significant damage/corrosion to Enclosure, a number of panels are loose, displaced, or missing
CR-5305 - Record the
Evaporator
GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage
AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
RED: Significant damage, corrosion or fouling of the evaporator/coils, operationally impaired
CR-5530 - Record the
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion
AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs
CR-5565 - Record the condition of the Receiver
Tank
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure
AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure
RED: Tank has noticeable damage, punctures, holes, and leaks, may be unstable or not fully secured
D3030135 - Chiller, Reciprocating, Air Cooled
Meter & Description Direct Condition Rating Guidance Condition
CR-5140 - Record the condition of the
Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational
AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional
CR-5155 - Record the condition of the
Condenser
GREEN: Minimal corrosion or fouling of the condenser/coils, no damage
AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
CR-5175 - Record the
Condenser Fan(s)
Assembly
GREEN: Motor operates properly, free of excessive noise/vibration, or overheating
AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance
RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired
GREEN: Controls function properly
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured
AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
Evaporator
GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage
AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
CR-5520 - Record the
Pipes/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion
AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Tank
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure
AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure
CR-5690 - Record the
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure
AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
RED: Wiring is significantly deteriorated or frayed, connection are loose, or risk of unintentional grounding
D3030140 - Chiller, Centrifugal, Water Cooled
CR-5110 - Record the
Centrifugal Motor
GREEN: Motor operates properly, free of excessive noise/vibration, or overheating
AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance
CR-5140 - Record the
Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational
AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional
Condenser
GREEN: Minimal corrosion or fouling of the condenser/coils, no damage
AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
CR-5210 - Record the
Controls/Sensors
GREEN: Controls function properly
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured
AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
Evaporator
GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage
AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion
AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Tank
GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure
AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure
D3030310 - Cooling Tower, Galvanized
CR-5025 - Record the condition of the
Basin/Sump
GREEN: Sump has minimal damage or corrosion, no leaking
AMBER: Sump has noticeable damage or corrosion, but no leaking
RED: Sump has significant damage or corrosion, and noticeable leaking, operationally impaired
CR-5280 - Record the
Electrodes
GREEN: Conductivity Electrodes have minimal damage and corrosion, secure connections and fully functional
AMBER: Conductivity Electrodes have noticeable damage and corrosion, some loose connections but still functional
RED: Conductivity Electrodes have significant damage and corrosion, loose or missing connections, operationally impaired
CR-5325 - Record the condition of the Fan
Assembly
GREEN: Fan blades are in balance and free of damage or corrosion
AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
RED: Fans blades are out of balance, significantly bent or corroded, or fan is operationally impaired
CR-5350 - Record the condition of the Fill
Material
GREEN: Filter has minimal to no dirt and debris, free of damage
AMBER: Filter shows noticeable signs of debris, but little to no damage allowing unobstructed flow
RED: Air Filter clogged with dirt and debris, or shows signs of damage such as, punctures, tears, rips
Pipes/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion
AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
D3030320 - Cooling Tower, Fiberglass
CR-5025 - Record the condition of the
Basin/Sump
GREEN: Sump has minimal damage or corrosion, no leaking
AMBER: Sump has noticeable damage or corrosion, but no leaking
Electrodes
GREEN: Conductivity Electrodes have minimal damage and corrosion, secure connections and fully functional
AMBER: Conductivity Electrodes have noticeable damage and corrosion, some loose connections but still functional
Assembly
GREEN: Fan blades are in balance and free of damage or corrosion
AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
Material
GREEN: Filter has minimal to no dirt and debris, free of damage
AMBER: Filter shows noticeable signs of debris, but little to no damage allowing unobstructed flow
Pipes/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion
AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
D3030330 - Cooling Tower, Stainless Steel
CR-5025 - Record the condition of the
Basin/Sump
GREEN: Sump has minimal damage or corrosion, no leaking
AMBER: Sump has noticeable damage or corrosion, but no leaking
Electrodes
GREEN: Conductivity Electrodes have minimal damage and corrosion, secure connections and fully functional
AMBER: Conductivity Electrodes have noticeable damage and corrosion, some loose connections but still functional
Assembly
GREEN: Fan blades are in balance and free of damage or corrosion
AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
Material
GREEN: Filter has minimal to no dirt and debris, free of damage
AMBER: Filter shows noticeable signs of debris, but little to no damage allowing unobstructed flow
Pipes/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion
AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
D3030902 - Condenser, DX, Evaporative
CR-5325 - Record the condition of the Fan
Assembly
GREEN: Fan blades are in balance and free of damage or corrosion
AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
CR-5495 - Record the condition of the Louvers
GREEN: Louvers have minimal damage and corrosion, fully secured
AMBER: Louvers have noticeable damage and corrosion, may be loose but still operational
RED: Louvers have significant damage and corrosion, may be loose, missing, and/or operationally impaired
CR-5515 - Record the condition of the Nozzles
GREEN: Nozzles show no signs of damage, corrosion, or clogging, fully operational
AMBER: Nozzles have some damage, corrosion, or clogs, noticeable obstruction of flow, but operational
RED: Nozzles have significant damage and corrosion, severely obstructed flow, operationally impaired
CR-5615 - Record the condition of the Sump
Pump
GREEN: Pump has minimal damage or corrosion, no unusual noise/vibration, no leaks, and is fully operational
AMBER: Pump has noticeable damage or corrosion, slight leaking, unusual noise/vibration, but still operational
RED: Pump has significant damage or corrosion, excessive noise/vibration, noticeable leaking, and/or is operationally impaired
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure
AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
D3030903 - Packaged DX Refrigerant System
CR-5140 - Record the condition of the
Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational
AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional
Condenser Fan(s)
Assembly
GREEN: Motor operates properly, free of excessive noise/vibration, or overheating
AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance
CR-5185 - Record the
Condensing Coils
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
RED: Coils are clogged, show some signs of damage, or significant scaling and deterioration.
CR-5200 - Record the condition of the Controls
GREEN: Controls function properly
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion
AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure
AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
D3040106 - Air Handling Unit, Field Fabricated
CR-5120 - Record the condition of the Coils
(Cooling)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
CR-5125 - Record the condition of the Coils
(Heating)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
CR-5145 - Record the
Condensate Piping
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion
AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Controls/Sensors
GREEN: Controls function properly
CR-5235 - Record the condition of the Dampers
GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational
AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational
RED: Damper has significant damage and corrosion, noticeably loose, misaligned, or missing, and/or operationally impaired
CR-5260 - Record the condition of the Drain
Pan
GREEN: Drain Pan has minimal damage or corrosion
AMBER: Drain Pan has noticeable damage or corrosion, but no leaks
RED: Drain Pan has significant damage or corrosion, and noticeable leaks
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured
AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
CR-5330 - Record the
Assy
GREEN: Fan blades are in balance and free of damage or corrosion
AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion
AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
D3040110 - Air Handling Unit, Central Station
CR-5120 - Record the condition of the Coils
(Cooling)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
(Heating)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
GREEN: Controls function properly
GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational
AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational
Pan
GREEN: Drain Pan has minimal damage or corrosion
AMBER: Drain Pan has noticeable damage or corrosion, but no leaks
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured
AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
CR-5340 - Record the condition of the Fan(s)
Assembly
GREEN: Fan blades are in balance and free of damage or corrosion
AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
CR-5495 - Record the condition of the Louvers
GREEN: Louvers have minimal damage and corrosion, fully secured
AMBER: Louvers have noticeable damage and corrosion, may be loose but still operational
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion
AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
D3040114 - Air Handling Unit, Rooftop
CR-5120 - Record the condition of the Coils
(Cooling)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
(Heating)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
GREEN: Controls function properly
GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational
AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational
Pan
GREEN: Drain Pan has minimal damage or corrosion
AMBER: Drain Pan has noticeable damage or corrosion, but no leaks
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured
AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
CR-5340 - Record the condition of the Fan(s)
Assembly
GREEN: Fan blades are in balance and free of damage or corrosion
AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
CR-5495 - Record the condition of the Louvers
GREEN: Louvers have minimal damage and corrosion, fully secured
AMBER: Louvers have noticeable damage and corrosion, may be loose but still operational
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion
AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
D3040220 - Fan System, Centrifugal In-Line
CR-5200 - Record the condition of the Controls
GREEN: Controls function properly
GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational
AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured
AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
Assy
GREEN: Fan blades are in balance and free of damage or corrosion
AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure
AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
D3040230 - Fan System, Utility Set
CR-5330 - Record the condition of the Fan
Assy
GREEN: Fan blades are in balance and free of damage or corrosion
AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
CR-5630 - Record the condition of the Switches
Controls
GREEN: Switches function properly
AMBER: None
RED: Switches do not function properly
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure
AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
D3040240 - Fan System, Roof Exhaust
CR-5200 - Record the condition of the Controls
GREEN: Controls function properly
GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational
AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured
AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
Assy
GREEN: Fan blades are in balance and free of damage or corrosion
AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure
AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
D3040330 - Circulating Pump, End Suction
CR-5045 - Record the condition of the Booster
Pump, w/ Oil Reservoir
GREEN: Pump has minimal damage or corrosion, no unusual noise/vibration, no leaks, and is fully operational AMBER: Pump has noticeable damage or corrosion, slight leaking, unusual noise/vibration, but still operational RED: Pump has significant damage or corrosion, excessive noise/vibration, noticeable leaking, and/or is operationally impaired
D3040340 - Circulating Pump, Double Suction
CR-5045 - Record the condition of the Booster
Pump, w/ Oil Reservoir
GREEN: Pump has minimal damage or corrosion, no unusual noise/vibration, no leaks, and is fully operational AMBER: Pump has noticeable damage or corrosion, slight leaking, unusual noise/vibration, but still operational RED: Pump has significant damage or corrosion, excessive noise/vibration, noticeable leaking, and/or is operationally impaired
D3040610 - Heat Exchanger, Plate Type
CR-5200 - Record the condition of the Controls
GREEN: Controls function properly
CR-5375 - Record the
Frame/Supports
GREEN: Supports have minimal damage and corrosion, are fully stable and secure
AMBER: Supports have noticeable damage and corrosion, but still structurally stable and secure
RED: Supports have significant damage and corrosion, and/or unstable or not secured
CR-5465 - Record the
Insulation
GREEN: Insulation has minimal deterioration, and is mostly in place where necessary
AMBER: Insulation has noticeable deterioration, portions may be loose or displaced, but mostly intact
RED: Insulation is significantly damaged, or large portions are displaced or missing
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion
AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
CR-5570 - Record the condition of the Relief
Valve
GREEN: Valve has little to no damage or corrosion, is fully operational
AMBER: Valve shows some damage or corrosion, valve functions but may require calibration
RED: Valve has significant damage or corrosion, is operationally impaired
CR-5590 - Record the condition of the Steam
Modulating Valve
GREEN: Valve has little to no damage or corrosion, is fully operational
AMBER: Valve shows some damage or corrosion, valve functions but may require calibration
D3040620 - Heat Exchanger, Shell Tube
CR-5200 - Record the condition of the Controls
GREEN: Controls function properly
CR-5375 - Record the
Frame/Supports
GREEN: Supports have minimal damage and corrosion, are fully stable and secure
AMBER: Supports have noticeable damage and corrosion, but still structurally stable and secure
RED: Supports have significant damage and corrosion, and/or unstable or not secured
CR-5465 - Record the
Insulation
GREEN: Insulation has minimal deterioration, and is mostly in place where necessary
AMBER: Insulation has noticeable deterioration, portions may be loose or displaced, but mostly intact
RED: Insulation is significantly damaged, or large portions are displaced or missing
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion
AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
CR-5570 - Record the condition of the Relief
Valve
GREEN: Valve has little to no damage or corrosion, is fully operational
AMBER: Valve shows some damage or corrosion, valve functions but may require calibration
CR-5590 - Record the condition of the Steam
Modulating Valve
GREEN: Valve has little to no damage or corrosion, is fully operational
AMBER: Valve shows some damage or corrosion, valve functions but may require calibration
D3050170 - Split Systems With Air Cooled Condensing Units
CR-5120 - Record the condition of the Coils
(Cooling)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
(Heating)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational
AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional
RED: Unacceptable Noise, Vibration, or overheating from compressor, significant damage, and/or operationally impaired
Condenser
GREEN: Minimal corrosion or fouling of the condenser/coils, no damage
AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
RED: Significant damage, corrosion or fouling of the condenser/coils, no damage, operationally impaired
GREEN: Motor operates properly, free of excessive noise/vibration, or overheating
AMBER: Motor exhibits unusual noise/vibration, but still operational, Condenser Fan(s)
Assembly may require maintenance
RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired
CR-5200 - Record the condition of the Controls
GREEN: Controls function properly
Pan
GREEN: Drain Pan has minimal damage or corrosion
AMBER: Drain Pan has noticeable damage or corrosion, but no leaks
RED: Drain Pan has significant damage or corrosion, and noticeable leaks
CR-5460 - Record the condition of the Indoor
Fan Motor Assembly
GREEN: Motor operates properly, free of excessive noise/vibration, or overheating
AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion
AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure
AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
RED: Wiring is significantly deteriorated or frayed, connection are loose, or risk of unintentional grounding
D3050185 - Computer Room Cooling Units
CR-5120 - Record the condition of the Coils
(Cooling)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
(Heating)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
CR-5150 - Record the
Condensate Pump
GREEN: Pump has minimal damage or corrosion, no unusual noise/vibration, no leaks, and is fully operational
AMBER: Pump has noticeable damage or corrosion, slight leaking, unusual noise/vibration, but still operational
RED: Pump has significant damage or corrosion, excessive noise/vibration, noticeable leaking, and/or is operationally impaired
Controls/Sensors
GREEN: Controls function properly
Pan
GREEN: Drain Pan has minimal damage or corrosion
AMBER: Drain Pan has noticeable damage or corrosion, but no leaks
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured
AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
Assy
GREEN: Fan blades are in balance and free of damage or corrosion
AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
CR-5450 - Record the
Humidifier
GREEN: Pan has minimal damage or corrosion
AMBER: Pan has noticeable damage or corrosion, but no leaks
RED: Pan has significant damage or corrosion, and noticeable leaks
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion
AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
D3050201 - Packaged A/C, Air Cooled, Elec Heat
CR-5120 - Record the condition of the Coils
(Cooling)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
(Heating)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational
AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional
Condenser
GREEN: Minimal corrosion or fouling of the condenser/coils, no damage
AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
Condenser Fan(s)
Assembly
GREEN: Motor operates properly, free of excessive noise/vibration, or overheating
AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance
D3050201 - Packaged A/C, Air Cooled, Elec Heat
CR-5200 - Record the condition of the Controls
GREEN: Controls function properly
Pan
GREEN: Drain Pan has minimal damage or corrosion
AMBER: Drain Pan has noticeable damage or corrosion, but no leaks
CR-5275 - Record the condition of the Duct
Connectors
GREEN: Ductwork has little to no damage or corrosion, insulation is intact and there are no holes, leaks, or blockages
AMBER: Ductwork has noticeable damage or corrosion, but minimal leaks or blockages
RED: Ductwork has significant damage or corrosion, holes, punctures, leaks, or blockages. Operation is severely impaired
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured
AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
Assy
GREEN: Fan blades are in balance and free of damage or corrosion
AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion
AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure
AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
D3050203 - Packaged A/C, Air Cooled, HW Heat
CR-5120 - Record the condition of the Coils
(Cooling)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
(Heating)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
D3050203 - Packaged A/C, Air Cooled, HW Heat
CR-5140 - Record the condition of the
Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational
AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional
Condenser
GREEN: Minimal corrosion or fouling of the condenser/coils, no damage
AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
Condenser Fan(s)
Assembly
GREEN: Motor operates properly, free of excessive noise/vibration, or overheating
AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance
GREEN: Controls function properly
Pan
GREEN: Drain Pan has minimal damage or corrosion
AMBER: Drain Pan has noticeable damage or corrosion, but no leaks
CR-5275 - Record the condition of the Duct
Connectors
GREEN: Ductwork has little to no damage or corrosion, insulation is intact and there are no holes, leaks, or blockages
AMBER: Ductwork has noticeable damage or corrosion, but minimal leaks or blockages
RED: Ductwork has significant damage or corrosion, holes, punctures, leaks, or blockages. Operation is severely impaired
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured
AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
Assy
GREEN: Fan blades are in balance and free of damage or corrosion
AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion
AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure
AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
DIRECT CONDITION RATING GUIDANCE BY METER GROUP AND UNIFORMAT
D3050210 - Packaged A/C, Water Cooled, Elec Heat
CR-5120 - Record the condition of the Coils
(Cooling)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
(Heating)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational
AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional
Condenser
GREEN: Minimal corrosion or fouling of the condenser/coils, no damage
AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
GREEN: Controls function properly
Pan
GREEN: Drain Pan has minimal damage or corrosion
AMBER: Drain Pan has noticeable damage or corrosion, but no leaks
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured
AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
Assy
GREEN: Fan blades are in balance and free of damage or corrosion
AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion
AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure
AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
D3050220 - Packaged A/C, Water Cooled, HW Heat
CR-5120 - Record the condition of the Coils
(Cooling)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
(Heating)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational
AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional
Condenser
GREEN: Minimal corrosion or fouling of the condenser/coils, no damage
AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
GREEN: Controls function properly
Pan
GREEN: Drain Pan has minimal damage or corrosion
AMBER: Drain Pan has noticeable damage or corrosion, but no leaks
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured
AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
Assy
GREEN: Fan blades are in balance and free of damage or corrosion
AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion
AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure
AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
D3050255 - Thru-Wall A/C Unit
CR-5120 - Record the condition of the Coils
(Cooling)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
(Heating)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational
AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional
Condenser
GREEN: Minimal corrosion or fouling of the condenser/coils, no damage
AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
Condenser Fan(s)
Assembly
GREEN: Motor operates properly, free of excessive noise/vibration, or overheating
AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance
GREEN: Controls function properly
Pan
GREEN: Drain Pan has minimal damage or corrosion
Fan Motor Assembly
GREEN: Motor operates properly, free of excessive noise/vibration, or overheating
AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion
AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure
AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
D3050260 - Thru-Wall Heat Pump
CR-5120 - Record the condition of the Coils
(Cooling)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
(Heating)
GREEN: Coils have minimal scaling and free of debris.
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
Compressor
GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational
AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional
Condenser
GREEN: Minimal corrosion or fouling of the condenser/coils, no damage
AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational
Condenser Fan(s)
Assembly
GREEN: Motor operates properly, free of excessive noise/vibration, or overheating
AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance
GREEN: Controls function properly
Pan
GREEN: Drain Pan has minimal damage or corrosion
Fan Motor Assembly
GREEN: Motor operates properly, free of excessive noise/vibration, or overheating
AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance
Piping/Fittings/Valves
GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion
AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure
AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
D5010906 - Panelboards
CR-5055 - Record the condition of the
Breakers/Fuses
GREEN: Breaker successfully trips when circuit is overloaded/shorted out. Fuse is not burnt out.
AMBER: Breaker has been tripped
RED: Breaker does not successfully trip when circuit is overloaded/shorted out. Fuse is burnt out.
CR-5245 - Record the
Disconnect/Safety
Switch
GREEN: Disconnect/Safety Switch is present and works properly
AMBER: None
RED: Disconnect/Safety Switch is missing or not functional
Enclosure
GREEN: Minimal damage and corrosion on Enclosure, fully secured
AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced
Wiring/Connections
GREEN: Wiring is protected/insulated and connections are secure
AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding
ATTACHMENT J-1501000-04
GENERAL DIRECT CONDITION RATING GUIDANCE