Fort_Vancouver_-_Bldg_722_Administration-_INSP_2024_0003.pdf
PDF 199 KB Posted
- Attached to
- Fort Vancouver NHS INSTALL FIRE SUPPRESSION
- Solicitation number
- 140P8325R0013
About this file
This document is a fire alarm test and inspection report for the Fort Vancouver Building 722 Administration facility located at 800 Hatheway Rd. in Vancouver, WA, conducted by Salem Fire Alarm on October 23, 2024. The comprehensive inspection was performed in accordance with state requirements and NFPA 72 Edition 2019, revealing several critical deficiencies that require immediate attention.
Key findings include two devices in the exterior southwest storage area that failed testing - a manual pull station and a smoke detector that did not report or go into alarm during the inspection. Additionally, the dialer battery has expired and needs replacement, and the AC power breaker is not locked as required by NFPA standards. The report mandates that these deficiencies be addressed, warning that unresolved issues will be reported to the local Fire Marshal's office. The system is also due for smoke detector sensitivity testing in the next year, and the report emphasizes that all previous year's unresolved deficiencies must be corrected promptly.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Salem Fire Alarm Phone: 503-364-4566
3160 22nd St SE Fax: 503-364-0617
Salem, Oregon 97302 Email: Inspections@SalemFireAlarm.com
Fort Vancouver Bldg 722- Administration
Fire Alarm Test & Inspection Performed in Accordance with State Requirements and NFPA 72 Edition 2019
800 Hatheway Rd.
Vancouver, WA 98661
Annual Test & Inspection October 23, 2024
Site Information Alarm Test Information
Site Name Date of Inspection
Site Address Lead Technician
City, State, Zip Technician
Site Contact Technician
Telephone Work Order Number
Customer Email Inspection Type
Monitoring Information Systems Interconnected Comments/Data Amount
Central Station Name Sprinkler
Telephone Elevator Recall
Account Number Fire Smoke Dampers
Operator Name Specialty Suppression
Time Placed on Test Roll Down Doors
Placed on Test By Door Holders
Password HVAC Control/Monitoring
HVAC Shutdown
Other Details
Other Details
FACP Location Dialer Manufacturer
FACP Manufacturer Dialer Model
Panel Model Lock Out Code
Pass Code Pass Code
Last Sensitivity Test Phone Line Type
120 Volt System Location
12/24 VDC System
Who Was Notified 1
2 2
3 3
4 4
System Was Normal Upon Commencement
8:45 AM
800 Hatheway Rd.
Staff
Operator
81-0305 & 83-0305
Vancouver, WA 98661
Alex Patterson
360-921-6240 alex_patterson@nps.gov
Remove NAC Wire To Silence Notification Devices While Testing
Radio
Action Technology
"1111"
Staff
Alex Patterson
Action Technology
Alex Patterson
System Information
I.T. Room, West Side AES
Notification of Inspection
7707Silent Knight
By FACP
Action Technology
503-231-1992
Contact Monitoring And Place Accounts On Test
Pre-Testing Sequence Of Operation and NAC/Controls Bypass Information
Upon Completion of Inspection
Unknown Due In 2025
Who Was Notified 1
Please Note Any Pre-Existing System Malfunctions
Staff
Prior to Inspection
Protected Premises Information
Wednesday, October 23, 2024
Annual Test & Inspection
Chance Chilson
Johnathon Greco
24086
Fort Vancouver Bldg 722- Administration mailto:alex_patterson@nps.gov mailto:alex_patterson@nps.gov mailto:alex_patterson@nps.gov
Pass/Fail Pass/Fail
Pass Pass
Pass Pass
Pass Pass
Pass Pass
Pass Pass
Pass Pass
Pass Pass
Pass Pass
Pass Pass
Pass Fail
No Pass
No Pass
Remote Dialer Testing Remote Annunciator
Manufacturer Result Fail N/A
Pass/Fail
Pass Pass/Fail
Fail Confirm Alarm Correlation N/A
Pass Lamps Tested N/A
Pass Reset Switch Functional N/A
Pass Local Sounder Operation Verified N/A
Pass Comments:
Pass/Fail
Model Number Charger Circuit Voltage N/A
Pass/Fail N/A
N/A A/C Breaker Labeled and Locked N/A
N/A N/A
N/A Ground Fault Test N/A
N/A Signal Circuit Short N/A
N/A Signal Circuit Open N/A
N/A N/A
N/A N/A
Pass/Fail
Pass Ambient
Pass Low
N/A High
Supervision Details
Zone Zone
Central Station Communication Pass / Fail
Pass
Pass
Pass
N/A
Primary Line Pass / Fail Secondary Line Pass / Fail
Pass N/A
Pass N/A
N/A N/A
Secondary Communication Means N/A
Central Station
Line Trouble at Central Station Within 4 Minutes
N/A
SIgnal Type
Visuals Model Number
Supervising Station Testing
Facility Supervising Station Type
Primary Communication Means One Way Radio
RJ31/RJ38x Wired to Seize Line/Dedicated LineRJ31/RJ38x Wired to Seize Line/Dedicated Line
Line Trouble at Central Station Within 4 Minutes
DACT Troubles/Supervisory's Confirmed at CS
Trip & Restoral at Central Station Match Zone Listing
RJ31/RJ38 Mounted Outside FACP
Battery Load Test A/H (right)
Amplifier Output Voltage
A/V Model Number
Comments/Data Decibel Levels
EST
EG1F-VM
Sufficient Notification Coverage
Strobe Synchronization Verified
Audible/Visuals Tested W/O A/C
Battery Expiration Date
Battery Load Test A/H (left)
Panel Sounder & LEDs
Local Trouble Signal Within 4 Minutes Local Trouble Signal Within 4 Minutes
A/C Breaker Location
Voice Evacuation System
Zone List Details
SIgnal Type
Speakers Tested W/O A/C
Comments/Data
Fire Fighter Phone Jacks Tested
11 AH
Charger Circuit Voltage
Battery A/H Size
13.81 VDC
12V 10.5AH
8/10/2024
12.96 VDC
Quantity
As Built Drawing On Site
Ground Fault Detection
Signal Circuit Open
Signal Circuit Short
Copy Of Program On Site
Speaker Wattage
Manufacturer
Battery Expiration Date
Comments/Data
7 AH
Primary AC Voltage
AC Breaker Labeled and Locked
System Operating Voltage
Model Number
Location/s
AES
Comments/Data
Comments/Data
Voice Clarity & Volume
Phone Handsets Test & Quantity
Ground Status/Type
Battery Voltage (AC off) RB
Battery Voltage (AC off) LB
24 VDC
Battery A/H Size
Device Information
SE Office Pnl Ckt #7
12V 7AH
A/C Breaker Location
Labeled Not Locked
120 VAC
Status of Circuit's Supervision
Notification Appliances
Model Number
Battery Load Test Voltage
Battery Load Test A/H
Comments
F.A.C.P. Controls & Notification
Fire Alarm Control Panel
Comments/Data
7/11/2028
Comments/Data
AC Power on - LED
Battery Expiration Date
Reset/Lamp Test
Supervisory - LED
Alarm LED
System Trouble - LED
90 Second or Less End to End Transmission to CS
Panel Sounder
N/A
Comments
Manufacturer
Battery A/H Size
12.78 VDC
12.97 VDC
6.8 AH
Charger Circuit Voltage
Battery Load Test A/H (left)
Battery Load Test A/H (right)
27.54 VDC
EST- SIGA-278System Sensor- 569X
System Sensor- 5601P
MFG Date: 1/2022
EST- SIGA-PS
System Sensor- 2W-B
Sensitivity Range: Various
Silent Knight
DUCT DETECTOR MODEL #
N/A
SMOKE MODEL #
FACP MAKE/MODEL # DIALER MAKE/MODEL # POWER SUPPLIES MODEL #
AES
STROBES MODEL #
EST
N/A
HEAT MODEL #
N/A
HORN STROBE MODEL #
EST
EG1F-VM
PULLS MODEL #
10/23/2024
0 Device Type
Address
/ Zone Location
Visual
Inspect
Function
Test
Factory
Sensitivity
Sens.
P/F
Overall
P/F Comments & Details
1 Smoke Detector Exterior SW Storage Pass Fail Fail Did Not Report/Go In Alarm
2 Manual Pull Station Exterior SW Storage Pass Fail Fail Did Not Report/Go In Alarm
3 Manual Pull Station Z3 Office By FACP Rm Exit Pass Pass Pass
4 Manual Pull Station Z3 Exterior North Storage Pass Pass Pass
5 Smoke Detector Z3 Exterior North Storage Pass Pass Pass
6 Heat Detector Z3 Above FACP Pass Pass Pass
7 Smoke Detector Z3 Office By FACP Rm Pass Pass Pass
8 Smoke Detector Z3 Conference Rm West Pass Pass Pass
9 Smoke Detector Z3 Conference Rm East Pass Pass Pass
10 Smoke Detector Z3 Office By Conference Rm West Pass Pass Pass
11 Smoke Detector Z3 Office By Conference Rm East Pass Pass Pass
12 Smoke Detector Z3 Above Reception Pass Pass Pass
13 Smoke Detector Z3 Kitchen Pass Pass Pass
14 Manual Pull Station Z3 East Entrance Pass Pass Pass
15 Smoke Detector Z3 Office By East Entrance Pass Pass Pass EOL
16 Smoke Detector Z3 Office By Reception Pass Pass Pass
17 Smoke Detector Z3 Administration Office Pass Pass Pass
Search: Type here to search
Initiating and Supervising Devices Tested
800 Hatheway Rd. Vancouver, WA 98661Fort Vancouver Bldg 722- Administration
Device Untested Passed Failed Totals
0 11 1
0 0 0
0 1 0
0 3 1
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 1 0
0 0 1
0 0 0
0 0 0
0 0 0
Location Size Date
Replace
Date Date
Passed Failed Totals
Strobe(s)
Horn / Strobe Combo(s) 5 5
Speaker(s)
Speaker Strobes Combo(s)
Bell(s) 1 1
Horn(s)
Fire Fighter Phone(s)
Heat Detector(s)
Manual Pull Station(s)
Duct Detector(s)
Valve Tamper(s)
Pressure Switch
Manual Release(s) 0
Waterflow(S)
Device Count Summary
12Smoke Detector(s)
10/23/24Fort Vancouver Bldg 722- Administration Vancouver, WA 98661800 Hatheway Rd.
Power Supply(s)
Monitor Module(s)
UV/IR Detector(s)
Linear Heat Detection/Thermal Wire
Abort Station(s)
Beam Detector(s)
Control Module(s)
Dialer(s)
Onboard Relay Contacts
Relay Module(s) 0
Battery Information
Location
Replace
Date
Notification Appliances
Size
Vancouver, WA 98661 10/23/2024
Manufacturer Model
2 EST SIGA-278
3 EST SIGA-PS
4 12V 10.5AH (x1)
Salem Fire Alarm Suggests the Following Additions to the System
The system is due for smoke detector sensitivity testing next year per NFPA 72, 14.4.4.3.3.
Per state requirements, all system deficiencies that are not repaired will be reported to the local Fire Marshal's/AHJ's office.
See recommendations at the bottom of the page.
All Of Last Year's Deficiencies Went Unamended, With No
Notice Of When They Will Be Fixed
Replace the Battery per NFPA 72, 14.4.3.2[9.c.1].Battery in the Dialer failed due to expiration.
Add a lock to the breaker per NFPA 72, 10.6.5.4.
Manual Pull Station In Exterior SW Storage Did Not Report Or Go
In Alarm While Testing
Smoke Detector In Exterior SW Storage Did Not Report Or Go In
Deficiencies Shall Be Amended per NFPA 72 14.2.2.2.2
Summary Of Deficiencies From Inspection
Recommended ActionNoncompliant Details
Have A Technician Troubleshoot/Replace Device
Have A Technician Troubleshoot/Replace Device
Alarm While Testing
Breaker for the AC power is not locked.
800 Hatheway Rd.Fort Vancouver Bldg 722- Administration
File details come from the government source that posted it. Updated .