Fort_Vancouver_-_Bldg_722_Administration-_INSP_2024_0003.pdf

PDF 199 KB Posted

Attached to
Fort Vancouver NHS INSTALL FIRE SUPPRESSION
Solicitation number
140P8325R0013
Issued by

About this file

This document is a fire alarm test and inspection report for the Fort Vancouver Building 722 Administration facility located at 800 Hatheway Rd. in Vancouver, WA, conducted by Salem Fire Alarm on October 23, 2024. The comprehensive inspection was performed in accordance with state requirements and NFPA 72 Edition 2019, revealing several critical deficiencies that require immediate attention.

Key findings include two devices in the exterior southwest storage area that failed testing - a manual pull station and a smoke detector that did not report or go into alarm during the inspection. Additionally, the dialer battery has expired and needs replacement, and the AC power breaker is not locked as required by NFPA standards. The report mandates that these deficiencies be addressed, warning that unresolved issues will be reported to the local Fire Marshal's office. The system is also due for smoke detector sensitivity testing in the next year, and the report emphasizes that all previous year's unresolved deficiencies must be corrected promptly.

View the file

Other files

File Type Posted
Sol_140P8325R0013_Amd_0003.pdf PDF
FAS_ITM_Bldg_733_Jan_2017_0003.pdf PDF
Building_Descriptions_FOVA_Fire_Sprinkler_Att_2-AMENDED_(2)_0003.docx DOCX document
B09_Questions_for_140P8325R0013_Forth_Vancouver_NHS_Install_Fire_Suppression_Install_0003.docx DOCX document
Fort_Vancouver_-_Bldg_704_Project_Office-_INSP_2024_0003.pdf PDF
Fort_Vancouver_-_Bldg_721_Auditorium___Gym_-_INSP_2024_0003.pdf PDF
Sol_140P8325R0013_Amd_0002.pdf PDF
A07_FOVA_Fire_Sprinkler_Att_2_Plans_attachment_4-AMENDED_0001.pdf PDF
Sol_140P8325R0013_Amd_0001.pdf PDF
B11__Site_Walk_Attendance_0001.jpg JPG image
_FOVA_Fire_Sprinkler_Att_2-AMENDED_0001.docx DOCX document
Sol_140P8325R0013.pdf PDF
A07_FOVA_Fire_Sprinkler_Att_2_Plans_attachment_4.pdf PDF
A06_FOVA_Fire_Sprinkler_Att_2_attachment_2.docx DOCX document
B08_Relevant_Project_Experience_Questionnaire_attachment_9.docx DOCX document
A03_-_Construction_Contract_Administration_attachment___7.docx DOCX document
A07_FOVA_Fire_Sprinkler_Att_1_Plans_attachment_3.pdf PDF
B03_WA20250120_05_23_2025_SAM_attacment_6.pdf PDF
B08_Limitations_on_Subcontracting_Worksheet_Attchment_10.xlsx XLSX spreadsheet
A04_FOVA_Fire_Sprinkler_SOW_attachment_1.docx DOCX document
B08_ContractPriceSchedule_attachment_5.xlsx XLSX spreadsheet
B08_Offeror_s_representations_and_certificates_to_be_provided_with_proposal_Attachment_11.pdf PDF
B08_PAST_PERFORMANCE_QUESTIONNAIRE_Attachment_8.docx DOCX document
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Salem Fire Alarm Phone: 503-364-4566

3160 22nd St SE Fax: 503-364-0617

Salem, Oregon 97302 Email: Inspections@SalemFireAlarm.com

Fort Vancouver Bldg 722- Administration

Fire Alarm Test & Inspection Performed in Accordance with State Requirements and NFPA 72 Edition 2019

800 Hatheway Rd.

Vancouver, WA 98661

Annual Test & Inspection October 23, 2024

Site Information Alarm Test Information

Site Name Date of Inspection

Site Address Lead Technician

City, State, Zip Technician

Site Contact Technician

Telephone Work Order Number

Customer Email Inspection Type

Monitoring Information Systems Interconnected Comments/Data Amount

Central Station Name Sprinkler

Telephone Elevator Recall

Account Number Fire Smoke Dampers

Operator Name Specialty Suppression

Time Placed on Test Roll Down Doors

Placed on Test By Door Holders

Password HVAC Control/Monitoring

HVAC Shutdown

Other Details

Other Details

FACP Location Dialer Manufacturer

FACP Manufacturer Dialer Model

Panel Model Lock Out Code

Pass Code Pass Code

Last Sensitivity Test Phone Line Type

120 Volt System Location

12/24 VDC System

Who Was Notified 1

2 2

3 3

4 4

System Was Normal Upon Commencement

8:45 AM

800 Hatheway Rd.

Staff

Operator

81-0305 & 83-0305

Vancouver, WA 98661

Alex Patterson

360-921-6240 alex_patterson@nps.gov

Remove NAC Wire To Silence Notification Devices While Testing

Radio

Action Technology

"1111"

Staff

Alex Patterson

Action Technology

Alex Patterson

System Information

I.T. Room, West Side AES

Notification of Inspection

7707Silent Knight

By FACP

Action Technology

503-231-1992

Contact Monitoring And Place Accounts On Test

Pre-Testing Sequence Of Operation and NAC/Controls Bypass Information

Upon Completion of Inspection

Unknown Due In 2025

Who Was Notified 1

Please Note Any Pre-Existing System Malfunctions

Staff

Prior to Inspection

Protected Premises Information

Wednesday, October 23, 2024

Annual Test & Inspection

Chance Chilson

Johnathon Greco

24086

Fort Vancouver Bldg 722- Administration mailto:alex_patterson@nps.gov mailto:alex_patterson@nps.gov mailto:alex_patterson@nps.gov

Pass/Fail Pass/Fail

Pass Pass

Pass Pass

Pass Pass

Pass Pass

Pass Pass

Pass Pass

Pass Pass

Pass Pass

Pass Pass

Pass Fail

No Pass

No Pass

Remote Dialer Testing Remote Annunciator

Manufacturer Result Fail N/A

Pass/Fail

Pass Pass/Fail

Fail Confirm Alarm Correlation N/A

Pass Lamps Tested N/A

Pass Reset Switch Functional N/A

Pass Local Sounder Operation Verified N/A

Pass Comments:

Pass/Fail

Model Number Charger Circuit Voltage N/A

Pass/Fail N/A

N/A A/C Breaker Labeled and Locked N/A

N/A N/A

N/A Ground Fault Test N/A

N/A Signal Circuit Short N/A

N/A Signal Circuit Open N/A

N/A N/A

N/A N/A

Pass/Fail

Pass Ambient

Pass Low

N/A High

Supervision Details

Zone Zone

Central Station Communication Pass / Fail

Pass

Pass

Pass

N/A

Primary Line Pass / Fail Secondary Line Pass / Fail

Pass N/A

Pass N/A

N/A N/A

Secondary Communication Means N/A

Central Station

Line Trouble at Central Station Within 4 Minutes

N/A

SIgnal Type

Visuals Model Number

Supervising Station Testing

Facility Supervising Station Type

Primary Communication Means One Way Radio

RJ31/RJ38x Wired to Seize Line/Dedicated LineRJ31/RJ38x Wired to Seize Line/Dedicated Line

Line Trouble at Central Station Within 4 Minutes

DACT Troubles/Supervisory's Confirmed at CS

Trip & Restoral at Central Station Match Zone Listing

RJ31/RJ38 Mounted Outside FACP

Battery Load Test A/H (right)

Amplifier Output Voltage

A/V Model Number

Comments/Data Decibel Levels

EST

EG1F-VM

Sufficient Notification Coverage

Strobe Synchronization Verified

Audible/Visuals Tested W/O A/C

Battery Expiration Date

Battery Load Test A/H (left)

Panel Sounder & LEDs

Local Trouble Signal Within 4 Minutes Local Trouble Signal Within 4 Minutes

A/C Breaker Location

Voice Evacuation System

Zone List Details

SIgnal Type

Speakers Tested W/O A/C

Comments/Data

Fire Fighter Phone Jacks Tested

11 AH

Charger Circuit Voltage

Battery A/H Size

13.81 VDC

12V 10.5AH

8/10/2024

12.96 VDC

Quantity

As Built Drawing On Site

Ground Fault Detection

Signal Circuit Open

Signal Circuit Short

Copy Of Program On Site

Speaker Wattage

Manufacturer

Battery Expiration Date

Comments/Data

7 AH

Primary AC Voltage

AC Breaker Labeled and Locked

System Operating Voltage

Model Number

Location/s

AES

Comments/Data

Comments/Data

Voice Clarity & Volume

Phone Handsets Test & Quantity

Ground Status/Type

Battery Voltage (AC off) RB

Battery Voltage (AC off) LB

24 VDC

Battery A/H Size

Device Information

SE Office Pnl Ckt #7

12V 7AH

A/C Breaker Location

Labeled Not Locked

120 VAC

Status of Circuit's Supervision

Notification Appliances

Model Number

Battery Load Test Voltage

Battery Load Test A/H

Comments

F.A.C.P. Controls & Notification

Fire Alarm Control Panel

Comments/Data

7/11/2028

Comments/Data

AC Power on - LED

Battery Expiration Date

Reset/Lamp Test

Supervisory - LED

Alarm LED

System Trouble - LED

90 Second or Less End to End Transmission to CS

Panel Sounder

N/A

Comments

Manufacturer

Battery A/H Size

12.78 VDC

12.97 VDC

6.8 AH

Charger Circuit Voltage

Battery Load Test A/H (left)

Battery Load Test A/H (right)

27.54 VDC

EST- SIGA-278System Sensor- 569X

System Sensor- 5601P

MFG Date: 1/2022

EST- SIGA-PS

System Sensor- 2W-B

Sensitivity Range: Various

Silent Knight

DUCT DETECTOR MODEL #

N/A

SMOKE MODEL #

FACP MAKE/MODEL # DIALER MAKE/MODEL # POWER SUPPLIES MODEL #

AES

STROBES MODEL #

EST

N/A

HEAT MODEL #

N/A

HORN STROBE MODEL #

EST

EG1F-VM

PULLS MODEL #

10/23/2024

0 Device Type

Address

/ Zone Location

Visual

Inspect

Function

Test

Factory

Sensitivity

Sens.

P/F

Overall

P/F Comments & Details

1 Smoke Detector Exterior SW Storage Pass Fail Fail Did Not Report/Go In Alarm

2 Manual Pull Station Exterior SW Storage Pass Fail Fail Did Not Report/Go In Alarm

3 Manual Pull Station Z3 Office By FACP Rm Exit Pass Pass Pass

4 Manual Pull Station Z3 Exterior North Storage Pass Pass Pass

5 Smoke Detector Z3 Exterior North Storage Pass Pass Pass

6 Heat Detector Z3 Above FACP Pass Pass Pass

7 Smoke Detector Z3 Office By FACP Rm Pass Pass Pass

8 Smoke Detector Z3 Conference Rm West Pass Pass Pass

9 Smoke Detector Z3 Conference Rm East Pass Pass Pass

10 Smoke Detector Z3 Office By Conference Rm West Pass Pass Pass

11 Smoke Detector Z3 Office By Conference Rm East Pass Pass Pass

12 Smoke Detector Z3 Above Reception Pass Pass Pass

13 Smoke Detector Z3 Kitchen Pass Pass Pass

14 Manual Pull Station Z3 East Entrance Pass Pass Pass

15 Smoke Detector Z3 Office By East Entrance Pass Pass Pass EOL

16 Smoke Detector Z3 Office By Reception Pass Pass Pass

17 Smoke Detector Z3 Administration Office Pass Pass Pass

Search: Type here to search

Initiating and Supervising Devices Tested

800 Hatheway Rd. Vancouver, WA 98661Fort Vancouver Bldg 722- Administration

Device Untested Passed Failed Totals

0 11 1

0 0 0

0 1 0

0 3 1

0 0 0

0 0 0

0 0 0

0 0 0

0 0 0

0 0 0

0 0 0

0 0 0

0 0 0

0 0 0

0 1 0

0 0 1

0 0 0

0 0 0

0 0 0

Location Size Date

Replace

Date Date

Passed Failed Totals

Strobe(s)

Horn / Strobe Combo(s) 5 5

Speaker(s)

Speaker Strobes Combo(s)

Bell(s) 1 1

Horn(s)

Fire Fighter Phone(s)

Heat Detector(s)

Manual Pull Station(s)

Duct Detector(s)

Valve Tamper(s)

Pressure Switch

Manual Release(s) 0

Waterflow(S)

Device Count Summary

12Smoke Detector(s)

10/23/24Fort Vancouver Bldg 722- Administration Vancouver, WA 98661800 Hatheway Rd.

Power Supply(s)

Monitor Module(s)

UV/IR Detector(s)

Linear Heat Detection/Thermal Wire

Abort Station(s)

Beam Detector(s)

Control Module(s)

Dialer(s)

Onboard Relay Contacts

Relay Module(s) 0

Battery Information

Location

Replace

Date

Notification Appliances

Size

Vancouver, WA 98661 10/23/2024

Manufacturer Model

2 EST SIGA-278

3 EST SIGA-PS

4 12V 10.5AH (x1)

Salem Fire Alarm Suggests the Following Additions to the System

The system is due for smoke detector sensitivity testing next year per NFPA 72, 14.4.4.3.3.

Per state requirements, all system deficiencies that are not repaired will be reported to the local Fire Marshal's/AHJ's office.

See recommendations at the bottom of the page.

All Of Last Year's Deficiencies Went Unamended, With No

Notice Of When They Will Be Fixed

Replace the Battery per NFPA 72, 14.4.3.2[9.c.1].Battery in the Dialer failed due to expiration.

Add a lock to the breaker per NFPA 72, 10.6.5.4.

Manual Pull Station In Exterior SW Storage Did Not Report Or Go

In Alarm While Testing

Smoke Detector In Exterior SW Storage Did Not Report Or Go In

Deficiencies Shall Be Amended per NFPA 72 14.2.2.2.2

Summary Of Deficiencies From Inspection

Recommended ActionNoncompliant Details

Have A Technician Troubleshoot/Replace Device

Have A Technician Troubleshoot/Replace Device

Alarm While Testing

Breaker for the AC power is not locked.

800 Hatheway Rd.Fort Vancouver Bldg 722- Administration