Fort_Vancouver_-_Bldg_721_Auditorium___Gym_-_INSP_2024_0003.pdf

PDF 196 KB Posted

Attached to
Fort Vancouver NHS INSTALL FIRE SUPPRESSION
Solicitation number
140P8325R0013
Issued by

About this file

This document is an annual fire alarm test and inspection report for Fort Vancouver Building 721's Auditorium/Gym, conducted by Salem Fire Alarm on October 17, 2024. The inspection revealed several critical deficiencies, including expired heat detectors in the basement (three devices from Chemetronics and Chemetron manufactured in 2002 and 1982) and a failed dialer battery. The report recommends replacing the heat detectors in accordance with NFPA 72 section 14.4.3.2, replacing the dialer battery, and addressing previously unresolved system issues. Salem Fire Alarm notes that if deficiencies are not corrected, they will be reported to the local Fire Marshal's office, and the system is due for smoke detector sensitivity testing in the next inspection cycle.

The inspection covered multiple system components, including smoke detectors, manual pull stations, and notification appliances. Two smoke detectors in the gym (north and south) passed visual and functional tests, as did three manual pull stations. However, the heat detectors in the basement (south, north, and boiler room) failed due to expiration. The report includes detailed technical information such as device manufacturers (Silent Knight, Wheelock, System Sensor), battery specifications, and communication system details. The facility is located at 1501 E. Evergreen Blvd in Vancouver, WA, and the site contact is Alex Patterson, who can be reached at 360-921-6240 or alex_patterson@nps.gov.

View the file

Other files

File Type Posted
Sol_140P8325R0013_Amd_0003.pdf PDF
FAS_ITM_Bldg_733_Jan_2017_0003.pdf PDF
Building_Descriptions_FOVA_Fire_Sprinkler_Att_2-AMENDED_(2)_0003.docx DOCX document
B09_Questions_for_140P8325R0013_Forth_Vancouver_NHS_Install_Fire_Suppression_Install_0003.docx DOCX document
Fort_Vancouver_-_Bldg_722_Administration-_INSP_2024_0003.pdf PDF
Fort_Vancouver_-_Bldg_704_Project_Office-_INSP_2024_0003.pdf PDF
Sol_140P8325R0013_Amd_0002.pdf PDF
A07_FOVA_Fire_Sprinkler_Att_2_Plans_attachment_4-AMENDED_0001.pdf PDF
Sol_140P8325R0013_Amd_0001.pdf PDF
B11__Site_Walk_Attendance_0001.jpg JPG image
_FOVA_Fire_Sprinkler_Att_2-AMENDED_0001.docx DOCX document
Sol_140P8325R0013.pdf PDF
A07_FOVA_Fire_Sprinkler_Att_2_Plans_attachment_4.pdf PDF
A06_FOVA_Fire_Sprinkler_Att_2_attachment_2.docx DOCX document
B08_Relevant_Project_Experience_Questionnaire_attachment_9.docx DOCX document
A03_-_Construction_Contract_Administration_attachment___7.docx DOCX document
A07_FOVA_Fire_Sprinkler_Att_1_Plans_attachment_3.pdf PDF
B03_WA20250120_05_23_2025_SAM_attacment_6.pdf PDF
B08_Limitations_on_Subcontracting_Worksheet_Attchment_10.xlsx XLSX spreadsheet
A04_FOVA_Fire_Sprinkler_SOW_attachment_1.docx DOCX document
B08_ContractPriceSchedule_attachment_5.xlsx XLSX spreadsheet
B08_Offeror_s_representations_and_certificates_to_be_provided_with_proposal_Attachment_11.pdf PDF
B08_PAST_PERFORMANCE_QUESTIONNAIRE_Attachment_8.docx DOCX document
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Salem Fire Alarm Phone: 503-364-4566

3160 22nd St SE Fax: 503-364-0617

Salem, Oregon 97302 Email: Inspections@SalemFireAlarm.com

Performed in Accordance with State Requirements and NFPA 72 Edition 2019

1501 E. Evergreen Blvd Vancouver, WA 98661

Annual Test & Inspection October 17, 2024

Fort Vancouver Bldg 721-

Auditorium/Gym

Fire Alarm Test & Inspection

Site Information Alarm Test Information

Site Name Date of Inspection

Site Address Lead Technician

City, State, Zip Technician

Site Contact Technician

Telephone Work Order Number

Customer Email Inspection Type

Monitoring Information Systems Interconnected Comments/Data Amount

Central Station Name Sprinkler

Telephone Elevator Recall

Account Number Fire Smoke Dampers

Operator Name Specialty Suppression

Time Placed on Test Roll Down Doors

Placed on Test By Door Holders

Password HVAC Control/Monitoring

HVAC Shutdown

Other Details

Other Details

FACP Location Dialer Manufacturer

FACP Manufacturer Dialer Model

Panel Model Lock Out Code

Pass Code Pass Code

Last Sensitivity Test Phone Line Type

120 Volt System Location

12/24 VDC System

Who Was Notified 1

2 2

3 3

4 4

System Was Normal Upon Commencement

Protected Premises Information

Thursday, October 17, 2024

Annual Test & Inspection

Chance Chilson

Johnathon Greco

24086

Fort Vancouver Bldg 721- Auditorium/Gym

Contact Monitoring And Place Accounts On Test

Pre-Testing Sequence Of Operation and NAC/Controls Bypass Information

Upon Completion of Inspection

Unknown Due In 2025

Who Was Notified 1

Please Note Any Pre-Existing System Malfunctions

Prior to Inspection

Action Technology

503-231-1992

AES

Notification of Inspection

7788FSilent Knight

1st Fl SW Rm By Gym

Radio

Action Technology

Alex Patterson

Action Technology

Alex Patterson

System Information

Basement, S Wall of Large Room

Remove NAC Wire (Terminal 34) To Silence Notification During Testing

9:00 AM

1501 E. Evergreen Blvd

Staff

Operator

81-0308/84-0308

Vancouver, WA 98661

Alex Patterson

360-921-6240 alex_patterson@nps.gov mailto:alex_patterson@nps.gov mailto:alex_patterson@nps.gov mailto:alex_patterson@nps.gov

Pass/Fail Pass/Fail

Pass Pass

Pass Pass

Pass Pass

Pass Pass

Pass Pass

Pass Pass

Pass Pass

Pass Pass

Pass Pass

Pass Pass

No Pass

No Pass

Remote Dialer Testing Remote Annunciator

Manufacturer Result Fail 1

Pass/Fail

Pass Pass/Fail

Fail Confirm Alarm Correlation Pass

Pass Lamps Tested Pass

Fail Reset Switch Functional Pass

Pass Local Sounder Operation Verified Pass

Pass Comments:

Pass/Fail

Model Number Charger Circuit Voltage N/A

Pass/Fail N/A

N/A A/C Breaker Labeled and Locked N/A

N/A N/A

N/A Ground Fault Test N/A

N/A Signal Circuit Short N/A

N/A Signal Circuit Open N/A

N/A N/A

N/A N/A

Pass/Fail

Pass Ambient

Pass Low

N/A High

Supervision Details

Zone Zone

Central Station Communication Pass / Fail

Pass

Pass

Pass

N/A

Primary Line Pass / Fail Secondary Line Pass / Fail

Pass N/A

Pass N/A

N/A N/A

Reset/Lamp Test

Supervisory - LED

Alarm LED

System Trouble - LED

90 Second or Less End to End Transmission to CS

Panel Sounder

N/A

Comments

Manufacturer

Battery A/H Size

12.65 VDC

12.67 VDC

7.6 AH

Charger Circuit Voltage

Battery Load Test A/H (left)

Battery Load Test A/H (right)

27.30 VDC

F.A.C.P. Controls & Notification

Fire Alarm Control Panel

Comments/Data

11/2/2027

Comments/Data

AC Power on - LED

Battery Expiration Date

Battery Voltage (AC off) RB

Battery Voltage (AC off) LB

24 VDC

Battery A/H Size

Device Information

Basement Pnl Ckt #19

12V 7AH

A/C Breaker Location

Locked & Labeled

120 VAC

Status of Circuit's Supervision

Notification Appliances

Model Number

Battery Load Test Voltage

Battery Load Test A/H

East Exit Of Gym

Comments

Silent Knight- 52307788F

Battery Expiration Date

Comments/Data

7.6 AH

Primary AC Voltage

AC Breaker Labeled and Locked

System Operating Voltage

Model Number

Location/s

AES

Comments/Data

Comments/Data

Voice Clarity & Volume

Phone Handsets Test & Quantity

Ground Status/Type

Speaker Wattage

Manufacturer

Quantity

As Built Drawing On Site

Ground Fault Detection

Signal Circuit Open

Signal Circuit Short

Copy Of Program On Site

Fire Fighter Phone Jacks Tested

2.5 AH

Charger Circuit Voltage

Battery A/H Size

13.79 VDC

12V 8AH

6/3/2020

12.75 VDC

Battery Expiration Date

Battery Load Test A/H (left)

Panel Sounder & LEDs

Local Trouble Signal Within 4 Minutes Local Trouble Signal Within 4 Minutes

A/C Breaker Location

Voice Evacuation System

Zone List Details

SIgnal Type

Speakers Tested W/O A/C

Comments/Data

Battery Load Test A/H (right)

Amplifier Output Voltage

A/V Model Number

Comments/Data Decibel Levels

Wheelock

MT-24-LSM

Sufficient Notification Coverage

Strobe Synchronization Verified

Audible/Visuals Tested W/O A/C

RJ31/RJ38x Wired to Seize Line/Dedicated LineRJ31/RJ38x Wired to Seize Line/Dedicated Line

Line Trouble at Central Station Within 4 Minutes

DACT Troubles/Supervisory's Confirmed at CS

Trip & Restoral at Central Station Match Zone Listing

RJ31/RJ38 Mounted Outside FACP

Secondary Communication Means N/A

Central Station

Line Trouble at Central Station Within 4 Minutes

N/A

SIgnal Type

Visuals Model Number

Supervising Station Testing

Facility Supervising Station Type

Primary Communication Means One Way Radio

Silent Knight

DUCT DETECTOR MODEL #

N/A

SMOKE MODEL #

FACP MAKE/MODEL # DIALER MAKE/MODEL # POWER SUPPLIES MODEL #

AES

7788F

STROBES MODEL #

Wheelock

N/A

HEAT MODEL #

N/A

HORN STROBE MODEL #

Wheelock

MT-24-LSM

PULLS MODEL #

System Sensor- 1400

Sensitivity Range:

Chemetronics- 601 MFG: 5/2002

Chemetron- 601 MFG: 12/1982

MFG Date: Various

Edwards- 270 SPO

10/17/2024

0 Device Type

Address

/ Zone Location

Visual

Inspect

Function

Test

Factory

Sensitivity

Sens.

P/F

Overall

P/F Comments & Details

1 Smoke Detector Z4 Gym North Pass Pass Pass

2 Smoke Detector Z4 Gym South Pass Pass Pass

3 Manual Pull Station Z4 Gym South Pass Pass Pass No Glass Rod

4 Manual Pull Station Z4 Gym North Pass Pass Pass

5 Manual Pull Station Z4 Front Entry Pass Pass Pass

6 Heat Detector Z5 Basement South Fail Pass Fail Expired

7 Heat Detector Z5 Basement North Fail Pass Fail Expired

8 Heat Detector Z3 Basement Boiler Rm Fail Pass Fail EOL- Expired

27 12.75 VDC

28 2.5 AH

29 13.79 VDC

Search: Type here to search

Initiating and Supervising Devices Tested

1501 E. Evergreen Blvd Vancouver, WA 98661Fort Vancouver Bldg 721- Auditorium/Gym

Device Untested Passed Failed Totals

0 2 0

0 0 0

0 0 3

0 3 0

0 0 0

0 0 0

0 0 0

0 0 0

0 0 0

0 0 0

0 0 0

0 0 0

0 0 0

0 0 0

0 1 0

0 0 1

0 0 0

0 0 0

0 0 0

Location Size Date

Replace

Date Date

Passed Failed Totals

Strobe(s)

Horn / Strobe Combo(s) 2 2

Speaker(s)

Speaker Strobes Combo(s)

Bell(s)

Horn(s)

Notification Appliances

Size

Battery Information

Location

Replace

Date

Control Module(s)

Dialer(s)

Onboard Relay Contacts

Relay Module(s) 0

Power Supply(s)

Monitor Module(s)

UV/IR Detector(s)

Linear Heat Detection/Thermal Wire

Abort Station(s)

Beam Detector(s)

Device Count Summary

2Smoke Detector(s)

10/17/24Fort Vancouver Bldg 721- Auditorium/Gym Vancouver, WA 986611501 E. Evergreen Blvd

Fire Fighter Phone(s)

Heat Detector(s)

Manual Pull Station(s)

Duct Detector(s)

Valve Tamper(s)

Pressure Switch

Manual Release(s) 0

Waterflow(S)

Vancouver, WA 98661 10/17/2024

Manufacturer Model

2 12V 8AH

3 Chemetronics 601

Mfg: 5/2002

Chemetron 601

Mfg: 12/1982

Summary Of Deficiencies From Inspection

Recommended ActionNoncompliant Details

Replace the heat detectors per NFPA 72, 14.4.3.2[17.d.3].

Replace the Batteries per NFPA 72, 14.4.3.2[9.c.1].

All The Heat Detectors Failed Due To Expiration

Most Of Last Year's Deficiencies Went Unamended, With No

Notice Of When They Will Be Fixed.

1501 E. Evergreen BlvdFort Vancouver Bldg 721- Auditorium/Gym

Deficiencies Shall Be Amended per NFPA 72 14.2.2.2.2.

The Battery In The Dialer Failed Due Its Expiration And Load Test

See recommendations at the bottom of the page.

Per state requirements, all system deficiencies that are not repaired will be reported to the local Fire Marshal's/AHJ's office.

Salem Fire Alarm Suggests the Following Additions to the System

The system is due for smoke detector sensitivity testing next year per NFPA 72, 14.4.4.3.3.