Fort_Vancouver_-_Bldg_721_Auditorium___Gym_-_INSP_2024_0003.pdf
PDF 196 KB Posted
- Attached to
- Fort Vancouver NHS INSTALL FIRE SUPPRESSION
- Solicitation number
- 140P8325R0013
About this file
This document is an annual fire alarm test and inspection report for Fort Vancouver Building 721's Auditorium/Gym, conducted by Salem Fire Alarm on October 17, 2024. The inspection revealed several critical deficiencies, including expired heat detectors in the basement (three devices from Chemetronics and Chemetron manufactured in 2002 and 1982) and a failed dialer battery. The report recommends replacing the heat detectors in accordance with NFPA 72 section 14.4.3.2, replacing the dialer battery, and addressing previously unresolved system issues. Salem Fire Alarm notes that if deficiencies are not corrected, they will be reported to the local Fire Marshal's office, and the system is due for smoke detector sensitivity testing in the next inspection cycle.
The inspection covered multiple system components, including smoke detectors, manual pull stations, and notification appliances. Two smoke detectors in the gym (north and south) passed visual and functional tests, as did three manual pull stations. However, the heat detectors in the basement (south, north, and boiler room) failed due to expiration. The report includes detailed technical information such as device manufacturers (Silent Knight, Wheelock, System Sensor), battery specifications, and communication system details. The facility is located at 1501 E. Evergreen Blvd in Vancouver, WA, and the site contact is Alex Patterson, who can be reached at 360-921-6240 or alex_patterson@nps.gov.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Salem Fire Alarm Phone: 503-364-4566
3160 22nd St SE Fax: 503-364-0617
Salem, Oregon 97302 Email: Inspections@SalemFireAlarm.com
Performed in Accordance with State Requirements and NFPA 72 Edition 2019
1501 E. Evergreen Blvd Vancouver, WA 98661
Annual Test & Inspection October 17, 2024
Fort Vancouver Bldg 721-
Auditorium/Gym
Fire Alarm Test & Inspection
Site Information Alarm Test Information
Site Name Date of Inspection
Site Address Lead Technician
City, State, Zip Technician
Site Contact Technician
Telephone Work Order Number
Customer Email Inspection Type
Monitoring Information Systems Interconnected Comments/Data Amount
Central Station Name Sprinkler
Telephone Elevator Recall
Account Number Fire Smoke Dampers
Operator Name Specialty Suppression
Time Placed on Test Roll Down Doors
Placed on Test By Door Holders
Password HVAC Control/Monitoring
HVAC Shutdown
Other Details
Other Details
FACP Location Dialer Manufacturer
FACP Manufacturer Dialer Model
Panel Model Lock Out Code
Pass Code Pass Code
Last Sensitivity Test Phone Line Type
120 Volt System Location
12/24 VDC System
Who Was Notified 1
2 2
3 3
4 4
System Was Normal Upon Commencement
Protected Premises Information
Thursday, October 17, 2024
Annual Test & Inspection
Chance Chilson
Johnathon Greco
24086
Fort Vancouver Bldg 721- Auditorium/Gym
Contact Monitoring And Place Accounts On Test
Pre-Testing Sequence Of Operation and NAC/Controls Bypass Information
Upon Completion of Inspection
Unknown Due In 2025
Who Was Notified 1
Please Note Any Pre-Existing System Malfunctions
Prior to Inspection
Action Technology
503-231-1992
AES
Notification of Inspection
7788FSilent Knight
1st Fl SW Rm By Gym
Radio
Action Technology
Alex Patterson
Action Technology
Alex Patterson
System Information
Basement, S Wall of Large Room
Remove NAC Wire (Terminal 34) To Silence Notification During Testing
9:00 AM
1501 E. Evergreen Blvd
Staff
Operator
81-0308/84-0308
Vancouver, WA 98661
Alex Patterson
360-921-6240 alex_patterson@nps.gov mailto:alex_patterson@nps.gov mailto:alex_patterson@nps.gov mailto:alex_patterson@nps.gov
Pass/Fail Pass/Fail
Pass Pass
Pass Pass
Pass Pass
Pass Pass
Pass Pass
Pass Pass
Pass Pass
Pass Pass
Pass Pass
Pass Pass
No Pass
No Pass
Remote Dialer Testing Remote Annunciator
Manufacturer Result Fail 1
Pass/Fail
Pass Pass/Fail
Fail Confirm Alarm Correlation Pass
Pass Lamps Tested Pass
Fail Reset Switch Functional Pass
Pass Local Sounder Operation Verified Pass
Pass Comments:
Pass/Fail
Model Number Charger Circuit Voltage N/A
Pass/Fail N/A
N/A A/C Breaker Labeled and Locked N/A
N/A N/A
N/A Ground Fault Test N/A
N/A Signal Circuit Short N/A
N/A Signal Circuit Open N/A
N/A N/A
N/A N/A
Pass/Fail
Pass Ambient
Pass Low
N/A High
Supervision Details
Zone Zone
Central Station Communication Pass / Fail
Pass
Pass
Pass
N/A
Primary Line Pass / Fail Secondary Line Pass / Fail
Pass N/A
Pass N/A
N/A N/A
Reset/Lamp Test
Supervisory - LED
Alarm LED
System Trouble - LED
90 Second or Less End to End Transmission to CS
Panel Sounder
N/A
Comments
Manufacturer
Battery A/H Size
12.65 VDC
12.67 VDC
7.6 AH
Charger Circuit Voltage
Battery Load Test A/H (left)
Battery Load Test A/H (right)
27.30 VDC
F.A.C.P. Controls & Notification
Fire Alarm Control Panel
Comments/Data
11/2/2027
Comments/Data
AC Power on - LED
Battery Expiration Date
Battery Voltage (AC off) RB
Battery Voltage (AC off) LB
24 VDC
Battery A/H Size
Device Information
Basement Pnl Ckt #19
12V 7AH
A/C Breaker Location
Locked & Labeled
120 VAC
Status of Circuit's Supervision
Notification Appliances
Model Number
Battery Load Test Voltage
Battery Load Test A/H
East Exit Of Gym
Comments
Silent Knight- 52307788F
Battery Expiration Date
Comments/Data
7.6 AH
Primary AC Voltage
AC Breaker Labeled and Locked
System Operating Voltage
Model Number
Location/s
AES
Comments/Data
Comments/Data
Voice Clarity & Volume
Phone Handsets Test & Quantity
Ground Status/Type
Speaker Wattage
Manufacturer
Quantity
As Built Drawing On Site
Ground Fault Detection
Signal Circuit Open
Signal Circuit Short
Copy Of Program On Site
Fire Fighter Phone Jacks Tested
2.5 AH
Charger Circuit Voltage
Battery A/H Size
13.79 VDC
12V 8AH
6/3/2020
12.75 VDC
Battery Expiration Date
Battery Load Test A/H (left)
Panel Sounder & LEDs
Local Trouble Signal Within 4 Minutes Local Trouble Signal Within 4 Minutes
A/C Breaker Location
Voice Evacuation System
Zone List Details
SIgnal Type
Speakers Tested W/O A/C
Comments/Data
Battery Load Test A/H (right)
Amplifier Output Voltage
A/V Model Number
Comments/Data Decibel Levels
Wheelock
MT-24-LSM
Sufficient Notification Coverage
Strobe Synchronization Verified
Audible/Visuals Tested W/O A/C
RJ31/RJ38x Wired to Seize Line/Dedicated LineRJ31/RJ38x Wired to Seize Line/Dedicated Line
Line Trouble at Central Station Within 4 Minutes
DACT Troubles/Supervisory's Confirmed at CS
Trip & Restoral at Central Station Match Zone Listing
RJ31/RJ38 Mounted Outside FACP
Secondary Communication Means N/A
Central Station
Line Trouble at Central Station Within 4 Minutes
N/A
SIgnal Type
Visuals Model Number
Supervising Station Testing
Facility Supervising Station Type
Primary Communication Means One Way Radio
Silent Knight
DUCT DETECTOR MODEL #
N/A
SMOKE MODEL #
FACP MAKE/MODEL # DIALER MAKE/MODEL # POWER SUPPLIES MODEL #
AES
7788F
STROBES MODEL #
Wheelock
N/A
HEAT MODEL #
N/A
HORN STROBE MODEL #
Wheelock
MT-24-LSM
PULLS MODEL #
System Sensor- 1400
Sensitivity Range:
Chemetronics- 601 MFG: 5/2002
Chemetron- 601 MFG: 12/1982
MFG Date: Various
Edwards- 270 SPO
10/17/2024
0 Device Type
Address
/ Zone Location
Visual
Inspect
Function
Test
Factory
Sensitivity
Sens.
P/F
Overall
P/F Comments & Details
1 Smoke Detector Z4 Gym North Pass Pass Pass
2 Smoke Detector Z4 Gym South Pass Pass Pass
3 Manual Pull Station Z4 Gym South Pass Pass Pass No Glass Rod
4 Manual Pull Station Z4 Gym North Pass Pass Pass
5 Manual Pull Station Z4 Front Entry Pass Pass Pass
6 Heat Detector Z5 Basement South Fail Pass Fail Expired
7 Heat Detector Z5 Basement North Fail Pass Fail Expired
8 Heat Detector Z3 Basement Boiler Rm Fail Pass Fail EOL- Expired
27 12.75 VDC
28 2.5 AH
29 13.79 VDC
Search: Type here to search
Initiating and Supervising Devices Tested
1501 E. Evergreen Blvd Vancouver, WA 98661Fort Vancouver Bldg 721- Auditorium/Gym
Device Untested Passed Failed Totals
0 2 0
0 0 0
0 0 3
0 3 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 1 0
0 0 1
0 0 0
0 0 0
0 0 0
Location Size Date
Replace
Date Date
Passed Failed Totals
Strobe(s)
Horn / Strobe Combo(s) 2 2
Speaker(s)
Speaker Strobes Combo(s)
Bell(s)
Horn(s)
Notification Appliances
Size
Battery Information
Location
Replace
Date
Control Module(s)
Dialer(s)
Onboard Relay Contacts
Relay Module(s) 0
Power Supply(s)
Monitor Module(s)
UV/IR Detector(s)
Linear Heat Detection/Thermal Wire
Abort Station(s)
Beam Detector(s)
Device Count Summary
2Smoke Detector(s)
10/17/24Fort Vancouver Bldg 721- Auditorium/Gym Vancouver, WA 986611501 E. Evergreen Blvd
Fire Fighter Phone(s)
Heat Detector(s)
Manual Pull Station(s)
Duct Detector(s)
Valve Tamper(s)
Pressure Switch
Manual Release(s) 0
Waterflow(S)
Vancouver, WA 98661 10/17/2024
Manufacturer Model
2 12V 8AH
3 Chemetronics 601
Mfg: 5/2002
Chemetron 601
Mfg: 12/1982
Summary Of Deficiencies From Inspection
Recommended ActionNoncompliant Details
Replace the heat detectors per NFPA 72, 14.4.3.2[17.d.3].
Replace the Batteries per NFPA 72, 14.4.3.2[9.c.1].
All The Heat Detectors Failed Due To Expiration
Most Of Last Year's Deficiencies Went Unamended, With No
Notice Of When They Will Be Fixed.
1501 E. Evergreen BlvdFort Vancouver Bldg 721- Auditorium/Gym
Deficiencies Shall Be Amended per NFPA 72 14.2.2.2.2.
The Battery In The Dialer Failed Due Its Expiration And Load Test
See recommendations at the bottom of the page.
Per state requirements, all system deficiencies that are not repaired will be reported to the local Fire Marshal's/AHJ's office.
Salem Fire Alarm Suggests the Following Additions to the System
The system is due for smoke detector sensitivity testing next year per NFPA 72, 14.4.4.3.3.