Fort_Vancouver_-_Bldg_704_Project_Office-_INSP_2024_0003.pdf
PDF 197 KB Posted
- Attached to
- Fort Vancouver NHS INSTALL FIRE SUPPRESSION
- Solicitation number
- 140P8325R0013
About this file
This document is an annual fire alarm test and inspection report for the Fort Vancouver Building 704 Project Office, conducted by Salem Fire Alarm on October 15, 2024. The comprehensive inspection was performed in accordance with state requirements and NFPA 72 Edition 2019, covering various fire alarm system components including smoke detectors, heat detectors, manual pull stations, and notification appliances.
The inspection revealed several deficiencies that require immediate attention: an expired heat detector in the restroom, batteries in the Fire Alarm Control Panel (FACP) that failed due to expiration, a dialer battery that failed its load test, and an AC power breaker that was not locked. The report recommends replacing the expired heat detector, replacing batteries per NFPA 72 guidelines, and adding a lock to the AC power breaker. Salem Fire Alarm also noted that the system is due for smoke detector sensitivity testing in the following year, and warned that unaddressed deficiencies may be reported to the local Fire Marshal's office.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Salem Fire Alarm Phone: 503-364-4566
3160 22nd St SE Fax: 503-364-0617
Salem, Oregon 97302 Email: Inspections@SalemFireAlarm.com
Performed in Accordance with State Requirements and NFPA 72 Edition 2019
988 E. McClellan Rd.
Vancouver, WA 98661
Annual Test & Inspection October 15, 2024
Fort Vancouver Bldg 704- Project Office
Fire Alarm Test & Inspection
Site Information Alarm Test Information
Site Name Date of Inspection
Site Address Lead Technician
City, State, Zip Technician
Site Contact Technician
Telephone Work Order Number
Customer Email Inspection Type
Monitoring Information Systems Interconnected Comments/Data Amount
Central Station Name Sprinkler
Telephone Elevator Recall
Account Number Fire Smoke Dampers
Operator Name Specialty Suppression
Time Placed on Test Roll Down Doors
Placed on Test By Door Holders
Password HVAC Control/Monitoring
HVAC Shutdown
Other Details
Other Details
FACP Location Dialer Manufacturer
FACP Manufacturer Dialer Model
Panel Model Lock Out Code
Pass Code Pass Code
Last Sensitivity Test Phone Line Type
120 Volt System Location
12/24 VDC System
Who Was Notified 1
2 2
3 3
4 4
System Was Normal Upon Commencement
Protected Premises Information
Tuesday, October 15, 2024
Annual Test & Inspection
Chance Chilson
Isaiah Aguero
24086
Fort Vancouver Bldg 704- Project Office
Contact Monitoring And Place Accounts On Test
Pre-Testing Sequence Of Operation and NAC/Controls Bypass Information
Upon Completion of Inspection
Unknown Due In 2025
Who Was Notified 1
Please Note Any Pre-Existing System Malfunctions
Staff
Prior to Inspection
Action Technology
503-231-1992
AES
Notification of Inspection
7788FDMP
XR500
By FACP
Radio
Action Technology
Staff
Alex Patterson
Action Technology
Alex Patterson
System Information
Office Closet Mech Rm
Use Bell Silence Toggle Switch To Silence Notification During Testing
Use DMP Keypad At Front Entrance To Silence And Reset Sensors
12:00 PM
988 E. McClellan Rd.
Staff
Operator
81-0307/83-0307
Vancouver, WA 98661
Alex Patterson
360-921-6240 alex_patterson@nps.gov mailto:alex_patterson@nps.gov mailto:alex_patterson@nps.gov mailto:alex_patterson@nps.gov
Pass/Fail Pass/Fail
Pass Pass
Pass Fail
Pass Pass
Pass Pass
N/A Pass
N/A Pass
N/A Pass
N/A Pass
N/A Pass
N/A Fail
No Pass
No Pass
Remote Dialer Testing Remote Annunciator
Manufacturer Result Fail 1
Pass/Fail
Pass Pass/Fail
Pass Confirm Alarm Correlation Pass
Pass Lamps Tested Pass
Fail Reset Switch Functional Pass
Pass Local Sounder Operation Verified Pass
Pass Comments:
Pass/Fail
Model Number Charger Circuit Voltage N/A
Pass/Fail N/A
N/A A/C Breaker Labeled and Locked N/A
N/A N/A
N/A Ground Fault Test N/A
N/A Signal Circuit Short N/A
N/A Signal Circuit Open N/A
N/A N/A
N/A N/A
Pass/Fail
Pass Ambient
Pass Low
N/A High
Supervision Details
Zone Zone
Central Station Communication Pass / Fail
Pass
Pass
Pass
N/A
Primary Line Pass / Fail Secondary Line Pass / Fail
Pass N/A
Pass N/A
N/A N/A
Reset/Lamp Test
Supervisory - LED
Alarm LED
System Trouble - LED
90 Second or Less End to End Transmission to CS
Panel Sounder
N/A
Comments
Manufacturer
Battery A/H Size
12.59 VDC
12.69 VDC
7.8 AH
Charger Circuit Voltage
Battery Load Test A/H (left)
Battery Load Test A/H (right)
27.42 VDC
F.A.C.P. Controls & Notification
Fire Alarm Control Panel
Comments/Data
10/18/2024
Comments/Data
AC Power on - LED
Battery Expiration Date
Battery Voltage (AC off) RB
Battery Voltage (AC off) LB
24 VDC
Battery A/H Size
Device Information
NW Office Pnl Ckt #1
12V 7AH
A/C Breaker Location
Labeled Not Locked
120 VAC
Status of Circuit's Supervision
Notification Appliances
Model Number
Code 5665 To Silence And Reset
Battery Load Test Voltage
Battery Load Test A/H
Front Entrance
Comments
DMP- XR1507788F
Battery Expiration Date
Comments/Data
7.9 AH
Primary AC Voltage
AC Breaker Labeled and Locked
System Operating Voltage
Model Number
Location/s
AES
Comments/Data
Comments/Data
Voice Clarity & Volume
Phone Handsets Test & Quantity
Ground Status/Type
Speaker Wattage
Manufacturer
Quantity
As Built Drawing On Site
Ground Fault Detection
Signal Circuit Open
Signal Circuit Short
Copy Of Program On Site
Fire Fighter Phone Jacks Tested
2.5 AH
Charger Circuit Voltage
Battery A/H Size
13.70 VDC
12V 9AH
3/1/2025
12.91 VDC
Battery Expiration Date
Battery Load Test A/H (left)
Panel Sounder & LEDs
Local Trouble Signal Within 4 Minutes Local Trouble Signal Within 4 Minutes
A/C Breaker Location
Voice Evacuation System
Zone List Details
SIgnal Type
Speakers Tested W/O A/C
Comments/Data
Battery Load Test A/H (right)
Amplifier Output Voltage
A/V Model Number
Comments/Data Decibel Levels
System Sensor
P2R
Sufficient Notification Coverage
Strobe Synchronization Verified
Audible/Visuals Tested W/O A/C
RJ31/RJ38x Wired to Seize Line/Dedicated LineRJ31/RJ38x Wired to Seize Line/Dedicated Line
Line Trouble at Central Station Within 4 Minutes
DACT Troubles/Supervisory's Confirmed at CS
Trip & Restoral at Central Station Match Zone Listing
RJ31/RJ38 Mounted Outside FACP
Secondary Communication Means N/A
Central Station
Line Trouble at Central Station Within 4 Minutes
SR
SIgnal Type
Visuals Model Number
Supervising Station Testing
Facility Supervising Station Type
Primary Communication Means One Way Radio
DMP
XR500
DUCT DETECTOR MODEL #
N/A
SMOKE MODEL #
FACP MAKE/MODEL # DIALER MAKE/MODEL # POWER SUPPLIES MODEL #
AES
7788F
STROBES MODEL #
System Sensor
SR
HEAT MODEL #
N/A
HORN STROBE MODEL #
System Sensor
P2R
PULLS MODEL #
System Sensor- 2W-B
Sensitivity Range: 1%-4%ft
Chemtronics- 601 Mfg:5/2002
System Sensor- 5602 Mfg:2/2014
MFG Date:
Bosch- FMM-100SA TK
10/15/2024
0 Device Type
Address
/ Zone Location
Visual
Inspect
Function
Test
Factory
Sensitivity
Sens.
P/F
Overall
P/F Comments & Details
1 Smoke Detector Z09 Rear West Office Pass Pass Pass
2 Smoke Detector Z09 West Open Office Pass Pass Pass
3 Heat Detector Z09 Above FACP Pass Pass Pass
4 Manual Pull Station Z02 By FACP Pass Pass Pass
5 Heat Detector Z10 Restroom Fail Pass Fail Expired
6 Smoke Detector Z10 Front Entry/By R/R Pass Pass Pass
7 Manual Pull Station Z01 Front Entry/By R/R Pass Pass Pass
8 Smoke Detector Z10 East Hall Pass Pass Pass
9 Smoke Detector Z10 East Hall West Office Pass Pass Pass
10 Smoke Detector Z10 East Hall East Office Pass Pass Pass
Search: Type here to search
Initiating and Supervising Devices Tested
988 E. McClellan Rd. Vancouver, WA 98661Fort Vancouver Bldg 704- Project Office
Device Untested Passed Failed Totals
0 6 0
0 0 0
0 1 1
0 2 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 1 0
0 0 1
0 0 0
0 0 0
0 0 0
Location Size Date
Replace
Date Date
Passed Failed Totals
Strobe(s) 4 4
Horn / Strobe Combo(s) 2 2
Speaker(s)
Speaker Strobes Combo(s)
Bell(s)
Horn(s) 1 1
Notification Appliances
Size
Battery Information
Location
Replace
Date
Control Module(s)
Dialer(s)
Onboard Relay Contacts
Relay Module(s) 0
Power Supply(s)
Monitor Module(s)
UV/IR Detector(s)
Linear Heat Detection/Thermal Wire
Abort Station(s)
Beam Detector(s)
Device Count Summary
6Smoke Detector(s)
10/15/24Fort Vancouver Bldg 704- Project Office Vancouver, WA 98661988 E. McClellan Rd.
Fire Fighter Phone(s)
Heat Detector(s)
Manual Pull Station(s)
Duct Detector(s)
Valve Tamper(s)
Pressure Switch
Manual Release(s) 0
Waterflow(S)
Vancouver, WA 98661 10/15/2024
Manufacturer Model
2 Chemtronics 601
Mfg:5/2002
3 12V 7AH
4 12V 9AH
Summary Of Deficiencies From Inspection
Recommended ActionNoncompliant Details
Replace the Battery per NFPA 72, 14.4.3.2[9.c.1].
Replace the heat detector per NFPA 72, 14.4.3.2[17.d.3].
Replace the Batteries per NFPA 72, 14.4.3.2[9.c.1].
Battery in the Dialer failed it's load test.
Breaker for the AC power is not locked.
988 E. McClellan Rd.Fort Vancouver Bldg 704- Project Office
Add a lock to the breaker per NFPA 72, 10.6.5.4.
Heat Detector In Restroom Is Expired
Batteries in the FACP failed due to expiration.
Deficiencies Shall Be Amended per NFPA 72 14.2.2.2.2None Of Last Year's Deficiencies Were Amended Since Last
See recommendations at the bottom of the page.
Annual Inspection, With No Notice Of When They Will Be Fixed.
Per state requirements, all system deficiencies that are not repaired will be reported to the local Fire Marshal's/AHJ's office.
Salem Fire Alarm Suggests the Following Additions to the System
The system is due for smoke detector sensitivity testing next year per NFPA 72, 14.4.4.3.3.