This document appears to be an Instrument List related to a federal contract opportunity for the rehabilitation of the El Portal Wastewater Treatment Facility and Administrative Camp in Yosemite National Park, California. The Instrument List provides detailed information on various instruments, sensors, and controls that will be part of the rehabilitated wastewater treatment facility, including level indicators, flow meters, pressure gauges, and air flow monitors. Key details include the instrument tag numbers, function, process connection details, and the associated process and instrumentation diagrams. The federal contract opportunity, solicitation number 140P2025R0008, is for the construction of this project, which will replace the 45-year-old wastewater treatment facility and rehabilitate the former El Portal Trailer Village to serve as workforce housing and a contractor staging area. The work is being procured by the Department of the Interior, National Park Service.
View the file
Other files
Show 40 more
Latest 50 of 87 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Tag No. Function Accessory Tag 1 Loop Title Component Code Instrument Name Process Range /
Set Point
ENGINEERING
UNITS
Process Connection Panel Number Installation
Details P&ID
010-AE-105 LEL 010-AIT-105 Headworks Building LEL A10 Combustible Gas Element and Transmitter % 010-LCP-100 Manufacturer STD 08-N-100
010-FE-101 010-FIT-101 Headworks Raw Water Feed Flow F4 Flow Element and Transmitter, Electromagnetic 0 to 2000 gpm 10" Flange, 150# 010-LCP-100 4091-211A 08-N-100
010-LSHH-122 Manual Bar Screen High High Level Switch L18 Level Switch, Non-Mercury 0 to 4.5 ft 010-LCP-100 4091-248 08-N-100
010-LE/LT-113 010-LI-113 Headworks Open Channel Level L29 Level Element/Transmitter and Indicator, Radar 0 to 4.5 ft 4" Slip-on flange with 3" antenna 010-LCP-100 4091-263, 4091-
383 08-N-100
010-LE/LT-114 010-LI-114 Headworks Open Channel Wet Well Level L29 Level Element/Transmitter and Indicator, Radar 0 to 4.5 ft 4" Slip-on flange with 3" antenna 010-LCP-100 4091-263, 4091-
383 08-N-100
010-PI-101 010-PE-101 MHO Feed Pressure Indicator with Diaphragm Seal P4 Pressure Gauge with Diaphragm Seal 0 to 30 psig 1/2" NPT 4091-304, 4091- 305 08-N-100
010-PI-102 Plant Water Feed to Rotary Drum Screen pressure Indicator P4 Pressure Gauge 0 to 40 psig 1/2" NPT 4091-304, 4091- 305 08-N-100
010-TE/TT-103 Headworks electrical Room Temperature T100 Temperature Sensor, Wall Mount 0 to 120 Deg F 010-LCP-100 08-N-101 010-PI-107 Plant Air to Grit Washer pressure Indicator P4 Pressure Gauge 0 to 70 psig 1/2" NPT 4091-304, 4091-
305 08-N-101
011-PI-104 Plant Water pressure supply pressure Indicator P4 Pressure Gauge 0 to 120 psig 1/2" NPT 4091-304, 4091- 305 08-N-110
011-PI-303 Plant Water pressure supply pressure Indicator P4 Pressure Gauge 0 to 120 psig 1/2" NPT 4091-304, 4091- 305 08-N-111
011-LE/LT-300 011-LI-300 Existing Septage Receiving Tank Level, Outdoor L29 Level Element/Transmitter and Indicator, Radar 0 to 15 ft 4" Slip-on flange with 3" antenna 011-LCP-400 4091-263, 4091-
383 08-N-111
011-PI-311 011-PE-311 Septage Discharge Pump 1 Suction Pressure Indicator P4 Pressure Gauge with Annular Seal 0 to 50 psig 2" Flanged, 150# 4091-304A 08-N-111 011-PI-312 Septage Discharge Pump 1 Discharge Pressure Indicator P4 Pressure Gauge 0 to 50 psig 1/2" NPT 4091-304A 08-N-111 011-PSH-312 011-PE-312 Septage Discharge Pump 1 Discharge Pressure High Alarm P7 Pressure Switch with Annular Seal Set @ 50 psig 2" Flanged, 150# 011-LCP-300 4091-304A 08-N-111 011-PI-321 011-PE-321 Septage Discharge Pump 2 Suction Pressure Indicator P4 Pressure Gauge with Annular Seal 0 to 50 psig 2" Flanged, 150# 4091-304A 08-N-111 011-PI-322 Septage Discharge Pump 2 Discharge Pressure Indicator P4 Pressure Gauge 0 to 50 psig 1/2" NPT 4091-304A 08-N-111 011-PSH-322 011-PE-322 Septage Discharge Pump 2 Discharge Pressure High Alarm P7 Pressure Switch with Annular Seal Set @ 50 psig 2" Flanged, 150# 011-LCP-300 4091-304A 08-N-111 011-FE-304 011-FIT-304 Septage Discharge Pumps Discharge header Flow, Outdoor F4 Flow Element and Transmitter, Electromagnetic 0 to 50 gpm 2" Flange, 150# 011-LCP-400 4091-211, 4091-
383, 4091-384 08-N-111
015-FE-101 015-FIT-101 Bioreactor 1 Feed Flow, Outdoor F4 Flow Element and Transmitter, Electromagnetic 0 to 800 gpm 6" Flange, 150# 010-LCP-100 4091-211, 4091- 383, 4091-384 08-N-150
015-LE/LT-111 015-LI-111 Bioreactor 1 Effluent Pump Station Level, Outdoor L29 Level Element/Transmitter and Indicator, Radar 0 to 20 ft 4" Slip-on flange with 3" antenna 010-LCP-100 4091-263, 4091-
383 08-N-150
015-PI-112 015-PE-112 Bioreactor 1 Pump 1 Discharge P4 Pressure Gauge with Annular Seal 0 to 50 psig 4" Flange, 150# 4091-304A 08-N-150 015-PI-122 015-PE-122 Bioreactor 1 Pump 2 Discharge P4 Pressure Gauge with Annular Seal 0 to 50 psig 4" Flange, 150# 4091-304A 08-N-150 015-PI-105 MHO Feed to Headwork Effluent Pump Station Inlet channel
Pressure Indicator P4 Pressure Gauge 0 to 150 psig 1/2" NPT 4091-304, 4091- 305 08-N-150
015-FE-201 015-FIT-201 Bioreactor 2 Feed Flow, Outdoor F4 Flow Element and Transmitter, Electromagnetic 0 to 800 gpm 6" Flange, 150# 010-LCP-100 4091-211, 4091- 383, 4091-384 08-N-151
015-LE/LT-211 015-LI-211 Bioreactor 2 Effluent Pump Station Level, Outdoor L29 Level Element/Transmitter and Indicator, Radar 0 to 20 ft 4" Slip-on flange with 3" antenna 010-LCP-100 4091-263, 4091-
383 08-N-151
015-PI-212 015-PE-212 Bioreactor 2 Pump 1 Discharge P4 Pressure Gauge with annular Seal 0 to 50 psig 4" Flange, 150# 4091-304A 08-N-151 015-PI-222 015-PE-222 Bioreactor 2 Pump 2 Discharge P4 Pressure Gauge with annular Seal 0 to 50 psig 4" Flange, 150# 4091-304A 08-N-151 015-FE-301 015-FIT-301 Bioreactor 3 Feed Flow, Outdoor F4 Flow Element and Transmitter, Electromagnetic 0 to 800 gpm 6" Flange, 150# 010-LCP-100 4091-211, 4091-
383, 4091-384 08-N-152
015-LE/LT-311 015-LI-311 Bioreactor 3 Effluent Pump Station Level, Outdoor L29 Level Element/Transmitter and Indicator, Radar 0 to 20 ft 4" Slip-on flange with 3" antenna 010-LCP-100 4091-263, 4091-
383 08-N-152
015-PI-312 015-PE-312 Bioreactor 3 Pump 1 Discharge pressure indicator P4 Pressure Gauge with annular Seal 0 to 50 psig 4" Flange, 150# 4091-304A 08-N-152 015-PI-322 015-PE-322 Bioreactor 3 Pump 2 Discharge pressure indicator P4 Pressure Gauge with annular Seal 0 to 50 psig 4" Flange, 150# 4091-304A 08-N-152
015-LE/LT-102 015-LI-102 Bioreactor 1 Reaeration Zone 1-3 Level, Outdoor L29 Level Element/Transmitter and Indicator, Radar 0 to 30 ft 4" Slip-on flange with 3" antenna 010-LCP-100 4091-263, 4091-
383 08-N-153
015-FE-108 015-FIT-108 Bioreactor 1 Aerobic Zone 1-2 Air Flow Rate 1, Outdoor F51 Flow Element and Transmitter, Thermal Mass Flow 0 to 600 SCFM 1" NPT 010-LCP-100 4091-217, 4091- 383, 4091-384 08-N-153
015-AE-109 DO 015-AIT-109 Bioreactor 1 Aerobic Zone 1-2 Dissolved Oxygen 1 A20 Dissolved Oxygen Element and Transmitter 0 to 5 mg/L 010-LCP-100 4091-162, 4091- 384, 4091-385 08-N-153
015-FE-112 015-FIT-112 Bioreactor 1 Aerobic Zone 1-2 Air Flow Rate 2, Outdoor F51 Flow Element and Transmitter, Thermal Mass Flow 0 to 300 SCFM 1" NPT 010-LCP-100 4091-217, 4091- 383, 4091-384 08-N-153
INSTRUMENT LIST
YOSE 196416
PW\DEN003\D3167637
INSTRUMENTATION AND
CONTROL FOR PROCESS SYSTEMS
40 90 00 SUPPLEMENT - 1
AMENDMENT
Set Point
ENGINEERING
UNITS
Process Connection Panel Number Installation
Details P&ID
INSTRUMENT LIST
015-AE-113 DO 015-AIT-113 Bioreactor 1 Aerobic Zone 1-2 Dissolved Oxygen 2 A20 Dissolved Oxygen Element and Transmitter 0 to 5 mg/L 010-LCP-100 4091-162, 4091- 384, 4091-385 08-N-153
015-FE-115 015-FIT-115 Bioreactor 1 Reaeration Zone 1-3 Air Flow Rate, Outdoor F51 Flow Element and Transmitter, Thermal Mass Flow with 2" Flanged spool piece 0 to 200 SCFM 2" Flange 010-LCP-100 Manufacturer STD 08-N-153
015-AE-116 DO 015-AIT-116 Bioreactor 1 Reaeration Zone 1-3 Dissolved Oxygen, Outdoor A20 Dissolved Oxygen Element and Transmitter 0 to 5 mg/L 010-LCP-100 4091-162, 4091-
384, 4091-385 08-N-153
015-FE-150 015-FIT-150 Bioreactor 1 MLR Pump Discharge Flow F4 Flow Element and Transmitter, Electromagnetic.
Straight Pipe: 0 x DN upstream and 0 x DN downstream 0 to 1000 gpm 8" Flange, 150# 010-LCP-100 4091-211, 4091-
383 08-N-153
015-LT-160 Bioreactor SCUM Pit Level, Outdoor L42 Level Element and Transmitter,Submersible 0 to 10 ft 010-LCP-100 4091-250 08-N-153 015-PI-160 015-PE-160 Bioreactor SCUM Pit Sump Pump Discharge pressure P4 Pressure Gauge with Diaphragm Seal 0 to 25 psig 1/2" NPT 4091-304B 08-N-153
015--FSL-150 Bioreactor 1 MLR Pump Seal Low Flow Alarm F23 Flow Element and Switch 0 to 20 gpm 3/4" NPT 015-AFD-150 Manufacturer STD 08-N-153
015-LE/LT-202 015-LI-202 Bioreactor 2 Reaeration Zone 2-3 Level, Outdoor L29 Level Element/Transmitter and Indicator, Radar 0 to 30 ft 4" Slip-on flange with 3" antenna 010-LCP-100 4091-263, 4091-
383 08-N-154
015-FE-208 015-FIT-208 Bioreactor 2 Aerobic Zone 2-2 Air Flow Rate 1, Outdoor F51 Flow Element and Transmitter, Thermal Mass Flow 0 to 600 SCFM 1" NPT 010-LCP-100 4091-217, 4091- 383, 4091-384 08-N-154
015-AE-209 DO 015-AIT-209 Bioreactor 2 Aerobic Zone 2-2 Dissolved Oxygen 1, Outdoor A20 Dissolved Oxygen Element and Transmitter 0 to 5 mg/L 010-LCP-100 4091-162, 4091- 384, 4091-385 08-N-154
015-FE-212 015-FIT-212 Bioreactor 2 Aerobic Zone 2-2 Air Flow Rate 2 F51 Flow Element and Transmitter, Thermal Mass Flow 0 to 300 SCFM 1" NPT 010-LCP-100 4091-217, 4091- 383, 4091-384 08-N-154
015-AE-213 DO 015-AIT-213 Bioreactor 2 Aerobic Zone 2-2 Dissolved Oxygen 2, Outdoor A20 Dissolved Oxygen Element and Transmitter 0 to 5 mg/L 010-LCP-100 4091-162, 4091- 384, 4091-385 08-N-154
015-FE-215 015-FIT-215 Bioreactor 2 Reaeration Zone 2-3 Air Flow Rate F51 Flow Element and Transmitter, Thermal Mass Flow with 2" Flanged spool piece 0 to 200 SCFM 2" Flange 010-LCP-100 Manufacturer STD 08-N-154
015-AE-216 DO 015-AIT-216 Bioreactor 2 Reaeration Zone 2-3 Dissolved Oxygen, Outdoor A20 Dissolved Oxygen Element and Transmitter 0 to 5 mg/L 010-LCP-100 4091-162, 4091-
384, 4091-385 08-N-154
015-FE-250 015-FIT-250 Bioreactor 2 MLR Pump Discharge Flow F4 Flow Element and Transmitter, Electromagnetic.
Straight Pipe: 0 x DN upstream and 0 x DN downstream 0 to 1000 gpm 8" Flange, 150# 010-LCP-100 4091-211, 4091-
383 08-N-154
015--FSL-250 Bioreactor 2 MLR Pump Seal Low Flow Alarm F23 Flow Element and Switch 0 to 20 gpm 3/4" NPT 015-AFD-250 Manufacturer STD 08-N-154
015-LE/LT-302 015-LI-302 Bioreactor 3 Reaeration Zone 3-3 Level L29 Level Element/Transmitter and Indicator, Radar 0 to 30 ft 4" Slip-on flange with 3" antenna 010-LCP-100 4091-263, 4091-
383 08-N-155
015-FE-308 015-FIT-308 Bioreactor 3 Aerobic Zone 3-2 Air Flow Rate 1, Outdoor F51 Flow Element and Transmitter, Thermal Mass Flow 0 to 600 SCFM 1" NPT 010-LCP-100 4091-217, 4091- 383, 4091-384 08-N-155
015-AE-309 DO 015-AIT-309 Bioreactor 3 Aerobic Zone 3-2 Dissolved Oxygen 1, Outdoor A20 Dissolved Oxygen Element and Transmitter 0 to 5 mg/L 010-LCP-100 4091-162, 4091- 384, 4091-385 08-N-155
015-FE-312 015-FIT-312 Bioreactor 3 Aerobic Zone 3-2 Air Flow Rate 2 F51 Flow Element and Transmitter, Thermal Mass Flow 0 to 300 SCFM 1" NPT 010-LCP-100 4091-217, 4091- 383, 4091-384 08-N-155
015-AE-313 DO 015-AIT-313 Bioreactor 3 Aerobic Zone 3-2 Dissolved Oxygen 2, Outdoor A20 Dissolved Oxygen Element and Transmitter 0 to 5 mg/L 010-LCP-100 4091-162, 4091- 384, 4091-385 08-N-155
015-FE-315 015-FIT-315 Bioreactor 3 Reaeration Zone 3-3 Air Flow Rate F51 Flow Element and Transmitter, Thermal Mass Flow with 2" Flanged spool piece 0 to 200 SCFM 2" Flange 010-LCP-100 Manufacturer STD 08-N-155
015-AE-316 DO 015-AIT-316 Bioreactor 3 Reaeration Zone 3-3 Dissolved Oxygen, Outdoor A20 Dissolved Oxygen Element and Transmitter 0 to 5 mg/L 010-LCP-100 4091-162, 4091-
384, 4091-385 08-N-155
025-LT-111 Secondary Clarifier 1 Scum Pit Level L42 Level Element and Transmitter,Submersible 0 to 6.0 ft 010-LCP-100 4091-250 08-N-251
025-PI-111 Plant water feed pressure Indicator P4 Pressure Gauge 0 to 40 psig 1/2" NPT 4091-304, 4091- 305 08-N-251
025-PI-211 Plant water feed pressure Indicator P4 Pressure Gauge 0 to 40 psig 1/2" NPT 4091-304, 4091- 305 08-N-252
025-LT-211 Secondary Clarifier 2 Scum Pit Level L42 Level Element and Transmitter,Submersible 0 to 6.0 ft 010-LCP-100 4091-250 08-N-252
025-LE/LT-101 025-LI-101 Secondary Clarifier Splitter Effluent Channel 1 Level, Outdoor L29 Level Element/Transmitter and Indicator, Radar 0 to 1000 ft 4" Slip-on flange with 3" antenna 010-LCP-100 4091-263, 4091- 383 08-N-250
025-LE/LT-102 025-LI-102 Secondary Clarifier Splitter Effluent Channel 2 Level, Outdoor L29 Level Element/Transmitter and Indicator, Radar 0 to 1000 ft 4" Slip-on flange with 3" antenna 010-LCP-100 4091-263, 4091- 383 08-N-250
INSTRUMENTATION AND
CONTROL FOR PROCESS SYSTEMS
40 90 00 SUPPLEMENT - 2
AMENDMENT
YOSE 196416
PW\DEN003\D3167637
Set Point
ENGINEERING
UNITS
Process Connection Panel Number Installation
Details P&ID
INSTRUMENT LIST
025-LE/LT-103 025-LI-103 Secondary Clarifier Splitter Effluent Channel 3 Level, Outdoor L29 Level Element/Transmitter and Indicator, Radar 0 to 1000 ft 4" Slip-on flange with 3" antenna 010-LCP-100 4091-263, 4091- 383 08-N-250
025-PI-107 ALUM Feed to Secondary Clarifier Splitter Effluent Structure P4 Pressure Gauge 0 to 30 psig 1/2" NPT 4091-304, 4091- 305 08-N-250
025-PI-108 ALUM Feed to Secondary Clarifier Splitter Effluent Structure P4 Pressure Gauge 0 to 30 psig 1/2" NPT 4091-304, 4091- 305 08-N-250
030-AE-104 TURB 030-AIT-104 Secondary Clarifier Effluent Turbidity A38 Turbidity Element and Transmitter, Inline Insertion-Mounted, Required minimum Pipe Size>4" 0.001 - 4000 NTU 2 1/2" 030-LCP-100 4091-173, 4091-
383 08-N-300
030-FE-111 030-FIT-111 Secondary Clarifier Effluent Flow to Rapid Mix Tank 1 Feed Flow F4 Flow Element and Transmitter, Electromagnetic 0 to 600 gpm 6" 030-LCP-100 4091-211, 4091-
383 08-N-300
030-LSH-110 Floc Tank 1-1 High Level Alarm L18 Level Switch, Non-Mercury Set @ EL.1705.0 ft 030-LCP-100 4091-248 08-N-300
030-PI-101 Polymer feed to Rapid Mix Tank 1 pressure Indicator 1 P4 Pressure Gauge 0 to 30 psig 1/2" NPT 4091-304, 4091- 305 08-N-300
030-PI-102 Polymer feed to Rapid Mix Tank 1 pressure Indicator 2 P4 Pressure Gauge 0 to 30 psig 1/2" NPT 4091-304, 4091- 305 08-N-300
030-PI-103 PACI feed pressure Indicator 1 P4 Pressure Gauge 0 to 30 psig 1/2" NPT 4091-304, 4091- 305 08-N-300
030-PI-104 PACI feed pressure Indicator 2 P4 Pressure Gauge 0 to 30 psig 1/2" NPT 4091-304, 4091- 305 08-N-300
030-FE-211 030-FIT-211 Secondary Effluent Flow to Rapid Mix Tank 2 Feed Flow F4 Flow Element and Transmitter, Electromagnetic 0 to 600 gpm 6" 030-LCP-100 4091-211, 4091- 383 08-N-301
030-LSH-210 Floc Tank 2-1 High Level Alarm L18 Level Switch, Non-Mercury Set @ EL.1705.0 ft 030-LCP-100 4091-248 08-N-301
030-FE-311 030-FIT-311 Secondary Effluent Flow to Rapid Mix Tank 3 Feed Flow F4 Flow Element and Transmitter, Electromagnetic 0 to 600 gpm 6" 030-LCP-100 4091-211, 4091- 383 08-N-302
030-LSH-310 Tertiary Filter Level L18 Level Switch, Non-Mercury Set @ EL.1700.0 ft 030-LCP-100 4091-248 08-N-302
015-FE-350 015-FIT-350 Bioreactor 3 MLR Pump Discharge Flow F4 Flow Element and Transmitter, Electromagnetic.
Straight Pipe: 0 x DN upstream and 0 x DN downstream 0 to 1000 gpm 8" Flange, 150# 010-LCP-100 4091-211, 4091-
383 08-N-155
015--FSL-350 Bioreactor 3 MLR Pump Seal Low Flow Alarm F23 Flow Element and Switch 0 to 20 gpm 3/4" NPT 015-AFD-350 Manufacturer STD 08-N-155 030-LIT-110 Tertiary Filters Level L10 Level Transmitter, Direct Sensing, Flange Mounted 0 to 20 Feet 3" Flange 030-LCP-100 4091-272 08-N-306
035-AE-104B TURB UV Effluent Turbidity A38 Turbidity Element, Immersion Mounted, Share Transmitter with 035-AE-104A Cable length: 50 ft extension cable with probe
0.001-4000 NTU 030-LCP-200 4091-171, 4091-
383, 4091-384 08-N-350
030-LE/LT-112 030-LI-112 Existing Backwash Holding Tank Level L29 Level Element/Transmitter and Indicator, Radar 0 to 30 ft 4" Slip-on flange with 3" antenna 030-LCP-100 4091-269, 4091-
383 08-N-312
030-FE-108 030-FIT-108 Backwash Supply Flow F6 Flow Element and Transmitter, Orifice, within Cla-Vlv package 0 to 1500 gpm 12" Flange, 150# 030-LCP-100 Manufacturer STD 08-N-312
030-FE-109 030-FIT-109 W3 Supply Flow F6 Flow Element and Transmitter, Orifice, within valve package 0 to 60 gpm 2" 030-LCP-100 Manufacturer STD 08-N-312
035-AE-104A UVT 035-AIT-104 UV Disinfection UVT and Turbidity A155 UV Element and Transmitter Cable length: 50 ft extension cable with probe 30% to 95% 035-LCP-200 4091-171, 4091-
383, 4091-384 08-N-350
035-FE-101 035-FIT-101 UV Inlet Flow F4 Flow Element and Transmitter, Electromagnetic Straight Pipe: 0 x DN upstream and 0 x DN downstream 0 to 1250 gpm 8" Flange, 150# 035-LCP-200 4091-211A 08-N-350
035-LE/LT-102 035-LI-102 UV Inlet Level L29 Level Element/Transmitter and Indicator, Radar 0 to 4 ft 4" Slip-on flange with 3" antenna 035-LCP-200 4091-263, 4091-
383 08-N-350
040-LT-111 Digester 1 Level L42 Level Element and Transmitter, Submersible 0 to 30 ft 040-LCP-100 4091-250 08-N-400
040-AE-112A DO 040-AIT-112A Digester 1 DO & ORP A20 Dissolved Oxygen Element and Transmitter 0 to 5 mg/L 040-LCP-100 4091-162, 4091- 384A, 4091-385 08-N-400
040-AE-112B ORP A5 ORP Element, Share Transmitter with 040-AE-112A -1500 to +1500 mV 040-LCP-100 4091-162 08-N-400
040-AE-112C pH/Temp 040-AIT-112C Digester 1 pH & Temp A7 pH/Temp Element and Transmitter 1 to 14 pH 040-LCP-100 4091-162, 4091- 384A, 4091-385 08-N-400
040-LT-121 Digester 2 Level L42 Level Element and Transmitter, Submersible 0 to 30 ft 040-LCP-100 4091-250 08-N-401
040-AE-122A DO 040-AIT-122A Digester 2 DO & ORP A20 Dissolved Oxygen Element and Transmitter 0 to 5 mg/L 040-LCP-100 4091-162, 4091- 384A, 4091-385 08-N-401
YOSE 196416
PW\DEN003\D3167637
INSTRUMENTATION AND
CONTROL FOR PROCESS SYSTEMS
40 90 00 SUPPLEMENT - 3
Set Point
ENGINEERING
UNITS
Process Connection Panel Number Installation
Details P&ID
INSTRUMENT LIST
040-AE-122B ORP A5 ORP Element, Share Transmitter with 040-AE-122A -1500 to +1500 mV 040-LCP-100 4091-162 08-N-401
040-AE-122C pH/Temp 040-AIT-122C Digester 2 pH & Temp A7 pH/Temp Element and Transmitter 1 to 14 pH 040-LCP-100 4091-162, 4091- 384A, 4091-385 08-N-401
040-LT-131 Digester 3 Level L42 Level Element and Transmitter, Submersible 0 to 30 ft 040-LCP-100 4091-250 08-N-402
040-AE-132A DO 040-AIT-132A Digester 3 DO & ORP A20 Dissolved Oxygen Element and Transmitter 0 to 5 mg/L 040-LCP-100 4091-162, 4091- 384A, 4091-385 08-N-402
040-AE-132B ORP Digester 3 ORP A5 ORP Element, Share Transmitter with 040-AE-132A -1500 to +1500 mV 040-LCP-100 4091-162 08-N-402
040-AE-132C pH/Temp 040-AIT-132C Digester 3 pH & Temp A7 pH/Temp Element and Transmitter 1 to 14 pH 040-LCP-100 4091-162, 4091- 384A, 4091-385 08-N-402
040-FE-301 040-FIT-301 Screw Press Feed Header Flow F4 Flow Element and Transmitter, Electromagnetic 0 to 30 gpm 2" Flange, 150# 040-LCP-100 4091-211, 4091- 383 08-N-404
040-FE-302 040-FIT-302 Polymer Feed Flow F4 Flow Element and Transmitter, Electromagnetic 0 to 30 gpm 1" 040-LCP-100 4091-211, 4091- 383 08-N-404
040-PI-301 Polymer Feed Line Pressure Indicating 1 P4 Pressure Gauge 0 to 100 psig 1/2" NPT 4091-304 08-N-404 040-PI-302 Polymer Feed Line Pressure Indicating 2 P4 Pressure Gauge 0 to 100 psig 1/2" NPT 4091-304 08-N-404 040-PI-311 040-PE-311 Dewatering Feed Pump 1 Suction Pressure Indicating P4 Pressure Gauge with annular Seal 0 to 10 psig 2" Flange, 150# 4091-304A 08-N-404 040-PI-321 040-PE-321 Dewatering Feed Pump 2 Suction Pressure Indicating P4 Pressure Gauge with annular Seal 0 to 10 psig 2" Flange, 150# 4091-304A 08-N-404 04-PSL-312 Dewatering Feed Pump 1 Suction Low Pressure Alarm P7 Pressure Switch Set @ 0 psig 1/2" NPT 040-LCP-100 4091-304A 08-N-404 04-PSL-322 Dewatering Feed Pump 2 Suction Low Pressure Alarm P7 Pressure Switch Set @ 0 psig 1/2" NPT 040-LCP-100 4091-304A 08-N-404 040-PIT-313 040-PE-313 Dewatering Feed Pump 1 Discharge Pressure P9 Pressure Element and Transmitter with annular Seal 0 to 50 psig 2" Flange, 150# 040-LCP-100 4091-303 08-N-404 040-PIT-323 040-PE-323 Dewatering Feed Pump 2 Discharge Pressure P9 Pressure Element and Transmitter with annular Seal 0 to 50 psig 2" Flange, 150# 040-LCP-100 4091-303 08-N-404 040-PSH-314 Dewatering Feed Pump 1 Discharge High Pressure Alarm P7 Pressure Switch Set @ 50 psig 1/2" NPT 040-AFD-310 4091-304 08-N-404 040-PSH-324 Dewatering Feed Pump 2 Discharge High Pressure Alarm P7 Pressure Switch Set @ 50 psig 1/2" NPT 040-AFD-320 4091-304 08-N-404 040-AE-101 LEL 040-AIT-101 Digester and Dewatering Building LEL A10 Combustible Gas Element and Transmitter 0.5 % 040-LCP-100 Manufacturer STD 08-N-405 040-PI-401 Screw Press 1 W3 Feed Pressure Indicating P4 Pressure Gauge 0 to 125 psig 1/2" NPT 4091-304 08-N-405 040-PI-402 Screw Press 2 W3 Feed Pressure Indicating P4 Pressure Gauge 0 to 125 psig 1/2" NPT 4091-304 08-N-406
040-FE-501 040-FIT-501 Dewatering Polymer Feed Pumps Discharge Flow F4 Flow Element and Transmitter, Electromagnetic 0 to 30 gpm 1" 040-LCP-100 4091-211, 4091- 383 08-N-407
040-PI-505 Dewatering W3 feed to Polymer Mixer Pressure Indicating P4 Pressure Gauge 0 to 5 psig 1/2" NPT 4091-304B 08-N-407
040-PI-506 Dewatering W3 feed to Polymer Blending Pressure Indicating P4 Pressure Gauge -1500 to +1500 psig 1/2" NPT 4091-304B 08-N-407
040-FE-601A 040-FIT-601A Digester 1 Air Manifold Air Flow Rate 1 F51 Flow Element and Transmitter, Thermal Mass Flow with 2" Flanged spool piece 0 to 215 SCFM 2" Flange 040-LCP-100 Manufacturer STD 08-N-408
040-FE-602A 040-FIT-602A Digester 1 Air Manifold Air Flow Rate 2 F51 Flow Element and Transmitter, Thermal Mass Flow, 2" Flanged spool piece 0 to 215 SCFM 2" Flange 040-LCP-100 Manufacturer STD 08-N-408
040-FE-603A 040-FIT-603A Digester 1 Air Manifold Air Flow Rate 3 F51 Flow Element and Transmitter, Thermal Mass Flow 0 to 805 SCFM 1" NPT 040-LCP-100 4091-217, 4091- 383 08-N-408
040-FE-601B 040-FIT-601B Digester 2 Air Manifold Air Flow Rate 1 F51 Flow Element and Transmitter, Thermal Mass Flow with 2" Flanged spool piece 0 to 215 SCFM 2" Flange 040-LCP-100 Manufacturer STD 08-N-408
040-FE-602B 040-FIT-602B Digester 2 Air Manifold Air Flow Rate 2 F51 Flow Element and Transmitter, Thermal Mass Flow, 2" Flanged spool piece 0 to 215 SCFM 2" Flange 040-LCP-100 Manufacturer STD 08-N-408
040-FE-603B 040-FIT-603B Digester 2 Air Manifold Air Flow Rate 3 F51 Flow Element and Transmitter, Thermal Mass Flow 0 to 805 SCFM 1" NPT 040-LCP-100 4091-217, 4091- 383 08-N-408
040-FE-601C 040-FIT-601C Digester 3 Air Manifold Air Flow Rate 1 F51 Flow Element and Transmitter, Thermal Mass Flow with 2" Flanged spool piece 0 to 215 SCFM 2" Flange 040-LCP-100 Manufacturer STD 08-N-408
040-FE-602C 040-FIT-602C Digester 3 Air Manifold Air Flow Rate 2 F51 Flow Element and Transmitter, Thermal Mass Flow, 2" Flanged spool piece 0 to 215 SCFM 2" Flange 040-LCP-100 Manufacturer STD 08-N-408
040-FE-603C 040-FIT-603C Digester 3 Air Manifold Air Flow Rate 3 F51 Flow Element and Transmitter, Thermal Mass Flow 0 to 805 SCFM 1" NPT 040-LCP-100 4091-217, 4091- 383 08-N-408
040-PIT-607 Digester Blowers Discharge Header Pressure P9 Pressure Element and Transmitter 0 to 15 psig 1/2" NPT 040-LCP-100 4091-306 08-N-409
045-AE-109 LEL 045-AIT-109 RAS/WAS Pumps Building LEL A10 Combustible Gas Element and Transmitter 0.5 % 010-LCP-100 Manufacturer STD 08-N-450
045-PIT-111 045-PE-111 RAS Pump 1 Suction P9 Pressure Element and Transmitter with annular Seal 0 to 10 psig 6" Flange, 150# 010-LCP-100 4091-303 08-N-450 045-PIT-121 045-PE-121 RAS Pump 2 Suction P9 Pressure Element and Transmitter with annular Seal 0 to 10 psig 6" Flange, 150# 010-LCP-100 4091-303 08-N-450 045-PIT-131 045-PE-131 RAS Pump 3 Suction P9 Pressure Element and Transmitter with annular Seal 0 to 10 psig 6" Flange, 150# 010-LCP-100 4091-303 08-N-450 045-PIT-141 045-PE-141 RAS Pump 4 Suction P9 Pressure Element and Transmitter with annular Seal 0 to 10 psig 6" Flange, 150# 010-LCP-100 4091-303 08-N-450 045-PIT-112 045-PE-112 RAS Pump 1 Discharge P9 Pressure Element and Transmitter with annular Seal 0 to 25 psig 6" Flange, 150# 010-LCP-100 4091-303 08-N-450 045-PIT-122 045-PE-122 RAS Pump 2 Discharge P9 Pressure Element and Transmitter with annular Seal 0 to 25 psig 6" Flange, 150# 010-LCP-100 4091-303 08-N-450
INSTRUMENTATION AND
CONTROL FOR PROCESS SYSTEMS
40 90 00 SUPPLEMENT - 4
AMENDMENT
Set Point
ENGINEERING
UNITS
Process Connection Panel Number Installation
Details P&ID
INSTRUMENT LIST
045-PIT-132 045-PE-132 RAS Pump 3 Discharge P9 Pressure Element and Transmitter with annular Seal 0 to 25 psig 6" Flange, 150# 010-LCP-100 4091-303 08-N-450 045-PIT-142 045-PE-142 RAS Pump 4 Discharge P9 Pressure Element and Transmitter with annular Seal 0 to 25 psig 6" Flange, 150# 010-LCP-100 4091-303 08-N-450
045-FE-101 045-FIT-101 RAS Pumps to Bioreactor 1 F4 Flow Element and Transmitter, Electromagnetic 0 to 350 gpm 4" Flange, 150# 010-LCP-100 4091-211, 4091- 383 08-N-450
045-FE-102 045-FIT-102 RAS Pumps to Bioreactor 2 F4 Flow Element and Transmitter, Electromagnetic 0 to 350 gpm 4" Flange, 150# 010-LCP-100 4091-211, 4091- 383 08-N-450
045-FE-103 045-FIT-103 RAS Pumps to Bioreactor 3 F4 Flow Element and Transmitter, Electromagnetic 0 to 350 gpm 4" Flange, 150# 010-LCP-100 4091-211, 4091- 383 08-N-450
045-PI-110 RAS Pump 1 Seal Water Pressure Indicating P4 Pressure Gauge 0 to 125 psig 1/2" NPT 4091-304 08-N-450 045-PI-120 RAS Pump 2 Seal Water Pressure Indicating P4 Pressure Gauge 0 to 125 psig 1/2" NPT 4091-304 08-N-450 045-PI-130 RAS Pump 3 Seal Water Pressure Indicating P4 Pressure Gauge 0 to 125 psig 1/2" NPT 4091-304 08-N-450 045-PI-140 RAS Pump 4 Seal Water Pressure Indicating P4 Pressure Gauge 0 to 125 psig 1/2" NPT 4091-304 08-N-450
045-FSL-110 RAS Pump 1 Seal Water Low Flow Alarm F23 Flow Element and Switch 0 to 20 gpm 3/4" NPT 045-AFD-110 Manufacturer STD 08-N-450
045-FSL-120 RAS Pump 2 Seal Water Low Flow Alarm F23 Flow Element and Switch 0 to 20 gpm 3/4" NPT 045-AFD-120 Manufacturer STD 08-N-450
045-FSL-130 RAS Pump 3 Seal Water Low Flow Alarm F23 Flow Element and Switch 0 to 20 gpm 3/4" NPT 045-AFD-130 Manufacturer STD 08-N-450
045-FSL-140 RAS Pump 4 Seal Water Low Flow Alarm F23 Flow Element and Switch 0 to 20 gpm 3/4" NPT 045-AFD-140 Manufacturer STD 08-N-450
045-PI-211 045-PE-211 WAS Pump 1 Section Pressure Indicating P4 Pressure Gauge with annular Seal 0 to 10 psig 4" Flange, 150# 4091-304A 08-N-451 045-PI-221 045-PE-221 WAS Pump 2 Section Pressure Indicating P4 Pressure Gauge with annular Seal 0 to 10 psig 4" Flange, 150# 4091-304A 08-N-451 045-PSL-211 WAS Pump 1 Section Low Pressure Alarm P7 Pressure Switch Set @ 0.5 psig 1/2" NPT 010-LCP-100 4091-304A 08-N-451 045-PSL-221 WAS Pump 2 Section Low Pressure Alarm P7 Pressure Switch Set @ 0.5 psig 1/2" NPT 010-LCP-100 4091-304A 08-N-451 045-PIT-212 045-PE-212 WAS Pump 1 Discharge Pressure P9 Pressure Element and Transmitter with annular Seal 0 to 25 psig 4" Flange, 150# 010-LCP-100 4091-304A 08-N-451 045-PIT-222 045-PE-222 WAS Pump 2 Discharge Pressure P9 Pressure Element and Transmitter with annular Seal 0 to 25 psig 4" Flange, 150# 010-LCP-100 4091-304A 08-N-451 045-PSH-212 WAS Pump 1 Discharge High Pressure Alarm P7 Pressure Switch Set @ 25 psig 1/2" NPT 045-AFD-210 4091-304A 08-N-451 045-PSH-222 WAS Pump 2 Discharge High Pressure Alarm P7 Pressure Switch Set @ 25 psig 1/2" NPT 045-AFD-220 4091-304A 08-N-451
045-FE-201 045-FIT-201 WAS Feed to Digesters Flow F4 Flow Element and Transmitter, Electromagnetic 0 to 250 gpm 4" Flange, 150# 010-LCP-100 4091-211, 4091- 383 08-N-451
045-PIT-316 Bioreactor Blower 1 Discharge Pressure P9 Pressure Element and Transmitter 0 to 15 psig 1/2" NPT 040-LCP-100 4091-306 08-N-452 045-PIT-326 Bioreactor Blower 2 Discharge Pressure P9 Pressure Element and Transmitter 0 to 15 psig 1/2" NPT 040-LCP-100 4091-306 08-N-452 045-PIT-336 Bioreactor Blower 3 Discharge Pressure P9 Pressure Element and Transmitter 0 to 15 psig 1/2" NPT 040-LCP-100 4091-306 08-N-452 045-PIT-346 Bioreactor Blower 4 Discharge Pressure P9 Pressure Element and Transmitter 0 to 15 psig 1/2" NPT 040-LCP-100 4091-306 08-N-452
055-PIT-111 055-PI-111 Headworks Odor Control Fans Inlet P9 Pressure Element and Transmitter (direct mounted) with Remote Indicator -10 to 0 in w.c. 1/2" FNPT 010-PLC-100 4091-380 08-N-550
055-PIT-112 055-PI-112 Headworks Odor Control Fans Outlet P9 Pressure Element and Transmitter (direct mounted) with Remote Indicator 0 to 10 in w.c. 1/2" FNPT 010-PLC-100 4091-380 08-N-550
065-LSHH-111 MHO Tank 1 High High Level Alarm L50 Level Switch, Tuning Fork
Set @ Overflow Nozzle of Tank, To be coordinated with approved tank submittal ft 2" 150# flange 065-PLC-100 9041-269 08-N-651
065-LSHH-121 MHO Tank 2 High High Level Alarm L50 Level Switch, Tuning Fork
Set @ Overflow Nozzle of Tank, To be coordinated with approved tank submittal ft 2" 150# flange 065-PLC-100 9041-269 08-N-651
065-LE/LT-112 065-LI-112 MHO Tank 1 Level L29 Level Element/Transmitter and Indicator, Radar 0 to 15 ft 6" Slip-on flange with 3" antenna 065-PLC-100 4091-269, 4091-
383 08-N-651
065-LE/LT-122 065-LI-122 MHO Tank 2 Level L29 Level Element/Transmitter and Indicator, Radar 0 to 15 ft 6" Slip-on flange with 3" antenna 065-PLC-100 4091-269, 4091-
383 08-N-651
065-LSH-113 MHO Tank 1 secondary containment Leak Detection L180 Leak Detector Switch, Electro-Optic, provided by tank manufacturer ft 065-PLC-100 Manufacturer STD 08-N-651
065-LSH-123 MHO Tank 2 secondary containment Leak Detection L180 Leak Detector Switch, Electro-Optic, provided by tank manufacturer ft 065-PLC-100 Manufacturer STD 08-N-651
YOSE 196416
PW\DEN003\D3167637
INSTRUMENTATION AND
CONTROL FOR PROCESS SYSTEMS
40 90 00 SUPPLEMENT - 5
Set Point
ENGINEERING
UNITS
Process Connection Panel Number Installation
Details P&ID
INSTRUMENT LIST
065-PI-111 065-PE-111 MHO Pump1 Discharge Pressure Indicator P4 Pressure Gauge with Diaphragm Seal 0 to 150 psig 1/2" NPT 4091-304B 08-N-652
065-PSH-112 065-PE-112 MHO Pump 1 Discharge High Pressure Alarm P7 Pressure Switch with Diaphragm Seal Set @ 150 psig 1/2" NPT 065-PLC-100 4091-304B 08-N-652 065-PI-121 065-PE-121 MHO Pump 2 Discharge Pressure Indicator P4 Pressure Gauge with Diaphragm Seal 0 to 150 psig 1/2" NPT 4091-304B 08-N-652 065-PSH-122 065-PE-122 MHO Pump2 Discharge High Pressure Alarm P7 Pressure Switch with Diaphragm Seal Set @ 150 psig 1/2" NPT 065-PLC-100 4091-304B 08-N-652
065-LSHH-211 ALUM Tank 1 High High Level Alarm L50 Level Switch, Tuning Fork
Set @ Overflow Nozzle of Tank, To be coordinated with approved tank submittal ft 2" 150# flange 065-PLC-100 9041-269 08-N-653
065-LSHH-221 ALUM Tank 2 High High Level Alarm L50 Level Switch, Tuning Fork
Set @ Overflow Nozzle of Tank, To be coordinated with approved tank submittal ft 2" 150# flange 065-PLC-100 9041-269 08-N-653
065-LE/LT-212 065-LI-212 ALUM Tank 1 Level L29 Level Element/Transmitter and Indicator, Radar 0 to 15 ft 6" Slip-on flange with 3" antenna 065-PLC-100 4091-269, 4091-
383 08-N-653
065-LE/LT-222 065-LI-222 ALUM Tank 2 Level L29 Level Element/Transmitter and Indicator, Radar 0 to 15 ft 6" Slip-on flange with 3" antenna 065-PLC-100 4091-269, 4091-
383 08-N-653
065-LSH-213 ALUM Tank 1 secondary containment Leak Detection L180 Leak Detector Switch, Electro-Optic, provided by tank manufacturer ft 065-PLC-100 Manufacturer STD 08-N-653
065-LSH-223 ALUM Tank 2 secondary containment Leak Detection L180 Leak Detector Switch, Electro-Optic, provided by tank manufacturer ft 065-PLC-100 Manufacturer STD 08-N-653
065-PI-211 065-PE-211 ALUM Pump 1 Discharge Pressure Indicating P4 Pressure Gauge with Diaphragm Seal 0 to 150 psig 1/2" NPT 4091-304B 08-N-654 065-PI-221 065-PE-221 ALUM Pump 2 Discharge Pressure Indicating P4 Pressure Gauge with Diaphragm Seal 0 to 150 psig 1/2" NPT 4091-304B 08-N-654 065-PSH-212 065-PE-212 ALUM Pump 1 Discharge High Pressure Alarm P7 Pressure Switch with Diaphragm Seal Set @ 150 psig 1/2" NPT 065-PLC-100 4091-304B 08-N-654 065-PSH-222 065-PE-222 ALUM Pump 2 Discharge High Pressure Alarm P7 Pressure Switch with Diaphragm Seal Set @ 150 psig 1/2" NPT 065-PLC-100 4091-304B 08-N-654
065-LSHH-311 PACLTank High High Level Alarm L50 Level Switch, Tuning Fork
Set @ Overflow Nozzle of Tank, To be coordinated with approved tank submittal ft 2" 150# flange 065-PLC-100 9041-269 08-N-655
065-LE/LT-312 065-LI-312 PACL Tank Level L29 Level Element/Transmitter and Indicator, Radar 0 to 15 ft 6" Slip-on flange with 3" antenna 065-PLC-100 4091-269, 4091-
383 08-N-655
065-LSH-313 PACL Tank secondary containment Leak Detection L180 Leak Detector Switch, Electro-Optic, provided by tank manufacturer ft 065-PLC-100 Manufacturer STD 08-N-655
065-PI-312 065-PE-312 PACL Metering Pump 1 Discharge Pressure Indicating P4 Pressure Gauge with Diaphragm Seal 0 to 150 psig 1/2" NPT 4091-304B 08-N-656 065-PI-322 065-PE-322 PACL Metering Pump 2 Discharge Pressure Indicating P4 Pressure Gauge with Diaphragm Seal 0 to 150 psig 1/2" NPT 4091-304B 08-N-656 065-PSH-311 065-PE-311 PACL Metering Pump 1 Discharge High Pressure Alarm P9 Pressure Switch with Diaphragm Seal Set @ 150 psig 1/2" NPT 065-PLC-100 4091-304B 08-N-656 065-PSH-321 065-PE-321 PACL Metering Pump 2 Discharge High Pressure Alarm P9 Pressure Switch with Diaphragm Seal Set @ 150 psig 1/2" NPT 065-PLC-100 4091-304B 08-N-656 065-PI-405 Tertiary W3 feed to Polymer Mixer Pressure Indicating P4 Pressure Gauge 0 to 5 psig 1/2" NPT 4091-304B 08-N-657 065-PI-406 Tertiary W3 feed to Polymer Blending Pressure Indicating P4 Pressure Gauge 0 to 5 psig 1/2" NPT 4091-304B 08-N-657
065-FE-401 065-FIT-401 TertiaryPolymer Feed Pumps Discharge Flow F4 Flow Element and Transmitter, Electromagnetic 0 to 30 psig 1" 065-LCP-100 4091-211, 4091- 383 08-N-657
080-PIT-150 Air Receiver Tank Pressure P9 Pressure Element and Transmitter 0 to 175 psig 1/2" NPT 040-PLC-100 4091-304B 08-N-800
075-AE-101 TURB 075-AIT-101 Lab Turbidity A16 Turbidity Element and Transmitter 0 to 100 NTU 075-NIP-100 Manufacturer STD 08-N-850
075-FI-101 Lab Sample Flow Indicator F16 Flow Element, Rotameter 0 to 2 gpm 1/4" NPT Manufacturer STD 08-N-850
085-FE-102 085-FIT-102 Plant Water Pumps Discharge Header Flow F4 Flow Element and Transmitter, Electromagnetic 0 to 600 gpm 4" Flange, 150# 040-LCP-100 4091-211, 4091- 383 08-N-850
085-LT-101 085-LI-101 Plant Water Pump Station Level L29 Level Element/Transmitter and Indicator, Radar 0 to 15 ft 4" Slip-on flange with 3" antenna 040-LCP-100 4091-263, 4091-
383 08-N-850
085-LT-105 085-LI-105 Existing Flow Measurement Chamber Level L42 Level Element and Transmitter,Submersible with Indicator 0 to 10 ft 040-LCP-100 4091-250, 4091- 383 08-N-850
INSTRUMENTATION AND
CONTROL FOR PROCESS SYSTEMS
40 90 00 SUPPLEMENT - 6
AMENDMENT
Set Point
ENGINEERING
UNITS
Process Connection Panel Number Installation
Details P&ID
INSTRUMENT LIST
085-PI-104 Plant Water Bypass Pressure Indicating P4 Pressure Gauge 0 to 200 1/2" NPT 4091-304 08-N-850 085-PIT-103 Plant Water Pumps Discharge Header Pressure P9 Pressure Element and Transmitter 0 to 150 psig 1/2" NPT 040-LCP-100 4091-306 08-N-850
086-FE-102 086-FIT-102 Return Flow Pumps Discharge Header Flow F4 Flow Element and Transmitter, Electromagnetic 0 to 200 gpm 3" Flange, 150# 065-LCP-100 4091-211, 4091- 383 08-N-860
086-LT-101 086-LI-101 Return Flow Pump Station Level L42 Level Element and Transmitter,Submersible with Indicator 0 to 30 ft 4" Slip-on flange with 3" antenna 065-LCP-100 4091-250, 4091-
383 08-N-860
086-LT-103 086-LI-103 Diversion Tank Basin 1 Level L42 Level Element and Transmitter,Submersible with Indicator 0 to 30 ft 4" Slip-on flange with 3" antenna 065-LCP-100 4091-250, 4091-
383 08-N-860
086-PI-112 086-PE-112 Return Flow Pump 1 Discharge Pressure Indicating P4 Pressure Gauge with annular Seal 0 to 15 psig 3" Flanged 4091-304A 08-N-860 086-PI-122 086-PE-122 Return Flow Pump 2 Discharge Pressure Indicating P4 Pressure Gauge with annular Seal 0 to 15 psig 3" Flanged 4091-304A 08-N-860 086-PI-132 086-PE-132 Return Flow Pump 3 Discharge Pressure Indicating P4 Pressure Gauge with annular Seal 0 to 15 psig 3" Flanged 4091-304A 08-N-860
YOSE 196416
PW\DEN003\D3167637
INSTRUMENTATION AND
CONTROL FOR PROCESS SYSTEMS
40 90 00 SUPPLEMENT - 7
File details come from the government source that posted it. Updated .