This file appears to be a collection of architectural or engineering drawings related to Amendment 09 for the construction of a Fire Station at Big Cypress National Preserve Headquarters Complex. As this is an image-based document containing technical drawings, it provides visual specifications and design details that would be used by contractors bidding on the fire station construction project. Without access to view the actual drawings, I cannot provide specific details about the building plans, dimensions, or technical specifications contained within. This document is part of solicitation number 140P2024R0084 issued by the Department of the Interior National Park Service.
View the file
Other files for this federal contract opportunity
Show all 50
BICY 229154 has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BUILDING INFORMATION AND LIMITATIONS
BUILDING OCCUPANCY CLASSIFICATION: BUSINESS (GROUP B)
CONSTRUCTION TYPE: ll-B
SPRINKLERED: N
ALLOWABLE BUILDING HEIGHT: 3 STORIES, 60'
ACTUAL BUILDING HEIGHT: 1 STORIES,<25'
ALLOWABLE BUILDING AREA (PER STORY): 36,000 GSF
ACTUAL BUILDING AREA (PER STORY): 5,142 GSF
TOTAL OCCUPANT LOAD: 42
PROJECT LOCATION
PARK BOUNDARY
LOCATION MAP
PROJECT LOCATION
PROJECT INFORMATION
INDEX OF DRAWINGS
REV SHEET
SUB
SHEET TITLE OF SHEET
1 1 G0.00 COVER
2 G0.01 GENERAL NOTES, SYMBOL LEGEND AND ABBREVIATIONS
3 G0.02 TYPICAL TOILET ROOMS AND MOUNTING HEIGHTS
4 G0.03 CODE COMPLIANCE
5 G0.04 CODE COMPLIANCE
6 G1.01 LEVEL 1 LIFE SAFETY PLAN
7 C0.01 GENERAL NOTES AND DETAILS
8 C0.02 LEGEND
1 9 C0.03 STORMWATER POLLUTION PREVENTION NOTES
1 10 C1.01 STORMWATER POLLUTION PREVENTION PLAN
1 11 C1.02 DEMOLITION AND TREE PROTECTION PLAN
1 12 C1.03 MASTER PLANNING PLAN
1 13 C1.04 DETAILED HORIZONTAL CONTROL AND SITE PLAN
1 14 C1.05 DETAILED GRADING, DRAINAGE, AND UTILITY PLAN
1 15 C1.06 DETAILED GRADING, DRAINAGE, AND UTILITY PLAN
1 16 A1.01 ARCHITECTURAL SITE PLAN
17 A1.02 LEVEL 1 FLOOR PLAN
18 A1.03 LEVEL 1 ACCESSIBILITY PLAN
19 A1.04 LEVEL 1 PARTITION PLAN
20 A1.05 LEVEL 1 CEILING PLAN
21 A1.06 ROOF PLAN
22 A1.07 LEVEL 1 FINISH PLAN
1 23 A2.01 EXTERIOR ELEVATIONS
24 A3.01 BUILDING SECTIONS
25 A3.02 BUILDING SECTIONS
26 A3.03 WALL SECTIONS
1 27 A4.01 ENLARGED ARCHITECTURAL SITE PLAN - PROJECT SITE
28 A4.02 ENLARGED INTERIOR VIEWS - FLOOR PLAN
29 A4.03 ENLARGED INTERIOR VIEWS - ELEVATIONS
30 A5.01 ROOF DETAILS
31 A5.02 ROOF DETAILS
32 A5.03 ROOF DETAILS
33 A5.04 ROOF DETAILS
34 A5.05 ROOF DETAILS
35 A5.06 ROOF DETAILS
36 A5.07 EXTERIOR DETAILS
37 A5.08 EXTERIOR DETAILS
1 38 A5.09 EXTERIOR DETAILS
39 A5.10 EXTERIOR DETAILS
40 A5.11 PARTITION DETAILS
41 A5.12 INTERIOR AND FINISH DETAILS
42 A5.13 INTERIOR CASEWORK DETAILS
43 A5.14 OPENING DETAILS
44 A5.15 OPENING DETAILS
45 A5.16 OPENING DETAILS
46 A5.17 OPENING DETAILS
47 A5.18 OPENING DETAILS
48 A5.19 OPENING DETAILS
49 A6.01 PARTITION TYPES
50 A6.02 OPENING TYPES AND SCHEDULE
51 A9.01 EXTERIOR PERSPECTIVE VIEW
TITLE OF DRAWING: DRAWING NO.
PMIS/PKG NO.
OF
A/E
PRIME/ARCH
SHEET
MECHANICA
HENRY
ADAMS, LLC.
BALTIMORE, MD
WALKER
ARCHITECTS, INC.
GAINESVILLE, FL
UNITED STATES
DEPARTMENT OF THE INTERIOR
LOCATION WITHIN PARK
NAME OF THE PARK
REGION STATECOUNTY
NATIONAL PARK SERVICE
DENVER SERVICE CENTER
QUALITY DESIGN CERTIFICATION
PREPARED IN ACCORDANCE WITH DESIGN
DEVELOPMENT (TITLE I) _________________________
VARIANCE FROM DESIGN DEVELOPMENT (TITLE I)
APPROVED BY SUPERINTENDENT ON ______________
CONSTRUCTION DRAWING NOT PRECEDED
BY DESIGN DEVELOPMENT (TITLE I)
PROJECT MANAGER DATE
DRAWING NO.
DATE
CIVIL
PLUMBIN
HENRY
ADAMS, LLC.
BALTIMORE, MD
CHW, INC.
ALACHUA, FL
ELECTRICAL
STRUCTURAL
AES, INC.
JACKSONVILLE,F
HENRY
ADAMS, LLC.
BALTIMORE, MD
/3
/2
:4
:1
P
M NEW FIRE OPERATIONS CENTER
BIG CYPRESS NATIONAL PRESERVE
229154
BICY HEADQUARTERS
DESIGN DEVELOPMENT
SOUTH-EAST COLLIER FLORIDA
REV SHEET
SUB
SHEET TITLE OF SHEET
52 E0.01 ELECTRICAL COVER SHEET
53 E0.02 ELECTRICAL NOTES AND CONVENTIONS
1 54 E0.03 ELECTRICAL SITE PLAN
55 E1.01 LEVEL 1 LIGHTING PLAN
56 E2.01 LEVEL 1 POWER PLAN
57 E2.02 ROOF POWER AND LIGHTING PROTECTION PLAN
58 E4.01 ELECTRICAL PART PLANS
59 E5.01 ELECTRICAL DETAILS
60 E5.02 ELECTRICAL DETAILS
61 E5.03 ELECTRICAL DETAILS
62 E5.04 ELECTRICAL DETAILS
63 E6.01 ELECTRICAL ONE-LINE DIAGRAM
64 E6.02 TELECOMMUNCATIONS RISER DIAGRAM
65 E6.03 ELECTRICAL GROUNDING AND BONDING DIAGRAM
66 E7.01 LIGHTING CONTROL DIAGRAMS
67 E7.02 LIGHTING CONTROL SCHEDULE AND MATRIX
68 E8.01 LUMINAIRE SCHEDULE
69 E8.02 ELECTRICAL EQUIPMENT SCHEDULES
70 E8.03 PANELBOARD SCHEDULES
71 M0.01 MECHANICAL COVER SHEET
72 M0.02 MECHANICAL SITE PLAN
73 M1.01 LEVEL 1 DUCTWORK PLAN
74 M2.01 LEVEL 1 MECHANICAL PIPING PLAN
75 M4.01 MECHANICAL SECTIONS
76 M5.01 MECHANICAL DETAILS
77 M6.01 AUTOMATIC TEMPERATURE CONTROLS
78 M7.01 MECHANICAL SCHEDULES
79 P0.01 PLUMBING COVER SHEET
1 80 P0.02 PLUMBING SITE PLAN
1 81 P1.00 FOUNDATION PLUMBING PLAN
82 P1.01 LEVEL 1 PLUMBING PLAN
83 P1.02 ROOF PLUMBING PLAN
1 84 P3.01 PLUMBING PART PLANS
85 P3.02 PLUMBING PART PLANS
86 P3.03 PLUMBING PART PLANS
87 P5.01 PLUMBING DETAILS
88 P6.01 DOMESTIC WATER RISER DIAGRAMS
89 P6.02 SANITARY RISER DIAGRAMS
90 P6.03 CONDENSATE RISER DIAGRAMS
91 P7.01 PLUMBING SCHEDULES
1 92 S0.01 GENERAL NOTES
1 93 S1.01 FOUNDATION PLAN
94 S1.02 GENERATOR PAD AND FIRE SUPPRESSION TANK PLANS
1 95 S3.01 SECTIONS
1 96 S3.02 SECTIONS
1 97 S3.03 SECTIONS
1 98 S5.01 TYPICAL DETAILS
NTS
N
MARK REVISION DATE INITIAL
1 REVISION 1, AMENDMENT 09 1/29/25
Lblake Image
Lblake Typewritten Text 2/4/2025
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME: MGM
TFC
03/12/2024
DHY SHEETNPS FIRE OPERATIONS CENTER AT
BIG CYPRESS NATIONAL PRESERVE
SUB:
NV5, INC.
WALKER
ARCHITECTS,
GAINESVILLE, FL
GAINESVILLE, FL
C0.03
STORMWATER POLLUTION
PREVENTION NOTES
WATERSHED
ID
POST DEVELOPMENT
AREA (ACRES)
POST DEVELOPMENT
RUNOFF FACTOR (CN)
POST DEVELOPMENT
IMPERVIOUS AREA
(ACRES)
STORMWATER
MANAGEMENT
FACILITY TYPE
1 0.26 DRY DETENTION
FACILITY DETENTION
CAPACITY
(ACRE-FEET)
100-YEAR FLOOD
ELEVATION (FT)
4.980.88 94 0.542
THIS DOCUMENT WAS PREPARED IN ORDER TO ILLUSTRATE COMPLIANCE WITH CHAPTER 62-621.300 (4) OF THE FLORIDA ADMINISTRATIVE CODE, WHICH PERTAINS TO THE GENERIC PERMIT FOR STORMWATER DISCHARGE FROM LARGE AND SMALL CONSTRUCTION ACTIVITIES. THE ADMINISTRATIVE CODE GRANTS THE FLORIDA DEPARTMENT OF ENVIRONMENTAL PROTECTION (FDEP) THE AUTHORITY TO REGULATE POINT SOURCE DISCHARGE OF STORMWATER FROM CONSTRUCTION SITES. THIS DOCUMENT ESTABLISHES A STORMWATER POLLUTION PREVENTION PLAN FOR THE SITE USING STANDARD PRACTICE AND BEST MANAGEMENT PRACTICES (BMPs) AND IS ORGANIZED TO CORRESPOND TO 62-621.300(4)(a) GENERIC PERMIT FOR STORMWATER DISCHARGE FROM LARGE AND SMALL CONSTRUCTION ACTIVITIES FDEP FORM 62-621.300(4)(b) IS TO BE SUBMITTED IN CONJUNCTION WITH THIS DOCUMENT. CONTRACTOR(S) MUST FILL IN THE ACTIVITIES SEQUENCE (SECTION ii. B. BELOW) AND SIGN THIS SHEET (REFER TO SIGNATURE TABLE THIS SHEET) AND RETAIN THIS SHEET AND ALL FOLLOWING SWPPP SHEETS ON SITE. ALTERNATIVELY, CONTRACTOR(S) MAY PREPARE AND SIGN THEIR OWN SWPP PLAN MEETING THE REQUIREMENTS. IF THE SITE OR CONTRACTOR ACTIVITIES REQUIRE ANY BMPs THAT ARE NOT DESCRIBED ON THIS SHEET, THE CONTRACTOR MUST PREPARE AN ALTERNATIVE OR ADDITIONAL SWPPP DOCUMENT CONTAINING THE NECESSARY BMPs.
COUNTY:
SECTION, TOWNSHIP, RANGE:
COUNTY PARCEL NO.:
STREET ADDRESS:
PROJECT AREA:
SITE LOCATION MAP:
COLLIER COUNTY, FLORIDA
SECTION 33, TOWNSHIP 52 SOUTH, RANGE 30 EAST
0114756004
33100 TAMIAMI TRAIL E, OCHOPEE, FL 34141
2.40 ACRES
SEE COVER SHEET OF CONSTRUCTION DRAWINGS
THE PROPOSED DEVELOPMENT IS THE CONSTRUCTION OF ±5,300 S.F. OF FIRE OPERATION BUILDING AND ASSOCIATED PAVEMENT FOR DRIVEWAYS AND PARKING, SIDEWALKS, UTILITIES, AND STORMWATER MANAGEMENT FACILITY(S). THE PROJECT SITE IS LOCATED AT 33100 TAMIAMI TRAIL E, OCHOPEE, FLORIDA. THE PROJECT
SITE TOTAL AREA IS APPROXIMATELY 2.40 ACRES.
PRIOR TO CONSTRUCTION, SILT FENCING AND TREE PROTECTION FENCING SHALL BE INSTALLED AND ALL EXISTING STORM DRAINAGE SWALE AND INLETS SHALL BE PROTECTED IN ACCORDANCE WITH THE STATE OF FLORIDA EROSION AND SEDIMENT CONTROL DESIGNER
AND REVIEWER MANUAL, DATED JULY 2013, AND THESE PLANS.
THE CONSTRUCTION SERVICE ENTRANCE SHALL BE STABILIZED TO MINIMIZE THE CREATION OF DUST AND OFF-SITE TRACKING OF
SEDIMENTS.
ONLY THE AREA COMPRISING THE PROPOSED STORMWATER MANAGEMENT FACILITY(S) SHALL BE CLEARED AND GRUBBED OF UNWANTED
VEGETATION.
THE PROPOSED STORMWATER MANAGEMENT FACILITY(S) SHALL BE CONSTRUCTED.
IF SUITABLE, THE EXCAVATED SOIL FROM THE FACILITY(S) MAY BE USED AS FILL FOR ON-SITE GRADING THAT IS DEPICTED IN THESE
CONSTRUCTION PLANS. THE CONTRACTOR SHALL DISPOSE OF ALL UNSUITABLE MATERIAL ON-SITE OR OFF-SITE TO A PERMITTED
LOCATION.
THE REMAINING PORTION OF THE SITE THAT IS TREATED BY THE CONSTRUCTED STORMWATER MANAGEMENT FACILITY(S) SHALL BE
CLEARED AND GRUBBED.
THE PERMANENT ROADWAYS/DRIVEWAYS SHALL BE ROUGHLY GRADED.
THE UNDERGROUND UTILITIES INFRASTRUCTURE AND STORMWATER PIPING SYSTEM SHALL BE INSTALLED. ANY DE-WATERING (PUMPED)
SHALL BE DIVERTED TO THE ASSOCIATED STORMWATER MANAGEMENT FACILITY(S).
THE PERMANENT ROADWAY/DRIVEWAY SUBGRADE SHALL BE COMPACTED, A LIMEROCK BASE SHALL BE ESTABLISHED, AND THEN
FOLLOWED BY AN OVERLAY OF ASPHALT.
UPON SIGNIFICANT COMPLETION OF CONSTRUCTION, THE STORMWATER PIPING SYSTEM SHALL BE FLUSHED OUT TO REMOVE
ACCUMULATED DEBRIS AND SEDIMENT.
UPON COMPLETION OF THE DEBRIS AND SEDIMENT REMOVAL FROM THE STORMWATER PIPING SYSTEM, THE PROPOSED STORMWATER
MANAGEMENT FACILITY(S) SHALL BE FINE GRADED AND SHALL BE EXCAVATED A MINIMUM OF SIX INCHES BELOW THE DESIGN BOTTOM ELEVATION AND REPLACED WITH FILL HAVING A MINIMUM PERMEABILITY RATE OF 20 FEET/DAY WITH A MAXIMUM OF 5% SOIL FINES PASSING THE NO. 200 SIEVE. THE BOTTOM SHALL BE SCARIFIED AND STABILIZED ACCORDING TO THESE PLANS. ONCE COMPLETED, NO HEAVY MACHINERY SHALL BE ALLOWED WITHIN THE STORMWATER MANAGEMENT FACILITY(S).
ALL REMAINING DISTURBED AREAS WITHIN THE CONSTRUCTION AREA SHALL BE COMPLETELY GRASSED AND/OR LANDSCAPED ACCORDING TO THESE PLANS. TURF ESTABLISHMENT SHALL BE PER FDOT STANDARD SPECIFICATIONS SECTION 570. EVIDENCE OF GROWTH MUST BE PRESENT PRIOR TO REMOVAL OF SILT FENCING AND OTHER EROSION CONTROL APPLICATIONS.
TOTAL PROJECT SITE AREA:
TOTAL SITE AREA TO BE DISTURBED:
TOTAL IMPERVIOUS AREA (AS SHOWN IN CONSTRUCTION DRAWINGS):
TOTAL DETENTION VOLUME:
TOTAL OPEN AREA:
2.40 ACRES
2.40 ACRES
0.26 ACRES
0.542 ACRE-FEET
1.87 ACRES
THE NRCS DATA FOR THE SITE REVEALS THAT THE SITE SOILS ARE COMPRISED OF PERRINE MARLY SILT LOAM. UNIVERSAL ENGINEERING SCIENCES CONDUCTED A GEOTECHNICAL EXPLORATION OF THE PROPOSED STORMWATER MANAGEMENT FACILITY(S) LOCATION IN JANUARY OF 2023. THE INVESTIGATION REVEALED THAT
THE PROJECT SITE'S SURFACE SOILS HAVE THE FOLLOWING CHARACTERISTICS:
DEPTH TO EFFECTIVE OR MOBILIZED AQUIFER:
DEPTH OF SEASONAL HIGH WATER TABLE:
HORIZONTAL HYDRAULIC CONDUCTIVITY:
UNSATURATED VERTICAL INFILTRATION:
THE STORMWATER MANAGEMENT FACILITY(S) WAS DESIGNED TO PROVIDE RATE CONTROL AND WATER QUALITY TREATMENT OF THE STORMWATER RUNOFF RESULTING FROM THE POST-DEVELOPMENT SITE UNDER 25-YEAR 72-HOUR CRITICAL STORM EVENT RAINFALL CONDITION. THE STORMWATER POLLUTION PREVENTION PLAN (C1.01) DEPICTS THE POST-DEVELOPMENT WATERSHED(S) LIMITS AND THE TABLE BELOW SUMMARIZES EACH WATERSHED.
0 FEET (NAVD88)
0.50 FEET (NAVD88)
N/A N/A
PLEASE SEE THE STORMWATER POLLUTION PREVENTION PLAN (C1.01) FOR DETAILS.
THE STORMWATER MANAGEMENT FACILITY 1 OUTFALL STRUCTURE IS LOCATED AT THE SOUTHEAST PORTION OF THE PROJECT (25°53'58" N, 81°19'13" W) AND THE ASSOCIATED
RECEIVING WATER BODY IS HALFWAY CREEK.
AS OUTLINED IN THE SOUTH FLORIDA WATER MANAGEMENT DISTRICT (SJRWMD) PERMIT, ALL CONSTRUCTION ACTIVITIES SHALL BE CONDUCTED IN A MANNER AS TO NOT VIOLATE STATE WATER QUALITY STANDARDS. PRIOR TO CONSTRUCTION, THE CONTRACTOR SHALL IMPLEMENT AND MAINTAIN ALL EROSION AND SEDIMENT CONTROL MEASURES REQUIRED TO RETAIN SEDIMENT ON-SITE. IF SITE CONDITIONS ARE SUCH THAT ADDITIONAL CONTROL MEASURES ARE REQUIRED OTHER THAN WHAT IS SPECIFIED IN THE EROSION AND SEDIMENTATION CONTROL PLAN, THEN THE CONTRACTOR SHALL IMPLEMENT ADDITIONAL BEST MANAGEMENT PRACTICES.
THESE MEASURES MUST BE INSPECTED AND MAINTAINED THROUGHOUT THE CONSTRUCTION PHASE AND UNTIL AS DIRECTED BY THESE PLANS. THE STORMWATER POLLUTION PREVENTION PLAN (C1.01) AND SECTION IV BELOW PROVIDE DETAILS ON THE SPECIFIC CONTROL MEASURES TO REDUCE STORMWATER POLLUTION.
EXISTING TREES AND NATURAL VEGETATION TO REMAIN ON-SITE SHALL BE PROTECTED BY TREE BARRICADE FENCING AS DEPICTED ON THE STORMWATER POLLUTION PREVENTION PLAN (C1.01). TYPE III SILT FENCING SHALL PROTECT ALL DRAINAGE STRUCTURES AND SHALL BUFFER AREAS WITH POTENTIAL TO CONTRIBUTE OFF-SITE RUNOFF AND AS SPECIFICALLY DEPICTED ON THE STORMWATER POLLUTION PREVENTION PLAN (C1.01). STABILIZATION MEASURES SHALL BE INITIATED FOR EROSION AND SEDIMENT CONTROL ON DISTURBED AREAS AS SOON AS PRACTICAL, BUT IN NO CASE MORE THAN 7 DAYS, IN PORTIONS OF THE SITE WHERE CONSTRUCTION HAS TEMPORARILY OR PERMANENTLY CEASED. AS SPECIFIED IN SECTION II.B. ABOVE, UPON COMPLETION OF CONSTRUCTION, ALL STORMWATER MANAGEMENT FACILITIES SHALL BE SCRAPED CLEAN OF ACCUMULATED SEDIMENT AFTER THE COMPLETION OF CONSTRUCTION. ALL TURF ESTABLISHMENT SHALL BE PERFORMED MEETING THE REQUIREMENTS OF SECTION 570 OF THE STANDARD SPECIFICATIONS. EVIDENCE OF GROWTH MUST BE PRESENT PRIOR TO FINAL RELEASE.
AS DEPICTED IN THE STORMWATER POLLUTION PREVENTION PLAN (C1.01), A STORMWATER MANAGEMENT SYSTEM WILL BE CONSTRUCTED AND WILL BE COMPRISED OF A DRY DETENTION FACILITY AND A STORM PIPE CONVEYANCE SYSTEM. TO PREVENT EROSION DURING CONSTRUCTION, TYPE III SILT FENCING WILL BE INSTALLED IN THE LOCATIONS SHOWN ON THE PLANS. ALL EXISTING AND PROPOSED STORM DRAINS AND DRAINAGE SWALES SHALL BE PROTECTED ACCORDING TO THE STATE OF FLORIDA EROSION AND SEDIMENT CONTROL DESIGNER AND REVIEWER MANUAL, DATED JULY 2013 OR PER DETAILS PROVIDED ON SHEET C1.01 UNTIL CONSTRUCTION IS COMPLETE. THE STORM PIPE CONVEYANCE SYSTEM SHALL BE FLUSHED OUT TO REMOVE ALL ACCUMULATED DEBRIS AND SEDIMENT UPON
COMPLETION OF CONSTRUCTION.
NOT APPLICABLE, SEE SECTION C, ABOVE.
AFTER CONSTRUCTION, THE STORMWATER MANAGEMENT SYSTEM SHALL BE MAINTAINED IN ACCORDANCE WITH THE SPECIFIED STORMWATER MAINTENANCE NOTES IN THE INCLUDED CONSTRUCTION DRAWINGS AND/OR RESPECTIVE MAINTENANCE REPORTS. SPECIFICALLY, THE PROPOSED SMF(S) SHALL BE MOWED REGULARLY IN THE SPECIFIED AREAS, STORM PIPES AND STRUCTURES WILL BE INSPECTED SEMI-ANNUALLY AND CLEANED ANNUALLY, SMF(S) SIDE SLOPES SHALL BE MAINTAINED TO PREVENT EROSION, AND LANDSCAPING AND GRASS THAT PREVENTS EROSION SHALL BE MAINTAINED. ADDITIONALLY, REMEDIAL ACTIONS SHALL BE TAKEN SHOULD
THE SMF(S) NOT PERFORM AS DESIGNED.
WHEN VEGETATED SWALES ARE UTILIZED, SILT FENCING OR EQUIVALENT SEDIMENT CONTROLS SHALL BE INSTALLED AT ADEQUATE INTERVALS TO COLLECT SEDIMENT ALONG THE SWALE. THE SEDIMENT SHALL BE REMOVED WHEN SEDIMENT REACHES ONE-THIRD OF THE HEIGHT OF THE SILT FENCING. SEE THE STORMWATER POLLUTION PREVENTION PLAN (C1.01) FOR DETAILS AND LOCATIONS, AS REQUIRED.
WHEN DISCHARGE POINTS ARE NOT LOCATED UNDER WATER, RIP RAP PADS HAVE BEEN PROVIDED AT LOCATIONS WHERE NECESSARY DUE TO ANTICIPATED DISCHARGE VELOCITIES. PLEASE SEE THE CONSTRUCTION PLANS FOR DETAILS AND LOCATIONS, AS NEEDED.
THE CONTRACTOR SHALL PROVIDE LITTER COLLECTION CONTAINERS WITHIN THE PROJECT BOUNDARIES DURING CONSTRUCTION. CONTRACTOR SHALL DISPOSE OF ALL UNSUITABLE MATERIALS AND CONSTRUCTION DEBRIS IN ACCORDANCE WITH ALL APPLICABLE LOCAL, STATE, AND FEDERAL REQUIREMENTS.
TO PREVENT OFF-SITE VEHICULAR TRACKING OF SEDIMENTS AND DUST GENERATION, A STABILIZED CONSTRUCTION ENTRANCE SHALL BE ESTABLISHED BY THE SITE CONTRACTOR. PLEASE SEE THE STORMWATER POLLUTION PREVENTION PLAN (C1.01) FOR DETAILS AND LOCATION(S).
THERE ARE EXISTING SANITARY SEWER AND POTABLE WATER SYSTEMS LOCATED ON THE PROJECT SITE. EXTENSION AND UPGRADES ARE PROPOSED. IF TEMPORARY SANITARY SYSTEMS ARE UTILIZED DURING CONSTRUCTION, THE CONTRACTOR SHALL PROPERLY CONTROL AND DISCHARGE ANY SANITARY WASTE IN ACCORDANCE
WITH ALL APPLICABLE LOCAL, STATE, AND FEDERAL REGULATIONS.
THE USE OF FERTILIZERS, HERBICIDES, AND PESTICIDES ON THE PROJECT SITE, WILL BE DIRECTED BY THE LANDSCAPE PLAN AND THE FDOT STANDARD SPECIFICATIONS SECTION 570, TO SUPPORT THE GROWTH OF THE PROPOSED VEGETATION. ESTABLISHING THIS VEGETATION WILL AID IN THE STABILIZATION OF THE PROJECT SITE AND REDUCE EROSION. APPLICATION RATES FOR THE FERTILIZERS, HERBICIDES, AND PESTICIDES SHALL BE IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS TO GUARD AGAINST OVER-USE, WHICH CAN LEAD TO VIOLATIONS OF STATE WATER QUALITY STANDARDS.
IN ACCORDANCE WITH THIS PLAN, THERE ARE NO ANTICIPATED DISCHARGES OF STORMWATER ASSOCIATED WITH CONSTRUCTION ACTIVITIES.
THIS STORMWATER POLLUTION PREVENTION PLAN SHALL BE AMENDED TO REFLECT ANY APPLICABLE CHANGE IN A STATE, REGIONAL, OR LOCAL PERMIT FOR WHICH THE PERMITTEE RECEIVES WRITTEN NOTICE. WHEN WRITTEN NOTICE IS RECEIVED, THE PERMITTEE SHALL PROVIDE A RE-CERTIFICATION OF THIS POLLUTION PREVENTION PLAN, WHICH HAS BEEN REVISED TO ADDRESS SUCH CHANGES. AMENDMENTS TO THE PLAN SHALL BE PREPARED, SIGNED, DATE, AND KEPT AS ATTACHMENTS TO THE
ORIGINAL PLAN.
NO ALTERNATIVE PERMIT REQUIREMENTS ARE REQUESTED.
THE CONTRACTOR IS RESPONSIBLE FOR THE MAINTENANCE, INSPECTION SCHEDULE, AND REPAIRS OUTLINED IN THIS PLAN. MAINTENANCE SHALL CONTINUE THROUGHOUT THE PROJECT UNTIL WORK IS COMPLETE. THE CONTRACTOR IS RESPONSIBLE FOR REMOVING ALL TEMPORARY EROSION AND SEDIMENT CONTROL DEVICES AFTER CONSTRUCTION IS COMPLETE. IN ADDITION TO THE TIMES MENTIONED IN THE PREVIOUS SECTIONS, THE CONTRACTOR SHALL INITIATE ANY REPAIRS WITHIN 24 HOURS OF BEING REPORTED. IN THE EVENT THAT THE SMF(S) DO NOT PERFORM PROPERLY OR IF A SINKHOLE DEVELOPS, THE PROJECT ENGINEER SHALL BE NOTIFIED TO ASSIST IN COORDINATING REMEDIAL ACTION. ACCUMULATED SEDIMENT SHALL BE REMOVED FROM SILT FENCING WHEN IT HAS REACHED ONE-THIRD THE HEIGHT OF THE SILT FENCE. UPON FINAL COMPLETION OF CONSTRUCTION AND ACCEPTANCE BY BOTH THE CITY AND OWNER, THE OPERATION AND MAINTENANCE ENTITY WILL BE
NATIONAL PARKS SERVICE.
THE CONTRACTOR SHALL INSPECT ALL POINTS OF POTENTIAL DISCHARGE FROM THE PROJECT SITE FOR ALL DISTURBED AREAS ON THE CONSTRUCTION SITE AT LEAST ONCE EVERY SEVEN CALENDAR DAYS AND WITHIN 24 HOURS OF THE END OF A STORM THAT IS 0.50 INCHES OR GREATER. FOR POINTS OF DISCHARGE INTO SURFACE WATERS OF THE STATE OR AN MS4, A QUALIFIED INSPECTOR (PROVIDED BY THE OPERATOR) SHALL PERFORM THE REQUIRED INSPECTIONS. THE CONTRACTOR SHALL INSTALL A RAIN GAUGE AT THE SITE TO MONITOR AND DOCUMENT RAINFALL EVENTS 0.50 INCHES OR GREATER. LOCATIONS WHERE THE SITE IS COMPLETELY CONSTRUCTED AND STABILIZED, SUCH INSPECTIONS SHALL BE CONDUCTED AT LEAST ONCE A MONTH. ALL INSPECTIONS SHALL BE RECORDED ON THE CONSTRUCTION INSPECTION FORM. THE CONTRACTOR MAY USE THEIR OWN FORM (MEETING FDEP SWPPP REQUIREMENTS) OR A SAMPLE FORM FROM FDEP. A SAMPLE CONSTRUCTION FORM IS AVAILABLE AT: "HTTPS://FLORIDADEP.GOV/WATER/STORMWATER/DOCUMENTS/CONSTRUCTION-SWPPP". MORE SPECIFICALLY, THE INSPECTION SHALL ENSURE
THE FOLLOWING CATEGORIES.
ALL DISTURBED AREAS AND AREAS USED FOR MATERIAL STORAGE SHALL BE INSPECTED FOR POLLUTANTS ENTERING THE STORMWATER SYSTEM. THE STORMWATER MANAGEMENT SYSTEM AND EROSION AND SEDIMENT CONTROL MEASURES IDENTIFIED IN THE PLAN SHALL BE INSPECTED TO ENSURE THEY ARE OPERATING CORRECTLY. LOCATIONS WHERE VEHICLES ENTER AND EXIT THE SITE SHALL BE INSPECTED FOR EVIDENCE OF OFF-SITE SEDIMENT TRACKING.
BASED ON THE RESULTS OF THE INSPECTION, ALL MAINTENANCE OPERATIONS NEEDED TO ASSURE PROPER COMPLIANCE WITH THIS PLAN SHALL BE DONE IN A TIMELY
MANNER, BUT IN NO CASE LATER THAN 7 DAYS FOLLOWING THE INSPECTION.
ALL INSPECTIONS SHALL BE RECORDED ON THE CONSTRUCTION INSPECTION FORM. THIS FORM IS CREATED TO SUMMARIZE THE SCOPE OF THE INSPECTION, THE NAME(S) AND QUALIFICATION OF THE INSPECTOR(S), THE DATE OF INSPECTION, RAINFALL DATA, OBSERVATIONS, THE ACTIONS TAKEN TO CORRECT INCIDENTS OF NON-COMPLIANCE WITH THE PROVISIONS OF THIS PLAN. IF NO INCIDENTS OF NON-COMPLIANTS ARE OBSERVED, THE REPORT SHALL CONTAIN A CERTIFICATION THAT THE FACILITY IS IN COMPLIANCE WITH THE STORMWATER POLLUTION PREVENTION PLAN AND THE ASSOCIATED PERMIT.
IN ADDITION TO STORMWATER RUNOFF, THIS PLAN APPLIES TO RUNOFF FROM IRRIGATION OPERATIONS AND CONSTRUCTION PRACTICES. THIS PLAN DOES NOT PERTAIN
TO DISCHARGES FROM FIRE FIGHTING ACTIVITIES.
THE CONTRACTORS OR SUB-CONTRACTORS SHALL PHOTOCOPY AND COMPLETE THE FORM ON THIS PAGE. IT SHALL BE PROVIDED TO THE OWNER AND KEPT ON FILE
PURSUANT TO SECTION XV REGARDING PROJECT RECORDS.
THE PERMITTEE SHALL RETAIN COPIES OF STORMWATER POLLUTION PREVENTION PLANS AND ALL REPORTS REQUIRED BY THIS PERMIT, AND RECORDS OF ALL DATA USED TO COMPLETE THE NOTICE OF INTENT TO BE COVERED BY THIS PERMIT, FOR A PERIOD OF AT LEAST THREE YEARS FROM THE DATE THAT THE SITE IS FINALLY STABILIZED.
THE PERMITTEE SHALL RETAIN A COPY OF THE STORMWATER POLLUTION PREVENTION PLAN AND ALL REPORTS, RECORDS, AND DOCUMENTATION REQUIRED BY THIS PERMIT AT THE CONSTRUCTION SITE, OR AN APPROPRIATE ALTERNATIVE LOCATION AS SPECIFIED IN THE NOTICE OF INTENT, FROM THE DATE OF PROJECT INITIATION
TO THE DATE OF FINAL STABILIZATION.
NOTICE OF TERMINATION:
1. WHERE A SITE HAS BEEN FINALLY STABILIZED AND ALL STORMWATER DISCHARGES AUTHORIZED BY THIS PERMIT ARE ELIMINATED, THE PERMITTEE SHALL SUBMIT A NOTICE OF TERMINATION (DEP FORM 62-621.300(6)), SIGNED IN ACCORDANCE WITH PART VII.C OF DEP DOCUMENT NO. 62-621.300(4)(a), WITHIN 14 DAYS OF FINAL
STABILIZATION OF THE SITE TO TERMINATE COVERAGE UNDER THIS PERMIT.
2. ELIMINATION OF STORMWATER DISCHARGES ASSOCIATED WITH CONSTRUCTION ACTIVITY MEANS THAT ALL DISTURBED SOILS AT THE SITE HAVE BEEN FINALLY STABILIZED AND TEMPORARY EROSION AND SEDIMENT CONTROL MEASURES HAVE BEEN REMOVED OR WILL BE REMOVED AT AN APPROPRIATE TIME, OR THAT ALL STORMWATER DISCHARGES ASSOCIATED WITH CONSTRUCTION ACTIVITY FROM THE SITE THAT ARE AUTHORIZED BY THIS GENERIC PERMIT HAVE OTHERWISE BEEN
ELIMINATED.
3. FOR CONSTRUCTION ACTIVITIES WHERE THE OPERATOR CHANGES, THE EXISTING OPERATOR SHALL FILE AN N.O.T. IN ACCORDANCE WITH THIS PART WITHIN 14
DAYS OF RELINQUISHING CONTROL OF THE PROJECT TO A NEW OPERATOR.
THE PERMITTEE SHALL SUBMIT A NOTICE OF TERMINATION TO THE FOLLOWING ADDRESS:
NPDES STORMWATER NOTICES CENTER, MS# 2510
FLORIDA DEPARTMENT OF ENVIRONMENTAL PROTECTION
2600 BLAIR STONE ROAD
TALLAHASSEE, FLORIDA 32399-2400
PROJECTS THAT DISCHARGED STORMWATER ASSOCIATED WITH CONSTRUCTION ACTIVITY TO A MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4) SHALL SUBMIT A
COPY OF THE N.O.T. TO THE OPERATOR OF THE MS4.
INDIVIDUAL'S NAME INDIVIDUAL'S SIGNATURE TITLE
THE CONTRACTOR(S) OR SUB-CONTRACTOR(S) RESPONSIBLE FOR COMPLYING WITH THIS STORMWATER POLLUTION PREVENTION PLAN SHALL SIGN THE CERTIFICATION STATEMENT BELOW. MULTIPLE COPIES OF THIS CERTIFICATION STATEMENT MAY BE NECESSARY DEPENDING ON THE NUMBER OF SUB-CONTRACTORS ASSOCIATED WITH THE PROJECT
Site Name: BIG CYPRESS FIRE STATION Site Location: 33100 TAMIAMI TRAIL E, OCHOPEE, COLLIER County, Florida
AS SPECIFIED IN THE "SEQUENCE OF MAJOR SOIL DISTURBING ACTIVITIES," THE SMF(S) WILL BE CONSTRUCTED PRIOR TO CLEARING AND GRUBBING OUTSIDE OF THE SMF(S) AREAS AND CONSTRUCTION OF THE PERMANENT PAVED AREAS. THE TOTAL CONTRIBUTING DRAINAGE AREA TO THE STORMWATER MANAGEMENT SYSTEM IS APPROXIMATELY 0.90 ACRES AND WILL CONSIST OF APPROXIMATELY 2.40 ACRES OF DISTURBED CONSTRUCTION AREA. THEREFORE, ADDITIONAL SEDIMENT TRAP BASINS MAY BE NECESSARY TO PROVIDE SEDIMENT STORAGE ON-SITE DURING CONSTRUCTION. AS SHOWN ON THE STORMWATER POLLUTION PREVENTION PLAN (C1.01), THE PROPOSED STORMWATER MANAGEMENT SYSTEM WILL PREVENT OFF-SITE EROSION DURING CONSTRUCTION. SILT FENCES OR EQUIVALENT SEDIMENT CONTROLS SHALL BE INSTALLED AT SIDE SLOPE AND DOWN SLOPE BOUNDARIES, INLET LOCATION, OUTLET LOCATIONS, AND OTHER LOCATIONS AS SHOWN ON THE STORMWATER POLLUTION PREVENTION PLAN, AS REQUIRED. BY COMPLETION OF CONSTRUCTION, THE SIDE SLOPES, SWALES, AND ALL DISTURBED AREAS SHALL BE
STABILIZED WITH GRASS AND LANDSCAPING AS SPECIFIED ON THE CONSTRUCTION DRAWINGS.
THE CONSTRUCTION DRAWINGS FOR THE PROJECT WERE APPROVED AND PERMITTED BY THE FOLLOWING AGENCIES:
* SOUTH FLORIDA WATER MANAGEMENT DISTRICT
* FLORIDA DEPARTMENT OF ENVIRONMENTAL PROTECTION
* ARMY CORPS OF ENGINEERS
* NATIONAL PARKS SERVICE
DAYS
FROM_______TO_______
FROM_______TO_______
FROM_______TO_______
FROM_______TO_______
FROM_______TO_______
FROM_______TO_______
FROM_______TO_______
FROM_______TO_______
FROM_______TO_______
FROM_______TO_______
FROM_______TO_______
FROM_______TO_______
THE CONSTRUCTION SITE WILL BE IN FULL COMPLIANCE WITH STATE AND FEDERAL REQUIREMENTS. A PLASTIC MAT, TAR PAPER, OR OTHER IMPERVIOUS MATERIAL
SHALL BE PLACED UNDER AREAS WHERE TOXIC LIQUIDS ARE TO BE OPENED AND STORED.
ALL HAZARDOUS MATERIALS SHALL BE STORED IN A SECURE LOCATION, UNDER COVER, AND IN APPROPRIATE TIGHTLY, SEALED CONTAINERS WHEN NOT IN USE. ALL PRODUCTS SHALL BE STORED IN AND USED FROM THE ORIGINAL CONTAINER WITH THE ORIGINAL PRODUCT LABEL. CONTAINERS MUST BE STORED IN A MANNER TO PROTECT THEM FROM THE ELEMENTS AND INCIDENTAL DAMAGE. THE MINIMUM PRACTICAL QUANTITY OF ALL SUCH MATERIALS SHALL BE KEPT ON THE JOB SITE AND
SCHEDULED FOR DELIVERY AS CLOSE TO TIME OF USE AS PRACTICAL.
ALL PRODUCTS SHALL BE USED IN STRICT COMPLIANCE WITH THE INSTRUCTIONS ON THE PRODUCT LABEL.
SUFFICIENT EQUIPMENT AND/OR MATERIALS SHALL BE KEPT ONSITE TO CONTAIN AND CLEAN UP SPILLS OF HAZARDOUS MATERIALS IN THE AREAS WHERE THESE MATERIALS ARE STORED OR USED. SPILL CONTROL AND CONTAINMENT KIT SUPPLIES SHALL BE OF SUFFICIENT QUANTITIES AND APPROPRIATE CONTENT TO CONTAIN A SPILL FROM THE LARGEST ANTICIPATED PIECE OF EQUIPMENT AND FROM THE LARGEST ANTICIPATED QUANTITIES OF PRODUCTS STORED ON THE SITE AT ANY
GIVEN TIME.
CONTRACTOR TO CONTAIN AND CLEAN UP ANY SPILLS IMMEDIATELY AFTER THEY OCCUR. ANY SPILLS OF PETROLEUM PRODUCTS OR HAZARDOUS MATERIALS IN EXCESS OF REPORTABLE QUANTITIES AS DEFINED BY EPA, STATE, OR LOCAL AGENCY REGULATIONS SHALL BE REPORTED TO THE APPROPRIATE AGENCIES IN THE REQUIRED TIME FRAMES. THE CONTRACTOR SHALL PROVIDE A WRITTEN NOTICE TO THE OWNER IMMEDIATELY UPON IDENTIFICATION OF ANY SPILL.
ALL EXCESS, USED, OR SPILLED PRODUCTS, INCLUDING CONTAMINATED SOIL, SHALL BE DISPOSED OF BY THE CONTRACTOR IN STRICT COMPLIANCE WITH
INSTRUCTIONS ON THE PRODUCT LABEL AND ALL APPLICABLE REGULATIONS.
I CERTIFY UNDER PENALTY OF LAW THAT I UNDERSTAND, AND SHALL COMPLY WITH, THE TERMS AND CONDITIONS OF THE STATE OF FLORIDA GENERIC PERMIT FOR STORMWATER DISCHARGE FROM LARGE AND SMALL CONSTRUCTION ACTIVITIES AND THIS STORMWATER POLLUTION PREVENTION PLAN PREPARED THEREUNDER.
ADDRESS, AND PHONE NUMBER
RESPONSIBLE RESPONSIBLE
DATE
COMPANY NAME,
9 98
X
XX
X
X
X
X
X
X
X X
X
X X
X
X
E T
EH
OF
OF
OF
OF
ST
(FO)
(FO)
(FO) (FO) (FO)
(FO)
(FO)
(FO
(FO
(FO
(FO)
(FO)
(FO)
(FO)
(FO)
(FO)
(F O
(F O
(FM)
(FM)
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
T
G E N
PROPOSED BUILDING
FFE=8.0
PROPOSED SMF #1
45° BENDS
WET TAP
EX. LINE
MATCHLINE X-X
OHW OHW OHW OHW OHW OHW
te
(TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE)
(TE)
(TE) (TE)
(T E)
(T E)
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W) (W) (W) (W)
(W) (W) (W) (W) (W) (W)
MATCHLINE X-X
C O
N S T
R U
C T
IO
N
E N
T R
A N
C E
R E F E R
T O
C
.0
F O
R D
E T
A
IL
N 0 30 6015
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME: MGM
TFC
03/12/2024
DHY SHEETNPS FIRE OPERATIONS CENTER AT
BIG CYPRESS NATIONAL PRESERVE
SUB:
NV5, INC.
WALKER
ARCHITECTS,
GAINESVILLE, FL
GAINESVILLE, FL
C1.01
STORMWATER POLLUTION
PREVENTION PLAN
= TREE BARRICADE LINE
= SILT FENCE LINE
= DOUBLE ROW
SILT FENCE LINE
= CONSTRUCTION ENTRANCE/EXIT
= OUTLET PROTECTION
= INLET PROTECTION
= SOD STABILIZATION
= PERMANENT SEEDING
= TEMPORARY SEEDING
= TREE BARRIER
= SILT BARRIER
INSTALLATION:
REMOVE THE GRATE FROM INLET. IF USING
OPTIONAL OIL ABSORBENTS; PLACE ABSORBENT
PILLOW IN UNIT. STAND THE GRATE ON END.
MOVE THE TOP LIFTING STRAPS OUT OF THE WAY
AND PLACE THE GRATE INTO THE DANDY SACK
SO THAT THE GRATE IS BELOW THE TOP STRAPS
AND ABOVE THE LOWER STRAPS. HOLDING THE
LIFTING DEVICES, INSERT THE GRATE INTO THE
INLET.
MAINTENANCE:
REMOVE ALL ACCUMULATED SEDIMENT AND DEBRIS
FROM VICINITY OF UNIT AFTER EACH STORM EVENT.
AFTER EACH STORM EVENT AND AT REGULAR
INTERVALS, LOOK INTO THE DANDY SACK. IF THE
CONTAINMENT AREA IS MORE THAN 1/3 FULL OF
SEDIMENT, THE UNIT MUST BE EMPTIED. TO EMPTY
UNIT, LIFT THE UNIT OUT OF THE INLET USING THE
LIFTING STRAPS AND REMOVE THE GRATE. IF USING
OPTIONAL OIL ABSORBENTS; REPLACE ABSORBENT
WHEN NEAR SATURATION.
STORM SEWER
GRATE
REINFORCED
CORNERS
MANAGEABLE
2 FOOT
CONTAINMENT AREA
LIFT
STRAPS
OPTIONAL
OVERFLOW
PORTS
DUMPING
STRAPS
STORM
INLET
NTS
TM
TM
TM
NTS
R
BASE OF FRAME
SHAPED & SIZED
TO FIT INLET TOP
TYPICAL INSTALLATION SEQUENCE FOR SILT-SAVER
FRAME AND FILTER
1. EXCAVATE APPROXIMATELY 4" TO 6" BELOW THE
TOP OF THE INLET STRUCTURE.
2. PLACE THE FRAME ONTO THE INLET STRUCTURE,
ENSURING PROPER SEATING OF FRAME TO STRUCTURE.
3. SLIDE THE FILTER OVER THE FRAME.
4. FILL THE FILTER POCKETS WITH SOIL, #57 GRAVEL
OR EQUIVALENT. THE FILTER POCKETS SHOULD BE
COMPLETELY FILLED TO ENSURE A GOOD SEAL
BETWEEN THE GROUND AND INLET STRUCTURE.
5. BACK FILL AROUND THE FRAME AND FILTER
ASSEMBLY IS NOT REQUIRED TO COMPLETE
INSTALLATION; HOWEVER, BACK FILLING MAY BE
NECESSARY TO COMPLETE EXCAVATION
REQUIREMENTS FOR THE SITE.
NECESSARY FOR VEHICLES
LENGTH AS
PIPE
BERM
SEDIMENT BASIN.
6"-8" BLEEDDOWN
WASH WATER TO TEMPORARY
SHALLOW SWALE TO CARRY
WASH PIT
NTS
20' M
IN6" MIN
50'
HARD SURFACE
STANDARD CONSTRUCTION EXIT
STONE SIZE:
ASTM D448 SIZE #1 (1-1/2" TO 3-1/2" DIA)
APPROX 50'X50'X2' DEEP
SEDIMENT BASIN SIZE
CONSTRUCTION EXIT WITH WASH PIT
WASH PIT DETAIL
NOTE:
1. CONSTRUCTION EXIT INSTALLATION SHALL REMOVE MUD/SOILS
FROM TIRES TO PREVENT TRACKING ONTO PUBLIC ROADS.
2. TOP DRESSING WITH 2" STONE MAY BE REQ'D AS DETERMINED BY
THE USE AND FUNCTION OF THE SYSTEM.
3. THE WASH PIT SHOULD BE INSTALLED IF THE STANDARD
CONSTRUCTION EXIT DOES NOT SUFFICIENTLY REMOVE SOILS AND
WASHING IS REQ'D.
NOTES:
1. ANCHOR FILTER FABRIC BY EXTENDING BEYOND RIPRAP AND BACKFILLING
AS SHOWN ON DETAIL.
2. RIPRAP SHALL NOT EXTEND ONTO SIDE SLOPES.
3. ADJUST SHAPE OF APRON WHERE REQUIRED TO MATCH TOE OF SLOPE.
4. BROKEN SLOPE IS NOT ACCEPTABLE.
PIPE
SECTION A-A
PLAN
S E E P
L A
N
SEE PLAN
BASIN
BOTTOM
NTS
2'
2'
MITERED END
SECTION
BASIN
BOTTOM
FILTER FABRIC
4"-12"Ø
BOULDERS
TOP OF
SLOPE
PROPOSED
STOCKPILE/EQUIPMENT
STAGING AREA
NOTE: SOD STABILIZATION REQUIRED FOR ALL UNPAVED
DISTURBED AREAS WITH SLOPES AT OR STEEPER THAN
4:1. ALL OTHER DISTURBED OPEN AREAS SHALL BE
SEEDED. REFER TO SHEET C1.00 FOR FURTHER DETAIL.
10 98
XX
X
X
X
X
X
X
X X
X
X X
X
X
E T
EH
te tete
OF
OF
OF
OF
ST
ST
(FO) (FO) (FO) (FO) (FO)
(FO)
(FO
(FO
(FO)
(TE)
(T E)
(T E)
(T E)
(TE)
(TE)
(TE)
(TE)
(TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE)
(TE)
(TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE)
(T E)
(T E)
(FO)
(FO)
(FO) (FO) (FO)
(FO)
(FO)
(FO
(FO
(FO
(FO)
(FO)
(FO)
(FO)
(F O
(F O
(FM) (FM)
(FM)
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
REMOVE AND RELOCATE
(COORDINATE WITH OWNER
FOR NEW LOCATION)
C O
N S T
R U
C T
IO
N
E N
T R
A N
C E
R E F E R
T O
C .0
F
O R
D E T
A
IL
PROTECT WIND SOCK
DURING CONSTRUCTION
(CONTRACTOR TO
PROTECT DURING
CONSTRUCTION)
N
NOTE:
- CONTRACTOR SHALL HAVE ALL SILT FENCE &
TREE BARRICADES INSTALLED PRIOR TO ANY
SITE WORK.
- CONTRACTORS SHALL REPAIR/RESTORE ANY
DISTURBED AREAS TO EXISTING OR BETTER
CONDITION.
= EX. TREE TO BE
REMOVED
= TREE BARRICADE LINE
= SILT FENCE LINE
= SAWCUT LINE
= EX. LIMEROCK ROAD
TO BE REMOVED
0 30 6015
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME: MGM
TFC
03/12/2024
DHY SHEETNPS FIRE OPERATIONS CENTER AT
BIG CYPRESS NATIONAL PRESERVE
SUB:
NV5, INC.
WALKER
ARCHITECTS,
GAINESVILLE, FL
GAINESVILLE, FL
REMOVE EX. CONCRETE PAD
= DOUBLE ROW
SILT FENCE LINE
EX. FIBER TO BE
PROTECTED DURING
CONSTRUCTION
C1.02
DEMOLITION AND TREE
PROTECTION PLAN
11 98
X X
X
E T
EH
OHW OHW OHW OHW OHW OHW OHW OHW OHW OHW OHW
te te tete te
OF
OF
OF
OF
OF
OF OF
FO
FO FO
W
OHW OHW OHW
SV
SV
SV
OF
O H
W
O H
W
T
G E N
SCALE: 1" = 10' HORIZ.
1" = 2.5' VERT.
SCALE: 1" = 10' HORIZ.
1" = 2.5' VERT.
N
SMF
PROPOSED
FOC BUILDING
FUTURE EOC
0 80 16040
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME: MGM
TFC
03/12/2024
DHY SHEETNPS FIRE OPERATIONS CENTER AT
BIG CYPRESS NATIONAL PRESERVE
SUB:
NV5, INC.
WALKER
ARCHITECTS,
GAINESVILLE, FL
GAINESVILLE, FL
C1.03
MASTER PLANNING PLAN
12 98
X
X
X
X
XX
X
X
X
OF
OF
T
G E N
N 90°00'00" E 397.70'
102.9'
.4
20 SPACES @ 9'=180' 12'
5'
12'
PROPOSED BUILDING
OUTDOOR
EXERCISE
COVERED
AREAFUTURE EOC BUILDING
(NOT INCLUDED IN THE
SCOPE OF THIS PROJECT)
PROPOSED
STORMWATER
MANAGMENT
FACILITY
R5'
R3 5'
R
R 5'
75'-6" FLUSH
CURB PER
DETAIL ON
C0.01
ACCESSIBLE SPACES STRIPED
PER FDOT INDEX 711-001
STRIPING SHOWN FOR
LAYOUT PURPOSES ONLY,
NOT TO BE APPLIED
N: 569511.4352 E: 550834.3952
N: 569511.4352 E: 550731.4993
N: 569411.7543 E: 550931.4997
N: 569411.7543 E: 550533.8152
25.42'
6'6'
29.44'
24'
N: 569294.4564 E: 550832.6201
N: 569397.3007 E: 550912.2116
N: 569397.3007 E: 550842.6201
REFER TO
ARCH. PLANS
FOR PAD
DETAILS
ACCESSIBLE
SIGNS (REFER
TO DETAIL
THIS SHEET)
5'
6'
N: 569496.8709 E: 550893.2981
N: 569512.8709 E: 550893.2981
R1-1 "STOP"
SIGN (36"X36")
N: 569456.7543 E: 550577.1666
N: 569366.7543 E: 550548.7661
DETECTABLE
WARNING STRIP PER
FDOT INDEX 711-001
9.5'
N: 569484.9425 E: 550893.7654
N: 569491.9425 E: 550893.7654
37.33'
HOUSEKEEPING PAD FOR
MECH. UNITS (REFER TO
MEP PLANS FOR DETAILS)
5'
8 SPACES @ 9'=72'
24.44' 5'
N 90°00'00" W 69.59'
R=10.00' L=15.71' Δ=90°00'00"
S
°0
'0
E
.8
R=10.00' L=7.25' Δ=41°33'27"
S 34°25'00" E 41.45'
R=10.00' L=9.52' Δ=54°32'17"
S 88°57'17" E 42.98'
R=10.00' L=15.69'
Δ=89°52'14"
N
°1 '0
E
.6
R=10.00' L=15.91'
Δ=91°10'04"
N
20 40100
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME: MGM
TFC
03/12/2024
DHY SHEETNPS FIRE OPERATIONS CENTER AT
BIG CYPRESS NATIONAL PRESERVE
SUB:
NV5, INC.
WALKER
ARCHITECTS,
GAINESVILLE, FL
GAINESVILLE, FL
7-6.5" RISERS
REFER TO ARCH.
PLANS FOR
RAMP/STAIR/
HANDRAIL DETAILS
12" TYPE 'B' STABILIZATION
98% COMPACTION
AASHTO-T180
CONCRETE SIDEWALK
(REFER TO C0.01 FOR DETAIL)
HEAVY DUTY CONCRETE
(REFER TO C0.01 FOR DETAIL)
4" NO. 57 GRAVEL
(REFER TO C0.01 FOR DETAIL) C1.04
DETAILED HORIZONTAL
CONTROL AND SITE PLAN
REFLECTIVE WHITE
NTS
1.5" SERIES 'C' LETTERS
POST
SIGN NOTES:
1. SIGN CONSTRUCTION, DESIGN AND PLACEMENT SHALL COMPLY
WITH STATE AND LOCAL STATUTES.
FINE = $250 MAX FINE
FINE AMOUNT VARIES FROM
CITY/COUNTY. REFER TO
LOCAL JURISDICTION FOR AMOUNT.
SIGN FTP 22-06
FINISHED GRADE
REFLECTIVE BLUE
REFLECTIVE 1.25"
WHITE LETTERS
REFLECTIVE WHITE
REFLECTIVE WHITE
BLACK BORDER
AND LETTERS
/2
BLACK BORDER12"
$250 MAX FINE
PERMIT
DISABLED
ONLY
PARKING BY
12"
REFLECTIVE BLUE
SIGN FTP-20-06 1
/2
CONTRACTOR SHALL VERIFY.
13 98
X
X
X
X
X
X X
X
OHW OHW OHW OHW OHW OHW OHW OHW OHW OHW OHW OHW OHW OHW OHW OHW OHW OHW OHW OHW OHW te te
(TE)
(TE)
(TE)
(TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE)
(TE)
(TE)
(TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (TE) (T
E)
(T E)
(T E)
(T E)
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W) (W) (W) (W) (W) (W) (W) (W) (W)
(W) (W) (W) (W) (W) (W) (W) (W) (W) (W)
PROPOSED 3" PVC WATER SERVICE
(MIN. 36" COVER)
PROPOSED ELECTRIC (SHOWN
FOR COORD. PURPOSED
ONLY, REFER TO MEP PLANS
FOR DETAILS)
CONNECT TO EX. 3" WATER MAIN
WITH 1-3" WET TAP AND VALVE
AND SAMPLE POINT. CONTRACTOR
TO FIELD VERIFY SIZE OF POTABLE
LINE PRIOR TO CONNECTION.
PROPOSED ELECTRICAL POLE (REFER
TO MEP PLANS FOR DETAILS)
COORDINATE WITH UTILITY
COMPANY FOR ELECTRIC
CROSSING OF ROAD (REFER TO
MEP PLANS FOR DETAILS)
RESTORE DRIVE TO EX.
CONDITIONS OR BETTER
6' CLEAR
MATCHLINE X-X
N: 569966.9312 E: 550875.5014
N: 569850.6627 E: 550875.6139
N: 569678.2031 E: 550897.8540
SCALE: 1" = 20' HORIZ.
1" = 2' VERT.
EX. WATERS
EDGE
2:1 SLOPE
MAX
DRIVE AISLE
SCALE: 1" = 20' HORIZ.
1" = 2' VERT.
(SEE PLAN SHEET C1.06 FOR LOCATION) (SEE PLAN SHEET C1.06 FOR LOCATION)
NOTE: ALL SLOPES 3:1 OR STEEPER SHALL USE STAKED/PEGGED SOD STABILIZATION
4:1
3:1
BASIN BOTTOM
= 1.5'
EX. WATERS EDGE
8:1 SLOPE
MAX
N
20 40100
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME: MGM
TFC
03/12/2024
DHY SHEETNPS FIRE OPERATIONS CENTER AT
BIG CYPRESS NATIONAL PRESERVE
SUB:
NV5, INC.
WALKER
ARCHITECTS,
GAINESVILLE, FL
GAINESVILLE, FL
C1.05
DETAILED GRADING,
DRAINAGE AND UTILITY PLAN
14 98
X
X
X
X X
X
X
X
X
XX
X
X
X
OF
OF
(FO)
(FO
(FO
(FO
(FO
(FO
(FO)
(F O
(F O
(F O
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
(W
T
G E N
7.5% MAX
8.0
7.96 7.96
4.17
4.09 3.59
3.40 3.10 4.14
4.42
3.10
4.99
4.92
7.5
4.58 4.08
3.50
3.45
4.02
3.95 4.0
8.0
7.64
7.75
7.75
8.0
7.25
7.25
7.25
3.60
3.60 3.90
3.96
.4
.3
.4
.2
.4
.2
4.01
.5
.3
.4
3.90
3.493.54
.4
3.95 4.00
4.65
5.76
5.71
4.10 4.15
4.20 5.71
5.66
3.25
3.25
4.24
4.24 3.50
3.47
8.08.0
7.92 7.92 3.0
7.50
8.0
7.89 7.39
7.45
7.50
7.45
3.70
3.80
3.80
3.90
4.38 3.88
3.50
4.45
3.40
3.503.25
1.75
1.75
3.50
3.97
3.0
7.5% MAX
4.03
PROPOSED BUILDING
FFE=8.0
PROPOSED SMF #1
DHW=3.24
(25YR-72HR)
PROPOSED FIBER OPTIC
(REFER TO MEP PLANS FOR DETAILS)
PROPOSED ELECTRIC
FDOT TYPE 'F' INLET WITH
CONCRETE APRON PER
FDOT INDEX 425-053
TOP=3.10
INV=0.00
OUTFALL STRUCTURE
FDOT TYPE 'C' INLET
WITH SKIMMER
(REFER TO DETAIL
THIS SHEET)
M A
C H
L
IN
E A
-A
PROPOSED 2" PVC FORCE MAIN
(MIN. 36" COVER)
PROPOSED 3" PVC
WATER SERVICE
(MIN. 36" COVER)
3"X2" REDUCER
1.5" METER
2" RPZ BFP
3" 45° PVC BEND
PAD MOUNTED
TRANSFORMER
(REFER TO MEP
PLANS FOR
DETAILS)
HP
HP
15" FES PER FDOT
INDEX 430-020
INV=-0.5
STEM WALL (REFER
TO STRUCTURAL
PLANS FOR DETAILS)
CONTRACTOR TO SOD ALL
DISTURBED AREAS
60'-6"
PVC @
1.0%
PROPOSED LIFTSTATION
(REFER TO DETAIL THIS SHEET)
CONTROL PANEL AND ALARM
(REFER TO MEP PLANS FOR
POWER & COMMUNICATIONS)
SS C/O
TOP=6.0
INV=0.40
2'-6" PVC
@ 1.0%
38'-15" RCP @ 1.3%
177'-15" RCP
@ 0.25%
FDOT TYPE 'F' INLET WITH
CONCRETE APRON PER
FDOT INDEX 425-053
TOP=3.10
INV=0.44
GENERATOR PAD (REFER
TO STRUCTURAL PLANS
FOR PAD DETAILS)
3" 45° PVC BEND
REFER TO SECTION
A-A THIS SHEET
14'-12" HDPE
@ 0.7%
12" FES SIMILAR
TO FDOT INDEX
430-020
INV=1.50
2"-22.5°
BEND
2.29ME
2.27ME
2.77ME
2.78ME
2.72ME
2.81ME
2.77ME
MATCHLINE X-X
CONNECT STORM
DOWNSPOUTS TO PROPOSED
STORM HEADER PIPES
STORM C/O W/ PED.
RATED COVER
TOP=7.94
INV=3.24
58'-8" HDPE
@ 1.0% MIN.
43'-12" HDPE
@ 1.15%
STORM C/O
TOP=7.00
INV=3.26
RIP RAP (REFER
TO C1.01 FOR DETAIL)
N: 569520.8268 E: 550668.9280
N: 569517.2222 E: 550855.4187
N: 569559.9491 E: 550898.1456
N: 569382.1013 E: 550847.7498
N: 569411.7559 E: 550822.1748
N: 569411.7543 E: 550625.8822
N: 569275.8431 E: 550855.5575
N: 569266.7031 E: 550842.3340
100'-12" HDPE
@ 2.8%
STORM C/O
TOP=5.75
INV=0.43
N: 569455.9296 E: 550861.5684
P A
D E
L .1
HOUSEKEEPING PAD
FOR MECH UNITS
(REFER TO MEP
PLANS FOR DETAILS)
N: 569456.0665 E: 550828.9925
N: 569455.9826 E: 550728.4993
32'-12" HDPE
@ 1.1%
STORM C/O
TOP=6.75
INV=0.78
STORM C/O
TOP=7.50
INV=2.96
28'-8" HDPE
@ 1.0%SS C/O
TOP=6.0
INV=1.00
IN
V
.8
12" AREA
DRAIN
TOP=2.2
INV=1.0
58'-8"
HDPE
N: 569514.2268 E: 550861.5361
N: 569489.7647 E: 550913.1018
STORM C/O
TOP=5.50
INV=3.50
N: 569504.7861 E: 550728.4993
48'-12" HDPE
@ 0.5%
X
XXX
X X
X
OF
(FO)
(FO)
(FO) (FO) (FO) (FO) (FO)
(FO)
(FO)
(FM)
(FM)
M A
C H
L
IN
E A
-A
OPEN CUT AND REPAIR
EXISTING ROADWAY FOR
CROSSING (MIN. 10')
2"-22.5°
BEND
45° BENDS
WET TAP
EX. LINE N
20 40100
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME: MGM
TFC
03/12/2024
DHY SHEETNPS FIRE OPERATIONS CENTER AT
BIG CYPRESS NATIONAL PRESERVE
SUB:
NV5, INC.
WALKER
ARCHITECTS,
GAINESVILLE, FL
GAINESVILLE, FL
INTEGRAL LIFTING LUGS
2" GREEN VENT
AND CARBON FILTER
CAST-IRON CAULKING HUB
W/ BOOT
FIBERGLASS WETWELL
H-20 LOAD RATED
S.S. HINGES
VENT
2" PVC DISCHARGE
FIBERGLASS VALVE BOX (LOCKABLE)
2" DRAIN LINE
PRIVATE LIFT STATION PLAN VIEW
3 - (2") FIELD
INSTALLED KNOCKOUTS
FOR ELECTRICAL
CONDUITS
2" SCH.80 PVC
SLIDE RAILS 1.5" SCH.40 AISI 304SS PIPE
PUMP DISCHARGE SEALING FLANGE
PRIVATE DUPLEX LIFT STATION SECTION VIEW
2' MIN.
2" PVC DRAIN
("P-TRAP")
INTEGRAL FIBERGLASS SLOPE
2" CAST-IRON FLANGED CHECK VALVE
2" CAST-IRON FLANGED
PLUG VALVE
FIBERGLASS VALVE BOX
(32" x 30" x 25" DEEP)
EMERGENCY PUMP-OUT
w/QUICK CONNECT CPLG.
FIN GRADE
" M
IN
GATE VALVE
EMERGENCY PUMP-OUT
w/ GATE VALVE
2" SS (0-100 PSI) PRESSURE GAUGE
w/ SHUT-OFF VALVE
2" SS (0-80 PSI) PRESSURE GAUGE
w/ SHUT-OFF VALVE
8"18"1
INTEGRAL
FIBERGLASS
SLOPE
SS
LIFTING
CABLE
SS CABLE
BRACKET
-2.76' OFF
300 PSF ALUMINUM COVER w/ (LOCKABLE) HATCH
300 PSF ALUMINUM HATCH (LOCKABLE)
.7
1.5' 1.5'
CONCRETE
ANTI-FLOAT
BALLAST
NOTE: INSTALL PER MANUFACTURE
SPECIFICATIONS
SUBMERSIBLE GRINDER PUMP
5.0 HP, 3500 RPM,
6" IMPELLER
3 PHASE 208V
PUMPS SHALL OPERATE IN
ALTERNATING PUMP OPERATION
-1.13' LEAD
-0.63' LAG
TOP 6.50'
4'
-0.13' HIGH WATER ALARM
2" PVC FM
2" PVC FM
2"X2" CROSS
BOTTOM -4.76'
NTS
NTS
2" CAST-IRON
FLANGED
CHECK VALVE
2" CAST-IRON FLANGED
PLUG VALVE
DESIGN OPERATION POINTS: 31.9 GPM @ 110.9 TDH
(1 PUMP-NORMAL OPERATION)
6"
6"
INTEGRAL
FIBERGLASS
SLOPE
POST MOUNTED CONTROL PANEL, MUST BE COMPATIBLE WITH SUBMERSIBLE
SEWAGE GRINDER PUMP, 5.0 HP, 3500 RPM, 6" IMPELLER, 208V 3 PHASE AND
INCLUDE ALARM BELL, HORN, GENERATOR RECEPTACLE, LIGHTNING PROTECTION,
SURGE PROTECTION, PUMP ELAPSED TIME METERS, EMERGENCY CONTACT PHONE
NUMBER SIGN AND MUST BE LOCKABLE, NEMA 3R ENCLOSURE, AND WORK WITH
DUPLEX SYSTEM.
NOTE: VALVE PIT FLOOR DRAIN VALVE
TO PROVIDE GAS AND WATERTIGHT
SEAL
NTS
FRONT VIEW SIDE VIEW
FIBERGLASS
SKIMMER
TOP EL = 3.50'
STRUCTURE TOP =
3.40'
SKIMMER
BOTTOM
ELEV. = 2.00'
TOP VIEW
FIBERGLASS SKIMMER PER
FDOT DESIGN STANDARD
425-070
3" DISCHARGE ORIFICE
INV. ELEV = 1.75'
S T
M
12" STM
FILL WITH GROUT TO EL = 1.60' BOTTOM OF
STRUCTURE
EL = -0.50'
4-BOLTS
INV. ELEV
= 1.60'
CONTRACTOR TO PROVIDE
MIN. 7" COVER OVER PIPE
0.00' (BOTTOM OF SUMP)
VARIES
SOD SIDE SLOPES, MAINTENANCE PATH,
AND SEED BOTTOM
1.5
3.03.0
1. IF A CONTINUOUS LIMEROCK FORMATION IS ENCOUNTERED IN THE BASIN AREA CONTACT THE ENGINEER OF RECORD. THE LIMEROCK SHALL BE EXCAVATED TO A MINIMUM DEPTH
OF 3 FEET BEYOND THE BASIN UNDERCUT LIMITS.
2. IF A SOLUTION PIPE SINKHOLE DOES FORM IN THE STORMWATER BASIN, THEN THE SINKHOLE SHALL BE REPAIRED BY BACKFILLING WITH MATERIAL OF LOWER-PERMEABILITY MATERIAL, SUCH AS CLAYEY SAND OR CLAY. THE MATERIAL SHALL BE COMPACTED AND THE SINKHOLE REPAIR SHOULD BRING THE SURFACE BACK TO AN ELEVATION WHICH IS
SLIGHTLY ABOVE THE ORIGINAL BOTTOM, CREATING A SMALL MOUND.
4' MAINTENANCE
PATH
4' MAINTENANCE
PATH
1:4 SLOPE
TIE TO EX.
GRADE
EX. GRADE
DHW=3.24
(25YR-72HR)
SHWT EL=0.50
1:4 SLOPE
TIE TO EX.
GRADE
EARTHEN BERM SHALL BE CONSTRUCTED WITH
SOILS WITH A MINIMUM OF 15% SOIL FINES PASSING
NO. 200 SIEVE. COMPACT BERM TO 95% MAXIMUM
DENSITY PER AASHTO METHOD T-99 WITH
MAXIMUM 12" LIFTS. FDOT A-3 SAND (OR ANY
OTHER HIGHLY PERMEABLE MATERIAL) SHALL NOT
BE USED; TYP.
1:8 MAX SLOPE
1:8 MAX SLOPE
STAIRS W/ HANDRAIL
(REFER TO ARCH.
PLANS FOR DETAILS)
SWITCHBACK
RAMPS W/
HANDRAIL (REFER
TO ARCH. PLANS
FOR DETAILS)
.7
12"
BOLTS
3" DISCHARGE
ORIFICE
INV. ELEV = 1.75'
NTS
DEFLECT EX. FIBER AS
NEEDED TO PROVIDE
MIN. 12" SEPARATION
2" PVC FM
(MIN. 36" COVER)
CONTRACTOR TO
CONFIRM EX. FM SIZE
PRIOR TO SHOP
DRAWING SUBMITTAL
C1.06
DETAILED GRADING,
DRAINAGE AND UTILITY PLAN
6" INLET INV = 0.37'
18"
3" CONC. PAD
BELOW ORIFICE
DEFLECT EX. FIBER AS
NEEDED TO PROVIDE
MIN. 12" SEPARATION
REFER TO C1.05
3.5 3.5
RAINFALL DEPTH
PEAK STAGE
ALLOWABLE DISCHARGE^
7.32"
2.82'
0.14 CFS
0.23 CFSPROPOSED DISCHARGE
10 YEAR 24 HOUR STORM* 25 YEAR 72 HOUR STORM
11.30"
3.24'
0.14 CFS
0.27 CFS
100 YEAR 72 HOUR STORM
15"
4.98'
N/A
N/A
* THE MORE CONSERVATIVE DESIGN FREQUENCY OF 10 YEARS WAS USED AS RECOMMENDED BY WATER MANAGEMENT DISTRICT STAFF.
^ COLLIER COUNTY HAS A MAXIMUM DISCHARGE OF 0.15 CFS/ACRE. THE PROPOSED DISCHARGE IS GOVERNED BY THE
MINIMUM 3" ORIFICE TO PREVENT CLOGGING PER SFWMD CODE.
CONTROL ELEVATION
FINISHED FLOOR ELEVATION
N/A
7.00'*
2.82'
3.24'PERIMETER BERM
ALLOWABLE PROPOSED
1.77'
8.00'
3.10'
3.25'
ROAD CROWN
*THE SITE IS LOCATED IN A FEMA FLOOD ZONE AE WITH A BASE FLOOD ELEVATION OF 7.0
12"
(2) BOLTS
15 98
EXTERIOR ELEVATION SHEET NOTES
1. COORDINATE EXTERIOR M/E/P/F EQUIPMENT AND PENETRATIONS WITH
EXTERIOR FINISHES AND ARCHITECTURAL ELEMENTS. COORDINATE
PLACEMENT WITH ARCHITECT FOR ELEMENTS NOT DOCUMENTED ON
EXTERIOR ELEVATIONS.
2. STANDING SEAM METAL ROOFING SHALL BE INSTALLED AS INDICATED ON
EXTERIOR ELEVATIONS AND ROOF PLANS. ALIGN STANDING SEAMS OR
RIBS WITH CENTERLINE OF RIDGE PEAK. EQUALLY SPACE STANDING
SEAMS OR RIBS ALONG LENGTH OF ROOF EDGES WHERE PEAKS ARE
NOT PRESENT. COORDINATE LAYOUT WITH ARCHITECT FOR AREAS NOT
DOCUMENTED. ROOFING MATERIALS NOT COORDINATED WITH
ARCHITECTURAL DOCUMENTS AND/OR ARCHITECT WILL BE SUBJECT TO
REMOVAL AND RE-INSTALLATION AT CONTRACTOR'S EXPENSE.
3. STRUCTURE AND ROOF ADDITION AS AN OPTION.
LEVEL 1
0"
ROOF RIDGE
19'-6"
A B C D E F G
ROOF EAVE
12'-0"
LEVEL -
SIDEWALK
-3'-6"
MP1
MP2
SEE NOTE 3
B A
S E
B
ID
O P
T
IO
N A
1 32
6'-3"
DOWNSPOUT - ROUTE ALONG
WALL AND CONNECT TO CIVIL
LEVEL 1
0"
ROOF RIDGE
19'-6"
ABCDEFG
ROOF EAVE
12'-0"
LEVEL -
SIDEWALK
-3'-6"
B A
S E
B
ID
O P
T
IO
N
INTAKE LOUVER EQUAL OR
SIMILAR TO EME745 60x24
A5.10
LEVEL 1
0"
ROOF RIDGE
19'-6"
13 2
ROOF EAVE
12'-0"
LEVEL -
SIDEWALK
-3'-6"
A5.10
13 2
A5.10
EXHAUST LOUVER
EQUAL OR SIMILAR
TO EME3625 72x14
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
REFERENCE
COVER SHEET
WALKER
ARCHITECTS,
GAINESVILLE, FL
/3
/2
:4
:1
P
M AI
AI
4/29/2024
A2.01TW
EXTERIOR ELEVATIONS
229154
NPS FIRE OPERATIONS CENTER AT
BIG CYPRESS NATIONAL PRESERVE
1/8" = 1'-0"
EXTERIOR ELEVATION - NORTH
1/8" = 1'-0"
EXTERIOR ELEVATION - WEST
1/8" = 1'-0"
EXTERIOR ELEVATION - SOUTH
1/8" = 1'-0"
EXTERIOR ELEVATION - EAST - OPTION
1/8" = 1'-0"
EXTERIOR ELEVATION - EAST - BASE
Lblake Image
Lblake
5,000
FOC 50X100
12,000
POLE BARN
60x200
4,000
EOC 50X80
20,000
OVERFLOW
PARKING
110X145
12,000
FIRE FUTURE
EXPANSION
1,300
WORKOUT
26x50
STACKABLE
SHEDS 12x56
TIRE SHED
12x56
FUELS SHED
12x56
GENERATOR
6X12
10,590
PARKING LOT
60X135
REFERENCE LEGEND
OUTLINE FOR TOTAL AREA OF WORK.
CONTRACTOR HAS TO STAY INSIDE THE
BOUNDARY.
PARKING MATERIAL STAGING AND JOB
TRAILER.
CONSTRUCTION ACCESS WITH FLAGGER
FOR DELIVERIES
PROPERTY LINE
PROJECT - IN SCOPE
PROJECT - FUTURE EXPANSION
NOTE:
1. ALL THE ILLUSTRATIONS SHOWN ON THIS PLAN IS FOR
REFERENCE ONLY, TO SHOW THE PROJECT IN SCOPE.
2. FOR CONSTRUCTION USE CIVIL DRAWINGS.
N
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
REFERENCE
COVER SHEET
WALKER
ARCHITECTS,
GAINESVILLE, FL
/3
/2
:4
:1
P
M AI
AI
4/29/2024
A4.01TW
ENLARGED ARCHITECTURAL
SITE PLAN - PROJECT SITE
229154
NPS FIRE OPERATIONS CENTER AT
BIG CYPRESS NATIONAL PRESERVE
1" = 40'-0"
OUTLINE FOR TOTAL AREA OF WORK
Lblake Image
Lblake
EXTERIOR ENVELOPE NOTES
1. PROVIDE AND INSTALL ALL WEATHER BARRIER SYSTEM COMPONENTS IN
ACCORDANCE WITH WEATHER BARRIER SYSTEM MANUFACTURER'S PUBLISHED
REQUIREMENTS AND INSTRUCTIONS IN ORDER TO ACHIEVE A CONTINUOUS AIR-&-
MOISTURE-TIGHT ENVELOPE AND TO UPHOLD THE MANUFACTURER'S SYSTEM
WARRANTY THROUGHOUT THE PROJECT.
2. COORDINATE ALL WEATHER BARRIER INSTALLATIONS WITH ALL ADJACENT
COMPONENTS AND SYSTEMS. MAKE ALL PROVISIONS REQUIRED BY THE WEATHER
BARRIER SYSTEM MANUFACTURER FOR EACH PENETRATION THROUGH AND JOINT IN
THE MEMBRANE IN ORDER TO MAINTAIN CONTINUITY OF THE AIR AND MOISTURE
BARRIER AND TO UPHOLD THE AIR AND MOISTURE BARRIER SYSTEM'S WARRANTY.
3. MAKE ALL PROVISIONS REQUIRED BY THE CLADDING PANEL AND OPENING INFILL
SYSTEM MANUFACTURER SO AS TO ACHIEVE A MANUFACTURER APPROVED AND
CODE COMPLIANT INSTALLATION THAT RESISTS PROJECT-SPECIFIC WIND LOADS AS
DEFINED BY THE STRUCTURAL CONSTRUCTION DOCUMENTS.
4. FULLY SEPARATE ALL DISSIMILAR METALS BY APPLYING CONTINUOUS MASTIC
COATING OR INSTALLING A 40 MIL SELF-ADHERING SHEET MEMBRANE EQUAL TO
GRACE PERM-A-BARRIER TO THE BASE METAL SURFACE.
5. IF CLIPS USED TO CONNECT COMPONENTS OF DISSIMILAR METALS ARE FABRICATED
OUT OF STAINLESS STEEL SO THAT DISSIMILAR METALS ARE COMPLETELY ISOLATED
FROM EACH OTHER BY THE CLIP, THEN SEPARATION BY MEANS OF MATERIAL
REQUIRED BY THE PREVIOUS SHALL NOT BE REQUIRED WHERE CONTACT IS MADE
WITH THE STAINLESS STEEL CLIP.
6. ALL ANCHORS AND FASTENERS CONNECTING AND/OR IN CONTACT WITH DISSIMILAR
METALS OR MATERIALS DELETERIOUS TO THE ANCHOR'S/FASTENER'S BASE METAL
SHALL BE STAINLESS STEEL, HOT-DIPPED GALVANIZED, OR COATED WITH A
PROTECTIVE MATERIAL THAT SHALL BE IN PLACE FOR THE LIFETIME OF THE
BUILDING.
7. REQUIREMENTS OF AND DIMENSIONS FOR ALL OPENING INFILL SYSTEMS AND
CLADDING MATERIALS SHALL BE FIELD VERIFIED WITH BUILT CONDITIONS TO DATE
PRIOR TO THEIR FABRICATION.
8. THE MINIMUM INSULATING VALUE OF EXTERIOR ASSEMBLIES SHALL BE IN
ACCORDANCE WITH THE BUILDING-WIDE ENERGY MODEL PREPARED BY THE
PROJECT MECHANICAL ENGINEER.
9. THE EXPOSED SURFACE OF ALL PAINTED ALUMINUM SHEET METAL FOR THIS
PROJECT SHALL RECEIVE A FACTORY APPLIED 70% KYNAR 500 COATING OR EQUAL.
THE SAME FINISH OR SIMILAR PROTECTIVE COATING SHALL ALSO BE APPLIED TO THE
CONCEALED SURFACE OF ALL SHEET ALUMINUM TO BE INSTALLED AS PART OF THE
STEEL PANEL ASSEMBLY.
10. ALL CLADDING AND INSULATIONS PROVIDED AND INSTALLED IN EXTERIOR
ASSEMBLIES SHALL HAVE A CLASS "A" FLAME SPREAD & SMOKE DEVELOPMENT
RATING WHEN TESTED PER ASTM E 84.
SECTION AA
CUT PANEL
SID
EW
ALL
ENDWALL
A
FULL PANELS
FULL PANELS
CUT PANEL
CUT PANEL
CUT PANEL
A
NOTE : UNLESS BUILDING PANEL LAYOUT PROHIBITS, THE ENDWALL PANELS WILL EXTEND PAST THE CORNER
STEEL / GIRT LINE BY THE THICKNESS OF THE SIDEWALL PANELS.THIS IS TO ALLOW FOR A FULLY CLOSED
CORNER.
CUT EDGE OF PANEL
APPLY A CONTINUOUS BEAD OF
SPRAY-IN-PLACE INSULATION
OTHER THREE CORNERS
ARE SIMILAR
1) FIELD CUT CORNER PANELS TO CREATE A CLOSED CORNER FOR
RETENTION OF INSULATING PROPERTIES. REFER TO ERECTION
DRAWINGS FOR START PANEL DIMENSIONS. END PANEL CUT
DIMENSIONS ARE DETERMINED IN THE FIELD.
2) APPLY REQ'D CAULK TO SUPPORT MEMBERS AT CORNER.
PLACE CUT EDGE OF FIRST PANEL IN PLACE, PLUMB AND FASTEN
TO SUPPORTS IN ORDER.
3) PLACE THE SECOND PANEL INTO POSITION SO THE BOTTOM
CORNER OF THE SECOND PANEL ENGAGES THE FIRST, THEN PUSH
UNTIL JOINT FULLY ENGAGES. ENSURE 2ND PANEL IS PLUMB.
CONTINUE THIS W/ REMAINING PANELS.
PANEL INSTALLATION GUIDELINE STEPS:
DO NOT SKIP MEMBER OR
ATTACH PANEL AT TOP THEN
BOTTOM. BOWING OF PANELS
MAY OCCUR IF THIS IS DONE.
CUT PANEL DIM.
(-) NEG START DIM (IF REQ'D)
SEE ELEVATION DRAWINGS
SEE DETAIL (GA4020)
ON WALL ELEVATIONS
SL
C U
T P
A N
E L D
IM
F
IN
IS
H
D
IM
SL
CUT EDGE OF PANEL
REFER TO PANEL JOINT CONNECTION AND
CORNER CONNECTION DETAILS FOR
PANEL ATTACHMENT INFORMATION
LEVEL 1
0"
CONCRETE SLAB
STEM WALL ON
FOOTING - SEE
STRUCTURAL
VAPOR RETARDER
RESILIENT FLOOR
WALL PANEL
DOWNSPOUT
DOWNSPOUT "S"
MATERIAL TO CONNECT
DOWNSPOUT "S" TO
DRAIN NOT BY MBS.
THIS IS SHOWN FOR
REFERENCE ONLY.
ACTUAL FIELD
CONDITION MAY VARY.
A5.07
RESILIENT BASE
5/8" GWB W/
INSULATION
C- CHANNEL
ATTACHED TO
FLOOR
2"
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
REFERENCE
COVER SHEET
WALKER
ARCHITECTS,
GAINESVILLE, FL
/3
/2
:4
:1
P
M AI
AI
4/29/2024
A5.09Checker
EXTERIOR DETAILS
229154
NPS FIRE OPERATIONS CENTER AT
BIG CYPRESS NATIONAL PRESERVE
3" = 1'-0"
WALL CORNER LAYOUT
1 1/2" = 1'-0"
WALL BASE AND FOUNDATION
Lblake Image
Lblake
L
IM
E R
O C
K D
R
IV
E
L
IM
E R
O C
K D
R
IV
E
L
IM
E R
O C
K D
R
IV
E
OHE OHE OHE OHE OHE
U E
U E
UE
UT
UT
TRANSFORMER
GENERATOR
1NPS FIRE
OPERATIONS
CENTER
GROUNDING
TRIAD
5 6
4 7
XBXB XBXB34e(E2)34e(E2) 34e(E2)34e(E2)
34(E2)34(E2)
PUMP-LS
ECB-PUMP-LS
11,13,15(E1)
U E
NEW PROPOSED UTILITY POLE
TWO 4"
CONDUITS 8
NEW PROPOSED UTILITY POLE
O H E
XBXB 34e(E2)34e(E2) XBXB 34e(E2)34e(E2)
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
WALKER
ARCHITECTS,
GAINESVILLE, FL
/2
/2
:3
:5
A
M
ZAJ
ZAJ
4/29/2024
E0.03JLW
ELECTRICAL SITE PLAN
NPS FIRE OPERATIONS CENTER AT
BIG CYPRESS NATIONAL PRESERVE
SCALE A
E0.03
1…