This document provides details for a federal contract solicitation to rehabilitate exterior systems of the Main Immigration Building of the Statue of Liberty National Monument and Ellis Island in New York. The solicitation number is 140P2022R0036 issued by the National Park Service, National Office within the Department of the Interior. Services required include rehabilitating exterior systems such as replacing deteriorated terra cotta, repairing steel structural components, and performing waterproofing. The contractor will be selected through a competitive proposal process with proposals due by June 1, 2022 and work expected to be completed by September 2023.
View the file
Other files
Show all 39
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REFER TO PACKAGE 312431 FOR SITE
ACCESS & PRELIMINARY CONTRACTOR
STAGING AREA
REFER TO PACKAGE 312431 FOR MASONRY, STRUCTURAL, & ROOF SCOPE AT CLERESTORY
REFER TO PACKAGE 312431 FOR MASONRY, STRUCTURAL, & ROOF SCOPE AT CLERESTORY
GENERAL NOTES
11. SEE ARCHITECT DRAWINGS FOR ALL MOUNTING
DETAILS AND CORRESPONDING SPECIFICATIONS.
LIGHTING FIXTURE MANUFACTURER TO APPROVE
MOUNTING DETAILS PRIOR TO FINAL ORDER.
2. CONTRACTOR SHALL VERIFY THAT ALL LIGHTING
EQUIPMENT SPECIFIED - IN ITS APPLICATION ON
THIS PROJECT - COMPLIES WITH ALL APPLICABLE
NATIONAL AND LOCAL CODES, ORDINANCES,
REGULATIONS AND JURISDICTIONS PRIOR TO
ORDERING ANY EQUIPMENT.
3. DO NOT SCALE ELECTRICAL DRAWING FOR
EXACT LOCATION OF THE LIGHTING FIXTURES. IN
GENERAL, THE EXHIBIT LIGHTING LAYOUT INDICATE
THE PROPER LOCATION OF LIGHTING FIXTURES.
4. WRITTEN DIMENSIONS ON DRAWINGS SHALL
HAVE AUTHORITY OVER SCALED MEASUREMENTS.
CONTRACTORS AND MANUFACTURERS SHALL
VERIFY AND BE RESPONSIBLE FOR ALL DIMENSIONS
AND CONDITIONS ON THE JOB AND INFORM THE
CONTRACTING OFFICER OF ALL VARIATIONS FROM
DRAWINGS PRIOR TO PERFORMING THE WORK.
5. FOR ALL REMOTE LOCATION DIMMERS, THE
ELECTRICAL CONTRACTOR SHALL PROVIDE SEPARATE
NEUTRALS FOR EACH DIMMING CIRCUIT (I.E., NO
COMMON NEUTRALS).
6. A LINE ITEM PRICE FOR THE COST TO
PROVIDE AND INSTALL EACH LIGHTING FIXTURE TYPE
IS REQUIRED.
THESE DRAWINGS AND ALL THE IDEAS,
ARRANGEMENTS, DESIGNS & PLANS INDICATED
THEREON OR REPRESENTED THEREBY ARE OWNED BY
AND REMAIN THE PROPERTY OF AVAILABLE LIGHT AND
HAVE BEEN CREATED AND DEVELOPED FOR USE ON
AND IN CONNECTION WITH THE SPECIFIED PROJECT.
NEITHER THIS DRAWING, NOR ANY SUCH IDEAS,
ARRANGEMENTS, DESIGNS OR PLANS SHALL BE
APPROPRIATED BY OR DISCLOSED TO ANY PERSON,
FIRM OR CORPORATION FOR ANY USE OR PURPOSE
WHATSOEVER, EXCEPT BY THE SPECIFIC AND
WRITTEN PERMISSION OF AVAILABLE LIGHT.
THESE DRAWINGS REPRESENT VISUAL CONCEPTS AND
SUGGESTIONS ONLY. PLEASE RIGIDLY OBSERVE ALL
LOCAL ELECTRICAL, STRUCTURAL AND SAFETY
PROCEDURES AND CODES. AVAILABLE LIGHT IS
UNQUALIFIED TO DETERMINE STRUCTURAL, ELECTRICAL
OR SAFETY APPROPRIATENESS AND WILL NOT ASSUME
RESPONSIBILITY OR LIABILITY FOR IMPROPER
ENGINEERING, CONSTRUCTION OR HANDLING OF
THESE DESIGN CONCEPTS.
REFERENCE NOTES (SPECIFIC TO THIS PAGE ONLY)
22" WIDE SURFACE-MOUNTED LINEAR LED
COVE FIXTURE MOUNTED IN ARCHITECTURAL
TROUGH WITH 25º BEAM SPREAD TO
UPLIGHT WINDOWS AND CEILING. SEE 2/L1.0
FOR MOUNTING DETAIL AT EAST-WEST
WINDOWS AND 3/L1.0 FOR MOUNTING DETAIL
AT NORTH-SOUTH WINDOWS. (TYPE LSA)
TYPICAL.
ELLIS ISLAND MAIN IMMIGRATION BUILDING
STATUE OF LIBERTY NATIONAL MONUMENT
BID OPTION 03
LIGHTING LAYOUT
CONSTRUCTION
DOCUMENTS
NOT FOR
CONSTRUCTION
JGWA
DESIGNED:
TECH. REVIEW:
DATE:
04/23/21
AVAILABLE LIGHT
YIC
RAG
SUB SHEET NO.
L1.0
TITLE OF SHEET
166781
305028
14 20
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
ELLIS ISLAND MAIN IMMIGRATION BUILDING
STATUE OF LIBERTY NATIONAL MONUMENT
SCALE OF INCHES
SSCALE J
FFIXTURE BEAM SPREAD AND FOCUS SKETCH55
L1.0
225º
TTYPE LSA AIMED UP TO REVEAL
ARCHITECTURAL DETAILS
225º
NO SCALE
LLSALSA
LLSA LSA LSA
LSA LSA LSA
CCLESTORY PLAN • LIGHTING LAYOUT11
L1.0
118'-0" 118'-0" 118'-0"
118'-0"118'-0"118'-0"
LL1.0
LL1.0
SSCALE B
EEAST-WEST TROUGH TYPE LSA MOUNTING DETAIL22
L1.0
BBLOCKING TO RAISE
FIXTURE MOUNTING HEIGHT
AALL DIMESIONS TO BE
VERIFIED IN THE FIELD
PRIOR TO PROCEEDING
WITH INSTALLATION.
EEXISTING HOLLOW
CHANNEL FOR CONDUIT
TTROV INTERIOR 25º AIMED
UP TO REVEAL
ARCHITECURAL DETAILS.
(TYPE LSA)
44"
55 1/2"
225°
33"
MMOUNTINIG HINGE
SSCALE J
NNORTH-SOUTH TROUGH TYPE LSA MOUNTING DETAIL33
L1.0
TTROV INTERIOR 25º AIMED
UP TO REVEAL
ARCHITECURAL DETAILS.
(TYPE LSA)
BBLOCKING TO RAISE
FIXTURE MOUNTING HEIGHT
AALL DIMESIONS TO BE
VERIFIED IN THE FIELD
PRIOR TO PROCEEDING
WITH INSTALLATION.
225°
55"
66"
22" MMOUNTINIG HINGE
SSCALE J
88 0 8 16
SCALE OF FEET
SSCALE B
BID OPTION 03
LIGHTING CONTROL RISER
CONSTRUCTION
DOCUMENTS
NOT FOR
CONSTRUCTION
JGWA
DESIGNED:
TECH. REVIEW:
DATE:
YIC
RAG
04/23/21
SUB SHEET NO.
L1.1
ELLIS ISLAND MAIN IMMIGRATION BUILDING
STATUE OF LIBERTY NATIONAL MONUMENT
TITLE OF SHEET
166781
305028
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
356AVAILABLE LIGHT
15 20
PPOWER
SUPPLY EELV DIMMER
NNORTH WINDOWS
LSA
EEAST WINDOWS
LSA
SSOUTH WINDOWS
LSA
WWEST WINDOWS
LSA
EELV DIMMER
EELV DIMMER
EELV DIMMER
PP1 PP1
PP1
PP1
EEC EEC
EEC
EEC
PP1
PP1
PP1
CONTROL 1CONTROL 2 CONTROL 3 CONTROL 4
TIMECLOCKKEYPAD
PRESETS
ZONE 1
ZONE 2
ZONE 3
ZONE 4
EEC
EEC
PP1
KKEY
NOTES:
SEE LIGHT FIXTURE SCHEDULE FOR COMPLETE
FIXTURE AND CONTROL EQUIPMENT PART
NUMBERS AND DESCRIPTIONS.
SEE LIGHTING LAYOUT DRAWING FOR FIXTURE
LENGTHS, PLACEMENT AND ZONING.
LINE VOLTAGE 120V
ETC CONNNECT WIRING
PP1
EEC
EEXACT LOCATION TBD
PP1
CONTROL 1
CONTROL 1
CONTROL 1
LLIGHTING CONTROL RISER11
L1.1
NO SCALE
ELLIS ISLAND WINDOWS LIGHTING CONTROL NARRATIVE
LIGHTING FIXTURES TO BE CONTROL VIA STANDALONE CONTROL
SYSTEM WITH SYSTEM CONTROL PER LIGHTING DRAWINGS.
SYSTEM TO ALLOW FOR FIXTURES TO TURN ON AND OFF AT
PREDETERMINED TIMES BASED ON TIME OF DAY.
PRESET KEYPAD TO ALLOW FOR MANUAL ON/OFF, DIMMING AND
OVERRIDES OF PRESETS.
PRESETS SCENES TO BE PROGRAMMED* TO INCLUDE:
1. DAYTIME
2. NIGHTIME
3. ALL ON
4. ALL OFF
*EXACT LIGHT LEVELS TBD IN FIELD WITH CONTRACTING
OFFICER.
FIXTURES TO TURN ON AUTOMATICALLY IN THE MORNING AND
INCORPORATE A LIGHTS OUT SWEEP AT END OF DAY.
SYSTEM SHALL CONTROL LIGHTING FIXTURES VIA ELV DIMMING
PROTOCOL PER THE LIGHTING FIXTURE SCHEDULE, RISER AND
SEQUENCE OF OPERATIONS ZONE SCHEDULE.
SYSTEM DOES NOT ALLOW FIXTURES TO BE CONTROLLED AS
PART OF EMERGENCY LIGHTING SYSTEM.
Fixture Type Purpose
Ellis Island Windows Lighting Zone Schedule by Area 100% Construction Documents
Channel Quantity Watts Each Load NotesLoad Type
• A local standalone control system will allow window lighting fixtures with local and manual overides for each zone.
• Preset Levels to be determined onsite with Contracting Officer.
Control System Notes
Windows
• See Zone Schedule Below.
Notes
Auto On via Timeclock with manual override via button station control.
Manual raise and lower via Button Station Auto Off via timeclock with manual off via button station control.
TimeclockAuto On via Timeclock with manual override via button station control.
ON
Manual raise and lower via Button Station
ADJUST
Auto Off via timeclock with manual off via button station control.
OFF
Timeclock
SENSORS, INTERFACES
1: North Windows
1 Window UplightLSA-1 12 726ELV
1 Window UplightLSA-4 48 57612ELV
2: East Windows
2 Window UplightLSA-4 48 2886ELV
2 Window UplightLSA-1 12 121ELV
3: South Windows
3 Window UplightLSA-4 48 57612ELV
3 Window UplightLSA-1 12 726ELV
4: West Windows
4 Window UplightLSA-1 12 121ELV
4 Window UplightLSA-4 48 2886ELV
1,896 WWatts Total
1. Dimming is to be ELV.
2. Occupied, unoccupied and late-night hours to be determined by Contacting Officer.
BID OPTION 03
LIGHTING FIXTURE SCHEDULE
CONSTRUCTION
DOCUMENTS
NOT FOR
CONSTRUCTION
JGWA
DESIGNED:
TECH. REVIEW:
DATE:
YIC
RAG
04/23/21
SUB SHEET NO.
L1.2
ELLIS ISLAND MAIN IMMIGRATION BUILDING
STATUE OF LIBERTY NATIONAL MONUMENT
TITLE OF SHEET
166781
305028
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
356AVAILABLE LIGHT
16 20
Ellis Island Windows 100% Construction DocumentsFixture Schedule
Type Scope/Notes/LocationManufacturer Description Lamp/Details
LSA-1
Location: Window Troffs
Notes: 4, 5, 6, 7, 13, 15
Provide all necessary parts and pieces for a complete and working system.
EcoSense L50-I-12-12-30-80-MULT-25x25
Provide with:
- CBL-3P-UNV-TBD (Leader Jumper Cable)
1-5/8” Wide by 2-1/4” tall by 12” long surface-mounted linear LED cove fixture with beamspread optics, adjustable lockable aiming, and plug ‘n play connectors.
Provide fixture with leader/jumper cables as needed per fixture lengths and layouts.
12 W per fixture
Volts: 120~277V Color Temp: 3000K
CRI: 80+
Beam Spread: 25° Lumens: 923 per fixture Dim: ELV Mount: Surface Finish: Standard Rating: Interior
LSA-4
Location: Window Troffs
Notes: 4, 5, 6, 7, 13, 15
Provide all necessary parts and pieces for a complete and working system.
EcoSense L50-I-48-12-30-80-MULT-25x25
Provide with:
- CBL-3P-UNV-TBD (Leader Jumper Cable)
1-5/8” Wide by 2-1/4” tall by 48” long surface-mounted linear LED cove fixture with beamspread optics, adjustable lockable aiming, and plug ‘n play connectors.
Provide fixture with leader/jumper cables as needed per fixture lengths and layouts.
48 W per fixture
Volts: 120~277V Color Temp: 3000K
CRI: 80+
Beam Spread: 25° Lumens: 3692 per fixture Dim: ELV Mount: Surface Finish: Standard Rating: Interior
Control 1
Location: Exact location to be coordinated with GC
Notes: 6, 13ETC
ELVD-G2-TBD
Provide with:
- E4VB (4" installation box with low-voltage barrier)
Phase-Adaptive dimmer with forward or reverse phase dimming for loads up to 600 watts.
Volts: Per EE Dim: ELV
Control 2
Location: Exact location to be coordinated with GC
Notes: 1, 13ETC
E1006-TBD
Provide with:
- EACC-5 EchoAccess Interface, White
Six button station keypad with (4) Presets and On/ Off buttons. Keypad to have rear illuminated LEDs to indicate system status.
Control 3
Location: Exact location to be coordinated with GC
Notes: 1, 13ETC
E-ATC-TBD
Provide with:
- E-2-TBD (Two-gang Locking Cover)
Timeclock station with astronomical timeclock with +/- sunset and sunrise settings and programmable latitude/longitude, 24 hour real time clock with user configurable daylight saving time, four recurrence setting and 50 field programmable events.
Control 4
Location: Exact location to be coordinated with GC
Notes: 6, 13ETC
E-SPS-DIN KIT
Provide with:
- DIN8 Enclosure
Station power module for use with Echoconnect enabled station responsive controls or power controllers and din rail mount enclosure.
General Notes
Contractor shall supply and install a complete, fully functioning lighting system, including but not limited to: mounting hardware and accessories;
appropriately sized transformers; power supplies; drivers; lamps; optical accessories; and electrical appurtenances.
A
Contractor shall be responsible for final fixture counts of all lighting fixtures and accessories, as well as linear fixture run lengths, as shown on Architect's drawings.
B
Contractor shall be responsible for verifying mounting conditions with mounting locations to ensure compatibility. Contractor shall notify Contacting Officer of any conflicts with all trades prior to the ordering of the equipment. For fixtures where more than one manufacturer is specified, mounting requirements may vary.
C
Contractor shall verify compliance of all lighting equipment specified in its intended application on this project with all applicable national and local codes, ordinances, regulations and jurisdictions prior to ordering any equipment.
D
Contractor shall supply "Contractor net" unit pricing for each lighting product specified. Unit price shall be for equipment only and shall not include installation or other costs. The unit price supplied shall be guaranteed for the project and valid for additions and deletions of product throughout the duration of the project.
E
All drawings represent visual concepts and suggestions only. Available Light is not qualified to determine structural or electrical suitability and will not assume liability for improper engineering, construction or handling of design concepts.
F
The accompanying drawings and all the ideas, arrangements, designs, and plans indicated thereon or represented thereby are owned by and remain the property of Available Light and have been created and developed for use on and in connection with the specified project. Neither this drawing, nor any such ideas, arrangements, designs, or plans shall be appropriated by or disclosed to any person, firm, or corporation for any use or purpose whatsoever, except by the specific and written permission of Available Light.
G
Written dimensions on drawings shall have authority over scaled measurements. Contractor shall field verify all dimensions on the job and inform the Contacting Officer of any proposed variations from drawings prior to performing the work.
H
Do not scale electrical drawings for exact location of the lighting fixtures. Refer to Architect drawings and other lighting layouts for proper locations of lighting fixtures.
I
Contractor shall not substitute products unless approved in writing by Contacting Officer. Lighting fixture, ballast, driver, power supply, lamp, and/or accessory substitutions shall be formally presented to Contacting Officer no later than fourteen (14) working days prior to bid due date.
All proposed substitute fixtures must:
1) Be proven to meet or exceed the standards of quality, design, appearance, and performance as established by the lighting fixture specified by Available Light. See next note for list of items to be submitted for all substitutions.
Contractor shall coordinate changes due to use of approved substitutes with all trades.
J
For a fixture type where a manufacturer is named as equal, the equal shall meet aesthetic criteria of the specified fixture, including but not limited to:
dimensional criteria, finishes, including custom finishes; mounting details; and specified modifications.
Additionally, for a fixture type where a manufacturer is named as equal, the equal shall meet the minimum performance requirements as defined by specified product, including but not limited to: regulatory listings; output as measured in delivered lumens; center beam candle power (CBCP);
baseline efficacies as measured in lumens delivered per watt; cut-off angle as measured from nadir; LED binning; color rendering (CRI); color temperature (CCT); Duv per Manufacturers supporting documentation; dimming and method; five (5) year minimum warranty including LED engine and driver; L70 lumen maintenance tested according to IES LM79; and specified modifications.
K
Contractor shall provide the following items to the Contacting Officer for evaluation of proposed substitutions:
1) A current manufacturer's data sheet with luminaire catalog numbers.
2) A complete and working sample wired with cord and plug for 120V operation furnished upon request.
3) A complete photometric report for the proposed substitute fixture using the same lamp type, wattage, and distribution as per the specification. The photometric report should include TM-30 or CRI documentation with R 1-14 values, tabulated candlepower values, a coefficient of utilization table, and an ISO foot-candle diagram from an independent testing laboratory. The photometric report must reflect the fixture specified without modification to the file.
4) The specified product defines minimum performance requirements as defined by specified product including but not limited to: regulatory listings;
output as measured in delivered lumens; center beam candle power (CBCP); baseline efficacies as measured in lumens delivered per watt; cut-off angle as measured from nadir; LED binning; color rendering (CRI); color temperature (CCT); Duv per Manufacturers supporting documentation;
dimming and method; five (5) year minimum warranty including LED engine and driver; and L70 lumen maintenance tested according to IES LM79.
L
Contractor shall provide the following items to the Contacting Officer for evaluation of specified fixtures:
1) Manufacturer’s product data sheets for each luminaire indicating luminaire type, dimensions, driver/ballast/power supply/transformer quantity and type, lamp quantity and type, photometric data (including lumnen output, CRI & TM-30 data), materials, finishes, accessories, voltage, input wattage, CFM data, and photographic image of luminaire.
2) Manufacturer’s data sheet for each driver/ballast/power supply/transformer including driver/ballast/power supply/transformer type, power factor, input voltage, input watts, and ballast factor.
3) Scaled and dimensioned detail plan and elevation drawings of custom and continuous row type luminaires including joints, mounting points and type, power connection locations(s), and emergency or separate switching configurations.
4) For custom luminaires, manufacturer shall perform and submit all engineering calculations as required to ensure the safe and proper installation and operation of the luminaire.
5) Dimming Power Supply Compatibility Certificates: Signed by driver/ballast/power supply manufacturer certifying that driver/ballast/power supply is compatible with dimming systems and equipment with which they are used.
6) All submittals shall have project name and luminaire type clearly shown.
M
Project Specific Notes
Final finish of fixture shall be approved in writing by Contacting Officer.1
Not used2
Not used3
Fixture shall be aimed and focused by Contractor under the direction of the Contacting Officer.4
The Contractor shall provide all ladders and mechanical lifts (i.e scissors lifts, articulating boom arm lifts, etc.) for the exclusive use of the aim and focus effort. The number and type of lifts and/or ladders to be pre-approved by the Contacting Officer. Crew shall arrive at aim and focus equipped with appropriate aim and focus tools including wrenches, gloves, electrical testers, etc., as per industry standards for a theatrical lighting technician.
All costs associated with aiming and focusing shall be included in the bid, including but not limited to travel expenses, parking, storage, etc.
Junction boxes and/or conduit that is used to wire fixtures and that is open to view shall be painted to match adjacent structure.6
Fixture or track shall be mounted to structure in a manner recommended by the manufacturer without compromising the integrity of the structure.
Contractor shall be responsible for all materials required to insure a safe and proper pendant installation. Contractor to coordinate changes in size of fixtures or track due to use of approved substitutes with all trades. Tracks shall be mounted to prevent twisting when fixtures are aimed and focused causing an asymmetrical load.
All luminaires shall be installed in the proper positions as indicated in the construction documents. Accessories (spread lenses, color filters, screens, gobos, top hats, snoots, etc.) shall be installed under the supervision of Contacting Officer during the aim and focus period.
Remote transformers, power supplies, or drivers shall be located in nearby accessible, concealed-from-view location with manufacturer recommended ventilation available. As per manufacturer's recommendations, Contractor shall not exceed the maximum allowable distance between any luminaire and its associated remote control devices. Contractor shall supply manufacturer's transformer, power supply or driver of proper capacity.
Not used10
Not used11
Not used12
Fixture shall be furnished and installed by Contractor. Contractor shall be responsible for final electrical termination.13
Not used14
Due to rapid advances in LED technology, Contacting Officer reserves the right to change lamp or LED module specifications at the time of submittal to another lamp or LED module of equal or lesser cost.
Electronic devices that generate radio frequency energy must not interfere with other electronic devices and must not be susceptible to interference from other devices. Equipment shall not be an Electromagnetic (EM) polluter or be effected by EM pollution. All relevant equipment shall comply with current EMC standards.
N
Unless otherwise specified all downlights (recessed, wallwasher, and adjustable) shall be supplied by the same manufacturer, and all linear fixtures (recessed, pendant, and surface mounted) shall be supplied by the same manufacturer.
O
Unless otherwise specified, all retrofit LED lamps shall be manufactured by LEDvance (Osram-Sylvania), Philips, GE, Soraa, or Green Creative. All lamps of a given type shall be supplied by the same manufacturer.
P
Unless otherwise specified, all LED drivers shall be manufactured by one of the following: Advance (Philips), LEDvance (Osram Sylavnia), Hatch, EldoLED, or Lutron.
Q
All fixtures shall be supplied with specified lamp(s). Contractor shall provide an additional 10% replacement lamps (minimum two of each lamp type specified). For fixtures that use replaceable LED modules and drivers rather than lamps, Contractor shall provide an additional 5% (minimum one) of each driver and module type.
R
Fixture construction and installation shall ensure no light leaks between ceiling trims of recessed lighting equipment and the ceiling plane. For applications in perforated or partially transparent ceilings, fixture construction shall also ensure no light leaks above the ceiling line.
S
Reflectors, reflector cones, and visible trim of all lighting fixtures shall not be installed until completion of plastering, ceiling tile work, painting, and general cleanup. Reflectors, reflector cones, and visible trim shall be carefully handled to avoid scratching or fingerprinting.
T
At the time of acceptance by the Contacting Officer, all lighting fixtures shall have been thoroughly cleaned with materials and methods recommended by the manufacturers, all broken parts shall have been replaced, and all lamps and/or LED modules shall be operative.
U
Fixtures may produce light past their rated life, however, lamps/ballasts/drivers/components must be replaced at or before rated end-of-life for the luminaire to meet minimum photometric performance standards. Neither the Architect nor Available Light shall be held responsible or liable for improper service and maintenance of lighting systems.
V
Not usedW
Contractor shall supply all low-voltage control data lines and wiring in order to properly network and dim fixtures together per control intent documentation and manufacturer’s documentation. Data runs must be properly terminated.
X
| A-SHEETS |
| Sheets and Views |
| T1.0-COVER SHEET-Layout1 |
| map |
| T1.1-GENERAL NOTES-Layout1 |
| map |
| C1.0-SITE PLAN-Layout1 |
| map |
| A1.0-CLERESTORY PLAN-Layout1 |
| map |
| A2.0-EXT ELEVATIONS-Layout1 |
| map |
| A2.1-EXT ELEVATIONS-Layout1 |
| map |
| A3.0-SECTION-Layout1 |
| map |
| A4.0-WINDOW DETAILS-Layout1 |
| map |
| A4.1-WINDOW DETAILS-Layout1 |
| map |
| A4.2-WINDOW DETAILS-Layout1 |
| map |
| A4.3-WINDOW DETAILS-Layout1 |
| map |
| A4.4-WINDOW DETAILS-Layout1 |
| map |
| A4.5-WINDOW DETAILS-Layout1 |
| map |
| L-SHEETS-flattened |
| STLI Windows H-Sheets |
| Sheets and Views |
| H1.0 ACM KEY PLAN-H1.0 |
| map |
| H2.1 LBP DETAILS-H2.1 |
| map |
| H1.1 LBP KEY PLAN-H1.1 |
| map |
| H2.0 ACM DETAILS-H2.0 |
| map |